ML14170A045: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(StriderTol Bot change)
 
Line 16: Line 16:


=Text=
=Text=
{{#Wiki_filter:Definitions 1.1 1.0 USE AND APPLICATION 1.1 Definitions
{{#Wiki_filter:Definitions 1.1 (continued)
Watts Bar - Unit 2 1.1-1 (developmental)
A 1.0 USE AND APPLICATION 1.1 Definitions  
-----------------------------------------------------------NOTE----------------------------------------------------------
-----------------------------------------------------------NOTE----------------------------------------------------------
The defined terms of this section appear in capitalized type and are applicable throughout these Technical Specifications and Bases.
The defined terms of this section appear in capitalized type and are applicable throughout these Technical Specifications and Bases.
Term                                         Definition ACTIONS                                       ACTIONS shall be that part of a Specification that prescribes Required Actions to be taken under designated Conditions within specified Completion Times.
Term Definition ACTIONS ACTIONS shall be that part of a Specification that prescribes Required Actions to be taken under designated Conditions within specified Completion Times.
ACTUATION LOGIC TEST                         An ACTUATION LOGIC TEST shall be the application of various simulated or actual input combinations in conjunction with each possible interlock logic state and the verification of the required logic output. The ACTUATION LOGIC TEST, as a minimum, shall include a continuity check of output devices.
ACTUATION LOGIC TEST An ACTUATION LOGIC TEST shall be the application of various simulated or actual input combinations in conjunction with each possible interlock logic state and the verification of the required logic output. The ACTUATION LOGIC TEST, as a minimum, shall include a continuity check of output devices.
AXIAL FLUX DIFFERENCE                         AFD shall be the difference in normalized flux signals (AFD)                                        between the top and bottom halves of a two section excore neutron detector.
AXIAL FLUX DIFFERENCE (AFD)
CHANNEL CALIBRATION                           A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel so that it responds within the required range and accuracy to known input. The CHANNEL CALIBRATION shall encompass the entire channel, including the required sensor, alarm, interlock, display, and trip functions. Calibration of instrument channels with resistance temperature detector (RTD) or thermocouple sensors may consist of an inplace qualitative assessment of sensor behavior and normal calibration of the remaining adjustable devices in the channel. Whenever a sensing element is replaced, the next required CHANNEL CALIBRATION shall include an inplace cross calibration that compares the other sensing elements with the recently installed sensing element.
AFD shall be the difference in normalized flux signals between the top and bottom halves of a two section excore neutron detector.
The CHANNEL CALIBRATION may be performed by means of any series of sequential, overlapping calibrations or total channel steps so that the entire channel is calibrated.
CHANNEL CALIBRATION A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel so that it responds within the required range and accuracy to known input. The CHANNEL CALIBRATION shall encompass the entire channel, including the required sensor, alarm, interlock, display, and trip functions. Calibration of instrument channels with resistance temperature detector (RTD) or thermocouple sensors may consist of an inplace qualitative assessment of sensor behavior and normal calibration of the remaining adjustable devices in the channel. Whenever a sensing element is replaced, the next required CHANNEL CALIBRATION shall include an inplace cross calibration that compares the other sensing elements with the recently installed sensing element.
(continued)
The CHANNEL CALIBRATION may be performed by means of any series of sequential, overlapping calibrations or total channel steps so that the entire channel is calibrated.  
Watts Bar - Unit 2                                          1.1-1 (developmental)                                                                                                              A


Definitions 1.1 1.1 Definitions (continued)
Definitions 1.1 1.1 Definitions (continued)
CHANNEL CHECK              A CHANNEL CHECK shall be the qualitative assessment, by observation, of channel behavior during operation. This determination shall include, where possible, comparison of the channel indication and status to other indications or status derived from independent instrument channels measuring the same parameter.
CHANNEL OPERATIONAL        A COT shall be the injection of a simulated or actual signal TEST (COT)                  into the channel as close to the sensor as practicable to verify the OPERABILITY of required alarm, interlock, display, and trip functions. The COT shall include adjustments, as necessary, of the required alarm, interlock, and trip setpoints so that the setpoints are within the required range and accuracy.
CORE ALTERATION            CORE ALTERATION shall be the movement of any fuel, sources, or other reactivity control components, within the reactor vessel with the vessel head removed and fuel in the vessel. Suspension of CORE ALTERATIONS shall not preclude completion of movement of a component to a safe position.
CORE OPERATING LIMITS      The COLR is the unit specific document that provides cycle REPORT (COLR)              specific parameter limits for the initial and current reload cycle. These cycle specific parameter limits shall be determined for the initial and each reload cycle in accordance with Specification 5.9.5. Plant operation within these limits is addressed in individual Specifications.
DOSE EQUIVALENT I-131      DOSE EQUIVALENT I-131 shall be that concentration of I-131 (microcuries/gram) that alone would produce the same thyroid dose as the quantity and isotopic mixture of I-131, I-132, I-133, I-134, and I-135 actually present. The thyroid dose conversion factors used for this calculation shall be those listed in Table E-7 of Regulatory Guide 1.109, Rev. 1, NRC, 1977.
(continued)
(continued)
Watts Bar - Unit 2                       1.1-2 (developmental)                                                                             AI
Watts Bar - Unit 2 1.1-2 (developmental)
AI CHANNEL CHECK A CHANNEL CHECK shall be the qualitative assessment, by observation, of channel behavior during operation. This determination shall include, where possible, comparison of the channel indication and status to other indications or status derived from independent instrument channels measuring the same parameter.
CHANNEL OPERATIONAL TEST (COT)
A COT shall be the injection of a simulated or actual signal into the channel as close to the sensor as practicable to verify the OPERABILITY of required alarm, interlock, display, and trip functions. The COT shall include adjustments, as necessary, of the required alarm, interlock, and trip setpoints so that the setpoints are within the required range and accuracy.
CORE ALTERATION CORE ALTERATION shall be the movement of any fuel, sources, or other reactivity control components, within the reactor vessel with the vessel head removed and fuel in the vessel. Suspension of CORE ALTERATIONS shall not preclude completion of movement of a component to a safe position.
CORE OPERATING LIMITS REPORT (COLR)
The COLR is the unit specific document that provides cycle specific parameter limits for the initial and current reload cycle. These cycle specific parameter limits shall be determined for the initial and each reload cycle in accordance with Specification 5.9.5. Plant operation within these limits is addressed in individual Specifications.
DOSE EQUIVALENT I-131 DOSE EQUIVALENT I-131 shall be that concentration of I-131 (microcuries/gram) that alone would produce the same thyroid dose as the quantity and isotopic mixture of I-131, I-132, I-133, I-134, and I-135 actually present. The thyroid dose conversion factors used for this calculation shall be those listed in Table E-7 of Regulatory Guide 1.109, Rev. 1, NRC, 1977.


Definitions 1.1 1.1 Definitions (continued)
Definitions 1.1 1.1 Definitions (continued)
- AVERAGE                  shall be the average (weighted in proportion to the DISINTEGRATION ENERGY      concentration of each radionuclide in the reactor coolant at the time of sampling) of the sum of the average beta and gamma energies per disintegration (in MeV) for isotopes, other than iodines, with half liveshalf-lives > 15 minutes, making up at least 95% of the total non-iodine activity in the coolant.
ENGINEERED SAFETY          The ESF RESPONSE TIME shall be that time interval from FEATURE (ESF) RESPONSE      when the monitored parameter exceeds its ESF actuation TIME                        setpoint at the channel sensor until the ESF equipment is capable of performing its safety function (i.e., the valves travel to their required positions, pump discharge pressures reach their required values, etc.). Times shall include diesel generator starting and sequence loading delays, where applicable. The response time may be measured by means of any series of sequential, overlapping, or total steps so that the entire response time is measured. In lieu of measurement, response time may be verified for selected components provided that the components and the methodology for verification have been previously reviewed and approved by the NRC.
La                          The maximum allowable primary containment leakage rate, La, shall be .25% of primary containment air weight per day at the calculated peak containment pressure (Pa).
(continued)
(continued)
Watts Bar - Unit 2                     1.1-3 (developmental)                                                                             AI
Watts Bar - Unit 2 1.1-3 (developmental)
AI  
- AVERAGE DISINTEGRATION ENERGY shall be the average (weighted in proportion to the concentration of each radionuclide in the reactor coolant at the time of sampling) of the sum of the average beta and gamma energies per disintegration (in MeV) for isotopes, other than iodines, with half liveshalf-lives > 15 minutes, making up at least 95% of the total non-iodine activity in the coolant.
ENGINEERED SAFETY FEATURE (ESF) RESPONSE TIME The ESF RESPONSE TIME shall be that time interval from when the monitored parameter exceeds its ESF actuation setpoint at the channel sensor until the ESF equipment is capable of performing its safety function (i.e., the valves travel to their required positions, pump discharge pressures reach their required values, etc.). Times shall include diesel generator starting and sequence loading delays, where applicable. The response time may be measured by means of any series of sequential, overlapping, or total steps so that the entire response time is measured. In lieu of measurement, response time may be verified for selected components provided that the components and the methodology for verification have been previously reviewed and approved by the NRC.
La The maximum allowable primary containment leakage rate, La, shall be.25% of primary containment air weight per day at the calculated peak containment pressure (Pa).


Definitions 1.1 1.1 Definitions (continued)
Definitions 1.1 1.1 Definitions (continued)
LEAKAGE                     LEAKAGE shall be:
(continued)
: a. Identified LEAKAGE
Watts Bar - Unit 2 1.1-4 (developmental)
AI LEAKAGE LEAKAGE shall be:
: a.
Identified LEAKAGE
: 1. LEAKAGE, such as that from pump seals or valve packing (except reactor coolant pump (RCP) seal water injection or leakoff), that is captured and conducted to collection systems or a sump or collecting tank;
: 1. LEAKAGE, such as that from pump seals or valve packing (except reactor coolant pump (RCP) seal water injection or leakoff), that is captured and conducted to collection systems or a sump or collecting tank;
: 2. LEAKAGE into the containment atmosphere from sources that are both specifically located and known either not to interfere with the operation of leakage detection systems or not to be pressure boundary LEAKAGE; or
: 2. LEAKAGE into the containment atmosphere from sources that are both specifically located and known either not to interfere with the operation of leakage detection systems or not to be pressure boundary LEAKAGE; or
: 3. Reactor Coolant System (RCS) LEAKAGE through a steam generator to the Secondary System (primary-to-secondary LEAKAGE);
: 3. Reactor Coolant System (RCS) LEAKAGE through a steam generator to the Secondary System (primary-to-secondary LEAKAGE);
: b. Unidentified LEAKAGE All LEAKAGE (except RCP seal water injection or leakoff) that is not identified LEAKAGE;
: b.
: c. Pressure Boundary LEAKAGE LEAKAGE (except primary-to-secondary LEAKAGE) through a nonisolable fault in an RCS component body, pipe wall, or vessel wall.
Unidentified LEAKAGE All LEAKAGE (except RCP seal water injection or leakoff) that is not identified LEAKAGE;
MASTER RELAY TEST           A MASTER RELAY TEST shall consist of energizing each master relay and verifying the OPERABILITY of each relay.
: c.
Pressure Boundary LEAKAGE LEAKAGE (except primary-to-secondary LEAKAGE) through a nonisolable fault in an RCS component body, pipe wall, or vessel wall.
MASTER RELAY TEST A MASTER RELAY TEST shall consist of energizing each master relay and verifying the OPERABILITY of each relay.
The MASTER RELAY TEST shall include a continuity check of each associated slave relay.
The MASTER RELAY TEST shall include a continuity check of each associated slave relay.
MODE                       A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, average reactor coolant temperature, and reactor vessel head closure bolt tensioning specified in Table 1.1-1 with fuel in the reactor vessel.
MODE A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, average reactor coolant temperature, and reactor vessel head closure bolt tensioning specified in Table 1.1-1 with fuel in the reactor vessel.  
(continued)
Watts Bar - Unit 2                      1.1-4 (developmental)                                                                              AI


Definitions 1.1 1.1 Definitions (continued)
Definitions 1.1 1.1 Definitions (continued)
OPERABLE-OPERABILITY        A system, subsystem, train, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified safety function(s) and when all necessary attendant instrumentation, controls, normal or emergency electrical power, cooling and seal water, lubrication, and other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its specified safety function(s) are also capable of performing their related support function(s).
PCO                        A pressure control operator (PCO) is a devise, such as a damper that is used to control pressure in an air handling system.
PDMS                        The Power Distribution Monitoring System (PDMS) is a real-time three dimensional core monitoring system. The system utilizes existing core instrumentation data and an on-line neutronics code to provide surveillance of core thermal limits.
PHYSICS TESTS              PHYSICS TESTS shall be those tests performed to measure the fundamental nuclear characteristics of the reactor core and related instrumentation. These tests are:
: a. Described in Chapter 14, Initial Test Program of the FSAR;
: b. Authorized under the provisions of 10 CFR 50.59; or
: c. Otherwise approved by the Nuclear Regulatory Commission.
PRESSURE AND                The PTLR is the unit specific document that provides the TEMPERATURE LIMITS          RCS pressure and temperature limits for heatup, cooldown, REPORT (PTLR)              low temperature operation, criticality, and hydrostatic testing as well as heatup and cooldown rates for the current reactor vessel fluence period. These pressure and temperature limits shall be determined for each fluence period in accordance with Specification 5.9.6. Plant operation within these operating limits is addressed in LCO 3.4.3, "RCS Pressure and Temperature (P/T) Limits," and LCO 3.4.12, "Cold Overpressure Mitigation System (COMS)."
(continued)
(continued)
Watts Bar - Unit 2                     1.1-5 (developmental)                                                                           BI
Watts Bar - Unit 2 1.1-5 (developmental)
BI OPERABLE-OPERABILITY A system, subsystem, train, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified safety function(s) and when all necessary attendant instrumentation, controls, normal or emergency electrical power, cooling and seal water, lubrication, and other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its specified safety function(s) are also capable of performing their related support function(s).
PCO A pressure control operator (PCO) is a devise, such as a damper that is used to control pressure in an air handling system.
PDMS The Power Distribution Monitoring System (PDMS) is a real-time three dimensional core monitoring system. The system utilizes existing core instrumentation data and an on-line neutronics code to provide surveillance of core thermal limits.
PHYSICS TESTS PHYSICS TESTS shall be those tests performed to measure the fundamental nuclear characteristics of the reactor core and related instrumentation. These tests are:
: a.
Described in Chapter 14, Initial Test Program of the FSAR;
: b.
Authorized under the provisions of 10 CFR 50.59; or
: c.
Otherwise approved by the Nuclear Regulatory Commission.
PRESSURE AND TEMPERATURE LIMITS REPORT (PTLR)
The PTLR is the unit specific document that provides the RCS pressure and temperature limits for heatup, cooldown, low temperature operation, criticality, and hydrostatic testing as well as heatup and cooldown rates for the current reactor vessel fluence period. These pressure and temperature limits shall be determined for each fluence period in accordance with Specification 5.9.6. Plant operation within these operating limits is addressed in LCO 3.4.3, "RCS Pressure and Temperature (P/T) Limits," and LCO 3.4.12, "Cold Overpressure Mitigation System (COMS)."


Definitions 1.1 1.1 Definitions (continued)
Definitions 1.1 1.1 Definitions (continued)
QUADRANT POWER TILT        QPTR shall be the ratio of the maximum upper excore RATIO (QPTR)                detector calibrated output to the average of the upper excore detector calibrated outputs, or the ratio of the maximum lower excore detector calibrated output to the average of the lower excore detector calibrated outputs, whichever is greater.
RATED THERMAL POWER        RTP shall be a total reactor core heat transfer rate to the (RTP)                      reactor coolant of 3411 MWt.
REACTOR TRIP SYSTEM        The RTS RESPONSE TIME shall be that time interval from (RTS) RESPONSE TIME        when the monitored parameter exceeds its RTS trip setpoint at the channel sensor until loss of stationary gripper coil voltage. The response time may be measured by means of any series of sequential, overlapping, or total steps so that the entire response time is measured. In lieu of measurement, response time may be verified for selected components provided that the components and the methodology for verification have been previously reviewed and approved by the NRC.
SHUTDOWN MARGIN (SDM)      SDM shall be the instantaneous amount of reactivity by which the reactor is subcritical or would be subcritical from its present condition assuming:
: a. All rod cluster control assemblies (RCCAs) are fully inserted except for the single RCCA of highest reactivity worth, which is assumed to be fully withdrawn. With any RCCA not capable of being fully inserted, the reactivity worth of the RCCA must be accounted for in the determination of SDM; and
: b. In MODES 1 and 2, the fuel and moderator temperatures are changed to the nominal zero power design level.
SLAVE RELAY TEST            A SLAVE RELAY TEST shall consist of energizing each slave relay and verifying the OPERABILITY of each slave relay.
The SLAVE RELAY TEST shall include, as a minimum, a continuity check of associated testable actuation devices.
(continued)
(continued)
Watts Bar - Unit 2                     1.1-6 (developmental)                                                                             A
Watts Bar - Unit 2 1.1-6 (developmental)
A QUADRANT POWER TILT RATIO (QPTR)
QPTR shall be the ratio of the maximum upper excore detector calibrated output to the average of the upper excore detector calibrated outputs, or the ratio of the maximum lower excore detector calibrated output to the average of the lower excore detector calibrated outputs, whichever is greater.
RATED THERMAL POWER (RTP)
RTP shall be a total reactor core heat transfer rate to the reactor coolant of 3411 MWt.
REACTOR TRIP SYSTEM (RTS) RESPONSE TIME The RTS RESPONSE TIME shall be that time interval from when the monitored parameter exceeds its RTS trip setpoint at the channel sensor until loss of stationary gripper coil voltage. The response time may be measured by means of any series of sequential, overlapping, or total steps so that the entire response time is measured. In lieu of measurement, response time may be verified for selected components provided that the components and the methodology for verification have been previously reviewed and approved by the NRC.
SHUTDOWN MARGIN (SDM)
SDM shall be the instantaneous amount of reactivity by which the reactor is subcritical or would be subcritical from its present condition assuming:
: a.
All rod cluster control assemblies (RCCAs) are fully inserted except for the single RCCA of highest reactivity worth, which is assumed to be fully withdrawn. With any RCCA not capable of being fully inserted, the reactivity worth of the RCCA must be accounted for in the determination of SDM; and
: b.
In MODES 1 and 2, the fuel and moderator temperatures are changed to the nominal zero power design level.
SLAVE RELAY TEST A SLAVE RELAY TEST shall consist of energizing each slave relay and verifying the OPERABILITY of each slave relay.
The SLAVE RELAY TEST shall include, as a minimum, a continuity check of associated testable actuation devices.


Definitions 1.1 1.1 Definitions (continued)
Definitions 1.1 1.1 Definitions (continued)
STAGGERED TEST BASIS       A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other designated components during the interval specified by the Surveillance Frequency, so that all systems, subsystems, channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems, channels, or other designated components in the associated function.
Watts Bar - Unit 2 1.1-7 (developmental)
THERMAL POWER               THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.
A STAGGERED TEST BASIS A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other designated components during the interval specified by the Surveillance Frequency, so that all systems, subsystems, channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems, channels, or other designated components in the associated function.
TRIP ACTUATING DEVICE       A TADOT shall consist of operating the trip actuating device OPERATIONAL TEST            and verifying the OPERABILITY of required alarm, interlock, (TADOT)                    display, and trip functions. The TADOT shall include adjustment, as necessary, of the trip actuating device so that it actuates at the required setpoint within the required accuracy.
THERMAL POWER THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.
Watts Bar - Unit 2                      1.1-7 (developmental)                                                                              A
TRIP ACTUATING DEVICE OPERATIONAL TEST (TADOT)
A TADOT shall consist of operating the trip actuating device and verifying the OPERABILITY of required alarm, interlock, display, and trip functions. The TADOT shall include adjustment, as necessary, of the trip actuating device so that it actuates at the required setpoint within the required accuracy.  


Definitions 1.1 Table 1.1-1 (page 1 of 1)
Definitions 1.1 Watts Bar - Unit 2 1.1-8 (developmental)
MODES AVERAGE REACTIVITY         % RATED      REACTOR COOLANT CONDITION           THERMAL        TEMPERATURE MODE                TITLE                  (keff)       POWER (a)             (&deg;F) 1       Power Operation                 0.99             >5                 NA 2       Startup                         0.99             <5                 NA 3       Hot Standby                   < 0.99             NA                 350 4       Hot Shutdown (b)               < 0.99             NA           350 > Tavg > 200 5       Cold Shutdown (b)             < 0.99             NA                 < 200 6       Refueling (c)                     NA             NA                 NA (a)   Excluding decay heat.
A Table 1.1-1 (page 1 of 1)
(b)   All reactor vessel head closure bolts fully tensioned.
MODES MODE TITLE REACTIVITY CONDITION (keff)  
(c)   One or more reactor vessel head closure bolts less than fully tensioned.
% RATED THERMAL POWER (a)
Watts Bar - Unit 2                            1.1-8 (developmental)                                                                                  A
AVERAGE REACTOR COOLANT TEMPERATURE
(&deg;F) 1 Power Operation 0.99  
> 5 NA 2
Startup 0.99  
< 5 NA 3
Hot Standby  
< 0.99 NA 350 4
Hot Shutdown (b)  
< 0.99 NA 350 > Tavg > 200 5
Cold Shutdown (b)  
< 0.99 NA  
< 200 6
Refueling (c)
NA NA NA (a)
Excluding decay heat.
(b)
All reactor vessel head closure bolts fully tensioned.
(c)
One or more reactor vessel head closure bolts less than fully tensioned.  


SDM - Tavg > 200&deg;F 3.1.1 3.1 REACTIVITY CONTROL SYSTEMS 3.1.1 SHUTDOWN MARGIN (SDM) - Tavg > 200&deg;F LCO 3.1.1           SDM shall be > 1.6% k/k.
SDM - Tavg > 200&deg;F 3.1.1 Watts Bar - Unit 2 3.1-1 (developmental)
APPLICABILITY:       MODE 2 with keff < 1.0, MODES 3 and 4.
AI 3.1 REACTIVITY CONTROL SYSTEMS 3.1.1 SHUTDOWN MARGIN (SDM) - Tavg > 200&deg;F LCO 3.1.1 SDM shall be > 1.6% k/k.
ACTIONS CONDITION                       REQUIRED ACTION                 COMPLETION TIME A. SDM not within limit.           A.1       Initiate boration to restore 15 minutes SDM to within limit.
APPLICABILITY:
SURVEILLANCE REQUIREMENTS SURVEILLANCE                                     FREQUENCY SR 3.1.1.1         Verify SDM is > 1.6% k/k.                             24 hours Watts Bar - Unit 2                          3.1-1 (developmental)                                                                              AI
MODE 2 with keff < 1.0, MODES 3 and 4.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. SDM not within limit.
A.1 Initiate boration to restore SDM to within limit.
15 minutes SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.1.1 Verify SDM is > 1.6% k/k.
24 hours  


SDM - Tavg < 200&deg;F 3.1.2 3.1 REACTIVITY CONTROL SYSTEMS 3.1.2 SHUTDOWN MARGIN (SDM) - Tavg < 200&deg;F LCO 3.1.2             The SDM shall be 1.0% k/k.
SDM - Tavg < 200&deg;F 3.1.2 Watts Bar - Unit 2 3.1-2 (developmental)
APPLICABILITY:       MODE 5.
AI 3.1 REACTIVITY CONTROL SYSTEMS 3.1.2 SHUTDOWN MARGIN (SDM) - Tavg < 200&deg;F LCO 3.1.2 The SDM shall be 1.0% k/k.
ACTIONS CONDITION                         REQUIRED ACTION               COMPLETION TIME A. SDM not within limit.             A.1     Initiate boration to restore 15 minutes SDM to within limit.
APPLICABILITY:
SURVEILLANCE REQUIREMENTS SURVEILLANCE                                       FREQUENCY SR 3.1.2.1         Verify SDM is 1.0% k/k.                               24 hours Watts Bar - Unit 2                            3.1-2 (developmental)                                                                                AI
MODE 5.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. SDM not within limit.
A.1 Initiate boration to restore SDM to within limit.
15 minutes SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.2.1 Verify SDM is 1.0% k/k.
24 hours  


MTC 3.1.4 3.1 REACTIVITY CONTROL SYSTEMS 3.1.4 Moderator Temperature Coefficient (MTC)
MTC 3.1.4 Watts Bar - Unit 2 3.1-5 (developmental)
LCO 3.1.4             The MTC shall be maintained within the limits specified in the COLR. The maximum upper limit shall be 0 k/k&deg;F at hot zero power.
A 3.1 REACTIVITY CONTROL SYSTEMS 3.1.4 Moderator Temperature Coefficient (MTC)
APPLICABILITY:       MODE 1 and MODE 2 with keff 1.0 for the upper MTC limit, MODES 1, 2, and 3 for the lower MTC limit.
LCO 3.1.4 The MTC shall be maintained within the limits specified in the COLR. The maximum upper limit shall be 0 k/k&deg;F at hot zero power.
ACTIONS CONDITION                     REQUIRED ACTION                   COMPLETION TIME A. MTC not within upper limit. A.1       Establish administrative       24 hours withdrawal limits for control banks to maintain MTC within limit.
APPLICABILITY:
B. Required Action and           B.1       Be in MODE 2 with             6 hours associated Completion Time              keff < 1.0.
MODE 1 and MODE 2 with keff 1.0 for the upper MTC limit, MODES 1, 2, and 3 for the lower MTC limit.
of Condition A not met.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. MTC not within upper limit.
C. MTC not within lower limit. C.1       Be in MODE 4.                 12 hours Watts Bar - Unit 2                          3.1-5 (developmental)                                                                              A
A.1 Establish administrative withdrawal limits for control banks to maintain MTC within limit.
24 hours B. Required Action and associated Completion Time of Condition A not met.
B.1 Be in MODE 2 with keff < 1.0.
6 hours C. MTC not within lower limit.
C.1 Be in MODE 4.
12 hours  


MTC 3.1.4 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                                   FREQUENCY SR 3.1.4.1         Verify MTC is within upper limit                                     Once prior to entering MODE 1 after initial fuel loading and each refueling SR 3.1.4.2         Verify MTC is within 300 ppm Surveillance limit                       ----------NOTE---------
MTC 3.1.4 Watts Bar - Unit 2 3.1-6 (developmental)
specified in the COLR.                                                Not required to be performed until 7 effective full power days (EFPD) after reaching the equivalent of an equilibrium RTP all rods out (ARO) boron concentration of 300 ppm Once each cycle SR 3.1.4.3         -------------------------------NOTES----------------------------      ----------NOTE---------
AI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.4.1 Verify MTC is within upper limit Once prior to entering MODE 1 after initial fuel loading and each refueling SR 3.1.4.2 Verify MTC is within 300 ppm Surveillance limit specified in the COLR.
: 1. If the MTC is more negative than the 300 ppm                       Not required to be Surveillance limit (not LCO limit) specified in the             performed until COLR, SR 3.1.4.3 shall be repeated once per                     7 EFPD after 14 EFPD during the remainder of the fuel cycle.                 reaching the equivalent of an
----------NOTE---------
: 2. SR 3.1.4.3 need not be repeated if the MTC                         equilibrium measured at the equivalent of equilibrium                       RTP-ARO boron RTP-ARO boron concentration of < 60 ppm is                     concentration of less negative than the 60 ppm Surveillance limit                 300 ppm specified in the COLR.                                           ---------------------------
Not required to be performed until 7 effective full power days (EFPD) after reaching the equivalent of an equilibrium RTP all rods out (ARO) boron concentration of 300 ppm Once each cycle SR 3.1.4.3  
Verify MTC is within lower limit.                                     Once each cycle Watts Bar - Unit 2                                    3.1-6 (developmental)                                                                                                  AI
-------------------------------NOTES----------------------------
: 1. If the MTC is more negative than the 300 ppm Surveillance limit (not LCO limit) specified in the COLR, SR 3.1.4.3 shall be repeated once per 14 EFPD during the remainder of the fuel cycle.
: 2. SR 3.1.4.3 need not be repeated if the MTC measured at the equivalent of equilibrium RTP-ARO boron concentration of < 60 ppm is less negative than the 60 ppm Surveillance limit specified in the COLR.  
----------NOTE---------
Not required to be performed until 7 EFPD after reaching the equivalent of an equilibrium RTP-ARO boron concentration of 300 ppm Verify MTC is within lower limit.
Once each cycle  


Rod Group Alignment Limits 3.1.5 3.1 REACTIVITY CONTROL SYSTEMS 3.1.5 Rod Group Alignment Limits LCO 3.1.5             All shutdown and control rods shall be OPERABLE, with all individual indicated rod positions within 12 steps of their group step counter demand position.
Rod Group Alignment Limits 3.1.5 Watts Bar - Unit 2 3.1-7 (developmental)
APPLICABILITY:       MODES 1 and 2.
A 3.1 REACTIVITY CONTROL SYSTEMS 3.1.5 Rod Group Alignment Limits LCO 3.1.5 All shutdown and control rods shall be OPERABLE, with all individual indicated rod positions within 12 steps of their group step counter demand position.
ACTIONS CONDITION                         REQUIRED ACTION                 COMPLETION TIME A. One or more rod(s)               A.1.1     Verify SDM is                 1 hour untrippable.                              1.6% k/k.
APPLICABILITY:
OR A.1.2     Initiate boration to restore   1 hour SDM to within limit.
MODES 1 and 2.
AND A.2       Be in MODE 3.                 6 hours B. One rod not within               B.1       Restore rod to within         1 hour alignment limits.                        alignment limits.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more rod(s) untrippable.
OR B.2.1.1   Verify SDM is                 1 hour 1.6% k/k.
A.1.1 Verify SDM is 1.6% k/k.
OR B.2.1.2   Initiate boration to restore   1 hour SDM to within limit.
1 hour OR A.1.2 Initiate boration to restore SDM to within limit.
AND                                           (continued)
1 hour AND A.2 Be in MODE 3.
Watts Bar - Unit 2                            3.1-7 (developmental)                                                                                  A
6 hours B. One rod not within alignment limits.
B.1 Restore rod to within alignment limits.
1 hour OR B.2.1.1 Verify SDM is 1.6% k/k.
1 hour OR B.2.1.2 Initiate boration to restore SDM to within limit.
1 hour AND (continued)  


Rod Group Alignment Limits 3.1.5 ACTIONS CONDITION                 REQUIRED ACTION                 COMPLETION TIME B. (continued)               B.2.2   Reduce THERMAL               2 hours POWER to < 75% RTP.
Rod Group Alignment Limits 3.1.5 Watts Bar - Unit 2 3.1-8 (developmental)
AND B.2.3   Verify SDM is                 Once per 12 hours 1.6% k/k.
AI ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. (continued)
AND B.2.4   Perform SR 3.2.1.1.           72 hours AND B.2.5   Perform SR 3.2.2.1.           72 hours AND B.2.6   Re-evaluate safety           5 days analyses and confirm results remain valid for duration of operation under these conditions C. Required Action and       C.1     Be in MODE 3.                 6 hours associated Completion Time of Condition B not met.
B.2.2 Reduce THERMAL POWER to < 75% RTP.
D. More than one rod not     D.1.1   Verify SDM is                 1 hour within alignment limit.            1.6% k/k.
2 hours AND B.2.3 Verify SDM is 1.6% k/k.
OR D.1.2   Initiate boration to restore 1 hour required SDM to within limit.
Once per 12 hours AND B.2.4 Perform SR 3.2.1.1.
AND D.2     Be in MODE 3.                 6 hours Watts Bar - Unit 2                    3.1-8 (developmental)                                                                        AI
72 hours AND B.2.5 Perform SR 3.2.2.1.
72 hours AND B.2.6 Re-evaluate safety analyses and confirm results remain valid for duration of operation under these conditions 5 days C. Required Action and associated Completion Time of Condition B not met.
C.1 Be in MODE 3.
6 hours D. More than one rod not within alignment limit.
D.1.1 Verify SDM is 1.6% k/k.
1 hour OR D.1.2 Initiate boration to restore required SDM to within limit.
1 hour AND D.2 Be in MODE 3.
6 hours  


Rod Group Alignment Limits 3.1.5 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                       FREQUENCY SR 3.1.5.1         Verify individual rod positions within alignment limit. 12 hours AND Once within 4 hours and every 4 hours thereafter when the rod position deviation monitor is inoperable SR 3.1.5.2         Verify rod freedom of movement (tripability) by         92 days moving each rod not fully inserted in the core 10 steps in either direction.
Rod Group Alignment Limits 3.1.5 Watts Bar - Unit 2 3.1-9 (developmental)
SR 3.1.5.3         Verify rod drop time of each rod, from the fully         Prior to reactor withdrawn position, is < 2.7 seconds from the           criticality after initial beginning of decay of stationary gripper coil voltage   fuel loading and to dashpot entry, with:                                 each removal of the reactor head
AI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.5.1 Verify individual rod positions within alignment limit.
: a. Tavg 551&deg;F; and
12 hours AND Once within 4 hours and every 4 hours thereafter when the rod position deviation monitor is inoperable SR 3.1.5.2 Verify rod freedom of movement (tripability) by moving each rod not fully inserted in the core 10 steps in either direction.
: b. All reactor coolant pumps operating.
92 days SR 3.1.5.3 Verify rod drop time of each rod, from the fully withdrawn position, is < 2.7 seconds from the beginning of decay of stationary gripper coil voltage to dashpot entry, with:
Watts Bar - Unit 2                              3.1-9 (developmental)                                                                                    AI
: a.
Tavg 551&deg;F; and
: b.
All reactor coolant pumps operating.
Prior to reactor criticality after initial fuel loading and each removal of the reactor head


FQ (Z) 3.2.1 3.2 POWER DISTRIBUTION LIMITS 3.2.1 Heat Flux Hot Channel Factor (FQ (Z))
FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-1 (developmental)
LCO 3.2.1             FQ (Z), as approximated by FQC (Z) and FQW (Z), shall be within the limits specified in the COLR.
AI 3.2 POWER DISTRIBUTION LIMITS 3.2.1 Heat Flux Hot Channel Factor (FQ (Z))
APPLICABILITY:       MODE 1.
LCO 3.2.1 FQ (Z), as approximated by FQ C (Z) and FQ W (Z), shall be within the limits specified in the COLR.
ACTIONS CONDITION                       REQUIRED ACTION                 COMPLETION TIME A. FQC (Z) not within limit.         A.1     Reduce THERMAL               15 minutes POWER 1% RTP for each 1% FQC (Z) exceeds limit.
APPLICABILITY:
AND A.2     Reduce Power Range           8 hours Neutron FluxHigh trip setpoints > 1% for each 1% FQC (Z) exceeds limit.
MODE 1.
AND A.3     Reduce Overpower T         72 hours trip setpoints 1% for each 1% FQC (Z) exceeds limit.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. FQ C (Z) not within limit.
AND A.4     Perform SR 3.2.1.1.         Prior to increasing THERMAL POWER above the limit of Required Action A.1 (continued)
A.1 Reduce THERMAL POWER 1% RTP for each 1% FQ C (Z) exceeds limit.
Watts Bar - Unit 2                          3.2-1 (developmental)                                                                                  AI
15 minutes AND A.2 Reduce Power Range Neutron FluxHigh trip setpoints > 1% for each 1% FQ C (Z) exceeds limit.
8 hours AND A.3 Reduce Overpower T trip setpoints 1% for each 1% FQ C (Z) exceeds limit.
72 hours AND A.4 Perform SR 3.2.1.1.
Prior to increasing THERMAL POWER above the limit of Required Action A.1 (continued)  


FQ (Z) 3.2.1 ACTIONS (continued)
FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-2 (developmental)
CONDITION               REQUIRED ACTION         COMPLETION TIME B. FQW (Z) not within limits. B.1   Reduce AFD limits 1% 2 hours for each 1% FQW (Z) exceeds limit.
A ACTIONS (continued)
C. Required Action and       C.1   Be in MODE 2.         6 hours associated Completion Time not met.
CONDITION REQUIRED ACTION COMPLETION TIME B. FQ W (Z) not within limits.
Watts Bar - Unit 2                  3.2-2 (developmental)                                                          A
B.1 Reduce AFD limits 1%
for each 1% FQ W (Z) exceeds limit.
2 hours C. Required Action and associated Completion Time not met.
C.1 Be in MODE 2.
6 hours  


FQ (Z) 3.2.1 SURVEILLANCE REQUIREMENTS
FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-3 (developmental)
A SURVEILLANCE REQUIREMENTS  
-----------------------------------------------------------NOTE----------------------------------------------------------
-----------------------------------------------------------NOTE----------------------------------------------------------
During power escalation at the beginning of each cycle, THERMAL POWER may be increased until an equilibrium power level has been achieved, at which a power distribution map is obtained.
During power escalation at the beginning of each cycle, THERMAL POWER may be increased until an equilibrium power level has been achieved, at which a power distribution map is obtained.
SURVEILLANCE                                                       FREQUENCY SR 3.2.1.1               Verify FQC (Z) is within limit.                                           Once after initial fuel loading and each refueling prior to THERMAL POWER exceeding 75% RTP AND Once within 12 hours after achieving equilibrium conditions after exceeding, by 10% RTP, the THERMAL POWER at which FQC (Z) was last verified AND 31 EFPD thereafter (continued)
SURVEILLANCE FREQUENCY SR 3.2.1.1 Verify FQ C (Z) is within limit.
Watts Bar - Unit 2                                         3.2-3 (developmental)                                                                                                             A
Once after initial fuel loading and each refueling prior to THERMAL POWER exceeding 75% RTP AND Once within 12 hours after achieving equilibrium conditions after exceeding, by 10% RTP, the THERMAL POWER at which FQ C (Z) was last verified AND 31 EFPD thereafter (continued)  
 
FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-4 (developmental)
B SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.2.1.2
-------------------------------NOTE------------------------------
If FQ W (Z) is within limits and measurements indicate maximum over z


FQ (Z) 3.2.1 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE                                                  FREQUENCY SR 3.2.1.2        -------------------------------NOTE------------------------------
If FQW (Z) is within limits and measurements indicate
()
()
maximum over z
()
()
has increased since the previous evaluation of FQC (Z):
has increased since the previous evaluation of FQ C
: a. Increase FQW (Z) by the appropriate factor specified in the COLR and reverify FQW (Z) is within limits; or
(Z):
: b. Repeat SR 3.2.1.2 once per 7 EFPD using the Power Distribution Monitoring System (PDMS) until two successive incore power distribution measurements indicate maximum over z               ()
: a.
Increase FQ W (Z) by the appropriate factor specified in the COLR and reverify FQ W (Z) is within limits; or
: b.
Repeat SR 3.2.1.2 once per 7 EFPD using the Power Distribution Monitoring System (PDMS) until two successive incore power distribution measurements indicate maximum over z  
 
()
()
()
has not increased.
has not increased.
Verify FQW (Z) is within limit.                                       Once after initial fuel loading and each refueling prior to THERMAL POWER exceeding 75% RTP AND (continued)
Verify FQ W (Z) is within limit.
Watts Bar - Unit 2                                    3.2-4 (developmental)                                                                                                B
Once after initial fuel loading and each refueling prior to THERMAL POWER exceeding 75% RTP AND (continued)  


FQ (Z) 3.2.1 SURVEILLANCE REQUIREMENTS SURVEILLANCE         FREQUENCY SR 3.2.1.2         (continued)                 Once within 12 hours after achieving equilibrium conditions after exceeding, by 10% RTP, the THERMAL POWER at which FQW (Z) was last verified AND 31 EFPD thereafter Watts Bar - Unit 2                      3.2-5 (developmental)                                                    A
FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-5 (developmental)
A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.2.1.2 (continued)
Once within 12 hours after achieving equilibrium conditions after exceeding, by 10% RTP, the THERMAL POWER at which FQ W (Z) was last verified AND 31 EFPD thereafter  


AFD 3.2.3 3.2 POWER DISTRIBUTION LIMITS 3.2.3 AXIAL FLUX DIFFERENCE (AFD)
AFD 3.2.3 Watts Bar - Unit 2 3.2-8 (developmental)
LCO 3.2.3           The AFD in % flux difference units shall be maintained within the limits specified in the COLR.
AI 3.2 POWER DISTRIBUTION LIMITS 3.2.3 AXIAL FLUX DIFFERENCE (AFD)
                    ---------------------------------------------NOTE--------------------------------------------
LCO 3.2.3 The AFD in % flux difference units shall be maintained within the limits specified in the COLR.  
---------------------------------------------NOTE--------------------------------------------
The AFD shall be considered outside limits when two or more OPERABLE excore channels indicate AFD to be outside limits.
The AFD shall be considered outside limits when two or more OPERABLE excore channels indicate AFD to be outside limits.
APPLICABILITY:       MODE 1 with THERMAL POWER > 50% RTP.
APPLICABILITY:
ACTIONS CONDITION                               REQUIRED ACTION                           COMPLETION TIME A. AFD not within limits.             A.1         Reduce THERMAL                         30 minutes POWER to < 50% RTP.
MODE 1 with THERMAL POWER > 50% RTP.
SURVEILLANCE REQUIREMENTS SURVEILLANCE                                                       FREQUENCY SR 3.2.3.1         Verify AFD within limits for each OPERABLE excore                       7 days channel.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. AFD not within limits.
AND Once within 1 hour and every 1 hour thereafter with the AFD monitor alarm inoperable Watts Bar - Unit 2                                  3.2-8 (developmental)                                                                                                      AI
A.1 Reduce THERMAL POWER to < 50% RTP.
30 minutes SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.2.3.1 Verify AFD within limits for each OPERABLE excore channel.
7 days AND Once within 1 hour and every 1 hour thereafter with the AFD monitor alarm inoperable  


RTS Instrumentation 3.3.1 3.3 INSTRUMENTATION 3.3.1 Reactor Trip System (RTS) Instrumentation LCO 3.3.1                   The RTS instrumentation for each Function in Table 3.3.1-1 shall be OPERABLE.
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-1 (developmental)
APPLICABILITY:             According to Table 3.3.1-1.
A 3.3 INSTRUMENTATION 3.3.1 Reactor Trip System (RTS) Instrumentation LCO 3.3.1 The RTS instrumentation for each Function in Table 3.3.1-1 shall be OPERABLE.
ACTIONS
APPLICABILITY:
According to Table 3.3.1-1.
ACTIONS  
-----------------------------------------------------------NOTE----------------------------------------------------------
-----------------------------------------------------------NOTE----------------------------------------------------------
Separate Condition entry is allowed for each Function.
Separate Condition entry is allowed for each Function.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One or more Functions with                 A.1           Enter the Condition                   Immediately one or more required                                  referenced in channels inoperable.                                  Table 3.3.1-1 for the channel(s).
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more Functions with one or more required channels inoperable.
B. One Manual Reactor Trip                   B.1           Restore channel to                   48 hours channel inoperable.                                    OPERABLE status.
A.1 Enter the Condition referenced in Table 3.3.1-1 for the channel(s).
OR B.2.1         Be in MODE 3.                         54 hours AND B.2.2         Open reactor trip                     55 hours breakers (RTBs).
Immediately B. One Manual Reactor Trip channel inoperable.
(continued)
B.1 Restore channel to OPERABLE status.
Watts Bar - Unit 2                                          3.3-1 (developmental)                                                                                                              A
48 hours OR B.2.1 Be in MODE 3.
54 hours AND B.2.2 Open reactor trip breakers (RTBs).
55 hours (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-2 (developmental)
CONDITION                   REQUIRED ACTION                       COMPLETION TIME C. One channel or train   C.1           Restore channel or train         48 hours inoperable.                          to OPERABLE status.
A ACTIONS (continued)
OR C.2           Open RTBs.                       49 hours D. One Power Range Neutron --------------------NOTE-------------------
CONDITION REQUIRED ACTION COMPLETION TIME C. One channel or train inoperable.
Flux-High channel      The inoperable channel may be inoperable.            bypassed for up to 12 hours for surveillance testing and setpoint adjustment of other channels.
C.1 Restore channel or train to OPERABLE status.
D.1.1         Place channel in trip.           72 hours AND D.1.2         Reduce THERMAL                   78 hours POWER to 75% RTP.
48 hours OR C.2 Open RTBs.
OR D.2.1         Place channel in trip.           72 hours AND
49 hours D. One Power Range Neutron Flux-High channel inoperable.
                          --------------------NOTE-------------------
--------------------NOTE-------------------
The inoperable channel may be bypassed for up to 12 hours for surveillance testing and setpoint adjustment of other channels.
D.1.1 Place channel in trip.
72 hours AND D.1.2 Reduce THERMAL POWER to 75% RTP.
78 hours OR D.2.1 Place channel in trip.
72 hours AND  
--------------------NOTE-------------------
Only required to be performed when the Power Range Neutron Flux input to QPTR is inoperable.
Only required to be performed when the Power Range Neutron Flux input to QPTR is inoperable.
D.2.2         Perform SR 3.2.4.2.               Once per 12 hours OR D.3           Be in MODE 3.                     78 hours (continued)
D.2.2 Perform SR 3.2.4.2.
Watts Bar - Unit 2                      3.3-2 (developmental)                                                                                A
Once per 12 hours OR D.3 Be in MODE 3.
78 hours (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-3 (developmental)
CONDITION                   REQUIRED ACTION                       COMPLETION TIME E. One channel inoperable. --------------------NOTE-------------------
A ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME E. One channel inoperable.  
--------------------NOTE-------------------
The inoperable channel may be bypassed for up to 12 hours for surveillance testing of other channels.
The inoperable channel may be bypassed for up to 12 hours for surveillance testing of other channels.
E.1           Place channel in trip.           72 hours OR E.2           Be in MODE 3.                     78 hours F. THERMAL POWER > P-6     F.1          Reduce THERMAL                    2 hours and < P-10, one                       POWER to < P-6.
E.1 Place channel in trip.
Intermediate Range Neutron Flux channel    OR inoperable.
72 hours OR E.2 Be in MODE 3.
F.2           Increase THERMAL                 2 hours POWER to > P-10.
78 hours F. THERMAL POWER > P-6 and < P-10, one Intermediate Range Neutron Flux channel inoperable.
G. THERMAL POWER > P-6     G.1          Suspend operations                Immediately and < P-10, two                       involving positive Intermediate Range                     reactivity additions.
F.1 Reduce THERMAL POWER to < P-6.
Neutron Flux channels inoperable.             AND G.2           Reduce THERMAL                   2 hours POWER to < P-6.
2 hours OR F.2 Increase THERMAL POWER to > P-10.
H. THERMAL POWER < P-6,     H.1           Restore channel(s) to             Prior to increasing one or two Intermediate                OPERABLE status.                  THERMAL POWER Range Neutron Flux                                                      to > P-6 channels inoperable.
2 hours G. THERMAL POWER > P-6 and < P-10, two Intermediate Range Neutron Flux channels inoperable.
I. One Source Range Neutron I.1           Suspend operations               Immediately Flux channel inoperable.              involving positive reactivity additions.
G.1 Suspend operations involving positive reactivity additions.
(continued)
Immediately AND G.2 Reduce THERMAL POWER to < P-6.
Watts Bar - Unit 2                        3.3-3 (developmental)                                                                                  A
2 hours H. THERMAL POWER < P-6, one or two Intermediate Range Neutron Flux channels inoperable.
H.1 Restore channel(s) to OPERABLE status.
Prior to increasing THERMAL POWER to > P-6 I. One Source Range Neutron Flux channel inoperable.
I.1 Suspend operations involving positive reactivity additions.
Immediately (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-4 (developmental)
CONDITION               REQUIRED ACTION             COMPLETION TIME J. Two Source Range Neutron J.1   Open RTBs.               Immediately Flux channels inoperable.
A ACTIONS (continued)
K. One Source Range Neutron K.1   Restore channel to       48 hours Flux channel inoperable.        OPERABLE status.
CONDITION REQUIRED ACTION COMPLETION TIME J. Two Source Range Neutron Flux channels inoperable.
OR K.2   Open RTBs.               49 hours L. Required Source Range     L.1   Suspend operations       Immediately Neutron Flux channel            involving positive inoperable.                    reactivity additions.
J.1 Open RTBs.
AND L.2   Close unborated water   1 hour source isolation valves.
Immediately K. One Source Range Neutron Flux channel inoperable.
AND L.3   Perform SR 3.1.1.1.     1 hour AND Once per 12 hours thereafter (continued)
K.1 Restore channel to OPERABLE status.
Watts Bar - Unit 2                  3.3-4 (developmental)                                                                  A
48 hours OR K.2 Open RTBs.
49 hours L. Required Source Range Neutron Flux channel inoperable.
L.1 Suspend operations involving positive reactivity additions.
Immediately AND L.2 Close unborated water source isolation valves.
1 hour AND L.3 Perform SR 3.1.1.1.
1 hour AND Once per 12 hours thereafter (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-5 (developmental)
CONDITION                   REQUIRED ACTION                       COMPLETION TIME M. One channel inoperable. --------------------NOTE-------------------
F ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME M. One channel inoperable.  
--------------------NOTE-------------------
The inoperable channel may be bypassed for up to 12 hours for surveillance testing of other channels.
The inoperable channel may be bypassed for up to 12 hours for surveillance testing of other channels.
M.1           Place channel in trip.           72 hours OR M.2           Reduce THERMAL                   78 hours POWER to < P-7.
M.1 Place channel in trip.
N. One Reactor Coolant     --------------------NOTE-------------------
72 hours OR M.2 Reduce THERMAL POWER to < P-7.
Flow - Low channel      One channel may be bypassed for inoperable.            up to 12 hours for surveillance testing.
78 hours N. One Reactor Coolant Flow - Low channel inoperable.
N.1           Place channel in trip.           72 hours OR N.2           Reduce THERMAL                   78 hours POWER to < P-7.
--------------------NOTE-------------------
(continued)
One channel may be bypassed for up to 12 hours for surveillance testing.
Watts Bar - Unit 2                      3.3-5 (developmental)                                                                                F
N.1 Place channel in trip.
72 hours OR N.2 Reduce THERMAL POWER to < P-7.
78 hours (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-6 (developmental)
CONDITION                     REQUIRED ACTION                       COMPLETION TIME O. One Low Fluid Oil Pressure --------------------NOTE-------------------
A ACTIONS (continued)
Turbine Trip channel      The inoperable channel may be inoperable.                bypassed for up to 12 hours for surveillance testing of other channels.
CONDITION REQUIRED ACTION COMPLETION TIME O. One Low Fluid Oil Pressure Turbine Trip channel inoperable.
O.1           Place channel in trip.             72 hours OR O.2           Reduce THERMAL                     76 hours POWER to < P-9.
--------------------NOTE-------------------
P. One train inoperable.     --------------------NOTE-------------------
The inoperable channel may be bypassed for up to 12 hours for surveillance testing of other channels.
O.1 Place channel in trip.
72 hours OR O.2 Reduce THERMAL POWER to < P-9.
76 hours P. One train inoperable.  
--------------------NOTE-------------------
One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE.
One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE.
P.1           Restore train to                   24 hours OPERABLE status.
P.1 Restore train to OPERABLE status.
OR P.2           Be in MODE 3.                     30 hours (continued)
24 hours OR P.2 Be in MODE 3.
Watts Bar - Unit 2                          3.3-6 (developmental)                                                                                  A
30 hours (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-7 (developmental)
CONDITION                     REQUIRED ACTION                       COMPLETION TIME Q. One RTB train inoperable. --------------------NOTE-----------------
A ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME Q. One RTB train inoperable.  
--------------------NOTE-----------------
One train may be bypassed for up to 4 hours for surveillance testing, provided the other train is OPERABLE.
One train may be bypassed for up to 4 hours for surveillance testing, provided the other train is OPERABLE.
Q.1           Restore train to                 24 hours OPERABLE status.
Q.1 Restore train to OPERABLE status.
OR Q.2           Be in MODE 3.                     30 hours R. One channel inoperable. R.1           Verify interlock is in           1 hour required state for existing unit conditions.
24 hours OR Q.2 Be in MODE 3.
OR R.2           Be in MODE 3.                     7 hours S. One channel inoperable. S.1           Verify interlock is in           1 hour required state for existing unit conditions.
30 hours R. One channel inoperable.
OR S.2           Be in MODE 2.                     7 hours (continued)
R.1 Verify interlock is in required state for existing unit conditions.
Watts Bar - Unit 2                        3.3-7 (developmental)                                                                                A
1 hour OR R.2 Be in MODE 3.
7 hours S. One channel inoperable.
S.1 Verify interlock is in required state for existing unit conditions.
1 hour OR S.2 Be in MODE 2.
7 hours (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-8 (developmental)
CONDITION                   REQUIRED ACTION                       COMPLETION TIME T. One trip mechanism     T.1           Restore inoperable trip           48 hours inoperable for one RTB.              mechanism to OPERABLE status.
A ACTIONS (continued)
OR T.2.1         Be in MODE 3.                     54 hours AND T.2.2         Open RTB.                         55 hours U. One Steam Generator     --------------------NOTE-------------------
CONDITION REQUIRED ACTION COMPLETION TIME T. One trip mechanism inoperable for one RTB.
Water Level - Low-Low  One channel may be bypassed channel inoperable. for up to 12 hours for surveillance testing.
T.1 Restore inoperable trip mechanism to OPERABLE status.
U.1.1         Place channel in trip.           72 hours AND U.1.2         For the affected                 72 hours protection set, set the Trip Time Delay (Ts) to match the Trip Time Delay (Tm).
48 hours OR T.2.1 Be in MODE 3.
OR U.2           Be in MODE 3.                     78 hours (continued)
54 hours AND T.2.2 Open RTB.
Watts Bar - Unit 2                      3.3-8 (developmental)                                                                              A
55 hours U. One Steam Generator Water Level - Low-Low channel inoperable.
--------------------NOTE-------------------
One channel may be bypassed for up to 12 hours for surveillance testing.
U.1.1 Place channel in trip.
72 hours AND U.1.2 For the affected protection set, set the Trip Time Delay (Ts) to match the Trip Time Delay (Tm).
72 hours OR U.2 Be in MODE 3.
78 hours (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-9 (developmental)
CONDITION                   REQUIRED ACTION                       COMPLETION TIME V. One Vessel T channel   --------------------NOTE-------------------
A ACTIONS (continued)
inoperable.            One channel may be bypassed for up to 12 hours for surveillance testing.
CONDITION REQUIRED ACTION COMPLETION TIME V. One Vessel T channel inoperable.  
V.1          Set the Trip Time Delay          72 hours threshold power level for (Ts) and (Tm) to 0% power.
--------------------NOTE-------------------
OR V.2          Be in MODE 3.                    78 hours W. One channel inoperable. --------------------NOTE-------------------
One channel may be bypassed for up to 12 hours for surveillance testing.
One channel may be bypassed for up to 12 hours for surveillance testing.
W.1           Place channel in trip.           72 hours OR W.2           Be in MODE 3.                     78 hours X. One channel inoperable. --------------------NOTE-------------------
V.1 Set the Trip Time Delay threshold power level for (Ts) and (Tm) to 0% power.
72 hours OR V.2 Be in MODE 3.
78 hours W. One channel inoperable.  
--------------------NOTE-------------------
One channel may be bypassed for up to 12 hours for surveillance testing.
One channel may be bypassed for up to 12 hours for surveillance testing.
X.1           Place channel in trip.           72 hours OR X.2           Reduce THERMAL                   78 hours POWER to < P-7.
W.1 Place channel in trip.
(continued)
72 hours OR W.2 Be in MODE 3.
Watts Bar - Unit 2                      3.3-9 (developmental)                                                                              A
78 hours X. One channel inoperable.
--------------------NOTE-------------------
One channel may be bypassed for up to 12 hours for surveillance testing.
X.1 Place channel in trip.
72 hours OR X.2 Reduce THERMAL POWER to < P-7.
78 hours (continued)  


RTS Instrumentation 3.3.1 ACTIONS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-10 (developmental)
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME Y. One, two or three Turbine                   Y.1         Place channel(s) in trip.             72 hours Stop Valve Closure channels inoperable.                      OR Y.2         Reduce THERMAL                       76 hours POWER to < P-9.
A ACTIONS (continued)
Z. Two RTS Trains inoperable.                 Z.1         Enter LCO 3.0.3.                     Immediately SURVEILLANCE REQUIREMENTS
CONDITION REQUIRED ACTION COMPLETION TIME Y. One, two or three Turbine Stop Valve Closure channels inoperable.
Y.1 Place channel(s) in trip.
72 hours OR Y.2 Reduce THERMAL POWER to < P-9.
76 hours Z. Two RTS Trains inoperable.
Z.1 Enter LCO 3.0.3.
Immediately SURVEILLANCE REQUIREMENTS  
-----------------------------------------------------------NOTE----------------------------------------------------------
-----------------------------------------------------------NOTE----------------------------------------------------------
Refer to Table 3.3.1-1 to determine which SRs apply for each RTS Function.
Refer to Table 3.3.1-1 to determine which SRs apply for each RTS Function.
SURVEILLANCE                                                       FREQUENCY SR 3.3.1.1               Perform CHANNEL CHECK.                                                   12 hours SR 3.3.1.2               -------------------------------NOTES----------------------------
SURVEILLANCE FREQUENCY SR 3.3.1.1 Perform CHANNEL CHECK.
12 hours SR 3.3.1.2  
-------------------------------NOTES----------------------------
: 1. Adjust NIS channel if absolute difference is > 2%.
: 1. Adjust NIS channel if absolute difference is > 2%.
: 2. Required to be performed within 12 hours after THERMAL POWER is 15% RTP.
: 2. Required to be performed within 12 hours after THERMAL POWER is 15% RTP.
Compare results of calorimetric heat balance                             24 hours calculation to Nuclear Instrumentation System (NIS) channel output.
Compare results of calorimetric heat balance calculation to Nuclear Instrumentation System (NIS) channel output.
(continued)
24 hours (continued)  
Watts Bar - Unit 2                                          3.3-10 (developmental)                                                                                                              A


RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-11 (developmental)
SURVEILLANCE                                                 FREQUENCY SR 3.3.1.3         -------------------------------NOTES----------------------------
G SURVEILLANCE REQUIREMENTS (continued)
: 1. Adjust NIS channel if absolute difference is 3%.
SURVEILLANCE FREQUENCY SR 3.3.1.3  
: 2. Required to be performed within 96 hours after THERMAL POWER is 25% RTP.
-------------------------------NOTES----------------------------
Compare results of the PDMS measurements to                           31 effective full NIS AFD.                                                              power days (EFPD)
: 1. Adjust NIS channel if absolute difference is 3%.
SR 3.3.1.4         -------------------------------NOTE------------------------------
: 2. Required to be performed within 96 hours after THERMAL POWER is 25% RTP.
Compare results of the PDMS measurements to NIS AFD.
31 effective full power days (EFPD)
SR 3.3.1.4  
-------------------------------NOTE------------------------------
This Surveillance must be performed on the reactor trip bypass breaker prior to placing the bypass breaker in service.
This Surveillance must be performed on the reactor trip bypass breaker prior to placing the bypass breaker in service.
Perform TADOT.                                                       62 days on a STAGGERED TEST BASIS SR 3.3.1.5         Perform ACTUATION LOGIC TEST.                                         92 days on a STAGGERED TEST BASIS SR 3.3.1.6         -------------------------------NOTE------------------------------
Perform TADOT.
Required to be performed within 6 days after THERMAL POWER is 50% RTP.
62 days on a STAGGERED TEST BASIS SR 3.3.1.5 Perform ACTUATION LOGIC TEST.
Calibrate excore channels to agree with the PDMS                     92 EFPD measurements.
92 days on a STAGGERED TEST BASIS SR 3.3.1.6  
(continued)
-------------------------------NOTE------------------------------
Watts Bar - Unit 2                                    3.3-11 (developmental)                                                                                              G
Required to be performed within 6 days after THERMAL POWER is 50% RTP.
Calibrate excore channels to agree with the PDMS measurements.
92 EFPD (continued)  


RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-12 (developmental)
SURVEILLANCE                                                   FREQUENCY SR 3.3.1.7         -------------------------------NOTE------------------------------
A SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.1.7  
-------------------------------NOTE------------------------------
For Functions 2 and 3 (Power Range Instrumentation), this Surveillance shall include verification that interlock P-10 is in the required state for existing unit conditions.
For Functions 2 and 3 (Power Range Instrumentation), this Surveillance shall include verification that interlock P-10 is in the required state for existing unit conditions.
Perform COT.                                                         184 days SR 3.3.1.8         -------------------------------NOTES----------------------------      ----------NOTE---------
Perform COT.
: 1. Not required to be performed for Source Range                     Only required when instrumentation prior to entering MODE 3 from                   not performed within MODE 2 until 4 hours after entry into MODE 3.                   previous 31 days
184 days SR 3.3.1.8  
: 2. This Surveillance shall include verification that interlock P-6 is in the required state for existing unit conditions.
-------------------------------NOTES----------------------------
Perform COT.                                                         Prior to reactor startup AND Four hours after reducing power below P-10 for intermediate range instrumentation AND Four hours after reducing power below P-6 for source range instrumentation AND Every 31 days thereafter (continued)
: 1.
Watts Bar - Unit 2                                    3.3-12 (developmental)                                                                                                    A
Not required to be performed for Source Range instrumentation prior to entering MODE 3 from MODE 2 until 4 hours after entry into MODE 3.
: 2.
This Surveillance shall include verification that interlock P-6 is in the required state for existing unit conditions.  
----------NOTE---------
Only required when not performed within previous 31 days Perform COT.
Prior to reactor startup AND Four hours after reducing power below P-10 for intermediate range instrumentation AND Four hours after reducing power below P-6 for source range instrumentation AND Every 31 days thereafter (continued)  


RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-13 (developmental)
SURVEILLANCE                                                 FREQUENCY SR 3.3.1.9         -------------------------------NOTE------------------------------
A SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.1.9  
-------------------------------NOTE------------------------------
Verification of setpoint is not required.
Verification of setpoint is not required.
Perform TADOT.                                                       92 days SR 3.3.1.10       -------------------------------NOTE------------------------------
Perform TADOT.
92 days SR 3.3.1.10  
-------------------------------NOTE------------------------------
This Surveillance shall include verification that the time constants are adjusted to the prescribed values.
This Surveillance shall include verification that the time constants are adjusted to the prescribed values.
Perform CHANNEL CALIBRATION.                                         18 months SR 3.3.1.11       -------------------------------NOTE------------------------------
Perform CHANNEL CALIBRATION.
18 months SR 3.3.1.11  
-------------------------------NOTE------------------------------
Neutron detectors are excluded from CHANNEL CALIBRATION.
Neutron detectors are excluded from CHANNEL CALIBRATION.
Perform CHANNEL CALIBRATION.                                         18 months SR 3.3.1.12       Perform COT.                                                         18 months SR 3.3.1.13       -------------------------------NOTE------------------------------
Perform CHANNEL CALIBRATION.
18 months SR 3.3.1.12 Perform COT.
18 months SR 3.3.1.13  
-------------------------------NOTE------------------------------
Verification of setpoint is not required.
Verification of setpoint is not required.
Perform TADOT.                                                       18 months (continued)
Perform TADOT.
Watts Bar - Unit 2                                    3.3-13 (developmental)                                                                                            A
18 months (continued)  


RTS Instrumentation 3.3.1 SURVEILLANCE REQUIREMENTS (continued)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-14 (developmental)
SURVEILLANCE                                                 FREQUENCY SR 3.3.1.14       -------------------------------NOTE------------------------------
AI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.1.14  
-------------------------------NOTE------------------------------
Verification of setpoint is not required.
Verification of setpoint is not required.
Perform TADOT.                                                       Prior to exceeding the P-9 interlock whenever the unit has been in Mode MODE 3, if not performed within the previous 31 days.
Perform TADOT.
SR 3.3.1.15       -------------------------------NOTE------------------------------
Prior to exceeding the P-9 interlock whenever the unit has been in Mode MODE 3, if not performed within the previous 31 days.
SR 3.3.1.15  
-------------------------------NOTE------------------------------
Neutron detectors are excluded from response time testing.
Neutron detectors are excluded from response time testing.
Verify RTS RESPONSE TIME is within limits.                           18 months on a STAGGERED TEST BASIS Watts Bar - Unit 2                                    3.3-14 (developmental)                                                                                              AI
Verify RTS RESPONSE TIME is within limits.
18 months on a STAGGERED TEST BASIS  


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 1 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-15 (developmental)
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER                                                                                           NOMINAL SPECIFIED           REQUIRED                           SURVEILLANCE        ALLOWABLE                TRIP FUNCTION              CONDITIONS            CHANNELS       CONDITIONS           REQUIREMENTS           VALUE             SETPOINT
F Table 3.3.1-1 (page 1 of 9)
: 1. Manual Reactor Trip                 1, 2             2                 B             SR 3.3.1.13               NA                   NA 3 (a), 4 (a), 5 (a)     2                 C             SR 3.3.1.13               NA                   NA
Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: 2. Power Range Neutron Flux
: 1.
: a. High                         1, 2             4                 D             SR 3.3.1.1         111.4% RTP           109% RTP SR 3.3.1.2 SR 3.3.1.7 (b)(c)
Manual Reactor Trip 1, 2 2
B SR 3.3.1.13 NA NA 3 (a), 4 (a), 5 (a) 2 C
SR 3.3.1.13 NA NA
: 2.
Power Range Neutron Flux
: a.
High 1, 2 4
D SR 3.3.1.1 111.4% RTP 109% RTP SR 3.3.1.2 SR 3.3.1.7 (b)(c)
SR 3.3.1.11 (b)(c)
SR 3.3.1.11 (b)(c)
SR 3.3.1.15
SR 3.3.1.15
: b. Low                         1 (d), 2           4                 E             SR 3.3.1.1           27.4% RTP           25% RTP SR 3.3.1.7 (b)(c)
: b.
Low 1 (d), 2 4
E SR 3.3.1.1 27.4% RTP 25% RTP SR 3.3.1.7 (b)(c)
SR 3.3.1.11 (b)(c)
SR 3.3.1.11 (b)(c)
SR 3.3.1.15
SR 3.3.1.15
: 3. Power Range Neutron Flux Rate
: 3.
: a. High Positive                 1, 2             4                 E             SR 3.3.1.7 (b)(c)     6.3% RTP             5% RTP Rate                                                                            SR 3.3.1.11 (b)(c)     with time          with time constant            constant 2 sec              2 sec
Power Range Neutron Flux Rate
: b. High Negative Rate - DELETED
: a.
: 4. Intermediate Range             1 (d), 2 (e)         2               F, G             SR 3.3.1.1           40% RTP             25% RTP Neutron Flux                                                                          SR 3.3.1.8 (b)(c)
High Positive Rate 1, 2 4
SR 3.3.1.11 (b)(c) 2 (f)             2                 H             SR 3.3.1.1           40% RTP             25% RTP SR 3.3.1.8 (b)(c)
E SR 3.3.1.7 (b)(c) 6.3% RTP with time constant 2 sec 5% RTP with time constant 2 sec SR 3.3.1.11 (b)(c)
: b.
High Negative Rate - DELETED
: 4.
Intermediate Range Neutron Flux 1 (d), 2 (e) 2 F, G SR 3.3.1.1 40% RTP 25% RTP SR 3.3.1.8 (b)(c)
SR 3.3.1.11 (b)(c) 2 (f) 2 H
SR 3.3.1.1 40% RTP 25% RTP SR 3.3.1.8 (b)(c)
SR 3.3.1.11 (b)(c)
SR 3.3.1.11 (b)(c)
(continued)
(continued)
Line 353: Line 538:
(d) Below the P-10 (Power Range Neutron Flux) interlocks.
(d) Below the P-10 (Power Range Neutron Flux) interlocks.
(e) Above the P-6 (Intermediate Range Neutron Flux) interlocks.
(e) Above the P-6 (Intermediate Range Neutron Flux) interlocks.
(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.
(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.  
Watts Bar - Unit 2                                            3.3-15 (developmental)                                                                                                                        F


