ML20052C265
| ML20052C265 | |
| Person / Time | |
|---|---|
| Site: | Grand Gulf |
| Issue date: | 02/01/1982 |
| From: | MISSISSIPPI POWER & LIGHT CO. |
| To: | |
| Shared Package | |
| ML20052C255 | List: |
| References | |
| NUDOCS 8205040552 | |
| Download: ML20052C265 (1) | |
Text
1.
c r,-' t -
h7,w[.r.,,,,i. ',,i' u.: U' i CONTAINMENT SYSTEMS gg, CONTAINMENT.AND ORYWELL HYDROGEN IGNITION SYSTEM LIMITING CONDITION FOR OPERATION 3.6.7.2 Two independent containment and drywell hydrogen ignition system subsystems,shall be OPERABLE.
APPLICABILITY:
OPERATIONAL CONDITIONS 1 and 2.
ACTION:
With one containment and drywell-hydrogen ignition subsystem inoperable,. restore the inoperable subsystem to OPERABLE status within 7 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.6.7.2 Each containment and drywell hydrogen ignition subsystem.shall be demonstrated OPERABLE:
At least. Once per 92 days by energizing the supply breakers and a.
verifying that at least 41 glow plugs are energized.
b.
At least once per 18 months by-1.
Verifying the cleanliness of each glow plug by a visual inspection.
2.
Energizing each glow plug and verifying a surface temperature.
of at least 1700 F.
4 t
)
b l
9 8205040552 820430 PDR ADOCK 05000416 A
PDR EEB 1 1982 GRAND GULF-UNIT 1 3/4 6-58
.