05000272/LER-1982-075, Forwards LER 82-075/03L-0.Detailed Event Analysis Encl

From kanterella
(Redirected from ML20065S908)
Jump to navigation Jump to search
Forwards LER 82-075/03L-0.Detailed Event Analysis Encl
ML20065S908
Person / Time
Site: Salem PSEG icon.png
Issue date: 10/14/1982
From: Midura H
Public Service Enterprise Group
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20065S910 List:
References
NUDOCS 8211020086
Download: ML20065S908 (3)


LER-1982-075, Forwards LER 82-075/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
2721982075R00 - NRC Website

text

_

D PSEG Public Service Electric and Gas Company P.O. Box E Hancocks Bridge, New Jersey 08038 Salem Generating Station 1

October 14, 1982 Mr.

R.

C. Haynes Regional Administrator USNRC Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Haynes:

LICENSE NO. DP R-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 82-075/03L Pursuant to the requirements of Salem Generating Station Unit No. 1, Technical Specifications, Section 6.9.1.9.b, we are submitting Licensee Event Report for Reportable Occurrence 82-075/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, ll, '

bu^J H.

J. Midura I

Gencral Manager -

Salem Operations fab [

RF:ks CC:

Distribution l

l 821102OOB6 M h 2 1

PDR ADOCK PDR I

S 1

l The Energy People pd

> ? ! p) 6 2".4 11 81

F 1

./

j Report Number:

82-075/03L l

Report Date:

10-14-82 Occurrence Date:

09-27-82 i

Facility:-

Salem' Generating Station, Unit 1 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

' Pressurizer Level Channel III Instrument - Inoperable.

This report was initiated by Incident Report 82-308.

CONDITIONS PRIOR'TO OCCURRENCE:

Mode 1 - Rx Power 100% - Unit Load 1100 MWe.

DESCRIPTION OF OCCURRENCE:

j At 0720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br />, September'27, 1982, during routine operation, the Control Room Operator discovered.that Pressurizer Level Channel III indication was reading 6% higher than the other i

channels.

Channel III was declared inoperable and Technical Specification Limiting Condition for Operation 3.3.1.1 Action 7 was entered.

At 0729' hours, the' channel bistable was placed in the tripped condition.

The Pressurizer High Pressure trip function was operable providing primary protection against in-creasing pressure transients.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Pressurizer Level Channel III level transmitter had failed previously on August 12, 1982 (see LER 82-063/03L).

The failure was assumed to be of an isolated nature.

Due to the similarity of the events, however, an investigation into the failures is presently being conducted.

ANALYSIS OF OCCURRENCE:

4 The pressurizer level instrumentation is utilized in the Reactor Trip System.to insure the reactor is shutdown during a design step' load decrease.

The trip function provides backup to the l

High Pressurizer Pressure trip; operability of the trip is re-quired to provide the diversity assumed available for the miti-I gation of accident conditions analyzed in the FSAR.

i I

. ~.

LER 82-075/03L ;

ANALYSIS OF OCCURRENCE:Since the redundant channels and primary trip were operable, no risk to the health or safety of the public was involved.

The occurrence constituted operation in a degraded mode per-mitted by a limiting condition for operation and is reportable in accordance with Technical Specification 6.9.1.9.b.

Limiting Condition for Operation 3.3.1.1 Action 7 requires:

With the number of operable channels one less than the total number of channels, power operation may proceed until performance of the next required channel functional test provided the inoperable channel is placed in the tripped condition within one hour.

CORRECTIVE ACTION

As noted, the channel was placed in the tripped condition in compliance with the action statement.

A reactor trip had occurred while restoring Pressurizer Level Channel III to service after the first transmitter failure.

To prevent a trip in the final days of the current fuel cycle, the repair of the channel was delayed until the refueling outage.

License Change Request 82-22 was submitted for a one time deferral of the channel functional test to maintain compliance with Limiting Condition for Operation Action 7.

A Supplemental Report will be submitted upon completion of investigation and repair of the problem.

FAILURE DATA:

Rosemount Inc.

Differential Pressure Transmitter Model 1153 0

/.'/'

A Prepared By R.

Frahm General Manager -

Salem Operations SORC Meeting No.

82-91