ML21257A287
Text
CALVERT CLIFFS UFSAR 2.5-1 Rev. 47 2.5 HYDROLOGY 2.
5.1 INTRODUCTION
AND
SUMMARY
This section of the report presents the results of the surface and ground water hydrology phase of the environmental study performed by Dames & Moore. Research for this phase included a review of available pertinent hydrologic literature (References 1 through 5) and interviews with representatives of government agencies and other individuals possessing knowledge of the local area (References 6 through 10).
A study of the hydrologic features of the site and the surrounding area was conducted.
This study included an inventory of water wells, an inspection of surface drainage features, a study of aquifers, measurement of ground water levels in exploratory borings, and an analysis of the depth, direction, and rate of ground water movement.
The site is well drained and not susceptible to flooding. Surface runoff is moderately high and accounts for about 35% of the total annual precipitation. Average annual precipitation in the region ranges from about 40.6" at the Patuxent NATC to about 44" at Prince Frederick. A drainage divide extends across the site in a general north-south direction.
The area east of the divide (20% of the site) drains into the Chesapeake Bay, whereas the area to the west drains into local tributaries and eventually into the Patuxent River. The plant is located east of the divide where surface drainage is toward the Chesapeake Bay.
The plant area is underlain by over 200 of relatively impermeable deposits which effectively confines the underlying artesian aquifers and minimizes their possible contamination by the downward percolation of an accidentally discharged contaminated liquid. The vertical component of ground water movement through the Chesapeake Group is upward. This precludes the possibility of contamination of the aquifers due to downward percolation of a contaminant.
Most of the potable water used in the region is obtained from the artesian aquifers underlying the Chesapeake Group. The aquifers are composed of glauconitic sand and silt of the Piney Point, Nanjemoy, and Aquia formations. The piezometric surfaces of these water-bearing formations slope to the southeast at about 2 per mile. Based upon this hydraulic gradient and coefficients of permeability for these formations, the estimated average rate of natural ground water movement is less than 1" per day.
A limited quantity of potable water is obtained from shallow wells completed in the surficial Pleistocene deposits which overlie the Chesapeake Group throughout most of the area surrounding the site. The areas in which these materials are utilized as a source of water are up-gradient from the plant and cannot be affected by the accidental release of contaminated liquids at or below the ground surface in the plant area.
The possibility of adversely affecting the available ground water resources or existing wells in the area, by the construction and operation of a nuclear facility, is remote. The hydrologic characteristics of the site are favorable for the construction and operation of a nuclear power plant.
2.5.2 SURFACE HYDROLOGY 2.5.2.1 General Calvert County is a peninsula bounded on the east by the Chesapeake Bay and on the west by the Patuxent River. The area is characterized by gently rolling terrain with a dendritic drainage pattern. A drainage divide extends longitudinally across the county. The county is well drained by a relatively large number of streams, although most are less than seven miles long. Many streams have moderately
CALVERT CLIFFS UFSAR 2.5-2 Rev. 47 steep valley walls, while others form estuaries to the Patuxent River. Swampy areas and tidal flats are common along the coastal areas.
Stream flow in Calvert County is measured at two gauging stations maintained by the U.S. Geological Survey. Their locations are shown on Figure 2.5-1, Map of Area Showing Surface Hydrology. The gauge on St. Leonard Creek is a continuous recording station, while the Hellen Creek station is a partial recording site. Average monthly discharges at the continuous recording station are presented in Table 2-31, Average Monthly Discharge at Gauging Station on St. Leonard Creek (1958-1964).
The average runoff measured at the St. Leonard gauge from 1958 to 1964 was 15-1/2"/year. The average annual precipitation for the same period as measured at Prince Frederick, about 10-1/2 miles north of the site, was about 44". Thus, runoff accounts for about 35% of the total precipitation. Evapotranspiration also accounts for a large portion of the annual precipitation. Relatively little precipitation percolates into the surficial materials to recharge the phreatic surface.