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 2 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-16 (developmental)
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER                                                                                           NOMINAL SPECIFIED         REQUIRED                             SURVEILLANCE        ALLOWABLE                TRIP FUNCTION              CONDITIONS          CHANNELS       CONDITIONS           REQUIREMENTS           VALUE             SETPOINT
G Table 3.3.1-1 (page 2 of 9)
: 5. Source Range                       2 (f)             2               I, J           SR 3.3.1.1           1.33 E5 cps         1.0 E5 cps Neutron Flux                                                                          SR 3.3.1.8 (b)(c)
Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
SR 3.3.1.11 (b)(c) 3 (a), 4 (a), 5 (a)     2               J, K           SR 3.3.1.1           1.33 E5 cps         1.0 E5 cps SR 3.3.1.8 (b)(c)
: 5.
Source Range Neutron Flux 2 (f) 2 I, J SR 3.3.1.1 1.33 E5 cps 1.0 E5 cps SR 3.3.1.8 (b)(c)
SR 3.3.1.11 (b)(c) 3 (a), 4 (a), 5 (a) 2 J, K SR 3.3.1.1 1.33 E5 cps 1.0 E5 cps SR 3.3.1.8 (b)(c)
SR 3.3.1.11 (b)(c)
SR 3.3.1.11 (b)(c)
SR 3.3.1.15 3 (g), 4 (g), 5 (g)     1                 L             SR 3.3.1.1               N/A                 N/A SR 3.3.1.11 (b)(c)
SR 3.3.1.15 3 (g), 4 (g), 5 (g) 1 L
: 6. Overtemperature T                 1, 2             4                 W             SR 3.3.1.1             Refer to             Refer to SR 3.3.1.3             Note 1               Note 1 SR 3.3.1.6          (Page 3.3-21)     (Page 3.3-21)
SR 3.3.1.1 N/A N/A SR 3.3.1.11 (b)(c)
: 6.
Overtemperature T 1, 2 4
W SR 3.3.1.1 Refer to Note 1 (Page 3.3-21)
Refer to Note 1 (Page 3.3-21)
SR 3.3.1.3 SR 3.3.1.6 SR 3.3.1.7 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.15
: 7.
Overpower T 1, 2 4
W SR 3.3.1.1 Refer to Note 2 (Page 3.3-22)
Refer to Note 2 (Page 3.3-22)
SR 3.3.1.7 (b)(c)
SR 3.3.1.7 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.15
SR 3.3.1.15
: 7. Overpower T                        1, 2              4                W              SR 3.3.1.1            Refer to            Refer to SR 3.3.1.7 (b)(c)      Note 2              Note 2 SR 3.3.1.10 (b)(c)  (Page 3.3-22)      (Page 3.3-22)
: 8.
SR 3.3.1.15
Pressurizer Pressure
: 8. Pressurizer Pressure
: a.
: a. Low                           1 (h)             4                 X             SR 3.3.1.1           1964.8 psig         1970 psig SR 3.3.1.7 (b)(c)
Low 1 (h) 4 X
SR 3.3.1.1 1964.8 psig 1970 psig SR 3.3.1.7 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.15
SR 3.3.1.15
: b. High                         1, 2             4                 W             SR 3.3.1.1           2390.2 psig         2385 psig SR 3.3.1.7 (b)(c)
: b.
High 1, 2 4
W SR 3.3.1.1 2390.2 psig 2385 psig SR 3.3.1.7 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.15 (continued)
SR 3.3.1.15 (continued)
Line 380: Line 580:
(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.
(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.
(g) With the RTBs open. In this condition, source range Function does not provide reactor trip but does provide indication.
(g) With the RTBs open. In this condition, source range Function does not provide reactor trip but does provide indication.
(h) Above the P-7 (Low Power Reactor Trips Block) interlock.
(h) Above the P-7 (Low Power Reactor Trips Block) interlock.  
Watts Bar - Unit 2                                            3.3-16 (developmental)                                                                                                                        G


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 3 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-17 (developmental)
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER                                                                                           NOMINAL SPECIFIED         REQUIRED                             SURVEILLANCE        ALLOWABLE                TRIP FUNCTION              CONDITIONS          CHANNELS       CONDITIONS           REQUIREMENTS           VALUE             SETPOINT
G Table 3.3.1-1 (page 3 of 9)
: 9. Pressurizer Water                 1 (h)               3                 X             SR 3.3.1.1           92.7% span         92% span Level-High                                                                            SR 3.3.1.7 (b)(c)
Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: 9.
Pressurizer Water Level-High 1 (h) 3 X
SR 3.3.1.1 92.7% span 92% span SR 3.3.1.7 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.10 (b)(c)
: 10. Reactor Coolant Flow -           1 (h)           3 per loop           N             SR 3.3.1.1           89.7% flow           90% flow Low                                                                                    SR 3.3.1.7 (b)(c)
: 10.
Reactor Coolant Flow -
Low 1 (h) 3 per loop N
SR 3.3.1.1 89.7% flow 90% flow SR 3.3.1.7 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.10 (b)(c)
SR 3.3.1.15
SR 3.3.1.15
: 11. Undervoltage RCPs                 1 (h)           1 per bus             M             SR 3.3.1.9             5112 V             5400 V SR 3.3.1.10 (b)(c)
: 11.
Undervoltage RCPs 1 (h) 1 per bus M
SR 3.3.1.9 5112 V 5400 V SR 3.3.1.10 (b)(c)
SR 3.3.1.15
SR 3.3.1.15
: 12. Underfrequency RCPs               1 (h)           1 per bus           M             SR 3.3.1.9             56.9 Hz             57.5 Hz SR 3.3.1.10 (b)(c)
: 12.
Underfrequency RCPs 1 (h) 1 per bus M
SR 3.3.1.9 56.9 Hz 57.5 Hz SR 3.3.1.10 (b)(c)
SR 3.3.1.15 (continued)
SR 3.3.1.15 (continued)
(b) If the as found channel setpoint is outside its predefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(b) If the as found channel setpoint is outside its predefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
(h) Above the P-7 (Low Power Reactor Trips Block) interlock.
(h) Above the P-7 (Low Power Reactor Trips Block) interlock.  
Watts Bar - Unit 2                                            3.3-17 (developmental)                                                                                                                        G


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 4 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-18 (developmental)
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER                                                                                           NOMINAL SPECIFIED         REQUIRED                             SURVEILLANCE        ALLOWABLE                TRIP FUNCTION              CONDITIONS          CHANNELS       CONDITIONS           REQUIREMENTS           VALUE             SETPOINT
G Table 3.3.1-1 (page 4 of 9)
: 13. SG Water Level -                 1, 2               3/SG               U             SR 3.3.1.1           16.4% of       17% of narrow Low-Low                                                                                SR 3.3.1.7 (b)(c)   narrow range        range span SR 3.3.1.10 (b)(c)       span SR 3.3.1.15 Coincident with:
Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
a)   Vessel T                   1, 2                 3               V             SR 3.3.1.7 (b)(c)     Vessel T           Vessel T Equivalent to                                                                    SR 3.3.1.10 (b)(c) variable input    variable input power                                                                                                52.6% RTP            50% RTP 50% RTP With a time                                                                                             1.01 Ts                Ts delay (Ts) if one                                                                                     (Refer to           (Refer to steam generator                                                                                        Note 3,              Note 3, is affected                                                                                          Page 3.3-23)       Page 3.3-23) or A time delay (Tm)                                                                                       1.01 Tm               Tm if two or more                                                                                        (Refer to            (Refer to steam                                                                                                  Note 3,              Note 3, generators are                                                                                      Page 3.3-23)       Page 3.3-23) affected b)   Vessel T                   1, 2                 3               V             SR 3.3.1.7 (b)(c)     Vessel T          Vessel T Equivalent to                                                                    SR 3.3.1.10 (b)(c) variable input     variable input power                                                                                                52.6% RTP           50% RTP
: 13. SG Water Level -
            > 50% RTP with no time delay (Ts and Tm = 0)
Low-Low 1, 2 3/SG U
: 14. Turbine Trip
SR 3.3.1.1 16.4% of narrow range span 17% of narrow range span SR 3.3.1.7 (b)(c)
: a. Low Fluid Oil               1 (i)               3               O                                   38.3 psig           45 psig Pressure                                                                        SR 3.3.1.14
SR 3.3.1.10 (b)(c)
: b. Turbine Stop               1 (i)               4               Y             SR 3.3.1.10           1% open             1% open Valve Closure                                                                    SR 3.3.1.14 (continued)
SR 3.3.1.15 Coincident with:
a)
Vessel T Equivalent to power 50% RTP 1, 2 3
V SR 3.3.1.7 (b)(c)
Vessel T variable input 52.6% RTP Vessel T variable input 50% RTP SR 3.3.1.10 (b)(c)
With a time delay (Ts) if one steam generator is affected 1.01 Ts (Refer to Note 3, Page 3.3-23)
Ts (Refer to Note 3, Page 3.3-23) or A time delay (Tm) if two or more steam generators are affected 1.01 Tm (Refer to Note 3, Page 3.3-23)
Tm (Refer to Note 3, Page 3.3-23) b)
Vessel T Equivalent to power
> 50% RTP with no time delay (Ts and Tm = 0) 1, 2 3
V SR 3.3.1.7 (b)(c)
SR 3.3.1.10 (b)(c)
Vessel T variable input 52.6% RTP Vessel T variable input 50% RTP
: 14.
Turbine Trip
: a.
Low Fluid Oil Pressure 1 (i) 3 O
38.3 psig 45 psig SR 3.3.1.14
: b.
Turbine Stop Valve Closure 1 (i) 4 Y
SR 3.3.1.10 1% open 1% open SR 3.3.1.14 (continued)
(b) If the as found channel setpoint is outside its predefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(b) If the as found channel setpoint is outside its predefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
(i) Above the P-9 (Power Range Neutron Flux) interlock.
(i) Above the P-9 (Power Range Neutron Flux) interlock.  
Watts Bar - Unit 2                                            3.3-18 (developmental)                                                                                                                        G


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 5 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-19 (developmental)
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER                                                                 NOMINAL SPECIFIED         REQUIRED                 SURVEILLANCE  ALLOWABLE          TRIP FUNCTION            CONDITIONS        CHANNELS       CONDITIONS REQUIREMENTS     VALUE       SETPOINT
F Table 3.3.1-1 (page 5 of 9)
: 15. Safety Injection (SI)           1, 2             2 trains         P     SR 3.3.1.13         NA           NA Input from Engineered Safety Feature Actuation System (ESFAS)
Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: 16. Reactor Trip System Interlocks
: 15.
: a. Intermediate Range Neutron Flux, P-6 (1) Enable               2 (f)               2           R       SR 3.3.1.11         NA     1.66E-04%
Safety Injection (SI)
Manual                                                      SR 3.3.1.12                     RTP Block of SR Trip (2) Auto Reset          2 (f)               2           R       SR 3.3.1.11   7.65E-5% 0.47E-4% RTP (Unblock                                                    SR 3.3.1.12       RTP    below setpoint Manual Block of SR Trip)
Input from Engineered Safety Feature Actuation System (ESFAS) 1, 2 2 trains P
: b. Low Power                 1             1 per train       S     SR 3.3.1.11         NA           NA Reactor Trips                                                    SR 3.3.1.12 Block, P-7
SR 3.3.1.13 NA NA
: c. Power Range               1                   4           S     SR 3.3.1.11   50.4% RTP     48% RTP Neutron Flux,                                                    SR 3.3.1.12 P-8
: 16.
: d. Power Range               1                   4           S     SR 3.3.1.11   52.4% RTP     50% RTP Neutron Flux,                                                    SR 3.3.1.12 P-9
Reactor Trip System Interlocks
: e. Power Range             1, 2                 4           R       SR 3.3.1.11   7.6% RTP     10% RTP Neutron Flux,                                                    SR 3.3.1.12       and P-10                                                                            12.4% RTP
: a.
: f. Turbine Impulse           1                   2           S     SR 3.3.1.10     12.4%         10%
Intermediate Range Neutron Flux, P-6 (1) Enable Manual Block of SR Trip 2 (f) 2 R
Pressure, P-13                                                    SR 3.3.1.12   full-power    full-power pressure      pressure (continued)
SR 3.3.1.11 NA 1.66E-04%
(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.
RTP SR 3.3.1.12 (2) Auto Reset (Unblock Manual Block of SR Trip) 2 (f) 2 R
Watts Bar - Unit 2                                        3.3-19 (developmental)                                                                                            F
SR 3.3.1.11 7.65E-5%
RTP 0.47E-4% RTP below setpoint SR 3.3.1.12
: b.
Low Power Reactor Trips Block, P-7 1
1 per train S
SR 3.3.1.11 NA NA SR 3.3.1.12
: c.
Power Range Neutron Flux, P-8 1
4 S
SR 3.3.1.11 50.4% RTP 48% RTP SR 3.3.1.12
: d.
Power Range Neutron Flux, P-9 1
4 S
SR 3.3.1.11 52.4% RTP 50% RTP SR 3.3.1.12
: e.
Power Range Neutron Flux, P-10 1, 2 4
R SR 3.3.1.11 7.6% RTP and 12.4% RTP 10% RTP SR 3.3.1.12
: f.
Turbine Impulse Pressure, P-13 1
2 S
SR 3.3.1.10 12.4%
full-power pressure 10%
full-power pressure SR 3.3.1.12 (continued)
(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.  


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 6 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-20 (developmental)
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER                                                                       NOMINAL SPECIFIED           REQUIRED                         SURVEILLANCE ALLOW-ABLE     TRIP FUNCTION              CONDITIONS            CHANNELS      CONDITIONS        REQUIREMENTS    VALUE    SETPOINT
A Table 3.3.1-1 (page 6 of 9)
: 17. Reactor Trip Breakers               1, 2           2 trains           Q           SR 3.3.1.4       NA           NA (j) 3 (a), 4 (a) , 5 (a)   2 trains           C           SR 3.3.1.4       NA           NA
Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOW-ABLE VALUE NOMINAL TRIP SETPOINT
: 18. Reactor Trip Breaker               1, 2             1 each           T           SR 3.3.1.4       NA           NA Undervoltage and                                    per RTB Shunt Trip Mechanisms                  3 (a), 4 (a) , 5 (a)   1 each           C           SR 3.3.1.4       NA           NA per RTB
: 17.
: 19. Automatic Trip Logic               1, 2           2 trains           P           SR 3.3.1.5       NA           NA 3 (a), 4 (a) , 5 (a)   2 trains           C           SR 3.3.1.5       NA           NA (a) With Reactor Trip Breakers (RTBs) closed and Rod Control System capable of rod withdrawal.
Reactor Trip Breakers (j) 1, 2 2 trains Q
(j) Including any reactor trip bypass breakers that are racked in and closed for bypassing an RTB.
SR 3.3.1.4 NA NA 3 (a), 4 (a), 5 (a) 2 trains C
Watts Bar - Unit 2                                            3.3-20 (developmental)                                                                                                    A
SR 3.3.1.4 NA NA
: 18.
Reactor Trip Breaker Undervoltage and Shunt Trip Mechanisms 1, 2 1 each per RTB T
SR 3.3.1.4 NA NA 3 (a), 4 (a), 5 (a) 1 each per RTB C
SR 3.3.1.4 NA NA
: 19.
Automatic Trip Logic 1, 2 2 trains P
SR 3.3.1.5 NA NA 3 (a), 4 (a), 5 (a) 2 trains C
SR 3.3.1.5 NA NA (a) With Reactor Trip Breakers (RTBs) closed and Rod Control System capable of rod withdrawal.
(j) Including any reactor trip bypass breakers that are racked in and closed for bypassing an RTB.  


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 7 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-21 (developmental)
A Table 3.3.1-1 (page 7 of 9)
Reactor Trip System Instrumentation Note 1: Overtemperature T The Overtemperature T Function Allowable Value shall not exceed the following Trip Setpoint by more than 1.2% of T span.
Reactor Trip System Instrumentation Note 1: Overtemperature T The Overtemperature T Function Allowable Value shall not exceed the following Trip Setpoint by more than 1.2% of T span.
1 + 4 s                  (1 + 1 s)
T 1 + 4s 1 + 5sT0 K1 K2 (1 + 1s)
T            T0 K1  K 2            T T   + K 3 P  P    f1 (I) 1 + 5 s                  (1 + 2 s)
(1 + 2s) T T+ K3P Pf1(I)
Where:   T is measured RCS T, &deg;F.
Where:
T is measured RCS T, &deg;F.
T0 is the indicated T at RTP, &deg;F.
T0 is the indicated T at RTP, &deg;F.
s is the Laplace transform operator, sec-1.
s is the Laplace transform operator, sec-1.
T is the measured RCS average temperature, &deg;F.
T is the measured RCS average temperature, &deg;F.
T is the indicated Tavg at RTP, 588.2&deg;F.
T is the indicated Tavg at RTP, 588.2&deg;F.
P is the measured pressurizer pressure, psig P is the nominal RCS operating pressure, 2235 psig K1 1.16                         K2 0.0183/&deg;F                           K3 = 0.000900/psig 1 33 sec                       2 4 sec 4 3 sec                         5 3 sec f1(I) =     -2.62{22 + (qt - qb)}                 when qt - qb < - 22% RTP 0                                     when -22% RTP qt - qb 10% RTP 1.96{(qt - qb) - 10}                 when qt - qb > 10% RTP Where qt and qb are percent RTP in the upper and lower halves of the core, respectively, and qt + qb is the total THERMAL POWER in percent RTP.
P is the measured pressurizer pressure, psig P is the nominal RCS operating pressure, 2235 psig K1 1.16 K2 0.0183/&deg;F K3 = 0.000900/psig 1 33 sec 2 4 sec 4 3 sec 5 3 sec f1(I) =  
Watts Bar - Unit 2                                  3.3-21 (developmental)                                                                                                A
-2.62{22 + (qt - qb)}
when qt - qb < - 22% RTP 0
when -22% RTP qt - qb 10% RTP 1.96{(qt - qb) - 10}
when qt - qb > 10% RTP Where qt and qb are percent RTP in the upper and lower halves of the core, respectively, and qt + qb is the total THERMAL POWER in percent RTP.  


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 8 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-22 (developmental)
AI Table 3.3.1-1 (page 8 of 9)
Reactor Trip System Instrumentation Note 2: Overpower T The Overpower T Function Allowable Value shall not exceed the following Trip Setpoint by more than 1.0% of T span.
Reactor Trip System Instrumentation Note 2: Overpower T The Overpower T Function Allowable Value shall not exceed the following Trip Setpoint by more than 1.0% of T span.
1+4 s                  (3 s)
T 1+4s 1+5sT0 K4-K5 (3s)
T          T0 K 4 -K 5          [T]+K 6 T-T '' -f2 (I) 1+5 s                  (1+3 s)
(1+3s) [T]+K6T-T''-f2(I)
Where:   T is measured RCS T, &deg;F.
Where:
T is measured RCS T, &deg;F.
T0 is the indicated T at RTP, &deg;F.
T0 is the indicated T at RTP, &deg;F.
s is the Laplace transform operator, sec-1.
s is the Laplace transform operator, sec-1.
T is the measured RCS average temperature, &deg;F.
T is the measured RCS average temperature, &deg;F.
T is the indicated Tavg at RTP, 588.2&deg;F.
T is the indicated Tavg at RTP, 588.2&deg;F.
K4 1.10       K5     0.02/&deg;F for increasing Tavg             K6 0.00162/&deg;F when T > T 0/&deg;F for decreasing Tavg                     0/&deg;F when T T 3 5 sec       4     3 sec                                   5   3 sec f2(I) = 0 for all I.
K4 1.10 K5 0.02/&deg;F for increasing Tavg K6 0.00162/&deg;F when T > T 0/&deg;F for decreasing Tavg 0/&deg;F when T T 3 5 sec 4
Watts Bar - Unit 2                                3.3-22 (developmental)                                                                                      AI
3 sec 5
3 sec f2(I) = 0 for all I.  


RTS Instrumentation 3.3.1 Table 3.3.1-1 (page 9 of 9)
RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-23 (developmental)
A Table 3.3.1-1 (page 9 of 9)
Reactor Trip System Instrumentation NOTE 3: Steam Generator Water Level Low-Low Trip Time Delay:
Reactor Trip System Instrumentation NOTE 3: Steam Generator Water Level Low-Low Trip Time Delay:
Ts = A(P)3 + B(P)2 + C(P)+ D Tm = E(P)3 + F(P)2 + G(P)+ H Where:
Ts = A(P)3 + B(P)2+ C(P)+ D Tm = E(P)3 + F(P)2+ G(P)+ H Where:
P   = Vessel T Equivalent to power (% RTP), P 50% RTP Ts   = Time Delay for Steam Generator Water Level - Low Low Reactor Trip, one Steam Generator affected.
P  
Tm   = Time Delay for Steam Generator Water Level - Low Low Reactor Trip, two or more Steam Generators affected.
= Vessel T Equivalent to power (% RTP), P 50% RTP Ts  
A     = -0.0085041 B     = 0.9266400 C     = -33.85998 D     = 474.6060 E     = -0.0047421 F     = 0.5682600 G     = -23.70753 H     = 357.9840 Watts Bar - Unit 2                          3.3-23 (developmental)                                                                          A
= Time Delay for Steam Generator Water Level - Low Low Reactor Trip, one Steam Generator affected.
Tm  
= Time Delay for Steam Generator Water Level - Low Low Reactor Trip, two or more Steam Generators affected.
A  
= -0.0085041 B  
= 0.9266400 C  
= -33.85998 D  
= 474.6060 E  
= -0.0047421 F  
= 0.5682600 G  
= -23.70753 H  
= 357.9840  


ESFAS Instrumentation 3.3.2 3.3 INSTRUMENTATION 3.3.2 Engineered Safety Feature Actuation System (ESFAS) Instrumentation LCO 3.3.2                   The ESFAS instrumentation for each Function in Table 3.3.2-1 shall be OPERABLE.
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-24 (developmental)
APPLICABILITY:             According to Table 3.3.2-1.
AI 3.3 INSTRUMENTATION 3.3.2 Engineered Safety Feature Actuation System (ESFAS) Instrumentation LCO 3.3.2 The ESFAS instrumentation for each Function in Table 3.3.2-1 shall be OPERABLE.
ACTIONS
APPLICABILITY:
According to Table 3.3.2-1.
ACTIONS  
-----------------------------------------------------------NOTE----------------------------------------------------------
-----------------------------------------------------------NOTE----------------------------------------------------------
Separate Condition entry is allowed for each Function.
Separate Condition entry is allowed for each Function.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One or more Functions with                 A.1           Enter the Condition                   Immediately one or more required                                  referenced in channels or trains                                    Table 3.3.2-1 for the inoperable.                                            channel(s) or train(s).
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more Functions with one or more required channels or trains inoperable.
B. One channel or train                       B.1           Restore channel or train             48 hours inoperable.                                            to OPERABLE status.
A.1 Enter the Condition referenced in Table 3.3.2-1 for the channel(s) or train(s).
OR B.2.1         Be in MODE 3.                         54 hours AND B.2.2         Be in Mode MODE 5.                   84 hours (continued)
Immediately B. One channel or train inoperable.
Watts Bar - Unit 2                                        3.3-24 (developmental)                                                                                                              AI
B.1 Restore channel or train to OPERABLE status.
48 hours OR B.2.1 Be in MODE 3.
54 hours AND B.2.2 Be in Mode MODE 5.
84 hours (continued)  


ESFAS Instrumentation 3.3.2 ACTIONS (continued)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-25 (developmental)
CONDITION               REQUIRED ACTION                       COMPLETION TIME C. One train inoperable. C.1     -------------NOTE------------
AI ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME C. One train inoperable.
C.1  
-------------NOTE------------
One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE.
One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE.
Restore train to                   24 hours OPERABLE status.
Restore train to OPERABLE status.
OR C.2.1   Be in Mode MODE 3.                 30 hours AND C.2.2   Be in Mode MODE 5.                 60 hours D. One channel inoperable. D.1     -------------NOTE------------
24 hours OR C.2.1 Be in Mode MODE 3.
30 hours AND C.2.2 Be in Mode MODE 5.
60 hours D. One channel inoperable.
D.1  
-------------NOTE------------
One channel may be bypassed for up to 12 hours for surveillance testing.
One channel may be bypassed for up to 12 hours for surveillance testing.
Place channel in trip.             72 hours OR D.2.1   Be in Mode MODE 3.                 78 hours AND D.2.2   Be in Mode MODE 4.                 84 hours (continued)
Place channel in trip.
Watts Bar - Unit 2                3.3-25 (developmental)                                                                          AI
72 hours OR D.2.1 Be in Mode MODE 3.
78 hours AND D.2.2 Be in Mode MODE 4.
84 hours (continued)  


ESFAS Instrumentation 3.3.2 ACTIONS (continued)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-26 (developmental)
CONDITION               REQUIRED ACTION                       COMPLETION TIME E. One Containment Pressure E.1     -------------NOTE------------
AI ACTIONS (continued)
channel inoperable.              One channel may be bypassed for up to 12 hours for surveillance testing.
CONDITION REQUIRED ACTION COMPLETION TIME E. One Containment Pressure channel inoperable.
Place channel in bypass.           72 hours OR E.2.1   Be in Mode MODE 3.                 78 hours AND E.2.2   Be in Mode MODE 4.                 84 hours F. One channel or train     F.1     Restore channel or train           48 hours inoperable.                      to OPERABLE status.
E.1  
OR F.2.1   Be in MODE 3.                       54 hours AND F.2.2   Be in Mode MODE 4.                 60 hours (continued)
-------------NOTE------------
Watts Bar - Unit 2                  3.3-26 (developmental)                                                                            AI
One channel may be bypassed for up to 12 hours for surveillance testing.
Place channel in bypass.
72 hours OR E.2.1 Be in Mode MODE 3.
78 hours AND E.2.2 Be in Mode MODE 4.
84 hours F. One channel or train inoperable.
F.1 Restore channel or train to OPERABLE status.
48 hours OR F.2.1 Be in MODE 3.
54 hours AND F.2.2 Be in Mode MODE 4.
60 hours (continued)  


ESFAS Instrumentation 3.3.2 ACTIONS (continued)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-27 (developmental)
CONDITION             REQUIRED ACTION                       COMPLETION TIME G. One train inoperable. G.1     -------------NOTE------------
AI ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME G. One train inoperable.
G.1  
-------------NOTE------------
One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE.
One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE.
Restore train to                   24 hours OPERABLE status.
Restore train to OPERABLE status.
OR G.2.1   Be in Mode MODE 3.                 30 hours AND G.2.2   Be in Mode MODE 4.                 36 hours H. One train inoperable. H.1     -------------NOTE------------
24 hours OR G.2.1 Be in Mode MODE 3.
30 hours AND G.2.2 Be in Mode MODE 4.
36 hours H. One train inoperable.
H.1  
-------------NOTE------------
One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE.
One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE.
Restore train to                   24 hours OPERABLE status.
Restore train to OPERABLE status.
OR H.2.1   Be in Mode MODE 3.                 30 hours AND H.2.2   Be in Mode MODE 4.                 36 hours (continued)
24 hours OR H.2.1 Be in Mode MODE 3.
Watts Bar - Unit 2              3.3-27 (developmental)                                                                        AI
30 hours AND H.2.2 Be in Mode MODE 4.
36 hours (continued)  


ESFAS Instrumentation 3.3.2 ACTIONS (continued)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-28 (developmental)
CONDITION                   REQUIRED ACTION                       COMPLETION TIME I. One Steam Generator       I.1      -------------NOTE------------
BI ACTIONS (continued)
Water Level - High High             One channel may be channel inoperable.                  bypassed for up to 12 hours for surveillance testing.
CONDITION REQUIRED ACTION COMPLETION TIME I. One Steam Generator Water Level - High High channel inoperable.
Place channel in trip.              72 hours OR I.2.1    Be in Mode MODE 3.                  78 hours AND I.2.2    Be in Mode MODE 4.                  84 hours J. One or more Turbine Driven J.1       Restore channel to                  48 hours Main Feedwater Pump trip            OPERABLE status.
I.1  
channel(s) inoperable.
-------------NOTE------------
OR J.2      Be in Mode MODE 3.                  54 hours K. One channel inoperable. K.1      -------------NOTE------------
One channel may be bypassed for up to 12 hours for surveillance testing.
One channel may be bypassed for up to 12 hours for surveillance testing.
Place channel in bypass.           72 hours OR K.2.1     Be in Mode MODE 3.                 78 hours AND K.2.2     Be in Mode MODE 5.                 108 hours (continued)
Place channel in trip.
Watts Bar - Unit 2                     3.3-28 (developmental)                                                                                 BI
72 hours OR I.2.1 Be in Mode MODE 3.
78 hours AND I.2.2 Be in Mode MODE 4.
84 hours J. One or more Turbine Driven Main Feedwater Pump trip channel(s) inoperable.
J.1 Restore channel to OPERABLE status.
48 hours OR J.2 Be in Mode MODE 3.
54 hours K. One channel inoperable.
K.1
-------------NOTE------------
One channel may be bypassed for up to 12 hours for surveillance testing.
Place channel in bypass.
72 hours OR K.2.1 Be in Mode MODE 3.
78 hours AND K.2.2 Be in Mode MODE 5.
108 hours (continued)  


ESFAS Instrumentation 3.3.2 ACTIONS (continued)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-29 (developmental)
CONDITION                     REQUIRED ACTION                       COMPLETION TIME L. One P-11 interlock channel L.1           Verify interlock is in             1 hour inoperable.                              required state for existing unit condition.
AI ACTIONS (continued)
OR L.2.1         Be in Mode MODE 3.                 7 hours AND L.2.2         Be in Mode MODE 4.                 13 hours M. One Steam Generator       --------------------NOTE-------------------
CONDITION REQUIRED ACTION COMPLETION TIME L. One P-11 interlock channel inoperable.
Water Level - Low-Low      One channel may be bypassed for channel inoperable.        up to 12 hours for surveillance testing.
L.1 Verify interlock is in required state for existing unit condition.
M.1.1         Place channel in trip.             72 hours AND M.1.2         For the affected                   72 hours protection set, set the Trip Time Delay (Ts) to match the Trip Time Delay (Tm).
1 hour OR L.2.1 Be in Mode MODE 3.
OR M.2.1         Be in Mode MODE 3.                 78 hours AND M.2.2         Be in Mode MODE 4.                 84 hours (continued)
7 hours AND L.2.2 Be in Mode MODE 4.
Watts Bar - Unit 2                        3.3-29 (developmental)                                                                                  AI
13 hours M. One Steam Generator Water Level - Low-Low channel inoperable.
--------------------NOTE-------------------
One channel may be bypassed for up to 12 hours for surveillance testing.
M.1.1 Place channel in trip.
72 hours AND M.1.2 For the affected protection set, set the Trip Time Delay (Ts) to match the Trip Time Delay (Tm).
72 hours OR M.2.1 Be in Mode MODE 3.
78 hours AND M.2.2 Be in Mode MODE 4.
84 hours (continued)  


ESFAS Instrumentation 3.3.2 ACTIONS (continued)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-30 (developmental)
CONDITION                 REQUIRED ACTION                         COMPLETION TIME N. One Vessel T channel --------------------NOTE-------------------
AI ACTIONS (continued)
inoperable.          One channel may be bypassed for up to 12 hours for surveillance testing.
CONDITION REQUIRED ACTION COMPLETION TIME N. One Vessel T channel inoperable.
N.1           Set the Trip Time Delay             72 hours threshold power level for (Ts) and (Tm) to 0%
--------------------NOTE-------------------
One channel may be bypassed for up to 12 hours for surveillance testing.
N.1 Set the Trip Time Delay threshold power level for (Ts) and (Tm) to 0%
power.
power.
OR N.2           Be in MODE 3.                       78 hours O. One MSVV Room Water   --------------------NOTE-------------------
72 hours OR N.2 Be in MODE 3.
Level High channel    The inoperable channel may be inoperable.          bypassed for up to 12 hours for surveillance testing of other channels.
78 hours O. One MSVV Room Water Level High channel inoperable.
O.1           Place channel in trip.             72 hours OR O.2           Be in MODE 3.                       78 hours Watts Bar - Unit 2                    3.3-30 (developmental)                                                                              AI
--------------------NOTE-------------------
The inoperable channel may be bypassed for up to 12 hours for surveillance testing of other channels.
O.1 Place channel in trip.
72 hours OR O.2 Be in MODE 3.
78 hours  


ESFAS Instrumentation 3.3.2 SURVEILLANCE REQUIREMENTS
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-31 (developmental)
B SURVEILLANCE REQUIREMENTS  
-----------------------------------------------------------NOTE----------------------------------------------------------
-----------------------------------------------------------NOTE----------------------------------------------------------
Refer to Table 3.3.2-1 to determine which SRs apply for each ESFAS Function.
Refer to Table 3.3.2-1 to determine which SRs apply for each ESFAS Function.
SURVEILLANCE                                                       FREQUENCY SR 3.3.2.1               Perform CHANNEL CHECK.                                                   12 hours SR 3.3.2.2               Perform ACTUATION LOGIC TEST.                                             92 days on a STAGGERED TEST BASIS SR 3.3.2.3               Perform MASTER RELAY TEST.                                               92 days on a STAGGERED TEST BASIS SR 3.3.2.4               Perform COT.                                                             184 days SR 3.3.2.5               -------------------------------NOTE------------------------------
SURVEILLANCE FREQUENCY SR 3.3.2.1 Perform CHANNEL CHECK.
12 hours SR 3.3.2.2 Perform ACTUATION LOGIC TEST.
92 days on a STAGGERED TEST BASIS SR 3.3.2.3 Perform MASTER RELAY TEST.
92 days on a STAGGERED TEST BASIS SR 3.3.2.4 Perform COT.
184 days SR 3.3.2.5  
-------------------------------NOTE------------------------------
Slave relays tested by SR 3.3.2.7 are excluded from this surveillance.
Slave relays tested by SR 3.3.2.7 are excluded from this surveillance.
Perform SLAVE RELAY TEST.                                                 92 days OR 18 months for Westinghouse type AR and Potter &
Perform SLAVE RELAY TEST.
Brumfield MDR Series relays (continued)
92 days OR 18 months for Westinghouse type AR and Potter &
Watts Bar - Unit 2                                          3.3-31 (developmental)                                                                                                              B
Brumfield MDR Series relays (continued)  


ESFAS Instrumentation 3.3.2 SURVEILLANCE REQUIREMENTS (continued)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-32 (developmental)
SURVEILLANCE                                                 FREQUENCY SR 3.3.2.6         -------------------------------NOTE------------------------------
FI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.2.6  
-------------------------------NOTE------------------------------
Verification of relay setpoints not required.
Verification of relay setpoints not required.
Perform TADOT.                                                         92 days SR 3.3.2.7         Perform SLAVE RELAY TEST on slave relays                               18 months K603A, K603B, K604A, K604B, K607A, K607B, K609A, K609B, K612A, K625A, and K625B, SR 3.3.2.8         -------------------------------NOTE------------------------------
Perform TADOT.
92 days SR 3.3.2.7 Perform SLAVE RELAY TEST on slave relays K603A, K603B, K604A, K604B, K607A, K607B, K609A, K609B, K612A, K625A, and K625B, 18 months SR 3.3.2.8  
-------------------------------NOTE------------------------------
Verification of setpoint not required for manual initiation.
Verification of setpoint not required for manual initiation.
Perform TADOT.                                                         18 months SR 3.3.2.9         -------------------------------NOTE------------------------------
Perform TADOT.
18 months SR 3.3.2.9  
-------------------------------NOTE------------------------------
This Surveillance shall include verification that the time constants are adjusted to the prescribed values.
This Surveillance shall include verification that the time constants are adjusted to the prescribed values.
Perform CHANNEL CALIBRATION.                                           18 months SR 3.3.2.10       -------------------------------NOTE------------------------------
Perform CHANNEL CALIBRATION.
18 months SR 3.3.2.10  
-------------------------------NOTE------------------------------
Not required to be performed for the turbine driven AFW pump until 24 hours after > 1092 psig in the steam generator.
Not required to be performed for the turbine driven AFW pump until 24 hours after > 1092 psig in the steam generator.
Verify ESFAS RESPONSE TIMES are within limit.                         18 months on a STAGGERED TEST BASIS SR 3.3.2.11       -------------------------------NOTE------------------------------
Verify ESFAS RESPONSE TIMES are within limit.
18 months on a STAGGERED TEST BASIS SR 3.3.2.11  
-------------------------------NOTE------------------------------
Verification of setpoint not required.
Verification of setpoint not required.
Perform TADOT.                                                         Once per reactor trip breaker cycle Watts Bar - Unit 2                                    3.3-32 (developmental)                                                                                              FI
Perform TADOT.
Once per reactor trip breaker cycle  


ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 1 of 8)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-33 (developmental)
Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER                                                                                             NOMINAL SPECIFIED         REQUIRED                             SURVEILLANCE          ALLOWABLE              TRIP FUNCTION              CONDITIONS          CHANNELS       CONDITIONS           REQUIREMENTS             VALUE           SETPOINT
FI Table 3.3.2-1 (page 1 of 8)
: 1. Safety Injection
Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: a. Manual Initiation       1, 2, 3, 4               2               B             SR 3.3.2.8                 NA                 NA
: 1.
: b. Automatic               1, 2, 3, 4           2 trains           C             SR 3.3.2.2                 NA                 NA Actuation Logic                                                                SR 3.3.2.3 and Actuation                                                                  SR 3.3.2.5 Relays                                                                          SR 3.3.2.7
Safety Injection
: c. Containment             1, 2, 3                 3               D             SR 3.3.2.1               1.6 psig         1.5 psig Pressure - High                                                                SR 3.3.2.4 (b) (c)
: a.
Manual Initiation 1, 2, 3, 4 2
B SR 3.3.2.8 NA NA
: b.
Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C
SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5 SR 3.3.2.7
: c.
Containment Pressure - High 1, 2, 3 3
D SR 3.3.2.1 1.6 psig 1.5 psig SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10
SR 3.3.2.10
: d. Pressurizer             1, 2, 3(a)               3               D             SR 3.3.2.1           > 1864.8 psig       1870 psig Pressure - Low                                                                  SR 3.3.2.4 (b) (c)
: d.
Pressurizer Pressure - Low 1, 2, 3(a) 3 D
SR 3.3.2.1  
> 1864.8 psig 1870 psig SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10
SR 3.3.2.10
: e. Steam Line             1, 2, 3(a)           3 per             D             SR 3.3.2.1           > 666.6(d) psi     675(d) psig Pressure - Low                            steam line                          SR 3.3.2.4 (b) (c)   g SR 3.3.2.9 (b) (c)
: e.
Steam Line Pressure - Low 1, 2, 3(a) 3 per steam line D
SR 3.3.2.1  
> 666.6(d) psi g
675(d) psig SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10
SR 3.3.2.10
: 2. Containment Spray
: 2.
: a. Manual Initiation       1, 2, 3, 4         2 per train,         B             SR 3.3.2.8                 NA                 NA 2 trains
Containment Spray
: b. Automatic               1, 2, 3, 4           2 trains           C             SR 3.3.2.2                 NA                 NA Actuation Logic                                                                SR 3.3.2.3 and Actuation                                                                  SR 3.3.2.5 Relays
: a.
: c. Containment             1, 2, 3                 4               E             SR 3.3.2.1             < 2.9 psig         2.8 psig Pressure -                                                                      SR 3.3.2.4 (b) (c)
Manual Initiation 1, 2, 3, 4 2 per train, 2 trains B
High High                                                                      SR 3.3.2.9 (b) (c)
SR 3.3.2.8 NA NA
SR 3.3.2.10 (a) Above the P-11 (Pressurizer Pressure) Interlock.
: b.
(b) If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5
(d) Time constants used in the lead/lag controller are t1 > 50 seconds and t2 < 5 seconds.
: c.
(continued)
Containment Pressure -
Watts Bar - Unit 2                                              3.3-33 (developmental)                                                                                                                        FI
High High 1, 2, 3 4
E SR 3.3.2.1  
< 2.9 psig 2.8 psig SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10 (a)
Above the P-11 (Pressurizer Pressure) Interlock.
(b)
If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(c)
The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
(d)
Time constants used in the lead/lag controller are t1 > 50 seconds and t2 < 5 seconds.
(continued)  


ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 2 of 8)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-34 (developmental)
Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER                                                                                             NOMINAL SPECIFIED         REQUIRED                               SURVEILLANCE          ALLOWABLE            TRIP FUNCTION              CONDITIONS          CHANNELS         CONDITIONS           REQUIREMENTS             VALUE         SETPOINT
FI Table 3.3.2-1 (page 2 of 8)
: 3. Containment Isolation
Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: a. Phase A Isolation
: 3.
: 1)   Manual             1, 2, 3, 4               2                 B             SR 3.3.2.8                 NA               NA Initiation
Containment Isolation
: 2)   Automatic         1, 2, 3, 4           2 trains             C             SR 3.3.2.2                 NA               NA Actuation                                                                    SR 3.3.2.3 Logic and                                                                    SR 3.3.2.5 Actuation                                                                    SR 3.3.2.7 Relays
: a.
: 3)   Safety         Refer to Function 1 (Safety Injection) for all initiation functions and requirements.
Phase A Isolation
Injection
: 1)
: b. Phase B Isolation
Manual Initiation 1, 2, 3, 4 2
: 1)   Manual             1, 2, 3, 4         2 per train,           B             SR 3.3.2.8                 NA               NA Initiation                              2 trains
B SR 3.3.2.8 NA NA
: 2)   Automatic         1, 2, 3, 4           2 trains             C             SR 3.3.2.2                 NA               NA Actuation                                                                    SR 3.3.2.3 Logic and                                                                    SR 3.3.2.5 Actuation                                                                    SR 3.3.2.7 Relays
: 2)
: 3)   Containment         1, 2, 3                 4                 E             SR 3.3.2.1             < 2.9 psig       2.8 psig Pressure -                                                                  SR 3.3.2.4 (b) (c)
Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C
High High                                                                    SR 3.3.2.9 (b) (c)
SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5 SR 3.3.2.7
: 3)
Safety Injection Refer to Function 1 (Safety Injection) for all initiation functions and requirements.
: b.
Phase B Isolation
: 1)
Manual Initiation 1, 2, 3, 4 2 per train, 2 trains B
SR 3.3.2.8 NA NA
: 2)
Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C
SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5 SR 3.3.2.7
: 3)
Containment Pressure -
High High 1, 2, 3 4
E SR 3.3.2.1  
< 2.9 psig 2.8 psig SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10 (continued)
SR 3.3.2.10 (continued)
(b) If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(b)
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
Watts Bar - Unit 2                                              3.3-34 (developmental)                                                                                                                        FI
(c)
The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.  


ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 3 of 8)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-35 (developmental)
Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER                                                                                           NOMINAL SPECIFIED           REQUIRED                             SURVEILLANCE          ALLOWABLE              TRIP FUNCTION              CONDITIONS          CHANNELS         CONDITIONS       REQUIREMENTS               VALUE           SETPOINT
FI Table 3.3.2-1 (page 3 of 8)
: 4. Steam Line Isolation
Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: a. Manual Initiation       1, 2 (e), 3 (e)       1/valve             F             SR 3.3.2.8                 NA                 NA (e)    (e)
: 4.
: b. Automatic               1, 2     ,3           2 trains             G             SR 3.3.2.2                 NA                 NA Actuation Logic                                                                  SR 3.3.2.3 and Actuation                                                                    SR 3.3.2.5 Relays
Steam Line Isolation
: c. Containment             1, 2 (e), 3 (e)           4               E             SR 3.3.2.1             < 2.9 psig         2.8 psig Pressure -                                                                      SR 3.3.2.4 (b) (c)
: a.
High High                                                                        SR 3.3.2.9 (b) (c)
Manual Initiation 1, 2 (e), 3 (e) 1/valve F
SR 3.3.2.8 NA NA
: b.
Automatic Actuation Logic and Actuation Relays 1, 2 (e), 3 (e) 2 trains G
SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5
: c.
Containment Pressure -
High High 1, 2 (e), 3 (e) 4 E
SR 3.3.2.1  
< 2.9 psig 2.8 psig SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10
SR 3.3.2.10
: d. Steam Line Pressure
: d.
: 1)   Low               1, 2 (e), 3 (a)(e)     3 per               D             SR 3.3.2.1             > 666.6         675 (d) psig (d) steam line                          SR 3.3.2.4 (b) (c)           psig SR 3.3.2.9 (b) (c)
Steam Line Pressure
: 1)
Low 1, 2 (e), 3 (a)(e) 3 per steam line D
SR 3.3.2.1  
> 666.6 (d) psig 675 (d) psig SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10
SR 3.3.2.10
: 2)   Negative             3 (e)(f)           3 per               D             SR 3.3.2.1           < 108.5 (g) psi     100 (g) psi Rate - High                            steam line                          SR 3.3.2.4 (b) (c)
: 2)
Negative Rate - High 3 (e)(f) 3 per steam line D
SR 3.3.2.1  
< 108.5 (g) psi 100 (g) psi SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10 (continued)
SR 3.3.2.10 (continued)
(b) If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(b)
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(d) Time constants used in the lead/lag controller are t1 > 50 seconds and t2 < 5 seconds.
(c)
(e) Except when all MSIVs are closed and de-activated.
The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
(f) Function automatically blocked above P-11 (Pressurizer Interlock) setpoint and is enabled below P-11 when safety injection on Steam Line Pressure Low is manually blocked.
(d)
(g) Time constants utilized in the rate/lag controller are t3 and t4 > 50 seconds.
Time constants used in the lead/lag controller are t1 > 50 seconds and t2 < 5 seconds.
Watts Bar - Unit 2                                                3.3-35 (developmental)                                                                                                                        FI
(e)
Except when all MSIVs are closed and de-activated.
(f)
Function automatically blocked above P-11 (Pressurizer Interlock) setpoint and is enabled below P-11 when safety injection on Steam Line Pressure Low is manually blocked.
(g)
Time constants utilized in the rate/lag controller are t3 and t4 > 50 seconds.  


ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 4 of 8)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-36 (developmental)
Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER                                                                                             NOMINAL SPECIFIED           REQUIRED                             SURVEILLANCE          ALLOWABLE              TRIP FUNCTION              CONDITIONS          CHANNELS       CONDITIONS           REQUIREMENTS             VALUE           SETPOINT
FI Table 3.3.2-1 (page 4 of 8)
: 5. Turbine Trip and Feedwater Isolation
Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: a. Automatic               1, 2 (h), 3 (h)       2 trains             H             SR 3.3.2.2                 NA                 NA Actuation Logic                                                                  SR 3.3.2.3 and Actuation                                                                    SR 3.3.2.5 Relays
: 5.
: b. SG Water Level -       1, 2 (h), 3 (h)     3 per SG               I             SR 3.3.2.1             < 83.1%             82.4%
Turbine Trip and Feedwater Isolation
High High (P-14)                                                                  SR 3.3.2.4 (b) (c)
: a.
Automatic Actuation Logic and Actuation Relays 1, 2 (h), 3 (h) 2 trains H
SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5
: b.
SG Water Level -
High High (P-14) 1, 2 (h), 3 (h) 3 per SG I
SR 3.3.2.1  
< 83.1%
82.4%
SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10
SR 3.3.2.10
: c. Safety Injection   Refer to Function 1 (Safety Injection) for all initiation functions and requirements.
: c.
: d. North MSV Vault           1, 2 (h)(i)         3 per               O             SR 3.3.2.6           < 5.31 inches       4 inches Room Water                                  vault room                            SR 3.3.2.9 Level - High
Safety Injection Refer to Function 1 (Safety Injection) for all initiation functions and requirements.
: e. South MSV Vault           1, 2 (h)(i)         3 per               O             SR 3.3.2.6           < 4.56 inches       4 inches Room Water                                  vault room                            SR 3.3.2.9 Level - High (continued)
: d.
(b) If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
North MSV Vault Room Water Level - High 1, 2 (h)(i) 3 per vault room O
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
SR 3.3.2.6  
(h) Except when all MFIVs, MFRVs, and associated bypass valves are closed and de-activated or isolated by a closed manual valve.
< 5.31 inches 4 inches SR 3.3.2.9
(i) Mode 2 if Turbine Driven Main Feed Pumps are operating.
: e.
Watts Bar - Unit 2                                              3.3-36 (developmental)                                                                                                                        FI
South MSV Vault Room Water Level - High 1, 2 (h)(i) 3 per vault room O
SR 3.3.2.6  
< 4.56 inches 4 inches SR 3.3.2.9 (continued)
(b)
If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(c)
The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
(h)
Except when all MFIVs, MFRVs, and associated bypass valves are closed and de-activated or isolated by a closed manual valve.
(i)
Mode 2 if Turbine Driven Main Feed Pumps are operating.  


ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 5 of 8)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-37 (developmental)
Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER                                                                                           NOMINAL SPECIFIED         REQUIRED                               SURVEILLANCE          ALLOWABLE            TRIP FUNCTION              CONDITIONS          CHANNELS         CONDITIONS           REQUIREMENTS             VALUE       SETPOINT
FI Table 3.3.2-1 (page 5 of 8)
: 6. Auxiliary Feedwater
Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: a. Automatic                 1, 2, 3           2 trains               G             SR 3.3.2.2                 NA               NA Actuation Logic                                                                    SR 3.3.2.3 and Actuation                                                                      SR 3.3.2.5 Relays
: 6.
: b. SG Water Level             1, 2, 3         3 per SG                 M             SR 3.3.2.1             > 16.4%         17.0%
Auxiliary Feedwater
          - Low Low                                                                          SR 3.3.2.4 (b) (c)
: a.
Automatic Actuation Logic and Actuation Relays 1, 2, 3 2 trains G
SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5
: b.
SG Water Level  
- Low Low 1, 2, 3 3 per SG M
SR 3.3.2.1  
> 16.4%
17.0%
SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10 Coincident with:
SR 3.3.2.10 Coincident with:
: 1) Vessel T                 1, 2               3                   N             SR 3.3.2.4 (b) (c)     Vessel T     Vessel T Equivalent to                                                                  SR 3.3.2.9 (b) (c)   variable input variable input power                                                                                                52.6% RTP      50% RTP 50% RTP With a time                                                                                             1.01 Ts          Ts delay (Ts) if                                                                                           (Note 1,      (Note 1, one SG is                                                                                            Page 3.3-40)   Page 3.3-40) affected or A time delay                                                                                           1.01 Tm          Tm (Tm) if two or                                                                                         (Note 1,      (Note 1, more SGs                                                                                            Page 3.3-40)   Page 3.3-40) are affected
: 1) Vessel T Equivalent to power 50% RTP 1, 2 3
: 2) Vessel T                 1, 2               3                   N             SR 3.3.2.4 (b) (c)     Vessel T     Vessel T equivalent to                                                                  SR 3.3.2.9 (b) (c)    variable input variable input power                                                                                                52.6% RTP      50% RTP
N SR 3.3.2.4 (b) (c)
                > 50% RTP with no time delay (Ts and Tm = 0)
Vessel T variable input 52.6% RTP Vessel T variable input 50% RTP SR 3.3.2.9 (b) (c)
: c. Safety Injection     Refer to Function 1 (Safety Injection) for all initiation functions and requirements.
With a time delay (Ts) if one SG is affected 1.01 Ts (Note 1, Page 3.3-40)
Ts (Note 1, Page 3.3-40) or A time delay (Tm) if two or more SGs are affected 1.01 Tm (Note 1, Page 3.3-40)
Tm (Note 1, Page 3.3-40)
: 2) Vessel T equivalent to power
> 50% RTP with no time delay (Ts and Tm = 0) 1, 2 3
N SR 3.3.2.4 (b) (c)
Vessel T variable input 52.6% RTP Vessel T variable input 50% RTP SR 3.3.2.9 (b) (c)
: c.
Safety Injection Refer to Function 1 (Safety Injection) for all initiation functions and requirements.
(continued)
(continued)
(b) If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(b)
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
Watts Bar - Unit 2                                              3.3-37 (developmental)                                                                                                                        FI
(c)
The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.  


ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 6 of 8)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-38 (developmental)
Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER                                                                                             NOMINAL SPECIFIED           REQUIRED                             SURVEILLANCE          ALLOWABLE              TRIP FUNCTION              CONDITIONS          CHANNELS       CONDITIONS           REQUIREMENTS               VALUE         SETPOINT
GI Table 3.3.2-1 (page 6 of 8)
: 6. Auxiliary Feedwater (continued)
Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: d. Loss of Offsite           1, 2, 3           4 per bus             F           Refer to Function 4 of Table 3.3.5-1 for SRs and Power                                                                          Allowable Values. Notes (b) and (c) are applicable to SR 3.3.5.2 for this function.
: 6.
: e. Trip of all             1 (j), 2 (k)     1 per pump             J             SR 3.3.2.8 (b)(c)     > 43.3 psig         50 psig Turbine Driven                                                                    SR 3.3.2.9 (b) (c)
Auxiliary Feedwater (continued)
Main Feedwater                                                                    SR 3.3.2.10 Pumps
: d.
: f. Auxiliary                 1, 2, 3               3                 F             SR 3.3.2.6           A) > 0.5 psig     A) 1.2 psig Feedwater                                                                        SR 3.3.2.9 (b) (c)
Loss of Offsite Power 1, 2, 3 4 per bus F
Pumps                                                                            SR 3.3.2.10         B) > 1.33 psi     B) 2.0 psig Train A and B                                                                                              g Suction Transfer on Suction Pressure - Low
Refer to Function 4 of Table 3.3.5-1 for SRs and Allowable Values. Notes (b) and (c) are applicable to SR 3.3.5.2 for this function.
: 7. Automatic Switchover to Containment Sump
: e.
: a. Automatic               1, 2, 3, 4         2 trains             C             SR 3.3.2.2                   NA               NA Actuation Logic                                                                  SR 3.3.2.3 and Actuation                                                                    SR 3.3.2.5 Relays
Trip of all Turbine Driven Main Feedwater Pumps 1 (j), 2 (k) 1 per pump J
: b. Refueling Water         1, 2, 3, 4             4                 K             SR 3.3.2.1           > 155.6 inche     158 inches Storage Tank                                                                     SR 3.3.2.4 (b) (c)         s from            from (RWST)                                                                            SR 3.3.2.9 (b) (c)     Tank Base        Tank Base Level - Low                                                                      SR 3.3.2.10 Coincident with     Refer to Function 1 (Safety Injection) for all initiation functions and requirements.
SR 3.3.2.8 (b)(c)  
Safety Injection and Coincident with         1, 2, 3, 4             4                 K             SR 3.3.2.1           > 37.2 inches     38.2 inches Containment                                                                      SR 3.3.2.4 (b) (c)         above            above Sump                                                                              SR 3.3.2.9 (b) (c)     el. 702.8 ft      el. 702.8 ft Level - High                                                                      SR 3.3.2.10 (continued)
> 43.3 psig 50 psig SR 3.3.2.9 (b) (c)
(b) If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
SR 3.3.2.10
(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
: f.
(j) Entry into Condition J may be suspended for up to 4 hours when placing the second Turbine Driven Main Feedwater (TDMFW) Pump in service or removing one of two TDMFW pumps from service.
Auxiliary Feedwater Pumps Train A and B Suction Transfer on Suction Pressure - Low 1, 2, 3 3
(k) When one or more Turbine Driven Main Feedwater Pump(s) are supplying feedwater to steam generators.
F SR 3.3.2.6 A) > 0.5 psig A) 1.2 psig SR 3.3.2.9 (b) (c)
Watts Bar - Unit 2                                              3.3-38 (developmental)                                                                                                                          GI
SR 3.3.2.10 B) > 1.33 psi g
B) 2.0 psig
: 7.
Automatic Switchover to Containment Sump
: a.
Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C
SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5
: b.
Refueling Water Storage Tank (RWST)
Level - Low 1, 2, 3, 4 4
K SR 3.3.2.1  
> 155.6 inche s from Tank Base 158 inches from Tank Base SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10 Coincident with Safety Injection Refer to Function 1 (Safety Injection) for all initiation functions and requirements.
and Coincident with Containment Sump Level - High 1, 2, 3, 4 4
K SR 3.3.2.1  
> 37.2 inches above el. 702.8 ft 38.2 inches above el. 702.8 ft SR 3.3.2.4 (b) (c)
SR 3.3.2.9 (b) (c)
SR 3.3.2.10 (continued)
(b)
If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.
(c)
The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.
(j)
Entry into Condition J may be suspended for up to 4 hours when placing the second Turbine Driven Main Feedwater (TDMFW) Pump in service or removing one of two TDMFW pumps from service.
(k)
When one or more Turbine Driven Main Feedwater Pump(s) are supplying feedwater to steam generators.  


ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 7 of 8)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-39 (developmental)
Engineered Safety Feature Actuation System Instrumentation APPLICABLE MODES OR OTHER                                                             NOMINAL SPECIFIED   REQUIRED                 SURVEILLANCE    ALLOWABLE        TRIP FUNCTION            CONDITIONS    CHANNELS       CONDITIONS REQUIREMENTS     VALUE       SETPOINT
FI Table 3.3.2-1 (page 7 of 8)
: 8. ESFAS Interlocks
Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT
: a. Reactor Trip, P-4       1, 2, 3   1 per train,       F     SR 3.3.2.11       NA           NA 2 trains
: 8.
: b. Pressurizer Pressure, P-11 (1) Unblock           1, 2, 3         3             L     SR 3.3.2.1   < 1975.2 psig 1970 psig (Auto Reset                                            SR 3.3.2.4 of SI Block)                                            SR 3.3.2.9 (2) Enable             1, 2, 3         3             L     SR 3.3.2.1   > 1956.8 psig 1962 psig Manual                                                  SR 3.3.2.4 Block of SI                                            SR 3.3.2.9 Watts Bar - Unit 2                                  3.3-39 (developmental)                                                                                    FI
ESFAS Interlocks
: a.
Reactor Trip, P-4 1, 2, 3 1 per train, 2 trains F
SR 3.3.2.11 NA NA
: b.
Pressurizer Pressure, P-11 (1) Unblock (Auto Reset of SI Block) 1, 2, 3 3
L SR 3.3.2.1  
< 1975.2 psig 1970 psig SR 3.3.2.4 SR 3.3.2.9 (2) Enable Manual Block of SI 1, 2, 3 3
L SR 3.3.2.1  
> 1956.8 psig 1962 psig SR 3.3.2.4 SR 3.3.2.9  


ESFAS Instrumentation 3.3.2 Table 3.3.2-1 (page 8 of 8)
ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-40 (developmental)
F Table 3.3.2-1 (page 8 of 8)
Engineered Safety Feature Actuation System Instrumentation NOTE 1: Steam Generator Water Level Low-Low Trip Time Delay:
Engineered Safety Feature Actuation System Instrumentation NOTE 1: Steam Generator Water Level Low-Low Trip Time Delay:
Ts = A(P)3 + B(P)2 + C(P)+ D Tm = E(P)3 + F(P)2 + G(P)+ H Where:
Ts = A(P)3 + B(P)2+ C(P)+ D Tm = E(P)3 + F(P)2+ G(P)+ H Where:
P   = Vessel T Equivalent to power (% RTP), P 50% RTP Ts   = Time Delay for Steam Generator Water Level - Low Low Reactor Trip, one Steam Generator affected.
P  
Tm   = Time Delay for Steam Generator Water Level - Low Low Reactor Trip, two or more Steam Generators affected.
= Vessel T Equivalent to power (% RTP), P 50% RTP Ts  
A     = -0.0085041 B     = 0.9266400 C     = -33.85998 D     = 474.6060 E     = -0.0047421 F     = 0.5682600 G     = -23.70753 H     = 357.9840 Watts Bar - Unit 2                          3.3-40 (developmental)                                                                          F
= Time Delay for Steam Generator Water Level - Low Low Reactor Trip, one Steam Generator affected.
Tm  
= Time Delay for Steam Generator Water Level - Low Low Reactor Trip, two or more Steam Generators affected.
A  
= -0.0085041 B  
= 0.9266400 C  
= -33.85998 D  
= 474.6060 E  
= -0.0047421 F  
= 0.5682600 G  
= -23.70753 H  
= 357.9840  


PAM InstrumentationTHIS SECTION NOT USED 3.3.3 3.3 INSTRUMENTATION 3.3.3 Post Accident Monitoring (PAM) InstrumentationTHIS SECTION NOT USED LCO 3.3.3                   The PAM instrumentation for each Function in Table 3.3.3-1 shall be OPERABLE.
PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-41 (developmental)
APPLICABILITY:               According to Table 3.3.3-1.
BI 3.3 INSTRUMENTATION 3.3.3 Post Accident Monitoring (PAM) InstrumentationTHIS SECTION NOT USED LCO 3.3.3 The PAM instrumentation for each Function in Table 3.3.3-1 shall be OPERABLE.
ACTIONS
APPLICABILITY:
According to Table 3.3.3-1.
ACTIONS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each Function.
Separate Condition entry is allowed for each Function.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. ------------NOTE----------------           A.1          Restore required channel              30 days Not applicable to Functions                           to OPERABLE status.
CONDITION REQUIRED ACTION COMPLETION TIME A. ------------NOTE----------------
3, 4, 14, and 16.
Not applicable to Functions 3, 4, 14, and 16.
One or more Functions with one required channel inoperable.
One or more Functions with one required channel inoperable.
B. Required Action and                       B.1          Initiate action in                    Immediately associated Completion Time                             accordance with of Condition A not met.                               Specification 5.9.8.
A.1 Restore required channel to OPERABLE status.
(continued)
30 days B. Required Action and associated Completion Time of Condition A not met.
Watts Bar - Unit 2                                        3.3-41 (developmental)                                                                                                              BI
B.1 Initiate action in accordance with Specification 5.9.8.
Immediately (continued)  


PAM InstrumentationTHIS SECTION NOT USED 3.3.3 ACTIONS (continued)
PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-42 (developmental)
CONDITION               REQUIRED ACTION             COMPLETION TIME C. One or more Functions with C.1  Restore one channel to    7 days two required channels           OPERABLE status.
BI ACTIONS (continued)
inoperable.
CONDITION REQUIRED ACTION COMPLETION TIME C. One or more Functions with two required channels inoperable.
OR Functions 3, 4, 14, and 16 with one required channel inoperable.
OR Functions 3, 4, 14, and 16 with one required channel inoperable.
D. Required Action and       D.1  Enter the Condition      Immediately associated Completion Time       referenced in of Condition C not met.         Table 3.3.3-1 for the channel.
C.1 Restore one channel to OPERABLE status.
E. As required by Required   E.1  Be in MODE 3.            6 hours Action D.1 and referenced in Table 3.3.3-1.         AND E.2   Be in MODE 4.             12 hours F. As required by Required   F.1  Initiate action in        Immediately Action D.1 and referenced       accordance with in Table 3.3.3-1.               Specification 5.9.8.
7 days D. Required Action and associated Completion Time of Condition C not met.
Watts Bar - Unit 2                3.3-42 (developmental)                                                              BI
D.1 Enter the Condition referenced in Table 3.3.3-1 for the channel.
Immediately E. As required by Required Action D.1 and referenced in Table 3.3.3-1.
E.1 Be in MODE 3.
6 hours AND E.2 Be in MODE 4.
12 hours F. As required by Required Action D.1 and referenced in Table 3.3.3-1.
F.1 Initiate action in accordance with Specification 5.9.8.
Immediately


PAM InstrumentationTHIS SECTION NOT USED 3.3.3 SURVEILLANCE REQUIREMENTS
PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-43 (developmental)
BI SURVEILLANCE REQUIREMENTS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
SR 3.3.3.1 and SR 3.3.3.2 apply to each PAM instrumentation Function in Table 3.3.3-1.
SR 3.3.3.1 and SR 3.3.3.2 apply to each PAM instrumentation Function in Table 3.3.3-1.
SURVEILLANCE                                                       FREQUENCY SR 3.3.3.1               Perform CHANNEL CHECK for each required                                   31 days instrumentation channel that is normally energized.
SURVEILLANCE FREQUENCY SR 3.3.3.1 Perform CHANNEL CHECK for each required instrumentation channel that is normally energized.
SR 3.3.3.2               -------------------------------NOTES----------------------------
31 days SR 3.3.3.2  
-------------------------------NOTES----------------------------
: 1. Neutron detectors are excluded from CHANNEL CALIBRATION.
: 1. Neutron detectors are excluded from CHANNEL CALIBRATION.
: 2. Not applicable to Functions 11 and 16.
: 2. Not applicable to Functions 11 and 16.
Perform CHANNEL CALIBRATION.                                             18 months SR 3.3.3.3               -------------------------------NOTES----------------------------
Perform CHANNEL CALIBRATION.
18 months SR 3.3.3.3  
-------------------------------NOTES----------------------------
: 1. Verification of relay setpoints not required.
: 1. Verification of relay setpoints not required.
: 2. Only applicable to Functions 11 and 16.
: 2. Only applicable to Functions 11 and 16.
Perform TADOT.                                                           18 months Watts Bar - Unit 2                                          3.3-43 (developmental)                                                                                                              BI
Perform TADOT.
18 months  


PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Table 3.3.3-1 (page 1 of 3)
PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-44 (developmental)
Post Accident Monitoring Instrumentation APPLICABLE                       CONDITION MODES OR                       REFERENCED OTHER         REQUIRED         FROM SPECIFIED      CHANNELS /       REQUIRED FUNCTION                        CONDITIONS        TRAINS        ACTION D.1 (g)          (a)    (b)
HI Table 3.3.3-1 (page 1 of 3)
: 1) Intermediate Range Neutron Flux               1 ,2 ,3             2             E (c)
Post Accident Monitoring Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS /
: 2) Source Range Neutron Flux                       2     ,3         2             E
TRAINS CONDITION REFERENCED FROM REQUIRED ACTION D.1
: 3) Reactor Coolant System (RCS) Hot Leg             1, 2, 3       1 per loop         E Temperature (T-Hot)
: 1)
: 4) RCS Cold Leg Temperature (T-Cold)               1, 2, 3       1 per loop         E
Intermediate Range Neutron Flux (g) 1(a), 2(b), 3 2
: 5) RCS Pressure (Wide Range)                       1, 2, 3           3             E (f)
E
: 6) Reactor Vessel Water Level                       1, 2, 3           2             F
: 2)
: 7) Containment Sump Water Level (Wide               1, 2, 3           2             E Range)
Source Range Neutron Flux 2(c), 3 2
: 8) Containment Lower Comp.                         1, 2, 3           2             E Atm. Temperature (g)
E
: 9) Containment Pressure (Wide Range)               1, 2, 3           2             E
: 3)
: 10) Containment Pressure (Narrow Range)             1, 2, 3           4             E (g)
Reactor Coolant System (RCS) Hot Leg Temperature (T-Hot) 1, 2, 3 1 per loop E
: 11) Containment Isolation Valve Position             1, 2, 3         2 per           E penetration flow (d)(i) path 2 upper
: 4)
: 12) Containment Radiation (High Range)               1, 2, 3                         F containment 2 lower containment
RCS Cold Leg Temperature (T-Cold) 1, 2, 3 1 per loop E
: 13) RCS Pressurizer Level                           1, 2, 3           3             E
: 5)
: 14) Steam Generator (SG) Water Level                 1, 2, 3         1/SG             E (g)
RCS Pressure (Wide Range) 1, 2, 3 3
(Wide Range)
E
(continued)
: 6)
Watts Bar - Unit 2                               3.3-44 (developmental)                                                                                 HI
Reactor Vessel Water Level (f) 1, 2, 3 2
F
: 7)
Containment Sump Water Level (Wide Range) 1, 2, 3 2
E
: 8)
Containment Lower Comp.
Atm. Temperature 1, 2, 3 2
E
: 9)
Containment Pressure (Wide Range) (g) 1, 2, 3 2
E
: 10)
Containment Pressure (Narrow Range) 1, 2, 3 4
E
: 11)
Containment Isolation Valve Position (g) 1, 2, 3 2 per penetration flow path (d)(i)
E
: 12)
Containment Radiation (High Range) 1, 2, 3 2 upper containment 2 lower containment F
: 13)
RCS Pressurizer Level 1, 2, 3 3
E
: 14)
Steam Generator (SG) Water Level (Wide Range) (g) 1, 2, 3 1/SG E
(continued)
 
PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-45 (developmental)
BI Table 3.3.3-1 (page 2 of 3)
Post Accident Monitoring Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS /
TRAINS CONDITION REFERENCED FROM REQUIRED ACTION D.1
: 15)
Steam Generator Water Level (Narrow Range) 1, 2, 3 3/SG E
: 16)
AFW Valve Status (j) 1, 2, 3 1 per valve E
: 17)
Core Exit Temperature-Quadrant 1(f) 1, 2, 3 2 (e)
E
: 18)
Core Exit Temperature-Quadrant 2(f) 1, 2, 3 2 (e)
E
: 19)
Core Exit Temperature-Quadrant 3(f) 1, 2, 3 2 (e)
E
: 20)
Core Exit Temperature-Quadrant 4(f) 1, 2, 3 2 (e)
E
: 21)
Auxiliary Feedwater Flow 1, 2, 3 2/SG E
: 22)
Reactor Coolant System Subcooling Margin Monitor (h) 1, 2, 3 2
E
: 23)
Refueling Water Storage Tank Water Level 1, 2, 3 2
E
: 24)
Steam Generator Pressure 1, 2, 3 2/SG E
: 25)
Auxiliary Building Passive Sump Level (j) 1, 2, 3 2
E


PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Table 3.3.3-1 (page 2 of 3)
PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-46 (developmental)
Post Accident Monitoring Instrumentation APPLICABLE                    CONDITION MODES OR                    REFERENCED OTHER        REQUIRED        FROM SPECIFIED      CHANNELS /    REQUIRED FUNCTION                        CONDITIONS        TRAINS    ACTION D.1
BI Table 3.3.3-1 (page 3 of 3)
: 15) Steam Generator Water Level (Narrow              1, 2, 3        3/SG          E Range)
Post Accident Monitoring Instrumentation (a)
Below the P-10 (Power Range Neutron Flux) interlocks.
(b)
Above the P-6 (Intermediate Range Neutron Flux) interlocks.
(c)
Below the P-6 (Intermediate Range Neutron Flux) interlocks (d)
Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated automatic valve, closed manual valve, blind flange, pressure relief valve, or check valve with flow through the valve secured.
(e)
A channel consists of two core exit thermocouples (CETs).
(f)
The Common Q Post Accident Monitoring System provides these functions on a flat screen display.
(g)
Regulatory Guide 1.97, non-Type A, Category 1 Variables.
(h)
This function is displayed on the Common Q Post Accident Monitoring System flat screen display and digital panel meters.
(i)
Only one position indication channel is required for penetration flow paths with only one installed control room indication channel.
(j)
(j)
: 16)  AFW Valve Status                                1, 2, 3      1 per valve      E (f)                              (e)
Watts Bar specific (not required by Regulatory Guide 1.97) non-Type A Category 1 variable.  
: 17)  Core Exit Temperature-Quadrant 1                 1, 2, 3          2            E (f)                              (e)
: 18)  Core Exit Temperature-Quadrant 2                1, 2, 3          2            E (f)                              (e)
: 19)  Core Exit Temperature-Quadrant 3                1, 2, 3          2            E (f)                              (e)
: 20)  Core Exit Temperature-Quadrant 4                1, 2, 3          2            E
: 21)  Auxiliary Feedwater Flow                        1, 2, 3        2/SG          E
: 22)  Reactor Coolant System Subcooling                1, 2, 3          2            E (h)
Margin Monitor
: 23)  Refueling Water Storage Tank Water              1, 2, 3          2            E Level
: 24)  Steam Generator Pressure                        1, 2, 3        2/SG          E (j)
: 25)  Auxiliary Building Passive Sump Level            1, 2, 3          2            E Watts Bar - Unit 2                              3.3-45 (developmental)                                                                            BI


PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Table 3.3.3-1 (page 3 of 3)
Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-53 (developmental)
Post Accident Monitoring Instrumentation (a)    Below the P-10 (Power Range Neutron Flux) interlocks.
H 3.3 INSTRUMENTATION 3.3.6 Containment Vent Isolation Instrumentation LCO 3.3.6 The Containment Vent Isolation instrumentation for each Function in Table 3.3.6-1 shall be OPERABLE.
(b)    Above the P-6 (Intermediate Range Neutron Flux) interlocks.
APPLICABILITY:
(c)    Below the P-6 (Intermediate Range Neutron Flux) interlocks (d)    Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated automatic valve, closed manual valve, blind flange, pressure relief valve, or check valve with flow through the valve secured.
MODES 1, 2, 3, and 4.
(e)    A channel consists of two core exit thermocouples (CETs).
ACTIONS  
(f)    The Common Q Post Accident Monitoring System provides these functions on a flat screen display.
(g)    Regulatory Guide 1.97, non-Type A, Category 1 Variables.
(h)    This function is displayed on the Common Q Post Accident Monitoring System flat screen display and digital panel meters.
(i)    Only one position indication channel is required for penetration flow paths with only one installed control room indication channel.
(j)    Watts Bar specific (not required by Regulatory Guide 1.97) non-Type A Category 1 variable.
Watts Bar - Unit 2                             3.3-46 (developmental)                                                                                 BI
 
Containment Vent Isolation Instrumentation 3.3.6 3.3 INSTRUMENTATION 3.3.6 Containment Vent Isolation Instrumentation LCO 3.3.6                   The Containment Vent Isolation instrumentation for each Function in Table 3.3.6-1 shall be OPERABLE.
APPLICABILITY:             MODES 1, 2, 3, and 4.
ACTIONS
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each Function.
Separate Condition entry is allowed for each Function.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One radiation monitoring                   A.1           Restore the affected                 4 hours channel inoperable.                                    channel to OPERABLE status.
CONDITION REQUIRED ACTION COMPLETION TIME A. One radiation monitoring channel inoperable.
(continued)
A.1 Restore the affected channel to OPERABLE status.
Watts Bar - Unit 2                                        3.3-53 (developmental)                                                                                                              H
4 hours (continued)  


Containment Vent Isolation Instrumentation 3.3.6 ACTIONS (continued)
Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-54 (developmental)
CONDITION                     REQUIRED ACTION                                 COMPLETION TIME B. One or more Functions with --------------------NOTE-------------------
H ACTIONS (continued)
one or more manual or      One train of automatic actuation automatic actuation trains logic may be bypassed and inoperable.                Required Action B.1 may be delayed for up to 4 hours for OR                        Surveillance testing provided the other train is OPERABLE.
CONDITION REQUIRED ACTION COMPLETION TIME B. One or more Functions with one or more manual or automatic actuation trains inoperable.
Two radiation monitoring channels inoperable.        -----------------------------------------------
OR Two radiation monitoring channels inoperable.
OR                        B.1           Enter applicable                   Immediately Conditions and Required Required Action and                      Actions of LCO 3.6.3, associated Completion                    "Containment Isolation Time of Condition A not                  Valves," for containment met.                                    purge and exhaust isolation valves made inoperable by isolation instrumentation.
OR Required Action and associated Completion Time of Condition A not met.
Watts Bar - Unit 2                          3.3-54 (developmental)                                                                                H
--------------------NOTE-------------------
One train of automatic actuation logic may be bypassed and Required Action B.1 may be delayed for up to 4 hours for Surveillance testing provided the other train is OPERABLE.
B.1 Enter applicable Conditions and Required Actions of LCO 3.6.3, "Containment Isolation Valves," for containment purge and exhaust isolation valves made inoperable by isolation instrumentation.
Immediately


Containment Vent Isolation Instrumentation 3.3.6 SURVEILLANCE REQUIREMENTS
Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-55 (developmental)
B SURVEILLANCE REQUIREMENTS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
Refer to Table 3.3.6-1 to determine which SRs apply for each Containment Vent Isolation Function.
Refer to Table 3.3.6-1 to determine which SRs apply for each Containment Vent Isolation Function.
SURVEILLANCE                                                       FREQUENCY SR 3.3.6.1               Perform CHANNEL CHECK.                                                   12 hours SR 3.3.6.2               -------------------------------NOTE------------------------------
SURVEILLANCE FREQUENCY SR 3.3.6.1 Perform CHANNEL CHECK.
12 hours SR 3.3.6.2  
-------------------------------NOTE------------------------------
This surveillance is only applicable to the actuation logic of the ESFAS instrumentation.
This surveillance is only applicable to the actuation logic of the ESFAS instrumentation.
Perform ACTUATION LOGIC TEST.                                             92 days on a STAGGERED TEST BASIS SR 3.3.6.3               -------------------------------NOTE------------------------------
Perform ACTUATION LOGIC TEST.
92 days on a STAGGERED TEST BASIS SR 3.3.6.3  
-------------------------------NOTE------------------------------
This surveillance is only applicable to the master relays of the ESFAS instrumentation.
This surveillance is only applicable to the master relays of the ESFAS instrumentation.
Perform MASTER RELAY TEST.                                               92 days on a STAGGERED TEST BASIS SR 3.3.6.4               Perform COT.                                                             92 days SR 3.3.6.5               Perform SLAVE RELAY TEST.                                                 92 days OR 18 months for Westinghouse type AR and Potter &
Perform MASTER RELAY TEST.
Brumfield MDR Series relays (continued)
92 days on a STAGGERED TEST BASIS SR 3.3.6.4 Perform COT.
Watts Bar - Unit 2                                          3.3-55 (developmental)                                                                                                              B
92 days SR 3.3.6.5 Perform SLAVE RELAY TEST.
92 days OR 18 months for Westinghouse type AR and Potter &
Brumfield MDR Series relays (continued)  


Containment Vent Isolation Instrumentation 3.3.6 SURVEILLANCE REQUIREMENTS (Continued)
Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-56 (developmental)
SURVEILLANCE                                                 FREQUENCY SR 3.3.6.6         -------------------------------NOTE------------------------------
A SURVEILLANCE REQUIREMENTS (Continued)
SURVEILLANCE FREQUENCY SR 3.3.6.6  
-------------------------------NOTE------------------------------
Verification of setpoint is not required.
Verification of setpoint is not required.
Perform TADOT.                                                       18 months SR 3.3.6.7         Perform CHANNEL CALIBRATION.                                         18 months Watts Bar - Unit 2                                    3.3-56 (developmental)                                                                                          A
Perform TADOT.
18 months SR 3.3.6.7 Perform CHANNEL CALIBRATION.
18 months  


Containment Vent Isolation Instrumentation 3.3.6 Table 3.3.6-1 (page 1 of 1)
Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-57 (developmental)
Containment Vent Isolation Instrumentation REQUIRED           SURVEILLANCE           ALLOWABLE FUNCTION                CHANNELS            REQUIREMENTS              VALUE
HI Table 3.3.6-1 (page 1 of 1)
: 1. Manual Initiation                     2               SR 3.3.6.6               NA
Containment Vent Isolation Instrumentation FUNCTION REQUIRED CHANNELS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE
: 2. Automatic Actuation Logic         2 trains           SR 3.3.6.2               NA and Actuation Relays                                  SR 3.3.6.3 SR 3.3.6.5
: 1.
: 3. Containment Purge                     2               SR 3.3.6.1       < 2.8E-02 &#xb5;Ci/cc(b)
Manual Initiation 2
Exhaust Radiation Monitors                            SR 3.3.6.4          (1.14x104 cpm)
SR 3.3.6.6 NA
SR 3.3.6.7
: 2.
: 4. Safety Injection           Refer to LCO 3.3.2, "ESFAS Instrumentation," Function 1, for all initiation functions and requirements.
Automatic Actuation Logic and Actuation Relays 2 trains SR 3.3.6.2 SR 3.3.6.3 SR 3.3.6.5 NA
Watts Bar - Unit 2                          3.3-57 (developmental)                                                                              HI
: 3.
Containment Purge Exhaust Radiation Monitors 2
SR 3.3.6.1 SR 3.3.6.4 SR 3.3.6.7
< 2.8E-02 &#xb5;Ci/cc(b)
(1.14x104 cpm)
: 4.
Safety Injection Refer to LCO 3.3.2, "ESFAS Instrumentation," Function 1, for all initiation functions and requirements.  


PAM Instrumentation 3.3.39 3.3 INSTRUMENTATION 3.3.3 9 Post Accident Monitoring (PAM) Instrumentation LCO 3.3.39                   The PAM instrumentation for each Function in Table 3.3.39-1 shall be OPERABLE.
PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-41 (developmental)
APPLICABILITY:               According to Table 3.3.3-91.
BI 3.3 INSTRUMENTATION 3.3.3 9 Post Accident Monitoring (PAM) Instrumentation LCO 3.3.39 The PAM instrumentation for each Function in Table 3.3.39-1 shall be OPERABLE.
ACTIONS
APPLICABILITY:
According to Table 3.3.3-91.
ACTIONS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each Function.
Separate Condition entry is allowed for each Function.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. ------------NOTE----------------           A.1          Restore required channel              30 days Not applicable to Functions                           to OPERABLE status.
CONDITION REQUIRED ACTION COMPLETION TIME A. ------------NOTE----------------
3, 4, 14, and 16.
Not applicable to Functions 3, 4, 14, and 16.
One or more Functions with one required channel inoperable.
One or more Functions with one required channel inoperable.
B. Required Action and                       B.1          Initiate action in                    Immediately associated Completion Time                             accordance with of Condition A not met.                               Specification 5.9.8.
A.1 Restore required channel to OPERABLE status.
(continued)
30 days B. Required Action and associated Completion Time of Condition A not met.
Watts Bar - Unit 2                                        3.3-41 (developmental)                                                                                                              BI
B.1 Initiate action in accordance with Specification 5.9.8.
Immediately (continued)  


PAM Instrumentation 3.3.39 ACTIONS (continued)
PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-42 (developmental)
CONDITION               REQUIRED ACTION           COMPLETION TIME C. One or more Functions with C.1  Restore one channel to 7 days two required channels           OPERABLE status.
BI ACTIONS (continued)
inoperable.
CONDITION REQUIRED ACTION COMPLETION TIME C. One or more Functions with two required channels inoperable.
OR Functions 3, 4, 14, and 16 with one required channel inoperable.
OR Functions 3, 4, 14, and 16 with one required channel inoperable.
D. Required Action and       D.1  Enter the Condition    Immediately associated Completion Time       referenced in of Condition C not met.         Table 3.3.39-1 for the channel.
C.1 Restore one channel to OPERABLE status.
E. As required by Required   E.1  Be in MODE 3.          6 hours Action D.1 and referenced in Table 3.3.39-1.         AND E.2   Be in MODE 4.         12 hours F. As required by Required   F.1  Initiate action in    Immediately Action D.1 and referenced       accordance with in Table 3.3.39-1.               Specification 5.9.8.
7 days D. Required Action and associated Completion Time of Condition C not met.
Watts Bar - Unit 2                3.3-42 (developmental)                                                              BI
D.1 Enter the Condition referenced in Table 3.3.39-1 for the channel.
Immediately E. As required by Required Action D.1 and referenced in Table 3.3.39-1.
E.1 Be in MODE 3.
6 hours AND E.2 Be in MODE 4.
12 hours F. As required by Required Action D.1 and referenced in Table 3.3.39-1.
F.1 Initiate action in accordance with Specification 5.9.8.
Immediately


PAM Instrumentation 3.3.39 SURVEILLANCE REQUIREMENTS
PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-43 (developmental)
BI SURVEILLANCE REQUIREMENTS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
SR 3.3.39.1 and SR 3.3.39.2 apply to each PAM instrumentation Function in Table 3.3.39-1.
SR 3.3.39.1 and SR 3.3.39.2 apply to each PAM instrumentation Function in Table 3.3.39-1.
SURVEILLANCE                                                       FREQUENCY SR 3.3.39.1             Perform CHANNEL CHECK for each required                                   31 days instrumentation channel that is normally energized.
SURVEILLANCE FREQUENCY SR 3.3.39.1 Perform CHANNEL CHECK for each required instrumentation channel that is normally energized.
R 3.3.39.2               -------------------------------NOTES----------------------------
31 days R 3.3.39.2  
-------------------------------NOTES----------------------------
: 1. Neutron detectors are excluded from CHANNEL CALIBRATION.
: 1. Neutron detectors are excluded from CHANNEL CALIBRATION.
: 2. Not applicable to Functions 11 and 16.
: 2. Not applicable to Functions 11 and 16.
Perform CHANNEL CALIBRATION.                                             18 months SR 3.3.39.3             -------------------------------NOTES----------------------------
Perform CHANNEL CALIBRATION.
18 months SR 3.3.39.3  
-------------------------------NOTES----------------------------
: 1. Verification of relay setpoints not required.
: 1. Verification of relay setpoints not required.
: 2. Only applicable to Functions 11 and 16.
: 2. Only applicable to Functions 11 and 16.
Perform TADOT.                                                           18 months Watts Bar - Unit 2                                         3.3-43 (developmental)                                                                                                             BI
Perform TADOT.
18 months  
 
PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-44 (developmental)
HI Table 3.3.39-1 (page 1 of 3)
Post Accident Monitoring Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS /
TRAINS CONDITION REFERENCED FROM REQUIRED ACTION D.1
: 1)
Intermediate Range Neutron Flux (g) 1(a), 2(b), 3 2
E
: 2)
Source Range Neutron Flux 2(c), 3 2
E
: 3)
Reactor Coolant System (RCS) Hot Leg Temperature (T-Hot) 1, 2, 3 1 per loop E
: 4)
RCS Cold Leg Temperature (T-Cold) 1, 2, 3 1 per loop E
: 5)
RCS Pressure (Wide Range) 1, 2, 3 3
E
: 6)
Reactor Vessel Water Level (f) 1, 2, 3 2
F
: 7)
Containment Sump Water Level (Wide Range) 1, 2, 3 2
E
: 8)
Containment Lower Comp.
Atm. Temperature 1, 2, 3 2
E
: 9)
Containment Pressure (Wide Range) (g) 1, 2, 3 2
E
: 10)
Containment Pressure (Narrow Range) 1, 2, 3 4
E
: 11)
Containment Isolation Valve Position (g) 1, 2, 3 2 per penetration flow path (d)(i)
E
: 12)
Containment Radiation (High Range) 1, 2, 3 2 upper containment 2 lower containment F
: 13)
RCS Pressurizer Level 1, 2, 3 3
E
: 14)
Steam Generator (SG) Water Level (Wide Range) (g) 1, 2, 3 1/SG E
(continued)


PAM Instrumentation 3.3.39 Table 3.3.39-1 (page 1 of 3)
PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-45 (developmental)
Post Accident Monitoring Instrumentation APPLICABLE                           CONDITION MODES OR                           REFERENCED OTHER         REQUIRED               FROM SPECIFIED      CHANNELS /           REQUIRED FUNCTION                        CONDITIONS        TRAINS            ACTION D.1 (g)          (a)    (b)
BI Table 3.3.39-1 (page 2 of 3)
: 1) Intermediate Range Neutron Flux                1 ,2 ,3             2                  E (c)
Post Accident Monitoring Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS /
: 2) Source Range Neutron Flux                        2      ,3          2                  E
TRAINS CONDITION REFERENCED FROM REQUIRED ACTION D.1
: 3)  Reactor Coolant System (RCS) Hot Leg            1, 2, 3       1 per loop              E Temperature (T-Hot)
: 15)
: 4) RCS Cold Leg Temperature (T-Cold)               1, 2, 3       1 per loop              E
Steam Generator Water Level (Narrow Range) 1, 2, 3 3/SG E
: 5) RCS Pressure (Wide Range)                        1, 2, 3            3                  E (f)
: 16)
: 6)  Reactor Vessel Water Level                      1, 2, 3           2                   F
AFW Valve Status (j) 1, 2, 3 1 per valve E
: 7)  Containment Sump Water Level (Wide              1, 2, 3            2                  E Range)
: 17)
: 8)  Containment Lower Comp.                          1, 2, 3            2                  E Atm. Temperature (g)
Core Exit Temperature-Quadrant 1(f) 1, 2, 3 2 (e)
: 9) Containment Pressure (Wide Range)               1, 2, 3           2                   E
E
: 10) Containment Pressure (Narrow Range)             1, 2, 3           4                  E (g)
: 18)
: 11) Containment Isolation Valve Position            1, 2, 3         2 per                  E penetration flow (d)(i) path 2 upper
Core Exit Temperature-Quadrant 2(f) 1, 2, 3 2 (e)
: 12) Containment Radiation (High Range)               1, 2, 3                               F containment 2 lower containment
E
: 13) RCS Pressurizer Level                           1, 2, 3           3                  E
: 19)
: 14) Steam Generator (SG) Water Level                1, 2, 3         1/SG                   E (g)
Core Exit Temperature-Quadrant 3(f) 1, 2, 3 2 (e)
(Wide Range)
E
(continued)
: 20)
Watts Bar - Unit 2                               3.3-44 (developmental)                                                                                      HI
Core Exit Temperature-Quadrant 4(f) 1, 2, 3 2 (e)
E
: 21)
Auxiliary Feedwater Flow 1, 2, 3 2/SG E
: 22)
Reactor Coolant System Subcooling Margin Monitor (h) 1, 2, 3 2
E
: 23)
Refueling Water Storage Tank Water Level 1, 2, 3 2
E
: 24)
Steam Generator Pressure 1, 2, 3 2/SG E
: 25)
Auxiliary Building Passive Sump Level (j) 1, 2, 3 2
E


PAM Instrumentation 3.3.39 Table 3.3.39-1 (page 2 of 3)
PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-46 (developmental)
Post Accident Monitoring Instrumentation APPLICABLE                        CONDITION MODES OR                        REFERENCED OTHER        REQUIRED            FROM SPECIFIED      CHANNELS /        REQUIRED FUNCTION                        CONDITIONS        TRAINS        ACTION D.1
BI Table 3.3.39-1 (page 3 of 3)
: 15) Steam Generator Water Level (Narrow              1, 2, 3        3/SG              E Range)
Post Accident Monitoring Instrumentation (a)
Below the P-10 (Power Range Neutron Flux) interlocks.
(b)
Above the P-6 (Intermediate Range Neutron Flux) interlocks.
(c)
Below the P-6 (Intermediate Range Neutron Flux) interlocks (d)
Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated automatic valve, closed manual valve, blind flange, pressure relief valve, or check valve with flow through the valve secured.
(e)
A channel consists of two core exit thermocouples (CETs).
(f)
The Common Q Post Accident Monitoring System provides these functions on a flat screen display.
(g)
Regulatory Guide 1.97, non-Type A, Category 1 Variables.
(h)
This function is displayed on the Common Q Post Accident Monitoring System flat screen display and digital panel meters.
(i)
Only one position indication channel is required for penetration flow paths with only one installed control room indication channel.
(j)
(j)
: 16)  AFW Valve Status                                1, 2, 3      1 per valve          E (f)                              (e)
Watts Bar specific (not required by Regulatory Guide 1.97) non-Type A Category 1 variable.  
: 17)  Core Exit Temperature-Quadrant 1                 1, 2, 3          2                E (f)                              (e)
: 18)  Core Exit Temperature-Quadrant 2                1, 2, 3          2                E (f)                              (e)
: 19)  Core Exit Temperature-Quadrant 3                1, 2, 3          2                E (f)                              (e)
: 20)  Core Exit Temperature-Quadrant 4                1, 2, 3          2                E
: 21)  Auxiliary Feedwater Flow                        1, 2, 3        2/SG              E
: 22)  Reactor Coolant System Subcooling                1, 2, 3          2                E (h)
Margin Monitor
: 23)  Refueling Water Storage Tank Water              1, 2, 3          2                E Level
: 24)  Steam Generator Pressure                        1, 2, 3        2/SG              E (j)
: 25)  Auxiliary Building Passive Sump Level            1, 2, 3          2                E Watts Bar - Unit 2                              3.3-45 (developmental)                                                                                BI


PAM Instrumentation 3.3.39 Table 3.3.39-1 (page 3 of 3)
RCS Loops - MODE 4 3.4.6 Watts Bar - Unit 2 3.4-9 (developmental)
Post Accident Monitoring Instrumentation (a)    Below the P-10 (Power Range Neutron Flux) interlocks.
BI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.6 RCS Loops - MODE 4 LCO 3.4.6 Two loops shall be OPERABLE, and consist of either:
(b)    Above the P-6 (Intermediate Range Neutron Flux) interlocks.
: a.
(c)    Below the P-6 (Intermediate Range Neutron Flux) interlocks (d)    Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated automatic valve, closed manual valve, blind flange, pressure relief valve, or check valve with flow through the valve secured.
Any combination of RCS loops and residual heat removal (RHR) loops, and one loop shall be in operation, when the rod control system is not capable of rod withdrawal; or
(e)    A channel consists of two core exit thermocouples (CETs).
: b.
(f)    The Common Q Post Accident Monitoring System provides these functions on a flat screen display.
Two RCS loops, and both loops shall be in operation, when the rod control system is capable of rod withdrawal.  
(g)    Regulatory Guide 1.97, non-Type A, Category 1 Variables.
---------------------------------------------NOTE--------------------------------------------
(h)    This function is displayed on the Common Q Post Accident Monitoring System flat screen display and digital panel meters.
(i)    Only one position indication channel is required for penetration flow paths with only one installed control room indication channel.
(j)    Watts Bar specific (not required by Regulatory Guide 1.97) non-Type A Category 1 variable.
Watts Bar - Unit 2                             3.3-46 (developmental)                                                                                 BI
 
RCS Loops - MODE 4 3.4.6 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.6 RCS Loops - MODE 4 LCO 3.4.6           Two loops shall be OPERABLE, and consist of either:
: a. Any combination of RCS loops and residual heat removal (RHR) loops, and one loop shall be in operation, when the rod control system is not capable of rod withdrawal; or
: b. Two RCS loops, and both loops shall be in operation, when the rod control system is capable of rod withdrawal.
                    ---------------------------------------------NOTE--------------------------------------------
No RCP shall be started with any RCS cold leg temperature less than or equal to the COMS arming temperature specified in the PTLR, unless the secondary side water temperature of each steam generator (SG) is 50&deg;F above each of the RCS cold leg temperatures.
No RCP shall be started with any RCS cold leg temperature less than or equal to the COMS arming temperature specified in the PTLR, unless the secondary side water temperature of each steam generator (SG) is 50&deg;F above each of the RCS cold leg temperatures.
APPLICABILITY:     MODE 4.
APPLICABILITY:
ACTIONS CONDITION                             REQUIRED ACTION                           COMPLETION TIME A. Only one RCS loop                 A.1          Initiate action to restore a          Immediately OPERABLE.                                      second loop to OPERABLE status.
MODE 4.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Only one RCS loop OPERABLE.
AND Two RHR loops inoperable.
AND Two RHR loops inoperable.
B. One required RHR loop             B.1          Be in MODE 5.                          24 hours inoperable.
A.1 Initiate action to restore a second loop to OPERABLE status.
Immediately B. One required RHR loop inoperable.
AND No RCS loops OPERABLE.
AND No RCS loops OPERABLE.
(continued)
B.1 Be in MODE 5.
Watts Bar - Unit 2                                  3.4-9 (developmental)                                                                                                    BI
24 hours (continued)  


RCS Loops - MODE 4 3.4.6 ACTIONS (continued)
RCS Loops - MODE 4 3.4.6 Watts Bar - Unit 2 3.4-10 (developmental)
CONDITION                   REQUIRED ACTION               COMPLETION TIME C. One required RCS loop not     C.1  Restore required RCS      1 hour in operation, and reactor trip       loop to operation.
A ACTIONS (continued)
breakers closed and Rod Control System capable of     OR rod withdrawal.
CONDITION REQUIRED ACTION COMPLETION TIME C. One required RCS loop not in operation, and reactor trip breakers closed and Rod Control System capable of rod withdrawal.
C.2   De-energize all control   1 hour rod drive mechanisms (CRDMs).
C.1 Restore required RCS loop to operation.
D. Required RCS or RHR           D.1   De-energize all CRDMs. Immediately loops inoperable.
1 hour OR C.2 De-energize all control rod drive mechanisms (CRDMs).
AND OR D.2   Suspend all operations     Immediately No required RCS or RHR              involving a reduction of loop in operation                    RCS boron concentration.
1 hour D. Required RCS or RHR loops inoperable.
AND D.3   Initiate action to restore Immediately one loop to OPERABLE status and operation.
OR No required RCS or RHR loop in operation D.1 De-energize all CRDMs.
Watts Bar - Unit 2                    3.4-10 (developmental)                                                                    A
Immediately AND D.2 Suspend all operations involving a reduction of RCS boron concentration.
Immediately AND D.3 Initiate action to restore one loop to OPERABLE status and operation.
Immediately


RCS Loops - MODE 4 3.4.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                   FREQUENCY SR 3.4.6.1         Verify two RCS loop are in operation when the rod   12 hours control system is capable of rod withdrawal.
RCS Loops - MODE 4 3.4.6 Watts Bar - Unit 2 3.4-11 (developmental)
SR 3.4.6.2         Verify one RHR or RCS loop is in operation when the 12 hours rod control system is not capable of rod withdrawal.
A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.6.1 Verify two RCS loop are in operation when the rod control system is capable of rod withdrawal.
SR 3.4.6.3         Verify SG secondary side water levels are greater   12 hours than or equal to 6% narrow range for required RCS loops.
12 hours SR 3.4.6.2 Verify one RHR or RCS loop is in operation when the rod control system is not capable of rod withdrawal.
SR 3.4.6.4         Verify correct breaker alignment and indicated power 7 days are available to the required pump that is not in operation.
12 hours SR 3.4.6.3 Verify SG secondary side water levels are greater than or equal to 6% narrow range for required RCS loops.
Watts Bar - Unit 2                            3.4-11 (developmental)                                                                          A
12 hours SR 3.4.6.4 Verify correct breaker alignment and indicated power are available to the required pump that is not in operation.
7 days


RCS Loops - MODE 5, Loops Filled 3.4.7 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.7 RCS Loops - MODE 5, Loops Filled LCO 3.4.7             One residual heat removal (RHR) loop shall be OPERABLE and in operation, and either:
RCS Loops - MODE 5, Loops Filled 3.4.7 Watts Bar - Unit 2 3.4-12 (developmental)
: a. One additional RHR loop shall be OPERABLE; or
BI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.7 RCS Loops - MODE 5, Loops Filled LCO 3.4.7 One residual heat removal (RHR) loop shall be OPERABLE and in operation, and either:
: b. The secondary side water level of at least two steam generators (SGs) shall be greater than or equal to 6% narrow range.
: a.
                      ---------------------------------------------NOTES------------------------------------------
One additional RHR loop shall be OPERABLE; or
: 1. One required RHR loop may be inoperable for up to 2 hours for surveillance testing provided that the other RHR loop is OPERABLE and in operation.
: b.
: 2. No reactor coolant pump shall be started with one or more RCS cold leg temperatures less than or equal to the COMS arming temperature specified in the PTLR unless the secondary side water temperature of each SG is 50&deg;F above each of the RCS cold leg temperatures.
The secondary side water level of at least two steam generators (SGs) shall be greater than or equal to 6% narrow range.  
: 3. All RHR loops may be removed from operation during planned heatup to MODE 4 when at least one RCS loop is in operation.
---------------------------------------------NOTES------------------------------------------
APPLICABILITY:       MODE 5 with RCS loops filled.
: 1.
ACTIONS CONDITION                             REQUIRED ACTION                           COMPLETION TIME A. One RHR loop inoperable.             A.1         Initiate action to restore a           Immediately second RHR loop to AND                                              OPERABLE status.
One required RHR loop may be inoperable for up to 2 hours for surveillance testing provided that the other RHR loop is OPERABLE and in operation.
Required SGs secondary              OR side water levels not within limits.                            A.2         Initiate action to restore             Immediately required SG secondary side water levels to within limits.
: 2.
(continued)
No reactor coolant pump shall be started with one or more RCS cold leg temperatures less than or equal to the COMS arming temperature specified in the PTLR unless the secondary side water temperature of each SG is 50&deg;F above each of the RCS cold leg temperatures.
Watts Bar - Unit 2                                  3.4-12 (developmental)                                                                                                      BI
: 3.
All RHR loops may be removed from operation during planned heatup to MODE 4 when at least one RCS loop is in operation.
APPLICABILITY:
MODE 5 with RCS loops filled.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One RHR loop inoperable.
AND Required SGs secondary side water levels not within limits.
A.1 Initiate action to restore a second RHR loop to OPERABLE status.
Immediately OR A.2 Initiate action to restore required SG secondary side water levels to within limits.
Immediately (continued)  


RCS Loops - MODE 5, Loops Filled 3.4.7 ACTIONS (continued)
RCS Loops - MODE 5, Loops Filled 3.4.7 Watts Bar - Unit 2 3.4-13 (developmental)
CONDITION                         REQUIRED ACTION                   COMPLETION TIME B. Required RHR loops               B.1       Suspend all operations       Immediately inoperable.                                involving a reduction of RCS boron concentration.
AI ACTIONS (continued)
OR AND No RHR loop in operation.
CONDITION REQUIRED ACTION COMPLETION TIME B. Required RHR loops inoperable.
B.2       Initiate action to restore   Immediately one RHR loop to OPERABLE status and operation.
OR No RHR loop in operation.
SURVEILLANCE REQUIREMENTS SURVEILLANCE                                         FREQUENCY SR 3.4.7.1         Verify one RHR loop is in operation.                       12 hours SR 3.4.7.2         Verify SG secondary side water level is greater than       12 hours or equal to 6% narrow range in required SGs.
B.1 Suspend all operations involving a reduction of RCS boron concentration.
SR 3.4.7.3         Verify correct breaker alignment and indicated power       7 days are available to the required RHR pump that is not in operation.
Immediately AND B.2 Initiate action to restore one RHR loop to OPERABLE status and operation.
Watts Bar - Unit 2                            3.4-13 (developmental)                                                                                AI
Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.7.1 Verify one RHR loop is in operation.
12 hours SR 3.4.7.2 Verify SG secondary side water level is greater than or equal to 6% narrow range in required SGs.
12 hours SR 3.4.7.3 Verify correct breaker alignment and indicated power are available to the required RHR pump that is not in operation.
7 days


Pressurizer Safety Valves 3.4.10 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.10 Pressurizer Safety Valves LCO 3.4.10           Three pressurizer safety valves shall be OPERABLE with lift settings 2410 psig and 2560 psig.
Pressurizer Safety Valves 3.4.10 Watts Bar - Unit 2 3.4-18 (developmental)
APPLICABILITY:       MODES 1, 2, and 3, MODE 4 with all RCS cold leg temperatures greater than> the COMS arming temperature specified in the PTLR.
FI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.10 Pressurizer Safety Valves LCO 3.4.10 Three pressurizer safety valves shall be OPERABLE with lift settings 2410 psig and 2560 psig.
                      ---------------------------------------------NOTE--------------------------------------------
APPLICABILITY:
MODES 1, 2, and 3, MODE 4 with all RCS cold leg temperatures greater than> the COMS arming temperature specified in the PTLR.  
---------------------------------------------NOTE--------------------------------------------
The lift settings are not required to be within the LCO limits during MODE 3 and MODE 4 with all RCS cold leg temperatures greater than>
The lift settings are not required to be within the LCO limits during MODE 3 and MODE 4 with all RCS cold leg temperatures greater than>
the COMS arming temperature specified in the PTLR for the purpose of setting the pressurizer safety valves under ambient (hot) conditions. This exception is allowed for 54 hours following entry into MODE 3 provided a preliminary cold setting was made prior to heatup.
the COMS arming temperature specified in the PTLR for the purpose of setting the pressurizer safety valves under ambient (hot) conditions. This exception is allowed for 54 hours following entry into MODE 3 provided a preliminary cold setting was made prior to heatup.
ACTIONS CONDITION                               REQUIRED ACTION                           COMPLETION TIME A. One pressurizer safety               A.1         Restore valve to                       15 minutes valve inoperable.                                OPERABLE status.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One pressurizer safety valve inoperable.
B. Required Action and                 B.1         Be in MODE 3.                         6 hours associated Completion Time not met.                      AND OR                                  B.2         Be in MODE 4 with any                 12 hours RCS cold leg temperature Two or more pressurizer                          less than or equal to < the safety valves inoperable.                        COMS arming temperature specified in the PTLR.
A.1 Restore valve to OPERABLE status.
Watts Bar - Unit 2                                  3.4-18 (developmental)                                                                                                        FI
15 minutes B. Required Action and associated Completion Time not met.
OR Two or more pressurizer safety valves inoperable.
B.1 Be in MODE 3.
6 hours AND B.2 Be in MODE 4 with any RCS cold leg temperature less than or equal to < the COMS arming temperature specified in the PTLR.
12 hours


Pressurizer Safety Valves 3.4.10 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                           FREQUENCY SR 3.4.10.1       Verify each pressurizer safety valve is OPERABLE in         In accordance with accordance with the Inservice Testing Program.             the Inservice Testing Following testing, lift settings shall be within +/- 1% of   Program the nominal lift setting of 2485 psig.
Pressurizer Safety Valves 3.4.10 Watts Bar - Unit 2 3.4-19 (developmental)
Watts Bar - Unit 2                              3.4-19 (developmental)                                                                                    A
A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.10.1 Verify each pressurizer safety valve is OPERABLE in accordance with the Inservice Testing Program.
Following testing, lift settings shall be within +/- 1% of the nominal lift setting of 2485 psig.
In accordance with the Inservice Testing Program


COMS 3.4.12 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.12 Cold Overpressure Mitigation System (COMS)
COMS 3.4.12 Watts Bar - Unit 2 3.4-23 (developmental)
LCO 3.4.12         A COMS System shall be OPERABLE with a maximum of one charging pump and no safety injection pump capable of injecting into the RCS and the accumulators isolated and either a or b below.
FI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.12 Cold Overpressure Mitigation System (COMS)
: a. Two RCS relief valves, as follows:
LCO 3.4.12 A COMS System shall be OPERABLE with a maximum of one charging pump and no safety injection pump capable of injecting into the RCS and the accumulators isolated and either a or b below.
: a.
Two RCS relief valves, as follows:
: 1. Two power operated relief valves (PORVs) with lift settings within the limits specified in the PTLR, or
: 1. Two power operated relief valves (PORVs) with lift settings within the limits specified in the PTLR, or
: 2. One PORV with a lift setting within the limits specified in the PTLR and the RHR suction relief valve with a setpoint 436.5 psig and 463.5 psig.
: 2. One PORV with a lift setting within the limits specified in the PTLR and the RHR suction relief valve with a setpoint 436.5 psig and 463.5 psig.
: b. The RCS depressurized and an RCS vent capable of relieving
: b.
                        > 475 gpm water flow.
The RCS depressurized and an RCS vent capable of relieving  
                  ---------------------------------------------NOTE--------------------------------------------
> 475 gpm water flow.  
: 1. Two charging pumps may be made capable of injecting for less than or equal to one hour for pump swap operations.
---------------------------------------------NOTE--------------------------------------------
: 2. Accumulator may be unisolated when accumulator pressure is less than the maximum RCS pressure for the existing RCS cold leg temperature allowed by the P/T limit curves provided in the PTLR.
: 1.
APPLICABILITY:     MODE 4 with any RCS cold leg temperature less than or equal to < the COMS arming temperature specified in the PTLR, MODE 5, MODE 6 when the reactor vessel head is on Watts Bar - Unit 2                                3.4-23 (developmental)                                                                                                    FI
Two charging pumps may be made capable of injecting for less than or equal to one hour for pump swap operations.
: 2.
Accumulator may be unisolated when accumulator pressure is less than the maximum RCS pressure for the existing RCS cold leg temperature allowed by the P/T limit curves provided in the PTLR.
APPLICABILITY:
MODE 4 with any RCS cold leg temperature less than or equal to < the COMS arming temperature specified in the PTLR, MODE 5, MODE 6 when the reactor vessel head is on  


COMS 3.4.12 ACTIONS
COMS 3.4.12 Watts Bar - Unit 2 3.4-24 (developmental)
BI ACTIONS  
-----------------------------------------------------------NOTE----------------------------------------------------------
-----------------------------------------------------------NOTE----------------------------------------------------------
LCO 3.0.4.b is not applicable when entering MODE 4.
LCO 3.0.4.b is not applicable when entering MODE 4.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One or more safety injection               A.1           Initiate action to verify no         Immediately pumps capable of injecting                            safety injection pumps into the RCS.                                          are capable of injecting into the RCS.
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more safety injection pumps capable of injecting into the RCS.
B. Two or more charging                       B.1           Initiate action to verify a           Immediately pumps capable of injecting                            maximum of one charging into the RCS.                                          pump is capable of injecting into the RCS.
A.1 Initiate action to verify no safety injection pumps are capable of injecting into the RCS.
C. An accumulator not isolated               C.1          Isolate affected                      1 hour when the accumulator                                   accumulator.
Immediately B. Two or more charging pumps capable of injecting into the RCS.
pressure is greater than or equal to the maximum RCS pressure for existing cold leg temperature allowed in the PTLR.
B.1 Initiate action to verify a maximum of one charging pump is capable of injecting into the RCS.
D. Required Action and                       D.1           Increase RCS cold leg                 12 hours associated Completion                                  temperature to greater Time of Condition C not                                than > the COMS arming met.                                                  temperature specified in the PTLR.
Immediately C. An accumulator not isolated when the accumulator pressure is greater than or equal to the maximum RCS pressure for existing cold leg temperature allowed in the PTLR.
OR D.2           Depressurize affected                 12 hours accumulator to less than the maximum RCS pressure for existing cold leg temperature allowed in the PTLR.
C.1 Isolate affected accumulator.
(continued)
1 hour D. Required Action and associated Completion Time of Condition C not met.
Watts Bar - Unit 2                                        3.4-24 (developmental)                                                                                                              BI
D.1 Increase RCS cold leg temperature to greater than > the COMS arming temperature specified in the PTLR.
12 hours OR D.2 Depressurize affected accumulator to less than the maximum RCS pressure for existing cold leg temperature allowed in the PTLR.
12 hours (continued)  


COMS 3.4.12 ACTIONS (continued)
COMS 3.4.12 Watts Bar - Unit 2 3.4-25 (developmental)
CONDITION                 REQUIRED ACTION       COMPLETION TIME E. One required RCS relief     E.1  Restore required RCS 7 days valve inoperable in MODE 4         relief valve to with any RCS cold leg             OPERABLE status.
BI ACTIONS (continued)
temperature less than or equal to< the COMS arming temperature specified in the PTLR.
CONDITION REQUIRED ACTION COMPLETION TIME E. One required RCS relief valve inoperable in MODE 4 with any RCS cold leg temperature less than or equal to< the COMS arming temperature specified in the PTLR.
F. One required RCS relief     F.1  Restore required RCS 24 hours valve inoperable in MODE 5         relief valve to or 6.                              OPERABLE status.
E.1 Restore required RCS relief valve to OPERABLE status.
G. Two required RCS relief     G.1  Depressurize RCS and 8 hours valves inoperable.                establish RCS vent.
7 days F. One required RCS relief valve inoperable in MODE 5 or 6.
F.1 Restore required RCS relief valve to OPERABLE status.
24 hours G. Two required RCS relief valves inoperable.
OR Required Action and associated Completion Time of Condition A, B, D, E, or F not met.
OR Required Action and associated Completion Time of Condition A, B, D, E, or F not met.
OR COMS inoperable for any reason other than Condition A, B, C, D, E, or F.
OR COMS inoperable for any reason other than Condition A, B, C, D, E, or F.
Watts Bar - Unit 2                  3.4-25 (developmental)                                                          BI
G.1 Depressurize RCS and establish RCS vent.
8 hours


COMS 3.4.12 SURVEILLANCE REQUIREMENTS SURVEILLANCE                             FREQUENCY SR 3.4.12.1       Verify no safety injection pumps are capable of Within 4 hours after injecting into the RCS.                         entering MODE 4 from MODE 3 prior to the temperature of one or more RCS cold legs decreasing below the COMS arming temperature specified in the PTLR225&deg;F.
COMS 3.4.12 Watts Bar - Unit 2 3.4-26 (developmental)
AND 12 hours thereafter SR 3.4.12.2       Verify a maximum of one charging pump is capable Within 4 hours after of injecting into the RCS.                       entering MODE 4 from MODE 3 prior to the temperature of one or more RCS cold legs decreasing below the COMS arming temperature specified in the PTLR225&deg;F.
GI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.12.1 Verify no safety injection pumps are capable of injecting into the RCS.
AND 12 hours thereafter SR 3.4.12.3       Verify each accumulator is isolated.             12 hours (continued)
Within 4 hours after entering MODE 4 from MODE 3 prior to the temperature of one or more RCS cold legs decreasing below the COMS arming temperature specified in the PTLR225&deg;F.
Watts Bar - Unit 2                            3.4-26 (developmental)                                                                          GI
AND 12 hours thereafter SR 3.4.12.2 Verify a maximum of one charging pump is capable of injecting into the RCS.
Within 4 hours after entering MODE 4 from MODE 3 prior to the temperature of one or more RCS cold legs decreasing below the COMS arming temperature specified in the PTLR225&deg;F.
AND 12 hours thereafter SR 3.4.12.3 Verify each accumulator is isolated.
12 hours (continued)  


COMS 3.4.12 SURVEILLANCE REQUIREMENTS (continued)
COMS 3.4.12 Watts Bar - Unit 2 3.4-27 (developmental)
SURVEILLANCE                                                 FREQUENCY SR 3.4.12.4       -------------------------------NOTE------------------------------
GI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.4.12.4  
-------------------------------NOTE------------------------------
Only required to be performed when complying with LCO 3.4.12.b.
Only required to be performed when complying with LCO 3.4.12.b.
Verify RCS vent open.                                                 12 hours for unlocked open vent paths AND 31 days for locked open vent paths (continued)
Verify RCS vent open.
SR 3.4.12.5       Verify PORV block valve is open for each required                     72 hours PORV.
12 hours for unlocked open vent paths AND 31 days for locked open vent paths (continued)
SR 3.4.12.6       Verify both RHR suction isolation valves are locked                   31 days open with operator power removed for the required RHR suction relief valve.
SR 3.4.12.5 Verify PORV block valve is open for each required PORV.
SR 3.4.12.7       -------------------------------NOTE------------------------------
72 hours SR 3.4.12.6 Verify both RHR suction isolation valves are locked open with operator power removed for the required RHR suction relief valve.
31 days SR 3.4.12.7  
-------------------------------NOTE------------------------------
Required to be met within 12 hours after decreasing RCS cold leg temperature to less than or equal to the COMS arming temperature specified in the PTLR.
Required to be met within 12 hours after decreasing RCS cold leg temperature to less than or equal to the COMS arming temperature specified in the PTLR.
Perform a COT on each required PORV, excluding                       31 days actuation.
Perform a COT on each required PORV, excluding actuation.
SR 3.4.12.8       Perform CHANNEL CALIBRATION for each required                         18 months PORV actuation channel.
31 days SR 3.4.12.8 Perform CHANNEL CALIBRATION for each required PORV actuation channel.
Watts Bar - Unit 2                                    3.4-27 (developmental)                                                                                            GI
18 months


COMS 3.4.12 SURVEILLANCE REQUIREMENTS (continued)
COMS 3.4.12 Watts Bar - Unit 2 3.4-28 (developmental)
SURVEILLANCE                                                                             FREQUENCY SR 3.4.12.5       Verify PORV block valve is open for each required                     72 hours PORV.
BI SURVEILLANCE REQUIREMENTS (continued)
SR 3.4.12.6       Verify both RHR suction isolation valves are locked                   31 days open with operator power removed for the required RHR suction relief valve.
SURVEILLANCE FREQUENCY SR 3.4.12.5 Verify PORV block valve is open for each required PORV.
SR 3.4.12.7       -------------------------------NOTE------------------------------
72 hours SR 3.4.12.6 Verify both RHR suction isolation valves are locked open with operator power removed for the required RHR suction relief valve.
31 days SR 3.4.12.7  
-------------------------------NOTE------------------------------
Required to be met within 12 hours after decreasing RCS cold leg temperature to less than or equal to the COMS arming temperature specified in the PTLR.
Required to be met within 12 hours after decreasing RCS cold leg temperature to less than or equal to the COMS arming temperature specified in the PTLR.
Perform a COT on each required PORV, excluding                       31 days actuation.
Perform a COT on each required PORV, excluding actuation.
SR 3.4.12.8       Perform CHANNEL CALIBRATION for each required                         18 months PORV actuation channel.
31 days SR 3.4.12.8 Perform CHANNEL CALIBRATION for each required PORV actuation channel.
Watts Bar - Unit 2                                    3.4-28 (developmental)                                                                                        BI
18 months


RCS Specific Activity 3.4.16 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.16 RCS Specific Activity LCO 3.4.16           The specific activity of the reactor coolant shall be within limits.
RCS Specific Activity 3.4.16 Watts Bar - Unit 2 3.4-35 (developmental)
APPLICABILITY:       MODES 1 and 2, MODE 3 with RCS average temperature (Tavg) 500&deg;F.
H 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.16 RCS Specific Activity LCO 3.4.16 The specific activity of the reactor coolant shall be within limits.
ACTIONS CONDITION                         REQUIRED ACTION                       COMPLETION TIME A. DOSE EQUIVALENT I-131           --------------------NOTE-------------------
APPLICABILITY:
    > 0.265 &#xb5;Ci/gm.                LCO 3.0.4.c is applicable.
MODES 1 and 2, MODE 3 with RCS average temperature (Tavg) 500&deg;F.
A.1           Verify DOSE                       Once per 4 hours EQUIVALENT I-131 14 &#xb5;Ci/gm.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. DOSE EQUIVALENT I-131  
AND A.2           Restore DOSE                       48 hours EQUIVALENT I-131 to within limit.
> 0.265 &#xb5;Ci/gm.
B. Gross specific activity of the B.1           Perform SR 3.4.16.2.               4 hours reactor coolant not within limit.                        AND B.2           Be in MODE 3 with                 6 hours Tavg < 500&deg;F.
--------------------NOTE-------------------
(continued)
LCO 3.0.4.c is applicable.
Watts Bar - Unit 2                              3.4-35 (developmental)                                                                                        H
A.1 Verify DOSE EQUIVALENT I-131 14 &#xb5;Ci/gm.
Once per 4 hours AND A.2 Restore DOSE EQUIVALENT I-131 to within limit.
48 hours B. Gross specific activity of the reactor coolant not within limit.
B.1 Perform SR 3.4.16.2.
4 hours AND B.2 Be in MODE 3 with Tavg < 500&deg;F.
6 hours (continued)  


RCS Specific Activity 3.4.16 ACTIONS (continued)
RCS Specific Activity 3.4.16 Watts Bar - Unit 2 3.4-36 (developmental)
CONDITION                                 REQUIRED ACTION                       COMPLETION TIME C. Required Action and                   C.1          Be in MODE 3 with                  6 hours associated Completion                             Tavg < 500&deg;F.
HI ACTIONS (continued)
Time of Condition A not met.
CONDITION REQUIRED ACTION COMPLETION TIME C. Required Action and associated Completion Time of Condition A not met.
OR DOSE EQUIVALENT I-131
OR DOSE EQUIVALENT I-131  
  > 14 &#xb5;Ci/gm.
> 14 &#xb5;Ci/gm.
SURVEILLANCE REQUIREMENTS SURVEILLANCE                                                 FREQUENCY SR 3.4.16.1       Verify reactor coolant gross specific activity                         7 days
C.1 Be in MODE 3 with Tavg < 500&deg;F.
                  < 100/E &#xb5;Ci/gm.
6 hours SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.16.1 Verify reactor coolant gross specific activity  
SR 3.4.16.2       -------------------------------NOTE------------------------------
< 100/E &#xb5;Ci/gm.
7 days SR 3.4.16.2  
-------------------------------NOTE------------------------------
Only required to be performed in MODE 1.
Only required to be performed in MODE 1.
Verify reactor coolant DOSE EQUIVALENT I-131                           14 days specific activity 0.265 &#xb5;Ci/gm.
Verify reactor coolant DOSE EQUIVALENT I-131 specific activity 0.265 &#xb5;Ci/gm.
AND Between 2 hours and 6 hours after a THERMAL POWER change of 15% RTP within a 1 hour period (continued)
14 days AND Between 2 hours and 6 hours after a THERMAL POWER change of 15% RTP within a 1 hour period (continued)  
Watts Bar - Unit 2                                    3.4-36 (developmental)                                                                                              HI


RCS Specific Activity 3.4.16 SURVEILLANCE REQUIREMENTS (continued)
RCS Specific Activity 3.4.16 Watts Bar - Unit 2 3.4-37 (developmental)
SURVEILLANCE                                                 FREQUENCY SR 3.4.16.3       -------------------------------NOTE------------------------------
A SURVEILLANCE REQUIREMENTS (continued)
Required to be performed within 31 days after a minimum of 2 effective full power days and 20 days of MODE 1 operation have elapsed since the reactor was last subcritical for 48 hours.
SURVEILLANCE FREQUENCY SR 3.4.16.3  
Determine from a sample taken in MODE 1 after a                     184 days minimum of 2 effective full power days and 20 days of MODE 1 operation have elapsed since the reactor was last subcritical for 48 hours.
-------------------------------NOTE------------------------------
Watts Bar - Unit 2                                    3.4-37 (developmental)                                                                                            A
Required to be performed within 31 days after a minimum of 2 effective full power days and 20 days of MODE 1 operation have elapsed since the reactor was last subcritical for 48 hours.
Determine from a sample taken in MODE 1 after a minimum of 2 effective full power days and 20 days of MODE 1 operation have elapsed since the reactor was last subcritical for 48 hours.
184 days


SG Tube Integrity 3.4.17 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.17 Steam Generator (SG) Tube Integrity LCO 3.4.17                 SG tube integrity shall be maintained AND All SG tubes satisfying the tube plugging or repair criteria shall be plugged or repaired in accordance with the Steam Generator Program.
SG Tube Integrity 3.4.17 Watts Bar - Unit 2 3.4-38 (developmental)
APPLICABILITY:             MODES 1, 2, 3, and 4.
GI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.17 Steam Generator (SG) Tube Integrity LCO 3.4.17 SG tube integrity shall be maintained AND All SG tubes satisfying the tube plugging or repair criteria shall be plugged or repaired in accordance with the Steam Generator Program.
ACTIONS
APPLICABILITY:
MODES 1, 2, 3, and 4.
ACTIONS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each SG tube.
Separate Condition entry is allowed for each SG tube.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One or more SG tubes                       A.1           Verify tube integrity of the         7 days satisfying the tube plugging                          affected tube(s) is or repair criteria and not                            maintained until the next plugged or repaired in                                refueling outage or SG accordance with the Steam                              tube inspection Generator Program AND A.2           Plug or repair the affected           Prior to entering tube(s) in accordance                 MODE 4 following with the Steam Generator             the next refueling Program                              outage or SG tube inspection B. Required Action and                       B.1           Be in MODE 3.                         6 hours associated Completion Time of Condition A not met              AND OR                                      B.2           Be in MODE 5.                         36 hours SG tube integrity not maintained Watts Bar - Unit 2                                        3.4-38 (developmental)                                                                                                              GI
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more SG tubes satisfying the tube plugging or repair criteria and not plugged or repaired in accordance with the Steam Generator Program A.1 Verify tube integrity of the affected tube(s) is maintained until the next refueling outage or SG tube inspection 7 days AND A.2 Plug or repair the affected tube(s) in accordance with the Steam Generator Program Prior to entering MODE 4 following the next refueling outage or SG tube inspection B. Required Action and associated Completion Time of Condition A not met OR SG tube integrity not maintained B.1 Be in MODE 3.
6 hours AND B.2 Be in MODE 5.
36 hours  


SG Tube Integrity 3.4.17 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                     FREQUENCY SR 3.4.17.1       Verify steam generator tube integrity in accordance    In accordance with with the Steam Generator Program.                       the Steam Generator Program SR 3.4.17.2       Verify that each inspected SG tube that satisfies the   Prior to entering tube plugging or repair criteria is plugged or repaired MODE 4 following a in accordance with the Steam Generator Program.         SG tube inspection Watts Bar - Unit 2                            3.4-39 (developmental)                                                                                GI
SG Tube Integrity 3.4.17 Watts Bar - Unit 2 3.4-39 (developmental)
GI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.17.1 Verify steam generator tube integrity in accordance with the Steam Generator Program.
In accordance with the Steam Generator Program SR 3.4.17.2 Verify that each inspected SG tube that satisfies the tube plugging or repair criteria is plugged or repaired in accordance with the Steam Generator Program.
Prior to entering MODE 4 following a SG tube inspection  


ECCS - Operating 3.5.2 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) 3.5.2 ECCS - Operating LCO 3.5.2             Two ECCS trains shall be OPERABLE.
ECCS - Operating 3.5.2 Watts Bar - Unit 2 3.5-3 (developmental)
                      ---------------------------------------------NOTE--------------------------------------------
A 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) 3.5.2 ECCS - Operating LCO 3.5.2 Two ECCS trains shall be OPERABLE.  
---------------------------------------------NOTE--------------------------------------------
: 1. In MODE 3, both safety injection (SI) pump flow paths may be isolated by closing the isolation valves for up to 2 hours to perform pressure isolation valve testing per SR 3.4.14.1.
: 1. In MODE 3, both safety injection (SI) pump flow paths may be isolated by closing the isolation valves for up to 2 hours to perform pressure isolation valve testing per SR 3.4.14.1.
: 2. In MODE 3, the safety injection pumps and charging pumps may be made incapable of injecting to support transition into or from the Applicability of the LCO 3.4.12, Cold Overpressure Mitigation System (COMS) for up to four hours or until the temperature of all the RCS cold legs exceeds 375&deg;F, whichever occurs first.
: 2. In MODE 3, the safety injection pumps and charging pumps may be made incapable of injecting to support transition into or from the Applicability of the LCO 3.4.12, Cold Overpressure Mitigation System (COMS) for up to four hours or until the temperature of all the RCS cold legs exceeds 375&deg;F, whichever occurs first.
APPLICABILITY:       MODES 1, 2, and 3.
APPLICABILITY:
ACTIONS CONDITION                               REQUIRED ACTION                           COMPLETION TIME A. One or more trains                   A.1          Restore train(s) to                    72 hours inoperable.                                      OPERABLE status.
MODES 1, 2, and 3.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more trains inoperable.
AND At least 100% of the ECCS flow equivalent to a single OPERABLE ECCS train available.
AND At least 100% of the ECCS flow equivalent to a single OPERABLE ECCS train available.
B. Required Action and                 B.1         Be in MODE 3.                         6 hours associated Completion Time not met.                      AND B.2         Be in MODE 4.                         12 hours Watts Bar - Unit 2                                    3.5-3 (developmental)                                                                                                        A
A.1 Restore train(s) to OPERABLE status.
72 hours B. Required Action and associated Completion Time not met.
B.1 Be in MODE 3.
6 hours AND B.2 Be in MODE 4.
12 hours  


ECCS - Operating 3.5.2 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                     FREQUENCY SR 3.5.2.1         Verify the following valves are in the listed position 12 hours with power to the valve operator removed.
ECCS - Operating 3.5.2 Watts Bar - Unit 2 3.5-4 (developmental)
Number           Position         Function 2-FCV-63-1       Open             RHR Supply 2-FCV-63-22     Open             SIS Discharge SR 3.5.2.2         Verify each ECCS manual, power operated, and           31 days automatic valve in the flow path, that is not locked, sealed, or otherwise secured in position, is in the correct position.
BI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.5.2.1 Verify the following valves are in the listed position with power to the valve operator removed.
SR 3.5.2.3         Verify ECCS piping is full of water.                   31 days SR 3.5.2.4         Verify each ECCS pump's developed head at the test     In accordance with flow point is greater than or equal to the required     the Inservice Testing developed head.                                        Program SR 3.5.2.5         Verify each ECCS automatic valve in the flow path       18 months that is not locked, sealed, or otherwise secured in position, actuates to the correct position on an actual or simulated actuation signal.
Number Position Function 2-FCV-63-1 Open RHR Supply 2-FCV-63-22 Open SIS Discharge 12 hours SR 3.5.2.2 Verify each ECCS manual, power operated, and automatic valve in the flow path, that is not locked, sealed, or otherwise secured in position, is in the correct position.
SR 3.5.2.6         Verify each ECCS pump starts automatically on an       18 months actual or simulated actuation signal.
31 days SR 3.5.2.3 Verify ECCS piping is full of water.
(continued)
31 days SR 3.5.2.4 Verify each ECCS pump's developed head at the test flow point is greater than or equal to the required developed head.
Watts Bar - Unit 2                              3.5-4 (developmental)                                                                                BI
In accordance with the Inservice Testing Program SR 3.5.2.5 Verify each ECCS automatic valve in the flow path that is not locked, sealed, or otherwise secured in position, actuates to the correct position on an actual or simulated actuation signal.
18 months SR 3.5.2.6 Verify each ECCS pump starts automatically on an actual or simulated actuation signal.
18 months (continued)  


ECCS - Operating 3.5.2 SURVEILLANCE REQUIREMENTS (continued)
ECCS - Operating 3.5.2 Watts Bar - Unit 2 3.5-5 (developmental)
SURVEILLANCE                                 FREQUENCY SR 3.5.2.7         Verify, for each ECCS throttle valve listed below,   18 months each position stop is in the correct position.
BI SURVEILLANCE REQUIREMENTS (continued)
Valve Number CCP                 SI               SI Discharge          Cold Leg         Hot Leg Throttle            Throttle        Throttle Valves             Valves           Valves 2-63-582           2-63-550         2-63-542 2-63-583           2-63-552         2-63-544 2-63-584           2-63-554         2-63-546 2-63-585           2-63-556         2-63-548 SR 3.5.2.8         Verify, by visual inspection, each ECCS train       18 months containment sump suction inlet is not restricted by debris and the suction inlet trash racks and screens show no evidence of structural distress or abnormal corrosion.
SURVEILLANCE FREQUENCY SR 3.5.2.7 Verify, for each ECCS throttle valve listed below, each position stop is in the correct position.
Watts Bar - Unit 2                            3.5-5 (developmental)                                                                          BI
Valve Number CCP Discharge Throttle SI Cold Leg Throttle SI Hot Leg Throttle Valves Valves Valves 2-63-582 2-63-550 2-63-542 2-63-583 2-63-552 2-63-544 2-63-584 2-63-554 2-63-546 2-63-585 2-63-556 2-63-548 18 months SR 3.5.2.8 Verify, by visual inspection, each ECCS train containment sump suction inlet is not restricted by debris and the suction inlet trash racks and screens show no evidence of structural distress or abnormal corrosion.
18 months


Containment Air Temperature 3.6.5 3.6 CONTAINMENT SYSTEMS 3.6.5 Containment Air Temperature LCO 3.6.5           Containment average air temperature shall be:
Containment Air Temperature 3.6.5 Watts Bar - Unit 2 3.6-15 (developmental)
: a.   > 85&deg;F and 110&deg;F for the containment upper compartment, and
AI 3.6 CONTAINMENT SYSTEMS 3.6.5 Containment Air Temperature LCO 3.6.5 Containment average air temperature shall be:
: b.   > 100&deg;F and 120&deg;F for the containment lower compartment.
: a.  
                    ---------------------------------------------NOTE--------------------------------------------
> 85&deg;F and 110&deg;F for the containment upper compartment, and
: b.  
> 100&deg;F and 120&deg;F for the containment lower compartment.  
---------------------------------------------NOTE--------------------------------------------
The minimum containment average air temperatures in MODES 2, 3, and 4 may be reduced to 60&deg;F.
The minimum containment average air temperatures in MODES 2, 3, and 4 may be reduced to 60&deg;F.
APPLICABILITY:       MODES 1, 2, 3, and 4.
APPLICABILITY:
ACTIONS CONDITION                           REQUIRED ACTION                           COMPLETION TIME A. Containment average air             A.1         Restore containment                   8 hours temperature not within                          average air temperature limits.                                        to within limits.
MODES 1, 2, 3, and 4.
B. Required Action and                 B.1         Be in MODE 3.                         6 hours associated Completion Time not met.                      AND B.2         Be in MODE 5.                         36 hours Watts Bar - Unit 2                                  3.6-15 (developmental)                                                                                                      AI
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Containment average air temperature not within limits.
A.1 Restore containment average air temperature to within limits.
8 hours B. Required Action and associated Completion Time not met.
B.1 Be in MODE 3.
6 hours AND B.2 Be in MODE 5.
36 hours  


Containment Air Temperature 3.6.5 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                 FREQUENCY SR 3.6.5.1         Verify containment upper compartment average air   24 hours temperature is within limits.
Containment Air Temperature 3.6.5 Watts Bar - Unit 2 3.6-16 (developmental)
SR 3.6.5.2         Verify containment lower compartment average air   24 hours temperature is within limits.
A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.5.1 Verify containment upper compartment average air temperature is within limits.
Watts Bar - Unit 2                            3.6-16 (developmental)                                                                          A
24 hours SR 3.6.5.2 Verify containment lower compartment average air temperature is within limits.
24 hours


HMS 3.6.8 3.6 CONTAINMENT SYSTEMS 3.6.8 Hydrogen Mitigation System (HMS)
HMS 3.6.8 Watts Bar - Unit 2 3.6-20 (developmental)
LCO 3.6.8             Two HMS trains shall be OPERABLE.
AI 3.6 CONTAINMENT SYSTEMS 3.6.8 Hydrogen Mitigation System (HMS)
APPLICABILITY:       MODES 1 and 2.
LCO 3.6.8 Two HMS trains shall be OPERABLE.
ACTIONS CONDITION                       REQUIRED ACTION         COMPLETION TIME A. One HMS train inoperable. A.1       Restore HMS train to   7 days OPERABLE status.
APPLICABILITY:
OR A.2       Perform SR 3.6.8.1 on Once per 7 days the OPERABLE train.
MODES 1 and 2.
B. One containment region       B.1       Restore one hydrogen   7 days with no OPERABLE                        ignitor igniter in the hydrogen ignitorigniter.                affected containment region to OPERABLE status.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One HMS train inoperable.
C. Required Action and           C.1       Be in MODE 3.         6 hours associated Completion Time not met.
A.1 Restore HMS train to OPERABLE status.
Watts Bar - Unit 2                          3.6-20 (developmental)                                                                      AI
7 days OR A.2 Perform SR 3.6.8.1 on the OPERABLE train.
Once per 7 days B. One containment region with no OPERABLE hydrogen ignitorigniter.
B.1 Restore one hydrogen ignitor igniter in the affected containment region to OPERABLE status.
7 days C. Required Action and associated Completion Time not met.
C.1 Be in MODE 3.
6 hours  


HMS 3.6.8 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                 FREQUENCY SR 3.6.8.1         Energize each HMS train power supply breaker and   92 days verify 33 ignitors igniters are energized in each train.
HMS 3.6.8 Watts Bar - Unit 2 3.6-21 (developmental)
SR 3.6.8.2         Verify at least one hydrogen ignitor igniter is     92 days OPERABLE in each containment region.
AI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.8.1 Energize each HMS train power supply breaker and verify 33 ignitors igniters are energized in each train.
SR 3.6.8.3         Energize each hydrogen ignitor igniter and verify   18 months temperature is 1700&deg;F.
92 days SR 3.6.8.2 Verify at least one hydrogen ignitor igniter is OPERABLE in each containment region.
Watts Bar - Unit 2                              3.6-21 (developmental)                                                                      AI
92 days SR 3.6.8.3 Energize each hydrogen ignitor igniter and verify temperature is 1700&deg;F.
18 months


