ML20140G935
| ML20140G935 | |
| Person / Time | |
|---|---|
| Site: | Point Beach |
| Issue date: | 02/14/1997 |
| From: | WISCONSIN ELECTRIC POWER CO. |
| To: | |
| Shared Package | |
| ML20140G761 | List:
|
| References | |
| IT-585, NUDOCS 9705120256 | |
| Download: ML20140G935 (9) | |
Text
_
NUCLEAR POWER BUSINESS UNIT IT 585 l
INSERVICE TESTS MAJOR.
Revision 13
~
LEAKAGE REDUCTION AND PREVENTIVE February 14,1997 MAINTENANCE PROGRAM TEST OF POST-ACCIDENT CONTAINMENT ATMOSPHERIC SAMPLING SYSTEM (REFUELING)
UNIT 2 Date RECORD DSS PROCEDURE VERIFIED CURRENT AND CllECKED FOR TEMPORARY CHANGF3. IF FIELD COPIES REQUIRED, USE PBF@26i IAW NP 1.2.4 AND DO M COMPLETE T11'.S BLOCK BY:
DATE:
1.0 PURPOSE The purpose of this test is to detect and quantify leakage from the post-accident containment atmospheric sampling system as required by Technical Specifications Table 15.4.1-2 (22) and NUREG-0578.
2.0 REFERENCES
2.1 P&lD M-2215, Sheet 2, RE-211&212 2.2 01-58, " Leak Testing of Containment Isolation Valves - Unit I and 2 General Instructions and Information" 2.3 EDS Nuclear, " Post-Accident Containment Atmospheric Sampling System Leakage Test," dated 12-80 2.4 EDS Nuclear Report, " Leakage Reduction and Preventive Maintenance Program at PBNP," dated 07-24-80 3.0 PRECAUTIONS AND LIMITATIONS 3.1 Gases leaking from various components of the post-accident containment atmospheric sampling system may be radioactive and appropriate health physics practices should be -
observed.
3.2 Do not pressurize the system to a pressure greater than required for the test.
3.3 Figure 1 is an informational drawing only.
INITIALS 4.0 INITIAL CONDITIONS 4.1 2RE-211&212 may be taken OOS for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> to perform this test.
4.2 An RWP is available, if required.
9705120256 970505 Page 1 of 9 CONTINUOUS USE PDR ADOCK 05000301 P
5 NUCLEAR POWER BUSINESS UNIT IT 585 INSERVICE TESTS MAJOR Revision 13 LEAKAGE REDUCTION AND PREVENTIVE February 14,1997
"~
MAINTENANCE PROGRAM TEST OF POST-ACCIDENT CONTAINMENT ATMOSPHERIC SAMPLING SYSTEM (REFUELING)
UNIT 2 INITIALS 4.3 Staging and pretest of Volumetrics test rig.
4.3.1 Station the Volumetrics test rig in an area not subject to draft or cold weather.
4.3.2 Route P-tubing from the test rig to the 2RM-211/212 cubicle at valve 2RM-3200Y but do not connect to 2RM-3200Y.
4.3.3 Install a Swageloc cap at the extreme end of the tubing.
4.3.4 Adjust the pressure regulator of the test rig for a supply pressure of 15 psig and pressurize the test rig and P-tubing.
4.3.5 When a stable test system leak rate is achieved:
Correct any substantial leak paths in the test system. The a.
leakage at the end fitting of the P-tubing should be zero.
- b. Record the as-left baseline test system leak rate on the test data sheet for the 15 psig test.
4.3.6 Adjust Volumetrics test pressure for 4.0j psig in preparation for the low pressure test.
4.4 Permission to Perform Test The conditions required by this test are consistent with required plant conditions including equipment operability. Permission is granted to perform this test.
DSS Time Date 5.0 PROCEDURE 5.1 Place the control switch for 2P-707B, containment forced air blower, to
" PULLOUT."
Page 2 of 9 CONTINUOUS USE
' NUCLEAR POWER BUSINESS UNIT IT 585 INSERVICE TESTS MAJOR 1
Revhion 13 j
J
^
LEAKAGE REDUCTION AND PREVENTIVE February 14,1997
~
MAINTENANCE PROGRAM TEST OF POST-ACCIDENT 3
CONTAINMENT ATMOSPHERIC SAMPLING SYSTEM (REFUELING) i UNIT 2 INITIALS NOTE:
Ifunit is atpower, LCO entrypoint.
5.2 Secure 2P-707A sample pump.
4 5.3 Position the " MODE SELECTOR" on 2C-20 for the containment air sampling system to the " CONTAINMENT" position.