The reason for the high runoff and low infiltration probably can be attributed to the impermeable nature of the Miocene subsoils which retard downward percolation of water. The surficial soils are Pleistocene or Recent deposits which are relatively pervious. Rainfall absorbed by them is soon discharged as stream runoff or lost through evapotranspiration. Many lowland areas of the county are not mantled by Pleistocene deposits and the relatively impermeable Miocene deposits are exposed. Precipitation falling on these areas is discharged almost immediately as surface runoff.
2.5.2.2 Site Conditions The topography at the site is gently rolling with steeper slopes along stream courses. Local relief ranges up to about 130. The site is well drained by short, intermittent streams. A drainage divide, which is generally parallel to the coastline, extends across the site as shown on Figure 2.5-1. The area to the east of the divide comprises about 20% of the site and includes the plant area. This area drains into the Chesapeake Bay. The western area is drained by tributaries of Johns Creek and Woodland Branch, which flow into St. Leonard Creek and subsequently into the Patuxent River. Grading performed during construction has not substantially altered the present drainage system.
The average Elevation of the site is about 100 above mean sea level. The site occupies the head-water area of several small drainage basins, and is not subject to flooding. It is possible that high intensity rain storms may cause water to back up in some valleys due to local constrictions in the stream beds, but this would be a temporary situation. The plant area has an Elevation of about +45 and has a storm drain system to handle runoff. High water levels in the bay due to storm conditions are discussed in Section 2.8.3.
Site grading in the vicinity of the Diesel Generator Buildings provides a system of swales that direct overland flow of the probable maximum precipitation runoff without producing drainage or flooding problems for the buildings. The system of swales direct runoff to the Chesapeake Bay without any dependence on the sites storm drain system. The results of the runoff and backwater analyses indicate that during the probable maximum precipitation storm the swale system at the Diesel Generator Building site will convey the surface runoff with a maximum water level of 44.8 above sea level near the Diesel Generator Buildings. This water level is below the floor grade of the Diesel Generator Buildings, which is 45.5 above sea
CALVERT CLIFFS UFSAR 2.5-3 Rev. 47 level, and thus precludes the potential for flooding of the Diesel Generator Buildings during the probable maximum precipitation.
2.5.3 GROUND WATER HYDROLOGY 2.5.3.1 Regional Conditions Ground water occurs in the surficial soils and is tapped by many shallow dug and driven wells. Ground water in deeper aquifers occurs under artesian conditions.
These aquifers, the Piney Point, Nanjemoy, and Aquia formations, are separated from the surficial deposits by an aquiclude averaging about 270 in thickness.
Recharge to these aquifers occurs in their outcrop areas about 15 to 30 miles west of the site. The geologic position of these aquifers relative to other formations in Calvert County is presented in Table 2-32, Geologic Units in Calvert County.
The hydrologic characteristics of the Piney Point, Nanjemoy, and Aquia formations are discussed in greater detail in the following subsections.
2.5.3.1.1 Piney Point Formation The Piney Point formation consists of glauconitic sand interspersed with shell beds and a little clay. Well cuttings and particle-size analyses indicate that the aquifer is composed mainly of medium to fine sand. The formation occurs as a wedge-shaped geologic unit and is known only in Southern Maryland. It is about 30 thick in the vicinity of the site and increases in thickness to the southeast.
The Piney Point formation is widely utilized as a source of ground water in Calvert County and adjoining St. Marys County. It is estimated that more than 500 domestic wells in these two counties tap the Piney Point and the underlying Nanjemoy formations. These two aquifers are hydrologically connected. The yields of domestic wells generally range from about 3 to 20 GPM. At the Patuxent NATC, located about 10 miles south of the site, large-capacity wells tap the Piney Point aquifer and the upper part of the Nanjemoy formation. These wells each yield as much as 190 GPM. The specific capacities of 25 selected wells in these formations range from 0.1 to 3.3, and average 1.2 GPM/ft of drawdown.
2.5.3.1.2 Nanjemoy Formation The lower part of the Nanjemoy formation consists of an impermeable red clay known as the Marlboro Clay. The remainder of the formation consists chiefly of greensand, but contains some clayey greensand. A limited number of particle-size analyses indicate that the sand is predominantly medium-to fine-grained.