MSSVs 3.7.1 3.7 PLANT SYSTEMS 3.7.1 Main Steam Safety Valves (MSSVs)
MSSVs 3.7.1 Watts Bar - Unit 2 3.7-1 (developmental)
LCO 3.7.1                   Five MSSVs per steam generator shall be OPERABLE.
FI 3.7 PLANT SYSTEMS 3.7.1 Main Steam Safety Valves (MSSVs)
APPLICABILITY:             MODES 1, 2, and 3.
LCO 3.7.1 Five MSSVs per steam generator shall be OPERABLE.
ACTIONS
APPLICABILITY:
MODES 1, 2, and 3.
ACTIONS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each MSSV.
Separate Condition entry is allowed for each MSSV.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One or more steam                         A.1           Reduce THERMAL                       4 hours generators with one MSSV                              POWER to inoperable.                                            59 58 % RTP.
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more steam generators with one MSSV inoperable.
B. One or more steam                         B.1           Reduce THERMAL                       4 hours generators with two or more                            POWER to less than or MSSVs inoperable.                                      equal to the Maximum Allowable % RTP specified in Table 3.7.1-1 for the number of OPERABLE MSSVs.
A.1 Reduce THERMAL POWER to 59 58 % RTP.
AND
4 hours B. One or more steam generators with two or more MSSVs inoperable.
                                                            ------------NOTE-------------
B.1 Reduce THERMAL POWER to less than or equal to the Maximum Allowable % RTP specified in Table 3.7.1-1 for the number of OPERABLE MSSVs.
4 hours AND  
------------NOTE-------------
Only required in MODE 1.
Only required in MODE 1.
B.2           Reduce the Power Range               36 hours Neutron Flux - High reactor trip setpoint to less than or equal to the Maximum Allowable
B.2 Reduce the Power Range Neutron Flux - High reactor trip setpoint to less than or equal to the Maximum Allowable  
                                                            % RTP specified in Table 3.7.1-1 for the number of OPERABLE MSSVs.
% RTP specified in Table 3.7.1-1 for the number of OPERABLE MSSVs.
(continued)
36 hours (continued)  
Watts Bar - Unit 2                                          3.7-1 (developmental)                                                                                                              FI


MSSVs 3.7.1 ACTIONS (continued)
MSSVs 3.7.1 Watts Bar - Unit 2 3.7-2 (developmental)
CONDITION                                 REQUIRED ACTION                       COMPLETION TIME C. Required Action and                   C.1         Be in MODE 3.                     6 hours associated Completion Time not met.                        AND OR                                    C.2         Be in MODE 4.                     12 hours One or more steam generators with  4 MSSVs inoperable.
A ACTIONS (continued)
SURVEILLANCE REQUIREMENTS SURVEILLANCE                                                   FREQUENCY SR 3.7.1.1         -------------------------------NOTE------------------------------
CONDITION REQUIRED ACTION COMPLETION TIME C. Required Action and associated Completion Time not met.
OR One or more steam generators with 4 MSSVs inoperable.
C.1 Be in MODE 3.
6 hours AND C.2 Be in MODE 4.
12 hours SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.1.1  
-------------------------------NOTE------------------------------
Only required to be performed in MODES 1 and 2.
Only required to be performed in MODES 1 and 2.
Verify each required MSSV lift setpoint per                           In accordance with Table 3.7.1-2 in accordance with the Inservice                        the Inservice Testing Testing Program. Following testing, lift settings shall               Program be within +/- 1%.
Verify each required MSSV lift setpoint per Table 3.7.1-2 in accordance with the Inservice Testing Program. Following testing, lift settings shall be within +/- 1%.
Watts Bar - Unit 2                                    3.7-2 (developmental)                                                                                              A
In accordance with the Inservice Testing Program


MSSVs 3.7.1 Table 3.7.1-1 (page 1 of 1)
MSSVs 3.7.1 Watts Bar - Unit 2 3.7-3 (developmental)
OPERABLE Main Steam Safety Valves Versus Maximum Allowable Power NUMBER OF OPERABLE MSSVs                     MAXIMUM ALLOWABLE POWER PER STEAM GENERATOR                                    (% RTP) 3                                             4241 2                                             2625 Table 3.7.1-2 (page 1 of 1)
AI Table 3.7.1-1 (page 1 of 1)
Main Steam Safety Valve Lift Settings VALVE NUMBER LIFT SETTING STEAM GENERATOR                                    (psig +/- 3%)
OPERABLE Main Steam Safety Valves Versus Maximum Allowable Power NUMBER OF OPERABLE MSSVs PER STEAM GENERATOR MAXIMUM ALLOWABLE POWER
      #1               #2               #3                 #4 12-522           12-517           12-512             12-527           1224 12-523           12-518           12-513             12-528           1215 12-524           12-519           12-514             12-529           1205 12-525           12-520           12-515             12-530           1195 12-526           12-521           12-516             12-531           1185 Watts Bar - Unit 2                      3.7-3 (developmental)                                                                        AI
(% RTP) 3 4241 2
2625 Table 3.7.1-2 (page 1 of 1)
Main Steam Safety Valve Lift Settings VALVE NUMBER LIFT SETTING (psig +/- 3%)
STEAM GENERATOR
#1  
#2  
#3  
#4 12-522 12-517 12-512 12-527 1224 12-523 12-518 12-513 12-528 1215 12-524 12-519 12-514 12-529 1205 12-525 12-520 12-515 12-530 1195 12-526 12-521 12-516 12-531 1185  


MFIVs and MFRVs and Associated Bypass Valves 3.7.3 3.7 PLANT SYSTEMS 3.7.3 Main Feedwater Isolation Valves (MFIVs) and Main Feedwater Regulation Valves (MFRVs) and Associated Bypass Valves LCO 3.7.3                   Four MFIVs, four MFRVs, and associated bypass valves shall be OPERABLE.
MFIVs and MFRVs and Associated Bypass Valves 3.7.3 Watts Bar - Unit 2 3.7-6 (developmental)
APPLICABILITY:             MODES 1, 2, and 3 except when MFIV, MFRV, or associated bypass valve is closed and de-activated or isolated by a closed manual valve.
A 3.7 PLANT SYSTEMS 3.7.3 Main Feedwater Isolation Valves (MFIVs) and Main Feedwater Regulation Valves (MFRVs) and Associated Bypass Valves LCO 3.7.3 Four MFIVs, four MFRVs, and associated bypass valves shall be OPERABLE.
ACTIONS
APPLICABILITY:
MODES 1, 2, and 3 except when MFIV, MFRV, or associated bypass valve is closed and de-activated or isolated by a closed manual valve.
ACTIONS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each valve.
Separate Condition entry is allowed for each valve.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One or more MFIVs                         A.1           Close or isolate MFIV.               72 hours inoperable.
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more MFIVs inoperable.
AND A.2           Verify MFIV is closed or             Once per 7 days isolated.
A.1 Close or isolate MFIV.
B. One or more MFRVs                         B.1           Close or isolate MFRV.               72 hours inoperable.
72 hours AND A.2 Verify MFIV is closed or isolated.
AND B.2           Verify MFRV is closed or             Once per 7 days isolated.
Once per 7 days B. One or more MFRVs inoperable.
C. One or more MFIV or                       C.1           Restore bypass valve to               72 hours MFRV bypass valves                                    OPERABLE status.
B.1 Close or isolate MFRV.
inoperable.
72 hours AND B.2 Verify MFRV is closed or isolated.
(continued)
Once per 7 days C. One or more MFIV or MFRV bypass valves inoperable.
Watts Bar - Unit 2                                          3.7-6 (developmental)                                                                                                              A
C.1 Restore bypass valve to OPERABLE status.
72 hours (continued)  


MFIVs and MFRVs and Associated Bypass Valves 3.7.3 ACTIONS (continued)
MFIVs and MFRVs and Associated Bypass Valves 3.7.3 Watts Bar - Unit 2 3.7-7 (developmental)
CONDITION                         REQUIRED ACTION               COMPLETION TIME D. One MFIV and MFRV in the         D.1       Isolate affected flow path. 8 hours same flow path inoperable.
AI ACTIONS (continued)
E. One MFIV bypass valve            E.1       Restore one MFIV           8 hours and MFRV bypass valve in                    bypass valve or MFRV the same flow path                          bypass valve to inoperable.                                OPERABLE status.
CONDITION REQUIRED ACTION COMPLETION TIME D. One MFIV and MFRV in the same flow path inoperable.
F. Required Action and             EF.1       Be in MODE 3.               6 hours associated Completion Time not met.                    AND EF.2       Be in MODE 4.               12 hours SURVEILLANCE REQUIREMENTS SURVEILLANCE                                       FREQUENCY SR 3.7.3.1         Verify the closure time of each MFIV, MFRV, and         In accordance with associated bypass valve is 6.5 seconds on an           the Inservice Testing actual or simulated actuation signal.                   Program or 18 months Watts Bar - Unit 2                            3.7-7 (developmental)                                                                                AI
D.1 Isolate affected flow path.
8 hours E. One MFIV bypass valve and MFRV bypass valve in the same flow path inoperable.
E.1 Restore one MFIV bypass valve or MFRV bypass valve to OPERABLE status.
8 hours F. Required Action and associated Completion Time not met.
EF.1 Be in MODE 3.
6 hours AND EF.2 Be in MODE 4.
12 hours SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.3.1 Verify the closure time of each MFIV, MFRV, and associated bypass valve is 6.5 seconds on an actual or simulated actuation signal.
In accordance with the Inservice Testing Program or 18 months  


AC Sources - Operating 3.8.1 3.8 ELECTRICAL POWER SYSTEMS 3.8.1 AC Sources - Operating LCO 3.8.1                   The following AC electrical sources shall be OPERABLE:
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-1 (developmental)
: a. Two qualified circuits between the offsite transmission network and the onsite Class 1E AC Electrical Power Distribution System; and
F 3.8 ELECTRICAL POWER SYSTEMS 3.8.1 AC Sources - Operating LCO 3.8.1 The following AC electrical sources shall be OPERABLE:
: b. Four diesel generators (DGs) capable of supplying the onsite Class 1E AC Electrical Power Distribution System.
: a.
APPLICABILITY:             MODES 1, 2, 3, and 4.
Two qualified circuits between the offsite transmission network and the onsite Class 1E AC Electrical Power Distribution System; and
ACTIONS
: b.
Four diesel generators (DGs) capable of supplying the onsite Class 1E AC Electrical Power Distribution System.
APPLICABILITY:
MODES 1, 2, 3, and 4.
ACTIONS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
LCO 3.0.4.b is not applicable to DGs.
LCO 3.0.4.b is not applicable to DGs.
CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One offsite circuit                       A.1           Perform SR 3.8.1.1 for               1 hour inoperable.                                            OPERABLE offsite circuit.
CONDITION REQUIRED ACTION COMPLETION TIME A. One offsite circuit inoperable.
AND Once per 8 hours thereafter AND A.2           Declare required                     24 hours from feature(s) with no offsite            discovery of no offsite power available                       power to one train inoperable when its                   concurrent with redundant required                   inoperability of feature(s) is inoperable.             redundant required feature(s)
A.1 Perform SR 3.8.1.1 for OPERABLE offsite circuit.
AND (continued)
1 hour AND Once per 8 hours thereafter AND A.2 Declare required feature(s) with no offsite power available inoperable when its redundant required feature(s) is inoperable.
Watts Bar - Unit 2                                          3.8-1 (developmental)                                                                                                              F
24 hours from discovery of no offsite power to one train concurrent with inoperability of redundant required feature(s)
AND (continued)  


AC Sources - Operating 3.8.1 ACTIONS CONDITION           REQUIRED ACTION               COMPLETION TIME A. (continued)         A.3     Restore offsite circuit to 72 hours OPERABLE status.
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-2 (developmental)
AND 6 days from discovery of failure to meet LCO B. One or more DG(s) in B.1     Perform SR 3.8.1.1 for     1 hour Train A inoperable.          the offsite circuits.
F ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)
AND OR Once per 8 hours One or more DG(s) in                                    thereafter Train B inoperable.
A.3 Restore offsite circuit to OPERABLE status.
AND B.2     Declare required           4 hours from feature(s) supported by     discovery of the inoperable DG(s)       Condition B inoperable when its         concurrent with required redundant         inoperability of feature(s) is inoperable   redundant required feature(s)
72 hours AND 6 days from discovery of failure to meet LCO B. One or more DG(s) in Train A inoperable.
AND B.3.1   Determine OPERABLE         24 hours DG(s) is not inoperable due to common cause failure.
OR One or more DG(s) in Train B inoperable.
OR B.3.2   Perform SR 3.8.1.2 for     24 hours OPERABLE DG(s).
B.1 Perform SR 3.8.1.1 for the offsite circuits.
AND (continued)
1 hour AND Once per 8 hours thereafter AND B.2 Declare required feature(s) supported by the inoperable DG(s) inoperable when its required redundant feature(s) is inoperable 4 hours from discovery of Condition B concurrent with inoperability of redundant required feature(s)
Watts Bar - Unit 2              3.8-2 (developmental)                                                                    F
AND B.3.1 Determine OPERABLE DG(s) is not inoperable due to common cause failure.
24 hours OR B.3.2 Perform SR 3.8.1.2 for OPERABLE DG(s).
24 hours AND (continued)  


AC Sources - Operating 3.8.1 ACTIONS CONDITION                     REQUIRED ACTION                         COMPLETION TIME B. (continued)               B.4           Restore required DG(s) to         72 hours OPERABLE status.
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-3 (developmental)
AND 6 days from discovery of failure to meet LCO C. Two offsite circuits       C.1           Declare required                   12 hours from inoperable.                              feature(s) inoperable             discovery of when its redundant                 Condition C required feature(s) is             concurrent with inoperable.                        inoperability of redundant required features AND C.2           Restore one offsite circuit       24 hours to OPERABLE status.
A ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. (continued)
D. One offsite circuit       --------------------NOTE-------------------
B.4 Restore required DG(s) to OPERABLE status.
inoperable.                Enter applicable Conditions and Required Actions of LCO 3.8.9, AND                        "Distribution Systems - Operating,"
72 hours AND 6 days from discovery of failure to meet LCO C. Two offsite circuits inoperable.
when Condition D is entered with no One or more required DG(s) AC power source to any train.
C.1 Declare required feature(s) inoperable when its redundant required feature(s) is inoperable.
in Train A inoperable.
12 hours from discovery of Condition C concurrent with inoperability of redundant required features AND C.2 Restore one offsite circuit to OPERABLE status.
OR D.1           Restore offsite circuit to         12 hours One or more required DG(s)              OPERABLE status.
24 hours D. One offsite circuit inoperable.
in Train B inoperable.
AND One or more required DG(s) in Train A inoperable.
OR D.2           Restore required DG(s) to         12 hours OPERABLE status.
OR One or more required DG(s) in Train B inoperable.
(continued)
--------------------NOTE-------------------
Watts Bar - Unit 2                          3.8-3 (developmental)                                                                                      A
Enter applicable Conditions and Required Actions of LCO 3.8.9, "Distribution Systems - Operating,"
when Condition D is entered with no AC power source to any train.
D.1 Restore offsite circuit to OPERABLE status.
12 hours OR D.2 Restore required DG(s) to OPERABLE status.
12 hours (continued)  


AC Sources - Operating 3.8.1 ACTIONS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-4 (developmental)
CONDITION               REQUIRED ACTION             COMPLETION TIME E. One or more required DG(s) E.1  Restore required DGs in  2 hours in Train A inoperable.          Train A to OPERABLE status.
A ACTIONS (continued)
AND OR One or more required DG(s) in Train B inoperable. E.Restore required DGs in 2 hours Train B to OPERABLE status.
CONDITION REQUIRED ACTION COMPLETION TIME E. One or more required DG(s) in Train A inoperable.
F. Required Action and       F.1  Be in MODE 3.            6 hours Associated Completion Time of Condition A. B, C, AND D, or E not met.
AND One or more required DG(s) in Train B inoperable.
F.2   Be in MODE 5.           36 hours G. Two offsite circuits       G.1  Enter LCO 3.0.3.        Immediately inoperable.
E.1 Restore required DGs in Train A to OPERABLE status.
2 hours OR E.2 Restore required DGs in Train B to OPERABLE status.
2 hours F. Required Action and Associated Completion Time of Condition A. B, C, D, or E not met.
F.1 Be in MODE 3.
6 hours AND F.2 Be in MODE 5.
36 hours G. Two offsite circuits inoperable.
AND One or more required DG(s) in Train A inoperable.
AND One or more required DG(s) in Train A inoperable.
OR One or more required DG(s) in Train B inoperable.
OR One or more required DG(s) in Train B inoperable.
H. One offsite circuit        H.1   Enter LCO 3.0.3.         Immediately inoperable.
G.1 Enter LCO 3.0.3.
Immediately H. One offsite circuit inoperable.
AND One or more required DG(s) in Train A inoperable.
AND One or more required DG(s) in Train A inoperable.
AND One or more required DG(s) in Train B inoperable.
AND One or more required DG(s) in Train B inoperable.
Watts Bar - Unit 2                  3.8-4 (developmental)                                                                  A
H.1 Enter LCO 3.0.3.
Immediately


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                                   FREQUENCY SR 3.8.1.1         Verify correct breaker alignment and indicated power                   7 days availability for each offsite circuit.
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-5 (developmental)
SR 3.8.1.2         -------------------------------NOTES----------------------------
AI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.1.1 Verify correct breaker alignment and indicated power availability for each offsite circuit.
7 days SR 3.8.1.2  
-------------------------------NOTES----------------------------
: 1. Performance of SR 3.8.1.7 satisfies this SR.
: 1. Performance of SR 3.8.1.7 satisfies this SR.
: 2. A modified DG start involving idling and gradual acceleration to synchronous speed may be used for this SR as recommended by the manufacturer. When modified start procedures are not used, the time, voltage, and frequency tolerances of SR 3.8.1.7 must be met.
: 2. A modified DG start involving idling and gradual acceleration to synchronous speed may be used for this SR as recommended by the manufacturer. When modified start procedures are not used, the time, voltage, and frequency tolerances of SR 3.8.1.7 must be met.
Verify each DG starts from standby conditions and                       As specified in achieves steady state voltage 6800 V and                             Table 3.8.1-1 7260 V, and frequency 58.8 Hz and 61.2 Hz60.0 Hz nominal.
Verify each DG starts from standby conditions and achieves steady state voltage 6800 V and 7260 V, and frequency 58.8 Hz and 61.2 Hz60.0 Hz nominal.
SR 3.8.1.3         -------------------------------NOTES----------------------------
As specified in Table 3.8.1-1 SR 3.8.1.3  
-------------------------------NOTES----------------------------
: 1. DG loadings may include gradual loading as recommended by the manufacturer.
: 1. DG loadings may include gradual loading as recommended by the manufacturer.
: 2. Momentary transients outside the load range do not invalidate this test.
: 2. Momentary transients outside the load range do not invalidate this test.
: 3. This Surveillance shall be conducted on only one DG at a time.
: 3. This Surveillance shall be conducted on only one DG at a time.
: 4. This SR shall be preceded by and immediately follow without shutdown a successful performance of SR 3.8.1.2 or SR 3.8.1.7.
: 4. This SR shall be preceded by and immediately follow without shutdown a successful performance of SR 3.8.1.2 or SR 3.8.1.7.
Verify each DG is synchronized and loaded and                           As specified in operates for 60 minutes at a load                                     Table 3.8.1-1 3960 kW and  4400 kW.
Verify each DG is synchronized and loaded and operates for 60 minutes at a load 3960 kW and 4400 kW.
SR 3.8.1.4         Verify each skid mounted day tank contains                             31 days 218.5 gal of fuel oil.
As specified in Table 3.8.1-1 SR 3.8.1.4 Verify each skid mounted day tank contains 218.5 gal of fuel oil.
Watts Bar - Unit 2                                    3.8-5 (developmental)                                                                                              AI
31 days


AC Sources - Operating 3.8.1 (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-6 (developmental)
Watts Bar - Unit 2 3.8-6 (developmental)                               AI
AI (continued)


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-7 (developmental)
SURVEILLANCE                                                   FREQUENCY SR 3.8.1.5         Check for and remove accumulated water from each                       31 days skid mounted day tank.
AI SURVEILLANCE REQUIREMENTS (continued)
SR 3.8.1.6         Verify the fuel oil transfer system operates to                         31 days automatically transfer fuel oil from 7 day storage tank to the skid mounted day tank.
SURVEILLANCE FREQUENCY SR 3.8.1.5 Check for and remove accumulated water from each skid mounted day tank.
SR 3.8.1.7         Verify each DG starts from standby condition and                       184 days achieves in 10 seconds, voltage 6800 V, and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.2 60.1 Hz.
31 days SR 3.8.1.6 Verify the fuel oil transfer system operates to automatically transfer fuel oil from 7 day storage tank to the skid mounted day tank.
SR 3.8.1.8         -------------------------------NOTE------------------------------
31 days SR 3.8.1.7 Verify each DG starts from standby condition and achieves in 10 seconds, voltage 6800 V, and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.2 60.1 Hz.
184 days SR 3.8.1.8  
-------------------------------NOTE------------------------------
For the 2A-A and 2B-B Shutdown Boards, This this Surveillance shall not be performed in MODE 1 or 2.
For the 2A-A and 2B-B Shutdown Boards, This this Surveillance shall not be performed in MODE 1 or 2.
However, credit may be taken for unplanned events that satisfy this SR.
However, credit may be taken for unplanned events that satisfy this SR.
Verify automatic and manual transfer of each                           18 months 6.9 kV shutdown board power supply from the normal offsite circuit to each alternate offsite circuit.
Verify automatic and manual transfer of each 6.9 kV shutdown board power supply from the normal offsite circuit to each alternate offsite circuit.
(continued)
18 months (continued)  
Watts Bar - Unit 2                                    3.8-7 (developmental)                                                                                              AI


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-8 (developmental)
SURVEILLANCE                                                   FREQUENCY SR 3.8.1.9         -------------------------------NOTES----------------------------
AI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.9  
-------------------------------NOTES----------------------------
: 1. For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2.
: 1. For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2.
However, credit may be taken for unplanned events that satisfy this SR.
However, credit may be taken for unplanned events that satisfy this SR.
: 2. If performed with the DG synchronized with offsite power, it shall be performed at a power factor 0.8 and 0.9.
: 2. If performed with the DG synchronized with offsite power, it shall be performed at a power factor 0.8 and 0.9.
Verify each DG rejects a load greater than or equal                     18 months to its associated single largest post-accident load, and:
Verify each DG rejects a load greater than or equal to its associated single largest post-accident load, and:
: a. Following load rejection, the frequency is 66.75 Hz;
: a.
: b. Within 3 seconds following load rejection, the voltage is 6555 V and 7260 V; and
Following load rejection, the frequency is 66.75 Hz;
: c. Within 4 seconds following load rejection, the frequency is 58.8 Hz and 61.2 Hz.
: b.
SR 3.8.1.10       -------------------------------NOTE------------------------------
Within 3 seconds following load rejection, the voltage is 6555 V and 7260 V; and
: c.
Within 4 seconds following load rejection, the frequency is 58.8 Hz and 61.2 Hz.
18 months SR 3.8.1.10  
-------------------------------NOTE------------------------------
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
Verify each DG operating at a power factor 0.8 and                   18 months 0.9 does not trip and voltage is maintained 8880 V during and following a load rejection of 3960 kW and 4400 kW and 2970 kVAR and 3300 kVAR.
Verify each DG operating at a power factor 0.8 and 0.9 does not trip and voltage is maintained 8880 V during and following a load rejection of 3960 kW and 4400 kW and 2970 kVAR and 3300 kVAR.
(continued)
18 months (continued)  
Watts Bar - Unit 2                                    3.8-8 (developmental)                                                                                              AI


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-9 (developmental)
SURVEILLANCE                                                   FREQUENCY SR 3.8.1.11       -------------------------------NOTE------------------------------
AI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.11  
-------------------------------NOTE------------------------------
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
Verify on an actual or simulated loss of offsite power                 18 months signal:
Verify on an actual or simulated loss of offsite power signal:
: a. De-energization of emergency buses;
: a.
: b. Load shedding from emergency buses;
De-energization of emergency buses;
: c. DG auto-starts from standby condition and:
: b.
Load shedding from emergency buses;
: c.
DG auto-starts from standby condition and:
: 1. energizes permanently connected loads in 10 seconds,
: 1. energizes permanently connected loads in 10 seconds,
: 2. energizes auto-connected shutdown loads through automatic load sequencer,
: 2. energizes auto-connected shutdown loads through automatic load sequencer,
: 3. maintains steady state voltage 6800 V and 7260 V,
: 3. maintains steady state voltage 6800 V and 7260 V,
: 4. maintains steady state frequency 58.859.8 Hz and 61.260.1 Hz, and
: 4. maintains steady state frequency 58.859.8 Hz and 61.260.1 Hz, and
: 5. supplies permanently connected and auto-connected shutdown loads for 5 minutes.
: 5. supplies permanently connected and auto-connected shutdown loads for 5 minutes.
(continued)
18 months (continued)  
Watts Bar - Unit 2                                    3.8-9 (developmental)                                                                                              AI


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-10 (developmental)
SURVEILLANCE                                                   FREQUENCY SR 3.8.1.12       -------------------------------NOTE------------------------------
AI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.12  
-------------------------------NOTE------------------------------
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
Verify on an actual or simulated Engineered Safety                     18 months Feature (ESF) actuation signal each Unit 2 DG auto-starts from standby condition and:
Verify on an actual or simulated Engineered Safety Feature (ESF) actuation signal each Unit 2 DG auto-starts from standby condition and:
: a. In 10 seconds after auto-start and during tests, achieves voltage 6800 V and frequency 58.8 Hz;
: a.
: b. After DG fast start from standby conditions the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.2 60.1 Hz.
In 10 seconds after auto-start and during tests, achieves voltage 6800 V and frequency 58.8 Hz;
: c. Operates for 5 minutes;
: b.
: d. Permanently connected loads remain energized from the offsite power system; and
After DG fast start from standby conditions the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.2 60.1 Hz.
: e. Emergency loads are energized from the offsite power system.
: c.
SR 3.8.1.13       -------------------------------NOTE------------------------------
Operates for 5 minutes;
: d.
Permanently connected loads remain energized from the offsite power system; and
: e.
Emergency loads are energized from the offsite power system.
18 months SR 3.8.1.13  
-------------------------------NOTE------------------------------
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.
Verify each DG's automatic trips are bypassed on                       18 months automatic or emergency start signal except:
Verify each DG's automatic trips are bypassed on automatic or emergency start signal except:
: a. Engine overspeed; and
: a.
: b. Generator differential current (continued)
Engine overspeed; and
Watts Bar - Unit 2                                    3.8-10 (developmental)                                                                                              AI
: b.
Generator differential current 18 months (continued)  


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-11 (developmental)
SURVEILLANCE                                                   FREQUENCY SR 3.8.1.14       -------------------------------NOTES----------------------------
AI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.14  
-------------------------------NOTES----------------------------
: 1. Momentary transients outside the load and power factor ranges do not invalidate this test.
: 1. Momentary transients outside the load and power factor ranges do not invalidate this test.
: 2. For performance of this test in MODE 1, 2, 3 or 4, three DGs must be maintained operable and in a standby condition.
: 2. For performance of this test in MODE 1, 2, 3 or 4, three DGs must be maintained operable and in a standby condition.
: 3. Credit may be taken for unplanned events that satisfy this SR.
: 3. Credit may be taken for unplanned events that satisfy this SR.
Verify each DG operating at a power factor                             18 months 0.8 and 0.9 operates for 24 hours:
Verify each DG operating at a power factor 0.8 and 0.9 operates for 24 hours:
: a. For 2 hours loaded 4620 kW and 4840 kW and 3465 kVAR and 3630 kVAR; and
: a.
: b. For the remaining hours of the test loaded 3960 kW and 4400 kW and 2970 kVAR and 3300 kVAR.
For 2 hours loaded 4620 kW and 4840 kW and 3465 kVAR and 3630 kVAR; and
SR 3.8.1.15       -------------------------------NOTES----------------------------
: b.
This Surveillance shall be performed within 5 minutes of shutting down the DG after the DG has operated 2 hours loaded 3960 kW and 4400 kW.
For the remaining hours of the test loaded 3960 kW and 4400 kW and 2970 kVAR and 3300 kVAR.
18 months SR 3.8.1.15  
-------------------------------NOTES----------------------------
This Surveillance shall be performed within 5 minutes of shutting down the DG after the DG has operated 2 hours loaded 3960 kW and 4400 kW.
Momentary transients outside of load range do not invalidate this test.
Momentary transients outside of load range do not invalidate this test.
Verify each DG starts and achieves, in 10 seconds,                   18 months voltage 6800 V, and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.260.1 Hz.
Verify each DG starts and achieves, in 10 seconds, voltage 6800 V, and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.260.1 Hz.
(continued)
18 months (continued)  
Watts Bar - Unit 2                                    3.8-11 (developmental)                                                                                              AI


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-12 (developmental)
SURVEILLANCE                                                   FREQUENCY SR 3.8.1.16       -------------------------------NOTE------------------------------
AI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.16  
-------------------------------NOTE------------------------------
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
Verify each DG:                                                         18 months
Verify each DG:
: a. Synchronizes with offsite power source while loaded with emergency loads upon a simulated restoration of offsite power;
: a.
: b. Transfers loads to offsite power source; and
Synchronizes with offsite power source while loaded with emergency loads upon a simulated restoration of offsite power;
: c. Returns to ready-to-load operation.
: b.
SR 3.8.1.17       -------------------------------NOTE------------------------------
Transfers loads to offsite power source; and
: c.
Returns to ready-to-load operation.
18 months SR 3.8.1.17  
-------------------------------NOTE------------------------------
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
Verify, DG 2A-A and 2B-B with each Unit 2 DG                           18 months operating in test mode and connected to its bus, an actual or simulated ESF actuation signal overrides the test mode by:
Verify, DG 2A-A and 2B-B with each Unit 2 DG operating in test mode and connected to its bus, an actual or simulated ESF actuation signal overrides the test mode by:
: a. Returning DG to ready-to-load operation; and
: a.
: b. Automatically energizing the emergency load from offsite power.
Returning DG to ready-to-load operation; and
(continued)
: b.
Watts Bar - Unit 2                                    3.8-12 (developmental)                                                                                              AI
Automatically energizing the emergency load from offsite power.
18 months (continued)  


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-13 (developmental)
SURVEILLANCE                                                   FREQUENCY SR 3.8.1.18       -------------------------------NOTE------------------------------
AI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.1.18  
-------------------------------NOTE------------------------------
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
Verify the time delay setting for each sequenced load                   18 months block is within limits for each accident condition and non-accident condition load sequence.
Verify the time delay setting for each sequenced load block is within limits for each accident condition and non-accident condition load sequence.
SR 3.8.1.19       -------------------------------NOTE------------------------------
18 months SR 3.8.1.19  
-------------------------------NOTE------------------------------
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
Verify on an actual or simulated loss of offsite power                 18 months signal in conjunction with an actual or simulated ESF actuation signal:
Verify on an actual or simulated loss of offsite power signal in conjunction with an actual or simulated ESF actuation signal:
: a. De-energization of emergency buses;
: a.
: b. Load shedding from emergency buses; and
De-energization of emergency buses;
: c. DGs of the same power train auto-start from standby condition and:
: b.
Load shedding from emergency buses; and
: c.
DGs of the same power train auto-start from standby condition and:
: 1. energizes permanently connected loads in 10 seconds,
: 1. energizes permanently connected loads in 10 seconds,
: 2. energizes auto-connected emergency loads through load sequencer,
: 2. energizes auto-connected emergency loads through load sequencer,
: 3. achieves steady state voltage:
: 3. achieves steady state voltage:
6800 V and 7260 V,
6800 V and 7260 V,
: 4. achieves steady state frequency 58.859.8 Hz and 61.260.1 Hz, and
: 4. achieves steady state frequency 58.859.8 Hz and 61.260.1 Hz, and
: 5. supplies permanently connected and auto-connected emergency loads for 5 minutes.
: 5. supplies permanently connected and auto-connected emergency loads for 5 minutes.
(continued)
18 months (continued)  
Watts Bar - Unit 2                                    3.8-13 (developmental)                                                                                              AI


AC Sources - Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-14 (developmental)
SURVEILLANCE                                         FREQUENCY SR 3.8.1.20       Verify during idle operation that any automatic or         18 months emergency start signal disables the idle start circuitry and commands the engine to full speed.
AI SURVEILLANCE REQUIREMENTS (continued)
SR 3.8.1.21       Verify when started simultaneously from standby           10 years condition, each DG achieves, in 10 seconds, voltage 6800 V and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.260.1 Hz.
SURVEILLANCE FREQUENCY SR 3.8.1.20 Verify during idle operation that any automatic or emergency start signal disables the idle start circuitry and commands the engine to full speed.
Watts Bar - Unit 2                            3.8-14 (developmental)                                                                                AI
18 months SR 3.8.1.21 Verify when started simultaneously from standby condition, each DG achieves, in 10 seconds, voltage 6800 V and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.260.1 Hz.
10 years


AC Sources - Operating 3.8.1 Table 3.8.1-1 (page 1 of 1)
AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-15 (developmental)
Diesel Generator Test Schedule NUMBER OF FAILURES IN LAST 25 VALID TESTS(a)                                   FREQUENCY 3                                               31 days 4                                               7 days(b)
AI Table 3.8.1-1 (page 1 of 1)
Diesel Generator Test Schedule NUMBER OF FAILURES IN LAST 25 VALID TESTS(a)
FREQUENCY 3
31 days 4
7 days(b)
(but no less than 24 hours)
(but no less than 24 hours)
(a) Criteria for determining number of failures and valid tests shall be in accordance with Regulatory Position C.2.1 of Regulatory Guide 1.9, Revision 3, where the number of tests and failures is determined on a per DG basis.
(a) Criteria for determining number of failures and valid tests shall be in accordance with Regulatory Position C.2.1 of Regulatory Guide 1.9, Revision 3, where the number of tests and failures is determined on a per DG basis.
(b) This test frequency shall be maintained until seven consecutive failure free starts from standby conditions and load and run tests have been performed. If, subsequent to the 7 failure free tests, 1 or more additional failures occur, such that there are again 4 or more failures in the last 25 tests, the testing interval shall again be reduced as noted above and maintained until 7 consecutive failure free tests have been performed.
(b) This test frequency shall be maintained until seven consecutive failure free starts from standby conditions and load and run tests have been performed. If, subsequent to the 7 failure free tests, 1 or more additional failures occur, such that there are again 4 or more failures in the last 25 tests, the testing interval shall again be reduced as noted above and maintained until 7 consecutive failure free tests have been performed.  
Watts Bar - Unit 2                              3.8-15 (developmental)                                                                                  AI


DC Sources - Operating 3.8.4 3.8 ELECTRICAL POWER SYSTEMS 3.8.4 DC Sources - Operating LCO 3.8.4             Four channels of vital DC and four Diesel Generator (DG) DC electrical power subsystems shall be OPERABLE.
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-21 (developmental)
                      ---------------------------------------------NOTES-------------------------------------------
HI 3.8 ELECTRICAL POWER SYSTEMS 3.8.4 DC Sources - Operating LCO 3.8.4 Four channels of vital DC and four Diesel Generator (DG) DC electrical power subsystems shall be OPERABLE.  
: 1. Vital Battery V may be substituted for any of the required vital batteries.
---------------------------------------------NOTES-------------------------------------------
: 2. Spare Vital Chargers 6-S, 7-S, 8-S, or 9-S may be substituted for required Vital chargers.
: 1.
: 3. Spare DG Chargers 1A1, 1B1, 2A1, or 2B1 may be substituted for required DG chargers.
Vital Battery V may be substituted for any of the required vital batteries.
APPLICABILITY:       MODES 1, 2, 3, and 4.
: 2.
ACTIONS CONDITION                             REQUIRED ACTION                           COMPLETION TIME A. One required vital DC               A.1         Restore vital DC electrical           2 hours electrical power subsystem                      power subsystem to inoperablebattery charger                        OPERABLE statusbattery inoperable.                                      terminal voltage to greater than or equal to the minimum established float voltage.
Spare Vital Chargers 6-S, 7-S, 8-S, or 9-S may be substituted for required Vital chargers.
AND A.2         Verify vital battery                   Once per 12 hours charger float current
: 3.
                                                    < 2 amps.
Spare DG Chargers 1A1, 1B1, 2A1, or 2B1 may be substituted for required DG chargers.
AND A.3         Restore vital battery                 72 hours charger to OPERABLE status.
APPLICABILITY:
Watts Bar - Unit 2                                  3.8-21 (developmental)                                                                                                      HI
MODES 1, 2, 3, and 4.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required vital DC electrical power subsystem inoperablebattery charger inoperable.
A.1 Restore vital DC electrical power subsystem to OPERABLE statusbattery terminal voltage to greater than or equal to the minimum established float voltage.
2 hours AND A.2 Verify vital battery charger float current  
< 2 amps.
Once per 12 hours AND A.3 Restore vital battery charger to OPERABLE status.
72 hours


DC Sources - Operating 3.8.4 (continued)
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-22 (developmental)
Watts Bar - Unit 2 3.8-22 (developmental)                               HI
HI (continued)


DC Sources - Operating 3.8.4 ACTIONS (continued)
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-23 (developmental)
CONDITION                 REQUIRED ACTION             COMPLETION TIME B. Required Action and         B.1  Restore vital battery to  2 6 hours Associated Completion             OPERABLE statusBe in Time of Condition A not           MODE 3.
HI ACTIONS (continued)
metOne required vital battery inoperable.         AND B.2   Be in MODE 5.             36 hours C. One DG DC electrical         C.1  Restore DG DC electrical  2 hours power subsystem                   power subsystem to inoperable.One required           OPRABLE statusRestore vital DC channel inoperable       vital DC channel to for reasons other than             OPERABLE status.
CONDITION REQUIRED ACTION COMPLETION TIME B. Required Action and Associated Completion Time of Condition A not metOne required vital battery inoperable.
Condition A or B..
B.1 AND B.2 Restore vital battery to OPERABLE statusBe in MODE 3.
D. Required Action and         D.1  Declare associated DG      6 hoursImmediately Associated Completion             inoperable.Be in Time of Condition A, B, or C       MODE 3.
Be in MODE 5.
not met.
2 6 hours 36 hours C. One DG DC electrical power subsystem inoperable.One required vital DC channel inoperable for reasons other than Condition A or B..
AND D.2   Be in MODE 5.             36 hours E. One required DG battery     E.1   Restore DG battery         2 hours charger inoperable.                terminal voltage to greater than or equal to the minimum established float voltage.
C.1 Restore DG DC electrical power subsystem to OPRABLE statusRestore vital DC channel to OPERABLE status.
AND E.2   Verify DG battery charger Once per 12 hours float current < 2 amps.
2 hours D. Required Action and Associated Completion Time of Condition A, B, or C not met.
AND E.3   Restore DG battery         72 hours charger to OPERABLE status.
D.1 Declare associated DG inoperable.Be in MODE 3.
Watts Bar - Unit 2                  3.8-23 (developmental)                                                                    HI
6 hoursImmediately AND D.2 Be in MODE 5.
36 hours E. One required DG battery charger inoperable.
E.1 Restore DG battery terminal voltage to greater than or equal to the minimum established float voltage.
2 hours AND E.2 Verify DG battery charger float current < 2 amps.
Once per 12 hours AND E.3 Restore DG battery charger to OPERABLE status.
72 hours


DC Sources - Operating 3.8.4 F. One required DG battery F.1 Restore DG battery to 2 hours inoperable.                OPERABLE status.
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-24 (developmental)
(continued)
HI F. One required DG battery inoperable.
Watts Bar - Unit 2            3.8-24 (developmental)                                                          HI
F.1 Restore DG battery to OPERABLE status.
2 hours (continued)  


DC Sources - Operating 3.8.4 ACTIONS (continued)
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-25 (developmental)
CONDITION                           REQUIRED ACTION                 COMPLETION TIME G. One required DG DC                G.1        Restore DG DC electrical    2 hours electrical power subsystem                   power subsystem to inoperable for reasons other                 OPERABLE status than Condition E or F.
H ACTIONS (continued)
H. Required Action and               H.1        Declare associated DG      Immediately associated Completion                         inoperable.
CONDITION REQUIRED ACTION COMPLETION TIME G. One required DG DC electrical power subsystem inoperable for reasons other than Condition E or F.
Time of Condition E, F, or G not met SURVEILLANCE REQUIREMENTS SURVEILLANCE                                       FREQUENCY SR 3.8.4.1         Verify vital battery terminal voltage is 128 V (132 V   7 days for vital battery V) on float chargegreater than or equal to the minimum established float voltage.
G.1 Restore DG DC electrical power subsystem to OPERABLE status 2 hours H. Required Action and associated Completion Time of Condition E, F, or G not met H.1 Declare associated DG inoperable.
SR 3.8.4.2         Verify DG battery terminal voltage is 124 V on float     7 days chargegreater than or equal to the minimum established float voltage.
Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.4.1 Verify vital battery terminal voltage is 128 V (132 V for vital battery V) on float chargegreater than or equal to the minimum established float voltage.
SR 3.8.4.3         Verify for the vital batteries that the alternate feeder   7 days breakers to each required battery charger are open.
7 days SR 3.8.4.2 Verify DG battery terminal voltage is 124 V on float chargegreater than or equal to the minimum established float voltage.
SR 3.8.4.4         Verify correct breaker alignment and indicated power       7 days availability for each DG 125 V DC distribution panel and associated battery charger (continued)
7 days SR 3.8.4.3 Verify for the vital batteries that the alternate feeder breakers to each required battery charger are open.
Watts Bar - Unit 2                              3.8-25 (developmental)                                                                                  H
7 days SR 3.8.4.4 Verify correct breaker alignment and indicated power availability for each DG 125 V DC distribution panel and associated battery charger 7 days (continued)  


DC Sources - Operating 3.8.4 SURVEILLANCE REQUIREMENTS (continued)
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-26 (developmental)
SURVEILLANCE                                       FREQUENCY SR 3.8.4.5         Verify no visible corrosion at terminals and             18 months92 days connectors for the vital batterieseach vital battery charger supplies > 200 amps at greater than or equal to the minimum established float voltage for
HI SURVEILLANCE REQUIREMENTS (continued)
                  > 4 hours.
SURVEILLANCE FREQUENCY SR 3.8.4.5 Verify no visible corrosion at terminals and connectors for the vital batterieseach vital battery charger supplies > 200 amps at greater than or equal to the minimum established float voltage for  
> 4 hours.
OR Verify connection resistance for the vital batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-rack connections, 120 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.
OR Verify connection resistance for the vital batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-rack connections, 120 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.
Verify each vital battery charger can recharge the battery to the fully charged state within 24 hours while supplying the largest combined demands of the various continuous steady state loads, after a battery discharge to the bounding design basis event discharge state.
Verify each vital battery charger can recharge the battery to the fully charged state within 24 hours while supplying the largest combined demands of the various continuous steady state loads, after a battery discharge to the bounding design basis event discharge state.
SR 3.8.4.6         Verify no visible corrosion at terminals and             18 months92 days connectors for the DG batteries each DG battery charger supplies > 200 amps at greater than or equal to the minimum established float voltage for
18 months92 days SR 3.8.4.6 Verify no visible corrosion at terminals and connectors for the DG batteries each DG battery charger supplies > 200 amps at greater than or equal to the minimum established float voltage for  
                  > 4 hours.
> 4 hours.
OR Verify connection resistance for the DG batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.
OR Verify connection resistance for the DG batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.
Verify each DG battery charger can recharge the battery to the fully charged state within 24 hours while supplying the largest combined demands of the various continuous steady state loads, after a battery discharge to the bounding design basis event discharge state.
Verify each DG battery charger can recharge the battery to the fully charged state within 24 hours while supplying the largest combined demands of the various continuous steady state loads, after a battery discharge to the bounding design basis event discharge state.
Watts Bar - Unit 2                            3.8-26 (developmental)                                                                                HI
18 months92 days


DC Sources - Operating 3.8.4 SR 3.8.4.7         -------------------------------NOTES----------------------------       18 12 months
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-27 (developmental)
HI SR 3.8.4.7  
-------------------------------NOTES----------------------------
: 1. The modified performance discharge test in SR 3.8.4.6 may be performed in lieu of the service test in SR 3.8.4.7 once per 60 months.
: 1. The modified performance discharge test in SR 3.8.4.6 may be performed in lieu of the service test in SR 3.8.4.7 once per 60 months.
: 2. Credit may be taken for unplanned events that satisfy this SR.
: 2. Credit may be taken for unplanned events that satisfy this SR.
Verify battery cells, cell plates, and racks show no visual indication of physical damage or abnormal deteriorationcapacity is adequate to supply, and maintain in OPERABLE status, the required emergency loads and any connected nonsafety loads for the design duty cycle when subjected to a battery service test.
Verify battery cells, cell plates, and racks show no visual indication of physical damage or abnormal deteriorationcapacity is adequate to supply, and maintain in OPERABLE status, the required emergency loads and any connected nonsafety loads for the design duty cycle when subjected to a battery service test.
SR 3.8.4.8         Remove visible terminal corrosion and verify battery                   12 months cell to cell and terminal connections are coated with anti-corrosion material.
18 12 months SR 3.8.4.8 Remove visible terminal corrosion and verify battery cell to cell and terminal connections are coated with anti-corrosion material.
SR 3.8.4.9         Verify connection resistance for the vital batteries is                 12 months 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-rack connections, 120 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.
12 months SR 3.8.4.9 Verify connection resistance for the vital batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-rack connections, 120 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.
SR 3.8.4.10       Verify connection resistance for the DG batteries is                   12 months 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.
12 months SR 3.8.4.10 Verify connection resistance for the DG batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.
Watts Bar - Unit 2                                    3.8-27 (developmental)                                                                                              HI
12 months


DC Sources - Operating 3.8.4 SR 3.8.4.11       -------------------------------NOTE------------------------------
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-28 (developmental)
HI SR 3.8.4.11  
-------------------------------NOTE------------------------------
This Surveillance is normally not performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
This Surveillance is normally not performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.
Verify each vital battery charger is capable of                         18 months recharging its associated battery from a service or capacity discharge test while supplying normal loads.
Verify each vital battery charger is capable of recharging its associated battery from a service or capacity discharge test while supplying normal loads.
OR Verify each vital battery charger is capable of operating for 4 hours at current limit 220 - 250 amps.
OR Verify each vital battery charger is capable of operating for 4 hours at current limit 220 - 250 amps.
SR 3.8.4.12       -------------------------------NOTE------------------------------
18 months SR 3.8.4.12  
-------------------------------NOTE------------------------------
Credit may be taken for unplanned events that satisfy this SR.
Credit may be taken for unplanned events that satisfy this SR.
Verify each diesel generator battery charger is capable of recharging its associated battery from a                     18 months service or capacity discharge test while supplying normal loads.
Verify each diesel generator battery charger is capable of recharging its associated battery from a service or capacity discharge test while supplying normal loads.
SR 3.8.4.13       -------------------------------NOTES----------------------------
18 months SR 3.8.4.13  
-------------------------------NOTES----------------------------
: 1. The modified performance discharge test in SR 3.8.4.14 may be performed in lieu of the service test in SR 3.8.4.13 once per 60 months.
: 1. The modified performance discharge test in SR 3.8.4.14 may be performed in lieu of the service test in SR 3.8.4.13 once per 60 months.
: 2. This Surveillance is not performed in MODE 1, 2, 3, or 4 for required vital batteries. Credit may be taken for unplanned events that satisfy this SR.
: 2. This Surveillance is not performed in MODE 1, 2, 3, or 4 for required vital batteries. Credit may be taken for unplanned events that satisfy this SR.
Verify battery capacity is adequate to supply, and                     18 months maintain in OPERABLE status, the required emergency loads and any connected nonsafety loads for the design duty cycle when subjected to a battery service test.
Verify battery capacity is adequate to supply, and maintain in OPERABLE status, the required emergency loads and any connected nonsafety loads for the design duty cycle when subjected to a battery service test.
Watts Bar - Unit 2                                    3.8-28 (developmental)                                                                                              HI
18 months


DC Sources - Operating 3.8.4 (continued)
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-29 (developmental)
Watts Bar - Unit 2 3.8-29 (developmental)                               HI
HI (continued)


DC Sources - Operating 3.8.4 SURVEILLANCE REQUIREMENTS (continued)
DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-30 (developmental)
SURVEILLANCE                                                     FREQUENCY SR 3.8.4.14       -------------------------------NOTE------------------------------
HI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.4.14  
-------------------------------NOTE------------------------------
This Surveillance is not performed in MODE 1, 2, 3, or 4 for required vital batteries. Credit may be taken for unplanned events that satisfy this SR.
This Surveillance is not performed in MODE 1, 2, 3, or 4 for required vital batteries. Credit may be taken for unplanned events that satisfy this SR.
Verify battery capacity is 80% of the manufacturer's                 60 months rating when subjected to a performance discharge test or a modified performance discharge test.                         AND 12 months when battery shows degradation or has reached 85% of expected life with capacity < 100% of manufacturer's rating AND 24 months when battery has reached 85% of the expected life with capacity 100% of manufacturer's rating Watts Bar - Unit 2                                    3.8-30 (developmental)                                                                                                HI
Verify battery capacity is 80% of the manufacturer's rating when subjected to a performance discharge test or a modified performance discharge test.
60 months AND 12 months when battery shows degradation or has reached 85% of expected life with capacity < 100% of manufacturer's rating AND 24 months when battery has reached 85% of the expected life with capacity 100% of manufacturer's rating  


DC Sources - Shutdown 3.8.5 3.8 ELECTRICAL POWER SYSTEMS 3.8.5 DC Sources - Shutdown LCO 3.8.5           Vital DC and Diesel Generator (DG) DC electrical power subsystems shall be OPERABLE to support the DC electrical power distribution subsystem(s) required by LCO 3.8.10, "Distribution Systems - Shutdown" and to support the Diesel Generators (DGs) required by LCO 3.8.2, "AC Sources - Shutdown."
DC Sources - Shutdown 3.8.5 Watts Bar - Unit 2 3.8-25 (developmental)
                    ---------------------------------------------NOTES------------------------------------------
HI 3.8 ELECTRICAL POWER SYSTEMS 3.8.5 DC Sources - Shutdown LCO 3.8.5 Vital DC and Diesel Generator (DG) DC electrical power subsystems shall be OPERABLE to support the DC electrical power distribution subsystem(s) required by LCO 3.8.10, "Distribution Systems - Shutdown" and to support the Diesel Generators (DGs) required by LCO 3.8.2, "AC Sources - Shutdown."  
---------------------------------------------NOTES------------------------------------------
: 1. Vital Battery V may be substituted for any of the required vital batteries.
: 1. Vital Battery V may be substituted for any of the required vital batteries.
: 2. Spare vital chargers 6-S, 7-S, 8-S, or 9-S may be substituted for required vital chargers.
: 2. Spare vital chargers 6-S, 7-S, 8-S, or 9-S may be substituted for required vital chargers.
: 3. Spare DG chargers 1A1, 1B1, 2A1, or 2B1 may be substituted for required DG chargers.
: 3. Spare DG chargers 1A1, 1B1, 2A1, or 2B1 may be substituted for required DG chargers.
APPLICABILITY:       MODES 5 and 6, During movement of irradiated fuel assemblies.
APPLICABILITY:
ACTIONS CONDITION                               REQUIRED ACTION                           COMPLETION TIME A. One or more required vital         A.1.1       Declare affected required             Immediately DC electrical power                            feature(s) inoperable.
MODES 5 and 6, During movement of irradiated fuel assemblies.
subsystems inoperable.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required vital DC electrical power subsystems inoperable.
OR A.2.1       Suspend CORE                           Immediately ALTERATIONS.
A.1.1 Declare affected required feature(s) inoperable.
AND (continued)
Immediately OR A.2.1 Suspend CORE ALTERATIONS.
Watts Bar - Unit 2                                  3.8-25 (developmental)                                                                                                      HI
Immediately AND (continued)  


DC Sources - Shutdown 3.8.5 ACTIONS (continued)
DC Sources - Shutdown 3.8.5 Watts Bar - Unit 2 3.8-26 (developmental)
CONDITION               REQUIRED ACTION               COMPLETION TIME A. (continued)             A.2.2   Suspend movement of         Immediately irradiated fuel assemblies.
H ACTIONS (continued)
AND A.2.3   Initiate action to suspend Immediately operations involving positive reactivity additions.
CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)
AND A.2.4   Initiate action to restore Immediately required vital DC electrical power subsystems to OPERABLE status.
A.2.2 Suspend movement of irradiated fuel assemblies.
B. One or more required DG B.1     Declare associated DG       Immediately DC electrical power            inoperable.
Immediately AND A.2.3 Initiate action to suspend operations involving positive reactivity additions.
subsystems inoperable.
Immediately AND A.2.4 Initiate action to restore required vital DC electrical power subsystems to OPERABLE status.
Watts Bar - Unit 2                3.8-26 (developmental)                                                                  H
Immediately B. One or more required DG DC electrical power subsystems inoperable.
B.1 Declare associated DG inoperable.
Immediately


DC Sources - Shutdown 3.8.5 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                                   FREQUENCY SR 3.8.5.1         -------------------------------NOTE------------------------------
DC Sources - Shutdown 3.8.5 Watts Bar - Unit 2 3.8-27 (developmental)
HI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.5.1  
-------------------------------NOTE------------------------------
The following SRs are not required to be performed:
The following SRs are not required to be performed:
SR 3.8.4.511, SR 3.8.4.612, SR 3.8.4.13, and SR 3.8.4.714.
SR 3.8.4.511, SR 3.8.4.612, SR 3.8.4.13, and SR 3.8.4.714.
For DC sources required to be OPERABLE, the                             In accordance with following SRs are applicable:                                           applicable SRs SR 3.8.4.1           SR 3.8.4.26           SR 3.8.4.311 SR 3.8.4.42         SR 3.8.4.57           SR 3.8.4.612 SR 3.8.4.73         SR 3.8.4.8            SR 3.8.4.13 SR 3.8.4.4          SR 3.8.4.9            SR 3.8.4.14 SR 3.8.4.5           SR 3.8.4.10 Watts Bar - Unit 2                                    3.8-27 (developmental)                                                                                              HI
For DC sources required to be OPERABLE, the following SRs are applicable:
SR 3.8.4.1 SR 3.8.4.26 SR 3.8.4.311 SR 3.8.4.42 SR 3.8.4.57 SR 3.8.4.612 SR 3.8.4.73 SR 3.8.4.4 SR 3.8.4.8 SR 3.8.4.9 SR 3.8.4.13 SR 3.8.4.14 SR 3.8.4.5 SR 3.8.4.10 In accordance with applicable SRs


Battery Cell Parameters 3.8.6 3.8 ELECTRICAL POWER SYSTEMS 3.8.6 Battery Cell Parameters LCO 3.8.6                   Battery cell parameters for 125 V vital batteries and 125 V diesel generator (DG) batteries shall be within the limits of Table 3.8.6-1.
Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-28 (developmental)
APPLICABILITY:             When associated DC electrical power subsystems and DGs are required to be OPERABLE.
HI 3.8 ELECTRICAL POWER SYSTEMS 3.8.6 Battery Cell Parameters LCO 3.8.6 Battery cell parameters for 125 V vital batteries and 125 V diesel generator (DG) batteries shall be within the limits of Table 3.8.6-1.
ACTIONS
APPLICABILITY:
When associated DC electrical power subsystems and DGs are required to be OPERABLE.
ACTIONS  
--------------------------------------------------------NOTE-------------------------------------------------------------
--------------------------------------------------------NOTE-------------------------------------------------------------
Separate Condition entry is allowed for each battery bank.
Separate Condition entry is allowed for each battery bank.
ACTIONS CONDITION                                   REQUIRED ACTION                           COMPLETION TIME A. One or more batteries with                 A.1           Verify pilot cells                   2 1 hours one or more battery cell                              electrolyte level and float parameters not within                                  voltage meet Table 3.8.6-Category A or B                                        1 Category C limitsrequired vital battery                          limitsPerform SR 3.8.4.1.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more batteries with one or more battery cell parameters not within Category A or B limitsrequired vital battery with one or more battery cells float voltage < 2.07 V.
with one or more battery cells float voltage < 2.07 V.            AND A.2           Verify battery cell                   24 hours parameters meet Table 3.8.6-1 Category C                   AND limitsPerform SR 3.8.6.1.
A.1 Verify pilot cells electrolyte level and float voltage meet Table 3.8.6-1 Category C limitsPerform SR 3.8.4.1.
Once per 7 days thereafter AND A.3           Restore battery cell                 31 days24 hours parameters to Category A and B limits of Table 3.8.6-1Restore affected cell float voltage
2 1 hours AND A.2 Verify battery cell parameters meet Table 3.8.6-1 Category C limitsPerform SR 3.8.6.1.
                                                            > 2.07 V.
24 hours AND Once per 7 days thereafter AND A.3 Restore battery cell parameters to Category A and B limits of Table 3.8.6-1Restore affected cell float voltage  
Watts Bar - Unit 2                                        3.8-28 (developmental)                                                                                                              HI
> 2.07 V.
31 days24 hours


Battery Cell Parameters 3.8.6 B. Required Action and         B.1 Declare associated          Immediately2 hours associated Completion           battery Time of Condition A not         inoperablePerform metOne required vital           SR 3.8.4.1.
Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-29 (developmental)
battery with float current
HI B. Required Action and associated Completion Time of Condition A not metOne required vital battery with float current  
  > 2 amps.                   AND OR                         B.2 Restore vital battery float  12 hours current to < 2 amps.
> 2 amps.
One or more batteries with average electrolyte temperature of the representative cells < 60oF for vital batteries and <
OR One or more batteries with average electrolyte temperature of the representative cells < 60oF for vital batteries and <
50oF for DG batteries.
50oF for DG batteries.
OR B. One or more batteries with one or more battery cell parameters not within Category C values.
OR B. One or more batteries with one or more battery cell parameters not within Category C values.
(continued)
B.1 Declare associated battery inoperablePerform SR 3.8.4.1.
Watts Bar - Unit 2                 3.8-29 (developmental)                                                                       HI
Immediately2 hours AND B.2 Restore vital battery float current to < 2 amps.
12 hours (continued)  


Battery Cell Parameters 3.8.6 ACTIONS (continued)
Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-30 (developmental)
CONDITION                               REQUIRED ACTION                         COMPLETION TIME C. One required DG battery                 C.1           Perform SR 3.8.4.2.                 2 hours with one or more battery cells float voltage < 2.07 V.        AND C.2           Perform SR 3.8.6.2.                 2 hours AND C.3           Restore affected cell float         24 hours voltage > 2.07 V.
HI ACTIONS (continued)
D. One required DG battery                 D.1           Perform SR 3.8.4.2.                 2 hours with float current > 1 amp.
CONDITION REQUIRED ACTION COMPLETION TIME C. One required DG battery with one or more battery cells float voltage < 2.07 V.
AND D.2           Restore DG battery float           12 hours current to < 2 amps.
C.1 Perform SR 3.8.4.2.
----------------NOTE------------------     --------------------NOTE--------------------
2 hours AND C.2 Perform SR 3.8.6.2.
Required Action E.2 shall be              Required Actions E.1 and E.2 are completed if electrolyte level            only applicable if electrolyte level was below the top of plates.              was below the top of plates.
2 hours AND C.3 Restore affected cell float voltage > 2.07 V.
E. One required battery with               E.1          Restore electrolyte levels          8 hours one or more cells with                             to above top of plates.
24 hours D. One required DG battery with float current > 1 amp.
electrolyte level less than minimum established                   AND design limits.
D.1 Perform SR 3.8.4.2.
E.2           Verify no evidence of               12 hours leakage.
2 hours AND D.2 Restore DG battery float current to < 2 amps.
AND E.3           Restore electrolyte level           31 days to greater than or equal to minimum established design limits.
12 hours
(continued)
----------------NOTE------------------
Watts Bar - Unit 2                                      3.8-30 (developmental)                                                                                                    HI
Required Action E.2 shall be completed if electrolyte level was below the top of plates.
--------------------NOTE--------------------
Required Actions E.1 and E.2 are only applicable if electrolyte level was below the top of plates.
E. One required battery with one or more cells with electrolyte level less than minimum established design limits.
E.1 Restore electrolyte levels to above top of plates.
8 hours AND E.2 Verify no evidence of leakage.
12 hours AND E.3 Restore electrolyte level to greater than or equal to minimum established design limits.
31 days (continued)  


Battery Cell Parameters 3.8.6 ACTIONS (continued)
Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-31 (developmental)
CONDITION                 REQUIRED ACTION               COMPLETION TIME F. One required battery with     F.1   Restore battery pilot cell 12 hours pilot cell electrolyte              temperature to greater temperature less than              than or equal to minimum minimum established                established design limits.
H ACTIONS (continued)
design limits.
CONDITION REQUIRED ACTION COMPLETION TIME F. One required battery with pilot cell electrolyte temperature less than minimum established design limits.
G. More than one required vital G.1  Restore battery            2 hours batteries with battery             parameters to within parameters not within limits.      limits.
F.1 Restore battery pilot cell temperature to greater than or equal to minimum established design limits.
12 hours G. More than one required vital batteries with battery parameters not within limits.
OR More than one required DG batteries with battery parameters not within limits.
OR More than one required DG batteries with battery parameters not within limits.
H. Required Action and           H.1  Declare associate battery  Immediately associated Completion               inoperable Time of Condition A, B, C, D, E, F, or G not met.
G.1 Restore battery parameters to within limits.
2 hours H. Required Action and associated Completion Time of Condition A, B, C, D, E, F, or G not met.
OR One required vital battery with one or more battery cells float voltage < 2.07 V and float current > 2 amps.
OR One required vital battery with one or more battery cells float voltage < 2.07 V and float current > 2 amps.
OR One required DG battery with one or more battery cells float voltage < 2.07 V and float current > 2 amps.
OR One required DG battery with one or more battery cells float voltage < 2.07 V and float current > 2 amps.
Watts Bar - Unit 2                    3.8-31 (developmental)                                                                        H
H.1 Declare associate battery inoperable Immediately


Battery Cell Parameters 3.8.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE                                                     FREQUENCY SR 3.8.6.1         -------------------------------NOTE-------------------------------
Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-32 (developmental)
HI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.6.1  
-------------------------------NOTE-------------------------------
Not required to be met when vital battery terminal voltage is less than the minimum established float voltage of SR 3.8.4.1.
Not required to be met when vital battery terminal voltage is less than the minimum established float voltage of SR 3.8.4.1.
Verify battery cell parameters meet Table 3.8.6-1                         7 days Category A limitseach vital battery float current is
Verify battery cell parameters meet Table 3.8.6-1 Category A limitseach vital battery float current is  
                  < 2 amps.
< 2 amps.
SR 3.8.6.2         -------------------------------NOTE-------------------------------
7 days SR 3.8.6.2  
-------------------------------NOTE-------------------------------
Not required to be met when DG battery terminal voltage is less than the minimum established float voltage of SR 3.8.4.2.
Not required to be met when DG battery terminal voltage is less than the minimum established float voltage of SR 3.8.4.2.
Verify battery cell parameters meet Table 3.8.6-1                         7 92 days Category B limitseach DG battery float current is
Verify battery cell parameters meet Table 3.8.6-1 Category B limitseach DG battery float current is  
                  < 1 amp.                                                                 AND Once within 24 hours after a battery discharge < 110 V for vital batteries (113.5 V for vital battery V) or 106.5 V for DG batteries AND Once within 24 hours after a battery overcharge > 150 V for vital batteries (155 V for vital battery V) or 145 V for DG batteries SR 3.8.6.3         Verify average electrolyte temperature of                                 31 92 days representative cells is 60oF for vital batteries and 50oF for the DG batterieseach required vital and DG battery pilot cell float voltage is > 2.07 V.
< 1 amp.
Watts Bar - Unit 2                                    3.8-32 (developmental)                                                                                                    HI
7 92 days AND Once within 24 hours after a battery discharge < 110 V for vital batteries (113.5 V for vital battery V) or 106.5 V for DG batteries AND Once within 24 hours after a battery overcharge > 150 V for vital batteries (155 V for vital battery V) or 145 V for DG batteries SR 3.8.6.3 Verify average electrolyte temperature of representative cells is 60oF for vital batteries and 50oF for the DG batterieseach required vital and DG battery pilot cell float voltage is > 2.07 V.
31 92 days


Battery Cell Parameters 3.8.6 SR 3.8.6.4         Verify each required vital and DG battery connected   31 days cell electrolyte level is greater than or equal to minimum established design limits.
Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-33 (developmental)
SR 3.8.6.5         Verify each required vital and DG battery pilot cell   31 days temperature is greater than or equal to minimum established design limits.
HI SR 3.8.6.4 Verify each required vital and DG battery connected cell electrolyte level is greater than or equal to minimum established design limits.
SR 3.8.6.6         Verify each required vital and DG battery connected   92 days cell float voltage is > 2.07 V.
31 days SR 3.8.6.5 Verify each required vital and DG battery pilot cell temperature is greater than or equal to minimum established design limits.
(continued)
31 days SR 3.8.6.6 Verify each required vital and DG battery connected cell float voltage is > 2.07 V.
Watts Bar - Unit 2                              3.8-33 (developmental)                                                                                HI
92 days (continued)  


Battery Cell Parameters 3.8.6 SURVEILLANCE REQUIREMENTS (continued)
Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-34 (developmental)
SURVEILLANCE                                                                                 FREQUENCY SR 3.8.6.7         -------------------------------NOTE-------------------------------
HI SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.6.7  
-------------------------------NOTE-------------------------------
Credit may be taken for unplanned events that satisfy this SR.
Credit may be taken for unplanned events that satisfy this SR.
Verify battery capacity is > 80% of the                                 60 months manufacturers rating when subjected to a                                 AND performance discharge test or a modified                                 12 months when performance discharge test.                                               battery shows degradation, or has reached 85% of the expected life with capacity < 100% of manufacturers rating AND 24 months when battery has reached 85% of the expected life with capacity
Verify battery capacity is > 80% of the manufacturers rating when subjected to a performance discharge test or a modified performance discharge test.
                                                                                            > 100% of manufacturers rating Watts Bar - Unit 2                                    3.8-34 (developmental)                                                                                                  HI
60 months AND 12 months when battery shows degradation, or has reached 85% of the expected life with capacity < 100% of manufacturers rating AND 24 months when battery has reached 85% of the expected life with capacity  
> 100% of manufacturers rating  


Battery Cell Parameters 3.8.6 Table 3.8.6-1 (page 1 of 1)
Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-35 (developmental)
Battery Cell Parameters Requirements CATEGORY A:                 CATEGORY B:               CATEGORY C:
I Table 3.8.6-1 (page 1 of 1)
PARAMETER                    LIMITS FOR EACH            LIMITS FOR EACH          ALLOWABLE LIMIT DESIGNATED PILOT            CONNECTED CELL            FOR EACH CELL                                                  CONNECTED CELL Electrolyte Level           > Minimum level            > Minimum level           Above top of plates, indication mark, and        indication mark, and     and not overflowing 1/4 inch above             1/4 inch above maximum level               maximum level indication mark (a)        indication mark (a)
Battery Cell Parameters Requirements PARAMETER CATEGORY A:
Float Voltage                 2.13 V                     2.13 V                 > 2.07 V Specific Gravity (b)(c)       1.200                     1.195                   Not more than 0.020 below average of all AND                      connected cells Average of all            AND connected cells
LIMITS FOR EACH DESIGNATED PILOT CELL CATEGORY B:
                                                          > 1.205                  Average of all connected cells 1.195 (a)     It is acceptable for the electrolyte level to temporarily increase above the specified maximum level during equalizing charges provided it is not overflowing.
LIMITS FOR EACH CONNECTED CELL CATEGORY C:
(b)     Corrected for electrolyte temperature and level. Level correction is not required, however, when battery charging is < 2 amps when on float charge for vital batteries and < 1.0 amp for DG batteries.
ALLOWABLE LIMIT FOR EACH CONNECTED CELL Electrolyte Level  
(c)     A battery charging current of < 2 amps when on float charge for vital batteries and < 1.0 amp for DG batteries is acceptable for meeting specific gravity limits following a battery recharge, for a maximum of 31 days. When charging current is used to satisfy specific gravity requirements, specific gravity of each connected cell shall be measured prior to expiration of the 31 day allowance.
> Minimum level indication mark, and 1/4 inch above maximum level indication mark (a)
Watts Bar - Unit 2                                    3.8-35 (developmental)                                                                                              I
> Minimum level indication mark, and 1/4 inch above maximum level indication mark (a)
Above top of plates, and not overflowing Float Voltage 2.13 V 2.13 V  
> 2.07 V Specific Gravity (b)(c) 1.200 1.195 AND Average of all connected cells
> 1.205 Not more than 0.020 below average of all connected cells AND Average of all connected cells 1.195 (a)
It is acceptable for the electrolyte level to temporarily increase above the specified maximum level during equalizing charges provided it is not overflowing.
(b)
Corrected for electrolyte temperature and level. Level correction is not required, however, when battery charging is < 2 amps when on float charge for vital batteries and < 1.0 amp for DG batteries.
(c)
A battery charging current of < 2 amps when on float charge for vital batteries and < 1.0 amp for DG batteries is acceptable for meeting specific gravity limits following a battery recharge, for a maximum of 31 days. When charging current is used to satisfy specific gravity requirements, specific gravity of each connected cell shall be measured prior to expiration of the 31 day allowance.  


