Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000321/LER-1982-020-03, /03L-0:on 820318,oil Leak Found on Reactor Core Isolation Cooling Turbine Outboard Bearing Housing.Caused by Clogged Drain Orifice Inside Bearing Housing.Orifice Cleared + (13:33:36, 18 December 2024)
- 05000321/LER-1982-020, Forwards LER 82-020/03L-0 + (13:33:43, 18 December 2024)
- ML20052A632 + (13:33:44, 18 December 2024)
- 05000338/LER-1982-008-01, /01T-0:on 820329,Westinghouse Determined That Six Output Slave Relays Did Not Have Qualified Latching Mechanisms.Caused by Use of Two Different Types of Latches. Latching Mechanisms Will Be Replaced + (13:33:45, 18 December 2024)
- ML20052A627 + (13:33:50, 18 December 2024)
- 05000338/LER-1982-008, Forwards LER 82-008/01T-0 + (13:33:52, 18 December 2024)
- ML20052A624 + (13:33:53, 18 December 2024)
- ML20052A621 + (13:33:55, 18 December 2024)
- ML20052A620 + (13:33:56, 18 December 2024)
- 05000338/LER-1982-006-03, /03L-0:on 820305,during Mode 1 at 100% Power,A Svc Water Return Header from Units 1 & 2 Charging Pumps & Air Compressors Were Isolated to Repair Pinhole Leak in Return Line.Caused by Aggressive Water Corrosion + (13:33:57, 18 December 2024)
- ML20052A617 + (13:33:58, 18 December 2024)
- 05000321/LER-1982-012-03, /03L-0:on 820211,HPCI Auxiliary Oil Pump Failed to Perform During Procedure HNP-1-3318,HPCI, Hydraulic Oil Piping Moisture Protection. Cause Not Positively Identified.Suspected Components Replaced + (13:34:00, 18 December 2024)
- ML20052A615 + (13:34:01, 18 December 2024)
- ML20052A614 + (13:34:02, 18 December 2024)
- 05000338/LER-1982-006, Forwards LER 82-006/03L-0 + (13:34:03, 18 December 2024)
- 05000321/LER-1982-012, Forwards LER 82-012/03L-0 + (13:34:05, 18 December 2024)
- ML20052A607 + (13:34:06, 18 December 2024)
- ML20052A606 + (13:34:07, 18 December 2024)
- 05000321/LER-1982-016-03, /03L-0:on 820213,while Performing Routine Surveillance,Sample Pump for Fission Product Monitors Found Inoperable.Caused by Blown Fuse.Fuse Replaced & Sys Returned to Svc + (13:34:08, 18 December 2024)
- ML20052A604 + (13:34:09, 18 December 2024)
- 05000321/LER-1982-016, Forwards LER 82-016/03L-0 + (13:34:10, 18 December 2024)
- ML20052A601 + (13:34:11, 18 December 2024)
- ML20052A600 + (13:34:12, 18 December 2024)
- ML20052A599 + (13:34:13, 18 December 2024)
- ML20052A598 + (13:34:14, 18 December 2024)
- 05000325/LER-1982-040-03, /03L-0:on 820319,primary Containment Multipoint Temp Recorder 1-CAC-TR-1258 Printed Erratically.Caused by Fouled Electrical Contacts in Recorder Point Select Relay. Contacts Cleaned + (13:34:15, 18 December 2024)
- ML20052A595 + (13:34:16, 18 December 2024)
- ML20052A593 + (13:34:17, 18 December 2024)
- ML20052A594 + (13:34:17, 18 December 2024)
- ML20052A592 + (13:34:18, 18 December 2024)
- ML20052A591 + (13:34:19, 18 December 2024)
- 05000366/LER-1982-014-03, /03L-0:on 820128,results of Primary Containment Leakage Test on D/W Personnel Airlock Interspace Determined Leak Rate Exceeded Tech Specs.Caused by Damaged Shaft & Seal Assembly on Outer Air Lock Door + (13:34:20, 18 December 2024)
- ML20052A589 + (13:34:25, 18 December 2024)
- ML20052A587 + (13:34:27, 18 December 2024)
- 05000339/LER-1982-016-03, /03L-0:on 820323,lower Main Bearing 14 in Emergency Diesel 2-EE-EG-1J Found Scored.Caused by Lack of Lubrication Due to Disconnected Lubrication Oil Line. Bearing Replaced + (13:34:28, 18 December 2024)
- 05000325/LER-1982-040, Forwards LER 82-040/03L-0 + (13:34:30, 18 December 2024)
- IR 05000395/1982027 + (13:34:31, 18 December 2024)
- 05000366/LER-1982-014, Forwards LER 82-014/03L-0 + (13:34:33, 18 December 2024)
- ML20052A579 + (13:34:36, 18 December 2024)
- 05000324/LER-1982-054-03, /03L-0:on 820314,reactor Low Level Switch 2-B21-LIS-NO17D-1 Actuated at Level Below Reportable Limit. Caused by Instrument Drift.Switch Recalibr & Returned to Svc + (13:34:38, 18 December 2024)
- ML20052A577 + (13:34:39, 18 December 2024)
- ML20052A574 + (13:34:40, 18 December 2024)
- ML20052A575 + (13:34:40, 18 December 2024)
- ML20052A573 + (13:34:41, 18 December 2024)
- 05000324/LER-1982-054, Forwards LER 82-054/03L-0 + (13:34:42, 18 December 2024)
- 05000339/LER-1982-016, Forwards LER 82-016/03L-0 + (13:34:44, 18 December 2024)
- ML20052A568 + (13:34:45, 18 December 2024)
- ML20052A567 + (13:34:46, 18 December 2024)
- PNO-V-82-017A, updating Info Re a & B Auxiliary Feedwater once-through Steam Generator Header Problem.Fiberoptics Exam of B Header Showed Deformation W/Pin in Place.Similar Exam of a Header to Be Performed + (13:34:48, 18 December 2024)
- 05000366/LER-1982-012-03, /03L-0:on 820126,reactor Core Isolation Cooling Turbine Trip & Throttle Valve Would Not Electronically Trip Closed Upon Receipt of Hi Dp Signal.Caused by Oxidized Contacts on Trip Coil Assembly.Contacts Cleaned + (13:34:50, 18 December 2024)
- ML20052A564 + (13:34:51, 18 December 2024)