The Nanjemoy formation is an important aquifer in Calvert County where it is tapped by several hundred wells. Most wells are completed in the permeable water bearing sands occurring in the uppermost 80 of the formation and yield less than 10 GPM. The specific capacities of 11 wells in Calvert County tapping this aquifer range from 0.2 to 2.4, and average 0.8 GPM/ft of drawdown. On the basis of water level recovery measurements made during a
pumping
- test, a
coefficient of transmissibility of approximately 2,000 GPD/ft has been computed. The field coefficient of permeability was 66 GPD/ft2. The results of a similar test in Prince Georges County indicate coefficients of transmissibility ranging from 260 to 840 GPD/ft.
CALVERT CLIFFS UFSAR 2.5-4 Rev. 47 2.5.3.1.3 Aquia Formation The Aquia formation is characterized by an abundance of glauconitic sand with some quartz sand and clay. The thickness of permeable sandy beds in the formation ranges up to slightly more than 40 in parts of Calvert County. Particle-size analyses of nine samples at the Aquia formation show that the sand is medium-to fine-grained.
The most productive wells tapping this formation are at the Patuxent NATC. Yields of individual wells range from 125 to 350 GPM. The specific capacities of eight of these wells range from 0.8 to 4.2 and average 2.5 GPM/ft of drawdown. The results of six pumping tests indicate field coefficients of permeability ranging from 130 to 1,340 GPD/ft2. Coefficients of transmissibility determined from the tests range from 5,500 to 33,000 GPD/ft2.
Plant wells tap this formation.
2.5.3.1.4 Water Levels The artesian head of the three principal aquifers in Calvert County is generally above sea level. The effect of tidal fluctuations on water levels is noticeable in two observation wells, completed in the Nanjemoy and Piney Point formations, at Solomons Island about 7 miles south of the site. Recorder charts from these wells, which are 248 and 493 deep, respectively, show semi-diurnal fluctuations of about 1/2.
The approximate configurations of the piezometric surfaces of the Aquia and Nanjemoy formations are shown on Figure 2.5-2, Piezometric Surfaces in Calvert County. The regional hydraulic gradient in the vicinity of the proposed plant site is to the southeast. However, local minor variations occur. The cone of depression at the southern end of Calvert County is the result of ground-water extraction at the Patuxent NATC.
Records of observation wells maintained by the U.S. Geological Survey indicate that water levels in the area have remained essentially unchanged since 1963. If the future rate and amount of ground-water extraction in the area is not significantly changed, it is likely that the cone of depression will remain constant and the existing hydraulic gradient in the vicinity of the site will be maintained.
2.5.3.2 Water Use 2.5.3.2.1 General Nearly all potable water used in Calvert County is from subsurface sources. Since little industry is located in this area, the major use of water is for domestic and agricultural purposes.
2.5.3.2.2 Public Water Supplies In 1967, there were 12 towns in Calvert County with public water supplies. The output from these systems is relatively small, but increases substantially in the summer to accommodate the seasonal population increase. Data concerning the public water supplies are presented in Table 2-33, Public Supply Wells in Calvert County. The locations of these supplies are shown on Figure 2.5-3, Public Water Supplies in Calvert County.
CALVERT CLIFFS UFSAR 2.5-5 Rev. 47 2.5.3.2.3 Private Wells Most domestic water supplies in Calvert County are obtained from private wells greater than 300 in depth. In some instances, other wells are less than 50 deep and are of limited capacity. The locations of the deep wells, in the vicinity of the site, are shown on Figure 2.5-4, Map of Area, Showing Known Water Wells. Information pertaining to these wells is presented in Table 2-34, Known Water Wells, Vicinity of Site.
Shallow dug or driven wells are not tabulated or shown on Figure 2.5-4.
The shallow wells will not be affected by changes in the ground water regimen at the site since they are at a higher elevation than the proposed plant grade.
