Duke Duke r REGIS T. REPKO
~
Vice President Energy. McGuire Nuclear Station Duke Energy MGO IVP / 12700 Hagers Ferry Rd.
Huntersville, NC 28078 980-875-4111 980-875-4809 fax regis.repko@duke-energy.com June 28, 2011 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555
Subject:
Duke Energy Carolinas, LLC (Duke)
McGuire Nuclear Station Docket Number 50-370 Inservice Inspection Report Unit 2, End of Cycle 20 Refueling Outage In accordance with ASME Section XI, attached is the Inservice Inspection Report for the end of cycle 20 (EOC-20) refueling outage for McGuire Nuclear Station, Unit 2. This was the third outage of the Second Inspection Period of the Third Ten-Year Interval.
No reportable indications were identified during this report period. Section 4.4 of the report lists one limited examination item number.
Questions regarding this submittal should be directed to Kay L. Crane at (980) 875-4306.
Regis T. Repko Attachment www.duke-energy.conm i t2 Q
U. S. Nuclear Regulatory Commission June 28, 2011 Page 2 xc V. M. McCree Regional Administrator, Region II U.S. Nuclear Regulatory Commission Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, GA 30303-1257 Senior Resident Inspector U.S. Nuclear Regulatory Commission McGuire Nuclear Station J.H. Thompson. (addressee only)
NRC Project Manager U.S. Nuclear Regulatory Commission 11555 Rockville Pike Mail Stop 0-8 G9A Rockville MD 20852-2738 INSERVICE INSPECTION REPORT Duke Energy Carolinas McGuire Nuclear Station Unit 2 Twentieth Refueling Outage Energy8
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules
- 1. Owner: Duke Enerav Carolinas. 526 S. Church St.. Charlotte. NC 28201-1006 (Name and Address of Owner)
- 2. Plant: McGuire Nuclear Station. 12700 Haqer's Ferry Road Huntersville, N.C. 28078 (Name and Address of Plant)
- 3. Plant Unit: 2 4. Owner Certificate of Authorization (if required) N/A
- 5. Commercial Service Date: March 1, 1984 6. National Board Number for Unit 84
- 7. Components Inspected:
Comnp on ent or Manufacturer or M an ufactu rer or State or National A ppu rten an ce Installer Installer Serial Province No. Board N o.
N o.
See Section 1.1 in the Attached Report Note: Supplemental sheets in form of lists, sketches, or drawings may be used provided (1) size is 81/2 in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
Total number of pages contained in this report 188
(
- 9. Examination Dates October 11, 2009 to April 5, 2011
- 9. Inspection Period Identification: Second Period
- 10. Inspection Interval Identification: Third Interval
- 11. Applicable Edition of Section XI 1998 Addenda 2000
- 12. Date / Revision of Inspection Plan: June 20, 2006 / Revision 2
- 13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See Sections 2.0, 3.0 and 6.0
- 14. Abstract of Results of Examinations and Tests. See Section 4.0 and 6.0
- 15. Abstract of Corrective Measures. See Subsection 4.3 We certify that a) the statements made in this report are correct b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date Signed Duke Energy By
,.I . 3 = 7-7 Z o, Carolina's.
Owner IMA9 ,- A.-
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina employed by
- HSBCT have inspected the components described in this Owner's Report during the period October 11, 2009 to April 5, 2011 and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor *s employer shall be liable in any manner for any personal injury or property damage rloss of anýy k rng from or connected with this inspection assions N.C. 1524,-I NdA? 1Z// 7--
/Instor A nature
-ntur National Board, State, Province, and Endorsements Date (0 / 0('0 1 / -
HSBCT 200 Ashford Center North Suite 205 Atlanta, GA. 30338-4860 (800) 417-3721 www.hsbct.com
OWNER'S REPORT FOR INSERVICE INSPECTIONS MCGUIRE UNIT 2 2011 REFUELING OUTAGE EOC 20 (OUTAGE 5)
(Third Interval)
Plant Location: McGuire Nuclear Station 12700 Hager's Ferry Road Huntersville, North Carolina 28078 - 9340 NRC Docket No. 50-370 National Board No. 84 Commercial Service Date: March 1, 1984 Document Completion Date: *-6.'7, 20t(
Owner: Duke Energy Carolinas 526 South Church Street Charlotte, N.C. 28201-1006 Revision 0 Originated By: ODate Checked By: aDate
/30'7-
-o/
Approved By: Date
TABLE OF CONTENTS Section Title Revision 1.0 General Information 0 2.0 Third Ten-Year Interval Inspection Status 0 3.0 Final Inservice Inspection Plan 0 4.0 Results of Inspections Performed 0 5.0 Owner's Report for Repair / Replacement Activities 0 6.0 Pressure Testing 0
1.0 General Information This report describes the Inservice Inspection of Duke Energy Corporation's McGuire Nuclear Station Unit 2 during Outage 5 / EOC 20. This is the third outage of the Second Inspection Period of the Third Ten-Year Interval. ASME Section XI, 1998 Edition with the 2000 Addenda, was the governing Code for selection and performance of the ISI examinations.
Included in this report are the inspection status for each examination category, the final inservice inspection plan, the inspection results for each item examined, and corrective action(s) taken when reportable conditions were found. In addition, there is an Owner's Report for the Repair / Replacement Section included for completed NIS-2 documentation of repairs and replacements.
1.1 Identification Numbers Manufacturer National Manufacturer or Installer State or Board Item or Installer Serial No. Province No. No.
Reactor Vessel Rotterdam 30664 NC-201819 --
Pressurizer Westinghouse 1491 NC-201818 W10285 Steam Generator 2A BWI 7700-02 NC-302674 159 Steam Generator 2B BWI 7700-04 NC-302675 161 Steam Generator 2C BWI 7700-01 NC-302676 158 Steam Generator 2D BWI 7700-03 NC-302677 160 Centrifugal Charging Pump Pacific Pumps 2A - 48584 N/A 25 2B- 48585 28 Containment Spray Heat Delta Southern Co. 2A-35005-73-3 NC-234203 3396 Exchanger Joseph Oat & (2B) 2514 NC-201822 5765 Sons, Inc.
Excess Letdown Heat Westinghouse 1810 NC-234264 1555 Exchanger Letdown Heat Exchanger Joseph Oat & 2049-2B NC-201842 553 Sons, Inc.
Reciprocating Charging Union Pump Co. N7210318-604 N/A N/A Pump EOC 20 Refueling Outage Report Page 1 of 5 McGuire Unit 2 Revision 0 Section 1 June 7, 2011
1.1 Identification Numbers (Continued)
Manufacturer National Manufacturer or Installer State or Board Item or Installer Serial No. Province No. No.
2A 5-114E841G02 Reactor Coolant Pump Westinghouse 2B 6-114E841G02 N/A N/A 2C 7-114E841G02 2D 8-114E841G02 Reciprocating Charging Metal Bellows Company 74730-002 N/A 002 Pump Accumulator Reciprocating Charging Richmond Engineering N-2409.20 N/A 75220 Pump Suction Stabilizer Supply Co.
Residual Heat Joseph Oat & Sons, Inc. 2A 2046-2C NC-169800 637 Removal Heat 2B 2046-2D NC-201823 638 Exchanger Safety Injection Pump Pacific Pumps 2A 49357 N/A 130 2B 49358 131 Regenerative Heat Joseph Oat & Sons, Inc. 2047-2B NC-201817 628 Exchanger 629 630 Seal Water Heat Atlas Industrial 1767 NC 201827 1549 Exchanger Manufacturing Company Seal Water AMF Cuno 2A - 20 N/A 4364 Injection Filter 2B - 22 4365 Main Steam Supply to Duke Power Co. SA N/A 62 Auxiliary Equipment System Containment Air Release Duke Power Co. VQ N/A 56 and Addition System Main Steam System Duke Power Co. SM N/A 70 Main Steam Vent to Duke Power Co. SV N/A 67 Atmosphere System Reactor Coolant System Duke Power Co. NC N/A 82 EOC 20 Refueling Outage Report Page 2 of 5 McGuire Unit 2 Revision 0 Section 1 June 7, 2011
1.1 Identification Numbers (Continued)
Manufacturer Manufacturer or Installer State or National Item or Installer Serial No. Province No. Board No.
Liquid Waste Recycle Duke Power Co. WL N/A 76 System Refueling Water System Duke Power Co. FW N/A 54 Auxiliary Feedwater Duke Power Co. CA N/A 73 System Residual Heat Removal Duke Power Co. ND N/A 63 System Nuclear Service Water Duke Power Co. RN N/A 60 System Chemical & Volume Duke Power Co. NV N/A 80 Control System Component Cooling Duke Power Co. KC N/A 78 System Main Feedwater System Duke Power Co. CF N/A 61 Containment Spray Duke Power Co. NS N/A 69 System Containment Ventilation Duke Power Co. RV N/A 72 Cooling Water System Safety Injection System Duke Power Co. NI N/A 83 Diesel Generator Engine Duke Power Co. KD N/A 47 Cooling Water System Spent Fuel Cooling Duke Power Co. KF N/A 81 System Diesel Generator Engine Duke Power Co. LD N/A 51 Lube Oil System Unit 2 Duke Power Co. N/A N/A 84 EOC 20 Refueling Outage Report Page 3 of 5 McGuire Unit 2 Revision 0 Section 1 June 7, 2011
1.2 Reference Documents The following reference documents apply to the inservice inspections performed during this report period. A copy may be obtained by contacting the ISI Plan Manager at Duke Energy Carolina's Corporate Office in Charlotte, North Carolina:
- 1. Code Case N-460 (Alternative Examination Coverage for Class 1 and Class 2 Welds, Section Xl, Division 1.) Applicable to items in this report where less than 100% coverage of the required weld examination volume was achieved.
- 2. Code Case N-665 (Alternative Requirements for Beam Angle Measurements using Refracted Longitudinal Wave Search Units.)
- 3. Code Case N-700 (Alternative Rules for Selection of Classes 1, 2 and 3 Vessel Welded Attachments for Examination Section Xl, Division 1) (Categories B-K, CC and D-A)
- 4. Code Case N-706 (Applicable to Category C-A Residual Heat Removal Heat Exchangers 2A and 2B and the Regenerative Heat Exchanger.)
- 5. Problem Investigation Process (PIP) M-1 1-04257 (Covers documentation and tracking and completion of request for relief on weld limitations for EOC 20.) See Section 4.4 for list of limited exams.
- 6. RFR 03-002 (Class 1, 2 and 3 snubber examination under station technical specification SLC 16.9.15.)
- 7. RFR 01-005 (Risk Informed Inservice Inspection Program Submittal.)
- 8. RFR 01-008 (Risk Informed ISI Alternative to Use VT-2 Instead of Volumetric Examination of Socket Welds.)
- 9. Code Case N-722 (Additional Examinations for Pressure Retaining Welds in Class 1 Components Fabricated with Alloy 600 / 82 / 182 Materials, Section Xl, Division 1, 10 CFR Part 50, Federal Register, final rule was issued September 10, 2008 mandates the use of this code case.) (Effective date is October 10, 2008.)
- 10. Code Case N-685 (Lighting Requirements for Surface Examinations, Section Xl, Division 1.)
- 11. Code Case N-729-1 (Alternative Examination Requirements for PWR Reactor Vessel Upper Heads with Nozzles Having Pressure Retaining Partial Penetration Welds Section Xl, Division 1. 10CFR Part 50, Federal Register, final rule was issued September 10, 2008 mandates the use of this code case.)
- 12. Plan Addenda 2MNS-065 (changed Category B-D B3.100 inspections req. from 36 to 40) and 2MNS-066 (changed Category RA inspections req. from 91 to 137.)
EOC 20 Refueling Outage Report Page 4 of 5 McGuire Unit 2 Revision 0 Section 1 June 7, 2011
Engineer evaluation determined snubber was not locked up documented in PIP.
- 16. PIP M-1 1-1508 This PIP was written for Summary Number M2.G6.2.0001 to address accumulation of boron on PZR manway cover, Engineer evaluation determined powder to be insulation dust.
- 17. PIP M-1 1-1846 This PIP was written to address adjacent weld 2NV2FW183-28 with linear indication outside of Section XI exam boundaries.
EOC 20 Refueling Outage Report Page 5 of 5 McGuire Unit 2 Revision 0 Section 1 June 7, 2011
2.0 Third Ten-Year Interval Inspection Status The completion status of inspections required by the 1998 ASME Code Section Xl through the 2000 Addenda is summarized in this section. The requirements are listed by the ASME Section Xl Examination Category as defined in Table IWB-2500-1 for Class 1 Inspections, Table IWC-2500-1 for Class 2 Inspections and IWF-2500-1 for Class 1, 2 and 3 Component Supports. Augmented, Elective, and Risk Informed Inspections are also included.
During the McGuire Third 10 Year Interval, piping welds will be examined under the Risk Informed Inservice Inspection Program developed in accordance with methodology contained in the Westinghouse Owner's Group (WOG) Topical Report, WCAP-14572, Revision 1-NP-A and its Supplement 2 Revision 1-NP-A. Request for Relief 01-005 was submitted to the NRC seeking approval to incorporate the Risk Informed Program into the Third 10 Year Interval ISI Plan for McGuire Unit 2. The NRC approved use of this program per SER dated June 12, 2002. Previous code examination Categories B-F, B-J, C-F-i, and C-F-2 will now be combined under the new Risk Informed Category R-A.
Class 1 Inspections Examination Description Inspections Inspections Percentage (1)Deferral Category Required Completed Completed Allowed B-A Pressure Retaining Welds 15 3 20.00% Yes in Reactor Vessel B-B Pressure Retaining Welds 5 3 60.00% No in Vessels Other than Reactor Vessel B-D Full Penetration Welded 40 20 50% Partial Nozzles in Vessels (4)
Inspection Program B Reference B-F Pressure Retaining Risk N/A N/A (2)
Dissimilar Metal Welds in Informed Vessel Nozzles Program R1. Items B-G-1 Pressure Retaining Bolting 241 175 72.61% Yes Greater than 2" in Diameter B-G-2 Pressure Retaining Bolting 22 15 68.18% No 2" and Less in Diameter I EOC 20 Refueling Outage Report Page I of 5 McGuire Unit 2 Revision 0 Section 2 June 7, 2011
Class I Inspections (Continued)
Examination Description Inspections Inspections Percentage 1Deferral Category Required Completed Completed Allowed Reference B-J Pressure Retaining Risk Informed N/A N/A (2)
Welds in Piping Program RI.
Items B-K Welded Attachments for 5 4 80% No Vessels, Piping, Pumps (3) (3) and Valves B-L-1 Pressure Retaining N/A N/A N/A Yes Welds in Pump Casings B-L-2 Pump Casings 1 0 00.00% Yes B-M-1 Pressure Retaining N/A N/A N/A Yes Welds in Valve Bodies B-M-2 Valve Body > 4 in. 9 4 44.44% Yes Nominal Pipe Size B-N-1 Interior of Reactor 3 2 66.66% No Vessel B-N-2 Welded Core Support 2 0 00.00% Yes Structures and Interior Attachments to Reactor Vessel B-N-3 Removable Core 1 0 00.00% Yes Support Structures B-O Pressure Retaining 3 2 66.66% Yes Welds in Control Rod Housings B-P All Pressure Retaining REFERENCE SECTION 6.0 OF THIS REPORT Components B-Q Steam Generator (5)
Tubing F-A Class 1 Component 58 36 62.10% No F1.10. Supports EOC 20 Refueling Outage Report Page 2 of 5 McGuire Unit 2 Revision 0 Section 2 June 7, 2011
Class 2 Inspections Examination Description Inspections Inspections Percentage Category Required Completed Completed C-A Pressure Retaining Welds 30 12.5 42%
in Pressure Vessels (6) (6)
C-B Pressure Retaining Nozzle 11 7 63.63%
Welds in Vessels C-C Welded Attachments for 17 12 70.60%
Vessels, Piping, Pumps and Valves C-D Pressure Retaining Bolting N/A N/A N/A Greater Than 2" in Diameter Reference C-F-1 Pressure Retaining Welds Risk Informed (2) (2) in Austenitic Stainless Program RI.
Steel or High Alloy Piping Items Reference C-F-2 Pressure Retaining Welds Risk Informed (2) (2) in Carbon or Low Alloy Program RI.
Steel Piping Items C-G Pressure Retaining Welds 8 4 50%
in Pumps and Valves C-H All Pressure Retaining REFERENCE SECTION 6.0 OF THIS Components REPORT F-A Class 2 Component 230 148 64.30%
F1.20. Supports Additional Component Support Examinations Class 1, 2 and 3 Examination Description Inspections Inspections Percentage Category Required Completed Completed F-A Supports other than Piping 42 30 71.40%
F1.40. Supports Class 1, 2 & 3 F-A Component Supports (7)
F1.50. Snubbers Class 1, 2 & 3 EOC 20 Refueling Outage Report Page 3 of 5 McGuire Unit 2 Revision 0 Section 2 June 7, 2011
Risk Informed Inservice Inspection Program Class I and 2 Examination Description Inspections Inspections Percentage Deferral Category Required Completed Completed Allowed (2)R-A Piping Examinations Class 137 71 51.80% No 1 and 2 (8)
Weld Overlay Section XI Appendix Q Augmented / Elective Inspections Summary Description PercentageComplete Number G1.1 Reactor Coolant Pump Flywheels No examinations required for Outage 5/ EOC 20 G2.1 RPV Closure Head Studs and Nuts per No examinations required for Outage 5 I EOC 20 Nuclear Guide 1.65 G3.1 Pipe Rupture Protection No examinations required for Outage 5 / EOC 20 G5.1 RPV Head Penetration Nozzles No examinations required for Outage 5/ EOC 20 G5.2 RPV Vent Line No examinations required for Outage 5 I EOC 20 G6.2 Pressurizer Manway 100% of Outage 5 / EOC 20 Requirements Met B15.80 Reactor Vessel BMI Nozzles 100% of Outage 5 / EOC 20 Requirements Met B4.10 Reactor Vessel Head 100% of Outage 5 / EOC 20 Requirements Met B4.20 Reactor Vessel Head Pen and Reactor No examinations required for Outage 5 / EOC 20 Vessel Head Vent EOC 20 Refueling Outage Report Page 4 of 5 McGuire Unit 2 Revision 0 Section 2 June 7, 2011
NOTES:
(1) Deferral of inspection to the end of the interval as allowed by ASME Section XI Table IWB 2500-1. These examination categories are exempt from percentage requirements per IWB-2412 (a), Inspection Program B.
(2) RFR 01-005 (3) Beginning with EOC-19, Code Case N-700 has been incorporated for Category B-K. This reduced the required number of exams to five from six. The impact on percentages for this category is only due to implementation of the code case during the interval.
(4) Totals changed from 36 to 40 due to Plan Addendum 2MNS-065 adding (4) B3.100's reference PIP G-10-0134.
(5) Steam Generator Tubing is examined and documented by the Steam Generator Maintenance and Engineering Group as required by the Station Technical Specifications and is not included in this report.
(6) Beginning with EOC-19, Code Case N-706 has been incorporated for Category C-A. This code case covers the examinations associated with the Regenerative and Residual Heat Removal Heat Exchangers.
(7) Inspections to be performed per Relief Request 03-002 (8) Totals changed from 91 to 137 per Plan Addendum 2MNS-066, reference PIP M-10-3538.
EOC 20 Refueling Outage Report Page 5 of 5 McGuire Unit 2 Revision 0 Section 2 June 7, 2011
3.0 Final Inservice Inspection Plan The final Inservice Inspection Plan shown in this section lists all ASME Section Xl Class 1, Class 2, Class 3, Augmented and Risk Informed examinations credited for this report period.
EOC 20 Refueling Outage Report Page 1 of 1 McGuire Unit 2 Revision 0 Section 3 June 7, 2011
DUKE ENERGY NUCLEAR TECHNICAL SERVICES ScheduleWorks Inservice Inspection DatabaseManagement System Plan Report McGuire 2, 3rd Interval, Outage 5 (EOC-20)
This report includes all changes through addendum 2MNS-074 Summary Nui m Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category AUG M2.B15.80.0001 2-RPV-BMI-NOZZLES Class 1 NC MP\0\A\7150-165 NDE-69 VT-2 Inconel Transition Weld to Stainless Steel Tube Bare Metal Visual Inspection by VT-2 qualified inspector of the BMI Nozzles per the requiements of Code Case N-722 (Item B15.80). The bare metal visual inspection shall include an inspection of the bottom head and Alloy 600 transition weld between the Alloy 600 tube and the stainless steel tube. This exam added per QA-513J ER-MNS-09-01. This exam should be scheduled every other outage begining with EOC-1 9. Reference Footnote 4 of Code Case N-722 for type of examination. Any questions concerning this exam should be directed to the Materials and NDE Services Group (Chris Cruz or Jody Suping).
These augmented examinations are being added to the ISI Plan per QA-513-J Form, Tracking Number ER-MNS-10-03, initiated by C.A. Cruz of the Materials and NDE Services Group. All bottom mounted instrument (BMI) nozzles and transition welds will be examined every refueling outage instead of every other outage outlined in ER-MNS-09-01.
M2.134.10.0001 2RPV-Head Class 1 NC MCFD 2553-01.00 NDE-70 VT-2 MCM 2201.01-0021 001 As specified in ASME Code Case N-729-1, a direct visual examination of the bare metal surface of the entire outer surface of the head, including essentially 100% of the intersection of each nozzle with the head (J-groove). For coverage requirements see Figure 1 of Code Case N-729-1. For additional information reference QA-513J (ER-MNS-09-06). Acceptance criteria specified in ASME Code Case N-729-1 subject to the conditions in 10CFR 50.55a (g)(6)(ii)(D)(2) through (6). Relevant conditions for the purpose of the VE shall include areas of corrosion, boric acid deposits, discoloration, and other evidence of nozzle leakage. If EDY<8 and no flaws unacceptable for continued service have been detected, the reexamination frequency may be extended to every third refueling outage or 5 calendar years, whichever is less, provided an IWA-2212 VT-2 visual examination of the head is performed under the insulation through multiple access points in outages that the VE is not completed. Last Bare Metal Visual occurred during 2EOC17, so next full bare metal visual will be due in 2EOC20, provided EDY remains less than 8 and IWA-2212 VT-2 visuals are performed in every outage these VE's are not. EDY Calculation will continue to be updated and if EDY greater than or equal to 8 these VE's will be required every refueling outage, with no flexibility. Schedule Flexibility: Time between inspections may be shortened, but not lengthened. For additional information, contact Rachel Doss in the Materials and NDE Services Section, Nuclear Technical Services Division. This inspection replaces Augmented examinations M2.G5.1.0001 and M2.G5.2.0004 required by NRC Order EA-03-009. Once licensee implements this requirement the First Revised NRC Order EA-03-009 no longer applies and is deemed to be withdrawn.