5.4 Align the system per Attachment A.
5.5 Connect the Volumetrics test rig to 2RM-3200Y, septum SA purge test connection.
- CAUTION
- THE TEST PRESSURE OF 65 PSIG PER OI-58 DOE'S NOT APPLY TO THIS TEST. DO NOT EXCEED 5 PSIG TEST PRESSURE, THE DESIGN PRESSURE OF THE i,
MYLAR WINDOW OF 2RE-211&212.
5.6 Open 2RM-3200Y and raise the system pressure to 4.0 psig per 01-58.
5.7 When a stable pressure and leak rate condition is achieved, record data on the test data sheet.
i 5.8 When the 4 psig test is complete, position the " MODE SELECTOR" on 2C-20 to the " SEPTUM" position.
5.9 Shut the following valves:
1 2RM-1,2P-707A bypass regulator inlet isolation 2RM-3200K,2RE-211&212 inlet manual isolation 4
i 5.10 Slowly unscrew the glass bowl of the 2RE-211/212 bypass line filter to vent 2RE-211/212 to atmosphere. When 2RE-211/212 is depressurized, i
then remove the bowl to protect 2RE-211/212 from an overpressure condition in the subsequent test.
t 4
Page 3 of 9 CONTINUOUS USE
l NUCLEAR POWER BUSINESS UNIT IT 585 l
. INSERVICE TESTS MAJOR i
l Revision 13 LEAKAGE REDUCTION AND PREVENTIVE February 14,1997 MAINTENANCE PROGRAM TEST OF POST-ACCIDENT CONTAINMENT ATMOSPHERIC SAMPLING SYSTEM (REFUELING)
UNIT 2 1
(
INITIALS 5.11 Using the Volumetrics test rig, raise system pressure to 15 j psig per OI-58.
5.12 When a stable pressure and leak rate condition is achieved:
i i
5.12.1 Check with Snoop and correct any leakage to atmosphere at mechanicaljoints, fittings, valve bonnet and packing gland, etc.
within the test volume.
5.12.2 Record data on the test data sheet.
5.13 If the corrected leak rate, as determined by subtracting the baseline leakage of Step 4.3.5.b, is >10 scem, then locate the source of the leakage by systematically isolating portions of the system using l
valves 2RM-3200W,3200Z,3200J,3200L,3200JJ and 3200LL. Record
)
trouble shooting results in the Remarks section of the test data sheet.
l 5.14 When the test is complete, then shut 2RM-3200Y and disconnect the Volumetrics test rig.
l 5.15 Verify open,2RM-3200J, JJ, LL, L, W and Z, then depressurize the test volume by opening 2RM-3200A.
5.16 When the system is depressurized:
5.16.1
. Screw on firmly the glass bowl of the 2RE-211/212 bypass line filter assembly.
i 5.16.2 Shut 2RM-3200JJ and 3200LL.
5.16.3 Open 2RM-1,3200K,3200EE and 3200FF.
5.16.4 Open 2RM-3200B and 3200C.
4 i
Page 4 of 9 CONTINUOUS USE
NUCLEAR POWER BUSINESS UNIT IT 585 INSERVICE TESTS MAJOR Revision 13
~
LEAKAGE REDUCTION AND PREVENTIVE February 14,1997 MAINTENANCE PROGRAM TEST OF POST-ACCIDENT CONTAINMENT ATMOSPHERIC SAMPLING SYSTEM (REFUELING)
UNIT 2 INITIALS 5.16.5 Lock open the following:
l 2RM-3200J Lock No.
/
l 2RM-3200L Lock No.
/
5.16.6 Perform an independent operator verification of the system valve alignment per CL-8A.
5.17 Return the system to the mode of operation determined by the DSS.
NOTE:
Ifunit is atpower, LCO exitpoint.
6.0 ACCEPTANCE CRITERION The leakage criteria of the Leakage Reduction and Preventive Maintenance Program are used to evaluate the leakage from the post-accident atmospheric sampling system. The check against Criterion 1 or Criterion 2 does not apply for this system as it is not located in the auxiliary building. The total post-accident system leakage from all areas of the plant is limited by Criterion 3. Thus, the acceptance of these test results require their evaluation together with the results of the other post-accident system leakage tests.
Page 5 of 9 CONTINUOUS USE
NUCLEAR PbWER BUSINESS UNIT IT 585 INSERVICE TESTS MAJOR Revision 13 LEAKAGE REDUCTION AND PREVENTIVE February 14,1997 MAINTENANCE PROGRAM TEST OF POST-ACCIDENT CONTAINMENT ATMOSPHERIC SAMPLING SYSTEM (REFUELING)
UNIT 2 INITIALS 7.0 ANALYSIS TO BE COMPLETED BY THE OPERATIONS MANAGER OR IIIS REPRESENTATIVE.
7.1 Comparison with allowable ranges of test values and analysis of deviations complete.
7.2 Any requirements for corrective action?
Yes No If yes, give details in the remarks section and MWR No.