Wells numbered 2 & 10 are located on BG&E property and were previously owned by YMCA. One is in use supplying water to our recreational pool facility for authorized personnel including BGE employees and the Red Cross. The same aquifer supplies water to this well and three others located close to the reactors on the plant site.
Output from the three onsite wells referred to in Section 2.5.3.3 is pumped to two storage tanks from the well water treatment building.
There is no comprehensive source of public information on dug wells in Calvert County. The Calvert County Health Department records and retains dug-well records for only five years. Permits are not required by the Maryland Department of Water Resources nor by the Maryland Department of Health. Several dug wells are listed in Reference 2 and Section 2.5.4.2; however, accurate public information is not available for most of them. It is believed that dug wells in the area are upgradient from the plant site or are across drainage area boundaries.
2.5.3.3 Site Conditions The depth of ground water at the site was measured in piezometers installed in seven of the Dames & Moore exploratory borings. The piezometers consisted of small-diameter steel pipe equipped with a well point, or perforated PVC pipe.
They were installed in borings DM-1, DM-2, DM-3, DM-5, DM-7, DM-8, and DM-9 immediately after completion of the drilling operations. The locations of the borings are shown on Figure 2.4-7, Plot Plan. The water level recorded in each piezometer is shown on the Log of Borings, Figures 2.4-9A through 2.4-9J in Section 2.4, Geology.
An in-situ soil percolation test was performed at the site in Miocene soils typical of those underlying the proposed plant. The test was conducted in a one-foot square hole in accordance with the procedure used for the Corps of Engineers Soil Absorption Test (Reference 5). Results of this test indicate a permeability of less than 1 GPD/ft2. The location of the test is shown on Figure 2.4-7.
Representative samples extracted from the exploratory borings were subjected to a laboratory testing program in order to evaluate the permeability characteristics of the natural soils and the physical properties of the material for correlation purposes. The laboratory program included the following tests:
- a.
moisture and density determinations;
- b.
particle-size analyses;
- c.
permeability tests; and
- d.
cation exchange and X-ray diffraction analyses.
CALVERT CLIFFS UFSAR 2.5-6 Rev. 47 The moisture and density determinations were performed on undisturbed samples for correlation purposes. The results of these determinations are shown on the Log of Borings in Section 2.4, Geology.
Selected soil samples were tested in order to measure their grain-size distribution.
The results of these analyses were used in evaluating soil permeability and for classification purposes. The results are presented on Figures 2.5-5A and 2.5-5B, Particle Size Analyses.
Two permeability tests were performed on materials typical of those underlying the plant. The results of these tests, which were performed in accordance with the American Society for Testing and Materials (ASTM) procedures, are presented in Table 2-35, Laboratory Permeability Tests.
The clay mineral content and the total cation exchange capacity of seven selected soil samples was analyzed. The results of these tests are presented in Table 2-36, Cation Exchange and X-ray Diffraction Analyses.
Data obtained from the geologic exploratory borings indicate that a large portion of the site is mantled by relatively permeable Pleistocene soils. These soils have been eroded from a portion of the site exposing the Chesapeake Group which includes the St. Marys, Choptank, and Calvert formations. The Chesapeake Group consists of about 270 of impervious sandy and clayey silts of Miocene age.
Underlying this material are the Piney Point, Nanjemoy, and Aquia formations of Eocene age.
The Pleistocene deposits consist mainly of silts and sands which have fairly good infiltration characteristics. A few domestic wells in the area obtain water from this material, but are up-gradient from the plant and cannot be affected by a change in the ground water regimen at the site. Grain-size analyses of the surficial soil samples indicate a maximum permeability coefficient of about 400 GPD/ft2. The elevation of the phreatic surface changes with the surface topography and can be expected to fluctuate slightly as a result of climatic changes. The water table occurs generally within 30 of the ground surface. East of the topographic divide, the direction of ground water movement is toward the Chesapeake Bay. The direction of ground water flow west of the divide is toward the existing stream valleys. Piezometers installed in the borings show that the ground water gradient at the site is generally less than 1%. The average rate of ground water flow probably does not exceed a few feet per day.