Decay Time 3.9.10 3.9 REFUELING OPERATIONS 3.9.10 Decay Time LCO 3.9.10           The reactor shall be subcritical for > 100 hours.
Decay Time 3.9.10 Watts Bar - Unit 2 3.9-13 (developmental)
APPLICABILITY:       During movement of irradiated fuel assemblies within the containment.
HI 3.9 REFUELING OPERATIONS 3.9.10 Decay Time LCO 3.9.10 The reactor shall be subcritical for > 100 hours.
ACTIONS CONDITION                         REQUIRED ACTION               COMPLETION TIME A. Reactor subcritical for         A.1       Suspend all operations     Immediately
APPLICABILITY:
    < 100 hours.                              involving movement of irradiated fuel assemblies within the containment.
During movement of irradiated fuel assemblies within the containment.
SURVEILLANCE REQUIREMENTS SURVEILLANCE                                       FREQUENCY SR 3.9.10.1       Verify the reactor has been subcritical for             Prior to movement
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Reactor subcritical for  
                  > 100 hours by confirming the date and time of         of irradiated fuel in subcriticality.                                        the reactor vessel.
< 100 hours.
Watts Bar - Unit 2                          3.9-13 (developmental)                                                                                  HI
A.1 Suspend all operations involving movement of irradiated fuel assemblies within the containment.
Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.9.10.1 Verify the reactor has been subcritical for  
> 100 hours by confirming the date and time of subcriticality.
Prior to movement of irradiated fuel in the reactor vessel.  


Design Features 4.0 4.0 DESIGN FEATURES 4.1 Site 4.1.1   Site and Exclusion Area Boundaries The site and exclusion area boundaries shall be as shown in Figure 4.1-1.
Design Features 4.0 (continued)
4.1.2   Low Population Zone (LPZ)
Watts Bar - Unit 2 4.0-1 (developmental)
C 4.0 DESIGN FEATURES 4.1 Site 4.1.1 Site and Exclusion Area Boundaries The site and exclusion area boundaries shall be as shown in Figure 4.1-1.
4.1.2 Low Population Zone (LPZ)
The LPZ shall be as shown in Figure 4.1-2 (within the 3-mile circle).
The LPZ shall be as shown in Figure 4.1-2 (within the 3-mile circle).
4.2 Reactor Core 4.2.1   Fuel Assemblies The reactor shall contain 193 fuel assemblies. Each assembly shall consist of a matrix of Zirlo fuel rods with an initial composition of natural or slightly enriched uranium dioxide (UO2) as fuel material. Limited substitutions of zirconium alloy or stainless steel filler rods for fuel rods, in accordance with approved applications of fuel rod configurations, may be used. Fuel assemblies shall be limited to those fuel designs that have been analyzed with applicable NRC staff approved codes and methods and shown by tests or analyses to comply with all fuel safety design bases. A limited number of lead test assemblies that have not completed representative testing may be placed in nonlimiting core regions.
4.2 Reactor Core 4.2.1 Fuel Assemblies The reactor shall contain 193 fuel assemblies. Each assembly shall consist of a matrix of Zirlo fuel rods with an initial composition of natural or slightly enriched uranium dioxide (UO2) as fuel material. Limited substitutions of zirconium alloy or stainless steel filler rods for fuel rods, in accordance with approved applications of fuel rod configurations, may be used. Fuel assemblies shall be limited to those fuel designs that have been analyzed with applicable NRC staff approved codes and methods and shown by tests or analyses to comply with all fuel safety design bases. A limited number of lead test assemblies that have not completed representative testing may be placed in nonlimiting core regions.
4.2.2   Control Rod Assemblies The reactor core shall contain 57 control rod assemblies. The control material shall be silver indium cadmium as approved by the NRC.
4.2.2 Control Rod Assemblies The reactor core shall contain 57 control rod assemblies. The control material shall be silver indium cadmium as approved by the NRC.  
 
Design Features 4.0 4.0 DESIGN FEATURES (continued)
(continued)
(continued)
Watts Bar - Unit 2                               4.0-1 (developmental)                                                                                     C
Watts Bar - Unit 2 4.0-2 (developmental)
 
HI 4.3 Fuel Storage 4.3.1 Criticality 4.3.1.1 The spent fuel storage racks (shown in Figure 4.3-1) are designed and shall be maintained with:
Design Features 4.0 4.0 DESIGN FEATURES (continued) 4.3 Fuel Storage 4.3.1   Criticality 4.3.1.1     The spent fuel storage racks (shown in Figure 4.3-1) are designed and shall be maintained with:
: a.
: a. Fuel assemblies having a maximum U-235 enrichment of 5.0 weight percent (wt%);
Fuel assemblies having a maximum U-235 enrichment of 5.0 weight percent (wt%);
: b. keff < 0.95 if fully flooded with unborated water, which, includes an allowance for uncertainties as described in Sections 4.3.2.7 and 9.1 of the FSAR;
: b.
: c. Distances between fuel assemblies are a nominal 10.375 inch center-to-center spacing in the twenty-four flux trap rack modules.
keff < 0.95 if fully flooded with unborated water, which, includes an allowance for uncertainties as described in Sections 4.3.2.7 and 9.1 of the FSAR;
: d. Fuel assemblies with initial enrichments less than a maximum of 5 wt% U-235 enrichment (nominally 4.95 +/- 0.05 wt% U-235) may be stored in the spent fuel racks in any one of four arrangements with specific limits as identified below:
: c.
Distances between fuel assemblies are a nominal 10.375 inch center-to-center spacing in the twenty-four flux trap rack modules.
: d.
Fuel assemblies with initial enrichments less than a maximum of 5 wt% U-235 enrichment (nominally 4.95 +/- 0.05 wt% U-235) may be stored in the spent fuel racks in any one of four arrangements with specific limits as identified below:
: 1. Fuel assemblies may be stored in the racks in an all cell arrangement provided the burnup of each assembly is in the acceptable domain identified in Figure 4.3-3, depending upon the specified initial enrichment.
: 1. Fuel assemblies may be stored in the racks in an all cell arrangement provided the burnup of each assembly is in the acceptable domain identified in Figure 4.3-3, depending upon the specified initial enrichment.
: 2. New and spent fuel assemblies may be stored in a checkerboard arrangement of 2 new and 2 spent assemblies, provided that each spent fuel assembly has accumulated a minimum burnup in the acceptable domain identified in Figure 4.3-4.
: 2. New and spent fuel assemblies may be stored in a checkerboard arrangement of 2 new and 2 spent assemblies, provided that each spent fuel assembly has accumulated a minimum burnup in the acceptable domain identified in Figure 4.3-4.
: 3. New fuel assemblies may be stored in 4-cell arrays with 1 of the 4 cells remaining empty of fuel (i.e. containing only water or water with up to 75 percent by volume of non-fuel bearing material).
: 3. New fuel assemblies may be stored in 4-cell arrays with 1 of the 4 cells remaining empty of fuel (i.e. containing only water or water with up to 75 percent by volume of non-fuel bearing material).  
(continued)
Watts Bar - Unit 2                              4.0-2 (developmental)                                                                                  HI


Design Features 4.0 4.0 DESIGN FEATURES (continued) 4.3 Fuel Storage (continued)
Design Features 4.0 4.0 DESIGN FEATURES (continued)
Watts Bar - Unit 2 4.0-3 (developmental)
A 4.3 Fuel Storage (continued)
: 4. New fuel assemblies with a minimum of 32 integral fuel burnable absorber (IFBA) rods may be stored without further restriction, provided the loading of ZrB2 in the coating of each IFBA rod is minimum of 1.25x (1.9625mg/in).
: 4. New fuel assemblies with a minimum of 32 integral fuel burnable absorber (IFBA) rods may be stored without further restriction, provided the loading of ZrB2 in the coating of each IFBA rod is minimum of 1.25x (1.9625mg/in).
A water cell is less reactive than any cell containing fuel and therefore a water cell may be used at any location in the loading arrangements.
A water cell is less reactive than any cell containing fuel and therefore a water cell may be used at any location in the loading arrangements.
A water cell is defined as a cell containing water or non-fissile material with no more than 75 percent of the water displaced.
A water cell is defined as a cell containing water or non-fissile material with no more than 75 percent of the water displaced.
4.3.1.2     The new fuel storage racks are designed and shall be maintained with:
4.3.1.2 The new fuel storage racks are designed and shall be maintained with:
: a. Fuel assemblies having a maximum enrichment of 5.0 weight percent U-235 and shall be maintained with the arrangement of 120 storage locations shown in Figure 4.3-2;
: a.
: b. keff 0.95 if fully flooded with unborated water, which includes an allowance for uncertainties as described in Section 9.1 of the FSAR;
Fuel assemblies having a maximum enrichment of 5.0 weight percent U-235 and shall be maintained with the arrangement of 120 storage locations shown in Figure 4.3-2;
: c. keff 0.98 if moderated by aqueous foam, which includes an allowance for uncertainties as described in Section 9.1 of the FSAR; and
: b.
: d. A nominal 21-inch center to center distance between fuel assemblies placed in the storage racks.
keff 0.95 if fully flooded with unborated water, which includes an allowance for uncertainties as described in Section 9.1 of the FSAR;
4.3.2     Drainage The spent fuel storage pool is designed and shall be maintained to prevent inadvertent draining of the pool below Elevation 747 feet - 1 1/2 inches.
: c.
4.3.3     Capacity The spent fuel storage pool is designed and shall be maintained with a storage capacity limited to no more than 1386 fuel assemblies in 24 flux trap rack modules.
keff 0.98 if moderated by aqueous foam, which includes an allowance for uncertainties as described in Section 9.1 of the FSAR; and
Watts Bar - Unit 2                              4.0-3 (developmental)                                                                                    A
: d.
A nominal 21-inch center to center distance between fuel assemblies placed in the storage racks.
4.3.2 Drainage The spent fuel storage pool is designed and shall be maintained to prevent inadvertent draining of the pool below Elevation 747 feet - 1 1/2 inches.
4.3.3 Capacity The spent fuel storage pool is designed and shall be maintained with a storage capacity limited to no more than 1386 fuel assemblies in 24 flux trap rack modules.  


Design Features 4.0 FIGURE 4.1-1 (PAGE 1 OF 1)
Design Features 4.0 (continued)
SITE AND EXCLUSION AREA BOUNDARIES (continued)
Watts Bar - Unit 2 4.0-4 (developmental)
Watts Bar - Unit 2                  4.0-4 (developmental)                                                    A
A FIGURE 4.1-1 (PAGE 1 OF 1)
SITE AND EXCLUSION AREA BOUNDARIES  


Design Features 4.0 FIGURE 4.1-2 (PAGE 1 OF 1)
Design Features 4.0 (continued)
LOW POPULATION ZONE (continued)
Watts Bar - Unit 2 4.0-5 (developmental)
Watts Bar - Unit 2           4.0-5 (developmental)                                             A
A FIGURE 4.1-2 (PAGE 1 OF 1)
LOW POPULATION ZONE


SOUTH WALL Watts Bar - Unit 2 (developmental) 4.0-6                                                                               WEST WALL FLUX TRAP RACK, TYPICAL                             FUEL CASK LOADING PIT Design Features PLAN                        FIGURE 4.3-1 SPENT FUEL POOL          SPENT FUEL STORAGE RACKS A
Design Features 4.0 (continued)
(continued)                                                                                              4.0
Watts Bar - Unit 2 4.0-6 (developmental)
A FLUX TRAP RACK, TYPICAL FUEL CASK LOADING PIT FIGURE 4.3-1 SPENT FUEL STORAGE RACKS PLAN SPENT FUEL POOL SOUTH WALL WEST WALL


Design Features 4.0 FIGURE 4.3-2 NEW FUEL STORAGE RACK LOADING PATTERN (continued)
Design Features 4.0 (continued)
Watts Bar - Unit 2                 4.0-7 (developmental)                                                       A
Watts Bar - Unit 2 4.0-7 (developmental)
A FIGURE 4.3-2 NEW FUEL STORAGE RACK LOADING PATTERN


Design Features 4.0 ACCEPTABLE BURNUP DOMAIN Burnup, MWD/kgU UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 FIGURE 4.3-3 MINIMUM REQUIRED BURNUP FOR UNRESTRICTED STORAGE OF FUEL OF VARIOUS INITIAL ENRICHMENTS (continued)
Design Features 4.0 (continued)
Watts Bar - Unit 2                              4.0-8 (developmental)                                                                        H
Watts Bar - Unit 2 4.0-8 (developmental)
H FIGURE 4.3-3 MINIMUM REQUIRED BURNUP FOR UNRESTRICTED STORAGE OF FUEL OF VARIOUS INITIAL ENRICHMENTS ACCEPTABLE BURNUP DOMAIN UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 Burnup, MWD/kgU ACCEPTABLE BURNUP DOMAIN UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 Burnup, MWD/kgU


Design Features 4.0 ACCEPTABLE BURNUP DOMAIN Burnup, MWD/kgU UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 FIGURE 4.3-4 MINIMUM REQUIRED BURNUP FOR A CHECKERBOARD ARRANGEMENT OF 2 SPENT AND 2 NEW FUEL ASSEMBLIES OF 5 wt% U-235 ENRICHMENT (MAXIMUM)
Design Features 4.0 Watts Bar - Unit 2 4.0-9 (developmental)
Watts Bar - Unit 2                    4.0-9 (developmental)                                                            H
H FIGURE 4.3-4 MINIMUM REQUIRED BURNUP FOR A CHECKERBOARD ARRANGEMENT OF 2 SPENT AND 2 NEW FUEL ASSEMBLIES OF 5 wt% U-235 ENRICHMENT (MAXIMUM)
ACCEPTABLE BURNUP DOMAIN UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 Burnup, MWD/kgU ACCEPTABLE BURNUP DOMAIN UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 Burnup, MWD/kgU


Responsibility 5.1 5.0 ADMINISTRATIVE CONTROLS 5.1 Responsibility 5.1.1   The Site Vice-President shall be responsible for overall activities of the site, while the Plant Manager shall be responsible for overall unit operation. The Site Vice-President and the Plant Manager shall delegate in writing the succession to this responsibility during his absence.
Responsibility 5.1 Watts Bar - Unit 2 5.0-1 (developmental)
A 5.0 ADMINISTRATIVE CONTROLS 5.1 Responsibility 5.1.1 The Site Vice-President shall be responsible for overall activities of the site, while the Plant Manager shall be responsible for overall unit operation. The Site Vice-President and the Plant Manager shall delegate in writing the succession to this responsibility during his absence.
The Plant Manager or his designee shall approve, prior to implementation, each proposed test, experiment or modification to systems or equipment that affect nuclear safety.
The Plant Manager or his designee shall approve, prior to implementation, each proposed test, experiment or modification to systems or equipment that affect nuclear safety.
5.1.2   The Shift Manager (SM) shall be responsible for the control room command function. During any absence of the SM from the control room while the unit is in MODE 1, 2, 3, or 4, an individual with an active Senior Reactor Operator (SRO) license shall be designated to assume the control room command function.
5.1.2 The Shift Manager (SM) shall be responsible for the control room command function. During any absence of the SM from the control room while the unit is in MODE 1, 2, 3, or 4, an individual with an active Senior Reactor Operator (SRO) license shall be designated to assume the control room command function.
During any absence of the SM from the control room while the unit is in MODE 5 or 6, an individual with an active SRO license or Reactor Operator license shall be designated to assume the control room command function.
During any absence of the SM from the control room while the unit is in MODE 5 or 6, an individual with an active SRO license or Reactor Operator license shall be designated to assume the control room command function.  
Watts Bar - Unit 2                            5.0-1 (developmental)                                                                                    A


Organization 5.2 5.0 ADMINISTRATIVE CONTROLS 5.2 Organization 5.2.1   Onsite and Offsite Organizations Onsite and offsite organizations shall be established for unit operation and corporate management, respectively. The onsite and offsite organizations shall include the positions for activities affecting safety of the nuclear power plant.
Organization 5.2 (continued)
: a. Lines of authority, responsibility, and communication shall be defined and established throughout highest management levels, intermediate levels, and all operating organization positions. These relationships shall be documented and updated, as appropriate, in organization charts, functional descriptions of departmental responsibilities and relationships, and job descriptions for key personnel positions, or in equivalent forms of documentation. These requirements shall be documented in the Nuclear Power Organization Topical Report (TVA-NPOD 89-A);
Watts Bar - Unit 2 5.0-2 (developmental)
: b. The Plant Manager shall be responsible for overall safe operation of the plant and shall have control over those onsite activities necessary for safe operation and maintenance of the plant;
A 5.0 ADMINISTRATIVE CONTROLS 5.2 Organization 5.2.1 Onsite and Offsite Organizations Onsite and offsite organizations shall be established for unit operation and corporate management, respectively. The onsite and offsite organizations shall include the positions for activities affecting safety of the nuclear power plant.
: c. The Site Vice-President shall have responsibility for overall plant nuclear safety and shall take any measures needed to ensure acceptable performance of the staff in operating, maintaining, and providing technical support to the plant to ensure nuclear safety; and
: a.
: d. The individuals who train the operating staff, carry out radiological controls, or perform quality assurance functions may report to the appropriate onsite manager; however, these individuals shall have sufficient organizational freedom to ensure their independence from operating pressures.
Lines of authority, responsibility, and communication shall be defined and established throughout highest management levels, intermediate levels, and all operating organization positions. These relationships shall be documented and updated, as appropriate, in organization charts, functional descriptions of departmental responsibilities and relationships, and job descriptions for key personnel positions, or in equivalent forms of documentation. These requirements shall be documented in the Nuclear Power Organization Topical Report (TVA-NPOD 89-A);
(continued)
: b.
Watts Bar - Unit 2                              5.0-2 (developmental)                                                                                    A
The Plant Manager shall be responsible for overall safe operation of the plant and shall have control over those onsite activities necessary for safe operation and maintenance of the plant;
: c.
The Site Vice-President shall have responsibility for overall plant nuclear safety and shall take any measures needed to ensure acceptable performance of the staff in operating, maintaining, and providing technical support to the plant to ensure nuclear safety; and
: d.
The individuals who train the operating staff, carry out radiological controls, or perform quality assurance functions may report to the appropriate onsite manager; however, these individuals shall have sufficient organizational freedom to ensure their independence from operating pressures.  


Organization 5.2 5.2 Organization (continued) 5.2.2   Unit Staff The unit staff organization shall include the following:
Organization 5.2 5.2 Organization (continued)
: a. A non-licensed operator shall be assigned to each reactor containing fuel and an additional non-licensed operator shall be assigned for each control room from which a reactor is being operated in MODES 1, 2, 3, or 4.
Watts Bar - Unit 2 5.0-3 (developmental)
: b. The shift crew composition may be less than the minimum requirements of 10 CFR 50.54(m)(2)(i) and Specifications 5.2.2.a and 5.2.2.f for a period of time not to exceed 2 hours in order to accommodate unexpected absences of on-duty shift crew members provided immediate action is taken to restore the shift crew composition to within the minimum requirements.
B 5.2.2 Unit Staff The unit staff organization shall include the following:
: c. A radiological controls technician shall be on site when fuel is in the reactor.
: a.
A non-licensed operator shall be assigned to each reactor containing fuel and an additional non-licensed operator shall be assigned for each control room from which a reactor is being operated in MODES 1, 2, 3, or 4.
: b.
The shift crew composition may be less than the minimum requirements of 10 CFR 50.54(m)(2)(i) and Specifications 5.2.2.a and 5.2.2.f for a period of time not to exceed 2 hours in order to accommodate unexpected absences of on-duty shift crew members provided immediate action is taken to restore the shift crew composition to within the minimum requirements.
: c.
A radiological controls technician shall be on site when fuel is in the reactor.
The position may be vacant for not more than 2 hours, in order to provide for unexpected absence, provided immediate action is taken to fill the required position.
The position may be vacant for not more than 2 hours, in order to provide for unexpected absence, provided immediate action is taken to fill the required position.
: d. Deleted
: d.
: e. The Operations Superintendent shall have a valid SRO license on this unit.
Deleted
: f. An individual shall provide advisory technical support to the unit operations shift crew in the areas of thermal hydraulics, reactor engineering, and plant analysis with regard to the safe operation of the unit. This individual shall meet the qualifications specified by the Commission Policy Statement on Engineering Expertise on shift (Generic Letter 86-04 dated 02/13/86).
: e.
Watts Bar - Unit 2                             5.0-3 (developmental)                                                                                   B
The Operations Superintendent shall have a valid SRO license on this unit.
: f.
An individual shall provide advisory technical support to the unit operations shift crew in the areas of thermal hydraulics, reactor engineering, and plant analysis with regard to the safe operation of the unit. This individual shall meet the qualifications specified by the Commission Policy Statement on Engineering Expertise on shift (Generic Letter 86-04 dated 02/13/86).  
 
Unit Staff Qualifications 5.3 Watts Bar - Unit 2 5.0-4 (developmental)
A 5.0 ADMINISTRATIVE CONTROLS 5.3 Unit Staff Qualifications 5.3.1 Each member of the unit staff shall meet or exceed the minimum qualifications for comparable positions, as specified in TVA Nuclear Quality Assurance Plan (TVA-NQA-PLN89-A).
5.3.2 For the purpose of 10 CFR 55.4, a licensed Senior Reactor Operator (SRO) and a licensed Reactor Operator (RO) are those individuals who, in addition to meeting the requirements of TS 5.3.1, perform the functions described in 10 CFR 50.54 (m).


Unit Staff Qualifications 5.3 5.0 ADMINISTRATIVE CONTROLS 5.3  Unit Staff Qualifications 5.3.1    Each member of the unit staff shall meet or exceed the minimum qualifications for comparable positions, as specified in TVA Nuclear Quality Assurance Plan (TVA-NQA-PLN89-A).
Training 5.4 Watts Bar - Unit 2 5.0-5 (developmental)
5.3.2    For the purpose of 10 CFR 55.4, a licensed Senior Reactor Operator (SRO) and a licensed Reactor Operator (RO) are those individuals who, in addition to meeting the requirements of TS 5.3.1, perform the functions described in 10 CFR 50.54 (m).
A 5.0 ADMINISTRATIVE CONTROLS 5.4 Training (removed from Technical Specifications)  
Watts Bar - Unit 2                          5.0-4 (developmental)                                                                               A


Training 5.4 5.0  ADMINISTRATIVE CONTROLS 5.4  Training (removed from Technical Specifications)
Reviews and Audits 5.5 Watts Bar - Unit 2 5.0-6 (developmental)
Watts Bar - Unit 2                   5.0-5 (developmental)                                                     A
A 5.0 ADMINISTRATIVE CONTROLS 5.5 Reviews and Audits (removed from Technical Specifications)


Reviews and Audits 5.5 5.0 ADMINISTRATIVE CONTROLS 5.5  Reviews and Audits (removed from Technical Specifications)
TS Bases Control Program 5.6 Watts Bar - Unit 2 5.0-7 (developmental)
Watts Bar - Unit 2                     5.0-6 (developmental)                                                                 A
A 5.0 ADMINISTRATIVE CONTROLS 5.6 Technical Specifications (TS) Bases Control Program This Program provides a means for processing changes to the Bases of these Technical Specifications.
5.6.1 Changes to the Bases of the TS shall be made under appropriate administrative controls and reviews.
5.6.2 Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:
: a.
A change in the TS incorporated in the license; or
: b.
A change to the updated FSAR or Bases that requires NRC approval pursuant to 10 CFR 50.59.
5.6.3 The Bases Control Program shall contain provisions to ensure that the Bases are maintained consistent with the FSAR.
5.6.4 Proposed changes that meet the criteria of Specification 5.6.2 shall be reviewed and approved by the NRC prior to implementation. Changes to the Bases implemented without prior NRC approval shall be provided to the NRC on a frequency consistent with 10 CFR 50.71(e).


TS Bases Control Program 5.6 5.0 ADMINISTRATIVE CONTROLS 5.6  Technical Specifications (TS) Bases Control Program This Program provides a means for processing changes to the Bases of these Technical Specifications.
Procedures, Programs, and Manuals 5.7 (continued)
5.6.1   Changes to the Bases of the TS shall be made under appropriate administrative controls and reviews.
Watts Bar - Unit 2 5.0-8 (developmental)
5.6.2    Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:
A 5.0 ADMINISTRATIVE CONTROLS 5.7 Procedures, Programs, and Manuals 5.7.1 Procedures 5.7.1.1 Scope Written procedures shall be established, implemented, and maintained covering the following activities:
: a. A change in the TS incorporated in the license; or
: a.
: b. A change to the updated FSAR or Bases that requires NRC approval pursuant to 10 CFR 50.59.
The applicable procedures recommended in Regulatory Guide 1.33, Revision 2, Appendix A, February 1978;
5.6.3    The Bases Control Program shall contain provisions to ensure that the Bases are maintained consistent with the FSAR.
: b.
5.6.4    Proposed changes that meet the criteria of Specification 5.6.2 shall be reviewed and approved by the NRC prior to implementation. Changes to the Bases implemented without prior NRC approval shall be provided to the NRC on a frequency consistent with 10 CFR 50.71(e).
The emergency operating procedures required to implement the requirements of NUREG-0737 and NUREG-0737, Supplement 1 (Generic Letter 82-33);
Watts Bar - Unit 2                          5.0-7 (developmental)                                                                               A
: c.
Quality assurance for effluent and environmental monitoring;
: d.
Fire Protection Program implementation; and
: e.
All programs specified in Specification 5.7.2.
5.7.1.2 Review and Approval (removed from Technical Specifications) 5.7.1.3 Temporarily Approved Changes (removed from Technical Specifications)  


Procedures, Programs, and Manuals 5.7 5.0  ADMINISTRATIVE CONTROLS 5.7 Procedures, Programs, and Manuals 5.7.1    Procedures 5.7.1.1  Scope Written procedures shall be established, implemented, and maintained covering the following activities:
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: a. The applicable procedures recommended in Regulatory Guide 1.33, Revision 2, Appendix A, February 1978;
: b. The emergency operating procedures required to implement the requirements of NUREG-0737 and NUREG-0737, Supplement 1 (Generic Letter 82-33);
: c. Quality assurance for effluent and environmental monitoring;
: d. Fire Protection Program implementation; and
: e. All programs specified in Specification 5.7.2.
5.7.1.2  Review and Approval (removed from Technical Specifications) 5.7.1.3  Temporarily Approved Changes (removed from Technical Specifications)
(continued)
(continued)
Watts Bar - Unit 2                           5.0-8 (developmental)                                                                           A
Watts Bar - Unit 2 5.0-9 (developmental)
 
A 5.7.2 Programs and Manuals The following programs shall be established, implemented, and maintained.
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2   Programs and Manuals The following programs shall be established, implemented, and maintained.
5.7.2.1 (removed from Technical Specifications) 5.7.2.2 (removed from Technical Specifications) 5.7.2.3 Offsite Dose Calculation Manual (ODCM)
5.7.2.1   (removed from Technical Specifications) 5.7.2.2   (removed from Technical Specifications) 5.7.2.3   Offsite Dose Calculation Manual (ODCM)
: a.
: a. The ODCM shall contain the methodology and parameters used in the calculation of offsite doses resulting from radioactive gaseous and liquid effluents, in the calculation of gaseous and liquid effluent monitoring alarm and trip setpoints, and in the conduct of the radiological environmental monitoring program; and
The ODCM shall contain the methodology and parameters used in the calculation of offsite doses resulting from radioactive gaseous and liquid effluents, in the calculation of gaseous and liquid effluent monitoring alarm and trip setpoints, and in the conduct of the radiological environmental monitoring program; and
: b. The ODCM shall also contain the radioactive effluent controls and radiological environmental monitoring activities, and descriptions of the information that should be included in the Annual Radiological Environmental Operating and Radioactive Effluent Release Reports required by Specifications 5.9.2 and 5.9.3.
: b.
The ODCM shall also contain the radioactive effluent controls and radiological environmental monitoring activities, and descriptions of the information that should be included in the Annual Radiological Environmental Operating and Radioactive Effluent Release Reports required by Specifications 5.9.2 and 5.9.3.
Licensee initiated changes to the ODCM:
Licensee initiated changes to the ODCM:
: a. Shall be documented and records of reviews performed shall be retained. This documentation shall contain:
: a.
: 1. sufficient information to support the change(s) together with the appropriate analyses or evaluations justifying the change(s),
Shall be documented and records of reviews performed shall be retained. This documentation shall contain:
: 2. a determination that the change(s) maintain the levels of radioactive effluent control required by 10 CFR 20.1302, 40 CFR 190, 10 CFR 50.36a, and 10 CFR 50, Appendix I, and not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations;
: 1.
: b. Shall become effective after the approval of the Plant Manager; and (continued)
sufficient information to support the change(s) together with the appropriate analyses or evaluations justifying the change(s),
Watts Bar - Unit 2                              5.0-9 (developmental)                                                                                  A
: 2.
a determination that the change(s) maintain the levels of radioactive effluent control required by 10 CFR 20.1302, 40 CFR 190, 10 CFR 50.36a, and 10 CFR 50, Appendix I, and not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations;
: b.
Shall become effective after the approval of the Plant Manager; and  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.3 Offsite Dose Calculation Manual (ODCM) (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: c. Shall be submitted to the NRC in the form of a complete, legible copy of the entire ODCM as a part of or concurrent with the Radioactive Effluent Release Report for the period of the report in which any change in the ODCM was made. Each change shall be identified by markings in the margin of the affected pages, clearly indicating the area of the page that was changed, and shall indicate the date (i.e., month and year) the change was implemented.
Watts Bar - Unit 2 5.0-10 (developmental)
5.7.2.4 Primary Coolant Sources Outside Containment This program provides controls to minimize leakage from those portions of systems outside containment that could contain highly radioactive fluids during a serious transient or accident to levels as low as practicable. The systems include Containment Spray, Safety Injection, Residual Heat Removal, Chemical and Volume Control, Reactor Coolant System Sampling, and Waste Gas. The program shall include the following:
A 5.7.2.3 Offsite Dose Calculation Manual (ODCM) (continued)
: a. Preventive maintenance and periodic visual inspection requirements; and
: c.
: b. Integrated leak test requirements for each system at least once per 18 months.
Shall be submitted to the NRC in the form of a complete, legible copy of the entire ODCM as a part of or concurrent with the Radioactive Effluent Release Report for the period of the report in which any change in the ODCM was made. Each change shall be identified by markings in the margin of the affected pages, clearly indicating the area of the page that was changed, and shall indicate the date (i.e., month and year) the change was implemented.
5.7.2.4 Primary Coolant Sources Outside Containment This program provides controls to minimize leakage from those portions of systems outside containment that could contain highly radioactive fluids during a serious transient or accident to levels as low as practicable. The systems include Containment Spray, Safety Injection, Residual Heat Removal, Chemical and Volume Control, Reactor Coolant System Sampling, and Waste Gas. The program shall include the following:
: a.
Preventive maintenance and periodic visual inspection requirements; and
: b.
Integrated leak test requirements for each system at least once per 18 months.
The provisions of SR 3.0.2 are applicable.
The provisions of SR 3.0.2 are applicable.
5.7.2.5 (removed from Technical Specifications) 5.7.2.6 (removed from Technical Specifications)
5.7.2.5 (removed from Technical Specifications) 5.7.2.6 (removed from Technical Specifications)
 
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
(continued)
(continued)
Watts Bar - Unit 2                         5.0-10 (developmental)                                                                               A
Watts Bar - Unit 2 5.0-11 (developmental)
 
A 5.7.2.7 Radioactive Effluent Controls Program This program conforms to 10 CFR 50.36a for the control of radioactive effluents and for maintaining the doses to members of the public from radioactive effluents as low as reasonably achievable.
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2.7 Radioactive Effluent Controls Program This program conforms to 10 CFR 50.36a for the control of radioactive effluents and for maintaining the doses to members of the public from radioactive effluents as low as reasonably achievable.
The program shall be contained in the ODCM, shall be implemented by procedures, and shall include remedial actions to be taken whenever the program limits are exceeded. The program shall include the following elements:
The program shall be contained in the ODCM, shall be implemented by procedures, and shall include remedial actions to be taken whenever the program limits are exceeded. The program shall include the following elements:
: a. Limitations on the functional capability of radioactive liquid and gaseous monitoring instrumentation including surveillance tests and setpoint determination in accordance with the methodology in the ODCM;
: a.
: b. Limitations on the concentrations of radioactive material released in liquid effluents to unrestricted areas, conforming to 10 times the concentration values in 10 CFR 20.1001-20.2402, Appendix B, Table 2, Column 2;
Limitations on the functional capability of radioactive liquid and gaseous monitoring instrumentation including surveillance tests and setpoint determination in accordance with the methodology in the ODCM;
: c. Monitoring, sampling, and analysis of radioactive liquid and gaseous effluents in accordance with 10 CFR 20.1302 and with the methodology and parameters in the ODCM;
: b.
: d. Limitations on the annual and quarterly doses or dose commitment to a member of the public from radioactive materials in liquid effluents released from each unit to unrestricted areas, conforming to 10 CFR 50, Appendix I;
Limitations on the concentrations of radioactive material released in liquid effluents to unrestricted areas, conforming to 10 times the concentration values in 10 CFR 20.1001-20.2402, Appendix B, Table 2, Column 2;
: e. Determination of cumulative dose contributions from radioactive effluents for the current calendar quarter and current calendar year in accordance with the methodology and parameters in the ODCM at least every 31 days. Determination of projected dose contributions from radioactive effluents in accordance with the methodology in the ODCM at least every 31 days;
: c.
: f. Limitations on the functional capability and use of the liquid and gaseous effluent treatment systems to ensure that appropriate portions of these systems are used to reduce releases of radioactivity when the projected doses in a period of 31 days would exceed 2% of the guidelines for the annual dose or dose commitment, conforming to 10 CFR 50, Appendix I; (continued)
Monitoring, sampling, and analysis of radioactive liquid and gaseous effluents in accordance with 10 CFR 20.1302 and with the methodology and parameters in the ODCM;
Watts Bar - Unit 2                          5.0-11 (developmental)                                                                                A
: d.
Limitations on the annual and quarterly doses or dose commitment to a member of the public from radioactive materials in liquid effluents released from each unit to unrestricted areas, conforming to 10 CFR 50, Appendix I;
: e.
Determination of cumulative dose contributions from radioactive effluents for the current calendar quarter and current calendar year in accordance with the methodology and parameters in the ODCM at least every 31 days. Determination of projected dose contributions from radioactive effluents in accordance with the methodology in the ODCM at least every 31 days;
: f.
Limitations on the functional capability and use of the liquid and gaseous effluent treatment systems to ensure that appropriate portions of these systems are used to reduce releases of radioactivity when the projected doses in a period of 31 days would exceed 2% of the guidelines for the annual dose or dose commitment, conforming to 10 CFR 50, Appendix I;  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2.7 Radioactive Effluent Controls Program (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: g. Limitations on the dose rate resulting from radioactive material released in gaseous effluents from the site to areas at or beyond the site boundary shall be in accordance with the following:
(continued)
: 1. For noble gases: a dose rate 500 mrem/yr to the whole body and a dose rate 3000 mrem/yr to the skin, and
Watts Bar - Unit 2 5.0-12 (developmental)
: 2. For idodine-131, idodine-133, tritium, and all radionuclides in particulate form with halfliveshalf lives greater than 8 days: a dose rate 1500 mrem/yr to any organ.
AI 5.7.2.7 Radioactive Effluent Controls Program (continued)
: h. Limitations on the annual and quarterly air doses resulting from noble gases released in gaseous effluents from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I;
: g.
: i. Limitations on the annual and quarterly doses to a member of the public from iodine-131, iodine-133, tritium, and all radionuclides in particulate form with half lives > 8 days in gaseous effluents released from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I; and
Limitations on the dose rate resulting from radioactive material released in gaseous effluents from the site to areas at or beyond the site boundary shall be in accordance with the following:
: j. Limitations on the annual dose or dose commitment to any member of the public, beyond the site boundary, due to releases of radioactivity and to radiation from uranium fuel cycle sources, conforming to 40 CFR 190.
: 1. For noble gases: a dose rate 500 mrem/yr to the whole body and a dose rate 3000 mrem/yr to the skin, and
: 2. For idodine-131, idodine-133, tritium, and all radionuclides in particulate form with halfliveshalf lives greater than 8 days: a dose rate 1500 mrem/yr to any organ.
: h.
Limitations on the annual and quarterly air doses resulting from noble gases released in gaseous effluents from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I;
: i.
Limitations on the annual and quarterly doses to a member of the public from iodine-131, iodine-133, tritium, and all radionuclides in particulate form with half lives > 8 days in gaseous effluents released from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I; and
: j.
Limitations on the annual dose or dose commitment to any member of the public, beyond the site boundary, due to releases of radioactivity and to radiation from uranium fuel cycle sources, conforming to 40 CFR 190.
The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Radioactive Effluent Controls Program surveillance frequency.
The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Radioactive Effluent Controls Program surveillance frequency.
5.7.2.8 (removed from Technical Specifications) 5.7.2.9 Component Cyclic or Transient Limit This program provides controls to track the FSAR, Section 5.2.1.5, cyclic and transient occurrences to ensure that components are maintained within the design limits.
5.7.2.8 (removed from Technical Specifications) 5.7.2.9 Component Cyclic or Transient Limit This program provides controls to track the FSAR, Section 5.2.1.5, cyclic and transient occurrences to ensure that components are maintained within the design limits.
5.7.2.10 Reactor Coolant Pump Flywheel Inspection Program This program shall provide for the inspection of each reactor coolant pump flywheel per the recommendations of Regulation Position c.4.b of Regulatory Guide 1.14, Revision 1, August 1975.
5.7.2.10 Reactor Coolant Pump Flywheel Inspection Program This program shall provide for the inspection of each reactor coolant pump flywheel per the recommendations of Regulation Position c.4.b of Regulatory Guide 1.14, Revision 1, August 1975.  
 
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
(continued)
(continued)
Watts Bar - Unit 2                         5.0-12 (developmental)                                                                                 AI
Watts Bar - Unit 2 5.0-13 (developmental)
A 5.7.2.11 Inservice Testing Program This program provides controls for inservice testing of ASME Code Class 1, 2, and 3 components. The program shall include the following:
: a.
Testing frequencies applicable to the ASME Code for Operations and Maintenance of Nuclear Power Plants (ASME OM Code) and applicable Addenda as follows:
ASME OM Code and applicable Addenda terminology for inservice testing activities Required Frequencies for performing inservice testing activities Weekly At least once per 7 days Monthly At least once per 31 days Quarterly or every 3 months At least once per 92 days Semiannually or every 6 months At least once per 184 days Every 9 months At least once per 276 days Yearly or annually At least once per 366 days Biennially or every 2 years At least once per 731 days
: b.
The provisions of SR 3.0.2 are applicable to the above required Frequencies and other normal and accelerated Frequencies specified as 2 years or less in the Inservice Testing Program for performing inservice testing activities;
: c.
The provisions of SR 3.0.3 are applicable to inservice testing activities; and
: d.
Nothing in the ASME OM Code shall be construed to supersede the requirements of any TS.


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2.11    Inservice Testing Program This program provides controls for inservice testing of ASME Code Class 1, 2, and 3 components. The program shall include the following:
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: a. Testing frequencies applicable to the ASME Code for Operations and Maintenance of Nuclear Power Plants (ASME OM Code) and applicable Addenda as follows:
ASME OM Code and applicable Addenda terminology          Required Frequencies for performing for inservice testing activities              inservice testing activities Weekly                    At least once per 7 days Monthly                  At least once per 31 days Quarterly or every 3 months          At least once per 92 days Semiannually or every 6 months          At least once per 184 days Every 9 months                At least once per 276 days Yearly or annually              At least once per 366 days Biennially or every 2 years          At least once per 731 days
: b. The provisions of SR 3.0.2 are applicable to the above required Frequencies and other normal and accelerated Frequencies specified as 2 years or less in the Inservice Testing Program for performing inservice testing activities;
: c. The provisions of SR 3.0.3 are applicable to inservice testing activities; and
: d. Nothing in the ASME OM Code shall be construed to supersede the requirements of any TS.
(continued)
(continued)
Watts Bar - Unit 2                             5.0-13 (developmental)                                                                                   A
Watts Bar-Unit 2 5.0-14 (developmental)
GI 5.7.2.12 Steam Generator (SG) Program A Steam Generator Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the Steam Generator Program shall include the following provisions:
: a.
Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the "as found" condition of the tubing with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the condition of the tubing during an SG inspection outage, as determined from the inservice inspection results or by other means, prior to the plugging or repair of tubes.
Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged, to confirm that the performance criteria are being met.
: b.
Performance criteria for SG tube integrity. SG tube integrity shall be maintained by meeting the performance criteria for tube structural integrity, accident induced leakage, and operational LEAKAGE.
: 1.
Structural integrity performance criterion: All in-service steam generator tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, hot standby, and cooldown, and all anticipated transients included in the design specification), and design basis accidents. This includes retaining a safety factor of 3.0 against burst under normal steady state full power operation primary-to-secondary pressure differential and a safety factor of 1.4 against burst applied to the design basis accident primary-to-secondary pressure differentials. Apart from the above requirements, additional loading conditions associated with the design basis accidents, or combination of accidents in accordance with the design and licensing basis, shall also be evaluated to determine if the associated loads contribute significantly to burst or collapse. In the assessment of tube integrity, those loads that do significantly affect burst or collapse shall be determined and assessed in combination with the loads due to pressure with a safety factor of 1.2 on the combined primary loads and 1.0 on axial secondary loads.


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2.12 Steam Generator (SG) Program A Steam Generator Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the Steam Generator Program shall include the following provisions:
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: a. Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the "as found" condition of the tubing with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the condition of the tubing during an SG inspection outage, as determined from the inservice inspection results or by other means, prior to the plugging or repair of tubes.
Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged, to confirm that the performance criteria are being met.
: b. Performance criteria for SG tube integrity. SG tube integrity shall be maintained by meeting the performance criteria for tube structural integrity, accident induced leakage, and operational LEAKAGE.
: 1. Structural integrity performance criterion: All in-service steam generator tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, hot standby, and cooldown, and all anticipated transients included in the design specification), and design basis accidents. This includes retaining a safety factor of 3.0 against burst under normal steady state full power operation primary-to-secondary pressure differential and a safety factor of 1.4 against burst applied to the design basis accident primary-to-secondary pressure differentials. Apart from the above requirements, additional loading conditions associated with the design basis accidents, or combination of accidents in accordance with the design and licensing basis, shall also be evaluated to determine if the associated loads contribute significantly to burst or collapse. In the assessment of tube integrity, those loads that do significantly affect burst or collapse shall be determined and assessed in combination with the loads due to pressure with a safety factor of 1.2 on the combined primary loads and 1.0 on axial secondary loads.
(continued)
(continued)
Watts Bar-Unit 2                             5.0-14 (developmental)                                                                                 GI
Watts Bar-Unit 2 5.0-15 (developmental)
GI 5.7.2.12 Steam Generator (SG) Program (continued)
: 2.
Accident induced leakage performance criterion: The primary-to-secondary accident induced leakage rate for any design basis accident, other than an SG tube rupture, shall not exceed the leakage rate assumed in the accident analysis in terms of total leakage rate for all SGs and leakage rate for an individual SG. Leakage is not to exceed1 gpm per SG, except for specific types of degradation at specific locations as described in paragraph c.
of the Steam Generator Program.
: 3.
The operational leakage performance criterion is specified in LCO 3.4.13, "RCS Operational LEAKAGE."
: c.
Provisions for SG tube plugging or repair criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged or repaired.
: d.
Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube plugging or repair criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of d.1, d.2, and d.3 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. An degradation assessment of degradation shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
: 1.
Inspect 100% of the tubes in each SG during the first refueling outage following SG installation.


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2.12 Steam Generator (SG) Program (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: 2. Accident induced leakage performance criterion: The primary-to-secondary accident induced leakage rate for any design basis accident, other than an SG tube rupture, shall not exceed the leakage rate assumed in the accident analysis in terms of total leakage rate for all SGs and leakage rate for an individual SG. Leakage is not to exceed1 gpm per SG, except for specific types of degradation at specific locations as described in paragraph c.
of the Steam Generator Program.
: 3. The operational leakage performance criterion is specified in LCO 3.4.13, "RCS Operational LEAKAGE."
: c. Provisions for SG tube plugging or repair criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged or repaired.
: d. Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube plugging or repair criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of d.1, d.2, and d.3 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. An degradation assessment of degradation shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
: 1. Inspect 100% of the tubes in each SG during the first refueling outage following SG installation.
(continued)
(continued)
Watts Bar-Unit 2                           5.0-15 (developmental)                                                                               GI
Watts Bar-Unit 2 5.0-16 (developmental)
GI 5.7.2.12 Steam Generator (SG) Program (continued)
: 2.
After the first refueling outage following SG installation, inspect each SG at least every 24 effective full power months or at least every refueling outage (whichever results in more frequent inspections). In addition, inspect 100% of the tubes at sequential periods of 60 effective full power months beginning after the first refueling outage inspection following SG installation. Each 60 effective full power month inspection period may be extended up to 3 effective full power months to include a SG inspection outage in an inspection period and the subsequent inspection period begins at the conclusion of the included SG inspection outage. If a degradation assessment indicates the potential for a type of degradation to occur at a location not previously inspected with a technique capable of detecting this type of degradation at this location and that may satisfy the applicable tube pluggingrepair criteria, the minimum number of locations inspected with such a capable inspection technique during the remainder of the inspection period may be prorated. The fraction of locations to be inspected for this potential type of degradation at this location at the end of the inspection period shall be no less than the ratio of the number of times the SG is scheduled to be inspected in the inspection period after the determination that a new form of degradation could potentially be occurring at this location divided by the total number of times the SG is scheduled to be inspected in the inspection period.
: 3.
If crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.
: e.
Provisions for monitoring operational primary-to-secondary LEAKAGE.


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2.12 Steam Generator (SG) Program (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: 2. After the first refueling outage following SG installation, inspect each SG at least every 24 effective full power months or at least every refueling outage (whichever results in more frequent inspections). In addition, inspect 100% of the tubes at sequential periods of 60 effective full power months beginning after the first refueling outage inspection following SG installation. Each 60 effective full power month inspection period may be extended up to 3 effective full power months to include a SG inspection outage in an inspection period and the subsequent inspection period begins at the conclusion of the included SG inspection outage. If a degradation assessment indicates the potential for a type of degradation to occur at a location not previously inspected with a technique capable of detecting this type of degradation at this location and that may satisfy the applicable tube pluggingrepair criteria, the minimum number of locations inspected with such a capable inspection technique during the remainder of the inspection period may be prorated. The fraction of locations to be inspected for this potential type of degradation at this location at the end of the inspection period shall be no less than the ratio of the number of times the SG is scheduled to be inspected in the inspection period after the determination that a new form of degradation could potentially be occurring at this location divided by the total number of times the SG is scheduled to be inspected in the inspection period.
: 3. If crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.
: e. Provisions for monitoring operational primary-to-secondary LEAKAGE.
(continued)
(continued)
Watts Bar-Unit 2                           5.0-16 (developmental)                                                                               GI
Watts Bar-Unit 2 5.0-17 (developmental)
AI 5.7.2.13 Secondary Water Chemistry Program This program provides controls for monitoring secondary water chemistry to inhibit SG tube degradation and low pressure turbine disc stress corrosion cracking. The program shall include:
: a.
Identification of a sampling schedule for the critical variables and control points for these variables;
: b.
Identification of the procedures used to measure the values of the critical variables;
: c.
Identification of process sampling points, which shall include monitoring the discharge of the condensate pumps for evidence of condenser in leakage;
: d.
Procedures for the recording and management of data; Secondary Water Chemistry Program (continued)
: e.
Procedures defining corrective actions for all off control point chemistry conditions; and
: f.
A procedure identifying the authority responsible for the interpretation of the data and the sequence and timing of administrative events, which is required to initiate corrective action.


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2.13 Secondary Water Chemistry Program This program provides controls for monitoring secondary water chemistry to inhibit SG tube degradation and low pressure turbine disc stress corrosion cracking. The program shall include:
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: a. Identification of a sampling schedule for the critical variables and control points for these variables;
: b. Identification of the procedures used to measure the values of the critical variables;
: c. Identification of process sampling points, which shall include monitoring the discharge of the condensate pumps for evidence of condenser in leakage;
: d. Procedures for the recording and management of data; Secondary Water Chemistry Program (continued)
: e. Procedures defining corrective actions for all off control point chemistry conditions; and
: f. A procedure identifying the authority responsible for the interpretation of the data and the sequence and timing of administrative events, which is required to initiate corrective action.
(continued)
(continued)
Watts Bar-Unit 2                             5.0-17 (developmental)                                                                               AI
Watts Bar-Unit 2 5.0-18 (developmental)
 
HI 5.7.2.14 Ventilation Filter Testing Program (VFTP)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued) 5.7.2.14 Ventilation Filter Testing Program (VFTP)
A program shall be established to implement the following required testing of Engineered Safety Feature (ESF) filter ventilation systems at the frequencies specified in accordance with Regulatory Guide 1.52, Revision 2; ASME N510-1989, and the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR.
A program shall be established to implement the following required testing of Engineered Safety Feature (ESF) filter ventilation systems at the frequencies specified in accordance with Regulatory Guide 1.52, Revision 2; ASME N510-1989, and the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR.
: a. Demonstrate for each of the ESF systems that an inplace test of the high efficiency particulate air (HEPA) filters shows a penetration and system bypass within acceptance criterion when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.
: a.
ESF VENTILATION             ACCEPTANCE SYSTEM                    CRITERIA             FLOW RATE Emergency Gas                       < 0.05%           4,000 cfm +/-+ 10%
Demonstrate for each of the ESF systems that an inplace test of the high efficiency particulate air (HEPA) filters shows a penetration and system bypass within acceptance criterion when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.
Treatment Auxiliary Building Gas               < 0.05%           9,000 cfm +/-+ 10%
ESF VENTILATION SYSTEM ACCEPTANCE CRITERIA FLOW RATE Emergency Gas Treatment
Treatment Control Room Emergency               < 1.00%           4,000 cfm +/-+ 10%
< 0.05%
(continued)
4,000 cfm +/-+ 10%
Watts Bar-Unit 2                            5.0-18 (developmental)                                                                              HI
Auxiliary Building Gas Treatment
< 0.05%
9,000 cfm +/-+ 10%
Control Room Emergency  
< 1.00%
4,000 cfm +/-+ 10%  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.14 Ventilation Filter Testing Program (VFTP) (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: b. Demonstrate for each of the ESF systems that an inplace test of the charcoal adsorber shows a penetration and system bypass within acceptance criterion when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.
Watts Bar-Unit 2 5.0-19 (developmental)
ESF VENTILATION             ACCEPTANCE SYSTEM                  CRITERIA           FLOW RATE Emergency Gas Treatment             < 0.05%         4,000 cfm +/-+ 10%
HI 5.7.2.14 Ventilation Filter Testing Program (VFTP) (continued)
Auxiliary Building Gas             < 0.05%         9,000 cfm +/-+ 10%
: b.
Treatment Control Room Emergency             < 1.00%         4,000 cfm +/-+ 10%
Demonstrate for each of the ESF systems that an inplace test of the charcoal adsorber shows a penetration and system bypass within acceptance criterion when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.
(continued)
ESF VENTILATION SYSTEM ACCEPTANCE CRITERIA FLOW RATE Emergency Gas Treatment  
Watts Bar-Unit 2                            5.0-19 (developmental)                                                                            HI
< 0.05%
4,000 cfm +/-+ 10%
Auxiliary Building Gas Treatment
< 0.05%
9,000 cfm +/-+ 10%
Control Room Emergency  
< 1.00%
4,000 cfm +/-+ 10%  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.14 Ventilation Filter Testing Program (VFTP) (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: c. Demonstrate for each of the ESF systems that a laboratory test of a sample of the charcoal adsorber, when obtained as described in Regulatory Guide 1.52, Revision 2, and the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, shows the methyl iodide penetration less than the value specified below when tested in accordance with ASTM D3803-1989 at a temperature of 30&deg;C and greater than or equal to the relative humidity specified below.
Watts Bar-Unit 2 5.0-20 (developmental)
METHYL IODIDE          RELATIVE ESF VENTILATION SYSTEM                 PENETRATION           HUMIDITY Emergency Gas Treatment                     < 0.175%             70%
HI 5.7.2.14 Ventilation Filter Testing Program (VFTP) (continued)
Auxiliary Building Gas                       < 0.175%             70%
: c.
Treatment Control Room Emergency                       < 1.0%             70%
Demonstrate for each of the ESF systems that a laboratory test of a sample of the charcoal adsorber, when obtained as described in Regulatory Guide 1.52, Revision 2, and the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, shows the methyl iodide penetration less than the value specified below when tested in accordance with ASTM D3803-1989 at a temperature of 30&deg;C and greater than or equal to the relative humidity specified below.
: d. Demonstrate for each of the ESF systems that the pressure drop across the entire filtration unit is less than the value specified below when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.
ESF VENTILATION SYSTEM METHYL IODIDE PENETRATION RELATIVE HUMIDITY Emergency Gas Treatment  
ESF VENTILATION SYSTEM               PRESSURE DROP               FLOW RATE Emergency Gas                   < 7.6 inches water     4,000 cfm +/-+ 10%
< 0.175%
Treatment Auxiliary Building Gas           < 7.6 inches water     9,000 cfm +/-+ 10%
70%
Treatment Control Room Emergency           < 3.5 inches water     4,000 cfm +/-+ 10%
Auxiliary Building Gas Treatment
(continued)
< 0.175%
Watts Bar-Unit 2                            5.0-20 (developmental)                                                                                HI
70%
Control Room Emergency  
< 1.0%
70%
: d.
Demonstrate for each of the ESF systems that the pressure drop across the entire filtration unit is less than the value specified below when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.
ESF VENTILATION SYSTEM PRESSURE DROP FLOW RATE Emergency Gas Treatment
< 7.6 inches water 4,000 cfm +/-+ 10%
Auxiliary Building Gas Treatment
< 7.6 inches water 9,000 cfm +/-+ 10%
Control Room Emergency  
< 3.5 inches water 4,000 cfm +/-+ 10%  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.14   Ventilation Filter Testing Program (VFTP) (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: e. Demonstrate that the heaters for each of the ESF systems dissipate the value specified below when tested in accordance with ASME N510-1989.
Watts Bar - Unit 2 5.0-21 (developmental)
ESF VENTILATION SYSTEM                     AMOUNT OF HEAT Emergency Gas Treatment                             20 +/-+ 2.0 kW Auxiliary Building Gas Treatment                     50 +/-+ 5.0 kW The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the VFTP test frequencies.
AI 5.7.2.14 Ventilation Filter Testing Program (VFTP) (continued)
5.7.2.15   Explosive Gas and Storage Tank Radioactivity Monitoring Program This program provides controls for potentially explosive gas mixtures contained in the Waste Gas Holdup System, the quantity of radioactivity contained in gas storage tanks and the quantity of radioactivity contained in unprotected outdoor liquid storage tanks.
: e.
Demonstrate that the heaters for each of the ESF systems dissipate the value specified below when tested in accordance with ASME N510-1989.
ESF VENTILATION SYSTEM AMOUNT OF HEAT Emergency Gas Treatment 20 +/-+ 2.0 kW Auxiliary Building Gas Treatment 50 +/-+ 5.0 kW The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the VFTP test frequencies.
5.7.2.15 Explosive Gas and Storage Tank Radioactivity Monitoring Program This program provides controls for potentially explosive gas mixtures contained in the Waste Gas Holdup System, the quantity of radioactivity contained in gas storage tanks and the quantity of radioactivity contained in unprotected outdoor liquid storage tanks.
The gaseous radioactivity quantities shall be determined following the methodology in Branch Technical Position (BTP) ETSB 11-5, Postulated Radioactive Release due to Waste Gas System Leak or Failure. The liquid radwaste quantities shall be determined in accordance with Standard Review Plan, Section 15.7.3, Postulated Radioactive Release due to Tank Failures.
The gaseous radioactivity quantities shall be determined following the methodology in Branch Technical Position (BTP) ETSB 11-5, Postulated Radioactive Release due to Waste Gas System Leak or Failure. The liquid radwaste quantities shall be determined in accordance with Standard Review Plan, Section 15.7.3, Postulated Radioactive Release due to Tank Failures.
The program shall include:
The program shall include:
: a. The limits for concentrations of hydrogen and oxygen in the Waste Gas Holdup System and a surveillance program to ensure the limits are maintained. Such limits shall be appropriate to the system's design criteria (i.e., the system is not designed to withstand a hydrogen explosion);
: a.
(continued)
The limits for concentrations of hydrogen and oxygen in the Waste Gas Holdup System and a surveillance program to ensure the limits are maintained. Such limits shall be appropriate to the system's design criteria (i.e., the system is not designed to withstand a hydrogen explosion);  
Watts Bar - Unit 2                            5.0-21 (developmental)                                                                                AI


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.15 Explosive Gas and Storage Tank Radioactivity Monitoring Program (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: b. A surveillance program to ensure that the quantity of radioactivity contained in each gas storage tank is less than the amount that would result in a whole body exposure of > 0.5 rem to any individual in an unrestricted area, in the event of an uncontrolled release of the tanks' contents; and
Watts Bar-Unit 2 5.0-22 (developmental)
: c. A surveillance program to ensure that the quantity of radioactivity contained in all outdoor liquid radwaste tanks that are not surrounded by liners, dikes, or walls, capable of holding the tanks' contents and that do not have tank overflows and surrounding area drains connected to the Liquid Radwaste Treatment System is less than the amount that would result in concentrations less than the limits of 10 CFR 20.1302(b)(2)(i), at the nearest potable water supply and the nearest surface water supply in an unrestricted area, in the event of an uncontrolled release of the tanks' contents.
A 5.7.2.15 Explosive Gas and Storage Tank Radioactivity Monitoring Program (continued)
: b.
A surveillance program to ensure that the quantity of radioactivity contained in each gas storage tank is less than the amount that would result in a whole body exposure of > 0.5 rem to any individual in an unrestricted area, in the event of an uncontrolled release of the tanks' contents; and
: c.
A surveillance program to ensure that the quantity of radioactivity contained in all outdoor liquid radwaste tanks that are not surrounded by liners, dikes, or walls, capable of holding the tanks' contents and that do not have tank overflows and surrounding area drains connected to the Liquid Radwaste Treatment System is less than the amount that would result in concentrations less than the limits of 10 CFR 20.1302(b)(2)(i), at the nearest potable water supply and the nearest surface water supply in an unrestricted area, in the event of an uncontrolled release of the tanks' contents.
The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program surveillance frequencies.
The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program surveillance frequencies.
5.7.2.16 Diesel Fuel Oil Testing Program A diesel fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil shall be established. The program shall include sampling and testing requirements, and acceptance criteria, all in accordance with applicable ASTM Standards. The purpose of the program is to establish the following:
5.7.2.16 Diesel Fuel Oil Testing Program A diesel fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil shall be established. The program shall include sampling and testing requirements, and acceptance criteria, all in accordance with applicable ASTM Standards. The purpose of the program is to establish the following:
: a. Acceptability of new fuel oil for use prior to addition to the 7 day storage tanks by determining that the fuel oil has:
: a.
: 1. an API gravity or an absolute specific gravity within limits,
Acceptability of new fuel oil for use prior to addition to the 7 day storage tanks by determining that the fuel oil has:
: 2. a flash point and kinematics viscosity within limits for ASTM 2D fuel oil, and
: 1.
: 3. a clear and bright appearance with proper color; (continued)
an API gravity or an absolute specific gravity within limits,
Watts Bar-Unit 2                            5.0-22 (developmental)                                                                                  A
: 2.
a flash point and kinematics viscosity within limits for ASTM 2D fuel oil, and
: 3.
a clear and bright appearance with proper color;  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.16 Diesel Fuel Oil Testing Program (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
: b. Other properties for ASTM 2D fuel oil are within limits within 31 days following sampling and addition to the 7 day storage tanks; and
Watts Bar-Unit 2 5.0-23 (developmental)
: c. Total particulate concentration of the fuel oil in each of the four interconnected tanks which constitute a 7 day storage tank is 10 mg/l when tested every 31 days in accordance with ASTM D-2276, Method A-2 or A-3.
A 5.7.2.16 Diesel Fuel Oil Testing Program (continued)
: b.
Other properties for ASTM 2D fuel oil are within limits within 31 days following sampling and addition to the 7 day storage tanks; and
: c.
Total particulate concentration of the fuel oil in each of the four interconnected tanks which constitute a 7 day storage tank is 10 mg/l when tested every 31 days in accordance with ASTM D-2276, Method A-2 or A-3.
5.7.2.17 (removed from Technical Specifications) 5.7.2.18 Safety Function Determination Program (SFDP)
5.7.2.17 (removed from Technical Specifications) 5.7.2.18 Safety Function Determination Program (SFDP)
This program ensures loss of safety function is detected and appropriate actions taken. Upon entry into LCO 3.0.6, an evaluation shall be made to determine if loss of safety function exists.
This program ensures loss of safety function is detected and appropriate actions taken. Upon entry into LCO 3.0.6, an evaluation shall be made to determine if loss of safety function exists.
Additionally, other appropriate actions may be taken as a result of the support system inoperability and corresponding exception to entering supported system Condition and Required Actions. This program implements the requirements of LCO 3.0.6. The SFDP shall contain the following:
Additionally, other appropriate actions may be taken as a result of the support system inoperability and corresponding exception to entering supported system Condition and Required Actions. This program implements the requirements of LCO 3.0.6. The SFDP shall contain the following:
: a. Provisions for cross train checks to ensure a loss of the capability to perform the safety function assumed in the accident analysis does not go undetected;
: a.
: b. Provisions for ensuring the plant is maintained in a safe condition if a loss of function condition exists;
Provisions for cross train checks to ensure a loss of the capability to perform the safety function assumed in the accident analysis does not go undetected;
: c. Provisions to ensure that an inoperable supported system's Completion Time is not inappropriately extended as a result of multiple support system inoperabilities; and
: b.
: d. Other appropriate limitations and remedial or compensatory actions.
Provisions for ensuring the plant is maintained in a safe condition if a loss of function condition exists;
(continued)
: c.
Watts Bar-Unit 2                            5.0-23 (developmental)                                                                                  A
Provisions to ensure that an inoperable supported system's Completion Time is not inappropriately extended as a result of multiple support system inoperabilities; and
: d.
Other appropriate limitations and remedial or compensatory actions.  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.18 Safety Function Determination Program (SFDP) (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
Watts Bar-Unit 2 5.0-24 (developmental)
A 5.7.2.18 Safety Function Determination Program (SFDP) (continued)
A loss of safety function exists when, assuming no concurrent single failure, a safety function assumed in the accident analysis cannot be performed. For the purpose of this program, a loss of safety function may exist when a support system is inoperable, and:
A loss of safety function exists when, assuming no concurrent single failure, a safety function assumed in the accident analysis cannot be performed. For the purpose of this program, a loss of safety function may exist when a support system is inoperable, and:
: a. A required system redundant to the system(s) supported by the inoperable support system is also inoperable; or
: a.
: b. A required system redundant to the system(s) in turn supported by the inoperable supported system is also inoperable; or
A required system redundant to the system(s) supported by the inoperable support system is also inoperable; or
: c. A required system redundant to the support system(s) for the supported systems (a) and (b) above is also inoperable.
: b.
A required system redundant to the system(s) in turn supported by the inoperable supported system is also inoperable; or
: c.
A required system redundant to the support system(s) for the supported systems (a) and (b) above is also inoperable.
The SFDP identifies where a loss of safety function exists. If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.
The SFDP identifies where a loss of safety function exists. If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.
5.7.2.19 Containment Leakage Rate Testing Program A program shall be established to implement the leakage rate testing of the containment as required by 10 CFR 50.54(o) and 10 CFR 50 Appendix J, Option B, as modified by approved exemptions. This program shall be in accordance with the guidelines contained in Regulatory Guide (RG) 1.163, Performance-Based Containment Leak-Test Program, dated September 1995.
5.7.2.19 Containment Leakage Rate Testing Program A program shall be established to implement the leakage rate testing of the containment as required by 10 CFR 50.54(o) and 10 CFR 50 Appendix J, Option B, as modified by approved exemptions. This program shall be in accordance with the guidelines contained in Regulatory Guide (RG) 1.163, Performance-Based Containment Leak-Test Program, dated September 1995.
The peak calculated containment internal pressure for the design basis loss of coolant accident, Pa, is 15.0 psig.
The peak calculated containment internal pressure for the design basis loss of coolant accident, Pa, is 15.0 psig.
The maximum allowable containment leakage rate, La, at Pa, is 0.25%
The maximum allowable containment leakage rate, La, at Pa, is 0.25%
of the primary containment air weight per day.
of the primary containment air weight per day.  
(continued)
Watts Bar-Unit 2                            5.0-24 (developmental)                                                                              A


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.19 Containment Leakage Rate Testing Program (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals Watts Bar-Unit 2 5.0-25 (developmental)
HI 5.7.2.19 Containment Leakage Rate Testing Program (continued)
Leakage rate acceptance criteria are:
Leakage rate acceptance criteria are:
: a. Containment overall leakage rate acceptance criterion is 1.0 La.
: a.
During the first unit startup following testing in accordance with this program, the leakage rate acceptance criteria are < 0.60 La for the combined Type B and Type C tests, and 0.75 La for Type A tests.
Containment overall leakage rate acceptance criterion is 1.0 La.
: b. Air lock testing acceptance criteria are:
During the first unit startup following testing in accordance with this program, the leakage rate acceptance criteria are < 0.60 La for the combined Type B and Type C tests, and 0.75 La for Type A tests.
: 1. Overall air lock leakage rate is 0.05 La when tested at >
: b.
Air lock testing acceptance criteria are:
: 1. Overall air lock leakage rate is 0.05 La when tested at >
Pa.
Pa.
: 2. For each door, leakage rate is 0.01 La when pressurized to 6 psig.
: 2. For each door, leakage rate is 0.01 La when pressurized to 6 psig.
The provisions of SR 3.0.2 do not apply to the test frequencies specified in the Containment Leakage Rate Testing Program.
The provisions of SR 3.0.2 do not apply to the test frequencies specified in the Containment Leakage Rate Testing Program.
The provisions of SR 3.0.3 are applicable to the Containment Leakage Rate Testing Program.
The provisions of SR 3.0.3 are applicable to the Containment Leakage Rate Testing Program.
5.7.2.20 Control Room Envelope Habitability Program A Control Room Envelope (CRE) Habitability Program shall be established and implemented to ensure that CRE habitability is maintained such that, with an OPERABLE Control Room Emergency Ventilation System (CREVS), CRE occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program shall ensure that adequate radiation protection is provided to permit access and occupancy of the CRE under design basis accident (DBA) conditions without personnel receiving radiation exposures in excess of the applicable regulatory requirement {i.e., 5 rem Total Effective Dose Equivalent (TEDE) for a fuel handling accident or 5 rem whole body or its equivalent to any part of the body} for the duration of the accident. The program shall include the following elements:
5.7.2.20 Control Room Envelope Habitability Program A Control Room Envelope (CRE) Habitability Program shall be established and implemented to ensure that CRE habitability is maintained such that, with an OPERABLE Control Room Emergency Ventilation System (CREVS), CRE occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program shall ensure that adequate radiation protection is provided to permit access and occupancy of the CRE under design basis accident (DBA) conditions without personnel receiving radiation exposures in excess of the applicable regulatory requirement {i.e., 5 rem Total Effective Dose Equivalent (TEDE) for a fuel handling accident or 5 rem whole body or its equivalent to any part of the body} for the duration of the accident. The program shall include the following elements:
: a. The definition of the CRE and the CRE boundary.
: a.
: b. Requirements for maintaining the CRE boundary in its design condition including configuration control and preventive maintenance.
The definition of the CRE and the CRE boundary.
Watts Bar-Unit 2                            5.0-25 (developmental)                                                                                HI
: b.
Requirements for maintaining the CRE boundary in its design condition including configuration control and preventive maintenance.  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.20 Control Room Envelope Habitability Program (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals Watts Bar-Unit 2 5.0-26 (developmental)
: c. Requirements for (i) determining the unfiltered air inleakage past the CRE boundary into the CRE in accordance with the testing methods and at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, "Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors," Revision 0, May 2003, and (ii) assessing CRE habitability at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, Revision 0.
A 5.7.2.20 Control Room Envelope Habitability Program (continued)
: d. Measurement, at designated locations, of the CRE pressure relative to all external areas adjacent to the CRE boundary during the pressurization mode of operation by one train of the CREVS, operating at the flow rate defined in the Ventilation Filter Testing Program (VFTP), at a Frequency of 18 months on a STAGGERED TEST BASIS. The results shall be trended and used as part of the 18 month assessment of the CRE boundary.
: c.
: e. The quantitative limits on unfiltered air inleakage into the CRE.
Requirements for (i) determining the unfiltered air inleakage past the CRE boundary into the CRE in accordance with the testing methods and at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, "Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors," Revision 0, May 2003, and (ii) assessing CRE habitability at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, Revision 0.
: d.
Measurement, at designated locations, of the CRE pressure relative to all external areas adjacent to the CRE boundary during the pressurization mode of operation by one train of the CREVS, operating at the flow rate defined in the Ventilation Filter Testing Program (VFTP), at a Frequency of 18 months on a STAGGERED TEST BASIS. The results shall be trended and used as part of the 18 month assessment of the CRE boundary.
: e.
The quantitative limits on unfiltered air inleakage into the CRE.
These limits shall be stated in a manner to allow direct comparison to the unfiltered air inleakage measured by the testing described in paragraph c. The unfiltered air inleakage limit for radiological challenges is the inleakage flow rate assumed in the licensing basis analyses of DBA consequences.
These limits shall be stated in a manner to allow direct comparison to the unfiltered air inleakage measured by the testing described in paragraph c. The unfiltered air inleakage limit for radiological challenges is the inleakage flow rate assumed in the licensing basis analyses of DBA consequences.
Unfiltered air inleakage limits for hazardous chemicals must ensure that exposure of CRE occupants to these hazards will be within the assumptions in the licensing basis.
Unfiltered air inleakage limits for hazardous chemicals must ensure that exposure of CRE occupants to these hazards will be within the assumptions in the licensing basis.
: f. The provisions of SR 3.0.2 are applicable to the frequencies for assessing CRE habitability, determining CRE unfiltered inleakage, and measuring CRE pressure and assessing the CRE boundary as required by paragraphs c and d, respectively.
: f.
Watts Bar-Unit 2                            5.0-26 (developmental)                                                                                  A
The provisions of SR 3.0.2 are applicable to the frequencies for assessing CRE habitability, determining CRE unfiltered inleakage, and measuring CRE pressure and assessing the CRE boundary as required by paragraphs c and d, respectively.  