7.3 Data analyzed. By Date Remarks:
Page 6 of 9 CONTINUOUS USE x
6
NUCLEAR POWER BUSINESS UNIT IT 585 INSERVICE TESTS MAJOR f
Rrrision 13 LEAKAGE REDUCTION AND PREVENTIVE February 14,1997 MAINTENANCE PROGRAM TEST OF POST-ACCIDENT CONTAINMENT ATMOSPHERIC SAMPLING SYSTEM (REFUELING)
UNIT 2 TEST DATA SHEET 1.0 LOW PRESSURE TEST NOTE:
This leak test data is not compensatedfor test apparatus leakage and is informational only.
Test pressure psig Leak rate seem Test Inst. ID Test Inst. Range scem Time /Date
/
2.0 HIGH PRESSURE TEST. SEPTUM SYSTEM ONLY 2.1 Test apparatus baseline leak rate (Step 4.3.5.b) =
seem 2.2 Test pressure psig Leak rate (total) seem Test Inst. ID Test Inst. Range seem Time /Date
/
2.3 Compensated system leakage = total leak rate (2.2 above) minus test apparatus baseline leak rate (2.1 above).
Compensated system leakage =
=
seem Remarks:
Page 7 of 9 CONTINUOUS USE
NUCLEAR POWER BUSINESS UNIT IT 585 INSERVICE TESTS MAJOR Revision 13
,l" LEAKAGE REDUCTION AND PREVENTIVE February 14,1997 l-MAINTENANCE PROGRAM TEST OF POST-ACCIDENT l
CONTAINMENT ATMOSPHERIC SAMPLING SYSTEM i
(REFUELING) l UNIT 2 l
ATTACHMENT A l
Valve No.
Description Position initials l
2RM-3200A Return to containment..................................... S l
2RM-3200B Sample from containment.....................
..S l
2RM-3200C Sample from containment............................... S
' 2RM-3200EE Purge exhaust sample, manual isolation............... S i
2RM-3200FF Facade sample manual isolation.
...................S l
2RM-3200J Sample septum inlet..
................................O 2RM-3200K RE-211/212 isolati on...............................
.....O 2RM-3200L Sample septum outlet.................................. O i
l 2RM-3200N Forced vent blower inlet.................................... S i
2RM-3200Q Natural vent isolation..............
............S l
2RM-3200R Supply test connection........................... S & Capped 2RM-3200V Return test connection............................. S & Capped 2RM-3200W Purge exhaust stack inlet.............................. O 2RM-3200Y Service air purge..
....................................S 2RM-3200Z Manual retum to containment............................ O 2RM-3200JJ Sample septum inlet series isolation.................... O 2RM-3200LL Sample septum outlet series isolation................... O t
L l
l i
i l
Page 8 of 9 CONTINUOUS USE
.-4
l O
A i
)
i a a 2is h g $ f b$ 0 h m.
h p;
/
'" m > M C
<m H>
3200c-1 32coAA FIGURE 1 - UNIT 2 32=A-1 Q>-(
r-gggm x
8 CONTAINMENT ATMOSPHERE SAMPUNG m
- mZ$
aO O
N RE-211/ RE-21.2 VALVE UNE-UP l
i
%Qc
@ $1 l 22cox 2
'v
- l C
Hm A.= c.
a =. w _ r
_o -
...=ww
- a. _. -+. i..i 2 -........w.
..,,,t
>To my v
7
,,,,,,,g'.
yWq
....3
/
Setvice Air 70~
W b
q Centeinment W 3 M*3 i>C r
f gQ O C f 88 p
i P3200A Z
d -
g 3200Y MJ k
d d
h T
2 320M O C j.
Z K >Z 5
3200L tt1 m qQ
)
Z g
F5 @ '
C M
R w--,.
r20on 32cou.
m4k g
um0 3,.
o E
f
[] N.E.
gy g',g, 3200w TTgH
[O Fl 91 1
34 h
34 3403 y 3'2..
l
~
" m <d o
m Eve 32000 *
{l P707A cn >
M RE k
til 212 01 RE tll / 282 e
9,,,,, p,,p HC m m Fecede
@ w.o.
v2 H
l Fleer 3200FF 3200F L2 _
2 ~<' "> oo o'
ve
@ Forcedw.e s% nip
, { aj00 Q -. g Esh Fahr us m
g m,ca y.
r M, k
kJ k2 1 o
F1 77,
=
?
m0 t
3200X 3200EE 3200E 3200N y,
- r. ese E'sh. Feirer llA t
I g
P7078 Ps 320W g
g 3405
-J
^
Z N.E. ='Normally Energtred d
3401 V
Q N.D..= Normally Deenergized j
7, z
32mo C
[
OC m
i C
m t
m i
f l
!