The underlying impervious sandy and clayey silts of the Chesapeake group extend to about 200 below mean sea level. A percolation test conducted near the plant indicates a permeability of less than 1 GPD/ft2. Particle-size analyses indicate that the permeability of the Chesapeake Group averages about 3 GPD/ft2. The rate of ground water movement is extremely low (much less than 1" per day). The formation is an aquiclude which effectively confines the underlying artesian aquifers. Regional studies by the U.S. Geological Survey have shown that the head in the artesian aquifers is above sea level. The result is vertical upward leakage through the Chesapeake Group. The rate of leakage is extremely low because of the low permeability of the Miocene sediments.
At the site, the combined thickness of the aquifers within the Piney Point and Nanjemoy formations is about 80. They occur at Elevations ranging between 200 and 300 below mean sea level and are separated from the deeper Aquia formation by a layer of clay (Lower Nanjemoy) about 150 thick. The general
CALVERT CLIFFS UFSAR 2.5-7 Rev. 47 direction of ground water movement in the Aquia formation is toward the southeast with a piezometric gradient of about 2 per mile.
Grain-size analyses of samples of the Piney Point formation collected at the site indicate a permeability of about 150 GPD/ft2. This value is probably typical of both the Piney Point and Nanjemoy aquifers. It is estimated that the permeability coefficient of the Aquia formation may be on the order of 1,000 GPD/ft2. The computed rate of flow of ground water through these aquifers ranges from about
.07 to.004 per day. The possibility of accidental contamination of the Eocene aquifers beneath the site is remote because; (a) the aquifers are covered by over 200 of relatively impervious soils and, (b) the vertical component of ground water movement is upward.
Cation exchange and X-ray diffraction analyses were performed on seven samples ranging in depth from 5 to 115 in order to evaluate the cation retention characteristics in the vicinity of the site. The cation exchange capacity of these soils is relatively high and would effectively absorb radioactive cations.
Three wells have been developed for plant use. They extend to a depth of approximately 640 and are each capable of producing 300 GPM from the Aquia formation. Casings for the three plant wells are continuous and sealed with grout to the top of the screens. The effect of pumping these wells will be to create a cone of depression in the Aquia formation such that the direction of groundwater flow will be toward the site rather than away from it. This will further minimize the possibility of lateral migration of any possible release of contaminated liquids beyond the site boundary. For other aquifers, the upward component of groundwater movement and the overlying aquiclude prevent contamination due to downward percolation.
2.
5.4 REFERENCES
- 1.
J.L. Back, 1966, Hydrochemical Facies and Ground Water Flow Patterns in the Northern Part of the Atlantic Coastal Plain, USG Professional Paper 498-4
- 2.
V.K. Bennion, D.F. Dougherty, and R.M. Overback, 1951, Water Resources of Calvert County, Maryland, Geological Survey, Bulletin 8, pp 100
- 3.
E.G. Otton, 1955, Ground Water Resources of the Southern Maryland Coastal Plain, Maryland Geological Survey, Bulletin 15
- 4.
H.E. Vokes, 1956, Geography and Geology of Maryland, Maryland Geological Survey, Bulletin 19
- 5.
U.S. Corps of Engineers, 1959, Sewage Treatment Plants, Engr. Manual 345-243
- 6.
U.S. Geological Survey Water Resources Division; Towson, MD; Mr. James Weigle, Mr. Wayne E. Webb
- 7.
Maryland State Department of Health; Baltimore, MD; Mr. Charles Gross
- 8.
Maryland Department of Geology Mines and Water Resources; Baltimore, MD; Mr. H. Hansen
- 9.
Maryland Division of Water Resources; Annapolis, MD; Dr. Bruce Martin
- 10.
Numerous local residents; Vicinity of Site
CALVERT CLIFFS UFSAR 2.5-8 Rev. 47 TABLE 2-31 AVERAGE MONTHLY DISCHARGE AT GAUGING STATION ON ST. LEONARD CREEK (1958-64)(a)
January 1.74" May 1.35" September 0.48" February 1.92" June 0.88" October 0.56" March 2.46" July 1.00" November 1.23" April 2.04" August 0.83" December 0.99" (a)
Expressed in inches of runoff.
