ML20211P709

From kanterella
Revision as of 21:22, 5 December 2024 by StriderTol (talk | contribs) (StriderTol Bot change)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

Requests Approval to Utilize ASME Code Case N-253/N253-1, Const of Class 2 or Class 3 Components for Elevated Temp Svc,Section Iii,Div 1, Not Recognized in Latest Rev of Reg Guide 1.84
ML20211P709
Person / Time
Site: Beaver Valley
Issue date: 12/12/1986
From: Carey J
DUQUESNE LIGHT CO.
To: Harold Denton, Tam P
Office of Nuclear Reactor Regulation
References
RTR-REGGD-01.084, RTR-REGGD-1.084 2NRC-6-122, TAC-63976, NUDOCS 8612190125
Download: ML20211P709 (3)


Text

.. -

e

~94 M

2NRC-6-122 Beaver Valley No. 2 Unit Project Organization Telecopy (

2 Ext.160 S.E.G. Buifding P.o. Box 328 Dec. 12, 1986 Shippingport, PA 15077 Mr. Harold R. Denton Office of Nuclear Reactor Regulation United States Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

Mr. Peter Tam, Project Manager Division of PWR Licensing - A Office of Nuclear Reactor Regulation

SUBJECT:

Beaver Valley Power Station - Unit No. 2 Docket No. 50-412 ASME Code Case N-253/N352-1 Gentlemen:

For two applicants at Beaver Valley Power Station Unit No. 2 (BVPS-2), Code Case N253/N253-1 " Construction of Class 2 or Class 3 Components for Elevated Temperature Service,Section III, Div. 1" has been implemented.

It pennits materials to be used under limited conditions at design temperatures which are higher than the normal ASME Section III Code allowables.

The applicable 1971 Edition through the Winter of 1972 Addenda and later editions and addenda of the Code only identify allowable stress values up to 800 F.

BVPS-2 has implemented N253/N253-1 in the design of tN following components:

1)

Thermal Hydrogen Recombiners (Code Case N-253)

_ Item Temperature Material ASME Class Heating Coil 1410 F 316 stainless steel 2

Cooling Coil 1400 F 316 stainless steel 2

Reaction Chamber 1400 F 316 stainless steel 2

2)

Emergency Diesel Generator Exhaust (Code Case N253-1)

Item Temperature Material ASME Class 22" & 38" 00 1000 F Carbon Steel 3

Exhaust Piping Since N253/N253-1 is not recognized in the latest revision of Regulatory Guide 1.84, Duquesne Light Company is hereby requesting approval to utilize it in these limited applications.

Q k2 ] [c{ M gg2

^

i i

United States Nuclear. Regulatory Comission Mr. Harold R. Denton, Director ASME' Code Case N253/N253-1 Page 2 The appropriate FSAR revisions will be included in a future amendment.

Your expeditious review of this request would be greatly appreciated.

DUQUESNE LIGHT COMPANY By

/ y Carey

(/ T SenioY Vice President JJS/ijr NR/ASME/ CASE At ents AR/

~

United States Nuclear Regulatory Commission Mr. Harold R. Denton, Director ASME Code Case N253/N253-1 Page 3 COMMONWEALTH OF PENNSYLVANIA )

)

SS:

COUNTY OF BEAVER

)

On this

/// M day of M4-jf/u/J

/8h, before me, a Notary Public in and for said Commonwealth and County, personally appeared J. J. Carey, who being duly sworn, deposed and said that (1) he is Senior Vice President of Duquesne Light, (2) he is duly authorized to execute and file the foregoing Submittal on behalf of said Company, and (3) the statements set forth in the Submittal are true and correct to the best of his knowledge.

N MW

/

Notary Puilic SHEllA M. FATTCRE NOTAU PUBUC SHIPPINGPORT B0A0. BEAVER COUNIT MY comell55105 EXPlRES OCT. 23,1989 Wmw. twenanh 2nec%tW af am