Printed 06/07/11 GJU8302 v.06/18/09 .C.M.2 SDQA Cat "C" McGuire 2 6/7/20116:33:01 AM . Page 0131 Peo1 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched ThickINPS Cal Blocks Componenet ID 2 Class I System Description Comments Category AUG M2.G6.2.0001 2PZR-Manway Class 1 NC MCM 1201.01-140 NDE-68 VT-2 Pressurizer Manway Pressurizer Manway Diaphram Seal Weld. Bare Metal Visual Exam by VT-2 qualified Inspector. Examine the gap between the Pressurizer Manway Cover and Manway for evidence of diaphram plate seal weld leakage. (For responsible Individual, contact J.M. Shuping, Alloy 600 Engineer Nuclear Technical Services). Reference NRC Bulletin 2004-01.
Category B-B M2.B2.11.0002 2PZR-5 Class 1 NC MCM 2201.01-15 NDE-640 UT CS 3.750 / N/A 50337 B02.01 1.00; Circumferential MCM 2201.01-16 Head to Shell PRESSURIZER UPPER HEAD TO SHELL.
This exam was moved from 2EOC-19 to 2EOC-20, to provide time to schedule Westinghouse to be on standby to perform analysis on weld if required. Reference Note from Rick Branch dated 8/13/2009 requesting rescheduling of weld.
Drawing EDSK 379624B in Manual MCM 1201.01-0371 shows 3.750 min. wall at weld.
M2.B2.11.0002 2PZR-5 Class 1 NC MCM 2201.01-15 NDE-820 UT CS 3.750 / N/A 50337 B02.01 1.00; Circumferential MCM 2201.01-16 Head to Shell PRESSURIZER UPPER HEAD TO SHELL.
This exam was moved from 2EOC-19 to 2EOC-20, to provide time to schedule Westinghouse to be on standby to perform analysis on weld if required. Reference Note from Rick Branch dated 8/13/2009 requesting rescheduling of weld.
Drawing EDSK 379624B in Manual MOM 1201 .01-0371 shows 3.750 min. wall at weld.
M2.B2.12.0002 2PZR-9 Class 1 NC MCM 2201.01-15 NDE-640 UT CS 3.750 / N/A 50337 B02.012.00; Longitudinal MCM 2201.01-16 Head to Shell PRESSURIZER UPPER HEAD TO SHELL.
This exam was moved from 2EOC-19 to 2EOC-20, to schedule exam to be done in conjunction with 2PZR-5 (M2.B2.11.0002).
Drawing EDSK 379624B in Manual MCM 1201.01-0371 shows 3.750 min. wall at weld.
M2.B2.12.0002 2PZR-9 Class 1 NC MCM 2201.01-15 NDE-820 UT CS 3.750 / N/A 50337 B02.012.00; Longitudinal MCM 2201.01-16 Head to Shell PRESSURIZER UPPER HEAD TO SHELL.
This exam was moved from 2EOC-19 to 2EOC-20, to schedule exam to be done in conjunction with 2PZR-5 (M2.B2.11.0002).
Drawing EDSK 379624B in Manual MCM 1201.01-0371 shows 3.750 min. wall at weld.
Printed 06/07111 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/712011 6:33:01 AM Page 2 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category B9-D M2.B3.140.0007 2SGD-INLET Class 1 NC MCM 2201.01-0207 NDE-680 UT CS 6.250/31 I.D. 50235 B03.140.00; Circumferential MCM 2201.01-0216 MCM 2201.01-0126 Nozzle To Head STEAM GENERATOR 2D INLET NOZZLE TO LOWER HEAD. Y1-X1 QUADRANT. (INSIDE RADIUS SECTION).
Drawing MCM 2201.01-0126 shows 6.250 min. wall at weld.
This item changed from VT-1 to UT because greater than 90% coverage can now be achieved using UT.
M2.B3.140.0008 2SGD-(OUTLET Class 1 NC MCM 2201.01-0207 NDE-680 UT CS 6.250/ 311.D. 50235 B03.140.00i Circumferential MCM 2201.01-0216 MCM 2201.01-0126 Nozzle To Head STEAM GENERATOR 2D OUTLET NOZZLE TO LOWER HEAD. Y2-X1 QUADRANT. (INSIDE RADIUS SECTION).
Drawing MCM 2201.01-0126 shows 6.250 min. wall at weld.
This item changed from VT-1 to UT because greater than 90% coverage can now be achieved using UT.
Category B-O M2.B14.10.0017 2RPV-CRDM-69 Class 1 NC MCM 2201.01-20/sht.7 NDE-35 PT SS-Inconel 0.642 / 4.000 B14.010.01!
MCM 2201.01-0001 MC-ISIN3-2553-01.00 Adapter To Housing Body CRD HOUSING WELD. (PERIPHERAL)
Shroud has to be lifted to inspect see W/O 1923497-10 and 13.
Category C-A M2.C1.10.0005 2ASWINJF-2 Class 2 NV MCM 1201.04-27 NDE-3630 UT SS 0.438 / 4.500 50424 C01.010.10, Circumferential MC-ISIN3-2554-03.00 SHELL to LOWER FLANGE SEAL WATER INJECTION FILTER 2A.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 3 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched ThickINPS Cal Blocks Componenet ID2 Class I System Description Comments Category C-A M2.C1.10.0008 2RHR-2B-3-4 Class 2 ND MCM 1201.06-22 NDE-68 VT-2 SS 0.750 / 35.750 C011.010.2559, C01.010.256(
Circumferential MC-ISIN3-2561-01.00 NOZZLE BELT to Flange RESIDUAL HEAT REMOVAL HEAT EXCHANGER 2B.
Residual Heat Removal Heat Exchanger 2B Nozzle Belt to Flange Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Residual Heat Removal Heat Exchanger 2B is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
If evidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2561-01.00 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
M2.Cl .10.0009 2RHRHX-2A-3-4 Class 2 ND MCM 1201.06-22 NDE-68 VT-2 SS 0.750 / 35.750 C01.010.05(
Circumferential MC-ISIN3-2561-01.00 NOZZLE BELT to Flange RESIDUAL HEAT REMOVAL HEAT EXCHANGER 2A.
Residual Heat Removal Heat Exchanger 2A Nozzle Belt to Flange Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Residual Heat Removal Heat Exchanger 2A is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2561-01.00 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
Printed 06/07/11 GJUB302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 4 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched ThickJNPS Cal Blocks Componenet ID 2 Class I System Description Comments Category C-A M2.C1.20.0014 2RHR-2B-2-3 Class 2 ND MCM 1201.06-22 NDE-68 VT-2 SS 0.750 / 37.250 C01.020.2561, C01.020.256, Circumferential MC-ISIN3-2561-01.00 NOZZLE BELT to HEAD RESIDUAL HEAT REMOVAL HEAT EXCHANGER 2B.
Residual Heat Removal Heat Exchanger 2B Nozzle Belt to Head Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Residual Heat Removal Heat Exchanger 2B is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2561-01.00and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
M2.Cl.20.0018 2RHRHX-2A-2-3 Class 2 ND MCM 1201.06-22 NDE-68 VT-2 SS 0.750 / 35.750 C01.020.03(
Circumferential MC-ISIN3-2561-01.00 NOZZLE BELT to HEAD RESIDUAL HEAT REMOVAL HEAT EXCHANGER 2A.
Residual Heat Removal Heat Exchanger 2A Nozzle Belt to Head Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Residual Heat Removal Heat Exchanger 2A is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
If evidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2561-01.00 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 5 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category C-A M2.C1.20.0019 2REGHX-1-HD1 Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 COl .020.07(
Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 NOZZLE BELT to HEAD REGENERATIVE HEAT EXCHANGER. (SHELL 1)0 EOC-1 7 report references RFR to be submitted for this exam. Implementation of Code Case N-706 will be used in place of RFR for this outage.
Regenerative Heat Exchanger (Shell 1) Nozzle Belt to Head Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternatine exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
If evidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 6 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched ThicklNPS Cal Blocks Componenet ID2 Class I System Description Comments Category C-A M2.C1.20.0020 2REGHX-1-HD2 Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C01.020.01" Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 SHELL to HEAD REGENERATIVE HEAT EXCHANGER. (SHELL 1)
EOC-17 report references RFR to be submitted for this exam. Implementation of Code Case N-706 will be used in place of RFR for this outage.
Regenerative Heat Exchanger (Shell 1) Shell to Head Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos.
MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
M2.Cl .20.0021 2REGHX-2-HD1 Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C01.020.07, Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 NOZZLE BELT to HEAD REGENERATIVE HEAT EXCHANGER. (SHELL 2)0 Regenerative Heat Exchanger (Shell 2) Nozzle Belt to Head Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an altematine exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 7 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched ThickINPS Cal Blocks Componenet ID 2 Class I System Description Comments Category C-A M2.C1.20.0022 2REGHX-2-HD2 Class 2 NV MCM1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C01.020.07' Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 SHELL to HEAD REGENERATIVE HEAT EXCHANGER. (SHELL 2)0 Regenerative Heat Exchanger (Shell 2) Shell to Head Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos.
MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
If evidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-011.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
M2.Cie.20.0023 2REGHX-3-HD1 Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 1 10.920 C01.020.074 Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 NOZZLE BELT to HEAD REGENERATIVE HEAT EXCHANGER. (SHELL 3)[1 Regenerative Heat Exchanger (Shell 3) Nozzle Belt to Head Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternatine exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
If evidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015 A VT-2 visual exam will be performed for this weld.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 8 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category C-A M2.Cl .20.0024 2REGHX-3-HD2 Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C01.020.07!
Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 SHELL to HEAD REGENERATIVE HEAT EXCHANGER. (SHELL 3)0 Regenerative Heat Exchanger (Shell 3) Shell to Head Weld. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos.
MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
If evidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
M2.C1.30.0007 2BCSHX-50-B Class 2 NS MCM 1201.06-0093 NDE-3630 UT SS 0.437 / 55.375 50420 C01.030.01' Circumferential MC-ISIN3-2563-01.00 MCM 1201.06-0090 SHELL to BOTTOM TUBESHEET CONTAINMENT SPRAY HEAT EXCHANGER 2B.
M2.C1.30.0008 2BCSHX-50-A Class 2 NS MCM 1201.06-0093 NDE-3630 UT SS 0.437 / 55.375 50420 C01.030.01; Circumferential MC-ISIN3-2563-01.00 MCM 1201.06-0090 SHELL to TOP TUBESHEET CONTAINMENT SPRAY HEAT EXCHANGER 2B.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 9 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC.20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched ThicklNPS Cal Blocks Componenet ID 2 Class I System Description Comments Category C-A M2.Cl.30.0015 2REGHX-2-TS-SH Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 10.920 C01.030.02=
Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 TUBESHEET to SHELL REGENERATIVE HEAT EXCHANGER. (SHELL 2)
Regenerative Heat Exchanger (Shell 2) Tubesheet to Shell. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-01 5. A VT-2 visual exam will be performed for this weld.
M2.C1.30.0016 2REGHX-3-NB-TS Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C01.030.02d Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 NOZZLE BELT to TUBESHEET REGENERATIVE HEAT EXCHANGER. (SHELL 3)
Regenerative Heat Exchanger (Shell 3) Nozzle Belt to Tubesheet. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 10 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched ThicklNPS Cal Blocks Componenet ID 2 Class / System Description Comments Category C-A M2.Cl .30.0017 2REGHX-3-TS-SH Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C01.030.02!
Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 TUBESHEET to SHELL REGENERATIVE HEAT EXCHANGER. (SHELL 3)
Regenerative Heat Exchanger (Shell 3) Tubesheet to Shell. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
M2.C1.30.0018 2REGHX-1-NB-TS Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C01.030.02(
Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 NOZZLE BELT to TUBESHEET REGENERATIVE HEAT EXCHANGER. (SHELL 1)
EOC-17 report references RFR to be submitted for this exam. Implementation of Code Case N-706 will be used in place of RFR for this outage.
Regenerative Heat Exchanger (Shell 1) Nozzle Belt to Tubesheet. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code# 000252).
If evidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 11 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID2 Class I System Description Comments Category C-A M2.C1.30.0019 2REGHX-1-TS-SH Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C011.030.02" Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 TUBESHEET to SHELL REGENERATIVE HEAT EXCHANGER. (SHELL 1)
EOC-17 report references RFR to be submitted for this exam. Implementation of Code Case N-706 will be used in place of RFR for this outage.
Regenerative Heat Exchanger (Shell 1) Tubesheet to Shell. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code # 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-0115. A VT-2 visual exam will be performed for this weld.
M2.C1.30.0020 2REGHX-2-NB-TS Class 2 NV MCM 1201.06-054 NDE-68 VT-2 SS 1.075 / 10.920 C01.030.02; Circumferential MC-ISIN3-2554-01.02 MCM 1201.06-015 NOZZLE BELT to TUBESHEET REGENERATIVE HEAT EXCHANGER. (SHELL 2)
Regenerative Heat Exchanger (Shell 2) Nozzle Belt to Tubesheet. Code Case N-706 has been incorporated for use during the Third Interval which allow an alternative exam (VT-2) for this weld. The Regenerative Heat Exchanger is inside the Class 2 Pressure Test Boundary and will receive a VT-2 exam once each period. For additional information reference PIP G-08-480 and File Nos. MC-1212.04, MC-1223.04, and MC-1223.11 (Record Retention Code# 000252).
Ifevidence of leakage is detected for this item during system leakage test, the NDE Plan Manager will be notified of leakage so evaluation can be performed. Use of this code case shall be discontinued for the heat exchanger and others of the same design or configuration if leakage has been detected.
This exam will be performed under the Pressure Test Program, reference McGuire Third Inspection Interval Inservice Inspection Plan. Reference drawing MC-ISIL-2554-01.02 and Plan Addendum M2-PT-015. A VT-2 visual exam will be performed for this weld.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 12 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched ThickINPS Cal Blocks Componenet ID 2 Class I System Description Comments Category C-C M2.C3.10.0011 2RCHPSS-SUPPORT Class 2 NV MCM 1201.04-272 NDE-35 PT SS 0.375 / 0.000 C03.010.00(
MC-ISIN3-2554-03.00 RECIPROCATING CHRGING PUMP SUCTION STABILIZER SUPPORT. WELDED ATTACHMENT.
M2.C3.20.0016 2MCA-ND-6109 Class 2 ND MCSRD-2ND-350/sht. 7 NDE-35 PT SS 0.125 / 8.000 C03.020.263(
Mech Snubber MC-ISIN3-2561-01.00 2MCA-ND-6109 Mech Snubber This item was exchanged with M2.C3.20.0001 2MCA-ND-6123, interference for that support made this change necessary.
Welded Attachment. Inspect with M2.F1.20.0359.
The Thickness 0.125 listed is a reference used to identify support as having a welded attachment since thickness can't be determined using the support sketch. If exact dimension is needed a field measurement will be required.
M2.C3.20.0021 2MCA-ND-6117 Class 2 ND MCSRD-2ND-350/sht. 7 NDE-35 PT SS 0.154 /8.000 C03.020.02ý Rigid Restraint MC-ISIN3-2561-01.00 2MCA-ND-6117 Rigid Restraint WELDED ATTACHMENT. INSPECT WITH F01.020.122B.
Category D-A M2.D1.10.0009 2MBD-SUPPORT-2A Class 3 NV MCM 2201.09-0008 NDE-65 VT-1 NA 0.250 / 0.000 D01.010.00' Rigid Support MC-ISIN3-2554-04.00 Rigid Support MIXED BED DEMINERALIZER 2A SUPPORT. WELDED ATTACHMENT. INSPECT WITH M2.F1.40.0094. Item was exempted in second interval per Engineering notethat allowed a temperature and pressure exemption. Reference PIP M-06-2995 This item was rescheduled from 2EOC-18 to 2EOC-19 per Plan Addendum 2MNS-036. The Mixed Bed Demineralizer is surrounded in lead, this is rescheduled to allow the station time to prepare for examination during EOC-19, reference WO 1748102/03 and PIP M-08-03046.
Code Case N-700 requires only one welded attachment on a component to be examined. On drawing MCM 2201.09.0008 examine one support leg to vessel weld, facing tank and item #10 examine support on the right hand side (also lined up with lifting lug). Reference PIP G-08-00499 ACA#2 and CA#5.
This exam moved from EOC-19 to EOC-20 per station request per note dated September 3, 2009. This is to align the exam with sluice by Chemistry and the 36 Month PM. Work order needs to be created to address this exam.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/712011 6:33:01 AM Page 13 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category D-A M2.D1.20.0003 2MCA-RN-3086 Class 3 RN MCSRD-2RN-351/sht. 2 NDE-65 VT-1 NA 0.375 / 18.000 D01.020.01" Rigid Support MC-ISIN-2574-03.01 2MCA-RN-3086 Rigid Support Inspect with M2.F1.30.0049 Category F-A
- r. --
M2.F1.10.0041 2MCR-NV-4443 Class 1 NV MCSRD-2NV-204/sht. 1 NDE-66 VT-3 NA 0.000 / 2.000 F01.010.102/
Rigid Support Rigid Support ______ __ _____ __________________________________
M2.F1.10.0042 2MCR-NV-4438 Class 1 NV MCSRD-2NV-204/sht. 1 NDE-66 VT-3 NA 0.000 13.000 FO1.010.103/
Rigid Support Rigid Support M2.F1.20.0022 2MCA-FW-5009 Class 2 FW MCSRD-2FW-350/sht. 1 NDE-66 VT-3 NA 0.000 / 24.000 F011.020.07813, F0l .020.078C Mech Snubber Mech Snubber M2.F1.20.0023 2MCA-FW-5160 Class 2 FW MCSRD-2FW-350/sht. 2 NDE-66 VT-3 NA 0.000 / 24.000 F01.020.079C Spring Hgr Spring Hgr M2,F1.20.0024 2MCA-FW-5180 Class 2 FW MCSRD-2FW-350/sht. 2 NDE-66 VT-3 NA 0.000 / 24.000 F01.020.080C Hyd Snubber Hyd Snubber M2.F1.20.0040 2MCA-ND-6108 Class 2 ND MCSRD-2ND-350/sht. 1 NDE-66 VT-3 NA 0.000 / 8.000 F01.020.108E Rigid Restraint Rigid Restraint Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 14 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched ThicklNPS Cal Blocks Componenet ID 2 Class I System Description Comments Category F-A M2.F1.20.0054 2MCA-ND-6117 Class 2 ND MCSRD-2ND-350/sht. 7 NDE-66 VT-3 NA 0.154 / 8.000 F01.020.122E Rigid Restraint Rigid Restraint INSPECT WITH C03.020.023.
M2.F1.20.0108 2MCA-NS-5305 Class 2 NS MCSRD-2NS-352/sht. 1 NDE-66 VT-3 NA 0.000 /10.000 F01.020.224E Rigid Restraint Rigid Restraint M2.F1.20.0109 2MCA-NS-5308 Class 2 NS MCSRD-2NS-352/sht. 2 NDE-66 VT-3 NA 0.000 / 8.000 F01.020.225E Rigid Restraint Rigid Restraint M2.F1.20.0316 2MCA-ND-5609 Class 2 ND MCSRD-2ND-350/sht. 4 NDE-66 VT-3 NA 0.125 /8.000 F01.020.131A, F01.020.653-Rigid Support Rigid Support M2.F1.20.0359 2MCA-ND-6109 Class 2 ND 2ND-350(SHT.7OF7) NDE-66 VT-3 NA 0.000 / 8.000 F01 .020.6619, F01 .020.662(
Mech Snubber Mech Snubber Inspect with M2.C3.20.0016.
M2.F1 .20.0521 2MCA-NV-5036 Class 2 NV MCSRD-2NV-350/sht. 1 NDE-66 VT-3 NA 0.000 / 3.000 F0l .020.264A, F01 .020.691' Rigid Support Rigid Support M2.F1.20.0844 2MCR-NI-4107 Class 2 NI MCSRD-2NI-209/sht. 1 NDE-66 VT-3 NA 0.000 / 4.000 F01.020.189A, FO1.020.748 Rigid Support Rigid Support Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 15 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category F-A M21F1.20.1139 2-MCA-S-NI-504-1-L Class 2 NI 2-MCA-S-NI-504-1 NDE-66 VT-3 NA 0.000 / 2.000 F01.020.179C Mech Snubber Mech Snubber M2.F1`.20.1140 2-MCA-S-NI-504-1 -K Class 2 NI 2-MCA-S-NI-504-1 NDE-66 VT-3 NA 0.000 / 2.000 F01.020.180/
Rigid Support
_____________Rigid Support ___
M2.F1.30.0047 2MCA-RN-3028 Class 3 RN MCSRD-2RN-351/sht. 1 NDE-66 VT-3 NA 0.000 / 20.000 F01.030.154E Rigid Restraint Rigid Restraint M2.F1.30.0048 2MCA-RN-3083 Class 3 RN MCSRD-2RN-351/sht. 2 NDE-66 VT-3 NA 0.594 /18.000 F01.030.155E Rigid Restraint Rigid Restraint M2.F1.30.0049 2MCA-RN-3086 Class 3 RN MCSRD-2RN-351/sht. 2 NDE-66 VT-3 NA 0.375 / 18.000 F01.030.156A, F01.030.157/
Rigid Support Inspect with M2.1)1.20.0003 M2.F1.30.0403 2MCA-KD-3130 Class 3 KD MCSRD-2KD-353/sht. 1 NDE-66 VT-3 NA 0.000 / 6.000 F01.030.102A, F01.030.858.