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.21 Battery Monitoring and Maintenance Program This Program provides controls for battery restoration and maintenance. The program shall be in accordance with IEEE Standard (Std) 450-2002, "IEEE Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid Batteries for Stationary Applications," as endorsed by Regulatory Guide 1.129, Revision 2 (RG), with RG exceptions and program provisions as identified below:
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
Watts Bar-Unit 2 5.0-27 (developmental)
HI 5.7.2.21 Battery Monitoring and Maintenance Program This Program provides controls for battery restoration and maintenance. The program shall be in accordance with IEEE Standard (Std) 450-2002, "IEEE Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid Batteries for Stationary Applications," as endorsed by Regulatory Guide 1.129, Revision 2 (RG), with RG exceptions and program provisions as identified below:
: a. The program allows the following RG 1.129, Revision 2 exceptions:
: a. The program allows the following RG 1.129, Revision 2 exceptions:
: 1. Battery temperature correction may be performed before or after conducting discharge tests.
: 1. Battery temperature correction may be performed before or after conducting discharge tests.
Line 1,803: Line 2,830:
: 3. In lieu of RG 1.129, Regulatory Position 2, Subsection 5.2, "Inspections," the following shall be used: "Where reference is made to the pilot cell, pilot cell selection shall be based on the lowest voltage cell in the battery.
: 3. In lieu of RG 1.129, Regulatory Position 2, Subsection 5.2, "Inspections," the following shall be used: "Where reference is made to the pilot cell, pilot cell selection shall be based on the lowest voltage cell in the battery.
: 4. In Regulatory Guide 1.129, Regulatory Position 3, Subsection 5.4.1, "State of Charge Indicator," the following statements in paragraph (d) may be omitted: "When it has been recorded that the charging current has stabilized at the charging voltage for three consecutive hourly measurements, the battery is near full charge. These measurements shall be made after the initially high charging current decreases sharply and the battery voltage rises to approach the charger output voltage."
: 4. In Regulatory Guide 1.129, Regulatory Position 3, Subsection 5.4.1, "State of Charge Indicator," the following statements in paragraph (d) may be omitted: "When it has been recorded that the charging current has stabilized at the charging voltage for three consecutive hourly measurements, the battery is near full charge. These measurements shall be made after the initially high charging current decreases sharply and the battery voltage rises to approach the charger output voltage."
: 5. In lieu of RG 1.129, Regulatory Position 7, Subsection 7.6, "Restoration", the following may be used: "Following the test, record the float voltage of each cell of the string."
: 5. In lieu of RG 1.129, Regulatory Position 7, Subsection 7.6, "Restoration", the following may be used: "Following the test, record the float voltage of each cell of the string."  
(continued)
Watts Bar-Unit 2                            5.0-27 (developmental)                                                                                HI


Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals 5.7.2.21 Battery Monitoring and Maintenance Program (continued)
Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)
Watts Bar-Unit 2 5.0-28 (developmental)
HI 5.7.2.21 Battery Monitoring and Maintenance Program (continued)
: b. The program shall include the following provisions:
: b. The program shall include the following provisions:
: 1. Actions to restore battery cells with float voltage < 2.13 V;
: 1. Actions to restore battery cells with float voltage < 2.13 V;
: 2. Actions to determine whether the float voltage of the remaining battery cells is 2.13 V when the float voltage of a battery cell has been found to be < 2.13 V;
: 2. Actions to determine whether the float voltage of the remaining battery cells is 2.13 V when the float voltage of a battery cell has been found to be < 2.13 V;
: 3. Actions to equalize and test battery cells that had been discovered with electrolyte level below the top of the plates;
: 3. Actions to equalize and test battery cells that had been discovered with electrolyte level below the top of the plates;
: 4. Limits on average electrolyte temperature, battery connection resistance, and battery terminal voltage; and
: 4. Limits on average electrolyte temperature, battery connection resistance, and battery terminal voltage; and
: 5. A requirement to obtain specific gravity readings of all cells at each discharge test, consistent with manufacturer recommendations.
: 5. A requirement to obtain specific gravity readings of all cells at each discharge test, consistent with manufacturer recommendations.  
(continued)
Watts Bar-Unit 2                          5.0-28 (developmental)                                                                              HI


SFDP 5.8 5.0 ADMINISTRATIVE CONTROLS 5.8 Safety Function Determination Program (SFDP)
SFDP 5.8 Watts Bar - Unit 2 5.0-29 (developmental)
(moved to 5.7.2.18)
A 5.0 ADMINISTRATIVE CONTROLS 5.8 Safety Function Determination Program (SFDP)
Watts Bar - Unit 2                        5.0-29 (developmental)                                            A
(moved to 5.7.2.18)  


Reporting Requirements 5.9 5.0 ADMINISTRATIVE CONTROLS 5.9 Reporting Requirements The following reports shall be submitted in accordance with 10 CFR 50.4.
Reporting Requirements 5.9 (continued)
5.9.1   DELETED 5.9.2   Annual Radiological Environmental Operating Report
Watts Bar - Unit 2 5.0-30 (developmental)
              -------------------------------------------------NOTE-------------------------------------------------
H 5.0 ADMINISTRATIVE CONTROLS 5.9 Reporting Requirements The following reports shall be submitted in accordance with 10 CFR 50.4.
5.9.1 DELETED 5.9.2 Annual Radiological Environmental Operating Report  
-------------------------------------------------NOTE-------------------------------------------------
A single submittal may be made for a multiple unit station. The submittal should combine sections common to all units at the station.
A single submittal may be made for a multiple unit station. The submittal should combine sections common to all units at the station.
The Annual Radiological Environmental Operating Report covering the operation of the unit during the previous calendar year shall be submitted by May 15 of each year. The report shall include summaries, interpretations, and analyses of trends of the results of the Radiological Environmental Monitoring Program for the reporting period. The material provided shall be consistent with the objectives outlined in the Offsite Dose Calculation Manual (ODCM), and in 10 CFR 50, Appendix I, Sections IV.B.2, IV.B.3, and IV.C.
The Annual Radiological Environmental Operating Report covering the operation of the unit during the previous calendar year shall be submitted by May 15 of each year. The report shall include summaries, interpretations, and analyses of trends of the results of the Radiological Environmental Monitoring Program for the reporting period. The material provided shall be consistent with the objectives outlined in the Offsite Dose Calculation Manual (ODCM), and in 10 CFR 50, Appendix I, Sections IV.B.2, IV.B.3, and IV.C.
The Annual Radiological Environmental Operating Report shall include the results of analyses of all radiological environmental samples and of all environmental radiation measurements taken during the period pursuant to the locations specified in the table and figures in the ODCM, as well as summarized and tabulated results of these analyses and measurements in the format of the table in the Radiological Assessment Branch Technical Position, Revision 1, November 1979. In the event that some individual results are not available for inclusion with the report, the report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted in a supplementary report as soon as possible.
The Annual Radiological Environmental Operating Report shall include the results of analyses of all radiological environmental samples and of all environmental radiation measurements taken during the period pursuant to the locations specified in the table and figures in the ODCM, as well as summarized and tabulated results of these analyses and measurements in the format of the table in the Radiological Assessment Branch Technical Position, Revision 1, November 1979. In the event that some individual results are not available for inclusion with the report, the report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted in a supplementary report as soon as possible.  
 
Reporting Requirements 5.9 5.9 Reporting Requirements (continued)
(continued)
(continued)
Watts Bar - Unit 2                                   5.0-30 (developmental)                                                                                                         H
Watts Bar - Unit 2 5.0-31 (developmental)
 
B 5.9.3 Radioactive Effluent Release Report  
Reporting Requirements 5.9 5.9 Reporting Requirements (continued) 5.9.3   Radioactive Effluent Release Report
-------------------------------------------------NOTE-------------------------------------------------
              -------------------------------------------------NOTE-------------------------------------------------
A single submittal may be made for a multiple unit station. The submittal should combine sections common to all units at the station; however, for units with separate radwaste systems, the submittal shall specify the releases of radioactive material from each unit.
A single submittal may be made for a multiple unit station. The submittal should combine sections common to all units at the station; however, for units with separate radwaste systems, the submittal shall specify the releases of radioactive material from each unit.
The Radioactive Effluent Release Report covering the operation of the unit during the previous year shall be submitted prior to May 1 of each year in accordance with 10 CFR 50.36a. The report shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the unit. The material provided shall be consistent with the objectives outlined in the ODCM and Process Control Program and in conformance with 10 CFR 50.36a and 10 CFR 50, Appendix I, Section IV.B.1.
The Radioactive Effluent Release Report covering the operation of the unit during the previous year shall be submitted prior to May 1 of each year in accordance with 10 CFR 50.36a. The report shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the unit. The material provided shall be consistent with the objectives outlined in the ODCM and Process Control Program and in conformance with 10 CFR 50.36a and 10 CFR 50, Appendix I, Section IV.B.1.
5.9.4   DELETED 5.9.5   CORE OPERATING LIMITS REPORT (COLR)
5.9.4 DELETED 5.9.5 CORE OPERATING LIMITS REPORT (COLR)
: a. Core operating limits shall be established prior to the initial and each reload cycle, or prior to any remaining portion of a cycle, and shall be documented in the COLR for the following:
: a.
LCO 3.1.4               Moderator Temperature Coefficient LCO 3.1.6               Shutdown Bank Insertion Limits LCO 3.1.7               Control Bank Insertion Limits LCO 3.2.1               Heat Flux Hot Channel Factor LCO 3.2.2               Nuclear Enthalpy Rise Hot Channel Factor LCO 3.2.3               Axial Flux Difference LCO 3.9.1               Boron Concentration
Core operating limits shall be established prior to the initial and each reload cycle, or prior to any remaining portion of a cycle, and shall be documented in the COLR for the following:
: b. The analytical methods used to determine the core operating limits shall be those previously reviewed and approved by the NRC, specifically those described in the following documents:
LCO 3.1.4 Moderator Temperature Coefficient LCO 3.1.6 Shutdown Bank Insertion Limits LCO 3.1.7 Control Bank Insertion Limits LCO 3.2.1 Heat Flux Hot Channel Factor LCO 3.2.2 Nuclear Enthalpy Rise Hot Channel Factor LCO 3.2.3 Axial Flux Difference LCO 3.9.1 Boron Concentration
: b.
The analytical methods used to determine the core operating limits shall be those previously reviewed and approved by the NRC, specifically those described in the following documents:  
 
Reporting Requirements 5.9 5.9 Reporting Requirements (continued)
(continued)
(continued)
Watts Bar - Unit 2                                   5.0-31 (developmental)                                                                                                         B
Watts Bar-Unit 2 5.0-32 (developmental)
 
B 5.9.5 CORE OPERATING LIMITS REPORT (COLR) (continued)
Reporting Requirements 5.9 5.9 Reporting Requirements (continued) 5.9.5   CORE OPERATING LIMITS REPORT (COLR) (continued)
: 1. WCAP-9272-P-A, WESTINGHOUSE RELOAD SAFETY EVALUATION METHODOLOGY, July 1985 (W Proprietary). (Methodology for Specifications 3.1.4 - Moderator Temperature Coefficient, 3.1.6 -
: 1. WCAP-9272-P-A, WESTINGHOUSE RELOAD SAFETY EVALUATION METHODOLOGY, July 1985 (W Proprietary). (Methodology for Specifications 3.1.4 - Moderator Temperature Coefficient, 3.1.6 -
Shutdown Bank Insertion Limit, 3.1.7 - Control Bank Insertion Limits, 3.2.1 - Heat Flux Hot Channel Factor, 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor, 3.2.3 - Axial Flux Difference, and 3.9.1 - Boron Concentration).
Shutdown Bank Insertion Limit, 3.1.7 - Control Bank Insertion Limits, 3.2.1 - Heat Flux Hot Channel Factor, 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor, 3.2.3 - Axial Flux Difference, and 3.9.1 - Boron Concentration).
Line 1,847: Line 2,878:
2b. WCAP-10054-P-A, Small Break ECCS Evaluation Model Using NOTRUMP Code, August 1985. Addendum 2, Rev. 1: Addendum to the Westinghouse Small Break ECCS Evaluation Model using the NOTRUMP Code: Safety Injection into the Broken Loop and COSI Condensation Model, July 1997. (W Proprietary). (Methodology for Specifications 3.2.1 - Heat Flux Hot Channel Factor, and 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).
2b. WCAP-10054-P-A, Small Break ECCS Evaluation Model Using NOTRUMP Code, August 1985. Addendum 2, Rev. 1: Addendum to the Westinghouse Small Break ECCS Evaluation Model using the NOTRUMP Code: Safety Injection into the Broken Loop and COSI Condensation Model, July 1997. (W Proprietary). (Methodology for Specifications 3.2.1 - Heat Flux Hot Channel Factor, and 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).
: 3. WCAP-10216-P-A, Revision 1A, RELAXATION OF CONSTANT AXIAL OFFSET CONTROL F(Q) SURVEILLANCE TECHNICAL SPECIFICATION, February 1994 (W Proprietary). (Methodology for Specifications 3.2.1 - Heat Flux Hot Channel Factor (W(Z) Surveillance Requirements For F(Q) Methodology) and 3.2.3 - Axial Flux Difference (Relaxed Axial Offset Control).)
: 3. WCAP-10216-P-A, Revision 1A, RELAXATION OF CONSTANT AXIAL OFFSET CONTROL F(Q) SURVEILLANCE TECHNICAL SPECIFICATION, February 1994 (W Proprietary). (Methodology for Specifications 3.2.1 - Heat Flux Hot Channel Factor (W(Z) Surveillance Requirements For F(Q) Methodology) and 3.2.3 - Axial Flux Difference (Relaxed Axial Offset Control).)
: 4. WCAP-12610-P-A, VANTAGE + FUEL ASSEMBLY REFERENCE CORE REPORT, April 1995. (W Proprietary). (Methodology for Specification 3.2.1 - Heat Flux Hot Channel Factor).
: 4. WCAP-12610-P-A, VANTAGE + FUEL ASSEMBLY REFERENCE CORE REPORT, April 1995. (W Proprietary). (Methodology for Specification 3.2.1 - Heat Flux Hot Channel Factor).  
 
Reporting Requirements 5.9 5.9 Reporting Requirements (continued)
(continued)
(continued)
Watts Bar-Unit 2                           5.0-32 (developmental)                                                                             B
Watts Bar-Unit 2 5.0-33 (developmental)
 
A 5.9.5 CORE OPERATING LIMITS REPORT (COLR) (continued)
Reporting Requirements 5.9 5.9 Reporting Requirements (continued) 5.9.5   CORE OPERATING LIMITS REPORT (COLR) (continued)
: 5. WCAP-15088-P, Rev. 1, Safety Evaluation Supporting A More Negative EOL Moderator Temperature Coefficient Technical Specification for the Watts Bar Nuclear Plant, July 1999, (W Proprietary), as approved by the NRC staffs Safety Evaluation accompanying the issuance of Amendment No. 20 (Methodology for Specification 3.1.4 - Moderator Temperature Coefficient.).
: 5. WCAP-15088-P, Rev. 1, Safety Evaluation Supporting A More Negative EOL Moderator Temperature Coefficient Technical Specification for the Watts Bar Nuclear Plant, July 1999, (W Proprietary), as approved by the NRC staffs Safety Evaluation accompanying the issuance of Amendment No. 20 (Methodology for Specification 3.1.4 - Moderator Temperature Coefficient.).
: 6. WCAP-11397-P-A, Revised Thermal Design Procedure, April 1989.
: 6. WCAP-11397-P-A, Revised Thermal Design Procedure, April 1989.
Line 1,857: Line 2,889:
: 7. WCAP-15025-P-A, Modified WRB-2 Correlation, WRB-2M, for Predicting Critical Heat Flux in 17 x 17 Rod Bundles with Modified LPD Mixing Vane Grids, April 1999. (Methodology for Specification 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).
: 7. WCAP-15025-P-A, Modified WRB-2 Correlation, WRB-2M, for Predicting Critical Heat Flux in 17 x 17 Rod Bundles with Modified LPD Mixing Vane Grids, April 1999. (Methodology for Specification 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).
: 8. WCAP-14565-P-A, VIPRE-01 Modeling and Qualification for Pressurized Water Reactor Non-LOCA Thermal-Hydraulic Safety Analysis, October 1999. (Methodology for Specification 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).
: 8. WCAP-14565-P-A, VIPRE-01 Modeling and Qualification for Pressurized Water Reactor Non-LOCA Thermal-Hydraulic Safety Analysis, October 1999. (Methodology for Specification 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).
: c. The core operating limits shall be determined such that all applicable limits (e.g., fuel thermal mechanical limits, core thermal hydraulic limits, Emergency Core Cooling Systems (ECCS) limits, nuclear limits such as SDM, transient analysis limits, and accident analysis limits) of the safety analysis are met.
: c.
: d. The COLR, including any midcycle revisions or supplements, shall be provided upon issuance for each reload cycle to the NRC.
The core operating limits shall be determined such that all applicable limits (e.g., fuel thermal mechanical limits, core thermal hydraulic limits, Emergency Core Cooling Systems (ECCS) limits, nuclear limits such as SDM, transient analysis limits, and accident analysis limits) of the safety analysis are met.
: d.
The COLR, including any midcycle revisions or supplements, shall be provided upon issuance for each reload cycle to the NRC.  
 
Reporting Requirements 5.9 5.9 Reporting Requirements (continued)
(continued)
(continued)
Watts Bar-Unit 2                           5.0-33 (developmental)                                                                                 A
Watts Bar-Unit 2 5.0-34 (developmental)
 
B 5.9.6 Reactor Coolant System (RCS) PRESSURE AND TEMPERATURE LIMITS REPORT (PTLR)
Reporting Requirements 5.9 5.9 Reporting Requirements (continued) 5.9.6   Reactor Coolant System (RCS) PRESSURE AND TEMPERATURE LIMITS REPORT (PTLR)
: a.
: a. RCS pressure and temperature limits for heatup, cooldown, low temperature operation, criticality, and hydrostatic testing as well as heatup and cooldown rates shall be established and documented in the PTLR for the following:
RCS pressure and temperature limits for heatup, cooldown, low temperature operation, criticality, and hydrostatic testing as well as heatup and cooldown rates shall be established and documented in the PTLR for the following:
LCO 3.4.3     RCS Pressure and Temperature (P/T) Limits
LCO 3.4.3 RCS Pressure and Temperature (P/T) Limits
: b. The power operated relief valve lift settings required to support the Cold Overpressure Mitigation System (COMS) and the COMS arming temperature shall be established and documented in the PTLR for the following:
: b.
The power operated relief valve lift settings required to support the Cold Overpressure Mitigation System (COMS) and the COMS arming temperature shall be established and documented in the PTLR for the following:
LCO 3.4.12 Cold Overpressure Mitigation System
LCO 3.4.12 Cold Overpressure Mitigation System
: c. The analytical methods used to determine the RCS pressure and temperature limits and Cold Overpressure Mitigation System setpoints shall be those previously reviewed and approved by the NRC, specifically those described in the following documents:
: c.
: 1. WCAP-14040-A, Rev. 4 Methodology Used to Develop Cold Overpressure Mitigating System Setpoints and RCS Heatup and Cooldown Limit Curves.
The analytical methods used to determine the RCS pressure and temperature limits and Cold Overpressure Mitigation System setpoints shall be those previously reviewed and approved by the NRC, specifically those described in the following documents:
: 2. The PTLR will contain the complete identification for each of the TS reference Topical Reports used to prepare the PTLR (i.e., report number, title, revision, date, and any supplements).
: 1.
: d. The PTLR shall be provided to the NRC upon issuance for each reactor vessel fluence period and for any revision or supplement thereto.
WCAP-14040-A, Rev. 4 Methodology Used to Develop Cold Overpressure Mitigating System Setpoints and RCS Heatup and Cooldown Limit Curves.
(continued)
: 2.
Watts Bar-Unit 2                              5.0-34 (developmental)                                                                                B
The PTLR will contain the complete identification for each of the TS reference Topical Reports used to prepare the PTLR (i.e., report number, title, revision, date, and any supplements).
: d.
The PTLR shall be provided to the NRC upon issuance for each reactor vessel fluence period and for any revision or supplement thereto.  


Reporting Requirements 5.9 5.9 Reporting Requirements (continued) 5.9.7   EDG Failures Report If an individual emergency diesel generator (EDG) experiences four or more valid failures in the last 25 demands, these failures and any nonvalid failures experienced by that EDG in that time period shall be reported within 30 days.
Reporting Requirements 5.9 5.9 Reporting Requirements (continued)
Watts Bar-Unit 2 5.0-35 (developmental)
GI 5.9.7 EDG Failures Report If an individual emergency diesel generator (EDG) experiences four or more valid failures in the last 25 demands, these failures and any nonvalid failures experienced by that EDG in that time period shall be reported within 30 days.
Reports on EDG failures shall include the information recommended in Regulatory Guide 1.9, Revision 3, Regulatory Position C.4, or existing Regulatory Guide 1.108 reporting requirement.
Reports on EDG failures shall include the information recommended in Regulatory Guide 1.9, Revision 3, Regulatory Position C.4, or existing Regulatory Guide 1.108 reporting requirement.
5.9.8   PAMS Report When a Report is required by Condition B or F of LCO 3.3.3, Post Accident Monitoring (PAM) Instrumentation, a report shall be submitted within the following 14 days. The report shall outline the preplanned alternate method of monitoring, the cause of the inoperability, and the plans and schedule for restoring the instrumentation channels of the Function to OPERABLE status.
5.9.8 PAMS Report When a Report is required by Condition B or F of LCO 3.3.3, Post Accident Monitoring (PAM) Instrumentation, a report shall be submitted within the following 14 days. The report shall outline the preplanned alternate method of monitoring, the cause of the inoperability, and the plans and schedule for restoring the instrumentation channels of the Function to OPERABLE status.
5.9.9   Steam Generator Tube Inspection Report A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.7.2.12, Steam Generator (SG) Program. The report shall include:
5.9.9 Steam Generator Tube Inspection Report A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.7.2.12, Steam Generator (SG) Program. The report shall include:
: a. The scope of inspections performed on each SG,
: a.
: b. Active dDegradation mechanisms found,
The scope of inspections performed on each SG,
: c. Nondestructive examination techniques utilized for each degradation mechanism,
: b.
: d. Location, orientation (if linear), and measured sizes (if available) of service induced indications,
Active dDegradation mechanisms found,
: e. Number of tubes plugged or repaired during the inspection outage for each active degradation mechanism,
: c.
: f. The number and percentage of tubes plugged or repaired to date, and the effective plugging percentage in each steam generatorSG,
Nondestructive examination techniques utilized for each degradation mechanism,
: g. The results of condition monitoring, including the results of tube pulls and in-situ testing., and h.g. Repair method utilized and the number of tubes repaired by each repair method.
: d.
Watts Bar-Unit 2                                5.0-35 (developmental)                                                                                    GI
Location, orientation (if linear), and measured sizes (if available) of service induced indications,
: e.
Number of tubes plugged or repaired during the inspection outage for each active degradation mechanism,
: f.
The number and percentage of tubes plugged or repaired to date, and the effective plugging percentage in each steam generatorSG,
: g.
The results of condition monitoring, including the results of tube pulls and in-situ testing., and h.g. Repair method utilized and the number of tubes repaired by each repair method.  


Record Retention 5.10 5.0 ADMINISTRATIVE CONTROLS 5.10 Record Retention (removed from Technical Specifications)
Record Retention 5.10 Watts Bar-Unit 2 5.0-36 (developmental)
Watts Bar-Unit 2                    5.0-36 (developmental)                                                              A
A 5.0 ADMINISTRATIVE CONTROLS 5.10 Record Retention (removed from Technical Specifications)  


High Radiation Area 5.11 5.0 ADMINISTRATIVE CONTROLS 5.11 High Radiation Area As provided in paragraph 20.1601(c) of 10 CFR Part 20, the following controls shall be applied to high radiation areas in place of the controls required by paragraph 20.1601(a) and (b) of 10 CFR Part 20:
High Radiation Area 5.11 (continued)
5.11.1   High Radiation Areas with Dose Rates Not Exceeding 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation
Watts Bar-Unit 2 5.0-37 (developmental)
: a. Each entryway to such an area shall be barricaded and conspicuously posted as a high radiation area. Such barricades may be opened as necessary to permit entry or exit of personnel or equipment.
A 5.0 ADMINISTRATIVE CONTROLS 5.11 High Radiation Area As provided in paragraph 20.1601(c) of 10 CFR Part 20, the following controls shall be applied to high radiation areas in place of the controls required by paragraph 20.1601(a) and (b) of 10 CFR Part 20:
: b. Access to, and activities in, each such area shall be controlled by means of Radiation Work Permit (RWP) or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.
5.11.1 High Radiation Areas with Dose Rates Not Exceeding 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation
: c. Individuals qualified in radiation protection procedures and personnel continuously escorted by such individuals may be exempted from the requirement for an RWP or equivalent while performing their assigned duties provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.
: a.
: d. Each individual entering such an area shall possess:
Each entryway to such an area shall be barricaded and conspicuously posted as a high radiation area. Such barricades may be opened as necessary to permit entry or exit of personnel or equipment.
: b.
Access to, and activities in, each such area shall be controlled by means of Radiation Work Permit (RWP) or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.
: c.
Individuals qualified in radiation protection procedures and personnel continuously escorted by such individuals may be exempted from the requirement for an RWP or equivalent while performing their assigned duties provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.
: d.
Each individual entering such an area shall possess:
: 1. A radiation monitoring device that continuously displays radiation dose rates in the area; or
: 1. A radiation monitoring device that continuously displays radiation dose rates in the area; or
: 2. A radiation monitoring device that continuously integrates the radiation dose rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or
: 2. A radiation monitoring device that continuously integrates the radiation dose rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or
: 3. A radiation monitoring device that continuously transmits dose rate and cumulative dose information to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area, or (continued)
: 3.
Watts Bar-Unit 2                              5.0-37 (developmental)                                                                                  A
A radiation monitoring device that continuously transmits dose rate and cumulative dose information to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area, or  


High Radiation Area 5.11 High Radiation Area 5.11.1   High Radiation Areas with Dose Rates Not Exceeding 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation (continued)
High Radiation Area 5.11 High Radiation Area (continued)
: 4. A self-reading dosimeter (e.g., pocket ionization chamber or electronic dosimeter) and, (i) Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii) Be under the surveillance as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with individuals in the area who are covered by such surveillance.
Watts Bar - Unit 2 5.0-38 (developmental)
: e. Except for individuals qualified in radiation protection procedures, or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them. These continuously escorted personnel will receive a pre-job briefing prior to entry into such areas. This dose rate determination, knowledge, and pre-job briefing does not require documentation prior to initial entry.
A 5.11.1 High Radiation Areas with Dose Rates Not Exceeding 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation (continued)
: 4. A self-reading dosimeter (e.g., pocket ionization chamber or electronic dosimeter) and, (i) Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii) Be under the surveillance as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with individuals in the area who are covered by such surveillance.
: e.
Except for individuals qualified in radiation protection procedures, or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them. These continuously escorted personnel will receive a pre-job briefing prior to entry into such areas. This dose rate determination, knowledge, and pre-job briefing does not require documentation prior to initial entry.  
 
High Radiation Area 5.11 High Radiation Area (continued)
(continued)
(continued)
Watts Bar - Unit 2                             5.0-38 (developmental)                                                                                     A
Watts Bar - Unit 2 5.0-39 (developmental)
 
A 5.11.2 High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation, but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation
High Radiation Area 5.11 High Radiation Area (continued) 5.11.2   High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation, but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation
: a.
: a. Each entryway to such an area shall be conspicuously posted as a high radiation area and shall be provided with a locked or, continuously guarded door or gate that prevents unauthorized entry, and, in addition:
Each entryway to such an area shall be conspicuously posted as a high radiation area and shall be provided with a locked or, continuously guarded door or gate that prevents unauthorized entry, and, in addition:
: 1. All such door and gate keys shall be maintained under the administrative control of the Shift Manager, radiation protection manager, or his or her designee.
: 1. All such door and gate keys shall be maintained under the administrative control of the Shift Manager, radiation protection manager, or his or her designee.
: 2. Doors and gates shall remain locked except during periods of personnel or equipment entry or exit.
: 2. Doors and gates shall remain locked except during periods of personnel or equipment entry or exit.
: b. Access to, and activities in, each such area shall be controlled by means of an RWP or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.
: b.
: c. Individuals qualified in radiation protection procedures may be exempted from the requirement for an RWP or equivalent while performing radiation surveys in such areas provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.
Access to, and activities in, each such area shall be controlled by means of an RWP or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.
: d. Each individual entering such an area shall possess:
: c.
Individuals qualified in radiation protection procedures may be exempted from the requirement for an RWP or equivalent while performing radiation surveys in such areas provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.
: d.
Each individual entering such an area shall possess:
: 1. A radiation monitoring device that continuously integrates the radiation rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or
: 1. A radiation monitoring device that continuously integrates the radiation rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or
: 2. A radiation monitoring device that continuously transmits dose rate and cumulative dose information to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area with the means to communicate with and control every individual in the area, or (continued)
: 2.
Watts Bar - Unit 2                            5.0-39 (developmental)                                                                                  A
A radiation monitoring device that continuously transmits dose rate and cumulative dose information to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area with the means to communicate with and control every individual in the area, or  


High Radiation Area 5.11 High Radiation Area 5.11.2   High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation, but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation (continued)
High Radiation Area 5.11 High Radiation Area Watts Bar - Unit 2 5.0-40 (developmental)
: 3. A self-reading dosimeter (e.g., pocket ionization chamber or electronic dosimeter) and, (i)   Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii) Be under the surveillance as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with and control every individual in the area.
B 5.11.2 High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation, but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation (continued)
: 3. A self-reading dosimeter (e.g., pocket ionization chamber or electronic dosimeter) and, (i) Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii) Be under the surveillance as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with and control every individual in the area.
: 4. In those cases where options (2) and (3), above, are impractical or determined to be inconsistent with the "As Low As is Reasonably Achievable" principle, a radiation monitoring device that continuously displays radiation dose rates in the area.
: 4. In those cases where options (2) and (3), above, are impractical or determined to be inconsistent with the "As Low As is Reasonably Achievable" principle, a radiation monitoring device that continuously displays radiation dose rates in the area.
: e. Except for individuals qualified in radiation protection procedures, or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them. These continuously escorted personnel will receive a pre-job briefing prior to entry into such areas. This dose rate determination, knowledge, and pre-job briefing does not require documentation prior to initial entry.
: e.
: f. Such individual areas that are within a larger area where no enclosure exists for the purpose of locking and where no enclosure can reasonably be constructed around the individual area need not be controlled by a locked door or gate, nor continuously guarded, but shall be barricaded, conspicuously posted, and a clearly visible flashing light shall be activated at the area as a warning device.
Except for individuals qualified in radiation protection procedures, or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them. These continuously escorted personnel will receive a pre-job briefing prior to entry into such areas. This dose rate determination, knowledge, and pre-job briefing does not require documentation prior to initial entry.
Watts Bar - Unit 2                              5.0-40 (developmental)                                                                                      B}}
: f.
Such individual areas that are within a larger area where no enclosure exists for the purpose of locking and where no enclosure can reasonably be constructed around the individual area need not be controlled by a locked door or gate, nor continuously guarded, but shall be barricaded, conspicuously posted, and a clearly visible flashing light shall be activated at the area as a warning device.}}

Latest revision as of 20:19, 10 January 2025

Attachment 1 - TS Developmental Revision I Changes (Mark-Up) for WBN Unit 2
ML14170A045
Person / Time
Site: Watts Bar Tennessee Valley Authority icon.png
Issue date: 06/16/2014
From:
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation
Shared Package
ML14170A054 List:
References
Download: ML14170A045 (194)


Text

Definitions 1.1 (continued)

Watts Bar - Unit 2 1.1-1 (developmental)

A 1.0 USE AND APPLICATION 1.1 Definitions


NOTE----------------------------------------------------------

The defined terms of this section appear in capitalized type and are applicable throughout these Technical Specifications and Bases.

Term Definition ACTIONS ACTIONS shall be that part of a Specification that prescribes Required Actions to be taken under designated Conditions within specified Completion Times.

ACTUATION LOGIC TEST An ACTUATION LOGIC TEST shall be the application of various simulated or actual input combinations in conjunction with each possible interlock logic state and the verification of the required logic output. The ACTUATION LOGIC TEST, as a minimum, shall include a continuity check of output devices.

AXIAL FLUX DIFFERENCE (AFD)

AFD shall be the difference in normalized flux signals between the top and bottom halves of a two section excore neutron detector.

CHANNEL CALIBRATION A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel so that it responds within the required range and accuracy to known input. The CHANNEL CALIBRATION shall encompass the entire channel, including the required sensor, alarm, interlock, display, and trip functions. Calibration of instrument channels with resistance temperature detector (RTD) or thermocouple sensors may consist of an inplace qualitative assessment of sensor behavior and normal calibration of the remaining adjustable devices in the channel. Whenever a sensing element is replaced, the next required CHANNEL CALIBRATION shall include an inplace cross calibration that compares the other sensing elements with the recently installed sensing element.

The CHANNEL CALIBRATION may be performed by means of any series of sequential, overlapping calibrations or total channel steps so that the entire channel is calibrated.

Definitions 1.1 1.1 Definitions (continued)

(continued)

Watts Bar - Unit 2 1.1-2 (developmental)

AI CHANNEL CHECK A CHANNEL CHECK shall be the qualitative assessment, by observation, of channel behavior during operation. This determination shall include, where possible, comparison of the channel indication and status to other indications or status derived from independent instrument channels measuring the same parameter.

CHANNEL OPERATIONAL TEST (COT)

A COT shall be the injection of a simulated or actual signal into the channel as close to the sensor as practicable to verify the OPERABILITY of required alarm, interlock, display, and trip functions. The COT shall include adjustments, as necessary, of the required alarm, interlock, and trip setpoints so that the setpoints are within the required range and accuracy.

CORE ALTERATION CORE ALTERATION shall be the movement of any fuel, sources, or other reactivity control components, within the reactor vessel with the vessel head removed and fuel in the vessel. Suspension of CORE ALTERATIONS shall not preclude completion of movement of a component to a safe position.

CORE OPERATING LIMITS REPORT (COLR)

The COLR is the unit specific document that provides cycle specific parameter limits for the initial and current reload cycle. These cycle specific parameter limits shall be determined for the initial and each reload cycle in accordance with Specification 5.9.5. Plant operation within these limits is addressed in individual Specifications.

DOSE EQUIVALENT I-131 DOSE EQUIVALENT I-131 shall be that concentration of I-131 (microcuries/gram) that alone would produce the same thyroid dose as the quantity and isotopic mixture of I-131, I-132, I-133, I-134, and I-135 actually present. The thyroid dose conversion factors used for this calculation shall be those listed in Table E-7 of Regulatory Guide 1.109, Rev. 1, NRC, 1977.

Definitions 1.1 1.1 Definitions (continued)

(continued)

Watts Bar - Unit 2 1.1-3 (developmental)

AI

- AVERAGE DISINTEGRATION ENERGY shall be the average (weighted in proportion to the concentration of each radionuclide in the reactor coolant at the time of sampling) of the sum of the average beta and gamma energies per disintegration (in MeV) for isotopes, other than iodines, with half liveshalf-lives > 15 minutes, making up at least 95% of the total non-iodine activity in the coolant.

ENGINEERED SAFETY FEATURE (ESF) RESPONSE TIME The ESF RESPONSE TIME shall be that time interval from when the monitored parameter exceeds its ESF actuation setpoint at the channel sensor until the ESF equipment is capable of performing its safety function (i.e., the valves travel to their required positions, pump discharge pressures reach their required values, etc.). Times shall include diesel generator starting and sequence loading delays, where applicable. The response time may be measured by means of any series of sequential, overlapping, or total steps so that the entire response time is measured. In lieu of measurement, response time may be verified for selected components provided that the components and the methodology for verification have been previously reviewed and approved by the NRC.

La The maximum allowable primary containment leakage rate, La, shall be.25% of primary containment air weight per day at the calculated peak containment pressure (Pa).

Definitions 1.1 1.1 Definitions (continued)

(continued)

Watts Bar - Unit 2 1.1-4 (developmental)

AI LEAKAGE LEAKAGE shall be:

a.

Identified LEAKAGE

1. LEAKAGE, such as that from pump seals or valve packing (except reactor coolant pump (RCP) seal water injection or leakoff), that is captured and conducted to collection systems or a sump or collecting tank;
2. LEAKAGE into the containment atmosphere from sources that are both specifically located and known either not to interfere with the operation of leakage detection systems or not to be pressure boundary LEAKAGE; or
3. Reactor Coolant System (RCS) LEAKAGE through a steam generator to the Secondary System (primary-to-secondary LEAKAGE);
b.

Unidentified LEAKAGE All LEAKAGE (except RCP seal water injection or leakoff) that is not identified LEAKAGE;

c.

Pressure Boundary LEAKAGE LEAKAGE (except primary-to-secondary LEAKAGE) through a nonisolable fault in an RCS component body, pipe wall, or vessel wall.

MASTER RELAY TEST A MASTER RELAY TEST shall consist of energizing each master relay and verifying the OPERABILITY of each relay.

The MASTER RELAY TEST shall include a continuity check of each associated slave relay.

MODE A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, average reactor coolant temperature, and reactor vessel head closure bolt tensioning specified in Table 1.1-1 with fuel in the reactor vessel.

Definitions 1.1 1.1 Definitions (continued)

(continued)

Watts Bar - Unit 2 1.1-5 (developmental)

BI OPERABLE-OPERABILITY A system, subsystem, train, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified safety function(s) and when all necessary attendant instrumentation, controls, normal or emergency electrical power, cooling and seal water, lubrication, and other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its specified safety function(s) are also capable of performing their related support function(s).

PCO A pressure control operator (PCO) is a devise, such as a damper that is used to control pressure in an air handling system.

PDMS The Power Distribution Monitoring System (PDMS) is a real-time three dimensional core monitoring system. The system utilizes existing core instrumentation data and an on-line neutronics code to provide surveillance of core thermal limits.

PHYSICS TESTS PHYSICS TESTS shall be those tests performed to measure the fundamental nuclear characteristics of the reactor core and related instrumentation. These tests are:

a.

Described in Chapter 14, Initial Test Program of the FSAR;

b.

Authorized under the provisions of 10 CFR 50.59; or

c.

Otherwise approved by the Nuclear Regulatory Commission.

PRESSURE AND TEMPERATURE LIMITS REPORT (PTLR)

The PTLR is the unit specific document that provides the RCS pressure and temperature limits for heatup, cooldown, low temperature operation, criticality, and hydrostatic testing as well as heatup and cooldown rates for the current reactor vessel fluence period. These pressure and temperature limits shall be determined for each fluence period in accordance with Specification 5.9.6. Plant operation within these operating limits is addressed in LCO 3.4.3, "RCS Pressure and Temperature (P/T) Limits," and LCO 3.4.12, "Cold Overpressure Mitigation System (COMS)."

Definitions 1.1 1.1 Definitions (continued)

(continued)

Watts Bar - Unit 2 1.1-6 (developmental)

A QUADRANT POWER TILT RATIO (QPTR)

QPTR shall be the ratio of the maximum upper excore detector calibrated output to the average of the upper excore detector calibrated outputs, or the ratio of the maximum lower excore detector calibrated output to the average of the lower excore detector calibrated outputs, whichever is greater.

RATED THERMAL POWER (RTP)

RTP shall be a total reactor core heat transfer rate to the reactor coolant of 3411 MWt.

REACTOR TRIP SYSTEM (RTS) RESPONSE TIME The RTS RESPONSE TIME shall be that time interval from when the monitored parameter exceeds its RTS trip setpoint at the channel sensor until loss of stationary gripper coil voltage. The response time may be measured by means of any series of sequential, overlapping, or total steps so that the entire response time is measured. In lieu of measurement, response time may be verified for selected components provided that the components and the methodology for verification have been previously reviewed and approved by the NRC.

SHUTDOWN MARGIN (SDM)

SDM shall be the instantaneous amount of reactivity by which the reactor is subcritical or would be subcritical from its present condition assuming:

a.

All rod cluster control assemblies (RCCAs) are fully inserted except for the single RCCA of highest reactivity worth, which is assumed to be fully withdrawn. With any RCCA not capable of being fully inserted, the reactivity worth of the RCCA must be accounted for in the determination of SDM; and

b.

In MODES 1 and 2, the fuel and moderator temperatures are changed to the nominal zero power design level.

SLAVE RELAY TEST A SLAVE RELAY TEST shall consist of energizing each slave relay and verifying the OPERABILITY of each slave relay.

The SLAVE RELAY TEST shall include, as a minimum, a continuity check of associated testable actuation devices.

Definitions 1.1 1.1 Definitions (continued)

Watts Bar - Unit 2 1.1-7 (developmental)

A STAGGERED TEST BASIS A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems, channels, or other designated components during the interval specified by the Surveillance Frequency, so that all systems, subsystems, channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems, channels, or other designated components in the associated function.

THERMAL POWER THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.

TRIP ACTUATING DEVICE OPERATIONAL TEST (TADOT)

A TADOT shall consist of operating the trip actuating device and verifying the OPERABILITY of required alarm, interlock, display, and trip functions. The TADOT shall include adjustment, as necessary, of the trip actuating device so that it actuates at the required setpoint within the required accuracy.

Definitions 1.1 Watts Bar - Unit 2 1.1-8 (developmental)

A Table 1.1-1 (page 1 of 1)

MODES MODE TITLE REACTIVITY CONDITION (keff)

% RATED THERMAL POWER (a)

AVERAGE REACTOR COOLANT TEMPERATURE

(°F) 1 Power Operation 0.99

> 5 NA 2

Startup 0.99

< 5 NA 3

Hot Standby

< 0.99 NA 350 4

Hot Shutdown (b)

< 0.99 NA 350 > Tavg > 200 5

Cold Shutdown (b)

< 0.99 NA

< 200 6

Refueling (c)

NA NA NA (a)

Excluding decay heat.

(b)

All reactor vessel head closure bolts fully tensioned.

(c)

One or more reactor vessel head closure bolts less than fully tensioned.

SDM - Tavg > 200°F 3.1.1 Watts Bar - Unit 2 3.1-1 (developmental)

AI 3.1 REACTIVITY CONTROL SYSTEMS 3.1.1 SHUTDOWN MARGIN (SDM) - Tavg > 200°F LCO 3.1.1 SDM shall be > 1.6% k/k.

APPLICABILITY:

MODE 2 with keff < 1.0, MODES 3 and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. SDM not within limit.

A.1 Initiate boration to restore SDM to within limit.

15 minutes SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.1.1 Verify SDM is > 1.6% k/k.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

SDM - Tavg < 200°F 3.1.2 Watts Bar - Unit 2 3.1-2 (developmental)

AI 3.1 REACTIVITY CONTROL SYSTEMS 3.1.2 SHUTDOWN MARGIN (SDM) - Tavg < 200°F LCO 3.1.2 The SDM shall be 1.0% k/k.

APPLICABILITY:

MODE 5.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. SDM not within limit.

A.1 Initiate boration to restore SDM to within limit.

15 minutes SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.2.1 Verify SDM is 1.0% k/k.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

MTC 3.1.4 Watts Bar - Unit 2 3.1-5 (developmental)

A 3.1 REACTIVITY CONTROL SYSTEMS 3.1.4 Moderator Temperature Coefficient (MTC)

LCO 3.1.4 The MTC shall be maintained within the limits specified in the COLR. The maximum upper limit shall be 0 k/k°F at hot zero power.

APPLICABILITY:

MODE 1 and MODE 2 with keff 1.0 for the upper MTC limit, MODES 1, 2, and 3 for the lower MTC limit.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. MTC not within upper limit.

A.1 Establish administrative withdrawal limits for control banks to maintain MTC within limit.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> B. Required Action and associated Completion Time of Condition A not met.

B.1 Be in MODE 2 with keff < 1.0.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> C. MTC not within lower limit.

C.1 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />

MTC 3.1.4 Watts Bar - Unit 2 3.1-6 (developmental)

AI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.4.1 Verify MTC is within upper limit Once prior to entering MODE 1 after initial fuel loading and each refueling SR 3.1.4.2 Verify MTC is within 300 ppm Surveillance limit specified in the COLR.


NOTE---------

Not required to be performed until 7 effective full power days (EFPD) after reaching the equivalent of an equilibrium RTP all rods out (ARO) boron concentration of 300 ppm Once each cycle SR 3.1.4.3


NOTES----------------------------

1. If the MTC is more negative than the 300 ppm Surveillance limit (not LCO limit) specified in the COLR, SR 3.1.4.3 shall be repeated once per 14 EFPD during the remainder of the fuel cycle.
2. SR 3.1.4.3 need not be repeated if the MTC measured at the equivalent of equilibrium RTP-ARO boron concentration of < 60 ppm is less negative than the 60 ppm Surveillance limit specified in the COLR.

NOTE---------

Not required to be performed until 7 EFPD after reaching the equivalent of an equilibrium RTP-ARO boron concentration of 300 ppm Verify MTC is within lower limit.

Once each cycle

Rod Group Alignment Limits 3.1.5 Watts Bar - Unit 2 3.1-7 (developmental)

A 3.1 REACTIVITY CONTROL SYSTEMS 3.1.5 Rod Group Alignment Limits LCO 3.1.5 All shutdown and control rods shall be OPERABLE, with all individual indicated rod positions within 12 steps of their group step counter demand position.

APPLICABILITY:

MODES 1 and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more rod(s) untrippable.

A.1.1 Verify SDM is 1.6% k/k.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OR A.1.2 Initiate boration to restore SDM to within limit.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND A.2 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> B. One rod not within alignment limits.

B.1 Restore rod to within alignment limits.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OR B.2.1.1 Verify SDM is 1.6% k/k.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OR B.2.1.2 Initiate boration to restore SDM to within limit.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND (continued)

Rod Group Alignment Limits 3.1.5 Watts Bar - Unit 2 3.1-8 (developmental)

AI ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. (continued)

B.2.2 Reduce THERMAL POWER to < 75% RTP.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> AND B.2.3 Verify SDM is 1.6% k/k.

Once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND B.2.4 Perform SR 3.2.1.1.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND B.2.5 Perform SR 3.2.2.1.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND B.2.6 Re-evaluate safety analyses and confirm results remain valid for duration of operation under these conditions 5 days C. Required Action and associated Completion Time of Condition B not met.

C.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> D. More than one rod not within alignment limit.

D.1.1 Verify SDM is 1.6% k/k.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OR D.1.2 Initiate boration to restore required SDM to within limit.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND D.2 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

Rod Group Alignment Limits 3.1.5 Watts Bar - Unit 2 3.1-9 (developmental)

AI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.1.5.1 Verify individual rod positions within alignment limit.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND Once within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and every 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> thereafter when the rod position deviation monitor is inoperable SR 3.1.5.2 Verify rod freedom of movement (tripability) by moving each rod not fully inserted in the core 10 steps in either direction.

92 days SR 3.1.5.3 Verify rod drop time of each rod, from the fully withdrawn position, is < 2.7 seconds from the beginning of decay of stationary gripper coil voltage to dashpot entry, with:

a.

Tavg 551°F; and

b.

All reactor coolant pumps operating.

Prior to reactor criticality after initial fuel loading and each removal of the reactor head

FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-1 (developmental)

AI 3.2 POWER DISTRIBUTION LIMITS 3.2.1 Heat Flux Hot Channel Factor (FQ (Z))

LCO 3.2.1 FQ (Z), as approximated by FQ C (Z) and FQ W (Z), shall be within the limits specified in the COLR.

APPLICABILITY:

MODE 1.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. FQ C (Z) not within limit.

A.1 Reduce THERMAL POWER 1% RTP for each 1% FQ C (Z) exceeds limit.

15 minutes AND A.2 Reduce Power Range Neutron FluxHigh trip setpoints > 1% for each 1% FQ C (Z) exceeds limit.

8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> AND A.3 Reduce Overpower T trip setpoints 1% for each 1% FQ C (Z) exceeds limit.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND A.4 Perform SR 3.2.1.1.

Prior to increasing THERMAL POWER above the limit of Required Action A.1 (continued)

FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-2 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. FQ W (Z) not within limits.

B.1 Reduce AFD limits 1%

for each 1% FQ W (Z) exceeds limit.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> C. Required Action and associated Completion Time not met.

C.1 Be in MODE 2.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-3 (developmental)

A SURVEILLANCE REQUIREMENTS


NOTE----------------------------------------------------------

During power escalation at the beginning of each cycle, THERMAL POWER may be increased until an equilibrium power level has been achieved, at which a power distribution map is obtained.

SURVEILLANCE FREQUENCY SR 3.2.1.1 Verify FQ C (Z) is within limit.

Once after initial fuel loading and each refueling prior to THERMAL POWER exceeding 75% RTP AND Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after achieving equilibrium conditions after exceeding, by 10% RTP, the THERMAL POWER at which FQ C (Z) was last verified AND 31 EFPD thereafter (continued)

FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-4 (developmental)

B SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.2.1.2


NOTE------------------------------

If FQ W (Z) is within limits and measurements indicate maximum over z

()

()

has increased since the previous evaluation of FQ C

(Z):

a.

Increase FQ W (Z) by the appropriate factor specified in the COLR and reverify FQ W (Z) is within limits; or

b.

Repeat SR 3.2.1.2 once per 7 EFPD using the Power Distribution Monitoring System (PDMS) until two successive incore power distribution measurements indicate maximum over z

()

()

has not increased.

Verify FQ W (Z) is within limit.

Once after initial fuel loading and each refueling prior to THERMAL POWER exceeding 75% RTP AND (continued)

FQ (Z) 3.2.1 Watts Bar - Unit 2 3.2-5 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.2.1.2 (continued)

Once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after achieving equilibrium conditions after exceeding, by 10% RTP, the THERMAL POWER at which FQ W (Z) was last verified AND 31 EFPD thereafter

AFD 3.2.3 Watts Bar - Unit 2 3.2-8 (developmental)

AI 3.2 POWER DISTRIBUTION LIMITS 3.2.3 AXIAL FLUX DIFFERENCE (AFD)

LCO 3.2.3 The AFD in % flux difference units shall be maintained within the limits specified in the COLR.


NOTE--------------------------------------------

The AFD shall be considered outside limits when two or more OPERABLE excore channels indicate AFD to be outside limits.

APPLICABILITY:

MODE 1 with THERMAL POWER > 50% RTP.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. AFD not within limits.

A.1 Reduce THERMAL POWER to < 50% RTP.

30 minutes SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.2.3.1 Verify AFD within limits for each OPERABLE excore channel.

7 days AND Once within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and every 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> thereafter with the AFD monitor alarm inoperable

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-1 (developmental)

A 3.3 INSTRUMENTATION 3.3.1 Reactor Trip System (RTS) Instrumentation LCO 3.3.1 The RTS instrumentation for each Function in Table 3.3.1-1 shall be OPERABLE.

APPLICABILITY:

According to Table 3.3.1-1.

ACTIONS


NOTE----------------------------------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more Functions with one or more required channels inoperable.

A.1 Enter the Condition referenced in Table 3.3.1-1 for the channel(s).

Immediately B. One Manual Reactor Trip channel inoperable.

B.1 Restore channel to OPERABLE status.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> OR B.2.1 Be in MODE 3.

54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> AND B.2.2 Open reactor trip breakers (RTBs).

55 hours6.365741e-4 days <br />0.0153 hours <br />9.093915e-5 weeks <br />2.09275e-5 months <br /> (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-2 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. One channel or train inoperable.

C.1 Restore channel or train to OPERABLE status.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> OR C.2 Open RTBs.

49 hours5.671296e-4 days <br />0.0136 hours <br />8.101852e-5 weeks <br />1.86445e-5 months <br /> D. One Power Range Neutron Flux-High channel inoperable.


NOTE-------------------

The inoperable channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing and setpoint adjustment of other channels.

D.1.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND D.1.2 Reduce THERMAL POWER to 75% RTP.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> OR D.2.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND


NOTE-------------------

Only required to be performed when the Power Range Neutron Flux input to QPTR is inoperable.

D.2.2 Perform SR 3.2.4.2.

Once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> OR D.3 Be in MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-3 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E. One channel inoperable.


NOTE-------------------

The inoperable channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing of other channels.

E.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR E.2 Be in MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> F. THERMAL POWER > P-6 and < P-10, one Intermediate Range Neutron Flux channel inoperable.

F.1 Reduce THERMAL POWER to < P-6.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> OR F.2 Increase THERMAL POWER to > P-10.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> G. THERMAL POWER > P-6 and < P-10, two Intermediate Range Neutron Flux channels inoperable.

G.1 Suspend operations involving positive reactivity additions.

Immediately AND G.2 Reduce THERMAL POWER to < P-6.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> H. THERMAL POWER < P-6, one or two Intermediate Range Neutron Flux channels inoperable.

H.1 Restore channel(s) to OPERABLE status.

Prior to increasing THERMAL POWER to > P-6 I. One Source Range Neutron Flux channel inoperable.

I.1 Suspend operations involving positive reactivity additions.

Immediately (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-4 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME J. Two Source Range Neutron Flux channels inoperable.

J.1 Open RTBs.

Immediately K. One Source Range Neutron Flux channel inoperable.

K.1 Restore channel to OPERABLE status.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> OR K.2 Open RTBs.

49 hours5.671296e-4 days <br />0.0136 hours <br />8.101852e-5 weeks <br />1.86445e-5 months <br /> L. Required Source Range Neutron Flux channel inoperable.

L.1 Suspend operations involving positive reactivity additions.

Immediately AND L.2 Close unborated water source isolation valves.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND L.3 Perform SR 3.1.1.1.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND Once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-5 (developmental)

F ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME M. One channel inoperable.


NOTE-------------------

The inoperable channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing of other channels.

M.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR M.2 Reduce THERMAL POWER to < P-7.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> N. One Reactor Coolant Flow - Low channel inoperable.


NOTE-------------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

N.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR N.2 Reduce THERMAL POWER to < P-7.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-6 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME O. One Low Fluid Oil Pressure Turbine Trip channel inoperable.


NOTE-------------------

The inoperable channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing of other channels.

O.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR O.2 Reduce THERMAL POWER to < P-9.

76 hours8.796296e-4 days <br />0.0211 hours <br />1.256614e-4 weeks <br />2.8918e-5 months <br /> P. One train inoperable.


NOTE-------------------

One train may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing provided the other train is OPERABLE.

P.1 Restore train to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> OR P.2 Be in MODE 3.

30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-7 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME Q. One RTB train inoperable.


NOTE-----------------

One train may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing, provided the other train is OPERABLE.

Q.1 Restore train to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> OR Q.2 Be in MODE 3.

30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> R. One channel inoperable.

R.1 Verify interlock is in required state for existing unit conditions.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OR R.2 Be in MODE 3.

7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br /> S. One channel inoperable.

S.1 Verify interlock is in required state for existing unit conditions.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OR S.2 Be in MODE 2.

7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br /> (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-8 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME T. One trip mechanism inoperable for one RTB.

T.1 Restore inoperable trip mechanism to OPERABLE status.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> OR T.2.1 Be in MODE 3.

54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> AND T.2.2 Open RTB.

55 hours6.365741e-4 days <br />0.0153 hours <br />9.093915e-5 weeks <br />2.09275e-5 months <br /> U. One Steam Generator Water Level - Low-Low channel inoperable.


NOTE-------------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

U.1.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND U.1.2 For the affected protection set, set the Trip Time Delay (Ts) to match the Trip Time Delay (Tm).

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR U.2 Be in MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-9 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME V. One Vessel T channel inoperable.


NOTE-------------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

V.1 Set the Trip Time Delay threshold power level for (Ts) and (Tm) to 0% power.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR V.2 Be in MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> W. One channel inoperable.


NOTE-------------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

W.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR W.2 Be in MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> X. One channel inoperable.


NOTE-------------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

X.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR X.2 Reduce THERMAL POWER to < P-7.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-10 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME Y. One, two or three Turbine Stop Valve Closure channels inoperable.

Y.1 Place channel(s) in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR Y.2 Reduce THERMAL POWER to < P-9.

76 hours8.796296e-4 days <br />0.0211 hours <br />1.256614e-4 weeks <br />2.8918e-5 months <br /> Z. Two RTS Trains inoperable.

Z.1 Enter LCO 3.0.3.

Immediately SURVEILLANCE REQUIREMENTS


NOTE----------------------------------------------------------

Refer to Table 3.3.1-1 to determine which SRs apply for each RTS Function.

SURVEILLANCE FREQUENCY SR 3.3.1.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.1.2


NOTES----------------------------

1. Adjust NIS channel if absolute difference is > 2%.
2. Required to be performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after THERMAL POWER is 15% RTP.

Compare results of calorimetric heat balance calculation to Nuclear Instrumentation System (NIS) channel output.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-11 (developmental)

G SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.3


NOTES----------------------------

1. Adjust NIS channel if absolute difference is 3%.
2. Required to be performed within 96 hours0.00111 days <br />0.0267 hours <br />1.587302e-4 weeks <br />3.6528e-5 months <br /> after THERMAL POWER is 25% RTP.

Compare results of the PDMS measurements to NIS AFD.

31 effective full power days (EFPD)

SR 3.3.1.4


NOTE------------------------------

This Surveillance must be performed on the reactor trip bypass breaker prior to placing the bypass breaker in service.

Perform TADOT.

62 days on a STAGGERED TEST BASIS SR 3.3.1.5 Perform ACTUATION LOGIC TEST.

92 days on a STAGGERED TEST BASIS SR 3.3.1.6


NOTE------------------------------

Required to be performed within 6 days after THERMAL POWER is 50% RTP.

Calibrate excore channels to agree with the PDMS measurements.

92 EFPD (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-12 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.7


NOTE------------------------------

For Functions 2 and 3 (Power Range Instrumentation), this Surveillance shall include verification that interlock P-10 is in the required state for existing unit conditions.

Perform COT.

184 days SR 3.3.1.8


NOTES----------------------------

1.

Not required to be performed for Source Range instrumentation prior to entering MODE 3 from MODE 2 until 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after entry into MODE 3.

2.

This Surveillance shall include verification that interlock P-6 is in the required state for existing unit conditions.


NOTE---------

Only required when not performed within previous 31 days Perform COT.

Prior to reactor startup AND Four hours after reducing power below P-10 for intermediate range instrumentation AND Four hours after reducing power below P-6 for source range instrumentation AND Every 31 days thereafter (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-13 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.9


NOTE------------------------------

Verification of setpoint is not required.

Perform TADOT.

92 days SR 3.3.1.10


NOTE------------------------------

This Surveillance shall include verification that the time constants are adjusted to the prescribed values.

Perform CHANNEL CALIBRATION.

18 months SR 3.3.1.11


NOTE------------------------------

Neutron detectors are excluded from CHANNEL CALIBRATION.

Perform CHANNEL CALIBRATION.

18 months SR 3.3.1.12 Perform COT.

18 months SR 3.3.1.13


NOTE------------------------------

Verification of setpoint is not required.

Perform TADOT.

18 months (continued)

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-14 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.14


NOTE------------------------------

Verification of setpoint is not required.

Perform TADOT.

Prior to exceeding the P-9 interlock whenever the unit has been in Mode MODE 3, if not performed within the previous 31 days.

SR 3.3.1.15


NOTE------------------------------

Neutron detectors are excluded from response time testing.

Verify RTS RESPONSE TIME is within limits.

18 months on a STAGGERED TEST BASIS

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-15 (developmental)

F Table 3.3.1-1 (page 1 of 9)

Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

1.

Manual Reactor Trip 1, 2 2

B SR 3.3.1.13 NA NA 3 (a), 4 (a), 5 (a) 2 C

SR 3.3.1.13 NA NA

2.

Power Range Neutron Flux

a.

High 1, 2 4

D SR 3.3.1.1 111.4% RTP 109% RTP SR 3.3.1.2 SR 3.3.1.7 (b)(c)

SR 3.3.1.11 (b)(c)

SR 3.3.1.15

b.

Low 1 (d), 2 4

E SR 3.3.1.1 27.4% RTP 25% RTP SR 3.3.1.7 (b)(c)

SR 3.3.1.11 (b)(c)

SR 3.3.1.15

3.

Power Range Neutron Flux Rate

a.

High Positive Rate 1, 2 4

E SR 3.3.1.7 (b)(c) 6.3% RTP with time constant 2 sec 5% RTP with time constant 2 sec SR 3.3.1.11 (b)(c)

b.

High Negative Rate - DELETED

4.

Intermediate Range Neutron Flux 1 (d), 2 (e) 2 F, G SR 3.3.1.1 40% RTP 25% RTP SR 3.3.1.8 (b)(c)

SR 3.3.1.11 (b)(c) 2 (f) 2 H

SR 3.3.1.1 40% RTP 25% RTP SR 3.3.1.8 (b)(c)

SR 3.3.1.11 (b)(c)

(continued)

(a) With Reactor Trip Breakers (RTBs) closed and Rod Control System capable of rod withdrawal.

(b) If the as found channel setpoint is outside its predefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

(d) Below the P-10 (Power Range Neutron Flux) interlocks.

(e) Above the P-6 (Intermediate Range Neutron Flux) interlocks.

(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-16 (developmental)

G Table 3.3.1-1 (page 2 of 9)

Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

5.

Source Range Neutron Flux 2 (f) 2 I, J SR 3.3.1.1 1.33 E5 cps 1.0 E5 cps SR 3.3.1.8 (b)(c)

SR 3.3.1.11 (b)(c) 3 (a), 4 (a), 5 (a) 2 J, K SR 3.3.1.1 1.33 E5 cps 1.0 E5 cps SR 3.3.1.8 (b)(c)

SR 3.3.1.11 (b)(c)

SR 3.3.1.15 3 (g), 4 (g), 5 (g) 1 L

SR 3.3.1.1 N/A N/A SR 3.3.1.11 (b)(c)

6.

Overtemperature T 1, 2 4

W SR 3.3.1.1 Refer to Note 1 (Page 3.3-21)

Refer to Note 1 (Page 3.3-21)

SR 3.3.1.3 SR 3.3.1.6 SR 3.3.1.7 (b)(c)

SR 3.3.1.10 (b)(c)

SR 3.3.1.15

7.

Overpower T 1, 2 4

W SR 3.3.1.1 Refer to Note 2 (Page 3.3-22)

Refer to Note 2 (Page 3.3-22)

SR 3.3.1.7 (b)(c)

SR 3.3.1.10 (b)(c)

SR 3.3.1.15

8.

Pressurizer Pressure

a.

Low 1 (h) 4 X

SR 3.3.1.1 1964.8 psig 1970 psig SR 3.3.1.7 (b)(c)

SR 3.3.1.10 (b)(c)

SR 3.3.1.15

b.

High 1, 2 4

W SR 3.3.1.1 2390.2 psig 2385 psig SR 3.3.1.7 (b)(c)

SR 3.3.1.10 (b)(c)

SR 3.3.1.15 (continued)

(a) With Reactor Trip Breakers (RTBs) closed and Rod Control System capable of rod withdrawal.

(b) If the as found channel setpoint is outside its predefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.

(g) With the RTBs open. In this condition, source range Function does not provide reactor trip but does provide indication.

(h) Above the P-7 (Low Power Reactor Trips Block) interlock.

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-17 (developmental)

G Table 3.3.1-1 (page 3 of 9)

Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

9.

Pressurizer Water Level-High 1 (h) 3 X

SR 3.3.1.1 92.7% span 92% span SR 3.3.1.7 (b)(c)

SR 3.3.1.10 (b)(c)

10.

Reactor Coolant Flow -

Low 1 (h) 3 per loop N

SR 3.3.1.1 89.7% flow 90% flow SR 3.3.1.7 (b)(c)

SR 3.3.1.10 (b)(c)

SR 3.3.1.15

11.

Undervoltage RCPs 1 (h) 1 per bus M

SR 3.3.1.9 5112 V 5400 V SR 3.3.1.10 (b)(c)

SR 3.3.1.15

12.

