Finding | |
|---|---|
| Title | Failure to Analyze RHUT Inlet Piping Loads |
| Description | The inspectors identified a finding of very low safety significance (Green) and an associated VIO of 10 CFR Part 50, Appendix B, Criterion III, Design Control, when licensee personnel failed to evaluate the effect of dynamic loads on inlet piping from Unit 1 and Unit 2 residual heat removal (RHR) suction relief valves that discharged to the recycle holdup tank (RHUT). The NRC previously issued two NCVs regarding this issue and corrective actions to date have been incomplete. In addition to entering this issue into their CAP, planned corrective actions included the installation of approximately 20 pipe supports. The inspectors determined that the performance deficiency was more than minor, because it was associated with the Barrier Integrity Cornerstone attribute of Design Control and adversely affected the cornerstone objective of providing reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. Specifically, the licensees existing design and piping configuration had not addressed water hammer effects when the Unit 1 and Unit 2 RHR suction relief valves were aligned to discharge to the RHUT. A ruptured RHUT and/or associated piping outside of containment could adversely affect on-site and offsite dose consequences. An NRC Senior Reactor Analyst (SRA) performed a detailed risk evaluation and determined that the finding was of very low safety significance (i.e., Green). The finding had a cross-cutting aspect in the Resources component of the Human Performance cross-cutting area because leaders at the station did not ensure that personnel, equipment, procedures, and other necessary resources were available and adequate to correct the condition adverse to quality (H.1). |
| Site: | Byron |
|---|---|
| Report | IR 05000454/2015007 Section 4OA2 |
| Date counted | Sep 30, 2015 (2015Q3) |
| Type: | Violation: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | B Palagi C Thompson E Duncan J Benjamin J Draper V Meghani |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
| CCA | H.1, Resources |
| INPO aspect | LA.1 |
| ' | |
Finding - Byron - IR 05000454/2015007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Byron) @ 2015Q3
Self-Identified List (Byron)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||