Rigid Support Rigid Support M2.F1`.30.0407 2MCA-KD-3144 Class 3 KD MCSRD-2KD-353/sht. 2 NDE-66 VT-3 NA 0.000 / 6.000 F01.030.103C, F01.030.858(
Mech Snubber Mech Snubber Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 16 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category F-A M2.F1.40.0094 2MBD-SUPPORT-2A Class 3 NV MCM 2201.09-0008 NDE-66 VT-3 NA 0.250 / 0.000 F01.040.011V Rigid Support MC-ISIN3-2554-04.00 Rigid Support MIXED BED DEMINERALIZER 2A SUPPORT. Inspect with M2.D1.10.0009 This item was rescheduled from 2EOC-18 to 2EOC-19 per Plan Addendum 2MNS-036. The Mixed Bed Demineralizer is surrounded in lead, this is rescheduled to allow the station time to prepare for examination during EOC-19, reference WO 1748102/03 and PIP M-08-03046.
This exam moved from EOC-19 to EOC-20 per station request per note dated September 3, 2009. This is to align the exam with sluice by Chemistry and the 36 Month PM. Work order needs to be created to address this exam.
M2.F1.40.0110 2RNP-SUPPORT-2B Class 3 RN MCM 1201.05-190 NDE-66 VT-3 NA 0.000 / 0.000 F01.040.023E Rigid Restraint MC-ISIN3-2574-01.01 Rigid Restraint NUCLEAR SERVICE WATER PUMP 2B SUPPORT.
Category R-A M2.R1.1 1.0090 2NV2FW 183-4 Risk Segment NV-020GP Class 2 NV MCFI-2NV183 NDE-12 RT SS 0.344 /2.000 R01.011.14' Circumferential MC-ISIN-2554-01.00 Pipe to Reducer This weld has been verified by NDE Level III looking at the construction RT film to be a butt weld. Due to weld configuration UT is not possible, RT can be performed and about 80% coverage can be obtained. Work order needs to be generated to schedule RT of this weld during EOC-20.
Examination to be done with M2.R1.16.0039.
M2.R1.11.0092 2NV2FW54-18 Risk Segment NV-06, Class 2 NV MCFI-2NV54 PDI-UT-2 UT SS 0.438 / 3.000 PDI-UT-2-C R01.011.14!
MC-ISIN-2554-03.00 50225 PDI-UT-2A-M Circumferential Tee to Pipe Examination to be done with M2.R1.16.0022.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 17 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category R-A M2.R1.11.0093 2NV2FW116-21 Risk Segment NV-077E Class 2 NV MCFI-2NV1 16 PDI-UT-2 UT SS 0.344 / 2.000 PDI-UT-2-C R01.011.14(
MC-ISIN-2554-01.02 8279-0410 PDI-UT-2A-M Circumferential Reducer to Pipe Examination to be done with M2.R1.16.0023.
M2.R1. 11.0276 2NV2FW216-60 Risk Segment NV-084A Class 2 NV MCFI-2NV216 PDI-UT-2 UT SS 0.344 / 2.000 PDI-UT-2A-M R01.011.15" MC-ISIN-2554-01.02 PDI-UT-2-C 8279-0410 Circumferential Pipe To Pipe M2.R1.11.1538 2NV2FW33-23 Risk Segment NV-002E Class 2 NV MCFI-2NV33 PDI-UT-2 UT SS 0.237 1 4.000 PDI-UT-2-C R01.011.13" MC-ISIN-2554-03.00 8279-0416 PDI-UT-2A-M Circumferential Pipe to Elbow Examination to be done with M2.R1.16.001 1.
M2.R1.11.156 4 2NV2FW179-31 Risk Segment NV-020C, Class 2 NV MCFI-2NV179 PDI-UT-2 UT SS 0.344 / 2.000 PDI-UT-2-C R01.011.14" MC-ISIN-2554-01.01 8279-0410 PDI-UT-2A-M Circumferential Pipe to Reducer Examination to be done with M2.R1.16.0020.
M2.R1.11.1593 2NV2FW183-29 Risk Segment NV-020E, Class 2 NV MCFI-2NV183 NDE-12 RT SS 0.344 / 2.000 R01.011.14.
Circumferential MC-ISIN-2554-01.01 Pipe to Reducer This weld has been verified by NDE Level III looking at the construction RT film to be a butt weld. Due to weld configuration UT is not possible, RT can be performed and about 80% coverage can be obtained. Work order needs to be generated to schedule RT of this weld during EOC-20.
Examination to be done with M2.R1.16.0038.
Printed06/07/11 JU8302 v.06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 18 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category R-A M2,R1.11.1595 2NV2FW216-57 Risk Segment NV-081 Class 2 NV MCFI-2NV216 PDI-UT-2 UT SS 0.436 / 2.000 PDI-UT-2-C R01.011.141 MC-ISIN-2554-01.02 8279-0411 PDI-UT-2A-M Circumferential Pipe To Pipe Examination to be done with M2.R1.16.0024.
M2.R1.11.1596 2NV2FW2 16-53 Risk Segment NV-082 Class 2 NV MCFI-2NV216 PDI-UT-2 UT SS 0.436 / 2.000 PDI-UT-2-C R01.011.14, MC-ISIN-2554-01 .02 8279-0411 PDI-UT-2A-M Circumferential Pipe To Pipe
_____________Examination to be done with M2.R1.16.0025.
M2.R1.11.1597 2NV2FW216-52 Risk Segment NV-082 Class 2 NV MCFI-2NV216 PDI-UT-2 UT SS 0.344 / 2.000 PDI-UT-2-C R01.011.15(
MC-ISIN-2554-01.02 8279-0410 PDI-UT-2A-M Circumferential Pipe To Pipe Examination to be done with M2.R1.16.0026.
M2.R1.16.0011 2NV2FW33-23 Risk Segment NV-002E Class 2 NV MCFI-2NV33 PDI-UT-2 UT SS 0.237 / 4.000 PDI-UT-2-C MC-ISIN-2554-03.00 8279-0416 PDI-UT-2A-M Pipe to Elbow This weld is considered (IGSCC) for the Risk Informed Inservice Inspection Program, Procedure PDI-UT-2 to be used reference PIP M-10-3538.
Examination to be done with M2.R1.11.1538.
Printed 06/07/11 GJU8302 v. 06118/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 19 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISOIDWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments CategoryR-A M2.R1.16.C0020 2NV2FW179-31 Risk Segment NV-020CP Class 2 NV MCFI-2NV179 PDI-UT-2 UT SS 0.344 / 2.000 8279-0410 MC-ISIN-2554-01.01 PDI-UT-2-C PDI-UT-2A-M Pipe to Reducer This weld is considered (IGSCC) for the Risk Informed Inservice Inspection Program, Procedure PDI-UT-2 to be used reference PIP M-10-3538.
Examination to be done with M2.R1.11.1564.
M2.R1.16.0022 2NV2FW54-18 Risk Segment NV-06!
Class 2 NV MCFI-2NV54 PDI-UT-2 UT SS 0.438 / 3.000 PDI-UT-2-C MC-ISIN-2554-03.00 50225 PDI-UT-2A-M Tee to Pipe This weld is considered (IGSCC) for the Risk Informed Inservice Inspection Program, Procedure PDI-UT-2 to be used reference PIP M-10-3538.
Examination to be done with M2.R1.11.0092.
M2.R1.16.0023 2NV2FW1 16-21 Risk Segment NV-077E Class 2 NV MCFI-2NV116 PDI-UT-2 UT SS 0.344 / 2.000 PDI-UT-2-C MC-ISIN-2554-01.02 8279-0410 PDI-UT-2A-M Reducer to Pipe This weld is considered (IGSCC) for the Risk Informed Inservice Inspection Program, Procedure PDI-UT-2 to be used reference PIP M-10-3538.
Examination to be done with M2.R1.11.0093.
M2.R1.16.0024 2NV2FW216-57 Risk Segment NV-081 Class 2 NV MCFI-2NV216 PDI-UT-2 UT SS 0.436 / 2.000 PDI-UT-2-C MC-ISIN-2554-01.02 8279-0411 PDI-UT-2A-M Pipe To Pipe This weld is considered (IGSCC) for the Risk Informed Inservice Inspection Program, Procedure PDI-UT-2 to be used reference PIP M-10-3538.
Examination to be done with M2.R1.11.1595.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 20 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category R-A M2.R1.16.0025 2NV2FW216-53 Risk Segment NV-082 Class 2 NV MCFI-2NV216 PDI-UT-2 UT SS 0.436 / 2.000 PDI-UT-2-C MC-ISIN-2554-01.02 8279-0411 PDI-UT-2A-M Pipe To Pipe This weld is considered (IGSCC) for the Risk Informed Inservice Inspection Program, Procedure PDI-UT-2 to be used reference PIP M-10-3538.
Examination to be done with M2.RI.11.1596.
M2.R1.16.0026 2NV2FW216-52 Risk Segment NV-082 Class 2 NV MCFI-2NV216 PDI-UT-2 UT SS 0.344 / 2.000 PDI-UT-2-C MC-ISIN-2554-01.02 8279-0410 PDI-UT-2A-M Pipe To Pipe This weld is considered (IGSCC) for the Risk Informed Inservice Inspection Program, Procedure PDI-UT-2 to be used reference PIP M-10-3538.
Examination to be done with M2.R1.11.1597.
M2.Rl.16.0032 2NV2FW27-2 Risk Segment NV-001 Class 2 NV MCFI-2NV27 PDI-UT-2 UT SS 0.148 / 8.000 8279-0415 MC-ISIN-2554-03.01 PDI-UT-2-C PDI-UT-2A-M Elbow to Pipe Reference PIP M-08-00778. For this weld to be examined valve 2NV223 must be disassembled to allow for the draining of pipe.
This evaluation was made with the concurrence of the Operations Technical Group.
This weld is considered (IGSCC) for Risk Informed Inservice Inspection Program. Procedure PDI-UT-2 to be used reference PIP M-1 0-3538.
(NOTE) This exam was performed under Summary Number M2.R1.11.1532 during EOC-19. UT examination will be performed during EOC-20 for this summary number.
Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C" McGuire 2 6/7/2011 6:33:01 AM Page 21 of 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISO/DWG Numbers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category R-A M2,Ri,16,0033 2NV2FW1 15-5 Risk Segment NV-002AP Class 2 NV MCFI-2NV115 PDI-UT-2 UT SS 0.148 /8.000 8279-0415 MC-ISIN-2554-03.01 PDI-UT-2-C PDI-UT-2A-M This weld is considered (IGSCC) for Risk Informed Inservice Inspection Program. Procedure PDI-UT-2 to be used reference PIP M-1 0-3538.
(NOTE) This exam was performed under Summary Number M2.RI.11.0189 during EOC-18. UT examination will be performed during EOC-20 for this summary number.
M2.R1.16.0034 2NV2FW115-4 Risk Segment NV-002A, Class 2 NV MCFI-2NV115 PDI-UT-2 UT SS 0.148/8.000 8279-0415 MC-ISIN-2554-03.01 PDI-UT-2-C PDI-UT-2A-M Elbow to Pipe This weld is considered (IGSCC) for Risk Informed Inservice Inspection Program. Procedure PDI-UT-2 to be used reference PIP M-10-3538.
(NOTE) This exam was performed under Summary Number M2.R1.11.1534 during EOC-18. UT examination will be performed during EOC-20 for this summary number.
M2.R1.16.0038 2NV2FW183-29 Risk Segment NV-020EA Class 2 NV MCFI-2NV183 NDE-12 RT SS 0.344 / 2.000 MC-ISIN-2554-01.01 Pipe to Reducer This weld has been verified by NDE Level III looking at the construction RT film to be a butt weld. Due to weld configuration UT is not possible, RT can be performed and about 80% coverage can be obtained. Work order needs to be generated to schedule RT of this weld during EOC-20.
This weld is considered (IGSCC) for Risk Informed Inservice Inspection Program. Procedure NDE-12 to be used reference PIP M-10-3538.
Examination to be done with M2.R1 .11.1593.
.SDQA Cat "C" McGuire 2.6/7/2011 6:33:01 AM Pa.e 22 Printed 06/07/11 GJU8302 v. 06/18/09 Printe 06/7/1 "CU0 vc.ir 06180 6//01:30 M Pg 23v f 23
This report includes all changes through addendum 2MNS-074 McGuire 2, 3rd Interval, outage 5 (EOC-20)
Summary Num Component ID ISO/DWG Num bers Procedure Insp Req Material Sched Thick/NPS Cal Blocks Componenet ID 2 Class I System Description Comments Category R-A M2.RI.16.0039 2NV2FW183-4 Risk Segment NV-020GP Class 2 NV MCFI-2NV183 NDE-12 RT SS 0.344 / 2.000 MC-ISIN-2554-01. 00 Pipe to Reducer This weld has been verified by NDE Level III looking at the construction RT film to be a butt weld. Due to weld configuration UT is not possible, RT can be performed and about 80% coverage can be obtained. Work order needs to be generated to schedule RT of this weld during EOC-20.
This weld is considered (IGSCC) for Risk Informed Inservice Inspection Program. Procedure NDE-12 to be used reference PIP M-10-3538.
Examination to be done with M2.R1.11.0090.
End of Report S TA TIS TICS ONL Y Class 1 12 Class 2 57 Class 3 9 Total by Class 78 Systems 78 Total Count 78 Printed 06/07/11 GJU8302 v. 06/18/09 SDQA Cat "C " McGuire 2 6/7/2011 6:33:01 AM Page 23 of 23
4.0 Results of Inspections Performed The results of each examination shown in the final Inservice Inspection Plan (Section 3 of this report) are included in this section. The completion date and status for each examination are shown. All examinations revealing reportable indications and any corrective action required as a result are described in further detail in Subsections 4.1 and 4.2. Corrective measures performed and limited examinations are described in further detail in Subsections 4.3 and 4.4.
4.1 Reportable Indications EOC 20 (Outage 5) had no reportable indications during this report period.
4.2 Corrective Action Corrective action is action taken to resolve flaws and relevant conditions, including supplemental examinations, analytical evaluations, repair /
replacement activities, and corrective measures.
There was no corrective action for the examinations associated with this report period.
4.3 Corrective Measures Corrective measures are actions (such as maintenance) taken to resolve relevant conditions, but not including supplemental examinations, analytical evaluations, and repair / replacement activities.. Any corrective measures performed for examinations associated with this report period will be shown on the examination data sheets which are on file at the Duke's Corporate Office in Charlotte, North Carolina.
4.4 Limited Examinations Limitations (i.e., 90% or less of the required examination coverage obtained) identified for examinations associated with this report period are shown below.
A relief request will be submitted to seek NRC acceptance of the limited coverage. This information will be on file at the Duke's Corporate Office in Charlotte, North Carolina.
Item Number PIP Number M2.R1.11.0276 M-11-04257 EOC 20 Refueling Outage Report Page 1 of 1 McGuire Unit 2 Revision 0 Section 4 June 7, 2011
DUKE ENERGY CORPORATION QUALITY ASSURANCE TECHNICAL SERVICES Scheduleworks Inservice Inspection DatabaseManagement System Inspection Results McGuire 2, 3rd Interval, Outage 5 (EOC-20)
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.B14.10.0017 2RPV-CRDM-69 NC 03/08/11 CLR N N N PT-11-029 M2.1B15.80.0001 2-RPV-BM I-NOZZLES NC 03/01/11 CLR N N N VT-11-526 M2.B2.11.0002 2PZR-5 NC 03/02/11 CLR Y N N UT-1i1-151 (Page 1)
NC 03/02/11 REC Y N N UT-1i1-151 (Page 2)
Indications sized and evaluated to Table IWB-3510-1 and found to be acceptable. Slag indication no change from previous data.
NC 03/02/11 CLR Y N N UT-11-151 (Page 3)
NC 03/02/11 CLR N N N UT-11-165 M2.B2.12.0002 2PZR-9 NC 03/02/11 CLR N N N UT-1 1-149 (Page 1)
NC 03/02/11 CLR N N N UT-11-149 (Page 2)
NC 03/02/11 CLR N N N UT-11-149 (Page 3)
NC 03/02/11 CLR N N N UT-11-166 M2,13.140.0007 2SGD-INLET NC 03/03/11 CLR N N N UT-1l1-153 (Page 1)
NC 03/03/11 CLR N N N UT-1i1-153 (Page 2)
Printed 617/2011 9:29:58 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 1 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.B3.140.0007 2SGD-INL ET NC 03/03/11 CLR N N N UT-1l1-153 (Page 3)
M2.B3.140.0008 2SGD-OU TLET NC 03/03/11 CLR N N N UT-1l1-154 (Page 1)
NC 03/03/11 CLR N N N UT-1 1-154 (Page 2)
NC 03/03/11 CLR N N N UT-1 1-154 (Page 3)
M2.14.10.0001 2RPV-Hea d NC 03/08/11 CLR N N N VT-1 1-531 M2.C1.10.0005 2ASWINJ F-2 NV 03/10/11 CLR N Y N UT-11-167 (Page 1)
Signal response indicated geometry (flange taper) 360 deg. intermitten.
NV 03/10/11 CLR N N N UT-11-167 (Page 2)
M2.C1.10.0008 2RHR-2B- 3-4 ND 02/24/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.10.0009 2RHRHX-.2A-3-4 ND 02/03/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.20.0014 2RHR-2B- 2-3 ND 02/24/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.20.0018 2RHRHX- 2A-2-3 ND 02/03/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.20.0019 2REGHX- 1-HD1 NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
Printed 6/7/2011 9:29:58 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 2 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.C1.20.0020 2REGHX-1 -HD2 NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.20.0021 2REGHX-2-HD1 NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.20.0022 2REGHX-2-HD2 NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.20.0023 2REGHX-3-HD1 NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.20.0024 2REGHX-3-HD2 NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.30.0007 2BCSHX-50-B NS 02/16/11 CLR N Y N UT-11-148 (Page 1)
Indications were determined to be geometry.
NS 02/16/11 CLR N N N UT-11-148 (Page 2)
M2.C1.30.0008 2BCSHX-50-A NS 02/16/11 CLR N Y N UT-11-147 (Page 1)
Indications were determined to be geometry.
NS 02/16/11 CLR N N N UT-11-147 (Page 2)
M2.C1.30.0015 2REGHX-2-TS-SH NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
Printed 6/7/2011 9:29:58 AM GJU8302 v. 01 /01 /08 SDOA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 3 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.C1.30.0016 2REGHX-3-NB-TS NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.30.0017 2REGHX-3-TS-SH NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.30.0018 2REGHX-1 -NB-TS NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.30.0019 2REGHX-1 -TS-SH NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C1.30.0020 2REGHX-2-NB-TS NV 04/02/11 CLR N N N VT-n/a See Pressure Test Program for additional results.
M2.C3.10.0011 2RCHPSS-SUPPORT NV 02/10/11 CLR N. N N PT-11-026 M2.C3.20.0016 2MCA-ND-6109 ND 02/10/11 CLR N N N PT-11-027 M2.C3.20.0021 2MCA-ND-6117 ND 02/10/11 CLR N N N PT-11-028 M2.D1.10.0009 2MBD-SUPPORT-2A NV 01/14/11 CLR N N N VT-11-510 M2.D1.20.0003 2MCA-RN-3086 RN 02/21/11 CLR N N N VT-11-525 M2.F1.10.0041 2MCR-NV-4443 NV 03/04/11 CLR N N N VT-1 1-533 Printed 6/7/2011 9:29:59 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 4 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.Fl.10.0042 2MCR-NV-4438 NV 03/04/11 REC N N N VT-11-532 Spherical bearing at the pipe attached end of the strut is dislodged. Eng.
evaluation: Spherical bearing is out 1/4" from flush position, this has no adverse affects on tension, compression, no operability issue W/R 1029564 written to make correction.
M2.F1.20.0022 2MCA-FW-5009 FW 03/02/11 CLR N N N VT-11-529 M2.F1.20.0023 2MCA-FW-5160 FW 02/17/11 CLR N N N VT-11-528 M2.F1.20.0024 2MCA-FW-5180 FW 02/17/11 CLR N N N VT-11-530 M2.F1.20.0040 2MCA-ND-6108 ND 02/07/11 CLR N N N VT-11-513 M2.F1.20.0054 2MCA-ND-6117 ND 02/03/11 CLR N N N' VT-11-517 M2.F1.20.0108 2MCA-NS-5305 NS 02/10/11 CLR N N N VT-11-518 M2.F1.20.0109 2MCA-NS-5308 NS 02/10/11 CLR N N N VT-11-520 M2.F1.20.0316 2MCA-ND-5609 ND 02/07/11 CLR N N N VT-11-514 M2.F1.20.0359 2MCA-ND-6109 ND 02/07/11 CLR N N N VT-11-516 M2.F1.20.0521 2MCA-NV-5036 NV 03/19/11 CLR N N N VT-11-535 M2.F1.20.0844 2MCR-NI-4107 NI 03/04/11 CLR N N N VT-11-534 M2.F1.20.1139 2-MCA-S-NI-504-1-L NI 01/31/11 CLR N N N VT-11-511 Printed 6/7/2011 9:29:59 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 5 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.F1.20.1140 2-MCA-S-NI-504-1 --K NI 01/31/11 CLR N N N VT-11-512 M2.F1 .30.0047 2MCA-RN-3028 RN 02/07/11 CLR N N N VT-1 1-515 M2.F1.30.0048 2MCA-RN-3083 RN 02/10/11 CLR N N N VT-11-519 M2.F1.30.0049 2MCA-RN-3086 RN 02/21/11 CLR N N N VT-11-524 M2.F1.30.0403 2MCA-KD-3130 KD 02/22/11 CLR N N N VT-11-523-M2.F1 .30.0407 2MCA-KD-3144 KD 02/22/11 REC N N N VT-11-522 Snubber item #8 is lockedup, pipe is not bearing on support. Eng. evaluation:
Snubber is not lockedup W/O 1971210 and PIP M-11-1233 documents this, pipe bearing 1/64" or less, this is an acceptable gap. No operability issue M2.F1.40.0094 2MBD-SUPPORT-22A NV 01/14/11 CLR N N N VT-11-509 M2.F1 .40.0110 2RNP-SUPPORT-2 B RN 02/16/11 CLR N N N VT-11-521 M2.G6.2.0001 2PZR-Manway NC 03/01/11 REC N N N VT-11-527 Small accumulation of boron and crystals on interface of pressurizer and manway cover and bolting. Eng. evaluation determined powder to be insulation dust. Reference PIP M-11-1508 and W/R 01028856 M2.R1.11.0090 2NV2FW183-4 NV 03/02/11 REC N N N RT-n/a Indication acceptable: Film artifacts and root edge M2.R1.11.0092 2NV2FW54-18 NV 03/04/11 CLR Y N N UT-11-161 (Page 1)
Tee is a forged fitting configuration causing limitation Printed 6/7/2011 9:29:59 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 6 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.R1.11.0092 2NV2FW54-18 NV 03/04/11 CLR Y N N UT-11-161 (Page 2)
Tee is a forged fitting configuration causing limitation NV 03/04/11 CLR Y N N UT-1 1-161 (Page 3)
Tee is a forged fitting configuration causing limitation NV 03/04/11 CLR Y N N UT-1 1-161 (Page 4)
Tee is a forged fitting configuration causing limitation NV 03/04/11 CLR Y N N UT-11-161 (Page 5)
Tee is a forged fitting configuration causing limitation M2.R1.1 1.0093 2NV2FW1 16-21 NV 02/08/11 CLR N N N UT-11-141 (Page 1)
NV 02/08/11 CLR N N N UT-11-141 (Page 2)
NV 02/08/11 CLR N N N UT-1 1-141 (Page 3)
NV 02/08/11 CLR N N N UT-11-141 (Page 4)
M2.R1.11.0276 2NV2FW216-60 NV 03/01/11 CLR Y N Y UT-11-159 (Page 1)
Limitation due to welded pipe support PIP M-11-04257 was written to determine the corrective action for the limited coverage obtained for this item.