Underfrequency RCPs 1 (h) 1 per bus M

SR 3.3.1.9 56.9 Hz 57.5 Hz SR 3.3.1.10 (b)(c)

SR 3.3.1.15 (continued)

(b) If the as found channel setpoint is outside its predefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

(h) Above the P-7 (Low Power Reactor Trips Block) interlock.

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-18 (developmental)

G Table 3.3.1-1 (page 4 of 9)

Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

13. SG Water Level -

Low-Low 1, 2 3/SG U

SR 3.3.1.1 16.4% of narrow range span 17% of narrow range span SR 3.3.1.7 (b)(c)

SR 3.3.1.10 (b)(c)

SR 3.3.1.15 Coincident with:

a)

Vessel T Equivalent to power 50% RTP 1, 2 3

V SR 3.3.1.7 (b)(c)

Vessel T variable input 52.6% RTP Vessel T variable input 50% RTP SR 3.3.1.10 (b)(c)

With a time delay (Ts) if one steam generator is affected 1.01 Ts (Refer to Note 3, Page 3.3-23)

Ts (Refer to Note 3, Page 3.3-23) or A time delay (Tm) if two or more steam generators are affected 1.01 Tm (Refer to Note 3, Page 3.3-23)

Tm (Refer to Note 3, Page 3.3-23) b)

Vessel T Equivalent to power

> 50% RTP with no time delay (Ts and Tm = 0) 1, 2 3

V SR 3.3.1.7 (b)(c)

SR 3.3.1.10 (b)(c)

Vessel T variable input 52.6% RTP Vessel T variable input 50% RTP

14.

Turbine Trip

a.

Low Fluid Oil Pressure 1 (i) 3 O

38.3 psig 45 psig SR 3.3.1.14

b.

Turbine Stop Valve Closure 1 (i) 4 Y

SR 3.3.1.10 1% open 1% open SR 3.3.1.14 (continued)

(b) If the as found channel setpoint is outside its predefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c) The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

(i) Above the P-9 (Power Range Neutron Flux) interlock.

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-19 (developmental)

F Table 3.3.1-1 (page 5 of 9)

Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

15.

Safety Injection (SI)

Input from Engineered Safety Feature Actuation System (ESFAS) 1, 2 2 trains P

SR 3.3.1.13 NA NA

16.

Reactor Trip System Interlocks

a.

Intermediate Range Neutron Flux, P-6 (1) Enable Manual Block of SR Trip 2 (f) 2 R

SR 3.3.1.11 NA 1.66E-04%

RTP SR 3.3.1.12 (2) Auto Reset (Unblock Manual Block of SR Trip) 2 (f) 2 R

SR 3.3.1.11 7.65E-5%

RTP 0.47E-4% RTP below setpoint SR 3.3.1.12

b.

Low Power Reactor Trips Block, P-7 1

1 per train S

SR 3.3.1.11 NA NA SR 3.3.1.12

c.

Power Range Neutron Flux, P-8 1

4 S

SR 3.3.1.11 50.4% RTP 48% RTP SR 3.3.1.12

d.

Power Range Neutron Flux, P-9 1

4 S

SR 3.3.1.11 52.4% RTP 50% RTP SR 3.3.1.12

e.

Power Range Neutron Flux, P-10 1, 2 4

R SR 3.3.1.11 7.6% RTP and 12.4% RTP 10% RTP SR 3.3.1.12

f.

Turbine Impulse Pressure, P-13 1

2 S

SR 3.3.1.10 12.4%

full-power pressure 10%

full-power pressure SR 3.3.1.12 (continued)

(f) Below the P-6 (Intermediate Range Neutron Flux) interlocks.

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-20 (developmental)

A Table 3.3.1-1 (page 6 of 9)

Reactor Trip System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOW-ABLE VALUE NOMINAL TRIP SETPOINT

17.

Reactor Trip Breakers (j) 1, 2 2 trains Q

SR 3.3.1.4 NA NA 3 (a), 4 (a), 5 (a) 2 trains C

SR 3.3.1.4 NA NA

18.

Reactor Trip Breaker Undervoltage and Shunt Trip Mechanisms 1, 2 1 each per RTB T

SR 3.3.1.4 NA NA 3 (a), 4 (a), 5 (a) 1 each per RTB C

SR 3.3.1.4 NA NA

19.

Automatic Trip Logic 1, 2 2 trains P

SR 3.3.1.5 NA NA 3 (a), 4 (a), 5 (a) 2 trains C

SR 3.3.1.5 NA NA (a) With Reactor Trip Breakers (RTBs) closed and Rod Control System capable of rod withdrawal.

(j) Including any reactor trip bypass breakers that are racked in and closed for bypassing an RTB.

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-21 (developmental)

A Table 3.3.1-1 (page 7 of 9)

Reactor Trip System Instrumentation Note 1: Overtemperature T The Overtemperature T Function Allowable Value shall not exceed the following Trip Setpoint by more than 1.2% of T span.

T 1 + 4s 1 + 5sT0 K1 K2 (1 + 1s)

(1 + 2s) T T+ K3P Pf1(I)

Where:

T is measured RCS T, °F.

T0 is the indicated T at RTP, °F.

s is the Laplace transform operator, sec-1.

T is the measured RCS average temperature, °F.

T is the indicated Tavg at RTP, 588.2°F.

P is the measured pressurizer pressure, psig P is the nominal RCS operating pressure, 2235 psig K1 1.16 K2 0.0183/°F K3 = 0.000900/psig 1 33 sec 2 4 sec 4 3 sec 5 3 sec f1(I) =

-2.62{22 + (qt - qb)}

when qt - qb < - 22% RTP 0

when -22% RTP qt - qb 10% RTP 1.96{(qt - qb) - 10}

when qt - qb > 10% RTP Where qt and qb are percent RTP in the upper and lower halves of the core, respectively, and qt + qb is the total THERMAL POWER in percent RTP.

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-22 (developmental)

AI Table 3.3.1-1 (page 8 of 9)

Reactor Trip System Instrumentation Note 2: Overpower T The Overpower T Function Allowable Value shall not exceed the following Trip Setpoint by more than 1.0% of T span.

T 1+4s 1+5sT0 K4-K5 (3s)

(1+3s) [T]+K6T-T-f2(I)

Where:

T is measured RCS T, °F.

T0 is the indicated T at RTP, °F.

s is the Laplace transform operator, sec-1.

T is the measured RCS average temperature, °F.

T is the indicated Tavg at RTP, 588.2°F.

K4 1.10 K5 0.02/°F for increasing Tavg K6 0.00162/°F when T > T 0/°F for decreasing Tavg 0/°F when T T 3 5 sec 4

3 sec 5

3 sec f2(I) = 0 for all I.

RTS Instrumentation 3.3.1 Watts Bar - Unit 2 3.3-23 (developmental)

A Table 3.3.1-1 (page 9 of 9)

Reactor Trip System Instrumentation NOTE 3: Steam Generator Water Level Low-Low Trip Time Delay:

Ts = A(P)3 + B(P)2+ C(P)+ D Tm = E(P)3 + F(P)2+ G(P)+ H Where:

P

= Vessel T Equivalent to power (% RTP), P 50% RTP Ts

= Time Delay for Steam Generator Water Level - Low Low Reactor Trip, one Steam Generator affected.

Tm

= Time Delay for Steam Generator Water Level - Low Low Reactor Trip, two or more Steam Generators affected.

A

= -0.0085041 B

= 0.9266400 C

= -33.85998 D

= 474.6060 E

= -0.0047421 F

= 0.5682600 G

= -23.70753 H

= 357.9840

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-24 (developmental)

AI 3.3 INSTRUMENTATION 3.3.2 Engineered Safety Feature Actuation System (ESFAS) Instrumentation LCO 3.3.2 The ESFAS instrumentation for each Function in Table 3.3.2-1 shall be OPERABLE.

APPLICABILITY:

According to Table 3.3.2-1.

ACTIONS


NOTE----------------------------------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more Functions with one or more required channels or trains inoperable.

A.1 Enter the Condition referenced in Table 3.3.2-1 for the channel(s) or train(s).

Immediately B. One channel or train inoperable.

B.1 Restore channel or train to OPERABLE status.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> OR B.2.1 Be in MODE 3.

54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> AND B.2.2 Be in Mode MODE 5.

84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> (continued)

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-25 (developmental)

AI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. One train inoperable.

C.1


NOTE------------

One train may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing provided the other train is OPERABLE.

Restore train to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> OR C.2.1 Be in Mode MODE 3.

30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> AND C.2.2 Be in Mode MODE 5.

60 hours6.944444e-4 days <br />0.0167 hours <br />9.920635e-5 weeks <br />2.283e-5 months <br /> D. One channel inoperable.

D.1


NOTE------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR D.2.1 Be in Mode MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> AND D.2.2 Be in Mode MODE 4.

84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> (continued)

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-26 (developmental)

AI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E. One Containment Pressure channel inoperable.

E.1


NOTE------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

Place channel in bypass.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR E.2.1 Be in Mode MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> AND E.2.2 Be in Mode MODE 4.

84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> F. One channel or train inoperable.

F.1 Restore channel or train to OPERABLE status.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> OR F.2.1 Be in MODE 3.

54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> AND F.2.2 Be in Mode MODE 4.

60 hours6.944444e-4 days <br />0.0167 hours <br />9.920635e-5 weeks <br />2.283e-5 months <br /> (continued)

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-27 (developmental)

AI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME G. One train inoperable.

G.1


NOTE------------

One train may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing provided the other train is OPERABLE.

Restore train to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> OR G.2.1 Be in Mode MODE 3.

30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> AND G.2.2 Be in Mode MODE 4.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> H. One train inoperable.

H.1


NOTE------------

One train may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing provided the other train is OPERABLE.

Restore train to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> OR H.2.1 Be in Mode MODE 3.

30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br /> AND H.2.2 Be in Mode MODE 4.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> (continued)

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-28 (developmental)

BI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME I. One Steam Generator Water Level - High High channel inoperable.

I.1


NOTE------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR I.2.1 Be in Mode MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> AND I.2.2 Be in Mode MODE 4.

84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> J. One or more Turbine Driven Main Feedwater Pump trip channel(s) inoperable.

J.1 Restore channel to OPERABLE status.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> OR J.2 Be in Mode MODE 3.

54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> K. One channel inoperable.

K.1


NOTE------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

Place channel in bypass.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR K.2.1 Be in Mode MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> AND K.2.2 Be in Mode MODE 5.

108 hours0.00125 days <br />0.03 hours <br />1.785714e-4 weeks <br />4.1094e-5 months <br /> (continued)

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-29 (developmental)

AI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME L. One P-11 interlock channel inoperable.

L.1 Verify interlock is in required state for existing unit condition.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OR L.2.1 Be in Mode MODE 3.

7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br /> AND L.2.2 Be in Mode MODE 4.

13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br /> M. One Steam Generator Water Level - Low-Low channel inoperable.


NOTE-------------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

M.1.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND M.1.2 For the affected protection set, set the Trip Time Delay (Ts) to match the Trip Time Delay (Tm).

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR M.2.1 Be in Mode MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> AND M.2.2 Be in Mode MODE 4.

84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> (continued)

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-30 (developmental)

AI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME N. One Vessel T channel inoperable.


NOTE-------------------

One channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing.

N.1 Set the Trip Time Delay threshold power level for (Ts) and (Tm) to 0%

power.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR N.2 Be in MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> O. One MSVV Room Water Level High channel inoperable.


NOTE-------------------

The inoperable channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing of other channels.

O.1 Place channel in trip.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR O.2 Be in MODE 3.

78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br />

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-31 (developmental)

B SURVEILLANCE REQUIREMENTS


NOTE----------------------------------------------------------

Refer to Table 3.3.2-1 to determine which SRs apply for each ESFAS Function.

SURVEILLANCE FREQUENCY SR 3.3.2.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.2.2 Perform ACTUATION LOGIC TEST.

92 days on a STAGGERED TEST BASIS SR 3.3.2.3 Perform MASTER RELAY TEST.

92 days on a STAGGERED TEST BASIS SR 3.3.2.4 Perform COT.

184 days SR 3.3.2.5


NOTE------------------------------

Slave relays tested by SR 3.3.2.7 are excluded from this surveillance.

Perform SLAVE RELAY TEST.

92 days OR 18 months for Westinghouse type AR and Potter &

Brumfield MDR Series relays (continued)

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-32 (developmental)

FI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.2.6


NOTE------------------------------

Verification of relay setpoints not required.

Perform TADOT.

92 days SR 3.3.2.7 Perform SLAVE RELAY TEST on slave relays K603A, K603B, K604A, K604B, K607A, K607B, K609A, K609B, K612A, K625A, and K625B, 18 months SR 3.3.2.8


NOTE------------------------------

Verification of setpoint not required for manual initiation.

Perform TADOT.

18 months SR 3.3.2.9


NOTE------------------------------

This Surveillance shall include verification that the time constants are adjusted to the prescribed values.

Perform CHANNEL CALIBRATION.

18 months SR 3.3.2.10


NOTE------------------------------

Not required to be performed for the turbine driven AFW pump until 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after > 1092 psig in the steam generator.

Verify ESFAS RESPONSE TIMES are within limit.

18 months on a STAGGERED TEST BASIS SR 3.3.2.11


NOTE------------------------------

Verification of setpoint not required.

Perform TADOT.

Once per reactor trip breaker cycle

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-33 (developmental)

FI Table 3.3.2-1 (page 1 of 8)

Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

1.

Safety Injection

a.

Manual Initiation 1, 2, 3, 4 2

B SR 3.3.2.8 NA NA

b.

Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C

SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5 SR 3.3.2.7

c.

Containment Pressure - High 1, 2, 3 3

D SR 3.3.2.1 1.6 psig 1.5 psig SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10

d.

Pressurizer Pressure - Low 1, 2, 3(a) 3 D

SR 3.3.2.1

> 1864.8 psig 1870 psig SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10

e.

Steam Line Pressure - Low 1, 2, 3(a) 3 per steam line D

SR 3.3.2.1

> 666.6(d) psi g

675(d) psig SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10

2.

Containment Spray

a.

Manual Initiation 1, 2, 3, 4 2 per train, 2 trains B

SR 3.3.2.8 NA NA

b.

Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C

SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5

c.

Containment Pressure -

High High 1, 2, 3 4

E SR 3.3.2.1

< 2.9 psig 2.8 psig SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10 (a)

Above the P-11 (Pressurizer Pressure) Interlock.

(b)

If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c)

The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

(d)

Time constants used in the lead/lag controller are t1 > 50 seconds and t2 < 5 seconds.

(continued)

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-34 (developmental)

FI Table 3.3.2-1 (page 2 of 8)

Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

3.

Containment Isolation

a.

Phase A Isolation

1)

Manual Initiation 1, 2, 3, 4 2

B SR 3.3.2.8 NA NA

2)

Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C

SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5 SR 3.3.2.7

3)

Safety Injection Refer to Function 1 (Safety Injection) for all initiation functions and requirements.

b.

Phase B Isolation

1)

Manual Initiation 1, 2, 3, 4 2 per train, 2 trains B

SR 3.3.2.8 NA NA

2)

Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C

SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5 SR 3.3.2.7

3)

Containment Pressure -

High High 1, 2, 3 4

E SR 3.3.2.1

< 2.9 psig 2.8 psig SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10 (continued)

(b)

If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c)

The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-35 (developmental)

FI Table 3.3.2-1 (page 3 of 8)

Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

4.

Steam Line Isolation

a.

Manual Initiation 1, 2 (e), 3 (e) 1/valve F

SR 3.3.2.8 NA NA

b.

Automatic Actuation Logic and Actuation Relays 1, 2 (e), 3 (e) 2 trains G

SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5

c.

Containment Pressure -

High High 1, 2 (e), 3 (e) 4 E

SR 3.3.2.1

< 2.9 psig 2.8 psig SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10

d.

Steam Line Pressure

1)

Low 1, 2 (e), 3 (a)(e) 3 per steam line D

SR 3.3.2.1

> 666.6 (d) psig 675 (d) psig SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10

2)

Negative Rate - High 3 (e)(f) 3 per steam line D

SR 3.3.2.1

< 108.5 (g) psi 100 (g) psi SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10 (continued)

(b)

If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c)

The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

(d)

Time constants used in the lead/lag controller are t1 > 50 seconds and t2 < 5 seconds.

(e)

Except when all MSIVs are closed and de-activated.

(f)

Function automatically blocked above P-11 (Pressurizer Interlock) setpoint and is enabled below P-11 when safety injection on Steam Line Pressure Low is manually blocked.

(g)

Time constants utilized in the rate/lag controller are t3 and t4 > 50 seconds.

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-36 (developmental)

FI Table 3.3.2-1 (page 4 of 8)

Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

5.

Turbine Trip and Feedwater Isolation

a.

Automatic Actuation Logic and Actuation Relays 1, 2 (h), 3 (h) 2 trains H

SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5

b.

SG Water Level -

High High (P-14) 1, 2 (h), 3 (h) 3 per SG I

SR 3.3.2.1

< 83.1%

82.4%

SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10

c.

Safety Injection Refer to Function 1 (Safety Injection) for all initiation functions and requirements.

d.

North MSV Vault Room Water Level - High 1, 2 (h)(i) 3 per vault room O

SR 3.3.2.6

< 5.31 inches 4 inches SR 3.3.2.9

e.

South MSV Vault Room Water Level - High 1, 2 (h)(i) 3 per vault room O

SR 3.3.2.6

< 4.56 inches 4 inches SR 3.3.2.9 (continued)

(b)

If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c)

The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

(h)

Except when all MFIVs, MFRVs, and associated bypass valves are closed and de-activated or isolated by a closed manual valve.

(i)

Mode 2 if Turbine Driven Main Feed Pumps are operating.

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-37 (developmental)

FI Table 3.3.2-1 (page 5 of 8)

Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

6.

Auxiliary Feedwater

a.

Automatic Actuation Logic and Actuation Relays 1, 2, 3 2 trains G

SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5

b.

SG Water Level

- Low Low 1, 2, 3 3 per SG M

SR 3.3.2.1

> 16.4%

17.0%

SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10 Coincident with:

1) Vessel T Equivalent to power 50% RTP 1, 2 3

N SR 3.3.2.4 (b) (c)

Vessel T variable input 52.6% RTP Vessel T variable input 50% RTP SR 3.3.2.9 (b) (c)

With a time delay (Ts) if one SG is affected 1.01 Ts (Note 1, Page 3.3-40)

Ts (Note 1, Page 3.3-40) or A time delay (Tm) if two or more SGs are affected 1.01 Tm (Note 1, Page 3.3-40)

Tm (Note 1, Page 3.3-40)

2) Vessel T equivalent to power

> 50% RTP with no time delay (Ts and Tm = 0) 1, 2 3

N SR 3.3.2.4 (b) (c)

Vessel T variable input 52.6% RTP Vessel T variable input 50% RTP SR 3.3.2.9 (b) (c)

c.

Safety Injection Refer to Function 1 (Safety Injection) for all initiation functions and requirements.

(continued)

(b)

If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c)

The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-38 (developmental)

GI Table 3.3.2-1 (page 6 of 8)

Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

6.

Auxiliary Feedwater (continued)

d.

Loss of Offsite Power 1, 2, 3 4 per bus F

Refer to Function 4 of Table 3.3.5-1 for SRs and Allowable Values. Notes (b) and (c) are applicable to SR 3.3.5.2 for this function.

e.

Trip of all Turbine Driven Main Feedwater Pumps 1 (j), 2 (k) 1 per pump J

SR 3.3.2.8 (b)(c)

> 43.3 psig 50 psig SR 3.3.2.9 (b) (c)

SR 3.3.2.10

f.

Auxiliary Feedwater Pumps Train A and B Suction Transfer on Suction Pressure - Low 1, 2, 3 3

F SR 3.3.2.6 A) > 0.5 psig A) 1.2 psig SR 3.3.2.9 (b) (c)

SR 3.3.2.10 B) > 1.33 psi g

B) 2.0 psig

7.

Automatic Switchover to Containment Sump

a.

Automatic Actuation Logic and Actuation Relays 1, 2, 3, 4 2 trains C

SR 3.3.2.2 NA NA SR 3.3.2.3 SR 3.3.2.5

b.

Refueling Water Storage Tank (RWST)

Level - Low 1, 2, 3, 4 4

K SR 3.3.2.1

> 155.6 inche s from Tank Base 158 inches from Tank Base SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10 Coincident with Safety Injection Refer to Function 1 (Safety Injection) for all initiation functions and requirements.

and Coincident with Containment Sump Level - High 1, 2, 3, 4 4

K SR 3.3.2.1

> 37.2 inches above el. 702.8 ft 38.2 inches above el. 702.8 ft SR 3.3.2.4 (b) (c)

SR 3.3.2.9 (b) (c)

SR 3.3.2.10 (continued)

(b)

If the as found channel setpoint is outside its redefined as found tolerance, then the channel shall be evaluated to verify that it is functioning as required before returning the channel to service.

(c)

The instrument channel setpoint shall be reset to a value that is within the as left tolerance around the Nominal Trip Setpoint (NTSP) at the completion of the surveillance; otherwise, the channel shall be declared inoperable. The methodologies used to determine the as found and as left tolerances for the NTSP are specified in FSAR Section 7.1.2.

(j)

Entry into Condition J may be suspended for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> when placing the second Turbine Driven Main Feedwater (TDMFW) Pump in service or removing one of two TDMFW pumps from service.

(k)

When one or more Turbine Driven Main Feedwater Pump(s) are supplying feedwater to steam generators.

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-39 (developmental)

FI Table 3.3.2-1 (page 7 of 8)

Engineered Safety Feature Actuation System Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS CONDITIONS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE NOMINAL TRIP SETPOINT

8.

ESFAS Interlocks

a.

Reactor Trip, P-4 1, 2, 3 1 per train, 2 trains F

SR 3.3.2.11 NA NA

b.

Pressurizer Pressure, P-11 (1) Unblock (Auto Reset of SI Block) 1, 2, 3 3

L SR 3.3.2.1

< 1975.2 psig 1970 psig SR 3.3.2.4 SR 3.3.2.9 (2) Enable Manual Block of SI 1, 2, 3 3

L SR 3.3.2.1

> 1956.8 psig 1962 psig SR 3.3.2.4 SR 3.3.2.9

ESFAS Instrumentation 3.3.2 Watts Bar - Unit 2 3.3-40 (developmental)

F Table 3.3.2-1 (page 8 of 8)

Engineered Safety Feature Actuation System Instrumentation NOTE 1: Steam Generator Water Level Low-Low Trip Time Delay:

Ts = A(P)3 + B(P)2+ C(P)+ D Tm = E(P)3 + F(P)2+ G(P)+ H Where:

P

= Vessel T Equivalent to power (% RTP), P 50% RTP Ts

= Time Delay for Steam Generator Water Level - Low Low Reactor Trip, one Steam Generator affected.

Tm

= Time Delay for Steam Generator Water Level - Low Low Reactor Trip, two or more Steam Generators affected.

A

= -0.0085041 B

= 0.9266400 C

= -33.85998 D

= 474.6060 E

= -0.0047421 F

= 0.5682600 G

= -23.70753 H

= 357.9840

PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-41 (developmental)

BI 3.3 INSTRUMENTATION 3.3.3 Post Accident Monitoring (PAM) InstrumentationTHIS SECTION NOT USED LCO 3.3.3 The PAM instrumentation for each Function in Table 3.3.3-1 shall be OPERABLE.

APPLICABILITY:

According to Table 3.3.3-1.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. ------------NOTE----------------

Not applicable to Functions 3, 4, 14, and 16.

One or more Functions with one required channel inoperable.

A.1 Restore required channel to OPERABLE status.

30 days B. Required Action and associated Completion Time of Condition A not met.

B.1 Initiate action in accordance with Specification 5.9.8.

Immediately (continued)

PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-42 (developmental)

BI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. One or more Functions with two required channels inoperable.

OR Functions 3, 4, 14, and 16 with one required channel inoperable.

C.1 Restore one channel to OPERABLE status.

7 days D. Required Action and associated Completion Time of Condition C not met.

D.1 Enter the Condition referenced in Table 3.3.3-1 for the channel.

Immediately E. As required by Required Action D.1 and referenced in Table 3.3.3-1.

E.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND E.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> F. As required by Required Action D.1 and referenced in Table 3.3.3-1.

F.1 Initiate action in accordance with Specification 5.9.8.

Immediately

PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-43 (developmental)

BI SURVEILLANCE REQUIREMENTS


NOTE-------------------------------------------------------------

SR 3.3.3.1 and SR 3.3.3.2 apply to each PAM instrumentation Function in Table 3.3.3-1.

SURVEILLANCE FREQUENCY SR 3.3.3.1 Perform CHANNEL CHECK for each required instrumentation channel that is normally energized.

31 days SR 3.3.3.2


NOTES----------------------------

1. Neutron detectors are excluded from CHANNEL CALIBRATION.
2. Not applicable to Functions 11 and 16.

Perform CHANNEL CALIBRATION.

18 months SR 3.3.3.3


NOTES----------------------------

1. Verification of relay setpoints not required.
2. Only applicable to Functions 11 and 16.

Perform TADOT.

18 months

PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-44 (developmental)

HI Table 3.3.3-1 (page 1 of 3)

Post Accident Monitoring Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS /

TRAINS CONDITION REFERENCED FROM REQUIRED ACTION D.1

1)

Intermediate Range Neutron Flux (g) 1(a), 2(b), 3 2

E

2)

Source Range Neutron Flux 2(c), 3 2

E

3)

Reactor Coolant System (RCS) Hot Leg Temperature (T-Hot) 1, 2, 3 1 per loop E

4)

RCS Cold Leg Temperature (T-Cold) 1, 2, 3 1 per loop E

5)

RCS Pressure (Wide Range) 1, 2, 3 3

E

6)

Reactor Vessel Water Level (f) 1, 2, 3 2

F

7)

Containment Sump Water Level (Wide Range) 1, 2, 3 2

E

8)

Containment Lower Comp.

Atm. Temperature 1, 2, 3 2

E

9)

Containment Pressure (Wide Range) (g) 1, 2, 3 2

E

10)

Containment Pressure (Narrow Range) 1, 2, 3 4

E

11)

Containment Isolation Valve Position (g) 1, 2, 3 2 per penetration flow path (d)(i)

E

12)

Containment Radiation (High Range) 1, 2, 3 2 upper containment 2 lower containment F

13)

RCS Pressurizer Level 1, 2, 3 3

E

14)

Steam Generator (SG) Water Level (Wide Range) (g) 1, 2, 3 1/SG E

(continued)

PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-45 (developmental)

BI Table 3.3.3-1 (page 2 of 3)

Post Accident Monitoring Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS /

TRAINS CONDITION REFERENCED FROM REQUIRED ACTION D.1

15)

Steam Generator Water Level (Narrow Range) 1, 2, 3 3/SG E

16)

AFW Valve Status (j) 1, 2, 3 1 per valve E

17)

Core Exit Temperature-Quadrant 1(f) 1, 2, 3 2 (e)

E

18)

Core Exit Temperature-Quadrant 2(f) 1, 2, 3 2 (e)

E

19)

Core Exit Temperature-Quadrant 3(f) 1, 2, 3 2 (e)

E

20)

Core Exit Temperature-Quadrant 4(f) 1, 2, 3 2 (e)

E

21)

Auxiliary Feedwater Flow 1, 2, 3 2/SG E

22)

Reactor Coolant System Subcooling Margin Monitor (h) 1, 2, 3 2

E

23)

Refueling Water Storage Tank Water Level 1, 2, 3 2

E

24)

Steam Generator Pressure 1, 2, 3 2/SG E

25)

Auxiliary Building Passive Sump Level (j) 1, 2, 3 2

E

PAM InstrumentationTHIS SECTION NOT USED 3.3.3 Watts Bar - Unit 2 3.3-46 (developmental)

BI Table 3.3.3-1 (page 3 of 3)

Post Accident Monitoring Instrumentation (a)

Below the P-10 (Power Range Neutron Flux) interlocks.

(b)

Above the P-6 (Intermediate Range Neutron Flux) interlocks.

(c)

Below the P-6 (Intermediate Range Neutron Flux) interlocks (d)

Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated automatic valve, closed manual valve, blind flange, pressure relief valve, or check valve with flow through the valve secured.

(e)

A channel consists of two core exit thermocouples (CETs).

(f)

The Common Q Post Accident Monitoring System provides these functions on a flat screen display.

(g)

Regulatory Guide 1.97, non-Type A, Category 1 Variables.

(h)

This function is displayed on the Common Q Post Accident Monitoring System flat screen display and digital panel meters.

(i)

Only one position indication channel is required for penetration flow paths with only one installed control room indication channel.

(j)

Watts Bar specific (not required by Regulatory Guide 1.97) non-Type A Category 1 variable.

Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-53 (developmental)

H 3.3 INSTRUMENTATION 3.3.6 Containment Vent Isolation Instrumentation LCO 3.3.6 The Containment Vent Isolation instrumentation for each Function in Table 3.3.6-1 shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. One radiation monitoring channel inoperable.

A.1 Restore the affected channel to OPERABLE status.

4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> (continued)

Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-54 (developmental)

H ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. One or more Functions with one or more manual or automatic actuation trains inoperable.

OR Two radiation monitoring channels inoperable.

OR Required Action and associated Completion Time of Condition A not met.


NOTE-------------------

One train of automatic actuation logic may be bypassed and Required Action B.1 may be delayed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for Surveillance testing provided the other train is OPERABLE.

B.1 Enter applicable Conditions and Required Actions of LCO 3.6.3, "Containment Isolation Valves," for containment purge and exhaust isolation valves made inoperable by isolation instrumentation.

Immediately

Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-55 (developmental)

B SURVEILLANCE REQUIREMENTS


NOTE-------------------------------------------------------------

Refer to Table 3.3.6-1 to determine which SRs apply for each Containment Vent Isolation Function.

SURVEILLANCE FREQUENCY SR 3.3.6.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.6.2


NOTE------------------------------

This surveillance is only applicable to the actuation logic of the ESFAS instrumentation.

Perform ACTUATION LOGIC TEST.

92 days on a STAGGERED TEST BASIS SR 3.3.6.3


NOTE------------------------------

This surveillance is only applicable to the master relays of the ESFAS instrumentation.

Perform MASTER RELAY TEST.

92 days on a STAGGERED TEST BASIS SR 3.3.6.4 Perform COT.

92 days SR 3.3.6.5 Perform SLAVE RELAY TEST.

92 days OR 18 months for Westinghouse type AR and Potter &

Brumfield MDR Series relays (continued)

Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-56 (developmental)

A SURVEILLANCE REQUIREMENTS (Continued)

SURVEILLANCE FREQUENCY SR 3.3.6.6


NOTE------------------------------

Verification of setpoint is not required.

Perform TADOT.

18 months SR 3.3.6.7 Perform CHANNEL CALIBRATION.

18 months

Containment Vent Isolation Instrumentation 3.3.6 Watts Bar - Unit 2 3.3-57 (developmental)

HI Table 3.3.6-1 (page 1 of 1)

Containment Vent Isolation Instrumentation FUNCTION REQUIRED CHANNELS SURVEILLANCE REQUIREMENTS ALLOWABLE VALUE

1.

Manual Initiation 2

SR 3.3.6.6 NA

2.

Automatic Actuation Logic and Actuation Relays 2 trains SR 3.3.6.2 SR 3.3.6.3 SR 3.3.6.5 NA

3.

Containment Purge Exhaust Radiation Monitors 2

SR 3.3.6.1 SR 3.3.6.4 SR 3.3.6.7

< 2.8E-02 µCi/cc(b)

(1.14x104 cpm)

4.

Safety Injection Refer to LCO 3.3.2, "ESFAS Instrumentation," Function 1, for all initiation functions and requirements.

PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-41 (developmental)

BI 3.3 INSTRUMENTATION 3.3.3 9 Post Accident Monitoring (PAM) Instrumentation LCO 3.3.39 The PAM instrumentation for each Function in Table 3.3.39-1 shall be OPERABLE.

APPLICABILITY:

According to Table 3.3.3-91.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. ------------NOTE----------------

Not applicable to Functions 3, 4, 14, and 16.

One or more Functions with one required channel inoperable.

A.1 Restore required channel to OPERABLE status.

30 days B. Required Action and associated Completion Time of Condition A not met.

B.1 Initiate action in accordance with Specification 5.9.8.

Immediately (continued)

PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-42 (developmental)

BI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. One or more Functions with two required channels inoperable.

OR Functions 3, 4, 14, and 16 with one required channel inoperable.

C.1 Restore one channel to OPERABLE status.

7 days D. Required Action and associated Completion Time of Condition C not met.

D.1 Enter the Condition referenced in Table 3.3.39-1 for the channel.

Immediately E. As required by Required Action D.1 and referenced in Table 3.3.39-1.

E.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND E.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> F. As required by Required Action D.1 and referenced in Table 3.3.39-1.

F.1 Initiate action in accordance with Specification 5.9.8.

Immediately

PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-43 (developmental)

BI SURVEILLANCE REQUIREMENTS


NOTE-------------------------------------------------------------

SR 3.3.39.1 and SR 3.3.39.2 apply to each PAM instrumentation Function in Table 3.3.39-1.

SURVEILLANCE FREQUENCY SR 3.3.39.1 Perform CHANNEL CHECK for each required instrumentation channel that is normally energized.

31 days R 3.3.39.2


NOTES----------------------------

1. Neutron detectors are excluded from CHANNEL CALIBRATION.
2. Not applicable to Functions 11 and 16.

Perform CHANNEL CALIBRATION.

18 months SR 3.3.39.3


NOTES----------------------------

1. Verification of relay setpoints not required.
2. Only applicable to Functions 11 and 16.

Perform TADOT.

18 months

PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-44 (developmental)

HI Table 3.3.39-1 (page 1 of 3)

Post Accident Monitoring Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS /

TRAINS CONDITION REFERENCED FROM REQUIRED ACTION D.1

1)

Intermediate Range Neutron Flux (g) 1(a), 2(b), 3 2

E

2)

Source Range Neutron Flux 2(c), 3 2

E

3)

Reactor Coolant System (RCS) Hot Leg Temperature (T-Hot) 1, 2, 3 1 per loop E

4)

RCS Cold Leg Temperature (T-Cold) 1, 2, 3 1 per loop E

5)

RCS Pressure (Wide Range) 1, 2, 3 3

E

6)

Reactor Vessel Water Level (f) 1, 2, 3 2

F

7)

Containment Sump Water Level (Wide Range) 1, 2, 3 2

E

8)

Containment Lower Comp.

Atm. Temperature 1, 2, 3 2

E

9)

Containment Pressure (Wide Range) (g) 1, 2, 3 2

E

10)

Containment Pressure (Narrow Range) 1, 2, 3 4

E

11)

Containment Isolation Valve Position (g) 1, 2, 3 2 per penetration flow path (d)(i)

E

12)

Containment Radiation (High Range) 1, 2, 3 2 upper containment 2 lower containment F

13)

RCS Pressurizer Level 1, 2, 3 3

E

14)

Steam Generator (SG) Water Level (Wide Range) (g) 1, 2, 3 1/SG E

(continued)

PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-45 (developmental)

BI Table 3.3.39-1 (page 2 of 3)

Post Accident Monitoring Instrumentation FUNCTION APPLICABLE MODES OR OTHER SPECIFIED CONDITIONS REQUIRED CHANNELS /

TRAINS CONDITION REFERENCED FROM REQUIRED ACTION D.1

15)

Steam Generator Water Level (Narrow Range) 1, 2, 3 3/SG E

16)

AFW Valve Status (j) 1, 2, 3 1 per valve E

17)

Core Exit Temperature-Quadrant 1(f) 1, 2, 3 2 (e)

E

18)

Core Exit Temperature-Quadrant 2(f) 1, 2, 3 2 (e)

E

19)

Core Exit Temperature-Quadrant 3(f) 1, 2, 3 2 (e)

E

20)

Core Exit Temperature-Quadrant 4(f) 1, 2, 3 2 (e)

E

21)

Auxiliary Feedwater Flow 1, 2, 3 2/SG E

22)

Reactor Coolant System Subcooling Margin Monitor (h) 1, 2, 3 2

E

23)

Refueling Water Storage Tank Water Level 1, 2, 3 2

E

24)

Steam Generator Pressure 1, 2, 3 2/SG E

25)

Auxiliary Building Passive Sump Level (j) 1, 2, 3 2

E

PAM Instrumentation 3.3.39 Watts Bar - Unit 2 3.3-46 (developmental)

BI Table 3.3.39-1 (page 3 of 3)

Post Accident Monitoring Instrumentation (a)

Below the P-10 (Power Range Neutron Flux) interlocks.

(b)

Above the P-6 (Intermediate Range Neutron Flux) interlocks.

(c)

Below the P-6 (Intermediate Range Neutron Flux) interlocks (d)

Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated automatic valve, closed manual valve, blind flange, pressure relief valve, or check valve with flow through the valve secured.

(e)

A channel consists of two core exit thermocouples (CETs).

(f)

The Common Q Post Accident Monitoring System provides these functions on a flat screen display.

(g)

Regulatory Guide 1.97, non-Type A, Category 1 Variables.

(h)

This function is displayed on the Common Q Post Accident Monitoring System flat screen display and digital panel meters.

(i)

Only one position indication channel is required for penetration flow paths with only one installed control room indication channel.

(j)

Watts Bar specific (not required by Regulatory Guide 1.97) non-Type A Category 1 variable.

RCS Loops - MODE 4 3.4.6 Watts Bar - Unit 2 3.4-9 (developmental)

BI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.6 RCS Loops - MODE 4 LCO 3.4.6 Two loops shall be OPERABLE, and consist of either:

a.

Any combination of RCS loops and residual heat removal (RHR) loops, and one loop shall be in operation, when the rod control system is not capable of rod withdrawal; or

b.

Two RCS loops, and both loops shall be in operation, when the rod control system is capable of rod withdrawal.


NOTE--------------------------------------------

No RCP shall be started with any RCS cold leg temperature less than or equal to the COMS arming temperature specified in the PTLR, unless the secondary side water temperature of each steam generator (SG) is 50°F above each of the RCS cold leg temperatures.

APPLICABILITY:

MODE 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Only one RCS loop OPERABLE.

AND Two RHR loops inoperable.

A.1 Initiate action to restore a second loop to OPERABLE status.

Immediately B. One required RHR loop inoperable.

AND No RCS loops OPERABLE.

B.1 Be in MODE 5.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (continued)

RCS Loops - MODE 4 3.4.6 Watts Bar - Unit 2 3.4-10 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. One required RCS loop not in operation, and reactor trip breakers closed and Rod Control System capable of rod withdrawal.

C.1 Restore required RCS loop to operation.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> OR C.2 De-energize all control rod drive mechanisms (CRDMs).

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> D. Required RCS or RHR loops inoperable.

OR No required RCS or RHR loop in operation D.1 De-energize all CRDMs.

Immediately AND D.2 Suspend all operations involving a reduction of RCS boron concentration.

Immediately AND D.3 Initiate action to restore one loop to OPERABLE status and operation.

Immediately

RCS Loops - MODE 4 3.4.6 Watts Bar - Unit 2 3.4-11 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.6.1 Verify two RCS loop are in operation when the rod control system is capable of rod withdrawal.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.6.2 Verify one RHR or RCS loop is in operation when the rod control system is not capable of rod withdrawal.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.6.3 Verify SG secondary side water levels are greater than or equal to 6% narrow range for required RCS loops.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.6.4 Verify correct breaker alignment and indicated power are available to the required pump that is not in operation.

7 days

RCS Loops - MODE 5, Loops Filled 3.4.7 Watts Bar - Unit 2 3.4-12 (developmental)

BI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.7 RCS Loops - MODE 5, Loops Filled LCO 3.4.7 One residual heat removal (RHR) loop shall be OPERABLE and in operation, and either:

a.

One additional RHR loop shall be OPERABLE; or

b.

The secondary side water level of at least two steam generators (SGs) shall be greater than or equal to 6% narrow range.


NOTES------------------------------------------

1.

One required RHR loop may be inoperable for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing provided that the other RHR loop is OPERABLE and in operation.

2.

No reactor coolant pump shall be started with one or more RCS cold leg temperatures less than or equal to the COMS arming temperature specified in the PTLR unless the secondary side water temperature of each SG is 50°F above each of the RCS cold leg temperatures.

3.

All RHR loops may be removed from operation during planned heatup to MODE 4 when at least one RCS loop is in operation.

APPLICABILITY:

MODE 5 with RCS loops filled.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One RHR loop inoperable.

AND Required SGs secondary side water levels not within limits.

A.1 Initiate action to restore a second RHR loop to OPERABLE status.

Immediately OR A.2 Initiate action to restore required SG secondary side water levels to within limits.

Immediately (continued)

RCS Loops - MODE 5, Loops Filled 3.4.7 Watts Bar - Unit 2 3.4-13 (developmental)

AI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. Required RHR loops inoperable.

OR No RHR loop in operation.

B.1 Suspend all operations involving a reduction of RCS boron concentration.

Immediately AND B.2 Initiate action to restore one RHR loop to OPERABLE status and operation.

Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.7.1 Verify one RHR loop is in operation.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.7.2 Verify SG secondary side water level is greater than or equal to 6% narrow range in required SGs.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.4.7.3 Verify correct breaker alignment and indicated power are available to the required RHR pump that is not in operation.

7 days

Pressurizer Safety Valves 3.4.10 Watts Bar - Unit 2 3.4-18 (developmental)

FI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.10 Pressurizer Safety Valves LCO 3.4.10 Three pressurizer safety valves shall be OPERABLE with lift settings 2410 psig and 2560 psig.

APPLICABILITY:

MODES 1, 2, and 3, MODE 4 with all RCS cold leg temperatures greater than> the COMS arming temperature specified in the PTLR.


NOTE--------------------------------------------

The lift settings are not required to be within the LCO limits during MODE 3 and MODE 4 with all RCS cold leg temperatures greater than>

the COMS arming temperature specified in the PTLR for the purpose of setting the pressurizer safety valves under ambient (hot) conditions. This exception is allowed for 54 hours6.25e-4 days <br />0.015 hours <br />8.928571e-5 weeks <br />2.0547e-5 months <br /> following entry into MODE 3 provided a preliminary cold setting was made prior to heatup.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One pressurizer safety valve inoperable.

A.1 Restore valve to OPERABLE status.

15 minutes B. Required Action and associated Completion Time not met.

OR Two or more pressurizer safety valves inoperable.

B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 4 with any RCS cold leg temperature less than or equal to < the COMS arming temperature specified in the PTLR.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />

Pressurizer Safety Valves 3.4.10 Watts Bar - Unit 2 3.4-19 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.10.1 Verify each pressurizer safety valve is OPERABLE in accordance with the Inservice Testing Program.

Following testing, lift settings shall be within +/- 1% of the nominal lift setting of 2485 psig.

In accordance with the Inservice Testing Program

COMS 3.4.12 Watts Bar - Unit 2 3.4-23 (developmental)

FI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.12 Cold Overpressure Mitigation System (COMS)

LCO 3.4.12 A COMS System shall be OPERABLE with a maximum of one charging pump and no safety injection pump capable of injecting into the RCS and the accumulators isolated and either a or b below.

a.

Two RCS relief valves, as follows:

1. Two power operated relief valves (PORVs) with lift settings within the limits specified in the PTLR, or
2. One PORV with a lift setting within the limits specified in the PTLR and the RHR suction relief valve with a setpoint 436.5 psig and 463.5 psig.
b.

The RCS depressurized and an RCS vent capable of relieving

> 475 gpm water flow.


NOTE--------------------------------------------

1.

Two charging pumps may be made capable of injecting for less than or equal to one hour for pump swap operations.

2.

Accumulator may be unisolated when accumulator pressure is less than the maximum RCS pressure for the existing RCS cold leg temperature allowed by the P/T limit curves provided in the PTLR.

APPLICABILITY:

MODE 4 with any RCS cold leg temperature less than or equal to < the COMS arming temperature specified in the PTLR, MODE 5, MODE 6 when the reactor vessel head is on

COMS 3.4.12 Watts Bar - Unit 2 3.4-24 (developmental)

BI ACTIONS


NOTE----------------------------------------------------------

LCO 3.0.4.b is not applicable when entering MODE 4.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more safety injection pumps capable of injecting into the RCS.

A.1 Initiate action to verify no safety injection pumps are capable of injecting into the RCS.

Immediately B. Two or more charging pumps capable of injecting into the RCS.

B.1 Initiate action to verify a maximum of one charging pump is capable of injecting into the RCS.

Immediately C. An accumulator not isolated when the accumulator pressure is greater than or equal to the maximum RCS pressure for existing cold leg temperature allowed in the PTLR.

C.1 Isolate affected accumulator.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> D. Required Action and associated Completion Time of Condition C not met.

D.1 Increase RCS cold leg temperature to greater than > the COMS arming temperature specified in the PTLR.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> OR D.2 Depressurize affected accumulator to less than the maximum RCS pressure for existing cold leg temperature allowed in the PTLR.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (continued)

COMS 3.4.12 Watts Bar - Unit 2 3.4-25 (developmental)

BI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E. One required RCS relief valve inoperable in MODE 4 with any RCS cold leg temperature less than or equal to< the COMS arming temperature specified in the PTLR.

E.1 Restore required RCS relief valve to OPERABLE status.

7 days F. One required RCS relief valve inoperable in MODE 5 or 6.

F.1 Restore required RCS relief valve to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> G. Two required RCS relief valves inoperable.

OR Required Action and associated Completion Time of Condition A, B, D, E, or F not met.

OR COMS inoperable for any reason other than Condition A, B, C, D, E, or F.

G.1 Depressurize RCS and establish RCS vent.

8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />

COMS 3.4.12 Watts Bar - Unit 2 3.4-26 (developmental)

GI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.12.1 Verify no safety injection pumps are capable of injecting into the RCS.

Within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after entering MODE 4 from MODE 3 prior to the temperature of one or more RCS cold legs decreasing below the COMS arming temperature specified in the PTLR225°F.

AND 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter SR 3.4.12.2 Verify a maximum of one charging pump is capable of injecting into the RCS.

Within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after entering MODE 4 from MODE 3 prior to the temperature of one or more RCS cold legs decreasing below the COMS arming temperature specified in the PTLR225°F.

AND 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter SR 3.4.12.3 Verify each accumulator is isolated.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (continued)

COMS 3.4.12 Watts Bar - Unit 2 3.4-27 (developmental)

GI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.4.12.4


NOTE------------------------------

Only required to be performed when complying with LCO 3.4.12.b.

Verify RCS vent open.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for unlocked open vent paths AND 31 days for locked open vent paths (continued)

SR 3.4.12.5 Verify PORV block valve is open for each required PORV.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> SR 3.4.12.6 Verify both RHR suction isolation valves are locked open with operator power removed for the required RHR suction relief valve.

31 days SR 3.4.12.7


NOTE------------------------------

Required to be met within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after decreasing RCS cold leg temperature to less than or equal to the COMS arming temperature specified in the PTLR.

Perform a COT on each required PORV, excluding actuation.

31 days SR 3.4.12.8 Perform CHANNEL CALIBRATION for each required PORV actuation channel.

18 months

COMS 3.4.12 Watts Bar - Unit 2 3.4-28 (developmental)

BI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.4.12.5 Verify PORV block valve is open for each required PORV.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> SR 3.4.12.6 Verify both RHR suction isolation valves are locked open with operator power removed for the required RHR suction relief valve.

31 days SR 3.4.12.7


NOTE------------------------------

Required to be met within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after decreasing RCS cold leg temperature to less than or equal to the COMS arming temperature specified in the PTLR.

Perform a COT on each required PORV, excluding actuation.

31 days SR 3.4.12.8 Perform CHANNEL CALIBRATION for each required PORV actuation channel.

18 months

RCS Specific Activity 3.4.16 Watts Bar - Unit 2 3.4-35 (developmental)

H 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.16 RCS Specific Activity LCO 3.4.16 The specific activity of the reactor coolant shall be within limits.

APPLICABILITY:

MODES 1 and 2, MODE 3 with RCS average temperature (Tavg) 500°F.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. DOSE EQUIVALENT I-131

> 0.265 µCi/gm.


NOTE-------------------

LCO 3.0.4.c is applicable.

A.1 Verify DOSE EQUIVALENT I-131 14 µCi/gm.

Once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> AND A.2 Restore DOSE EQUIVALENT I-131 to within limit.

48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> B. Gross specific activity of the reactor coolant not within limit.

B.1 Perform SR 3.4.16.2.

4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> AND B.2 Be in MODE 3 with Tavg < 500°F.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> (continued)

RCS Specific Activity 3.4.16 Watts Bar - Unit 2 3.4-36 (developmental)

HI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. Required Action and associated Completion Time of Condition A not met.

OR DOSE EQUIVALENT I-131

> 14 µCi/gm.

C.1 Be in MODE 3 with Tavg < 500°F.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.16.1 Verify reactor coolant gross specific activity

< 100/E µCi/gm.

7 days SR 3.4.16.2


NOTE------------------------------

Only required to be performed in MODE 1.

Verify reactor coolant DOSE EQUIVALENT I-131 specific activity 0.265 µCi/gm.

14 days AND Between 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> after a THERMAL POWER change of 15% RTP within a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> period (continued)

RCS Specific Activity 3.4.16 Watts Bar - Unit 2 3.4-37 (developmental)

A SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.4.16.3


NOTE------------------------------

Required to be performed within 31 days after a minimum of 2 effective full power days and 20 days of MODE 1 operation have elapsed since the reactor was last subcritical for 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />.

Determine from a sample taken in MODE 1 after a minimum of 2 effective full power days and 20 days of MODE 1 operation have elapsed since the reactor was last subcritical for 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />.

184 days

SG Tube Integrity 3.4.17 Watts Bar - Unit 2 3.4-38 (developmental)

GI 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.17 Steam Generator (SG) Tube Integrity LCO 3.4.17 SG tube integrity shall be maintained AND All SG tubes satisfying the tube plugging or repair criteria shall be plugged or repaired in accordance with the Steam Generator Program.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each SG tube.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more SG tubes satisfying the tube plugging or repair criteria and not plugged or repaired in accordance with the Steam Generator Program A.1 Verify tube integrity of the affected tube(s) is maintained until the next refueling outage or SG tube inspection 7 days AND A.2 Plug or repair the affected tube(s) in accordance with the Steam Generator Program Prior to entering MODE 4 following the next refueling outage or SG tube inspection B. Required Action and associated Completion Time of Condition A not met OR SG tube integrity not maintained B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />

SG Tube Integrity 3.4.17 Watts Bar - Unit 2 3.4-39 (developmental)

GI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.17.1 Verify steam generator tube integrity in accordance with the Steam Generator Program.

In accordance with the Steam Generator Program SR 3.4.17.2 Verify that each inspected SG tube that satisfies the tube plugging or repair criteria is plugged or repaired in accordance with the Steam Generator Program.

Prior to entering MODE 4 following a SG tube inspection

ECCS - Operating 3.5.2 Watts Bar - Unit 2 3.5-3 (developmental)

A 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) 3.5.2 ECCS - Operating LCO 3.5.2 Two ECCS trains shall be OPERABLE.


NOTE--------------------------------------------

1. In MODE 3, both safety injection (SI) pump flow paths may be isolated by closing the isolation valves for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> to perform pressure isolation valve testing per SR 3.4.14.1.
2. In MODE 3, the safety injection pumps and charging pumps may be made incapable of injecting to support transition into or from the Applicability of the LCO 3.4.12, Cold Overpressure Mitigation System (COMS) for up to four hours or until the temperature of all the RCS cold legs exceeds 375°F, whichever occurs first.

APPLICABILITY:

MODES 1, 2, and 3.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more trains inoperable.

AND At least 100% of the ECCS flow equivalent to a single OPERABLE ECCS train available.

A.1 Restore train(s) to OPERABLE status.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> B. Required Action and associated Completion Time not met.

B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />

ECCS - Operating 3.5.2 Watts Bar - Unit 2 3.5-4 (developmental)

BI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.5.2.1 Verify the following valves are in the listed position with power to the valve operator removed.

Number Position Function 2-FCV-63-1 Open RHR Supply 2-FCV-63-22 Open SIS Discharge 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.5.2.2 Verify each ECCS manual, power operated, and automatic valve in the flow path, that is not locked, sealed, or otherwise secured in position, is in the correct position.

31 days SR 3.5.2.3 Verify ECCS piping is full of water.

31 days SR 3.5.2.4 Verify each ECCS pump's developed head at the test flow point is greater than or equal to the required developed head.

In accordance with the Inservice Testing Program SR 3.5.2.5 Verify each ECCS automatic valve in the flow path that is not locked, sealed, or otherwise secured in position, actuates to the correct position on an actual or simulated actuation signal.

18 months SR 3.5.2.6 Verify each ECCS pump starts automatically on an actual or simulated actuation signal.

18 months (continued)

ECCS - Operating 3.5.2 Watts Bar - Unit 2 3.5-5 (developmental)

BI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.5.2.7 Verify, for each ECCS throttle valve listed below, each position stop is in the correct position.

Valve Number CCP Discharge Throttle SI Cold Leg Throttle SI Hot Leg Throttle Valves Valves Valves 2-63-582 2-63-550 2-63-542 2-63-583 2-63-552 2-63-544 2-63-584 2-63-554 2-63-546 2-63-585 2-63-556 2-63-548 18 months SR 3.5.2.8 Verify, by visual inspection, each ECCS train containment sump suction inlet is not restricted by debris and the suction inlet trash racks and screens show no evidence of structural distress or abnormal corrosion.

18 months

Containment Air Temperature 3.6.5 Watts Bar - Unit 2 3.6-15 (developmental)

AI 3.6 CONTAINMENT SYSTEMS 3.6.5 Containment Air Temperature LCO 3.6.5 Containment average air temperature shall be:

a.

> 85°F and 110°F for the containment upper compartment, and

b.

> 100°F and 120°F for the containment lower compartment.


NOTE--------------------------------------------

The minimum containment average air temperatures in MODES 2, 3, and 4 may be reduced to 60°F.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Containment average air temperature not within limits.

A.1 Restore containment average air temperature to within limits.

8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> B. Required Action and associated Completion Time not met.

B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />

Containment Air Temperature 3.6.5 Watts Bar - Unit 2 3.6-16 (developmental)

A SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.5.1 Verify containment upper compartment average air temperature is within limits.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> SR 3.6.5.2 Verify containment lower compartment average air temperature is within limits.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

HMS 3.6.8 Watts Bar - Unit 2 3.6-20 (developmental)

AI 3.6 CONTAINMENT SYSTEMS 3.6.8 Hydrogen Mitigation System (HMS)

LCO 3.6.8 Two HMS trains shall be OPERABLE.

APPLICABILITY:

MODES 1 and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One HMS train inoperable.

A.1 Restore HMS train to OPERABLE status.

7 days OR A.2 Perform SR 3.6.8.1 on the OPERABLE train.

Once per 7 days B. One containment region with no OPERABLE hydrogen ignitorigniter.

B.1 Restore one hydrogen ignitor igniter in the affected containment region to OPERABLE status.

7 days C. Required Action and associated Completion Time not met.

C.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

HMS 3.6.8 Watts Bar - Unit 2 3.6-21 (developmental)

AI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.8.1 Energize each HMS train power supply breaker and verify 33 ignitors igniters are energized in each train.

92 days SR 3.6.8.2 Verify at least one hydrogen ignitor igniter is OPERABLE in each containment region.

92 days SR 3.6.8.3 Energize each hydrogen ignitor igniter and verify temperature is 1700°F.

18 months

MSSVs 3.7.1 Watts Bar - Unit 2 3.7-1 (developmental)

FI 3.7 PLANT SYSTEMS 3.7.1 Main Steam Safety Valves (MSSVs)

LCO 3.7.1 Five MSSVs per steam generator shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each MSSV.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more steam generators with one MSSV inoperable.

A.1 Reduce THERMAL POWER to 59 58 % RTP.

4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> B. One or more steam generators with two or more MSSVs inoperable.

B.1 Reduce THERMAL POWER to less than or equal to the Maximum Allowable % RTP specified in Table 3.7.1-1 for the number of OPERABLE MSSVs.

4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> AND


NOTE-------------

Only required in MODE 1.

B.2 Reduce the Power Range Neutron Flux - High reactor trip setpoint to less than or equal to the Maximum Allowable

% RTP specified in Table 3.7.1-1 for the number of OPERABLE MSSVs.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> (continued)

MSSVs 3.7.1 Watts Bar - Unit 2 3.7-2 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. Required Action and associated Completion Time not met.

OR One or more steam generators with 4 MSSVs inoperable.

C.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND C.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.1.1


NOTE------------------------------

Only required to be performed in MODES 1 and 2.

Verify each required MSSV lift setpoint per Table 3.7.1-2 in accordance with the Inservice Testing Program. Following testing, lift settings shall be within +/- 1%.

In accordance with the Inservice Testing Program

MSSVs 3.7.1 Watts Bar - Unit 2 3.7-3 (developmental)

AI Table 3.7.1-1 (page 1 of 1)

OPERABLE Main Steam Safety Valves Versus Maximum Allowable Power NUMBER OF OPERABLE MSSVs PER STEAM GENERATOR MAXIMUM ALLOWABLE POWER

(% RTP) 3 4241 2

2625 Table 3.7.1-2 (page 1 of 1)

Main Steam Safety Valve Lift Settings VALVE NUMBER LIFT SETTING (psig +/- 3%)

STEAM GENERATOR

  1. 1
  1. 2
  1. 3
  1. 4 12-522 12-517 12-512 12-527 1224 12-523 12-518 12-513 12-528 1215 12-524 12-519 12-514 12-529 1205 12-525 12-520 12-515 12-530 1195 12-526 12-521 12-516 12-531 1185

MFIVs and MFRVs and Associated Bypass Valves 3.7.3 Watts Bar - Unit 2 3.7-6 (developmental)

A 3.7 PLANT SYSTEMS 3.7.3 Main Feedwater Isolation Valves (MFIVs) and Main Feedwater Regulation Valves (MFRVs) and Associated Bypass Valves LCO 3.7.3 Four MFIVs, four MFRVs, and associated bypass valves shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, and 3 except when MFIV, MFRV, or associated bypass valve is closed and de-activated or isolated by a closed manual valve.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each valve.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more MFIVs inoperable.

A.1 Close or isolate MFIV.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND A.2 Verify MFIV is closed or isolated.

Once per 7 days B. One or more MFRVs inoperable.

B.1 Close or isolate MFRV.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND B.2 Verify MFRV is closed or isolated.

Once per 7 days C. One or more MFIV or MFRV bypass valves inoperable.

C.1 Restore bypass valve to OPERABLE status.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> (continued)

MFIVs and MFRVs and Associated Bypass Valves 3.7.3 Watts Bar - Unit 2 3.7-7 (developmental)

AI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME D. One MFIV and MFRV in the same flow path inoperable.

D.1 Isolate affected flow path.

8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> E. One MFIV bypass valve and MFRV bypass valve in the same flow path inoperable.

E.1 Restore one MFIV bypass valve or MFRV bypass valve to OPERABLE status.

8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> F. Required Action and associated Completion Time not met.

EF.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND EF.2 Be in MODE 4.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.7.3.1 Verify the closure time of each MFIV, MFRV, and associated bypass valve is 6.5 seconds on an actual or simulated actuation signal.

In accordance with the Inservice Testing Program or 18 months

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-1 (developmental)

F 3.8 ELECTRICAL POWER SYSTEMS 3.8.1 AC Sources - Operating LCO 3.8.1 The following AC electrical sources shall be OPERABLE:

a.

Two qualified circuits between the offsite transmission network and the onsite Class 1E AC Electrical Power Distribution System; and

b.

Four diesel generators (DGs) capable of supplying the onsite Class 1E AC Electrical Power Distribution System.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS


NOTE-------------------------------------------------------------

LCO 3.0.4.b is not applicable to DGs.

CONDITION REQUIRED ACTION COMPLETION TIME A. One offsite circuit inoperable.

A.1 Perform SR 3.8.1.1 for OPERABLE offsite circuit.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter AND A.2 Declare required feature(s) with no offsite power available inoperable when its redundant required feature(s) is inoperable.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> from discovery of no offsite power to one train concurrent with inoperability of redundant required feature(s)

AND (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-2 (developmental)

F ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.3 Restore offsite circuit to OPERABLE status.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND 6 days from discovery of failure to meet LCO B. One or more DG(s) in Train A inoperable.

OR One or more DG(s) in Train B inoperable.

B.1 Perform SR 3.8.1.1 for the offsite circuits.

1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND Once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter AND B.2 Declare required feature(s) supported by the inoperable DG(s) inoperable when its required redundant feature(s) is inoperable 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> from discovery of Condition B concurrent with inoperability of redundant required feature(s)

AND B.3.1 Determine OPERABLE DG(s) is not inoperable due to common cause failure.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> OR B.3.2 Perform SR 3.8.1.2 for OPERABLE DG(s).

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> AND (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-3 (developmental)

A ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. (continued)

B.4 Restore required DG(s) to OPERABLE status.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> AND 6 days from discovery of failure to meet LCO C. Two offsite circuits inoperable.

C.1 Declare required feature(s) inoperable when its redundant required feature(s) is inoperable.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> from discovery of Condition C concurrent with inoperability of redundant required features AND C.2 Restore one offsite circuit to OPERABLE status.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> D. One offsite circuit inoperable.

AND One or more required DG(s) in Train A inoperable.

OR One or more required DG(s) in Train B inoperable.


NOTE-------------------

Enter applicable Conditions and Required Actions of LCO 3.8.9, "Distribution Systems - Operating,"

when Condition D is entered with no AC power source to any train.

D.1 Restore offsite circuit to OPERABLE status.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> OR D.2 Restore required DG(s) to OPERABLE status.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-4 (developmental)

A ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME E. One or more required DG(s) in Train A inoperable.

AND One or more required DG(s) in Train B inoperable.

E.1 Restore required DGs in Train A to OPERABLE status.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> OR E.2 Restore required DGs in Train B to OPERABLE status.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> F. Required Action and Associated Completion Time of Condition A. B, C, D, or E not met.

F.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND F.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> G. Two offsite circuits inoperable.

AND One or more required DG(s) in Train A inoperable.

OR One or more required DG(s) in Train B inoperable.

G.1 Enter LCO 3.0.3.

Immediately H. One offsite circuit inoperable.

AND One or more required DG(s) in Train A inoperable.

AND One or more required DG(s) in Train B inoperable.

H.1 Enter LCO 3.0.3.

Immediately

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-5 (developmental)

AI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.1.1 Verify correct breaker alignment and indicated power availability for each offsite circuit.

7 days SR 3.8.1.2


NOTES----------------------------

1. Performance of SR 3.8.1.7 satisfies this SR.
2. A modified DG start involving idling and gradual acceleration to synchronous speed may be used for this SR as recommended by the manufacturer. When modified start procedures are not used, the time, voltage, and frequency tolerances of SR 3.8.1.7 must be met.

Verify each DG starts from standby conditions and achieves steady state voltage 6800 V and 7260 V, and frequency 58.8 Hz and 61.2 Hz60.0 Hz nominal.

As specified in Table 3.8.1-1 SR 3.8.1.3


NOTES----------------------------

1. DG loadings may include gradual loading as recommended by the manufacturer.
2. Momentary transients outside the load range do not invalidate this test.
3. This Surveillance shall be conducted on only one DG at a time.
4. This SR shall be preceded by and immediately follow without shutdown a successful performance of SR 3.8.1.2 or SR 3.8.1.7.

Verify each DG is synchronized and loaded and operates for 60 minutes at a load 3960 kW and 4400 kW.

As specified in Table 3.8.1-1 SR 3.8.1.4 Verify each skid mounted day tank contains 218.5 gal of fuel oil.

31 days

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-6 (developmental)

AI (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-7 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.5 Check for and remove accumulated water from each skid mounted day tank.

31 days SR 3.8.1.6 Verify the fuel oil transfer system operates to automatically transfer fuel oil from 7 day storage tank to the skid mounted day tank.

31 days SR 3.8.1.7 Verify each DG starts from standby condition and achieves in 10 seconds, voltage 6800 V, and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.2 60.1 Hz.

184 days SR 3.8.1.8


NOTE------------------------------

For the 2A-A and 2B-B Shutdown Boards, This this Surveillance shall not be performed in MODE 1 or 2.

However, credit may be taken for unplanned events that satisfy this SR.

Verify automatic and manual transfer of each 6.9 kV shutdown board power supply from the normal offsite circuit to each alternate offsite circuit.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-8 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.9


NOTES----------------------------

1. For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2.

However, credit may be taken for unplanned events that satisfy this SR.

2. If performed with the DG synchronized with offsite power, it shall be performed at a power factor 0.8 and 0.9.

Verify each DG rejects a load greater than or equal to its associated single largest post-accident load, and:

a.

Following load rejection, the frequency is 66.75 Hz;

b.

Within 3 seconds following load rejection, the voltage is 6555 V and 7260 V; and

c.

Within 4 seconds following load rejection, the frequency is 58.8 Hz and 61.2 Hz.

18 months SR 3.8.1.10


NOTE------------------------------

For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG operating at a power factor 0.8 and 0.9 does not trip and voltage is maintained 8880 V during and following a load rejection of 3960 kW and 4400 kW and 2970 kVAR and 3300 kVAR.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-9 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.11


NOTE------------------------------

For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify on an actual or simulated loss of offsite power signal:

a.

De-energization of emergency buses;

b.

Load shedding from emergency buses;

c.

DG auto-starts from standby condition and:

1. energizes permanently connected loads in 10 seconds,
2. energizes auto-connected shutdown loads through automatic load sequencer,
3. maintains steady state voltage 6800 V and 7260 V,
4. maintains steady state frequency 58.859.8 Hz and 61.260.1 Hz, and
5. supplies permanently connected and auto-connected shutdown loads for 5 minutes.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-10 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.12


NOTE------------------------------

For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.

Verify on an actual or simulated Engineered Safety Feature (ESF) actuation signal each Unit 2 DG auto-starts from standby condition and:

a.

In 10 seconds after auto-start and during tests, achieves voltage 6800 V and frequency 58.8 Hz;

b.

After DG fast start from standby conditions the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.2 60.1 Hz.

c.

Operates for 5 minutes;

d.

Permanently connected loads remain energized from the offsite power system; and

e.

Emergency loads are energized from the offsite power system.

18 months SR 3.8.1.13


NOTE------------------------------

For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1 or 2. However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG's automatic trips are bypassed on automatic or emergency start signal except:

a.

Engine overspeed; and

b.

Generator differential current 18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-11 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.14


NOTES----------------------------

1. Momentary transients outside the load and power factor ranges do not invalidate this test.
2. For performance of this test in MODE 1, 2, 3 or 4, three DGs must be maintained operable and in a standby condition.
3. Credit may be taken for unplanned events that satisfy this SR.

Verify each DG operating at a power factor 0.8 and 0.9 operates for 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:

a.

For 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded 4620 kW and 4840 kW and 3465 kVAR and 3630 kVAR; and

b.

For the remaining hours of the test loaded 3960 kW and 4400 kW and 2970 kVAR and 3300 kVAR.

18 months SR 3.8.1.15


NOTES----------------------------

This Surveillance shall be performed within 5 minutes of shutting down the DG after the DG has operated 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded 3960 kW and 4400 kW.

Momentary transients outside of load range do not invalidate this test.

Verify each DG starts and achieves, in 10 seconds, voltage 6800 V, and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.260.1 Hz.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-12 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.16


NOTE------------------------------

For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG:

a.

Synchronizes with offsite power source while loaded with emergency loads upon a simulated restoration of offsite power;

b.

Transfers loads to offsite power source; and

c.

Returns to ready-to-load operation.

18 months SR 3.8.1.17


NOTE------------------------------

For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify, DG 2A-A and 2B-B with each Unit 2 DG operating in test mode and connected to its bus, an actual or simulated ESF actuation signal overrides the test mode by:

a.