CALVERT CLIFFS UFSAR 2.5-9 Rev. 47 TABLE 2-32 GEOLOGIC UNITS IN CALVERT COUNTY GEOLOGIC UNIT APPROXIMATE RANGE IN THICKNESS (ft)
PHYSICAL CHARACTERISTICS WATER BEARING PROPERTIES Pleistocene surficial deposits 0-150 Silt and sand with some clay gravel Yields small quantities of water to relatively shallow dug or driven wells.
Chesapeake Group:
St. Marys, Choptank, and Calvert Formations30-325 Sandy and clayey silt with inter-bedded sand and fossiliferous layers An aquiclude. Yields small supplies of water to a few dug wells.
Piney Point Formation 0-60 Glauconitic sand Yields up to 200 GPM are reported from drilled wells.
An important aquifer in Calvert County.
Nanjemoy Formation 40-240 Glauconitic sand with clayey layers. Basal part is red or gray clay Yields of individual wells reported up to 60 GPM.
An important aquifer in Calvert County.
Aquia Formation 30-200 Green to brown glauconitic sand Yields up to 300 GPM reported from wells. An important aquifer in Southern Maryland.
Brightseat Formation 0-40 Gray to dark gray micaceous silty and sandy clay Not known to be an aquifer in Southern Maryland.
Monmouth and Matawan Formations20-135 Sandy clay and sand, dark gray to black, with some glauconite Not a major aquifer in Southern Maryland, but yields up to 50 GPM have been reported.
Magothy Formation 0-40 Light-gray to white sand and gravel with interbedded clay layers A few wells reportedly yield up to 1,000 GPM but average yields are considerably less. This aquifer is not used in Calvert County because of its depth.
Raritan Formation 100 Interbedded sand and clay with iron-stone nodules Yields up to a few hundred GPM reported. Not utilized in Calvert County due to depth.
Patapsco Formation 100-650 Interbedded sand, clay, and sandy clay Large-diameter wells yield up to 1,000 GPM. Not used in Calvert County because of depth.
Arundel Clay Formation 25-200 Red, brown, and gray clay Not generally a water-bearing formation.
CALVERT CLIFFS UFSAR 2.5-10 Rev. 47 TABLE 2-32 GEOLOGIC UNITS IN CALVERT COUNTY GEOLOGIC UNIT APPROXIMATE RANGE IN THICKNESS (ft)
PHYSICAL CHARACTERISTICS WATER BEARING PROPERTIES Patuxent Formation 100-450+
Chiefly gray and yellow sand with interbedded clay Yields of several hundred GPM reported. Not used in Calvert County due to great depth.
Precambrian Unknown Gneiss, granite, gabbro, meta-gabbro, quartz diorite, and granitized schist Yields moderate supplies of ground water, generally not more than 50 GPM.
Not used in Calvert County because of its great depth.
CALVERT CLIFFS UFSAR 2.5-11 Rev. 47 TABLE 2-33 PUBLIC SUPPLY WELLS IN CALVERT COUNTY (1967)
TOWN POPULATION SERVED(a)
NUMBER OF CONNECTIONS AVERAGE OUTPUT (mgd)
WELL TOTAL DEPTH (ft)
DIA (in)
Calvert Beach 60 15
.006 1
475 5
Chesapeake Beach 500 155
.05 1(b) 2 3
4(b) 5 400 400 400 400 400 8
8 6
2 2
Chesapeake Ranch Estates 150 1
2 3
400 750 750 4
4 4
Dares Beach 600 175
.05 1(b) 2 217 210 1 1/2 2 1/2 Hunting Hills 30 8
.003 1
4 Kenwood Beach 250 62
.025 1
365 1 1/2 Long Beach 720 180
.07 1
2 3
4 525 500 475 500 3
4 4
4 Prince Frederick 125 35
.02 1
552 8
St. Leonard 60 14
.006 1
550 5
Scientists Cliffs 120 185
.025 1
240 6
Western Shores 1
325 3
White Sands(c) 160 (approx.)