NV 03/01/11 CLR Y N Y UT-1l1-159 (Page 2)
Limitation due to welded pipe support PIP M-1 1-04257 was written to determine the corrective action for the limited coverage obtained for this item.
M2.R1.11.1538 2NV2FW33-23 NV 02/08/11 CLR N N N UT-11-143 (Page 1)
NV 02/08/11 CLR N N N UT-1 1-143 (Page 2)
Printed 6/7/2011 9:29:59 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/712011 9:29:17 AM Page 7 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.R1.11.1564 2NV2FW179-31 NV 02/08/11 CLR Y N N UT-11-145 (Page 1)
Limitation due to reducer configuration NV 02/08/11 CLR Y N N UT-1 1-145 (Page 2)
Limitation due to reducer configuration NV 02/08/11 CLR Y N N UT-11-145 (Page 3)
Limitation due to reducer configuration NV 02/08/11 CLR Y N N UT-1 1-145 (Page 4)
Limitation due to reducer configuration M2IR1.11.1593 2NV2FW183-29 NV 03/02/11 REC Y N N RT-11-04 Indications are acceptable: Film artifacts, convexity, and root edge. Linear indications outside Section XI exam area in adjacent weld 2NV2FW183-28 see PIP M-11-1846.
M2.R1.11.1595 2NV2FW216-57 NV 03/01/11 CLR N N N UT-11-157 (Page 1)
NV 03/01/11 CLR N N N UT-11-157 (Page 2)
NV 03/01/11 CLR N N N UT-11-157 (Page 3)
M2.R1.11.1596 2NV2FW216-53 NV 03/16/11 CLR N N N UT-11-168 (Page 1)
NV 03/16/11 CLR N Y N UT-1 1-168 (Page 2)
Indication intermitten geometry NV 03/16/11 CLR N N N UT-11-168 (Page 3)
NV 03/16/11 CLR N N N UT-11-168 (Page 4)
Printed 6/7/2011 9ý29:59 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 8 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.R1.11.1596 2NV2FW216-53 NV 03/16/11 CLR N N N UT-11-168 (Page 5)
M2.R1.11.1597 2NV2FW216-52 NV 03/01/11 CLR N N N UT-11-155 (Page 1)
NV 03/01/11 CLR N Y N IUT-11-155 (Page 2)
Indication 360 deg. intermittent geometry at lower amplitudes seen from S1 (downstream side)
M2.R1.16.0011 2NV2FW33-23 NV 02/08/11 CLR N N N UT-11-144 (Page 1)
NV 02/08/11 CLR N N N UT-1 1-144 (Page 2)
M2.R1.16.0020 2NV2FW179-31 NV 02/08/11 CLR Y N N UT-11-146 (Page 1)
Limitation due to reducer configuration NV 02/08/11 CLR Y N N UT-11-146 (Page 2)
Limitation due to reducer configuration NV 02/08/11 CLR Y N N UT-1 1-146 (Page 3)
Limitation due to reducer configuration NV 02/08/11 CLR Y N N UT-1 1-146 (Page 4)
Limitation due to reducer configuration M2.Rl.16.0022 2NV2FW54-18 NV 03/04/11 CLR Y N N UT-11-160 (Page 1)
Tee is a forged fitting configuration causing limitation NV 03/04/11 CLR Y N N UT-11-160 (Page 2)
Tee is a forged fitting configuration causing limitation Printed 6/7/2011 9:29:59 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page9 of12
EOC 20 Report Results Insp Insp I r1sp Geo Summary No Component ID System Date Status Linnited Ref RFR Comment M2.R1.16.0022 2NV2FW54-18 NV 03/04/11 CLR Y N N UT-11-160 (Page 3)
Tee is a forged fitting configuration causing limitation NV 03/04/11 CLR Y N N UT-11-160 (Page 4)
Tee is a forged fitting configuration causing limitation NV 03/04/11 CLR Y N N UT-1 1-160 (Page 5)
Tee is a forged fitting configuration causing limitation M2.R1.16.0023 2NV2FW116-21 NV 02/08/11 CLR N N N UT-11-142 (Page 1)
NV 02/08/11 CLR N N N UT-11-142 (Page 2)
NV 02/08/11 CLR N N N UT-11-142 (Page 3)
NV 02/08/11 CLR N N N UT-1 1-142 (Page 4)
M2.R1.16.0024 2NV2FW216-57 NV 03/01/11 CLR N N N UT-1l1-158 (Page 1)
NV 03/01/11 CLA N N N UT-1l1-158 (Page 2)
NV 03/01/11 CLR *N N N UT-11-158 (Page 3)
M2.R1.16.0025 2NV2FW216-53 NV 03/16/11 CLR N N N UT-11-169 (Page 1)
NV 03/16/11 CLR N Y N UT-11-169 (Page 2)
Indication 360 deg. intermitent geometry NV 03/16/11 CLR N N N UT-1 1-169 (Page 3)
NV 03/16/11 CLR N N N UT-11-169 (Page 4)
Printed 6/7/2011 9:30:00 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 10 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.R1.16.0025 2NV2FW216-53 NV 03/16/11 CLR N N N UT-1 1-169 (Page 5)
M2.R1.16.0026 2NV2FW216-52 NV 03/01/11 CLR N N N UT-11-156 (Page 1)
NV 03/01/11 CLR N Y N UT-1l1-156 (Page 2)
Indication 360 deg. intermittent geometry at lower amplitudes seen from S1 (downstream side)
M2.R1.16.0032 2NV2FW27-2 NV 03/04/11 CLR N N N UT-11-162 (Page 1)
NV 03/04/11 CLR *N N N UT-11-162 (Page 2)
NV 03/04/11 CLR N N N UT-1 1-162 (Page 3)
NV 03/04/11 CLR N N N UT-1 1-162 (Page 4)
M2.Ri.16.0033 2NV2FW115-5 NV 03/04/11 CLR N UT-11-163 (Page 1)
NV 03/04/11 CLR N UT-11-163 (Page 2)
NV 03/04/11 CLR N UT-11-163 (Page 3)
NV 03/04/11 CLR N UT-1 1-163 (Page 4)
M2.R1.16.0034 2NV2FW115-4 NV 03/04/11 CLR N UT-11-164 (Page 1)
NV 03/04/11 CLR N UT-1 1-164 (Page 2)
NV 03/04/11 CLR N UT-11-164 (Page 3)
NV 03/04/11 CLR N UT-11-164 (Page 4)
Printed 6/7/2011 9:30:00 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 11 of 12
EOC 20 Report Results Insp Insp Insp Geo Summary No Component ID System Date Status Limited Ref RFR Comment M2.R1.16.0038 2NV2FW183-29 NV 03/02/11 REC Y N N RT-11-04 Indications are acceptable: Film artifacts, convexity, and root edge. Linear indication outside section Xl exam area in adjacent weld 2NV2FW1 83-28 see PIP M-11-1846.
M2.R1.16.0039 2NV2FW183-4 NV 03/02/11 REC N N N RT-n/a Indications acceptable: Film artifacts and root edge.
Printed 6/7/2011 9:30:00 AM GJU8302 v. 01/01/08 SDQA Cat "C" McGuire 2 6/7/2011 9:29:17 AM Page 12 of 12
5.0 Owner's Report for Repair / Replacement Activities As required by the applicable code, records of Class 1 and Class 2 Repair and Replacement work is included on NIS-2 forms in this section.
No item was determined to have had work performed outside this report period.
The NIS-2 forms included in this section were completed for work performed during this report period. The individual work request documents and manufacturers' data reports are on file at McGuire Nuclear Station.
5.1 Class 1 and 2 PreserviceExaminations As required by the applicable code, Preservice Inspection (PSI)
Examinations were performed on ISI Class 1 and 2 items during this report period. All Class 1 and 2 PSI examination data shown in Attachment A is on file in the McGuire Nuclear Station QA Vault. Also included in this listing are the Class 3 PSI Examinations performed during this report period.
See Attachment A listing for Repair and Replacements for McGuire EOC 20.
EOC 20 Refueling Outage Report Page 1 of 1 McGuire Unit 2 Revision 0 Section 5 June 7, 2011
Work Order# Task Class Description of work Attachment A 592075 13 B Cut out and replaced valve 2BB6 Page I of 2 592077 3 B Replaced pivot pin in rear bracket on hanger 2MCR-BB-4520 592077 15 B Cut out and replaced valve 2BB8 592077 24 B Replaced bolting material in pipe clamp on hanger 2MCR-BB-4519 1840801 2 B Replaced soft seat disc in valve 2VI149 1841062 3 B Replaced bolting material at valve 2VB50 1850786 6 B Modified hanger 2MCA-FW-5009 per MGMM15247 1850786 7 B Deleted hanger 2MCA-FW-5185 1850786 8 B Deleted hanger 2MCA-ND-5483 1850786 9 B Deleted hanger 2MCA-ND-5487 1850786 10 B Replaced gap support with snubber on hanger 2MCA-FW-5184 1850786 11 B Replaced gap support with snubber on hanger 2MCA-FW-5103 1850786 12 B Replaced gap support with snubber on hanger 2MCA-FW-5181 1850786 13 B Replaced gap support with snubber on hanger 2MCA-ND-5204 1850786 14 B Replaced gap support with snubber on hanger 2MCA-ND-5280 1850786 15 B Replaced gap support with snubber on hanger 2MCA-ND-5306 1850786 16 B Replaced gap support with snubber on hanger 2MCA-ND-5311 1850786 17 B Replaced gap support with snubber on hanger 2MCA-ND-5405 1850786 18 B Replaced two gap supports with two snubbers on hanger 2MCA-ND-5461 1850786 19 B Replaced gap support with snubber on hanger 2MCA-ND-5480 1850786 20 B Replaced gap support with snubber on hanger 2MCA-ND-5482 1850786 21 B Replaced gap support with snubber on hanger 2MCA-ND-5484 1850786 22 B Replaced gap support with snubber on hanger 2MCA-ND-5485 1864184 19 B Modified hanger 2MCA-RN-3215 per EC99741 1864184 39 B Modified hanger 2MCA-RN-3215 per EC99741 1865842 16 B Installed hanger 2MCR-RV-4173 per EC99747 1865842 26 B Deleted hanger 2MCR-RV-4112 per EC99747 1865844 16 B Modified item# 9 on hanger 2MCA-RV-511 per EC99747 1883394 1 B Replaced disc in valve 2NV1047 1892972 3 B Installed 4 item# 8s (1/2" x 3 1/2" x 6" plates) on hanger 2MCR-NS-4767 per EC101538 1897283 11 B Replaced bolting material in flange 2NVFE5300 1897290 7 B Replaced bolting material in flange 2NVFE5330 1900003 4 B Replaced valve 2NV155
1900647 5 B Replaced relief valve 2NV229 Page 2 of 2 1907056 14 B Replaced item# 7 (2 x 2 tube steel) on hanger 2MCA-NV-5050 per EC104199 1907056 2 B Replaced valve 2NV494 and piping per EC104199 1922371 1 B Replaced snubber on hanger 2MCA-SM-20 1922374 1 B Replaced snubber on hanger 2MCA-CA-60 1923830 2 B Replaced #4 rear valve and #5 cone valve in snubber for 2D Steam Generator 1923837 19 A Replaced bolting materialon hangers 2MCR-NV-4379, 4380, and 4381 per EC105482 1923857 28 B Replaced pivit pin on hanger 2MCA-NV-6523 1923857 45 A Replaced snubber on hanger 2MCR-NC-4000 1923857 49 B Replaced load pin in hanger 2MCR-NI-4589 1923857 62 B Replaced snubber on hanger 2MCA-BB-5218 1923857 68 B Replaced snubber on hanger 2MCR-S-VS-150-01-l 1923857 69 B Replaced snubber on hanger 2MCR-NI-4918 1923857 75 B Replaced snubber on hanger 2MCR-NV-4483 1923857 76 B Replaced snubber on hanger 2MCR-ND-6326 1924239 4 A Replaced valve 2NC1 1925900 $ B Installed items 8, 9, and 10 on hanger 2MCR-NS-4516 per EC101538 1927185 2 B Replaced disc and yoke on valve 2WL1302 1929198 6 B Replaced bolting material in pipe clamp on hanger 2MCR-NV-5192 1930670 89 B Replaced snubber on hanger 2MCA-NV-5405 1932306 2 B Replaced disc in valve 2NV248 1933815 7 A Replaced disc and bonnet nuts on valve 2NI71 1972897 2 B Made weld repair on weld NV2FW183-28 1973388 5 B Welds NV2FW293-12, 38, and 39 were cut out and remade 1974289 2 A Replaced bolting material in flange down stream of valve 2NV180
FORM NIS-2 OWNER'S REPORT FO. gPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duke- Energy Carolinas, LLC --- Date 4/3/2011 526 South Church Street, Charlotte, NC, 282.01 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 592075-13 Address Work Order # (or Repair/Replacement Organization P.O No .lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Name Type Code Symbol Stamp: N/A Authnrizatinn Nn : N/A 526 South Church Street, Charlotte, N.C._2.8_20.!.:.1..0_06 ....-......
Address Expiration Date: N/A
- 4. Identification of System BB - Steam Generator Blowdown Recycle
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition withthe_.1_999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2BB6 Borg Warner 9081 90 N/A 1976 Removed Yes 2BB6 Flowserve 02BPK 2503 N/A 2009 Installed Yes
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description valve 2BB6 was cut out and replaced
- 8. Tests Conducted: Hydrostatic " Pneumatic - Nominal Operation Pressure F Exempt F Other r- Pressure 910 PSI Test Temp. 53.9 IF Description (Optional): test performed per procedure M.P/O/A/7650/076.
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY
" As Required by the Provisions of the ASME Code Section X1
- 9. Remarks.(Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nomiCnal) System Class: ASME Class_2 Weld Isometric Drawing No(s).: MCFI-2BB60 & 62 Flow Diagram No(s).: MCFD-2580-Ol .00 Support/Restraint'Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCM 1205.00-0381 001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date IN/A Signed FL Grass, Quality Assurance Technical Specialist Date April 3 20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
- North Carolina nA - . ,.Hartford Steam Boiler Inspection and Insurance Company ý4ý
..Connecticut have inspected the components described in this Owner's Report during the period k- /b to '- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither th nspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fro r connected with this inspectio JF Swan ] /!".-" Commissions NC1524, N-1 Inspector's Signature -V National Board, State, Province, and Endorsements F)Atp.
Dt~te.
r) 2o_-R 20]]
FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*
As Required by the Provisions of the ASME Code,Section III, Division 1 2 Pg. 1 of
- 1. Manufactured and certified by Flowserve Corporation, 1900 South Saunders St. Raleigh, NC 27603 Itame and address of N Certificate Holder)
- 2. Manufactured for Duke Energy PO Box 37925 Charlotte, NC 28237 Inmanmand address of Purchaser)
- 3. Location of installation McGuire Site 13225 Hagers Ferry (HWY 73) Huntersville, NC 28078-8985 enameand addr*ss)
- 4. Model No., Series No., or Type 1500' Gate Valve Drawing 74450 Rev. C CRN N/A
- 5. ASME Code,Section III, Division 1: 1971 Summer 1973 2 N/A (edition) (addenda date) (class) lCode Case no.)
- 6. Pump or valve Valve Nominal inlet size 2 Outlet size 2 (in.) (in.)
- 7. Material:
(a) valve Body SA182-F316 Bonnet SA182-F316 Disk SA351-UO' Bolting N/A (b) pump Casing Cover Bolting la) * (bW (c) (d) (e)
Cert. Nat'l Body/Casing Bonnet/Cover Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.
.18427-1-1 02BPK/ 2503 / A2-76// N9519-6 03BPK ," 2504 A2-77 38427-1-2 N9519-7 1
- Supplemental information in the form of lists, siketches. or drawings may be used provided (41 size is 8 /%x 11, (2) information in items 1 through 4 on this Data is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the lop of this form.
I'll
FORM NPV-1 (Back - Pg. 2 of )
S02BPK/ANDO03BPK' Certificate Holder's Serial No.
- 8. Design conditions 1200 pso 567 tF or valve pressure class 1500 (lcrsa~areI ttemptratui el
- 9. Cold working pressure 3600 psi at 100T 5400 3960
- 10. Hydrostatic lest psi. Disk differential test pressure psi
- 11. Remarks: S.0- 53881 DRAIN PIPE- MATI: SA312-304, HEAT: 801951 CERTIFICATION OF DESIGN R.E.Miller RE. State SC Reg. no. 4237 Design Specification certified by Design Report certified by N/A PE. State N/A Reg. no. N/A CERTIFICATE OF COMPLIANCE We certify that the statements made in this report ate correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.
N-1562 Expires 11-26-09 N Certificate of Authorization No.
Date ',_-9* Name Flowserve Corporation IN Ce~sficele I-QIderlta.,
Signed ed pfcscfnLaloe)
CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province and employed by HSB CT of NC of Hartford, CT have inspected the pump, or valve, described in this Data Report on
,and state that to the best of my knowledge and belief, the Certificate Holder has constructed this pump, or valve.
in accordance with the ASME Code,Section III, Division 1.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or properly damage or a loss of any kind arising from or connected with this inspection.
Date ol / Signed Commissions A)B /7o,9/t/( e-L/5Y7 I Auflthorizad Nuclear Insp.tq lNatl. 1d. fincl. endorsements end state or pov. and no.)
FORM NIS-2 OWNER'S REPORT FO, -PAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LLC . Date 4/12/2011 526.Sou.th..Chu-urch Street., Charlotte,.NC, 28201 1 of 2 Address Sheet
- 2. Plant McGuire Nuclear Station Unit 2 Narne 1.2700 Hagers Ferry Road, Huntersville, NC 28078 592077-03 Address 592077-03 Work Order # (or Repair/Replacement Organization P.O. No., lob No , etc
- 3. Work Performed by Duke Energy Carolinas, LLC Name Type Code Symbol Stamp: N/A Authorization No.: N/A 526 South Church Street, Charlotte, NC 2820 1-1006 Address Expiration Date: N/A
- 4. Identification of System BB - Steam Generator Blowdown Recycle
- 5. (a) Applicable Construction Code ASME 111 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Editioh with the_19.99.and 2000 Adde.nda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Nane of alttfacturcr Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-BB-4520 Duke Energy N/A N/A N/A N/A Installed No
- 7. Description of Work Replaced CopretprtApreac Additional Description replaced pivot pin in rear bracket on hangrer 2MCR-BB-4520.
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F Exempt Fý Other F- Pressure PSI Test Temp. _ °F Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASME.Class2 Weld Isometric Drawing No(s).: MCFI-2BB60 & 63 Flow Diagram No(s).: MCFD-2580-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCR-BB-4520 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requiremnents of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist ,Q: ,*,A. Date April 12 _ 20.11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by .Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period Zto _* /2- .- //Z, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither t e Inspector nor his employer shall be liable in any manner for any persdnal injury or property damage or a loss of any kind arising fro or connected with this inspectio JF Swan O 2.21v0-tj- - Commissions NC1524, N-I Inspector's Signature National Board, State, Province, and Endorsements Dat/ 20 20 /1
//
Dat
FORM NIS-2 OWNER'S REPORT FOK JIPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke. Energy Carolinas, LLC Date 4/3/2011 526_South Church Street, Charlott.e.,.NC, 2820-1... Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28.078 592077-15 Address Work Order # (or Repair/Replacement Organization P.O. No, Job No., etc
- 3. Work Performed by Duke Energy Carolinas, LLC. rp,*
,, r-,*, 1 .,Q.11 IQ... N/A Name Authorization No.:
526 South Church Street, Charlotte, NC.2820! .-1006 Address Expiration Date:
- 4. Identification of System BB - Steam Generator Blowdown Recycle
- 5. (a) Applicable Construction Code ASME Ill 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacernent Activity 1998 Edition with .the 19.99 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Serial No. Board No. Identification Built Installed (Yes or No)
Name of Manut'acturerSeilNBorNodetfctoBut nald(YsrNo 2BB8 Borg Warner 9087 95 N/A 1976 Removed Yes 2BB8 Flowserve 04BPK 2501 'N/A 2009 Installed Yes
- 7. Description of Work Replaced Componen.t/Part/Apipiureenance Additional Description valve 2BB8 was cut out and replaced
- 8. Tests Conducted: Hydrostatic - Pneumatic r Nominal Operation Pressure Exempt r. Other Fl- Pressure 910 PSI Test Temp. 53.9 OF Description (Optional): test performed. per procedure MP/0/A/7650/076.
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X1
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) Systern Class: ASMEClass_2 Weld Isometric Drawing No(s).: MCFI-2BB60 & 63 Flow Diagram No(s).: MCFD-2580-01.00 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: :MCM 1205.00-0381 001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist - Date April 3 ,20 11 Owner or Owner's Designee, Title CERTI FICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by :Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
.*2 7- to - /Z' ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the I tor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from i connected with this inspection.
