Information Notice 2007-07, Potential Failure of All Control Rod Groups to Insert in a Boiling Water Reactor (BWR) Due to a Fire

From kanterella
(Redirected from Information Notice 2007-07)
Jump to navigation Jump to search
Potential Failure of All Control Rod Groups to Insert in a Boiling Water Reactor (BWR) Due to a Fire
ML063540138
Person / Time
Issue date: 02/15/2007
From: Michael Case
NRC/NRR/ADRA/DPR
To:
References
IN-07-007
Download: ML063540138 (5)


UNITED STATES

NUCLEAR REGULATORY COMMISSION

OFFICE OF NUCLEAR REACTOR REGULATION

WASHINGTON, D.C. 20555-0001

February 15, 2007

NRC INFORMATION NOTICE 2007-07:

POTENTIAL FAILURE OF ALL CONTROL ROD

GROUPS TO INSERT IN A BOILING WATER

REACTOR DUE TO A FIRE

ADDRESSEES

All holders of operating licenses for boiling water reactors (BWRs), except those who have

permanently ceased operations and have certified that fuel has been permanently removed

from the reactor.

PURPOSE

The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to inform

addressees of an issue discovered at Columbia Generating Station (CGS) regarding the

possibility of fire-induced hot shorts preventing all control rod groups from inserting when

required due to a postulated fire. The NRC expects that recipients will review the information

for applicability to their facilities and consider actions, as appropriate, to avoid similar problems.

However, suggestions contained in this information notice are not NRC requirements; therefore, no specific action or written response is required.

DESCRIPTION OF CIRCUMSTANCES

During an inspection at CGS completed on July 13, 2006, the NRC inspectors identified that

two hot shorts, caused by a postulated fire, could prevent one of the four groups of control rods

from inserting when the operator places the reactor mode selector switch in the SHUTDOWN

position in the control room. The inspection results are summarized in Inspection Report 05000397/200608, dated August 18, 2006 (Agencywide Documents Access Management

System, Accession No. ML062300334).

The reactor protection and control rod drive systems are identified as part of the minimum safe

shutdown systems necessary to accomplish the reactivity control shutdown function and are

credited in the post-fire safe shutdown procedures developed by this licensee. However, the

potential for fire to cause a loss of this required shutdown function has not been evaluated. The

Final Safety Analysis Report states Fail safe circuits (electrical divisions 4, 5, 6, and 7) are

designed to fail in a safe manner if subjected to fire damage. For example, reactor

scram, once initiated, cannot be overridden as a consequence of fire. The licensees analysis

was based on the assumption that the operator would initiate and confirm shutdown before

control circuiting is damaged; therefore, evaluation of the effects of fire damage to the reactor

protection (RPS) and control rod drive systems was not performed.

Fires can potentially damage circuits prior to the decision to initiate a plant shutdown using

alternative shutdown capability and control room evacuation. At CGS, a reactor shutdown

would not be initiated unless:

  • there are indications that the fire threatens safe operation of the plant,
  • the operator observes degraded equipment performance, or
  • there is visible damage to vital plant equipment or cabling.

Since a reactor scram would possibly not be initiated until the fire had damaged vital plant

equipment, the NRC staff noted the possibility that hot shorts could occur prior to making the

decision to scram the unit.

At CGS, the licensee revised plant procedures to ensure that the RPS would be de-energized

prior to initiating depressurization. This action would ensure that all control rods insert into the

reactor prior to opening the safety/relief valves (SRVs) and starting low pressure injection. Due

to various power supplies that may be in the cabinet, the response by CGS may not be effective

for other BWR designs.

BACKGROUND

Title 10 of the Code of Federal Regulations (CFR) Part 50.48(a) requires that each operating

nuclear power plant has a fire protection plan that satisfies General Design Criterion (GDC) 3 of

Appendix A of Part 50. Criterion 3 specifies that Structures, systems, and components

important to safety shall be designed and located to minimize, consistent with other safety

requirements, the probability and effect of fires and explosions.