Comm.
40 2
.012
.015 1
2 402 315 6
2 1/2 (a)
Does not include seasonal increases, with the exception of Chesapeake Ranch.
(b)
Not in use.
(c)
Appropriate permits data per Maryland Department Natural Resources ground water.
NOTES:
- 1)
Information based on 1963 data from United States Public Health Service and Maryland Department of Health.
- 2)
Total population of a community is not necessarily served by the public water supply.
CALVERT CLIFFS UFSAR 2.5-12 Rev. 47 TABLE 2-34 KNOWN WATER WELLS, VICINITY OF SITE OWNER WELL NUMBER WELL DEPTH (ft)
WELL DIAMETER (in)
AMOUNT OF CASING (ft)
YIELD (GPM)
K. C. Gerard 1
365 4
280 22 BGE 2
585 6
560 60 Yacht Club 3
315 2 1/2 189 25 H. Krellen 4
285 2
180 15 E. Zinn 5
384 4
237 25 B. Foot 6
399 2 1/2 252 20 H. C. Wilder 7
399 2 1/2 273 20 H. J. Mishou 8
404 2 1/2 277 D. Wood 9
315 2
273 5
BGE 10 540 6
520 10 R. C. Hall 11 274 2 1/2 50 G. D. Wait 12 252 2
3 D. Adams 13 300 2 1/2 William Rekar 14 461 3
E. Bowen 15 525 3
E. Daniels 16 450 W. Jenkin 17 435 140 Knotty Pine Bar & Grill 18 Bay Breeze Camp 19 340 Mrs. Faron 20 Mrs. Moran 21 22 365 2 1/2 Mr. McQueen 23 300 Mr. Street 24 375 P. Andjiano 25 360 Mr. Bancroft 26 Mr. Wohlgenmuth 27 Mrs. Mansfield 28 29 30 31 Information not available.
NOTE:
Well locations are shown on Figure 2.5-4.
CALVERT CLIFFS UFSAR 2.5-13 Rev. 47 TABLE 2-35 LABORATORY PERMEABILITY TESTS BORING DEPTH (ft)
SOIL TYPE DRY DENSITY (lbs/ft3)
COEFFICIENT OF PERMEABILITY (ft/day)
DM-6 45 Sandy silt with shells 93 3.18 DM-8 75 Sandy silt 82 0.86
CALVERT CLIFFS UFSAR 2.5-14 Rev. 47 TABLE 2-36 CATION EXCHANGE AND X-RAY DIFFRACTION ANALYSES BORING DEPTH SOIL TYPE GRADATION IN % FINER(a)
% OF TOTAL CLAY MINERALS(b)
TOTAL CATION EXCHANGE CAPACITY(c)
(ft)
Montmorillonite and Mixed Clay
.074
.048
.005
.002 Illite Minerals Chlorite Test 1 Test 2 (in millimeters)
DM-1 45 Gray Silty Clay 98 44 23 17 30 50 20 23.8 24.5 DM-6 43 1/2 Green Silty Sand 28 25 21 15 40 60 10.0 11.0 DM-6 115 Green Clayey Silt 98 91 44 31 30 50 20 24.3 27.3 DM-8 30 Green Silty Sand 28 25 22 15 35 65 13.8 12.8 DM-8 45 Green Clayey Silt 90 80 45 35 20 60 20 25.0 30.6 DM-9 5
Reddish-Brown Sandy Clay 80 65 38 34 100 10.0 10.3 DM-10 47 Gray Sandy Silt 59 22 16 11 20 80 14.4 10.0 (a)
Soil samples soaked for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in 0.4% hours in 0.4% sodium hexametaphosphate before hydrometer analysis.
(b)
X-ray diffraction analyses of minus 2 micron material.
(c)
Because of the CaCO3 in some of the samples, the ammonium acetate method was used. Total Cation Exchange was determined on the minus 40 micron material.
NOTE: Swell observed in samples DM-1 (45), DM-6 (115), and DM-8 (45).