- JF Swan Commissions NC1524, N-i
,.. Inspector's Signature "
.- National Board, State, Province, and Endorsements LI
FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*
As Required by the Provisions of the ASME Code,Section III, Division 1 Pg. 1 of__
- 1. Manufactured and certified by. Flowserve Corporation, 1900 South Saunders St. Raleigh. NC 27603 Iname and address of N Ceitilicate Holdai)
- 2. Manufactured for Duke Energy PO Box 37925 Charlotte, NC 28237 Insme and address oi Puidrascil
- 3. Location of installation McGuire Site 13225 Hagers Ferry (HWY 73) Huntersviile, NC 28078-8985 Inama and address)
- 4. Model No., Series No., or Type 1500# Gate Valve Drawing 74450 Rev. C CRN N/A
- 5. ASME Code, Section I11,Division 1: 1971 Summer 1973 2 N/A (ediSon) (addenda date) Wclass) lCode Case no.)
- 6. Pump or valve Valve Nominal inlet size 2 Outlet size 2 jin.) tin.)
.7. Material:
(a) valve Body SA182-F316 Bonnet SA182-F316 Disk SA351-8M Bolting N/A (b) pump Casing Cover Bolting (a) Wb (c) (d) let Cen. Nat'l Body/Casing BonneVCover Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.
04BPK 2501 A2-78 38427-1-3 N9519-8~
OSBPK 2502 A2-79 18427-114 N9519-9 y I supplemental information in the form of lists, sketches, or dfawings may be used provided 11) size is 8112x 11. (2) information in items I through 4 on this Data Report is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
rn~so(%/7
FORM NPV-1 (Back - Pg. 2 of _ _
02BPK THRU OSBPK Certificate Holder's Serial No. 02_PK___________
- 8. Design conditions 1200 psi 567 t or valve pressure class 1500 lprfessul tli pecralne)
- 9. Cold working pressure 3600 psi at 100'F s40Oo 3960
- 10. Hydrostatic test psi. Disk difleiential test pressure psi
- 11. Remarks: S.O. 53881 f DRAIN PIPE- MATL: SA312-304. HEAT; 801951 CERTIFICATION OF DESIGN Design Specification certilied by R.E.Miller RE. State SC Reg. no.4237 Design Report certified by N/A RE. State N/A Reg. no. N/A CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.
N-1562 Expires 11-26-09 N Certificate of Authorization No.
Date Name Sge in IN Certie c Holdel) Seientgdne "oor CERTIFICATE OF INSPECTION I, the undersigned, holding a vaiid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NC and employed by HSB CT of Hartford, CT have inspected the pump, or valve, described in this Data Report on 9 2A
"* , and state that to the best of my knowledge and belief, the Certificate Holder has constructed this pump, or valve, in accordance with.the ASME Code,Section III, Division 1.
By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date l Commissions (AU:,J ze uclteo Irnspacror tNarl. Bd. (incl. endoisenen it3land state Of prOi. and no.l p 63ro/'7:
FORM NIS-2 OWNER'S REPORT F. *EPAIP/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 1. Owner Duke Energy Carolinas,.LL C .. Date 4/12/2011 526.So.uthChurch Street,. Charlotte, NC_, 28201 .. Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, _Huntersville, NC 28078 592077-24 Address Work Order # (or Repair/Replacement Organization P.O. No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street,..Ch.arlotte,._NC 28201-1006 N/A Address Expiration Date:
- 4. Identification of System BB - Steam Generator Blowdown Recycle
- 5. (a) Applicable Construction Code ASME I11 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity .19.98 Edition with_the._199.9..and 2.000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of' Manufacturer National Other Year Removed, or Stamped ComponentIntle YsoN)
Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-BB-4519 Duke Energy N/A N/A N/A N/A in!Pstalled No
- 7. Description of Work Re placed Component/Part/Apputecnance Additional Description re~placed bolting material in pipe clamp on hanger 2MCR-BB-45 19.
- 8. Tests Conducted: Hydrostatic F Pneumatic F- Nominal Operation Pressure iF Exempt F Other F Pressure -PSI Test Temp. _
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASME.Class 2 Weld Isometric Drawing No(s).: MCFI-2BB60 & 63 Flow Diagram No(s).: .MCFD-2580-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCR-BB-4519 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date ýApril 12 ,20W.l Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
-'2- 7-62 /( to /-7./'Z.2 ,.--, ., and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Insp tor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspection.
JF Swan' = .*Commissions NC 1524, N- I Inspector's Signature ----- ational Board, State, Province, and Endorsements L - /Z- ,20/_/_
FORM NIS-2 OWNER'S REPORT F REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duk.e Energy Carolinas, LL LC Date 4/3/2011 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers .Ferry Road, H.untersviIlle,.N.C 28078 1840801-02 Address Work Order # (or Repair/Replacement Organization P 0. No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC ..... N/A Name Type Code Symbol Stamp:
Authorization *No.: N/A 526 South Church Street,.Ch.arlotte, NC 28_20.1-1006 Address Expiration Date: N/A
- 4. Identification of System VI - Instrument Air
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with..the .19.99 an-d_2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Mantfacttrer Serial No. Board No.. Identification Built Installed. (Yes or No) 2V 1149 Kerotest S20-15 N/A N/A 1973 In.s*talled Yes
- 7. Description of Work Re placed Component/Part/Appurtenance Additional Description replaced soft seat disc in valve 2V1149.
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure Exempt F Other F Pressure PSI Test Temp. _ °F Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASNIE Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) SystemDClass: ASMEClass2 Weld Isometric Drawing No(s).: MCFI-2VI29 Flow Diagram No(s).: MCI FD-2605-Ol .02 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2V1-250 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section.XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date April 3 ,20 il Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
,,_ t.- / Z to " and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither t Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from r connected with this inspectio JF Swan Commissions NC1524, N-I National Board, State, Province, and Endorsements DateU- ", 20//
FORM NIS-2 OWNER'S REPORT I REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the .-\SME Code Section XI
- 1. Owner Duke Energy Carolinas, LL'C Date 3/31/20 I1 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1841062-03 Address Work Qrder # (or Repair/Replacement Organization P 0. No.. lob No , etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Statnp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 Address Expiration Date: N/A
- 4. Identification of Systern VB - Breathing Air
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI CodeCase(s) N/A
- 6. Identification of Components Corrected, ASME Code Namne of Matnufacturer National Other Year Removed, or Stamped Component ofMaUfacturer Serial No. Board No. IdenTification Built Installed (Yes or No) 2VB50 Anderson Greenwood N 15025 26 N/A 1982 Installed Yes
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description replaced bolting material at valve 2VB50.
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure [F Exempt F- Other r- Pressure PSI Test Temnp. _ IF Description (Optional): test performed per procedure MP/0/A/7700/045.
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section X I
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2) in. (nomninal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: MCFI-2VB3 Flow Diagram No(s).: MCFD-2605-03.Ol Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manutacturer'.s Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist .,,Date March,31 -. l Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period Co-nnci -c / to - ?-- h to the best of my knowledge and belief, the Owner has performed examinations and taken corrective
, and state that measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner'A Report. Furthermore, neither the spector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any. kind arising from/ connected with this inspection.
JF Swan =- Commissions NC1524, N-I Inspector's Signature ,." National Board, State, Province, and Endorsements Dat C -)0_/a Dat 20/L
FORM NIS-2 OWNER'S REPORT FC .ýEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LILC Date 3/22/2011 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-06 Address Work Order l9(or Repair/Replacement Organization P.O. No.. lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 Address Expiration Date: N/A
- 4. Identification of System FW - Refueling Water
- 5. (a) Applicable Construction Code ASME I1l 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1.9.99 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Maltlttfcturer National Other Year Removed, or Stamped Component Nate of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No)
Duke Energy N/A N/A N/A N/A Installed No 2MCA-FW-5009
_____________ J -~ 4- 4 4 1 4- +
- 7. Description of Work Re: placed Component/Part/Appurtenance Additional Description tnodified hanger 2MCA-FW-5009 per MGMM 15247
- 8. Tests Conducted: Hydrostatic F Pneumatic r- Nominal Operation Pressure [- Exempt . Other r Pressure PSI Test Temp. _ °F Description (Optional): -
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 24 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A
- Flow Diagram No(s).: MCFD-257 1-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-FW-5009 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM 15247, MCSRD-2FW-350-001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist . Date March 22 201L Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period Q--. /c/o to 2 2
- // , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Ins tor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or onnected with this inspection.
JF Swnom SInspector's Signature 7,,,.
.Commissions NC 1524, N- I National Board, State, Province, and Endorsements Dat e0 -. 20 /
FORM NIS-2 OWNER'S REPORT FO. .EPAIRJREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LI LC Date 3/22/2011 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-07 Address Work Order # (or Repair/Replacernent Organization P 0) No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A N*lve Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 Address Expiration Date: N/A
- 4. Identification of System FW - Refueling Water
.5. (a) Applicable Construction Code ASME Ill 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section X1 used for Repair/Replacement Activity 1998 Edition with the 1999 and 2.000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufaclurer National Other Year Removed, or Stamped Component Name of Manutitclurer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-FW-5185 Duke Power N/A N/A N/A N/A Removed No
- 7. Description of Work dther (Describe Below)
Additional Description deleted hanger 2MCA-FW-5 185
- 8. Tests Conducted: Hydrostatic Pneumatic F- Nominal Operation Pressure F Exempt F Other F Pressure __ PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 12 in. (nominal) System Class: ASME Class.2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-257 1-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-FW-5185 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM 15247, MCSRD-2FW-350-005 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality, Assurance Technical Specialist - /Date March 22 ,20 11 Owner or Owner's Designee, Title CERTI FICATE OF INSERV ICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina *and employed by Hartford Steam Boiler Inspection and Insurance Company of
.Connecticut have inspected the components described in this Owner's Report during the period 2~ -.. / 1Z: to / and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from o,, connected with this inspection JF Swan V 0,,,ý. Commissions NC1524,N-I Inspector's Signature 1/ National Board, State, Province, and Endorsements Date d 20o//
Date 20 /1
FORM NIS-2 OWNER'S REPORT FL HEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LL C -Date 3/22/2011 526 South Church Street, Charlotte, NC, 2820 1 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville,.NC 28078 1850786 Address Work Order # (or Repair/Replacement Organization P.O. No., lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Name Type Code Symbol Stamp: N/A Authorization No.: N/A 526 South Church Street, Charlotte, NC 2.820 1-.1006 Expiration Date: N/A Address
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME I11 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999_and 2000 Addenda.
(c) Applicable Section X1 Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Buiilt Installed (Yes or No) 2MCA-ND-5483 Duke Energy N/A N/A N/A N/A Removed No 4- F + 4 +/-
- 4. F t -r i
+ F t r -r i T
.1. 5 F + 4 +
_____________________ +/-
- 7. Description of Work Other (Describe Below)
Additional Description Deleted hanger 2MCA-ND-5483
- 8. Tests Conducted: Hydrostatic F Pneumatic "- Nominal Operation Pressure F Exempt F" Other F Pressure IPSI Test Temp. _ °F Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet of 2 Component Line Size: 14 in. (nominal) SystemFClass: ASME CFass20 Weld Isometric Drawing No(s).: MCFI-2ND3 Flow Diagram No(s).: MCFD-MvCFD-256 1-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5483 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM 15247, MCSRD-2FW-350-005 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist , Date March 22 , 201L_
Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
.North Carolina and employed by Hartford Stearn Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
- to 2-2-. - ii , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.
By signing this certificate neither the Inspector nor his employer makes any warrantvy expressed or implied, concerning the examinations and corrective rneasures described in this Owner's Report. Furthermore, neither t# Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from( connected with this inspectio JF Swan 0, y, -.. .- Commissions NC1524, N-I Inspectors Signature , National Board, State, Province, and Endorsements D teý-2 - , 20//'
FORM NIS-2 OWNER'S REPORT F( .ýEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke.Energy Carolinas, LLC . Date 3/22/2011 526. South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-09 Address Work Order I (or Repair/Replacement Organization P.O No., lob No, etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Naine Type Code Symbol Stamp: N/A Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 Address Expiration Date: N/A
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME Il l 1971 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2.000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASIM E Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5487 Duke Energy N/A N/A N/A N/A Removed No
- 7. Description of Work Other (Describe Below)
Additional Description Deleted hanger 2MCA-ND-5487
- 8. Tests Conducted: Hydrostatic F- Pneumatic F Nominal Operation Pressure F Exempt F Other F Pressure __ PSI Test Ternp.. _ '
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 2 of 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet Component Line Size: 14 in. (nominal.) System Class: ASME Class.2 Weld Isometric Drawing No(s).: MCFl-2ND3 Flow Diagram No(s).: MCFD-256 1-0 1.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5487 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM 15247, MCSRD-2FW-350-005 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A
-*Z,/,-_ D/
Date March 22 ,20jL Signed FL Grass, Quality Assurance Technical Specialist -,,,
Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by, Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
- -. to 2- / and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore; neither the Ins ctor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from o ed with this inspection.
JF Swan re Commissions NC 1524, N-I f National Board, State, Province, and Endorsements Dt I[nspector's Signature Date 6- -2 I 20./1 (
FORM NIS-2 OWNER'S REPORT FC .EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI I. Owner Duke Energy Carolinas, LILC Date 3/21/2011 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire NuclearrStation Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-10 Address Work Order # (or Repair/Replacement Organization P.O. No., Job No, etc.)
- 3. Work Performed by Duke Energy.Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South. Church Street,_-Charlotte,. NC 28201-1006.
Address Expiration Date: N/A
- 4. Identification of System FW - Refueling Water
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-FW-5184 Duke Energy 38039 N/A N/A N/A Installed No
- 7. Description of Work Rep)laced Component/Part/Appurtenance Additional Description Reeplaced gap support with snubber on hanger 2MCA-FW-5 184
- 8. Tests Conducted: Hydrostatic - Pneumatic r-" Nominal Operation Pressure r- Exempt F Other F Pressure PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X I 2 of 2
- 9. Remarks (Should Include the Follow ingaInformation, as Applicable): Sheet Component Line Size: 12 in. (nominal) System Class: ASME'Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-257 1-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-FW-5184 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist ./ . -- Date 'March 21 ,20 1I Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and emplnvoyed b Hartford Steam Boiler Inspection and Insurance Company
-'J of Connecticut have inspected the components described in this Owner's Report during the period
.- 2/7"// / to _S-2 2--g( " ,and state that to the best of my knowl6dge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner' Report. Furthermore, neither the spector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspection.
JF Swan Commissions NC1524, N-1
/
II~~pcLI0I ~ .J~~gI~a~uI~,r 014 U IN~Ij~
1N4aLtIion oar l, tatel,
- 44C UIUCIUICIC rlUVl ce, anll Av~s nlUUrsernetsli InpctrsSi ntr2_*
Dat 6 1 , 20__/
FORM NIS-2 OWNER'S REPORT FO EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LILC Date 3/21/2011 526 South Church Street, Charlotte, NC, 28.201 Sheet I of 2 Address 2, Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-11 Address Work Order # (or Repair/Replacement Organization P.O. No., .Job No., etc
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC ._28201-1006 Address Expiration Date: N/A
- 4. Identification of System FW - Refueling Water
- 5. (a) Applicable Construction Code ASME III 19 7_1 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section X I used for Repair/Replacement Activity 1998. Edition with the_19_99.9_and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stampedo Cotmponentitsald (Yso Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-FW-5103 Duke Energy 38040 N/A N/A N/A Installed No
- 7. Description of Work Re placed Component/Part/Appurtenance Additional Description Rteplaced gap support with snubber on hanger 2MCA-FW-5 103
- 8. Tests Conducted: Hydrostatic " Pneumatic F Nominal Operation Pressure F Exempt P. Other F Pressure -PSI Test Temp. _ °F Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of Component Line Size: 18 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2563-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-FW-5103 Other Applicable Information (e.g., W.O. No., EC No.) if ndt included elsewhere on NIS-2 Form: MGMM 15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist "DateMarch 21 20_11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina aHartford Steam Boiler Inspection and Insurance Company Norh .and aroin employed by _____________________________________of Connecticut have inspected the components described in this Owner's Report during the period 13 / / -
-- -/1 to 3 - 2. Z -l(e, and state that to the 'best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's eport. Furthermore, neither the I ector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from o onnected with this inspection.
JF Swan Commissions NC 1524, N-I I / Inspector's Signature National Board, State, Province, and Endorsements I
FORM NIS-2 OWNER'S REPORT FO .EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LI-C Date 3/21/2011 526.South Church Street, Charlotte, NC, 28201. Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-12 Address Work Order # (or Repair/Replacernent Organization P.O. No., lob No. etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-.1006 Address Expiration Date: N/A
- 4. Identification of System FW - Refueling Water
- 5. (a) Applicable Construction Code ASME III 19 7_1 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section Xf Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of' Manufacturer National Other Year Removed, or Stamped Component Serial No. Board No. dentification Bult Installed (Yes or No)
Name of39Ma8N//cturerS No 2MCA-FW-5 181 .Duke Energy 37958 N/A N/A N/A Installed No
- 7. Description of Work ReF laced Component/Part/Appurtenance Additional Description Reeplaced gap support with snubber on hanger 2MCA-FW-5 181
- 8. Tests Conducted: Hydrostatic F Pneumatic F' Nominal Operation Pressure F Exempt F Other F- Pressure PSI Test Temp. _ IF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 24 in. (nominal) System Class: ASMECass.2.
Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2563-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-FW-5181 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere oin NIS-2 Form: MGMMI5247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March21 50f11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
.North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period Z .3 2
- -/ ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner' Report. Furthermore, neither t Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspectio JF Swan Commissions NC 1524, N-I Inspector's Signature National Board, State, Province, and Endorsements Date () 3 Z - - ,210 Itl
FORM NIS-2 OWNER'S REPORT FO. ..EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LLC Date 3/21/2011 526 South Church Street, Charlotte, NC, 28201 I of 2 Address Sheet
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville,.NC 28078 1850786-13 Address Work Order 9 (or Repair/Replacement Organization P 0 No., ,Job No., etc.)
- 3. Work Performed by Du.k.e Energy Caro.linas, LLC Name Type Code Symbol Stamp:
Authorization No.:
526 South Church Street, Charlott., NC 2820 1--1006 Address Expiration Date:
- 4. Identification of System ND - Residual Heat Removal
- 5. (a).Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity 1998 Ed[ition with the 1999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Comn)onents Corrected. ASME Code Name of Manufacturer National Other Year Removed. or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5204 Duke Energy 36142 N/A N/A N/A Installed No
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description Replaced gap support with snubber on hanger 2MCA-ND-5204
- 8. Tests Conducted: Hydrostatic - Pneumatic F Nominal Operation Pressure F Exempt F Other I- Pressure PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions ofthe ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 12 in. (nominal) System Class: ASME Class.2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2561-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5204 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM 15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Grass, Quality Assurance Technical Specialist SignedFL ,Date.March 21 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period to 3 -- /(and state that to the best of my knowledge and.belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his ployer makes any warranty, expressed or implied, concerning the examinations and corrective.measures described in this Owner's eport. Furthermore, neither the Ins 'tor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from o nnected with this inspection.
. Swan Commissions NC1524, N-I eNational Board. State, Province, and Endorsements
FORM NIS-2 OWNER'S REPORT Ft AEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duke Energy Carolinas, LL C Date 3/21/2011 526 South Church Street, harlotte,.NC_28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-14 Address 1850786-14 Work Order # (or Repair/Replacement Organization P.O No, Job No , etc
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 N/A Address Expiration Date: N/A
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME Il1 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition W\ith the..1999 and 2000 Addenda (c) Applicable Section XI Code Case(s).N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name ofManufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5280 Duke Energy 37464 N/A N/A N/A Installed No
- 7. Description of Work Rel placed Component/Pa&Appurtgrance Additional Description Rt eplaced gap support with snubber on hanger 2MCA-ND-5280
- 8. Tests Conducted: Hydrostatic F Pneumatic -- Nominal Operation Pressure r- Exempt F Other F Pressure .PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASNIE Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 12 in. (nominal) System Class: ASMEClass_2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2561-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5280 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE, I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist March 21
- MDate 2011
- Owner or Owner's Designee, Title /
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
.North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
$ .Lf zZ- ..." to Is 2 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Fuermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from9 connected ith this inspection.
JF Swan Commissions NC1524, N-1 National Board, State, Province, and Endorsements C ~n~'r~ctor's Signature Date , 2-, 20fL
FORM NIS-2 OWNER'S REPORT FG-- AEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duke Energy Carolinas, LI £C Date 3/21/2011 526 South. Church Street, Charlotte, NC, 28201 Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name
.12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-15 Address Work Order 9 (or Repair/Replacemnent Organization P.O. No.. Job No., etc
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Ch.arlotte. N.C 28201 -.1006 N/A Address Expiration Date:
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity .199 _Edition with the 1999 and 2000 Addenda._
(c) Applicable Section Xl Code Case(s) N/A
- 6. Ide~ntificntion of Cnmnone~nts Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5306 Duke Energy .37465 N/A N/A N/A Installed No
- 7. Description of Work Repplaced Component/.Part/Appurtenance Additional Description Retplaced gap support with snubber on hanger 2MCA-ND-5306
- 8. Tests Conducted: Hydrostatic r Pneumatic F Nominal Operation Pressure F Exempt F Other F Pressure PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 12 in. (nominal) System Class: ASMEClasss 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2561-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5306 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM15247 Applicable Manufacturer's Data Reports to be attached
- CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A
- ,20 Signed FL Grass, Quality Assurance Technical Specialist Date :March 21 ,2'IlI Owner or Owner's Designee, Title CERTI FICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
.3*.-*.'to S . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthennore, neithe ie Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fro or connected with this ins t JF Swan Commissions NC1524,N-I Inspector's Signature / National Board, State, Province, and Endorsements
/
I
FORM NIS-2 OWNER'S REPORT FO. .EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LILC Date 3/21/201'l
.52.6__South Church Street, Charlotte,NNC,2820_ .. .. . Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-16 Address Work Order # (or Repair/Replacement Organization P 0. No., .lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 2§1201-1.I006 N/A Address Expiration Date:
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME III 19 7_1 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity 1998 Edition with the.1.9.9.*.and _2.000_Ad~dend.a (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5311 Duke Energy 37466 N/A N/A N/A Installed No 4 4 4 5 +
4 4 4 5 +
5 4 4 1 5 +/-
- 7. Description of Work Relplaced Comp onnt/Par/Appiurtenance Additional Description R eplaced gap support with snubber on hanger 2MCA-ND-531 I
- 8. Tests Conducted: Hydrostatic F Pneumatic F' Nominal Operation Pressure F Exempt F7 Other -- Pressure PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 2 of 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet Component Line Size: 12 in. (nominal) System Class: ASM.E Class.2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-256 101.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5311 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A 2 11 D
Signed FL Grass, Quality Assurance Technical Specialist Date March 21 ,2011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
,to -Z.2 -/ ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner' Report. Furthermore, neither th Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from1connected with, this inspection.
