Temporary Instruction (TI) 2515/191 Summary of Findings Page 1 of 3 Site Region Inspection Report Date of Issuance Inspection Report ADAMS #
NRC Documented Findings Finding Summary Beaver Valley I
5/3/18 ML18124A002 One Green Finding Failure to ensure that the portable diesel equipment could function within the required temperature range.
Calvert Cliffs I
5/30/17 ML17151A232 None N/A Fitzpatrick I
8/23/18 ML18240A368 None N/A Ginna I
12/2/16 ML16337A092 None N/A Hope Creek I
10/26/17 ML17300A141 None N/A Indian Point I
1/31/18 ML18031A358 One Green Finding Failure to ensure that the portable diesel equipment could function within the required temperature range.
Limerick I
7/26/19 ML19207A083 None N/A Millstone I
11/28/16 ML16334A454 None N/A Nine Mile Point I
10/19/17 ML17293A057 None N/A Oyster Creek I
11/30/17 ML17334A756 None N/A Peach Bottom I
3/5/19 ML19065A010 One Green Finding Failure to maintain the SFPI battery functional.
Pilgrim I
7/7/16 ML16189A066 None N/A Salem I
10/26/17 ML17300A058 None N/A Seabrook I
6/27/17 ML17180A060 None N/A Susquehanna I
8/6/19 ML19219A244 None N/A Three Mile Island I
9/11/17 ML17255A131 None N/A Browns Ferry II 1/4/19 ML19015A302 None N/A Brunswick II 3/12/18 ML18071A151 None N/A Catawba II 11/16/17 ML17320A365 None N/A Farley II 8/6/18 ML18218A291 None N/A Harris II 1/11/17 ML17011A222 None N/A Hatch II 9/21/18 ML18264A038 None N/A McGuire II 8/30/16 ML16243A298 None N/A North Anna II 3/30/16 ML16091A340 None N/A Oconee II 8/28/18 ML18240A355 None N/A Robinson II 5/26/16 ML16147A118 None N/A Sequoyah II 4/18/17 ML17108A583 None N/A St. Lucie II 8/15/17 ML17227A031 None N/A
Temporary Instruction (TI) 2515/191 Summary of Findings Page 2 of 3 Site Region Inspection Report Date of Issuance Inspection Report ADAMS #
NRC Documented Findings Finding Summary Summer II 4/10/18 ML18100A270 None N/A Surry II 4/11/17 ML17101A808 None N/A Turkey Point II 3/30/18 ML18089A127 None N/A Vogtle II 12/11/17 ML17345A892 None N/A Watts Bar II 6/22/15 ML15173A317 None N/A Braidwood III 2/2/18 ML18033A711 None N/A Byron III 9/20/17 ML17263B152 None N/A Clinton III 9/22/16 ML16266A301 One Green Finding Failure to provide adequate analysis to ensure that temporary hose can provide adequate diesel generator cooling.
Davis Besse III 5/23/17 ML17143A342 One Green Finding Failure to maintain adequate room temperature to support FLEX operation.
DC Cook III 6/7/16 ML16160A133 None N/A Dresden III 1/2/18 ML18002A344 None N/A Duane Arnold III 10/17/17 ML17292A738 None N/A Fermi III 2/23/17 ML17058A086 None N/A LaSalle III 11/26/18 ML18331A139 One Green Finding Failure to ensure that sufficient electrical cabling was available for one deployment path of the mitigating strategy.
Monticello III 4/25/18 ML18115A064 None N/A Palisades III 12/2/06 ML16337A098 None N/A Perry III 9/14/16 ML16258A452 Two Green Findings Failure to establish replacement program or justify deviations for high-temperature rated hoses based on vendor recommendations. Failure to establish periodic maintenance for communication equipment.
Point Beach III 6/16/17 ML17170A097 None N/A Prairie Island III 8/9/17 ML17222A208 None N/A Quad Cities III 5/17/19 ML19140A084 None N/A ANO IV 5/22/17 ML17143A032 Two Green Findings Failure to assure that FLEX DG power supply connection design would be reliable following high wind events.
Failure to provide adequate procedures to ensure implementation of the FLEX strategies.
Temporary Instruction (TI) 2515/191 Summary of Findings Page 3 of 3 Site Region Inspection Report Date of Issuance Inspection Report ADAMS #
NRC Documented Findings Finding Summary Callaway IV 10/3/17 ML17277A053 None N/A Columbia IV 8/20/18 ML18232A432 None N/A Comanche Peak IV 7/9/17 ML17192A436 None N/A Cooper IV 5/8/18 ML18128A074 One Green Finding Failure to maintain the station satellite phones in locations that would provide reasonable assurance that the phones would remain available.
Diablo Canyon IV 1/24/18 ML18025A000 None N/A Grand Gulf IV 5/16/17 ML17136A174 None N/A Palo Verde IV 1/3/17 ML17004A044 None N/A River Bend IV 8/1/17 ML17214A822 None N/A South Texas IV 12/22/17 ML17354A799 None N/A Waterford IV 7/20/18 ML18201A492 Two Green Findings (Notice of Violation also issued with one finding)
Failure to maintain availability of N+1 FLEX EDG. Notice of Violation issued.
Failure to consider internal flooding assumptions could result in unavailability of FLEX core cooling pump.
Wolf Creek IV 3/23/18 ML18082A107 None N/A