Part 58.48(b) of Title 10 of the Code of Federal Regulations identifies some methods to comply

with 10 CFR 50.48(a) and imposes a backfit requirement for plants licensed to operate prior to

January 1, 1979, to comply with section III.G of Appendix R. For plants licensed to operate

after January 1, 1979, similar requirements were incorporated into NUREG-0800, Standard

Review Plan, Section 9-5.1, Fire Protection Program, and were incorporated into the licensee

programs during the licensing process for these plants. These licensees then had planned

implementation as a condition of the Operating License for the facility. To satisfy GDC 3, each

licensee must have fire protection features that are capable of limiting fire damage so that:

a. One train of systems necessary to achieve and maintain hot shutdown conditions from either

the control room or emergency control station(s) is free of fire damage; and

b. Systems necessary to achieve and maintain cold shutdown from either the control room or

emergency control station(s) can be repaired within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

DISCUSSION

The control rods are divided into four control rod groups. The scram of each control rod group

is controlled by separate circuits within the RPS system. The system design has two trip logic

channels functioning in a 1-out-of-2 twice arrangement. This design requires that one trip logic

be satisfied in both trip logic channels before the control rod group will scram. The RPS circuits

are a fail-safe design in that the circuits are normally energized, and the loss of power will

initiate a scram. Also, the RPS scram circuits are routed separately from other circuits to

prevent any possibility for interaction.

For CGS, in all fires other than a control room fire, the circuits will be de-energized when the

mode switch in the control room is placed in the SHUTDOWN position and circuit damage does

not prevent the scram. For fires in the control room, a hot short between conductors to the

mode switch could keep the associated trip channel logic energized. Two hot shorts without the

occurrence of an open circuit or short to ground have the potential of affecting the scram

function. A hot short as described above would have to be present in both of the trip channel

logic circuits associated with the same trip channel. This would keep the trip channel energized

so that half of the 1-out-of-2 twice logic would not be satisfied. The result would be that the

associated rod group would not scram. The other three rod groups would not be affected and

would scram as expected.

CGS is a BWR-5 design. This plant design has the Power Generation Control Complex which

provides cable separation in the control room subflooring when the wires exit the control

cabinets. In part, due to this cable separation, the NRC determined this issue at CGS to be of

very low safety significance.

To accomplish alternative safe shutdown, for a fire in the control room, most BWRs rely upon

using three to six SRVs to depressurize the reactor vessel. The vessel is then reflooded with a

low pressure coolant injection system using a residual heat removal pump in the low pressure

coolant injection mode. By design, the negative reactivity, added by all four rod groups during a

scram, provides adequate shutdown margin to offset the positive void and temperature

reactivity would have been added to the vessel. A typical BWR reactor has about 180 control

rods. One of the four rod groups remaining in the fully out position would place the reactor

outside of the design basis.

RELEVANT GENERIC COMMUNICATIONS

Regulatory Issue Summary 2004-03, Revision 1, Risk-Informed Approach for Post-Fire

Safe-Shutdown Circuit Inspections discusses the probability of two hot shorts occurring for a

postulated fire.

CONTACT

S

This information notice requires no specific action or written response. Please direct any

questions about this matter to the technical contacts listed below or the appropriate Office of

Nuclear Reactor Regulation (NRR) project manager.

/RA/

Michael Case, Director

Division of Policy and Rulemaking

Office of Nuclear Reactor Regulation

Technical Contacts: John M. Mateychick, R IV

Edward McCann, NRR

817-276-6560

301-415-1218 E-mail: JMM3@nrc.gov

E-mail: EVM@nrc.gov

Phillip M. Qualls, NRR

301-415-1849 E-mail: PMQ@nrc.gov

ML063540138 RIV/SRI

AFPB/FPE

AFPB/FPE

AFPB/BC

TECH EDITOR

PGCB/PM

PGCB/LA

PGCB/BC

DPR/DD

JMateychick

PQualls

EMcCann

SWeerakkody

CClark

QNguyen

CHawes -

CMH

CJackson

MCase

12/20/06

2/05/2007

2/02/2007

2/08/2007

02/12/2007

2/01/2007

2/14/2007

02/15/2007

02/15/2007