JF Swan_* 2 7A._ -. ^ - Commissions .NC1524, N-I Inspector's Signature O ooý National Board, State, Province, and Endorsements Date- 20-/
FORM NIS-2 OWNER'S REPORT FO. _,*EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LLC .. .- Date 3/21/2011 526 South Church Street, Charlotte,. NC, 28201 . I of 2 Address Sheet
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-17 Address Work Order 9 (or Repair/Replacement Organization P 0. No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Name Type Code Symbol Stamp:
Authorization No.:
526 South Church Street, Charlotte, NC 2820 1-1006 Address Expiration Date:
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edlition with the- 1999 and 200.0 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5405 Duke Energy 37467 N/A N/A N/A Installed No
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description Replaced gap support with sntibber on hanger 2MCA-ND-5405
- 8. Tests Conducted: Hydrostatic " Pneumatic F]- Nominal Operation Pressure F Exempt WF. Other F Pressure PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of (he ASME Code Section X1
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 14 :in. (nominal) System Class: ASME Class_2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2561-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5405 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM 15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 21 ,2011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of
.Connecticut have inspected the components described in this Owner's Report during the period 54 /-- to 12.2-/, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner' eport. Furthermore, neither the I ector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from onnected with this inspection.
417 Swan tCommissions NC1524, N-I
-nspector's Signature / F National Board, State, Province, and Endorsements Date C'j -S, - ?,"2-- _ , 20_A/
FORM NIS-2 OWNER'S REPORT. A REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 1. Owner DukeEn.ergy Carolinas, LLQ -Date 3/21/2011
.526 South Church.Street, Charlotte,..NC,.28201 Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, .Iuntersville, NC 28078 1850786-18 Address Work Order # (or Repair/Replacement Organization P.O. No., Job No., etc.)
- 3. Work Performed by Duke EnergyCarolinas, LLC Narne Type Code Symbol Stamp: N/A Authorization No : N/A 526 South Church Street, C.harlotteNC .?820-.0.6 1N/A Address Expiration Date:
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity _1998.Ed.i.tion with .th-e 1_999.and.2000_Add-en-da__
(c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manmfactttrer National Other Year Removed, or Stamped Component Installed (Yes or No)
Name oftManufacturer Serial No. Board No. ldeniication Bil(
2MCA-ND-5461 Duke Energy 37640 N/A N/A N/A Installed No 2MCA-ND-5461 Duke Energy 37468 N/A N/A N/A Installed No
- 7. Description of Work Replaced Comip onent/Part/Appurtenance Additional Description Replaced two gap supports with two snubbers on hanger 2MCA-ND-5461
- 8. Tests Conducted: Hydrostatic 7 Pneumatic [- Nominal Operation Pressure F Exempt F. Other [7 Pressure PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section X I
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 14 - in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: IVICFD-2561-Ol .00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5461 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM 15247 Applicable Manufacturer's Data Reports'to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist -.--Date March 21 ,20 li Iw Owner or Owners e orO Designee, Title nrsDsIne il CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina , . . ,, Hartford Steam Boiler Inspection and Insurance Company have inspectd te cy U0 Connecticut have inspected the components described in this Owner's Report during tihe period m - /d7- a to L-3 2 -- - // , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fron* or connected with this inspec/n.
JF Swan V .*,- /.Commissions Inspector's Signature NC1524, N-1 National Board, State, Province, and Endorsements Date(I 20 //
Dates 20J/
FORM NIS-2 OWNER'S REPORT FO. .,EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LILC Date 3/21/2011
.5.2. South Church Street, Charlotte, NC, 28201 . Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-19 Address 1850786-19 Work Order 9 (or Repair/Replacement Organization P.O No., Job No, etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 52.6 South Church Street, Charlotte, NC 2_8201 -1006 .. Dt:./
Address Expiration Date: N/A
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity .1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Comn onents Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Matiracturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5480 Duke Energy 37469 N/A N/A N/A Installed No
- 7. Description of Work Repplaced Component/Part/Appurtenance Additional Description Re eplaced gap support with snubber on hanger 2MCA-ND-5480
- 8. Tests Conducted: Hydrostatic F Pneumatic F- Nominal Operation Pressure F Exempt F. Other F Pressure PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 2 of 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet Component Line Size: 14 in. (nominal) System Class: ASMjE.CIass.2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-256l-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5480 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 21 ,0 1 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut - have inspected the components described in this Owner's Report during the period
,12 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner'Report. Furthermore, neither the I pector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from o onnected with this inspection.
F Swan Commissions NC1524, N-I National Board, State, Province, and Endorsements Date U e Inspector's Signature 20//
FORM NIS-2 OWNER'S REPORT FO. -EPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LI C .. Date 3/21/2011 526 South _Church Street, Charlotte, NC, 2820! ... . . Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers.Ferry Road, Huntersville _NC(.2807.8_ 1850786-20 Address Work Order # (or Repair/Replacement Organization P.O. No., Job No, etc
- 3. Work Performed by DukeeEnergyCarolinas, LLC N/A Type Code Symbol Stamp:
Name Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-100_6 Address Expiration Date: N/A
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME Il1 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with-the 1999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5482 Duke Energy 37545 N/A N/A N/A Installed No
- 7. Description of Work Repilaced Component/Part/Appurtenance Additional Description Re placed gap support with snubber on hanger 2MCA-ND-5482
- 8. Tests Conducted: Hydrostatic r Pneumatic F- Nominal Operation Pressure Exempt f Other F Pressure PSI Test Ternp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR!REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 14 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2561-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5482 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the.report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 21 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
'North Carolina , . Hartford Steam Boiler Inspection and Insurance- Company
,,, H,,* r
.Connecticut have inspected the components described in this Owner's Report during the period
-Z.. to .33 z.2.i*
-. ., and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the nspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspection.
JF Swan (I.,,-t.'/ t Inspector's Signature -'-'
Commissions NC1524, N-I National Board, State, Province, and Endorsernents Dat(2 '; 22 20-L
FORM NIS-2 OWNER'S REPORT FO. .EPAIR1REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner .Duk.e. Energy Carolinas, LL C ..... Date 3/21/2011 526.South.Church Street, Cha.rlotte,. NC,.28201 .. . Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers FerryRoad,.Huntersvl lle, NC 28078 1850786-21 Address Work Order # (or Repair/Replacement Organization P 0. No, .Job No., etc )
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Starnp:
Authorization No.:
526 South Church Street, Charlotte, NC 2.8201-1006 N/A Address Expiration Date:
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1.9.98 Edition with t.he_1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name ofManufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5484 Duke Energy 37470 N/A N/A N/A Installed No
- 7. Description of Work Re placed Component/Part/Appurtenance Additional Description Rt eplaced gap support with snubber on hanger 2MCA-ND-5484
- 8. Tests Conducted: Hydrostatic r Pneumatic F Nominal Operation Pressure r Exempt Wl Other F Pressure .PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of- 2 Component Line Size: 14 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2561-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5484 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM15247 r
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist . Date March 21 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina Noh CHartford arid employed by Steam Boiler Inspection and Insurance Company o of
'Connecticut have inspected the components described in this Owner's Report during the period 7"to- 40,and -//, state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector norhis employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Ownerj# Report. Furthermore, neither thee spector nor his employer shall be liable in any manner for any personal injury or property' damage or a loss of any kind arising from connected with this inspection.
JF Swan _. Commissions NC1524, N-I Inspector's Signature National Board, State, Province, and Endorsements Date 1201!
20 //
(1 Date 2-22~
FORM NIS-2 OWNER'S REPORT FC EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LLLC Date 3/21/2011 S526..South Church Street, Charlot-te, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1850786-22 Address Work Order # (or Repair/Replacement Organization P 0 No., .lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC .
Name Type Code Symbol Stamp: N/A Authorization No.: N/A 526 South Church Street, C~harlo~tte,. NC 28201 -1006 ..
Address Expiration Date: "N/A
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME 111 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity .1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name ofManufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-5485 Duke Energy 37558 N/A N/A N/A Installed No
- 7. Description of Work Re placed Component/Part/Appurtenance Additional Description Rieplaced gap support with snubber on hanger 2MCA-ND-5485
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F Exempt F Other F Pressure PSI Test Temp. _ °F Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 14 in. (nominal) System Class: ASME Class_2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2561-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-5485 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MGMM15247 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 21 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by :Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
/ 7-/ to 3 / / , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nortis employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the spector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspection.
JF Swan . _____ _ _ _Commissions NC1524, N-I National Board, State, Province, and Endorsements Dat J" Inspector's Signature' 201-Date 20o//
FORM NIS-2 OWNER'S REPORT F(,- AEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LL*,C Date 3/21/2011 52.6 South Church Street, Tharlotte, NC, 28201 . .... ..... .. S heet I oof 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Narne 12700 Hagers Ferry Road, Huntersville, NC 28078 1864184-19 Address Work Order # (or Repair/Replacement Organization P.O. No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Name Type Code Symbol Stamp: N/A Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-10.06 Address Expiration Date: N/A
- 4. Identification of System RN - Nuclear Service Water
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity .1998 Ec [ition with. the 1999 and. 2000 A-ddenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-RN-3215 Duke Energy N/A N/A N/A N/A Installed No
- 7. Description of Work Replaced Cornponent/Part/Appurtenance Additional Description Modified hanger 2MCA-RN-3215 per EC99741
- 8. Tests Conducted: Hydrostatic r Pneumatic F Nominal Operation Pressure F Exempt F7 Other F Pressure .PSI Test Temp. _
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 6 in, (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2574-04.OO Support/Restraint Sketch/Drawing No(s).: 2MCA-RN-3215 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: EC99741, MCSRD-2RV-350-001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date :March 21 20:11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by :Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period I
7
-. , .to ._ 2- 2 =//and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied; concerning the examinations and corrective measures described in this Owner'seport. Furthermore, neither the I pector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or/c nnected with this inspection.
JF Swan___ _ ___Commissions NC1524, N-1 National Board, State, Province, and Endorsements Inspector's Signature Date 2-- , 2O _f
FORM NIS-2 OWNER'S REPORT FG.. REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASNIE Code Section XI
- 1. Owner Duke Energy Carolinas, LLC Date 3/24/2011
_5.26 South_ Church Street, Charlotte, NC, 28201 I of 2 Sheet Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road,-Huntersville, NC 28078 1864184-39 Address Work Order # (or Repair/Replacement Organization P.O No., Job No., etc.)
- 3. Work Performed by Duke Energy _Carolinas, LLC. S/IA Name Type Code Symbol Stamp: !XI Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 Expiration Date: N/A Address
- 4. Identification of System RN - Nuclear Service Water
- 5. (a) Applicable Construction Code ASME 111 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity -1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Nate of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-RN-3215 Duke Energ*y N/A N/A N/A N/A [nstalled No
- 7. Description of Work Replaced Component/Pra rt-/Appurtenanc9e Additional Description Modified hanger 2MCA-RN-32 15 per EC99741I
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F Exempt f7 Other F Pressure .PSI Test Tetnp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 6 in. (nominal) System Class: ASME Class_2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2574-04.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-RN-3215 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2RV-350-001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
N/A Type Code Symbol Stamp Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 24 ,20:11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina , .... ... , Hartford Steam Boiler Inspection and Insurance Company ýýF
.Connecticut have inspected the components described in this Owner's Report during the period
_ "22. - 61 to 2-.7'. // , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any varranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from r connected with this inspect IJF Swan 0. Commissions NC1524, N-1 m
Inspector's SignatUre""/ National Board, State, Province, and Endorsements D tea
FORM NIS-2 OWNER'S REPORT Fý_ -REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASMIE Code Section XI
- 1. Owner Duke Energy Carolinas, LLC Date 3/29/2011 526 South Church Street, Charlotte, NC, 28201 I of 2 Sheet Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 1.2700 Hagers Ferry Road, Huntersville, NC 28078 1865842-16 Address Work Order # (.or Repair/Replacement Organization P.O No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Namne Type Code Symbol Stamp: N/A Authorization No.: N/A 526 South Church Street, .Charlotte, N.C 28.201- 10.06 Address Expiration Date: N/A
- 4. Identification of System RV -
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Surnmer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity 1998 Edition with the 1.99.9 and2_2000.Ad-denda....
(c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Nane ot'ManufatUrer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-RV-4173 Duke Energy N/A N/A N/A N/A Installed Yes
- 7. Description of Work Replaced Comnponent/Part/Appurtenance Additional Description installed hanger 2-MCR-RV-4 173) per EC99747
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F Exempt Fi Other F- Pressure _ PSI Test Temp. OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASNIE Code Section XI 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of Component Line Size: 6 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: MCFI-2RV20 Flow Diagram No(s).: MCFD-2604-03.00 Support/Restraint Sketch/Drawing No(s).: 2MCR-RV-4 173 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: EC99747 Applicable Manuhacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 29 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected.the components described in this Owner's Report during the period to *3 ..-. / and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures descriteýi in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither e Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspecti JF Swan II *07,,, .*_*.../ -- Comrnissions NC1524, N-1 Inspector's Signa""-e Z/ National Board, State, Province, and Endorsements DateU - -* 2, 20//_
FORM NIS-2 OWNER'S REPORT F REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy.Carolinas, LLQ. Date 3/24/2011 526 South. Church.Street,. Charlotte,.NC, 28201 ... Sheet 1 o Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1865842-26 Address Work Order # (or Repair/Replacement Organization P.O. No, lob No , etc )
- 3. Work Performed by Duke Energy Carolinas, LLC... N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 Address Expiration Date: N/A
- 4. Identification of System RV - Containment Ventilation Cooling Water
- 5. (a) Applicable Construction Code ASME Ill 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section X I used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identificantion of Cnmnonents Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name ot ManllCtUrer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-RV-4112 Duke Energy N./A N/A N/A N/A Removed No
- 7. Description of Work Ot- ter (Describe Below)
Additional Description D eleted hanger'- MCR-RV-41 12 per EC99747
- 8. Tests Conducted: Hydrostatic ' Pneumatic r- Nominal Operation Pressure F Exempt F7 Other F Pressure PSI Test Temp. _ °F Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASMIE Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 6 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2604-03 .00 Support/Restraint Sketch/Drawing No(s).: 2MCR-RV-4112 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2RV-207-002 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 24 ,20:11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the. State or.Province of North Carolina ,, - . , Hartford Steam Boiler Inspection and Insurance Company -f' F .7 .7 Connecticut have inspected the components described in this Owner's Report during the period
. - tZ to - 2.4" -/1 ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor'his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner'l Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fromPconnected ith this inspection.
Cs Comlmissions NC1524, N-1 JF SwanJFSwn y' /- .,,
- ictor's Signature National Board, State, Province, and Endorseinents Date_1
FORM NIS-2 OWNER'S REPORT Ft.. AEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duke Energy Carolinas, LLC Date 3/24/2011 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1865844-16 Address Work Order # (Or Repair/Replacement Organization P.O No., lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 2820 1-1006 Address Expiration Date: N/A
- 4. Identification of System RV - Containment Ventilation Cooling Water
- 5. (a) Applicable Construction Code ASME I11 19 7_1 Edition, Sunmner and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected. ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Serial No. Board No. Identification Built Installed (Yes or No)
Name of Manufacturer 2MCA-RV-511I Duke Energy N/A N/A N/A N/A Inrstalled No
- 7. Description of Work RZeplaced Component/Part/Appurtenance Additional Description modified item# 9 on hanger 2MCA-RV-511I per EC99747
- 8. Tests Conducted: Hydrostatic F- Pneumatic Fr Nominal Operation Pressure F Exempt 7 Other [- Pressure __ PSI Test Ternp. _ IF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 6 in. (nominal) System Class: ASME.CI.ass 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2604-03 .00 Support/Restraint Sketch/Drawing No(s).: 2MCA-RV-51 I Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: EC99747 Applicable Manufaclurer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date .March 24 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a Valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
" Z to -2 - and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the 14ispector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or onnected with this inspecti.
JF Swanfr Commissions NC1524, N-I Z 1 Inspector's Sipnature National Board, State, Province, and Endorsements
FORM NIS-2 OWNER'S REPORT FG, .4EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 1. Owner Duke Energy Carolinas, LI . Date 10/20/20 10 526 South Church Street, Charlotte, NC,28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferr2y-Road, ju-nntersvill, NC 28078 1883394-01 Address Work Order 4 (or Repair/Replacement Organization P.O No., Job No, etc. )
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 .
Address Expiration Date: N/A
- 4. Identification of Svstem NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity ..1.99-8 Edit-ion with the_19_99 and.200_0 Addenda.
(c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, . ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2NV 1047 Kerotest CA014-6 26712 N/A 1979 Installed. Yes
- 7. Description of Work Rel placed C omiponent/Part/Appurtenance Additional Description re placed disc in valve 2NV 1047
- 8. Tests Conducted: Hydrostatic F Pneumatic r- Nominal Operation Pressure Exempt F7 Other F Pressure PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASNIE Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: MCFI-2NV303 Flow Diagram No(s).: MCFD-2554-03.00 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not includedelsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are con'ect and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date October20 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut *have inspected the components described in this Owner's Report during the period
-6.) to /6 " * /Cand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective
-1',
measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's !yport. Furthermore, neither the Ins tor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or nnected with this inspection.
JF Swan -Commissions .NC 1524, N- I o SNational Board, State, Province, and Endorsements Date 22Du 20.
FORM NIS-2 OWNER'S REPORT k . REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASIME Code Section XI
- 1. Owner Duke Energy Carolinas, LLC Date 3/11/2011 526 South Church Street, Charlotte, NC, 28201 I of 2 Sheet Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road,.Huntersvi.!le, NC 28078 1892972-03 Address Work Order P (or Repair/Replacement Organization P.O. No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas,. LLC Type Code Symbol Stamp: N/A Name Authorization No.: N/A 526 South Church Street,..Charlotte,.NC-28201-1006 Address Expiration Date: N/A
- 4. Identification of System NS - Containment Spray
- 5. (a) Applicable Construction Code ASME 11I 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section X I used for Repair/Replacement Activity .1998 Edition with the 1999 and 2.000 .Addenda.
(c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped C n Name of Manufacturer Serial No. Board No. Identification Built
.2MCR-NS-4767 Duke Energy N/A N./A N/A N/A Installed 'No t 4 4 4 .4- 5 4 4 4 4 .4. 5 4 4 4 4 -4. 4 r 1 1 1 4 +/- 4
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description In stalled 4 item# 8s (1/2" x 3 1/2" x 6" plates) on hanger 2MCR-NS-4767 per EC101538.
- 8. Tests Conducted: Hydrostatic F Pneumatic F" Nominal Operation Pressure r- Exempt F Other '- Pressure -PSI Test Temp. _ IF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 8 in. (nomninal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2563-01 .00 Support/Restraint Sketch/Drawing No(s).: 2MCR-NS-4767 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: EC101538 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist \' .4- Date March 11 - 20 11 Owner or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
, to " and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Own0 Is Report. Furthermore, neither the Ins ctor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fro Ibr connected with this inspection.
JF Swan 1 - - /, Commissions NC1524, N-1 gnaturV National Board, State, Province, and Endorsements (I Insp/ctor'ssS, /4 Da -3 20_/_1
FORM NIS-2 OWNER'S REPORT , . REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASNME Code Section XI
- 1. Owner .uke Energy Carol-inasjLIC . . Date 4/6/2011 526 South Church Street, Charlotte, NC, 2820_1...... Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, H.untersvill.e.,NC 28078 1897283-11 Address Work Order 9 (or Repair/Replacement Organization P.O. No., lob No., etc )
- 3. Work Performed by Duke Energy Carolinas,. LLC Name Type Code Symbol Stamp:
Authorization No.:
526 South Church Street, Charlotte, NC. 28201-1006.
Address Expiration Date:
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME I11 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name ot Manufacturer National Other Year Removed, or Stamped Component Name of Manulacturer Serial No Board No. Identification Butilt Installed (Yes or No)
NV Piping Duke Energy N/A 80 2NVFE5300 1982
- 7. Description of Work Rep lacec..Com~ponent/Patrt/Appj~urtenance Additional Description replaced bolting material in flange at 2NVFE5300
- 8. Tests Conducted: Hydrostatic -' Pneumatic -" Nominal Operation Pressure Exempt I- Other F- Pressure PSI Test Temp. __
Description (Optional): test performed per prc*edure MP/0/A/7700/045.
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASMEClass 2 Weld Isometric Drawing No(s).:
Flow Diagram No(s).: MCFD-2554-O 1.01 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist \7 ,i--- Date April 6 -20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned,.holding a valid commission issued by theNational Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina r - In a PA. , Hartford Steam Boiler Inspection and Insurance Company nýF
'Connecticut have inspected the components described in this Owner's Report during the period
- .9.*"C:Q--[_'to -'7 ./. ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fron/rr connected with this ins ction.
JF Swan z;.,,4-. Commissions NC 1524, N- I National Board, State, Province, and Endorsements Inspector's Date 0-20o/
Date 20 /1
FORM NIS-2 OWNER'S REPORT k . REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI I. Owner Duke Energy Carolinas, LL C .Date 4/6/2011
.526_South Church _.Street- Charlotte, N.C, 2.8201_ .. Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersyille,.N.C 28078 1897290-07 Address Work Order (or Repair/Replacement Organization P.O. No, ,lob No., etc.)
- 3. Work Performed by Duke Energy.Caroli.nas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte,.NC 28201-1006 N/A Address Expiration Date:
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME Il1 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity .1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Camn"onents Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No)
NV Piping Duke Energy N/A 80 N/A 1982 Installed Yes
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description replaced bolting material in flange 2NVFE5330
- 8. Tests Conducted: Hydrostatic FV Pneumatic E- Nominal Operation Pressure F'_ Exempt F- Other r- Pressure PSI Test Temp. __ F Description (Optional): test performed perprocedure.MPP//A/7700/045.