Returning DG to ready-to-load operation; and

b.

Automatically energizing the emergency load from offsite power.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-13 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.18


NOTE------------------------------

For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify the time delay setting for each sequenced load block is within limits for each accident condition and non-accident condition load sequence.

18 months SR 3.8.1.19


NOTE------------------------------

For DGs 2A-A and 2B-B, This this Surveillance shall not be performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify on an actual or simulated loss of offsite power signal in conjunction with an actual or simulated ESF actuation signal:

a.

De-energization of emergency buses;

b.

Load shedding from emergency buses; and

c.

DGs of the same power train auto-start from standby condition and:

1. energizes permanently connected loads in 10 seconds,
2. energizes auto-connected emergency loads through load sequencer,
3. achieves steady state voltage:

6800 V and 7260 V,

4. achieves steady state frequency 58.859.8 Hz and 61.260.1 Hz, and
5. supplies permanently connected and auto-connected emergency loads for 5 minutes.

18 months (continued)

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-14 (developmental)

AI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.20 Verify during idle operation that any automatic or emergency start signal disables the idle start circuitry and commands the engine to full speed.

18 months SR 3.8.1.21 Verify when started simultaneously from standby condition, each DG achieves, in 10 seconds, voltage 6800 V and frequency 58.8 Hz. Verify after DG fast start from standby conditions that the DG achieves steady state voltage 6800 V and 7260 V, and frequency 58.859.8 Hz and 61.260.1 Hz.

10 years

AC Sources - Operating 3.8.1 Watts Bar - Unit 2 3.8-15 (developmental)

AI Table 3.8.1-1 (page 1 of 1)

Diesel Generator Test Schedule NUMBER OF FAILURES IN LAST 25 VALID TESTS(a)

FREQUENCY 3

31 days 4

7 days(b)

(but no less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />)

(a) Criteria for determining number of failures and valid tests shall be in accordance with Regulatory Position C.2.1 of Regulatory Guide 1.9, Revision 3, where the number of tests and failures is determined on a per DG basis.

(b) This test frequency shall be maintained until seven consecutive failure free starts from standby conditions and load and run tests have been performed. If, subsequent to the 7 failure free tests, 1 or more additional failures occur, such that there are again 4 or more failures in the last 25 tests, the testing interval shall again be reduced as noted above and maintained until 7 consecutive failure free tests have been performed.

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-21 (developmental)

HI 3.8 ELECTRICAL POWER SYSTEMS 3.8.4 DC Sources - Operating LCO 3.8.4 Four channels of vital DC and four Diesel Generator (DG) DC electrical power subsystems shall be OPERABLE.


NOTES-------------------------------------------

1.

Vital Battery V may be substituted for any of the required vital batteries.

2.

Spare Vital Chargers 6-S, 7-S, 8-S, or 9-S may be substituted for required Vital chargers.

3.

Spare DG Chargers 1A1, 1B1, 2A1, or 2B1 may be substituted for required DG chargers.

APPLICABILITY:

MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required vital DC electrical power subsystem inoperablebattery charger inoperable.

A.1 Restore vital DC electrical power subsystem to OPERABLE statusbattery terminal voltage to greater than or equal to the minimum established float voltage.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> AND A.2 Verify vital battery charger float current

< 2 amps.

Once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND A.3 Restore vital battery charger to OPERABLE status.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-22 (developmental)

HI (continued)

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-23 (developmental)

HI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME B. Required Action and Associated Completion Time of Condition A not metOne required vital battery inoperable.

B.1 AND B.2 Restore vital battery to OPERABLE statusBe in MODE 3.

Be in MODE 5.

2 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> 36 hours C. One DG DC electrical power subsystem inoperable.One required vital DC channel inoperable for reasons other than Condition A or B..

C.1 Restore DG DC electrical power subsystem to OPRABLE statusRestore vital DC channel to OPERABLE status.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> D. Required Action and Associated Completion Time of Condition A, B, or C not met.

D.1 Declare associated DG inoperable.Be in MODE 3.

6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />sImmediately AND D.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> E. One required DG battery charger inoperable.

E.1 Restore DG battery terminal voltage to greater than or equal to the minimum established float voltage.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> AND E.2 Verify DG battery charger float current < 2 amps.

Once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND E.3 Restore DG battery charger to OPERABLE status.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-24 (developmental)

HI F. One required DG battery inoperable.

F.1 Restore DG battery to OPERABLE status.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> (continued)

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-25 (developmental)

H ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME G. One required DG DC electrical power subsystem inoperable for reasons other than Condition E or F.

G.1 Restore DG DC electrical power subsystem to OPERABLE status 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> H. Required Action and associated Completion Time of Condition E, F, or G not met H.1 Declare associated DG inoperable.

Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.4.1 Verify vital battery terminal voltage is 128 V (132 V for vital battery V) on float chargegreater than or equal to the minimum established float voltage.

7 days SR 3.8.4.2 Verify DG battery terminal voltage is 124 V on float chargegreater than or equal to the minimum established float voltage.

7 days SR 3.8.4.3 Verify for the vital batteries that the alternate feeder breakers to each required battery charger are open.

7 days SR 3.8.4.4 Verify correct breaker alignment and indicated power availability for each DG 125 V DC distribution panel and associated battery charger 7 days (continued)

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-26 (developmental)

HI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.4.5 Verify no visible corrosion at terminals and connectors for the vital batterieseach vital battery charger supplies > 200 amps at greater than or equal to the minimum established float voltage for

> 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

OR Verify connection resistance for the vital batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-rack connections, 120 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.

Verify each vital battery charger can recharge the battery to the fully charged state within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> while supplying the largest combined demands of the various continuous steady state loads, after a battery discharge to the bounding design basis event discharge state.

18 months92 days SR 3.8.4.6 Verify no visible corrosion at terminals and connectors for the DG batteries each DG battery charger supplies > 200 amps at greater than or equal to the minimum established float voltage for

> 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

OR Verify connection resistance for the DG batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.

Verify each DG battery charger can recharge the battery to the fully charged state within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> while supplying the largest combined demands of the various continuous steady state loads, after a battery discharge to the bounding design basis event discharge state.

18 months92 days

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-27 (developmental)

HI SR 3.8.4.7


NOTES----------------------------

1. The modified performance discharge test in SR 3.8.4.6 may be performed in lieu of the service test in SR 3.8.4.7 once per 60 months.
2. Credit may be taken for unplanned events that satisfy this SR.

Verify battery cells, cell plates, and racks show no visual indication of physical damage or abnormal deteriorationcapacity is adequate to supply, and maintain in OPERABLE status, the required emergency loads and any connected nonsafety loads for the design duty cycle when subjected to a battery service test.

18 12 months SR 3.8.4.8 Remove visible terminal corrosion and verify battery cell to cell and terminal connections are coated with anti-corrosion material.

12 months SR 3.8.4.9 Verify connection resistance for the vital batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-rack connections, 120 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.

12 months SR 3.8.4.10 Verify connection resistance for the DG batteries is 80 E-6 ohm for inter-cell connections, 50 E-6 ohm for inter-tier connections, and 50 E-6 ohm for terminal connections.

12 months

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-28 (developmental)

HI SR 3.8.4.11


NOTE------------------------------

This Surveillance is normally not performed in MODE 1, 2, 3, or 4. However, credit may be taken for unplanned events that satisfy this SR.

Verify each vital battery charger is capable of recharging its associated battery from a service or capacity discharge test while supplying normal loads.

OR Verify each vital battery charger is capable of operating for 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> at current limit 220 - 250 amps.

18 months SR 3.8.4.12


NOTE------------------------------

Credit may be taken for unplanned events that satisfy this SR.

Verify each diesel generator battery charger is capable of recharging its associated battery from a service or capacity discharge test while supplying normal loads.

18 months SR 3.8.4.13


NOTES----------------------------

1. The modified performance discharge test in SR 3.8.4.14 may be performed in lieu of the service test in SR 3.8.4.13 once per 60 months.
2. This Surveillance is not performed in MODE 1, 2, 3, or 4 for required vital batteries. Credit may be taken for unplanned events that satisfy this SR.

Verify battery capacity is adequate to supply, and maintain in OPERABLE status, the required emergency loads and any connected nonsafety loads for the design duty cycle when subjected to a battery service test.

18 months

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-29 (developmental)

HI (continued)

DC Sources - Operating 3.8.4 Watts Bar - Unit 2 3.8-30 (developmental)

HI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.4.14


NOTE------------------------------

This Surveillance is not performed in MODE 1, 2, 3, or 4 for required vital batteries. Credit may be taken for unplanned events that satisfy this SR.

Verify battery capacity is 80% of the manufacturer's rating when subjected to a performance discharge test or a modified performance discharge test.

60 months AND 12 months when battery shows degradation or has reached 85% of expected life with capacity < 100% of manufacturer's rating AND 24 months when battery has reached 85% of the expected life with capacity 100% of manufacturer's rating

DC Sources - Shutdown 3.8.5 Watts Bar - Unit 2 3.8-25 (developmental)

HI 3.8 ELECTRICAL POWER SYSTEMS 3.8.5 DC Sources - Shutdown LCO 3.8.5 Vital DC and Diesel Generator (DG) DC electrical power subsystems shall be OPERABLE to support the DC electrical power distribution subsystem(s) required by LCO 3.8.10, "Distribution Systems - Shutdown" and to support the Diesel Generators (DGs) required by LCO 3.8.2, "AC Sources - Shutdown."


NOTES------------------------------------------

1. Vital Battery V may be substituted for any of the required vital batteries.
2. Spare vital chargers 6-S, 7-S, 8-S, or 9-S may be substituted for required vital chargers.
3. Spare DG chargers 1A1, 1B1, 2A1, or 2B1 may be substituted for required DG chargers.

APPLICABILITY:

MODES 5 and 6, During movement of irradiated fuel assemblies.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required vital DC electrical power subsystems inoperable.

A.1.1 Declare affected required feature(s) inoperable.

Immediately OR A.2.1 Suspend CORE ALTERATIONS.

Immediately AND (continued)

DC Sources - Shutdown 3.8.5 Watts Bar - Unit 2 3.8-26 (developmental)

H ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME A. (continued)

A.2.2 Suspend movement of irradiated fuel assemblies.

Immediately AND A.2.3 Initiate action to suspend operations involving positive reactivity additions.

Immediately AND A.2.4 Initiate action to restore required vital DC electrical power subsystems to OPERABLE status.

Immediately B. One or more required DG DC electrical power subsystems inoperable.

B.1 Declare associated DG inoperable.

Immediately

DC Sources - Shutdown 3.8.5 Watts Bar - Unit 2 3.8-27 (developmental)

HI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.5.1


NOTE------------------------------

The following SRs are not required to be performed:

SR 3.8.4.511, SR 3.8.4.612, SR 3.8.4.13, and SR 3.8.4.714.

For DC sources required to be OPERABLE, the following SRs are applicable:

SR 3.8.4.1 SR 3.8.4.26 SR 3.8.4.311 SR 3.8.4.42 SR 3.8.4.57 SR 3.8.4.612 SR 3.8.4.73 SR 3.8.4.4 SR 3.8.4.8 SR 3.8.4.9 SR 3.8.4.13 SR 3.8.4.14 SR 3.8.4.5 SR 3.8.4.10 In accordance with applicable SRs

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-28 (developmental)

HI 3.8 ELECTRICAL POWER SYSTEMS 3.8.6 Battery Cell Parameters LCO 3.8.6 Battery cell parameters for 125 V vital batteries and 125 V diesel generator (DG) batteries shall be within the limits of Table 3.8.6-1.

APPLICABILITY:

When associated DC electrical power subsystems and DGs are required to be OPERABLE.

ACTIONS


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each battery bank.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more batteries with one or more battery cell parameters not within Category A or B limitsrequired vital battery with one or more battery cells float voltage < 2.07 V.

A.1 Verify pilot cells electrolyte level and float voltage meet Table 3.8.6-1 Category C limitsPerform SR 3.8.4.1.

2 1 hours1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> AND A.2 Verify battery cell parameters meet Table 3.8.6-1 Category C limitsPerform SR 3.8.6.1.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> AND Once per 7 days thereafter AND A.3 Restore battery cell parameters to Category A and B limits of Table 3.8.6-1Restore affected cell float voltage

> 2.07 V.

31 days24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-29 (developmental)

HI B. Required Action and associated Completion Time of Condition A not metOne required vital battery with float current

> 2 amps.

OR One or more batteries with average electrolyte temperature of the representative cells < 60oF for vital batteries and <

50oF for DG batteries.

OR B. One or more batteries with one or more battery cell parameters not within Category C values.

B.1 Declare associated battery inoperablePerform SR 3.8.4.1.

Immediately2 hours AND B.2 Restore vital battery float current to < 2 amps.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (continued)

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-30 (developmental)

HI ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME C. One required DG battery with one or more battery cells float voltage < 2.07 V.

C.1 Perform SR 3.8.4.2.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> AND C.2 Perform SR 3.8.6.2.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> AND C.3 Restore affected cell float voltage > 2.07 V.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> D. One required DG battery with float current > 1 amp.

D.1 Perform SR 3.8.4.2.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> AND D.2 Restore DG battery float current to < 2 amps.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />


NOTE------------------

Required Action E.2 shall be completed if electrolyte level was below the top of plates.


NOTE--------------------

Required Actions E.1 and E.2 are only applicable if electrolyte level was below the top of plates.

E. One required battery with one or more cells with electrolyte level less than minimum established design limits.

E.1 Restore electrolyte levels to above top of plates.

8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> AND E.2 Verify no evidence of leakage.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> AND E.3 Restore electrolyte level to greater than or equal to minimum established design limits.

31 days (continued)

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-31 (developmental)

H ACTIONS (continued)

CONDITION REQUIRED ACTION COMPLETION TIME F. One required battery with pilot cell electrolyte temperature less than minimum established design limits.

F.1 Restore battery pilot cell temperature to greater than or equal to minimum established design limits.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> G. More than one required vital batteries with battery parameters not within limits.

OR More than one required DG batteries with battery parameters not within limits.

G.1 Restore battery parameters to within limits.

2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> H. Required Action and associated Completion Time of Condition A, B, C, D, E, F, or G not met.

OR One required vital battery with one or more battery cells float voltage < 2.07 V and float current > 2 amps.

OR One required DG battery with one or more battery cells float voltage < 2.07 V and float current > 2 amps.

H.1 Declare associate battery inoperable Immediately

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-32 (developmental)

HI SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.6.1


NOTE-------------------------------

Not required to be met when vital battery terminal voltage is less than the minimum established float voltage of SR 3.8.4.1.

Verify battery cell parameters meet Table 3.8.6-1 Category A limitseach vital battery float current is

< 2 amps.

7 days SR 3.8.6.2


NOTE-------------------------------

Not required to be met when DG battery terminal voltage is less than the minimum established float voltage of SR 3.8.4.2.

Verify battery cell parameters meet Table 3.8.6-1 Category B limitseach DG battery float current is

< 1 amp.

7 92 days AND Once within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a battery discharge < 110 V for vital batteries (113.5 V for vital battery V) or 106.5 V for DG batteries AND Once within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after a battery overcharge > 150 V for vital batteries (155 V for vital battery V) or 145 V for DG batteries SR 3.8.6.3 Verify average electrolyte temperature of representative cells is 60oF for vital batteries and 50oF for the DG batterieseach required vital and DG battery pilot cell float voltage is > 2.07 V.

31 92 days

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-33 (developmental)

HI SR 3.8.6.4 Verify each required vital and DG battery connected cell electrolyte level is greater than or equal to minimum established design limits.

31 days SR 3.8.6.5 Verify each required vital and DG battery pilot cell temperature is greater than or equal to minimum established design limits.

31 days SR 3.8.6.6 Verify each required vital and DG battery connected cell float voltage is > 2.07 V.

92 days (continued)

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-34 (developmental)

HI SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.6.7


NOTE-------------------------------

Credit may be taken for unplanned events that satisfy this SR.

Verify battery capacity is > 80% of the manufacturers rating when subjected to a performance discharge test or a modified performance discharge test.

60 months AND 12 months when battery shows degradation, or has reached 85% of the expected life with capacity < 100% of manufacturers rating AND 24 months when battery has reached 85% of the expected life with capacity

> 100% of manufacturers rating

Battery Cell Parameters 3.8.6 Watts Bar - Unit 2 3.8-35 (developmental)

I Table 3.8.6-1 (page 1 of 1)

Battery Cell Parameters Requirements PARAMETER CATEGORY A:

LIMITS FOR EACH DESIGNATED PILOT CELL CATEGORY B:

LIMITS FOR EACH CONNECTED CELL CATEGORY C:

ALLOWABLE LIMIT FOR EACH CONNECTED CELL Electrolyte Level

> Minimum level indication mark, and 1/4 inch above maximum level indication mark (a)

> Minimum level indication mark, and 1/4 inch above maximum level indication mark (a)

Above top of plates, and not overflowing Float Voltage 2.13 V 2.13 V

> 2.07 V Specific Gravity (b)(c) 1.200 1.195 AND Average of all connected cells

> 1.205 Not more than 0.020 below average of all connected cells AND Average of all connected cells 1.195 (a)

It is acceptable for the electrolyte level to temporarily increase above the specified maximum level during equalizing charges provided it is not overflowing.

(b)

Corrected for electrolyte temperature and level. Level correction is not required, however, when battery charging is < 2 amps when on float charge for vital batteries and < 1.0 amp for DG batteries.

(c)

A battery charging current of < 2 amps when on float charge for vital batteries and < 1.0 amp for DG batteries is acceptable for meeting specific gravity limits following a battery recharge, for a maximum of 31 days. When charging current is used to satisfy specific gravity requirements, specific gravity of each connected cell shall be measured prior to expiration of the 31 day allowance.

Decay Time 3.9.10 Watts Bar - Unit 2 3.9-13 (developmental)

HI 3.9 REFUELING OPERATIONS 3.9.10 Decay Time LCO 3.9.10 The reactor shall be subcritical for > 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br />.

APPLICABILITY:

During movement of irradiated fuel assemblies within the containment.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Reactor subcritical for

< 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br />.

A.1 Suspend all operations involving movement of irradiated fuel assemblies within the containment.

Immediately SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.9.10.1 Verify the reactor has been subcritical for

> 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> by confirming the date and time of subcriticality.

Prior to movement of irradiated fuel in the reactor vessel.

Design Features 4.0 (continued)

Watts Bar - Unit 2 4.0-1 (developmental)

C 4.0 DESIGN FEATURES 4.1 Site 4.1.1 Site and Exclusion Area Boundaries The site and exclusion area boundaries shall be as shown in Figure 4.1-1.

4.1.2 Low Population Zone (LPZ)

The LPZ shall be as shown in Figure 4.1-2 (within the 3-mile circle).

4.2 Reactor Core 4.2.1 Fuel Assemblies The reactor shall contain 193 fuel assemblies. Each assembly shall consist of a matrix of Zirlo fuel rods with an initial composition of natural or slightly enriched uranium dioxide (UO2) as fuel material. Limited substitutions of zirconium alloy or stainless steel filler rods for fuel rods, in accordance with approved applications of fuel rod configurations, may be used. Fuel assemblies shall be limited to those fuel designs that have been analyzed with applicable NRC staff approved codes and methods and shown by tests or analyses to comply with all fuel safety design bases. A limited number of lead test assemblies that have not completed representative testing may be placed in nonlimiting core regions.

4.2.2 Control Rod Assemblies The reactor core shall contain 57 control rod assemblies. The control material shall be silver indium cadmium as approved by the NRC.

Design Features 4.0 4.0 DESIGN FEATURES (continued)

(continued)

Watts Bar - Unit 2 4.0-2 (developmental)

HI 4.3 Fuel Storage 4.3.1 Criticality 4.3.1.1 The spent fuel storage racks (shown in Figure 4.3-1) are designed and shall be maintained with:

a.

Fuel assemblies having a maximum U-235 enrichment of 5.0 weight percent (wt%);

b.

keff < 0.95 if fully flooded with unborated water, which, includes an allowance for uncertainties as described in Sections 4.3.2.7 and 9.1 of the FSAR;

c.

Distances between fuel assemblies are a nominal 10.375 inch center-to-center spacing in the twenty-four flux trap rack modules.

d.

Fuel assemblies with initial enrichments less than a maximum of 5 wt% U-235 enrichment (nominally 4.95 +/- 0.05 wt% U-235) may be stored in the spent fuel racks in any one of four arrangements with specific limits as identified below:

1. Fuel assemblies may be stored in the racks in an all cell arrangement provided the burnup of each assembly is in the acceptable domain identified in Figure 4.3-3, depending upon the specified initial enrichment.
2. New and spent fuel assemblies may be stored in a checkerboard arrangement of 2 new and 2 spent assemblies, provided that each spent fuel assembly has accumulated a minimum burnup in the acceptable domain identified in Figure 4.3-4.
3. New fuel assemblies may be stored in 4-cell arrays with 1 of the 4 cells remaining empty of fuel (i.e. containing only water or water with up to 75 percent by volume of non-fuel bearing material).

Design Features 4.0 4.0 DESIGN FEATURES (continued)

Watts Bar - Unit 2 4.0-3 (developmental)

A 4.3 Fuel Storage (continued)

4. New fuel assemblies with a minimum of 32 integral fuel burnable absorber (IFBA) rods may be stored without further restriction, provided the loading of ZrB2 in the coating of each IFBA rod is minimum of 1.25x (1.9625mg/in).

A water cell is less reactive than any cell containing fuel and therefore a water cell may be used at any location in the loading arrangements.

A water cell is defined as a cell containing water or non-fissile material with no more than 75 percent of the water displaced.

4.3.1.2 The new fuel storage racks are designed and shall be maintained with:

a.

Fuel assemblies having a maximum enrichment of 5.0 weight percent U-235 and shall be maintained with the arrangement of 120 storage locations shown in Figure 4.3-2;

b.

keff 0.95 if fully flooded with unborated water, which includes an allowance for uncertainties as described in Section 9.1 of the FSAR;

c.

keff 0.98 if moderated by aqueous foam, which includes an allowance for uncertainties as described in Section 9.1 of the FSAR; and

d.

A nominal 21-inch center to center distance between fuel assemblies placed in the storage racks.

4.3.2 Drainage The spent fuel storage pool is designed and shall be maintained to prevent inadvertent draining of the pool below Elevation 747 feet - 1 1/2 inches.

4.3.3 Capacity The spent fuel storage pool is designed and shall be maintained with a storage capacity limited to no more than 1386 fuel assemblies in 24 flux trap rack modules.

Design Features 4.0 (continued)

Watts Bar - Unit 2 4.0-4 (developmental)

A FIGURE 4.1-1 (PAGE 1 OF 1)

SITE AND EXCLUSION AREA BOUNDARIES

Design Features 4.0 (continued)

Watts Bar - Unit 2 4.0-5 (developmental)

A FIGURE 4.1-2 (PAGE 1 OF 1)

LOW POPULATION ZONE

Design Features 4.0 (continued)

Watts Bar - Unit 2 4.0-6 (developmental)

A FLUX TRAP RACK, TYPICAL FUEL CASK LOADING PIT FIGURE 4.3-1 SPENT FUEL STORAGE RACKS PLAN SPENT FUEL POOL SOUTH WALL WEST WALL

Design Features 4.0 (continued)

Watts Bar - Unit 2 4.0-7 (developmental)

A FIGURE 4.3-2 NEW FUEL STORAGE RACK LOADING PATTERN

Design Features 4.0 (continued)

Watts Bar - Unit 2 4.0-8 (developmental)

H FIGURE 4.3-3 MINIMUM REQUIRED BURNUP FOR UNRESTRICTED STORAGE OF FUEL OF VARIOUS INITIAL ENRICHMENTS ACCEPTABLE BURNUP DOMAIN UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 Burnup, MWD/kgU ACCEPTABLE BURNUP DOMAIN UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 Burnup, MWD/kgU

Design Features 4.0 Watts Bar - Unit 2 4.0-9 (developmental)

H FIGURE 4.3-4 MINIMUM REQUIRED BURNUP FOR A CHECKERBOARD ARRANGEMENT OF 2 SPENT AND 2 NEW FUEL ASSEMBLIES OF 5 wt% U-235 ENRICHMENT (MAXIMUM)

ACCEPTABLE BURNUP DOMAIN UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 Burnup, MWD/kgU ACCEPTABLE BURNUP DOMAIN UNACCEPTABLE BURNUP DOMAIN Initial Enrichment wt% U-235 Burnup, MWD/kgU

Responsibility 5.1 Watts Bar - Unit 2 5.0-1 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.1 Responsibility 5.1.1 The Site Vice-President shall be responsible for overall activities of the site, while the Plant Manager shall be responsible for overall unit operation. The Site Vice-President and the Plant Manager shall delegate in writing the succession to this responsibility during his absence.

The Plant Manager or his designee shall approve, prior to implementation, each proposed test, experiment or modification to systems or equipment that affect nuclear safety.

5.1.2 The Shift Manager (SM) shall be responsible for the control room command function. During any absence of the SM from the control room while the unit is in MODE 1, 2, 3, or 4, an individual with an active Senior Reactor Operator (SRO) license shall be designated to assume the control room command function.

During any absence of the SM from the control room while the unit is in MODE 5 or 6, an individual with an active SRO license or Reactor Operator license shall be designated to assume the control room command function.

Organization 5.2 (continued)

Watts Bar - Unit 2 5.0-2 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.2 Organization 5.2.1 Onsite and Offsite Organizations Onsite and offsite organizations shall be established for unit operation and corporate management, respectively. The onsite and offsite organizations shall include the positions for activities affecting safety of the nuclear power plant.

a.

Lines of authority, responsibility, and communication shall be defined and established throughout highest management levels, intermediate levels, and all operating organization positions. These relationships shall be documented and updated, as appropriate, in organization charts, functional descriptions of departmental responsibilities and relationships, and job descriptions for key personnel positions, or in equivalent forms of documentation. These requirements shall be documented in the Nuclear Power Organization Topical Report (TVA-NPOD 89-A);

b.

The Plant Manager shall be responsible for overall safe operation of the plant and shall have control over those onsite activities necessary for safe operation and maintenance of the plant;

c.

The Site Vice-President shall have responsibility for overall plant nuclear safety and shall take any measures needed to ensure acceptable performance of the staff in operating, maintaining, and providing technical support to the plant to ensure nuclear safety; and

d.

The individuals who train the operating staff, carry out radiological controls, or perform quality assurance functions may report to the appropriate onsite manager; however, these individuals shall have sufficient organizational freedom to ensure their independence from operating pressures.

Organization 5.2 5.2 Organization (continued)

Watts Bar - Unit 2 5.0-3 (developmental)

B 5.2.2 Unit Staff The unit staff organization shall include the following:

a.

A non-licensed operator shall be assigned to each reactor containing fuel and an additional non-licensed operator shall be assigned for each control room from which a reactor is being operated in MODES 1, 2, 3, or 4.

b.

The shift crew composition may be less than the minimum requirements of 10 CFR 50.54(m)(2)(i) and Specifications 5.2.2.a and 5.2.2.f for a period of time not to exceed 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> in order to accommodate unexpected absences of on-duty shift crew members provided immediate action is taken to restore the shift crew composition to within the minimum requirements.

c.

A radiological controls technician shall be on site when fuel is in the reactor.

The position may be vacant for not more than 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, in order to provide for unexpected absence, provided immediate action is taken to fill the required position.

d.

Deleted

e.

The Operations Superintendent shall have a valid SRO license on this unit.

f.

An individual shall provide advisory technical support to the unit operations shift crew in the areas of thermal hydraulics, reactor engineering, and plant analysis with regard to the safe operation of the unit. This individual shall meet the qualifications specified by the Commission Policy Statement on Engineering Expertise on shift (Generic Letter 86-04 dated 02/13/86).

Unit Staff Qualifications 5.3 Watts Bar - Unit 2 5.0-4 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.3 Unit Staff Qualifications 5.3.1 Each member of the unit staff shall meet or exceed the minimum qualifications for comparable positions, as specified in TVA Nuclear Quality Assurance Plan (TVA-NQA-PLN89-A).

5.3.2 For the purpose of 10 CFR 55.4, a licensed Senior Reactor Operator (SRO) and a licensed Reactor Operator (RO) are those individuals who, in addition to meeting the requirements of TS 5.3.1, perform the functions described in 10 CFR 50.54 (m).

Training 5.4 Watts Bar - Unit 2 5.0-5 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.4 Training (removed from Technical Specifications)

Reviews and Audits 5.5 Watts Bar - Unit 2 5.0-6 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.5 Reviews and Audits (removed from Technical Specifications)

TS Bases Control Program 5.6 Watts Bar - Unit 2 5.0-7 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.6 Technical Specifications (TS) Bases Control Program This Program provides a means for processing changes to the Bases of these Technical Specifications.

5.6.1 Changes to the Bases of the TS shall be made under appropriate administrative controls and reviews.

5.6.2 Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:

a.

A change in the TS incorporated in the license; or

b.

A change to the updated FSAR or Bases that requires NRC approval pursuant to 10 CFR 50.59.

5.6.3 The Bases Control Program shall contain provisions to ensure that the Bases are maintained consistent with the FSAR.

5.6.4 Proposed changes that meet the criteria of Specification 5.6.2 shall be reviewed and approved by the NRC prior to implementation. Changes to the Bases implemented without prior NRC approval shall be provided to the NRC on a frequency consistent with 10 CFR 50.71(e).

Procedures, Programs, and Manuals 5.7 (continued)

Watts Bar - Unit 2 5.0-8 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.7 Procedures, Programs, and Manuals 5.7.1 Procedures 5.7.1.1 Scope Written procedures shall be established, implemented, and maintained covering the following activities:

a.

The applicable procedures recommended in Regulatory Guide 1.33, Revision 2, Appendix A, February 1978;

b.

The emergency operating procedures required to implement the requirements of NUREG-0737 and NUREG-0737, Supplement 1 (Generic Letter 82-33);

c.

Quality assurance for effluent and environmental monitoring;

d.

Fire Protection Program implementation; and

e.

All programs specified in Specification 5.7.2.

5.7.1.2 Review and Approval (removed from Technical Specifications) 5.7.1.3 Temporarily Approved Changes (removed from Technical Specifications)

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar - Unit 2 5.0-9 (developmental)

A 5.7.2 Programs and Manuals The following programs shall be established, implemented, and maintained.

5.7.2.1 (removed from Technical Specifications) 5.7.2.2 (removed from Technical Specifications) 5.7.2.3 Offsite Dose Calculation Manual (ODCM)

a.

The ODCM shall contain the methodology and parameters used in the calculation of offsite doses resulting from radioactive gaseous and liquid effluents, in the calculation of gaseous and liquid effluent monitoring alarm and trip setpoints, and in the conduct of the radiological environmental monitoring program; and

b.

The ODCM shall also contain the radioactive effluent controls and radiological environmental monitoring activities, and descriptions of the information that should be included in the Annual Radiological Environmental Operating and Radioactive Effluent Release Reports required by Specifications 5.9.2 and 5.9.3.

Licensee initiated changes to the ODCM:

a.

Shall be documented and records of reviews performed shall be retained. This documentation shall contain:

1.

sufficient information to support the change(s) together with the appropriate analyses or evaluations justifying the change(s),

2.

a determination that the change(s) maintain the levels of radioactive effluent control required by 10 CFR 20.1302, 40 CFR 190, 10 CFR 50.36a, and 10 CFR 50, Appendix I, and not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations;

b.

Shall become effective after the approval of the Plant Manager; and

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar - Unit 2 5.0-10 (developmental)

A 5.7.2.3 Offsite Dose Calculation Manual (ODCM) (continued)

c.

Shall be submitted to the NRC in the form of a complete, legible copy of the entire ODCM as a part of or concurrent with the Radioactive Effluent Release Report for the period of the report in which any change in the ODCM was made. Each change shall be identified by markings in the margin of the affected pages, clearly indicating the area of the page that was changed, and shall indicate the date (i.e., month and year) the change was implemented.

5.7.2.4 Primary Coolant Sources Outside Containment This program provides controls to minimize leakage from those portions of systems outside containment that could contain highly radioactive fluids during a serious transient or accident to levels as low as practicable. The systems include Containment Spray, Safety Injection, Residual Heat Removal, Chemical and Volume Control, Reactor Coolant System Sampling, and Waste Gas. The program shall include the following:

a.

Preventive maintenance and periodic visual inspection requirements; and

b.

Integrated leak test requirements for each system at least once per 18 months.

The provisions of SR 3.0.2 are applicable.

5.7.2.5 (removed from Technical Specifications) 5.7.2.6 (removed from Technical Specifications)

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar - Unit 2 5.0-11 (developmental)

A 5.7.2.7 Radioactive Effluent Controls Program This program conforms to 10 CFR 50.36a for the control of radioactive effluents and for maintaining the doses to members of the public from radioactive effluents as low as reasonably achievable.

The program shall be contained in the ODCM, shall be implemented by procedures, and shall include remedial actions to be taken whenever the program limits are exceeded. The program shall include the following elements:

a.

Limitations on the functional capability of radioactive liquid and gaseous monitoring instrumentation including surveillance tests and setpoint determination in accordance with the methodology in the ODCM;

b.

Limitations on the concentrations of radioactive material released in liquid effluents to unrestricted areas, conforming to 10 times the concentration values in 10 CFR 20.1001-20.2402, Appendix B, Table 2, Column 2;

c.

Monitoring, sampling, and analysis of radioactive liquid and gaseous effluents in accordance with 10 CFR 20.1302 and with the methodology and parameters in the ODCM;

d.

Limitations on the annual and quarterly doses or dose commitment to a member of the public from radioactive materials in liquid effluents released from each unit to unrestricted areas, conforming to 10 CFR 50, Appendix I;

e.

Determination of cumulative dose contributions from radioactive effluents for the current calendar quarter and current calendar year in accordance with the methodology and parameters in the ODCM at least every 31 days. Determination of projected dose contributions from radioactive effluents in accordance with the methodology in the ODCM at least every 31 days;

f.

Limitations on the functional capability and use of the liquid and gaseous effluent treatment systems to ensure that appropriate portions of these systems are used to reduce releases of radioactivity when the projected doses in a period of 31 days would exceed 2% of the guidelines for the annual dose or dose commitment, conforming to 10 CFR 50, Appendix I;

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar - Unit 2 5.0-12 (developmental)

AI 5.7.2.7 Radioactive Effluent Controls Program (continued)

g.

Limitations on the dose rate resulting from radioactive material released in gaseous effluents from the site to areas at or beyond the site boundary shall be in accordance with the following:

1. For noble gases: a dose rate 500 mrem/yr to the whole body and a dose rate 3000 mrem/yr to the skin, and
2. For idodine-131, idodine-133, tritium, and all radionuclides in particulate form with halfliveshalf lives greater than 8 days: a dose rate 1500 mrem/yr to any organ.
h.

Limitations on the annual and quarterly air doses resulting from noble gases released in gaseous effluents from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I;

i.

Limitations on the annual and quarterly doses to a member of the public from iodine-131, iodine-133, tritium, and all radionuclides in particulate form with half lives > 8 days in gaseous effluents released from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I; and

j.

Limitations on the annual dose or dose commitment to any member of the public, beyond the site boundary, due to releases of radioactivity and to radiation from uranium fuel cycle sources, conforming to 40 CFR 190.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Radioactive Effluent Controls Program surveillance frequency.

5.7.2.8 (removed from Technical Specifications) 5.7.2.9 Component Cyclic or Transient Limit This program provides controls to track the FSAR, Section 5.2.1.5, cyclic and transient occurrences to ensure that components are maintained within the design limits.

5.7.2.10 Reactor Coolant Pump Flywheel Inspection Program This program shall provide for the inspection of each reactor coolant pump flywheel per the recommendations of Regulation Position c.4.b of Regulatory Guide 1.14, Revision 1, August 1975.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar - Unit 2 5.0-13 (developmental)

A 5.7.2.11 Inservice Testing Program This program provides controls for inservice testing of ASME Code Class 1, 2, and 3 components. The program shall include the following:

a.

Testing frequencies applicable to the ASME Code for Operations and Maintenance of Nuclear Power Plants (ASME OM Code) and applicable Addenda as follows:

ASME OM Code and applicable Addenda terminology for inservice testing activities Required Frequencies for performing inservice testing activities Weekly At least once per 7 days Monthly At least once per 31 days Quarterly or every 3 months At least once per 92 days Semiannually or every 6 months At least once per 184 days Every 9 months At least once per 276 days Yearly or annually At least once per 366 days Biennially or every 2 years At least once per 731 days

b.

The provisions of SR 3.0.2 are applicable to the above required Frequencies and other normal and accelerated Frequencies specified as 2 years or less in the Inservice Testing Program for performing inservice testing activities;

c.

The provisions of SR 3.0.3 are applicable to inservice testing activities; and

d.

Nothing in the ASME OM Code shall be construed to supersede the requirements of any TS.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar-Unit 2 5.0-14 (developmental)

GI 5.7.2.12 Steam Generator (SG) Program A Steam Generator Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the Steam Generator Program shall include the following provisions:

a.

Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the "as found" condition of the tubing with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the condition of the tubing during an SG inspection outage, as determined from the inservice inspection results or by other means, prior to the plugging or repair of tubes.

Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged, to confirm that the performance criteria are being met.

b.

Performance criteria for SG tube integrity. SG tube integrity shall be maintained by meeting the performance criteria for tube structural integrity, accident induced leakage, and operational LEAKAGE.

1.

Structural integrity performance criterion: All in-service steam generator tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, hot standby, and cooldown, and all anticipated transients included in the design specification), and design basis accidents. This includes retaining a safety factor of 3.0 against burst under normal steady state full power operation primary-to-secondary pressure differential and a safety factor of 1.4 against burst applied to the design basis accident primary-to-secondary pressure differentials. Apart from the above requirements, additional loading conditions associated with the design basis accidents, or combination of accidents in accordance with the design and licensing basis, shall also be evaluated to determine if the associated loads contribute significantly to burst or collapse. In the assessment of tube integrity, those loads that do significantly affect burst or collapse shall be determined and assessed in combination with the loads due to pressure with a safety factor of 1.2 on the combined primary loads and 1.0 on axial secondary loads.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar-Unit 2 5.0-15 (developmental)

GI 5.7.2.12 Steam Generator (SG) Program (continued)

2.

Accident induced leakage performance criterion: The primary-to-secondary accident induced leakage rate for any design basis accident, other than an SG tube rupture, shall not exceed the leakage rate assumed in the accident analysis in terms of total leakage rate for all SGs and leakage rate for an individual SG. Leakage is not to exceed1 gpm per SG, except for specific types of degradation at specific locations as described in paragraph c.

of the Steam Generator Program.

3.

The operational leakage performance criterion is specified in LCO 3.4.13, "RCS Operational LEAKAGE."

c.

Provisions for SG tube plugging or repair criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged or repaired.

d.

Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube plugging or repair criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of d.1, d.2, and d.3 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. An degradation assessment of degradation shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.

1.

Inspect 100% of the tubes in each SG during the first refueling outage following SG installation.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar-Unit 2 5.0-16 (developmental)

GI 5.7.2.12 Steam Generator (SG) Program (continued)

2.

After the first refueling outage following SG installation, inspect each SG at least every 24 effective full power months or at least every refueling outage (whichever results in more frequent inspections). In addition, inspect 100% of the tubes at sequential periods of 60 effective full power months beginning after the first refueling outage inspection following SG installation. Each 60 effective full power month inspection period may be extended up to 3 effective full power months to include a SG inspection outage in an inspection period and the subsequent inspection period begins at the conclusion of the included SG inspection outage. If a degradation assessment indicates the potential for a type of degradation to occur at a location not previously inspected with a technique capable of detecting this type of degradation at this location and that may satisfy the applicable tube pluggingrepair criteria, the minimum number of locations inspected with such a capable inspection technique during the remainder of the inspection period may be prorated. The fraction of locations to be inspected for this potential type of degradation at this location at the end of the inspection period shall be no less than the ratio of the number of times the SG is scheduled to be inspected in the inspection period after the determination that a new form of degradation could potentially be occurring at this location divided by the total number of times the SG is scheduled to be inspected in the inspection period.

3.

If crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.

e.

Provisions for monitoring operational primary-to-secondary LEAKAGE.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar-Unit 2 5.0-17 (developmental)

AI 5.7.2.13 Secondary Water Chemistry Program This program provides controls for monitoring secondary water chemistry to inhibit SG tube degradation and low pressure turbine disc stress corrosion cracking. The program shall include:

a.

Identification of a sampling schedule for the critical variables and control points for these variables;

b.

Identification of the procedures used to measure the values of the critical variables;

c.

Identification of process sampling points, which shall include monitoring the discharge of the condensate pumps for evidence of condenser in leakage;

d.

Procedures for the recording and management of data; Secondary Water Chemistry Program (continued)

e.

Procedures defining corrective actions for all off control point chemistry conditions; and

f.

A procedure identifying the authority responsible for the interpretation of the data and the sequence and timing of administrative events, which is required to initiate corrective action.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

(continued)

Watts Bar-Unit 2 5.0-18 (developmental)

HI 5.7.2.14 Ventilation Filter Testing Program (VFTP)

A program shall be established to implement the following required testing of Engineered Safety Feature (ESF) filter ventilation systems at the frequencies specified in accordance with Regulatory Guide 1.52, Revision 2; ASME N510-1989, and the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR.

a.

Demonstrate for each of the ESF systems that an inplace test of the high efficiency particulate air (HEPA) filters shows a penetration and system bypass within acceptance criterion when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.

ESF VENTILATION SYSTEM ACCEPTANCE CRITERIA FLOW RATE Emergency Gas Treatment

< 0.05%

4,000 cfm +/-+ 10%

Auxiliary Building Gas Treatment

< 0.05%

9,000 cfm +/-+ 10%

Control Room Emergency

< 1.00%

4,000 cfm +/-+ 10%

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar-Unit 2 5.0-19 (developmental)

HI 5.7.2.14 Ventilation Filter Testing Program (VFTP) (continued)

b.

Demonstrate for each of the ESF systems that an inplace test of the charcoal adsorber shows a penetration and system bypass within acceptance criterion when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.

ESF VENTILATION SYSTEM ACCEPTANCE CRITERIA FLOW RATE Emergency Gas Treatment

< 0.05%

4,000 cfm +/-+ 10%

Auxiliary Building Gas Treatment

< 0.05%

9,000 cfm +/-+ 10%

Control Room Emergency

< 1.00%

4,000 cfm +/-+ 10%

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar-Unit 2 5.0-20 (developmental)

HI 5.7.2.14 Ventilation Filter Testing Program (VFTP) (continued)

c.

Demonstrate for each of the ESF systems that a laboratory test of a sample of the charcoal adsorber, when obtained as described in Regulatory Guide 1.52, Revision 2, and the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, shows the methyl iodide penetration less than the value specified below when tested in accordance with ASTM D3803-1989 at a temperature of 30°C and greater than or equal to the relative humidity specified below.

ESF VENTILATION SYSTEM METHYL IODIDE PENETRATION RELATIVE HUMIDITY Emergency Gas Treatment

< 0.175%

70%

Auxiliary Building Gas Treatment

< 0.175%

70%

Control Room Emergency

< 1.0%

70%

d.

Demonstrate for each of the ESF systems that the pressure drop across the entire filtration unit is less than the value specified below when tested in accordance with Regulatory Guide 1.52, Revision 2, the exceptions noted for each ESF system in Tables 6.5-1, 6.5-2, 6.5-3, and 6.5-4 of the FSAR, and ASME N510-1989 at the system flowrate specified below.

ESF VENTILATION SYSTEM PRESSURE DROP FLOW RATE Emergency Gas Treatment

< 7.6 inches water 4,000 cfm +/-+ 10%

Auxiliary Building Gas Treatment

< 7.6 inches water 9,000 cfm +/-+ 10%

Control Room Emergency

< 3.5 inches water 4,000 cfm +/-+ 10%

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar - Unit 2 5.0-21 (developmental)

AI 5.7.2.14 Ventilation Filter Testing Program (VFTP) (continued)

e.

Demonstrate that the heaters for each of the ESF systems dissipate the value specified below when tested in accordance with ASME N510-1989.

ESF VENTILATION SYSTEM AMOUNT OF HEAT Emergency Gas Treatment 20 +/-+ 2.0 kW Auxiliary Building Gas Treatment 50 +/-+ 5.0 kW The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the VFTP test frequencies.

5.7.2.15 Explosive Gas and Storage Tank Radioactivity Monitoring Program This program provides controls for potentially explosive gas mixtures contained in the Waste Gas Holdup System, the quantity of radioactivity contained in gas storage tanks and the quantity of radioactivity contained in unprotected outdoor liquid storage tanks.

The gaseous radioactivity quantities shall be determined following the methodology in Branch Technical Position (BTP) ETSB 11-5, Postulated Radioactive Release due to Waste Gas System Leak or Failure. The liquid radwaste quantities shall be determined in accordance with Standard Review Plan, Section 15.7.3, Postulated Radioactive Release due to Tank Failures.

The program shall include:

a.

The limits for concentrations of hydrogen and oxygen in the Waste Gas Holdup System and a surveillance program to ensure the limits are maintained. Such limits shall be appropriate to the system's design criteria (i.e., the system is not designed to withstand a hydrogen explosion);

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar-Unit 2 5.0-22 (developmental)

A 5.7.2.15 Explosive Gas and Storage Tank Radioactivity Monitoring Program (continued)

b.

A surveillance program to ensure that the quantity of radioactivity contained in each gas storage tank is less than the amount that would result in a whole body exposure of > 0.5 rem to any individual in an unrestricted area, in the event of an uncontrolled release of the tanks' contents; and

c.

A surveillance program to ensure that the quantity of radioactivity contained in all outdoor liquid radwaste tanks that are not surrounded by liners, dikes, or walls, capable of holding the tanks' contents and that do not have tank overflows and surrounding area drains connected to the Liquid Radwaste Treatment System is less than the amount that would result in concentrations less than the limits of 10 CFR 20.1302(b)(2)(i), at the nearest potable water supply and the nearest surface water supply in an unrestricted area, in the event of an uncontrolled release of the tanks' contents.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program surveillance frequencies.

5.7.2.16 Diesel Fuel Oil Testing Program A diesel fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil shall be established. The program shall include sampling and testing requirements, and acceptance criteria, all in accordance with applicable ASTM Standards. The purpose of the program is to establish the following:

a.

Acceptability of new fuel oil for use prior to addition to the 7 day storage tanks by determining that the fuel oil has:

1.

an API gravity or an absolute specific gravity within limits,

2.

a flash point and kinematics viscosity within limits for ASTM 2D fuel oil, and

3.

a clear and bright appearance with proper color;

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar-Unit 2 5.0-23 (developmental)

A 5.7.2.16 Diesel Fuel Oil Testing Program (continued)

b.

Other properties for ASTM 2D fuel oil are within limits within 31 days following sampling and addition to the 7 day storage tanks; and

c.

Total particulate concentration of the fuel oil in each of the four interconnected tanks which constitute a 7 day storage tank is 10 mg/l when tested every 31 days in accordance with ASTM D-2276, Method A-2 or A-3.

5.7.2.17 (removed from Technical Specifications) 5.7.2.18 Safety Function Determination Program (SFDP)

This program ensures loss of safety function is detected and appropriate actions taken. Upon entry into LCO 3.0.6, an evaluation shall be made to determine if loss of safety function exists.

Additionally, other appropriate actions may be taken as a result of the support system inoperability and corresponding exception to entering supported system Condition and Required Actions. This program implements the requirements of LCO 3.0.6. The SFDP shall contain the following:

a.

Provisions for cross train checks to ensure a loss of the capability to perform the safety function assumed in the accident analysis does not go undetected;

b.

Provisions for ensuring the plant is maintained in a safe condition if a loss of function condition exists;

c.

Provisions to ensure that an inoperable supported system's Completion Time is not inappropriately extended as a result of multiple support system inoperabilities; and

d.

Other appropriate limitations and remedial or compensatory actions.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar-Unit 2 5.0-24 (developmental)

A 5.7.2.18 Safety Function Determination Program (SFDP) (continued)

A loss of safety function exists when, assuming no concurrent single failure, a safety function assumed in the accident analysis cannot be performed. For the purpose of this program, a loss of safety function may exist when a support system is inoperable, and:

a.

A required system redundant to the system(s) supported by the inoperable support system is also inoperable; or

b.

A required system redundant to the system(s) in turn supported by the inoperable supported system is also inoperable; or

c.

A required system redundant to the support system(s) for the supported systems (a) and (b) above is also inoperable.

The SFDP identifies where a loss of safety function exists. If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.

5.7.2.19 Containment Leakage Rate Testing Program A program shall be established to implement the leakage rate testing of the containment as required by 10 CFR 50.54(o) and 10 CFR 50 Appendix J, Option B, as modified by approved exemptions. This program shall be in accordance with the guidelines contained in Regulatory Guide (RG) 1.163, Performance-Based Containment Leak-Test Program, dated September 1995.

The peak calculated containment internal pressure for the design basis loss of coolant accident, Pa, is 15.0 psig.

The maximum allowable containment leakage rate, La, at Pa, is 0.25%

of the primary containment air weight per day.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals Watts Bar-Unit 2 5.0-25 (developmental)

HI 5.7.2.19 Containment Leakage Rate Testing Program (continued)

Leakage rate acceptance criteria are:

a.

Containment overall leakage rate acceptance criterion is 1.0 La.

During the first unit startup following testing in accordance with this program, the leakage rate acceptance criteria are < 0.60 La for the combined Type B and Type C tests, and 0.75 La for Type A tests.

b.

Air lock testing acceptance criteria are:

1. Overall air lock leakage rate is 0.05 La when tested at >

Pa.

2. For each door, leakage rate is 0.01 La when pressurized to 6 psig.

The provisions of SR 3.0.2 do not apply to the test frequencies specified in the Containment Leakage Rate Testing Program.

The provisions of SR 3.0.3 are applicable to the Containment Leakage Rate Testing Program.

5.7.2.20 Control Room Envelope Habitability Program A Control Room Envelope (CRE) Habitability Program shall be established and implemented to ensure that CRE habitability is maintained such that, with an OPERABLE Control Room Emergency Ventilation System (CREVS), CRE occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program shall ensure that adequate radiation protection is provided to permit access and occupancy of the CRE under design basis accident (DBA) conditions without personnel receiving radiation exposures in excess of the applicable regulatory requirement {i.e., 5 rem Total Effective Dose Equivalent (TEDE) for a fuel handling accident or 5 rem whole body or its equivalent to any part of the body} for the duration of the accident. The program shall include the following elements:

a.

The definition of the CRE and the CRE boundary.

b.

Requirements for maintaining the CRE boundary in its design condition including configuration control and preventive maintenance.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals Watts Bar-Unit 2 5.0-26 (developmental)

A 5.7.2.20 Control Room Envelope Habitability Program (continued)

c.

Requirements for (i) determining the unfiltered air inleakage past the CRE boundary into the CRE in accordance with the testing methods and at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, "Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors," Revision 0, May 2003, and (ii) assessing CRE habitability at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, Revision 0.

d.

Measurement, at designated locations, of the CRE pressure relative to all external areas adjacent to the CRE boundary during the pressurization mode of operation by one train of the CREVS, operating at the flow rate defined in the Ventilation Filter Testing Program (VFTP), at a Frequency of 18 months on a STAGGERED TEST BASIS. The results shall be trended and used as part of the 18 month assessment of the CRE boundary.

e.

The quantitative limits on unfiltered air inleakage into the CRE.

These limits shall be stated in a manner to allow direct comparison to the unfiltered air inleakage measured by the testing described in paragraph c. The unfiltered air inleakage limit for radiological challenges is the inleakage flow rate assumed in the licensing basis analyses of DBA consequences.

Unfiltered air inleakage limits for hazardous chemicals must ensure that exposure of CRE occupants to these hazards will be within the assumptions in the licensing basis.

f.

The provisions of SR 3.0.2 are applicable to the frequencies for assessing CRE habitability, determining CRE unfiltered inleakage, and measuring CRE pressure and assessing the CRE boundary as required by paragraphs c and d, respectively.

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar-Unit 2 5.0-27 (developmental)

HI 5.7.2.21 Battery Monitoring and Maintenance Program This Program provides controls for battery restoration and maintenance. The program shall be in accordance with IEEE Standard (Std) 450-2002, "IEEE Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid Batteries for Stationary Applications," as endorsed by Regulatory Guide 1.129, Revision 2 (RG), with RG exceptions and program provisions as identified below:

a. The program allows the following RG 1.129, Revision 2 exceptions:
1. Battery temperature correction may be performed before or after conducting discharge tests.
2. RG 1.129, Regulatory Position 1, Subsection 2, "References,"

is not applicable to this program.

3. In lieu of RG 1.129, Regulatory Position 2, Subsection 5.2, "Inspections," the following shall be used: "Where reference is made to the pilot cell, pilot cell selection shall be based on the lowest voltage cell in the battery.
4. In Regulatory Guide 1.129, Regulatory Position 3, Subsection 5.4.1, "State of Charge Indicator," the following statements in paragraph (d) may be omitted: "When it has been recorded that the charging current has stabilized at the charging voltage for three consecutive hourly measurements, the battery is near full charge. These measurements shall be made after the initially high charging current decreases sharply and the battery voltage rises to approach the charger output voltage."
5. In lieu of RG 1.129, Regulatory Position 7, Subsection 7.6, "Restoration", the following may be used: "Following the test, record the float voltage of each cell of the string."

Procedures, Programs, and Manuals 5.7 5.7 Procedures, Programs, and Manuals (continued)

Watts Bar-Unit 2 5.0-28 (developmental)

HI 5.7.2.21 Battery Monitoring and Maintenance Program (continued)

b. The program shall include the following provisions:
1. Actions to restore battery cells with float voltage < 2.13 V;
2. Actions to determine whether the float voltage of the remaining battery cells is 2.13 V when the float voltage of a battery cell has been found to be < 2.13 V;
3. Actions to equalize and test battery cells that had been discovered with electrolyte level below the top of the plates;
4. Limits on average electrolyte temperature, battery connection resistance, and battery terminal voltage; and
5. A requirement to obtain specific gravity readings of all cells at each discharge test, consistent with manufacturer recommendations.

SFDP 5.8 Watts Bar - Unit 2 5.0-29 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.8 Safety Function Determination Program (SFDP)

(moved to 5.7.2.18)

Reporting Requirements 5.9 (continued)

Watts Bar - Unit 2 5.0-30 (developmental)

H 5.0 ADMINISTRATIVE CONTROLS 5.9 Reporting Requirements The following reports shall be submitted in accordance with 10 CFR 50.4.

5.9.1 DELETED 5.9.2 Annual Radiological Environmental Operating Report


NOTE-------------------------------------------------

A single submittal may be made for a multiple unit station. The submittal should combine sections common to all units at the station.

The Annual Radiological Environmental Operating Report covering the operation of the unit during the previous calendar year shall be submitted by May 15 of each year. The report shall include summaries, interpretations, and analyses of trends of the results of the Radiological Environmental Monitoring Program for the reporting period. The material provided shall be consistent with the objectives outlined in the Offsite Dose Calculation Manual (ODCM), and in 10 CFR 50, Appendix I, Sections IV.B.2, IV.B.3, and IV.C.

The Annual Radiological Environmental Operating Report shall include the results of analyses of all radiological environmental samples and of all environmental radiation measurements taken during the period pursuant to the locations specified in the table and figures in the ODCM, as well as summarized and tabulated results of these analyses and measurements in the format of the table in the Radiological Assessment Branch Technical Position, Revision 1, November 1979. In the event that some individual results are not available for inclusion with the report, the report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted in a supplementary report as soon as possible.

Reporting Requirements 5.9 5.9 Reporting Requirements (continued)

(continued)

Watts Bar - Unit 2 5.0-31 (developmental)

B 5.9.3 Radioactive Effluent Release Report


NOTE-------------------------------------------------

A single submittal may be made for a multiple unit station. The submittal should combine sections common to all units at the station; however, for units with separate radwaste systems, the submittal shall specify the releases of radioactive material from each unit.

The Radioactive Effluent Release Report covering the operation of the unit during the previous year shall be submitted prior to May 1 of each year in accordance with 10 CFR 50.36a. The report shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the unit. The material provided shall be consistent with the objectives outlined in the ODCM and Process Control Program and in conformance with 10 CFR 50.36a and 10 CFR 50, Appendix I, Section IV.B.1.

5.9.4 DELETED 5.9.5 CORE OPERATING LIMITS REPORT (COLR)

a.

Core operating limits shall be established prior to the initial and each reload cycle, or prior to any remaining portion of a cycle, and shall be documented in the COLR for the following:

LCO 3.1.4 Moderator Temperature Coefficient LCO 3.1.6 Shutdown Bank Insertion Limits LCO 3.1.7 Control Bank Insertion Limits LCO 3.2.1 Heat Flux Hot Channel Factor LCO 3.2.2 Nuclear Enthalpy Rise Hot Channel Factor LCO 3.2.3 Axial Flux Difference LCO 3.9.1 Boron Concentration

b.

The analytical methods used to determine the core operating limits shall be those previously reviewed and approved by the NRC, specifically those described in the following documents:

Reporting Requirements 5.9 5.9 Reporting Requirements (continued)

(continued)

Watts Bar-Unit 2 5.0-32 (developmental)

B 5.9.5 CORE OPERATING LIMITS REPORT (COLR) (continued)

1. WCAP-9272-P-A, WESTINGHOUSE RELOAD SAFETY EVALUATION METHODOLOGY, July 1985 (W Proprietary). (Methodology for Specifications 3.1.4 - Moderator Temperature Coefficient, 3.1.6 -

Shutdown Bank Insertion Limit, 3.1.7 - Control Bank Insertion Limits, 3.2.1 - Heat Flux Hot Channel Factor, 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor, 3.2.3 - Axial Flux Difference, and 3.9.1 - Boron Concentration).

2a. WCAP-16009-P-A, Realistic Large-Break LOCA Evaluation Methodology Using the Automated Statistical Treatment of Uncertainty Method (ASTRUM), January 2005 (W Proprietary).(Methodology for Specification 3.2.1 - Heat Flux HotChannel Factor, and 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).

2b. WCAP-10054-P-A, Small Break ECCS Evaluation Model Using NOTRUMP Code, August 1985. Addendum 2, Rev. 1: Addendum to the Westinghouse Small Break ECCS Evaluation Model using the NOTRUMP Code: Safety Injection into the Broken Loop and COSI Condensation Model, July 1997. (W Proprietary). (Methodology for Specifications 3.2.1 - Heat Flux Hot Channel Factor, and 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).

3. WCAP-10216-P-A, Revision 1A, RELAXATION OF CONSTANT AXIAL OFFSET CONTROL F(Q) SURVEILLANCE TECHNICAL SPECIFICATION, February 1994 (W Proprietary). (Methodology for Specifications 3.2.1 - Heat Flux Hot Channel Factor (W(Z) Surveillance Requirements For F(Q) Methodology) and 3.2.3 - Axial Flux Difference (Relaxed Axial Offset Control).)
4. WCAP-12610-P-A, VANTAGE + FUEL ASSEMBLY REFERENCE CORE REPORT, April 1995. (W Proprietary). (Methodology for Specification 3.2.1 - Heat Flux Hot Channel Factor).

Reporting Requirements 5.9 5.9 Reporting Requirements (continued)

(continued)

Watts Bar-Unit 2 5.0-33 (developmental)

A 5.9.5 CORE OPERATING LIMITS REPORT (COLR) (continued)

5. WCAP-15088-P, Rev. 1, Safety Evaluation Supporting A More Negative EOL Moderator Temperature Coefficient Technical Specification for the Watts Bar Nuclear Plant, July 1999, (W Proprietary), as approved by the NRC staffs Safety Evaluation accompanying the issuance of Amendment No. 20 (Methodology for Specification 3.1.4 - Moderator Temperature Coefficient.).
6. WCAP-11397-P-A, Revised Thermal Design Procedure, April 1989.

(Methodology for Specification 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).

7. WCAP-15025-P-A, Modified WRB-2 Correlation, WRB-2M, for Predicting Critical Heat Flux in 17 x 17 Rod Bundles with Modified LPD Mixing Vane Grids, April 1999. (Methodology for Specification 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).
8. WCAP-14565-P-A, VIPRE-01 Modeling and Qualification for Pressurized Water Reactor Non-LOCA Thermal-Hydraulic Safety Analysis, October 1999. (Methodology for Specification 3.2.2 - Nuclear Enthalpy Rise Hot Channel Factor).
c.

The core operating limits shall be determined such that all applicable limits (e.g., fuel thermal mechanical limits, core thermal hydraulic limits, Emergency Core Cooling Systems (ECCS) limits, nuclear limits such as SDM, transient analysis limits, and accident analysis limits) of the safety analysis are met.

d.

The COLR, including any midcycle revisions or supplements, shall be provided upon issuance for each reload cycle to the NRC.

Reporting Requirements 5.9 5.9 Reporting Requirements (continued)

(continued)

Watts Bar-Unit 2 5.0-34 (developmental)

B 5.9.6 Reactor Coolant System (RCS) PRESSURE AND TEMPERATURE LIMITS REPORT (PTLR)

a.

RCS pressure and temperature limits for heatup, cooldown, low temperature operation, criticality, and hydrostatic testing as well as heatup and cooldown rates shall be established and documented in the PTLR for the following:

LCO 3.4.3 RCS Pressure and Temperature (P/T) Limits

b.

The power operated relief valve lift settings required to support the Cold Overpressure Mitigation System (COMS) and the COMS arming temperature shall be established and documented in the PTLR for the following:

LCO 3.4.12 Cold Overpressure Mitigation System

c.

The analytical methods used to determine the RCS pressure and temperature limits and Cold Overpressure Mitigation System setpoints shall be those previously reviewed and approved by the NRC, specifically those described in the following documents:

1.

WCAP-14040-A, Rev. 4 Methodology Used to Develop Cold Overpressure Mitigating System Setpoints and RCS Heatup and Cooldown Limit Curves.

2.

The PTLR will contain the complete identification for each of the TS reference Topical Reports used to prepare the PTLR (i.e., report number, title, revision, date, and any supplements).

d.

The PTLR shall be provided to the NRC upon issuance for each reactor vessel fluence period and for any revision or supplement thereto.

Reporting Requirements 5.9 5.9 Reporting Requirements (continued)

Watts Bar-Unit 2 5.0-35 (developmental)

GI 5.9.7 EDG Failures Report If an individual emergency diesel generator (EDG) experiences four or more valid failures in the last 25 demands, these failures and any nonvalid failures experienced by that EDG in that time period shall be reported within 30 days.

Reports on EDG failures shall include the information recommended in Regulatory Guide 1.9, Revision 3, Regulatory Position C.4, or existing Regulatory Guide 1.108 reporting requirement.

5.9.8 PAMS Report When a Report is required by Condition B or F of LCO 3.3.3, Post Accident Monitoring (PAM) Instrumentation, a report shall be submitted within the following 14 days. The report shall outline the preplanned alternate method of monitoring, the cause of the inoperability, and the plans and schedule for restoring the instrumentation channels of the Function to OPERABLE status.

5.9.9 Steam Generator Tube Inspection Report A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.7.2.12, Steam Generator (SG) Program. The report shall include:

a.

The scope of inspections performed on each SG,

b.

Active dDegradation mechanisms found,

c.

Nondestructive examination techniques utilized for each degradation mechanism,

d.

Location, orientation (if linear), and measured sizes (if available) of service induced indications,

e.

Number of tubes plugged or repaired during the inspection outage for each active degradation mechanism,

f.

The number and percentage of tubes plugged or repaired to date, and the effective plugging percentage in each steam generatorSG,

g.

The results of condition monitoring, including the results of tube pulls and in-situ testing., and h.g. Repair method utilized and the number of tubes repaired by each repair method.

Record Retention 5.10 Watts Bar-Unit 2 5.0-36 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.10 Record Retention (removed from Technical Specifications)

High Radiation Area 5.11 (continued)

Watts Bar-Unit 2 5.0-37 (developmental)

A 5.0 ADMINISTRATIVE CONTROLS 5.11 High Radiation Area As provided in paragraph 20.1601(c) of 10 CFR Part 20, the following controls shall be applied to high radiation areas in place of the controls required by paragraph 20.1601(a) and (b) of 10 CFR Part 20:

5.11.1 High Radiation Areas with Dose Rates Not Exceeding 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation

a.

Each entryway to such an area shall be barricaded and conspicuously posted as a high radiation area. Such barricades may be opened as necessary to permit entry or exit of personnel or equipment.

b.

Access to, and activities in, each such area shall be controlled by means of Radiation Work Permit (RWP) or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.

c.

Individuals qualified in radiation protection procedures and personnel continuously escorted by such individuals may be exempted from the requirement for an RWP or equivalent while performing their assigned duties provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.

d.

Each individual entering such an area shall possess:

1. A radiation monitoring device that continuously displays radiation dose rates in the area; or
2. A radiation monitoring device that continuously integrates the radiation dose rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or
3.

A radiation monitoring device that continuously transmits dose rate and cumulative dose information to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area, or

High Radiation Area 5.11 High Radiation Area (continued)

Watts Bar - Unit 2 5.0-38 (developmental)

A 5.11.1 High Radiation Areas with Dose Rates Not Exceeding 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation (continued)

4. A self-reading dosimeter (e.g., pocket ionization chamber or electronic dosimeter) and, (i) Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii) Be under the surveillance as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with individuals in the area who are covered by such surveillance.
e.

Except for individuals qualified in radiation protection procedures, or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them. These continuously escorted personnel will receive a pre-job briefing prior to entry into such areas. This dose rate determination, knowledge, and pre-job briefing does not require documentation prior to initial entry.

High Radiation Area 5.11 High Radiation Area (continued)

(continued)

Watts Bar - Unit 2 5.0-39 (developmental)

A 5.11.2 High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation, but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation

a.

Each entryway to such an area shall be conspicuously posted as a high radiation area and shall be provided with a locked or, continuously guarded door or gate that prevents unauthorized entry, and, in addition:

1. All such door and gate keys shall be maintained under the administrative control of the Shift Manager, radiation protection manager, or his or her designee.
2. Doors and gates shall remain locked except during periods of personnel or equipment entry or exit.
b.

Access to, and activities in, each such area shall be controlled by means of an RWP or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.

c.

Individuals qualified in radiation protection procedures may be exempted from the requirement for an RWP or equivalent while performing radiation surveys in such areas provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.

d.

Each individual entering such an area shall possess:

1. A radiation monitoring device that continuously integrates the radiation rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or
2.

A radiation monitoring device that continuously transmits dose rate and cumulative dose information to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area with the means to communicate with and control every individual in the area, or

High Radiation Area 5.11 High Radiation Area Watts Bar - Unit 2 5.0-40 (developmental)

B 5.11.2 High Radiation Areas with Dose Rates Greater than 1.0 rem/hour at 30 Centimeters from the Radiation Source or from any Surface Penetrated by the Radiation, but less than 500 rads/hour at 1 Meter from the Radiation Source or from any Surface Penetrated by the Radiation (continued)

3. A self-reading dosimeter (e.g., pocket ionization chamber or electronic dosimeter) and, (i) Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii) Be under the surveillance as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with and control every individual in the area.
4. In those cases where options (2) and (3), above, are impractical or determined to be inconsistent with the "As Low As is Reasonably Achievable" principle, a radiation monitoring device that continuously displays radiation dose rates in the area.
e.

Except for individuals qualified in radiation protection procedures, or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them. These continuously escorted personnel will receive a pre-job briefing prior to entry into such areas. This dose rate determination, knowledge, and pre-job briefing does not require documentation prior to initial entry.

f.

Such individual areas that are within a larger area where no enclosure exists for the purpose of locking and where no enclosure can reasonably be constructed around the individual area need not be controlled by a locked door or gate, nor continuously guarded, but shall be barricaded, conspicuously posted, and a clearly visible flashing light shall be activated at the area as a warning device.