Information Notice 2005-01, Halon Fire Extinguishing System Piping Incorrectly Connected

From kanterella
Jump to navigation Jump to search
Halon Fire Extinguishing System Piping Incorrectly Connected
ML050350091
Person / Time
Issue date: 02/04/2005
From: Hiland P
NRC/NRR/DIPM/IROB
To:
John Kramer, NRR, 301-415-1173
References
IN-05-001
Download: ML050350091 (4)


UNITED STATES

NUCLEAR REGULATORY COMMISSION

OFFICE OF NUCLEAR REACTOR REGULATION

WASHINGTON, D.C. 20555-0001

February 4, 2005

NRC INFORMATION NOTICE 2005-01:

HALON FIRE-EXTINGUISHING SYSTEM PIPING

INCORRECTLY CONNECTED

ADDRESSEES

All holders of operating licenses for nuclear reactors (except those who have permanently

ceased operations and have certified that fuel has been permanently removed from the reactor

vessel), research and test reactors, and fuel cycle facilities.

PURPOSE

The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to inform

addressees of the potential generic issue of incorrectly connected piping in the halon

fire-extinguishing systems. It is expected that recipients will review the information for

applicability to their facilities and consider actions, as appropriate, to avoid similar problems.

However, suggestions contained in this information notice are not NRC requirements; therefore, no specific action or written response is required.

DESCRIPTION OF CIRCUMSTANCES

On January 12, 2005, the Callaway and Wolf Creek licensees notified the NRC Operations

Center (Event Notification 41326 and 41327) of incorrectly connected piping in the halon

fire-extinguishing systems at both facilities. The piping to the manual-pneumatic actuators in

the halon systems protecting safety-related equipment was found to be reversed. The

licensees implemented compensatory measures until the actuation piping was reconnected in

the proper configuration.

After reviewing the above events and as a result of being questioned by NRC inspectors, the

licensees of other nuclear power reactors checked the condition of the halon systems at their

facilities. Several licensees also found discrepancies in the configuration of the halon systems.

DISCUSSION

The halon fire-extinguishing system is used at many nuclear facilities to protect plant equipment

and rooms from the effects of a fire. Halon extinguishes the fire by interfering with the

combustion chemical reaction. A typical halon system has a bottle or series of bottles to deliver

the appropriate amount of gas to extinguish a fire. During the actuation sequence, the opening

of the manual-pneumatic actuator allows bottle pressure to pressurize the pilot manifold.

Pressurization of the pilot manifold causes the bottle cylinder valve or valves (for multi-bottle

systems) to open and allows the flow of halon into the distribution manifold and into the

protected enclosure.

Typically, each of the manual-pneumatic actuators have ports marked A and B, (see Figure 1).

The ports have specific requirements for connection to the pilot manifold (from port A) and to

the solenoid pilot valve assembly (from port B). In the improper configurations recently

identified, the actuation piping to ports A and B was reversed. Figure 2 is a diagram of a

correctly configured actuator.

Figure 1 - Manual-Pneumatic

Actuator

Figure 2 - Diagram

of Actuator Setup Improper configurations of the halon fire-extinguishing system could have adverse effects on

the system. The Callaway and Wolf Creek licensees contacted the vendor (Chemetron) to

assist in the assessment of the halon system with the piping to the actuator reversed. On

January 26, 2005, an NRC fire protection specialist observed the vendor perform a series of

tests with the actuator piped in both the correct and reversed configuration. With the piping to

the actuator reversed and based on the internal non-symmetric construction of the actuator, there was an approximate 2-second delay in the opening of the cylinder valve. This would

result in a 2-second delay in the delivery of halon gas to the affected equipment.

GENERIC IMPLICATIONS

Based on the above discussion, both carbon dioxide and halon fire-extinguishing systems that

are not properly configured have the potential to impact the extinguishing capability of the

system. Thorough inspection of the systems and adequate postmaintenance testing

procedures can help to ensure that the systems are properly configured.

CONTACT

This information notice requires no specific action or written response. Please direct any

questions about this matter to the technical contact listed below or the appropriate Office of

Nuclear Reactor Regulation (NRR) project manager.

/RA/

Patrick L Hiland, Chief

Reactor Operations Branch

Division of Inspection Program Management

Office of Nuclear Reactor Regulation

Technical Contact:

Daniel Frumkin, NRR

John Kramer, NRR

301-415-2280

301-415-1173 E-mail: dxf1@nrc.gov

E-mail: jgk@nrc.gov

Note: NRC generic communications may be found on the NRC public website, http://www.nrc.gov, under Electronic Reading Room/Document Collections.

ML050350091 DOCUMENT NAME: E:\\Filenet\\ML050350091.wpd

OFFICE

OES:IROB:DIPM

TECH EDITOR

SPSB:DSSA

BC:SPLB:DSSA

D:DSSA

NAME

JGKramer

PKlein

DMFrumkin

JNHannon

SCBlack

DATE

02/02/2005

02/02/2005

02/02/2005

02/03/2005

02/03/2005 OFFICE

RGN-IV

SC:OES:IROB:DIPM

C:IROB:DIPM

NAME

DDChamberlain

TReis

PLHiland

DATE

02/03/2005

02/04/2005

02/04/2005