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (norninal) System Class: ASME.Class2 Weld Isometric Drawing No(s).: MCFI-2NVI80 Flow Diagram No(s).: MCFD-2554-01.00 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist , Date 'April 6 , 2 0 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
_Z t ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report 'in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspect*
JF Swan .b,,. -AS Commissions NC1524,N-1 Inspector's Signalt '" National Board, State, Province, and Endorsements Date (ý,
i/Jr7 1 20 //
FORM NIS-2 OWNER'S REPORT I . REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X I Duke Energy Carolinas, LLC Date 4/2/2011
- 1. Owner 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700IHagers Ferry Road, Huntersville, NC 28078 1900003-04 Address Work Order 9 (or Repair/Replacement Organization P.O No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Name Type Code Symbol Stamp:
Authorization No.:
526 South Church .Street, Charlotte, NC. 2.8201-1006 Address Expiration Date:
- 4. Identification of System NV - Chemical Volume And Control
- 5. (a) Applicable Construction Code ASME-II 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Serial No. Board No. Identification Buit Installed (Yes or No)
Name of Manufiacturer 2NV 155 Dresser TE09049 293 N/A 1978 Removed No 2NV 155 Dresser TH03994 1936 N/A 1987 Installed No
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description replaced valve 2NV 155
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure [ Exempt r- Other r- Pressure PSI Test Temp. _ IF Description (Optional): test performed perprocedlure M.P/O/A/770_/ 045
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 4 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCI FD-2554-O2.O I Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date :April 2 ,2011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and ernnloved hv Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period Z // , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's eport. Furthermore, neither the In ector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from onnected with this inspection.
JF Swan Commissions NC1524, N-I Inspector's Signature " National Board, State, Province, and Endorsements Dat "201/
FORM NIS-2 OWNER'S REPORT I REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner .Duk-e .Energy Carolinas, LI C .Date 4/3/2011 526 South Church Street, Tharlotte, NC, 28201.. Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road,.Huntersville,..NC 28078 1900647-05 Address Work Order # (or Repair/Replacement Organization P.O. No., Job No., etc.)
- 3. Work Performed by Duke.Energy Qauolinas, LLC Type Code Symbol Stamp: N/A Name Authorization No.: N/A 526 South Church Street._Charlotte, NC 28201-1006 Address Expiration Date: N/A
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity 1998 Edition with the_.19.99.and 2000 Addenda...
(c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2NV229 Dresser TE09051 262 N/A 1978 Re.moved Yes 2NV229 Dresser TE09050 261 N/A 1978 Installed Yes
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description replaced relief valve 2NV229
- 8. Tests Conducted: Hydrostatic F Pneumatic r- Nominal Operation Pressure F Exempt r- Other i- Pressure PSI Test Temp. OF Description (Optional): test.performed per procedure M.P/O/A/7700/045.
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet .2 of 2 Component Line Size: 1 1/2 x 2 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: [vICFD-2554-03.O1 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date April3 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
" ...*S zi**..to
<- , an statethattothebestofmyknowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's eport. Furthermore, neither the In ector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from o onnected with this inspection.
.JF Swan Commissions iNC1524, N-I 0* Inspector's Signature JNational Board, State. Province, and Endorsements Date* " 2-)-
FOR)4 NV-I N CERTIFICATE HOLDERS* DATA REPORT FOR SAFETY AN; SAFETY RELIEF VALVES*
(AS REQUIRED BY THE PROVISIONS OF THE ASNIE CODE. SECTION- III. DIV. 1)
I. 14m. '.TUREDBY DRESSER INDUSTRIAL VALVE & INSTR, DIV. HIGK',XAY 71 NGRqWT ALEXANDRIA, LOUISIANA (NA2E AND ADDRESS OF CERTIFICATE HOLDER)
.i
- 2. MAiUFACTURED FOR Mill Power Supply (HANME Co.,P.O. Box 1339, Charlotte, NC 28232 AND ADDRESS OF PIURCHASER OR OIWNER)
- 3. LOCATION OF INSTALLATION Duke Power Co. ,McGuire Nuclear Sta., Cowans Ford, NC (NAME AND ADDRESS) 4 3NC3004 ýi) 1978 (CNN) (DRAWING NO.) (HAT Nf*'t0 (YEAR BUILT)
- 5. VALVE;I-12-/)1910-30F/S4-1LXRL1-NC3004 IDENTIFYINGNO. /E95 (MODEL NO..SERIES NO.) '(N _CEaRS SERIAL.NO.f TYPE Safety Relief CLASS n2 _
(SAFETY.SAFETY RELIEF; PILOT;POWlER A4,t A:fD)
ORIFICE SIZE .650 NOMINAL INLET SIZE 1-1/2" OUTLET SIZE 2" INCH INCH INCH B. SET PRESSURE (PSIG) 220 RATED TEMPERATURE 189 0 F
STAMPED CAPACITY 3753 LBS/HR. @ 10 % OVERPRESSURE BLOWOOIN (PSiG) 11.0 SAT.STEAAM HYDROSTATIC TEST (PSIG) INLET **See.Below OUTLET N/A ***
(APPLICABLE TO VALVES FORCLOSED SYSTEMS ONLY)
- 7. PRESSURE RETAINIKG PIECES SERIAL NO. OR MATERIAL SPECIFICATION IDENTIFICATION INCL. TYPE OR GRADE BODY AAD60 SA351 Cr. CF8M BONNET OR YOAE AAE32 SA351 Cr. CF8M SUPPORT RODS NOZZLE AAA69 SA182 Gr. F316 DISC X16110 SA182 Gr. F316 SPRIN3 WASHERS G9345/G9064 SA479 Type 316/SA182 Gr. 316 ADJUSTING SCREW G9380 SA479 Type 316 SPINDLE Head G9380 SA479 Type 316 SPRING 88540 ASTM A313 Type 316 BOLTING OTHER PIECES Disc Holder r G9392 SA182 Cr. F316 Base stild5, C.I(I I SA453 Gr. 660 GKI I _qA1 QL r.r Base stild N11t.q r,K6
- SUPPLEMENT SHEETS IN FORM OF LISTS.SXETCHES OR DRAIIHGS MAYBE USED PROVIDED (1) SIZE IS 8-1/2" v ,I" (2) INFORNATION IN ITE3S 1-2 ON THIS DATA REPORT IS INCLUDED ON EACH SHEET, AND (3) EACH SHEET IS HUNBEREU AND NUMBER OF SHEETS IS RECORDED AT TOP OF THIS FORM.
- -Base 450 PSIG **
Nozzle 5575 PSIG Disc 9275 PSIG Bonnet 450 PSIG RM NO. OArOO71-0178
FOr*HV-I FORN4 NY-I (BiACK)
=
CERTIFICATE OF COMPLIANCE VE CERTIFY THAT THE STATEMENTS MADE IN THIS REPORT ARE CORRECT AND THAT THIS VALVE CONFORNS TO THE POLES OF CONSTRUCTION OF THE ASME CODE FOR NUCLEAR POWER PLANT COMPONENTS. SECTION 111, DIV.I. 1971' EDITION. ADDENDA Summer 1973 , CODE CASE NO. N[A (DATE)
DATE 1-27-78 SIGNED Dresser IVID BY,/
(N CERTIFICATE HOLDER) Princ al Q.A. E gineer OUR ASNE CERTIFICATE OF AUTHORIZATION NO. N-1747 TO USE THE, NV Nay 20, 1980 (N)
My SYMBOL. EXPIRES (DATE)
CERTIFICATION OF DESIGK DESIGN INFORNATION CN FILE AT Dresser Plant, Alexandria, La.
STRESS ANALYSIS REPORT (CLASS I ONLY) ON FILE AT DESIGN SPECIFICATIONS CERTIFIED BYI T. F. Wyke PE STATE North Carolina REG. NO. 4870
.STRESS REPORT CERTIFIED BYI PE S.TATE REG.NO.
1 SICHATURE NOT REOUIRED-LIST NAME ONLY CERTIFICATE OF SHOP INSPECTION I.THE UNDERSIGNED. HOLDING A VALID COMXISSIOH ISSUED BY THE NATIONAL BOARD OF BOILER AND PRESSURE VESSEL INSPECTORS AND THE STATE OR PROVINCE OF LOUISIANA AND EMPLOYED BY THE HARTFOM9 STS-. BOILER I-&. ...
C04A?4Y OF RARTFO.", CONN.. HAVE iNSPECTED THE PUMP.OR VALVE.DESCRI,3ED IN THIS DATA REPORT ON 197I2ANOD STATE THIAT TO THE REST OF LY KNOWLEDGE AND BELIEF.THE N CERTIFICATE HOLDER HAS CONSTRUCTED.TNI$S PUNP, OR.VALVE. IN ACCORDANCE WITH THE-ASME CODE FOR NUCLEAR POWER PLANT COMPONENTS.
BY SiNINg THIS CERTIFICAIE. NEITHER THE INSPECTOR NOR HIS EMPLOYER MAKES ANY VARlffrrY.EXPRESSED OR IMPLIED.
CCHCERNiNtG THE EOJIPFENT OESCRIBED IN THIS DATA REPORT.FUTHERMORE.HEITHER THE INSPECTOR NOR HIS ENPLOYER SHALL BE LIABLE IN ANY MANNER FOR ANY PERSONAL INJURY OR PROPERTY DA4AGE OR A LOSS OF ANY KIND ARISINg F101 OR CONtE'TTED 1ITHT'HIS INSPECTION.
DATE .Ma[rch27. ,ta 78 SIGNEO COmmISSIOnS. National Board No. 7779
"! (INSPECTOR) (NATIL.BD.STATE PROV.AND NO.)
k
~cs~i;.h~. O~ -COil-OTTO
FORM NIS-2 OWNER'S REPORT F( .EPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASMIE Code Section XI
- 1. Owner Duke Energy Carolinas, LL C .. Date 3/26/2011 526 South Church Street, Charlotte, NC, 28201 . Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1907056-14 Address Work Order # (or Repair/Replacement Organization P.O. No., lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC. N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 Expiration N/A Address Expiration Date:
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity .1998 Edition with the1999.and 20.00 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification ofComponents Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-NV-5050 Duke Energy N/A N/A N/A N/A Installed No
- 7. Description of Work Rer placed Component/Part/Appurtenance Additional Description Re:placed item# 7 (2x2 tube steel) on hanger 2MCA-NV-5050 per EC 104199.
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation-Pressure F Exempt F Other F Pressure PSI Test Temp. _ F Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X!
2 of 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet Component Line Size: . in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2554-03.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-NV-5050 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2NV-350-00I Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ::FL Grass, Quality Assurance Technical Specialist \ Date March 26 .20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by NHartford Steam Boiler Inspection and Insurance Company o of Connecticut have inspected the components described in this Owner's Report during the period
- Z( to - 2-b -// , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither th spector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from *connected with this inspection JF Swan /[e '-,07 _. / ,6,u- - Commissions NC1524, N-1 Inspector's Signature.,,-/' National Board, State, Province, and Endorsements Dater 20//-
201/
fl~ rp
FORM NIS-2 OWNER'S REPORT F( AEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duke.Energy Carolinas, LI S. ....... Date 4/3/2011
.526_South. Church Street, Charlotte,. NC,28.201 . Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers. Ferry Road, Huntersville, NC 28078 1907056-02 Address 1907056-02 Work Order 9 (or Repair/Replacement Organization P 0 No., lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-10.06 N/A Address Expiration Date:
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1.99.8 Edition with the 199_9 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No)
NV Piping Duke Energy N/A 80 N/A 1982 Installed Yes 2NV494 Flowserve E990A-2-3 2356 Body S/N 3 2000 Installed Yes 2NV494 Borg Warner 8003 53 N/A 1976 Removed Ye..S
- 7. Description of Work Replaced .Component/Part/Appurtenance Additional Description Replaced valve 2NV494 and piping per EC104199.
- 8. Tests Conducted: Hydrostatic - Pneumatic - Nominal Operation Pressure P Exempt -- Other -- Pressure 2516 PSI Test Temp. 86.1 OF Description (Optional): test performed p[er procedure .MP/0/A/7650/076.
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASME Class_2 Weld Isometric Drawing No(s).: MCFI-2NV294 Flow Diagram No(s).: MCFD-25554-03.00 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: EC104199 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist ,,.c-t, Date April 3 ,20.11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of
.Connecticut have inspected the components described in this Owner's Report during the period
~ Z/ I */7- to - ,and state thato the best ofmy knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in an), manner for any personal injury or property damage or a loss of any kind arising from o connected with this inspection.
JF Swan Y *Commissions NCI 524, N-lI
- National Board, State, Province, and EndorsenenIs Date 2o/_./_
Jun-15-]O 01:55pm From-FLOWSERVE WILLIAUSPORT +T]73274922 T-642 P.01/04 F-513 FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVESI As Required by the NIovLuions of the ASME Code, Section Ill. Divizion 1 I. 2 Pg. of Flowserve Corp.
701 First Srreet, Williamsport., PA 17701 1
°.. manui.taured
............... 3n3 canft.-,a Oy n 1nalA 4l10011 01 N C. MT.?,CatoMOO9 2 1 Duke Energy Corporation, P.O. Box 1015, Charlotte, NC. 28201-IO15.
- 2. MaI utaclufc0 t .. . (e'uinl
- 1*2l'e 0? Pjrnagim.If o O.n.e,e.
McGuire Nuclear Starion, 13225 hagers Ferry Rd., Highway 73, Huntersville, NC.
I1 Lac3tion of instauation
- 3. a m0clre"" '2 8 0 28 -8 9 8 5 .
Y-Globe W9925265 Rau A cRNN/A
- 4. MOceI No., Serris No.. orT 1986 N/A N/A
- 5. ASME Coce. Section Ill. D,,isson 1: Wa~bbofn fiagoatnca cai*ni 104S3 4cocit C-*Oz -o I Nomianal -nift s _, O&tie $Saz 2 8 Purp ar avalve 7 Material: floor SA351-CF8M Bonnlux 5A479-316 5A564-630-1C75 OISI. - - ~ n N/A tC' (01 to) lal to]
Boav Bonne omsr Na.'l aNo. Soara Sanas NO. No. No. No E990A 1 NB9 2354 SN: I HTT86684 Y-E990A-2-2 NB# 2355 SN: 2 HT#48908 Pc 2 HT48656804 (TXY)
E990OA-2T NB# 2356 SN: 3 HT448908 Pc 3 HT#8656804 (TX'i)
E99 OA- 2-4 NB# 2357 SN: 4 HT#48908 Pc 4 HT#8656804 (TXY)
E990A 5 NB# 2358 SN: 5 HT#48908 Pc S HT48656804ATXY) 5 .vbcUmiivn .15rmtxmWSW 'n birn 0?
t 4=. 3&=Cr%i. Or *iWVsg MaY 06 - .0 ".o-do bi A .5s Bt 11. 121 iom stbionbdnS.%am* I dIfirgb 4
.2nStN, Oat Raoeort mi ,ucaao an .acri zriest. t31 eacri usa.?. nmbarooria ucrta p%.mw of a, Ioss -a 4K(obOOOat Ma WogOr M5g bIrn (1 21861 Th~avwm tE i0OO37i ma, ci6 oouata from vma Ownir Dept.. ASME-. 22 La. On. a. Sax 2300. Fwa..nm. NJ O70O07.2rp 0
/~1Tf/:< 764-1 /~d~V qoo
Jun-15-00 01:55pm From-FLOWSERVE WILLIAMSPORT +7173274922 T-642 P.02/04 F-513 FORM NPV-1 (back)
Serial Numbers: E990A-2-1 through E990A-2-5 Material; Gasket Retainer: SA564-630-1075; Cast#700781; Code: WGT.
- 9. Nsign conaalom 2735 680 "F or .. , prussure cla= 1878 iII
( preisuf"a1 lIamleun','1*
- 10. Cold ,workig pres3ure 4507 ita iooF0 1 1. H~yarcistatic tes-t 6775 ps,. u;"* ataeonza,* cast prats.urn 4958 psi CERTIFICATION Of DESIGN F. A. Bensinger PA PE-31002-E Design soficao_ cf_ by FAensnP.E. Stae Ag. no.
oesign Aeporz Certifie by Theron C. Bartlett I11 P.E. sra PA R.g no.
PE-039036-E CERTIFiCATE OF SHOP COMPLUANCE we carutf met me statements made ,n xr" teport are corTect aiax mat mis pump or val-. conforms 'o te rules for construjction of trio ASME CocOa.Section III. Dhv.a.on 1.
N Certificate of AtnOrnzation No N1712 Epr, __ 4/15/01
,'WLDat 8 ame E1otserve Corp. Signed e [L 6 iN C1&rficme Malawi) toIral bO ,greaoprolotat-al CERTICATE OF SHOP MISPECT"ON I. me undersigned. ho*Ling a vatic cOzmrw'4on a z.rjo, d by, ife. Natiorial Board of B-odat &no Prxivure Vedsseo Inspectors ann Tr*niszale *J;ý Of per'nsylvai*ria an. employed yCor*nerci;al Union Ins. Co.
.07 a ' .
r* , la.o inspaecte the purp. of valve. desc.ibed in tmhs Date Repor* On 1-3 ..- _.. .. -- /. and state ina t o trio m-e of my knowledge and belief. me Certificate Holoer has cons;njCEC Mtts Dump. Of valve, ,n accordance witri Me ASME Coco, Secison lit. O;v;aion 1.
8y sigruN mis cartmficate. netul"r the tl:n cor nor tiaemployer makes anty warranty, expf'ssec or implieOd. conc.rn*ng tmel componeont described in tir3 Data Report. F-wr'rcrmo4'e. naotmeor Te inspector nor isz emplOvOyr somll be haole in any manner fOr any personal injury or ptoperrvy Damage or oaany kind aLrsng trom of corn'cted wrt tnhi ,iln ii--o.___
e Date S/ Counm4om Pennsylvania 2392
'q,* re**'5'V70 44^,* *'0oVL. So. o. w.%oar -inj mta or pir, . a.d ;.).
i II For mri-rtally Opera-ted 'akwsveonly.
FORM NIS-2 OWNER'S REPORT FOi ZPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 1. Owner Duke Energy Carolinas, LILC Date 3/9/2011
..526 South Church Street,. Charlotte, NC, 2820 ... Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12.700.Hagers Ferry Road, Huntersville, NC 280.78 1922371-01 Address Work Order I9(or Repair/Replacement Organization P.O. No, Fob No.. etc
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte,. NC 2820l!-.l006.
Address Expiration Date: N/A
- 4. Identification of System SM - Main Steam
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity .1998 Edition with the 1999 and_2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Com onents Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Serial No. Board No. Identification Built Installed (Yes or No)
Name of ManufacturerSeilN.BadN.detfctoBulInald (YsrN) 2MCA-SM-20 Duke Energy 21359 N/A :N/A N/A Removed No 2MCA-SM-20 Duke Energy 37227 N/A N/A N/A Installed No
- 7. Description of Work Re placed Com pon.ent/Pa.rt/Appurtegnan.ce Additional Description Rt eplaced snubber on hanger 2MCA-SM-20
- 8. Tests Conducted: Hydrostatic r Pneumatic F Nominal Operation Pressure F Exempt F Other F Pressure " PSI Test Temp. _ '
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of Component Line Size: 42 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow.Diagram No(s).: MCFD-2593-0 1.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-SM-20 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2SMA-002 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration.Date N/A Signed FL Grass, Quality Assurance Technical Specialist *S,, 4 .- Date March 9 2011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina andc emnonved bv Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
-to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither td Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fromn r connected with this inspection JF Swan (I* AZv-L..------ Commissions NC 1524, N-I
.National Board, State, Province, and Endorsements e Inspector's Signature _ -
Date (- /, 20-d/
FORM NIS-2 OWNER'S REPORT FOi. ZPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LL C Date 3/8/2011 526 South .Church. Street, Charlotte, NC,.28201 . Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1922374-01 Address Work Order # (or Repair/Replacement Organization P O. No , lob No., etc I
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Type Code Symbol Stamp:
Name A 0,t ; ,t;,, X1,- N/A 526 South Church Street, Charlotte, NC 28201l-1006 __-.N/A Expiration Date: N/A Address
- 4. Identification of System CA - Auxiliary Feedwater
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity 1.99_8.Edition with the 19_99 and 2000 Addenda, (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name ofMiutlCttrer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-CA-60 Duke Energy 18871 N/A N/A N/A Removed No 2MCA-CA-60 Duke Energy 37226 N/A N/A N/A Installed NO
.4- 4 4 + *
+ + 1 1 r
.4- 5 1 7 1 r
______________________ .1. 1 _____________________ .4___________________ +/- ___________________________ _______ a ___________________ __________
- 7. Description of Work Rel placed. Com ponent/Part/Appurte-nance Additional Description re placed snubber on hanger 2MCA-CA-60
- 8. Tests Conducted: Hydrostatic F' Pneumatic F Nominal Operation Pressure -. Exempt r- Other r Pressure .PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 6 in. (nominal) System Class: ASMEClass 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-26 17-0 1.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-CA-60 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code. Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist " . Date March 8 20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina . ,., Hartford Steam Boiler Inspection and Insurance Company Connecticut have inspected the components described in this Owner's Report during the oeriod and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the I pector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or cnected with this inspection.
JF Swan r - I Commissions .NC1524, N-1 Inspector's Signature .1 *' National Board, State, Province, and Endorsements Date J 1 ec t
o , 20 ..
FORM NIS-2 OWNER'S REPORT FOR PAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner .Duke Energy Carolinas, LiLC .Date 3/7/2011
.526 SouthChurch Street, Charlotte, NC, 28201. I of 2 Address Sheet
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1923830-02 Address Work Order # (or Repair/Replacement Organization P.O. No, Job No, etc
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1.0.06 Address Expiration Date: N/A
- 4. Identification of System NC - Reactor Coolant
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2D S/G Lisega Duke Energy 9 N/A :N/A N/A Installed No
- 7. Description of Work Replaced Co nmp on0ent/Pa-rt/,A.p p.u.rten an._e Additional Description Replaced #4 rear valve and #5 cone valve in snubber for 2D Steam Generator
- 8. Tests Conducted: Hydrostatic f- Pneumatic r- Nominal Operation Pressure r- Exempt F7 Other r- Pressure PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: N/A in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: N/A Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCM 1117.03-0053.001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist - .Date March 7 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
'.3. iL.- -/ . to --Lc- iL." *L and state that to the best of my knowledge and belief, the Owner has performed examinations and taketn corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner' Report. Furthermore, neither the Ins ctor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from r connected with this inspection.
