1.

c r,-' t -

h7,w[.r.,,,,i. ',,i' u.: U' i CONTAINMENT SYSTEMS gg, CONTAINMENT.AND ORYWELL HYDROGEN IGNITION SYSTEM LIMITING CONDITION FOR OPERATION 3.6.7.2 Two independent containment and drywell hydrogen ignition system subsystems,shall be OPERABLE.

APPLICABILITY:

OPERATIONAL CONDITIONS 1 and 2.

ACTION:

With one containment and drywell-hydrogen ignition subsystem inoperable,. restore the inoperable subsystem to OPERABLE status within 7 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.6.7.2 Each containment and drywell hydrogen ignition subsystem.shall be demonstrated OPERABLE:

At least. Once per 92 days by energizing the supply breakers and a.

verifying that at least 41 glow plugs are energized.

b.

At least once per 18 months by-1.

Verifying the cleanliness of each glow plug by a visual inspection.

2.

Energizing each glow plug and verifying a surface temperature.

of at least 1700 F.

4 t

)

b l

9 8205040552 820430 PDR ADOCK 05000416 A

PDR EEB 1 1982 GRAND GULF-UNIT 1 3/4 6-58

.