SCommissions'NC1524, N-I Inspectors Signature National Board, State, Province, and Endorsements Date 20
FORM NIS-2 OWNER'S REPORT FOi. EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LLCDate 3/25/2011 526 South Church Street, Tharlotte, NC, 28201 Sheet 1 of 2 Address
- 2. Plant M.cGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville_,NC 28078 1923837-19 Address Work Order P (or Repair/Replacernent Organization 13.0. No., lob No., etc.)
- 3. Work Performed by Duke Energy.Carolinas, LLC N/A Type Code Symbol Stamp:
Name Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 N/A Address Expiration Date: N/A
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the. 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-NV-4379 Duke Energy N/A N/A N/A N/A Installed No 2MCR-NV-4380 Duke Energy N/A N/A N/A N/A Installed No 2MCR-NV-4381 Duke Energy N/A N/A N/A N/A Installed No
- 7. Description of Work Re placed Component/Part/A~ppurte.nance Additional Description Rt eplaced the bolting material on hangers 2MCR-NV-4379, 4380, and 4381 per EC105482
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure -- Exempt F Other F Pressure PSI Test Temp. _ IF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASMD5Class1 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2554-0 1.01 Support/Restraint Sketch/Drawing No(s.pCANca,48 andr43 Other Applicable Information (e.g., WO. No., EC No.) if not included elsewhere on NIS-2 Form: o MCSRMD-2NV-209-001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 25 _ , 20 11 Owner or Owner's Designee, Title /
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of
- Connecticut have inspected the components described in this Owner's Report during the period S- 11{ to - and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither thed nspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or onnected with this inspection./
JF SwanCommissions NC 1524, N- I Inspector's Signature /National Board, State, Province, and Endorsements Dat 3- 20
FORM NIS-2 OWNER'S REPORT FC EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duke Energy Carolinas, LL*C Date 3/21/20 11 526 .South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Naine 12700 Hagers Ferry Road, Huntersville, NC 28078 1923857-28 Address Work Order # (or Repair/Replacement Organization P.O. No., .lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Narne Type Code Symbol Stamp: N/A Authorization No.: N/A 526 South. ChuTch Street, .Charlotte, NC 28201-1006.
Address Expiration Date: N/A
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME I11 19 7.1 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity 1998 Edition with th-e_.1999 and 200OAdd.enda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of ManufactUrer National Other Year Removed, or Stamped Component Naite 01Mantiturer Serial No. Board No. Identification, Built Installed (Yes or No) 2MCA-NV-6523 Duke Energy N/A N/A N/A N/A Installed No
- 7. Description of Work Replaced Coin ponent/Part/Appurtenance Additional Description replaced pivot pin on hanger 2MCA-NV-6523
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F Exempt F Other F Pressure .PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASNIE Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 3 in. (nominal) System Class: ASME.Class.2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2554-0 1.02 Support/Restraint Sketch/Drawing No(s).: 2MCA-NV-6523 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FLGrass, Quality Assurance Technical Specialist 2011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
.North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period J
measures cescribed /in this Owner's Report in accordance
_to__.___--_...2.-._-____ , and statethethat with requirements my ASME to the best of the knowledgeCode, andSection belief,Xl.
the Owner has performed exarninations and taken corrective By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner'skeport. Furthermore, neither the In ctor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from o 'Ionnected with this inspection.
.JF Swan . Commissions NC 1524, N- I nspectors Signature /
/ National Board, State, Province, and Endorsements Date .3 "-72---- .20j
-/
FORM NIS-2 OWNER'S REPORT FOK .,EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 1. Owner Duke Energy Carolinas, LI LC Date 3/21/2011 526 South Church Street, CharlotteNC, 28201 Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2
- Narne 127.00 Hagers Ferry Road, Huntersyille, N.C 28078 1923857-45 Address Work Order # (or Repair/Replacement Organization P C. No, lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC. N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South.Church Street, Charlotte, NC_28201-.1:006 Address Expiration Date: N/A
- 4. Identification of System NC - Reactor Coolant
- 5. (a) Applicable Construction Code ASME III 1971 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the...1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No)
.2MCR-NC-4000 Duke Energy 3605 N/A N/A N/A Removed No 2MCR-NC-4000 Duke Energy 38038 N/A N/A N/A Installed No
- 7. Description of Work Re placed Component/Part/Appurtenance Additional Description re placed snubber on hanger 2MCR-NC-4000
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F Exempt F Other F Pressure PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X1 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of.
Component Line Size: 14 in. (nominal) System Class: ASME.Class .I Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2562-01 .00 Support/Restraint Sketch/Drawing No(s).: 2MCR-NC-4000 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2NC-201-001, PIP# M-1 1-01899 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, QUality Assurance Technical Specialist \7 Date March 21 ,0 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina Hartford Steam Boiler Inspection and Insurance Company and employed by of
- Connecticut have inspected the components described in this Owner's Report during the period 3 -,/ `7-' ý/ to .3 - 2 - 1/, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the I pector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from ed with this inspection.
F Swan ~Commissions NC1524,rN-I Dt Inspector's Signature 1/0/ National Board, State, Province, and Endorsements Date 2-2 , 2o0
FORM°NIS-2 OWNER'S REPORT F6O. -EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 1. Owner Duke.Energy Carolinas, LLC.. Date 3/11/2011
..526 South Church Street, Charlotte, NC, 282.01 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 N arme 12700 Hagers Ferry Road, .Huntersvile, NC 28078 1923857-49 Address Work Order 0 (or Repair/Replacement Organization P.O. No., lob No . etc
- 3. Work Performed by Duke .Energy Carolinas, LLC Type Code Symbol Stamp:
Name Authorization No.:
526 South Church Street, Charlotte, NC 28201-1006 Expiration Date: N/A Address
- 4. Identification of System NI - Safety Injection
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A 6, Identification of Components Corrected. ASME Code Name of MNanuifacturer National- Other Year Removed, or Stamped Component Name of MattufactUrer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-N[-4589 Duke Energy .2816 N/A N/A N/A Installed No
- 7. Description of Work Replaced Component/Part/Appurtenance.
Additional Description Replaced load pin in hanger 2MCR-NI1-4589
- 8. Tests Conducted: Hydrostatic F Pneumatic F' Nominal Operation Pressure F" Exempt 1F Other F Pressure PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X!
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 10 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-Support/Restraint Sketch/Drawing No(s).: 2MCR-NI-4589 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2N1-203-002 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date March 1I1)011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of
- Connecticut have inspected the components described in this Owner's Report during the period
".31-f..L[L[ to "2, - /
- 1/ ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspection.
JF Swan - Commissions NC 1524, N- I 1__7 Inspector's Signature .x' National Board, State, Province, and Endorsements
/_/__
FORM NIS-2 OWNER'S REPORT FO. .EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke. Energy Carolinas,. L . Date 3/11/2011 526 -Sou.th.Church Street, Charlotte,.NC,..2.8201 .. Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road.,Huntersville, NC 28078 1923 85 7-62 Address Work Order # (or Repair/Replacement Organization P 0 No., lob No., etc.)
- 3. Work Performed by Duke Energy. Carolinas, LLC.. N/A Type Code Symbol Stamp:
Name Authorization No.: N/A 526 South Church St reet._Charlotte, NC 28201-1006 N/A Address Expiration Date:
- 4. Identification of System BB - Steam Generator Blowdown Recycle
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998. Edition with.the 1_9.99_and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No)
.2MCA-BB-5218 Duke Energy 10425 N/A N/A N/A Removed No
.2MCA-BB-5218 Duke Energy 38035 N/A N/A N/A Installed No
- 7. Description of Work Re tlaced Compon.ent/Part/A.ppurternanrce Additional Description re placed snubber on hanger 2MCA-BB-52 18
- 8. Tests Conducted: Hydrostatic r Pneumatic F- Nominal Operation Pressure F Exempt F Other F Pressure .PSI Test Temp. _
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section X I
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 4 -in. (nominal) System Class: ASME C.lass. 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2580-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCA-BB-52 18 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist "'- Date March11 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
- North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report durincr the period i.w.* -* / z to .-- Z//' ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the I pector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fromy*r connected with this inspection.
.JF Swan //76 Inspector's Signature
- "- Commissions NC1524, N-1 National Board, State, Province, and Endorsements D tea 2~- i'1 20-9_
D te 2016
FORM NIS-2 OWNER'S REPORT FG.. AEPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LI C .Date 3/11/2011 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1923857-68 Address Work Order 9 (or Repair/Replacement Organization P.O. No., tob No, etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 N/A Address Expiration Date:
- 4. Identification of System VS - Station Air System - Station Air System (High Pressure)
(a) Applicable Construction Code ASME [II 19 71 Edition, Summer and Winter Addenda, N/A Code Case 5.
(b) Applicable Edition of Section Xl used for Repair/Replacernent Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected. ASME Code Nameof Manutaciurer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2-MCR-S-VS-150-01-1 Duke Energy 6342 N/A N/A N/A Removed No 2-MCR-S-VS-150-01-1 Duke Energy 38034 N/A N/A N/A Installed No
- 7. Description of Work Re placed Component/Part/Appurtenance Additional Description re placed snubber on hanger 2-MCR-S-VS- 150-01-1
- 8. Tests Conducted: Hydrostatic r Pneumatic -- Nominal Operation Pressure F Exempt 7" Other F- Pressure PSI Test Temp. __ IF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASMEClasss2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: N/A Support/Restraint Sketch/Drawing No(s).: 2-MCR-S-VS-150-01-1 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requiremnents of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist '-.. Date March II 2)0 I1I Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by "Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
-to -. 31 9 and state that to the best of my knowledge and belief, the Owner has perforned examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspecti JF SanCommissions NC1524, N-I Inspector's Signature National Board, State, Province, and Endorsements
,ate -)"o0.f/
FORM NIS-2 OWNER'S REPORT FOk. .EPAIRJREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 1.Owner Duke Energy Carolinas, LI C - Date 3/21/2011 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 19233857-69 Address Work Order # (or Repair/Replacement Organization P 0 No., lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Type Code Symbol Stamp: N/A Name Authorization No.: N/A 526 South Church Street, Charl.otte,.NC 2820 1-1006 Address Expiration Date: N/A
- 4. Identification of System NI - Safety Injection
- 5. (a) Applicable Construction Code ASME 11 19 71 . Edition, Summer and Winter Addenda,, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity .1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Naome ofn Manut'aclurer National Other Year Removed, or Stamped Component N e MatfaCtUrer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-NI-4918 Duke Energy 8916 N/A N/A N/A Removed No 2MCR-NI-4918 Duke Energy 37057 N/A N/A N/A Installed No
- 7. Description of Work Re[ placed Component/Part/Appurtenance Additional Description re placed snubber on hanger 2MCR-NI-49 18
- 8. Tests Conducted: Hydrostatic - Pneumatic f- Nominal Operation Pressure F Exempt Other f- Pressure PS.J Test Ternp. OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: I 1/2 in. (norninal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2562-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCR-NI-4918 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2N1-214-001, PIP# M- 11-01899 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XL.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist '$&X'a,#- Date March 21 ,20 11 Owner or Owner's Designee, Title I
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
- '* -- /(
/'"' to . 2 * . ( and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's in ti Report. Furthermore, neither Owner'snnReport.Frhroe ned th ,Inspector nor his employer shall be liable in any manner for any"r personal injury or property damage or a loss of any kind arising from d with this inspectio
- JF Swan *Commissions NC 1524, N- I Inspctor's'Signaturet National Board, State, Province, and Endorsements Date 3 --2-? n,
FORM NIS-2 OWNER'S REPORT FOR. _PAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duke Energy Carolinas, LI LC Date 3/21/2011
.526.South Church Street, Charlotte, NC, 28201.... Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 12700 Hagers Ferry Road, Huntersville, NC 28078 1923857-75 Address Work Order 9 (or Repair/Replacemrent Organization P.O. No., lob No, etc.)
- 3. Work Performed by Duke Energy Carolinas, LILC N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC._2820 1-1006* N/A Address Expiration Date:.
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name ofManufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-NV-4483 Duke Energy 61257-50 N/A N/A N/A ..Removed No 2MCR-NV-4483 Duke Energy 30800150-031 N/A N/A N/A _In stalled No
- 7. Description of Work Rep)laced Component/Part/Appurtenance Additional Description re placed snubber on hanger 2MCR-NV-4483
- 8. Tests Conducted: Hydrostatic " Pneumatic F- Nominal Operation Pressure F Exempt F Other F Pressure -PSI Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 3 in. (nominal) System Class: ASME Class2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2554-01.02 Support/Restraint Sketch/Drawing No(s).: 2MCR-NV-4483 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2NV-202-001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist -"--Date:March 21 ,
Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of
,Cormecticut have inspected the components described in this Owner's Report during the period
- ~ £'Z/ 2 - ' to 2- Ž - / and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the I pector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or nnected with this inspection.
JF Swan Commissions NC 1524, N-I 6* I nspector's Signature 7* National Board, State, Province, and Endorsements
ýDate , 20/t/
Date 201.6
FORM NIS-2 OWNER'S REPORT FOi LPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI I. Owner Duke Energy Carolinas, LLC Date 3/21/2011
_.526.South Church Street, Charlotte, NC, 28201........1. . ....... . Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700.Hagers._Ferry Road_Hu.n.tersvill.e, NC 280_78 1923857-76 Address Work Order # (or Repair/Replacement Organization P 0. No., Job No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Type Code Symbol Stamp:
Name Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 N/A Address Expiration Date:
- 4. Identification of System ND - Residual Heat Removal
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-ND-6326 Duke Energy 10977 N/A N/A N/A Removed No 2MCA-ND-6326 Duke Energy *38037 N/A N/A N/A Installed No.
- 7. Description of Work Reptlaced Component/Part/Appurtenance Additional Description rei placed snubber on hanger 2MCA-ND-6326
- 8. Tests Conducted: Hydrostatic "- Pneumatic F Nominal Operation Pressure F Exempt F" Other F Pressure PSI Test Temp. _ OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 2 of 2
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet Component Line Size: 1 1/2 in. (nominal) System Class: ASSME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2561-01 .00 Support/Restraint Sketch/Drawing No(s).: 2MCA-ND-6326 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhereon NIS-2 Form: PIP# M-I 1-0 1899 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist '.'. ,,,- Date March 21 ,2011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of
.Connecticut have inspected the components described in this Owner's Report during the period
- -t '22.
- / ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Ownrs Report. Furthermore, neit.thpi he Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fro0 r connected with this inspec n.
JF Swan , Commissions NC 1524, N-I Inspector's Signature'! National Board. State, Province, and Endorsements Dat a Dat ,20L6
FORM NIS-2 OWNER'S REPORT FC REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section X1
- 1. Owner Duke Energy.Carolinas_, L Date 4/3/2011 526 South Church. Street,..Charlotte, NC,.28201 Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear .Station. Unit 2 Name 12700 Haoers Feirry Road, Huntersville, NC 28078 1924239-04 Address Work Order # (or Repair/Replacement Organization P.O. No., lob No., etc.)
- 3. Work Performed by DQuke Energy Carolinas,.LLC . . N/A Type Code Symbol Stamp:
Name Authorization No.: N/A 526 South Church Street,. Charlotte,. NC 282l0-1006 Address Expiration Date: N/A
- 4. Identification of System NC - Reactor Coolant
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Ed it ion with the 1999 and 200.0 Addenda.
(c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2NC I Crosby N56925-00-0003 27 N/A 1974 Renmoved Yes
- 2NC I* Crosby N56925-00-0009 525 N/A 1978 Installed Yes
- 7. Description of Work RepJaned_ ComponetTart/Appurtenance Additional Description replaced valve 2NC 1.
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure [7 Exempt F Other F Pressure 2235 PSI Test Temp. "535 'F Description (Optional): testperformedper procedure MP/0/A/7650/076 aga.instork_order 0 _924575-01 (Class A Walk -Down fo2EOC20)
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of. 2 Component Line Size: 16 in. (nominal) System1 Class: ASME-Class-Weld Isometric Drawing No(s).: MCFI-2NC7 & 53 Flow Diagram No(s).: MCI ~D-2561-01 .00 Support/Restraint Sketch/Drawing, No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist -. 5#, .,.- Date April 3 ,2011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Nort h Carolina and employed by: Hartford Steam Boiler Inspection and Insurance Company of
'Connecticut have inspected the components described in this Owner's Report during the period to .t./" _ t/t/" , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code. Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthennore, neither the I0ector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from r connected with this inspecttion "JFSvan h Commissions .NC 1524, N-1 National Board. State, Province, and Endorsements Date( 2___________W____
I K ziossV CROSBY VALVE 8 GA GE CO M PANY CI W R ENTH AM , MASS 4.-
FORM NV-i FOR SAFETY AND SAFETY RELIEF VALVES Q.C.-44C As required by the provisions of the ASME Code Rule*
DATA REPORT Safety and Safety Relief Valves I. Manufactured By Crosby Valve & Gage Co., 43 Kendrick St., Wrentham, MA 02093 Name and Address 86 Model No. HB- -Brder No N300580J Contract Date /25/76ational Board No. 525 Charlotte, No. Carolina Order No. A 33957
- 2. Manufactured For Duke Power Co.,
Name and Address
- 3. owner Duke Power C,. , 422 South Church St., Chariotte, North Carolina 28201 Name and Address
- 4. Location of Plant McGuire Nuclear Station Unit, Cowans Ford, North Carolina 56 5 9
- 5. Valve Identification SPARE - 3 Serial No.N 92 -OO-00O Drawing No. DS-C-56925 Rev. C Type Safety Orifice Size. Pipe Size - Inlet_1.. _Outlet._. .
SafetySafety Relief. pilot. power Actuated Inch Inch Inch inch --
- 6. Set pressure (PSIG) 2485 700 F Rated Temperature I Stamped Capacity 420006 lbs./hr.
Hydrostatic Test (PSIC) Inlet 4575 Sat-. 3 Overpressure_
Complete Valve
- 7. The material, design. construction and workmanship comply with ASME Code, Section I1I.
Blowdown OU100 750 57' rlf S P.
Class 1 Fdition 1971 ,Addenda Date Winter 1972 Case No.
Pressure Containing or Pressure Retaining Components Serial No. Material Specification
- a. Castings Identification - Including Type or Grade Body N9039 7-33-0009 ASME SA351 Gr. CF8M t Bonnet N90353-44-0123 ASME SA105
- b. Bar Stock and Forgings 3
Dellojw K56 8 3 0023 N90356-41-0042 Inconel Alloy 718 Nozzle N90399-35-0009 ASME SA182 Gr. F316 Disc Insert N90426-36-0024 Haynes Stellite Alloy No. 6B N90350-17-0.69 Spring WashersK56380-30-0084 N90350- 2-0025 ASMF SA15 ASTM A193-70 Gr. B6 F Adjusting Bolt N90351-44-01 2 ASME SA193 Gr. B6 Spindle K56381-50-0144 N90354-52-0143 arli~rr B6B
1.1...
Serial No. or Material Specification Identification Including Type or Grade
- c. Spring K56380-39-0084 NX2761-0088 ASTM A304-76 51B60H
- d. Bolting
- e. Other Parts such as Pilot Components Qonnet Stud 87589 ASTM A193 cr. B7 N / 2371 AS'r- A197 CT,_ 24
,We certify that the statements made in tbis report are correct.
DateZ -7 19 '7ý Signed Crosbv Valve & Gage Co. By Manufact rer
.ertificate of Authorization No. 1878 expires September 30, 1980 CERTIFICATE OF SHOP INSPECTION I. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Proince of Mass and eniployed by Factory. LMutual Svstemq,ý_ _'=o* cd- "gs. / ave inspected the equipment desciued in z.ib Dja Re:)or on - !9 and state that to the best of my knowledge and belief. the Manufacturer hoi* constructed this equip-ment in accordance with the applicable Subsections of ASME Section III.
By signing this certificate, neither the Inspector nor his emploYer makes an. warranty, ex-pressed or implied. concerning the ecn:prmenr described in this Data Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injur% or property danmage or a loss of any kind arisirg from or connected with this inspection.
Date i__"7,"h-- )
- ' t' 1 Co.,missions (Inspector .nn B.ad.
- Arkwright-Boston Manufacturers 'lutual Insurance Company - Mutual Boiler & Machinery Division.
I I.;
DUKE POWER COMPANY QUALITY ASSURANCE DEPARTMENT SUPPLIER QUALITY ASSURANCE CERTIFICATION Name of Supplier Crosby Valve & Gage Company Date March 14, 1978 Address of Supplier Plant 43 Kendrick Street Mill Power Order No. A-33957 Wrentham, Mass, 02093 Duke Item or Req. No. Item 1 Spec. No. MCS-1205o09-i Rev.
Supplier ID Nos. N56925-00-0007, N56925-OO-0008. N56925-00-0009 Description of Component(s) or Material(s) Steel Safety Valves x Attached Documentation covers all Components/Materials on Mill Power Order.
Attached Documentation covers partial shipment of Components/Materials on Mill Power Order.
The following listed tests, inspections and reports have been completed as required by the speci fication:
X Physical G Chemical Analysis X Major Repair Records f Charts X Hydro (Test Pressure - PSIG 2485) X Personnel Qualifications on Record
- Crosby No. EC-158 & EC-427 X* Design Report N Stress Report X Heat Treatment Xj( Radiographic Test X Ultrasonic Test X Magnetic Particle Penetrant Test X. Repair NOE X Cleanliness Operating Test N Performance Curve ASME Data Report X Dimensional Check N7/5 Deviation Record #
I) Tested in accordance with Crosby Procedure T-16063 Opyv o
2) 3)
This certifies that the listed Component(s) or Material(s) conform to the requirements of the above referenced Duke Power documents including all codes, standards, test requirements and Quality Assurance requirements invoked therein.
Suppl ier Represenatni e Authiori Sign,,I.re Title Q. A. Supervisor Date '70_4ý1/ /4-/97c.
(See Instructions)
Form 930.IA / Rev. 3
FORM NIS-2 OWNER'S REPORT FOR. .?AIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI 1.Owner .Duke.Energy Carolinas, LILC . Date 3/16/2011 Charlotte, NC, 28201 5.26 South Church Street,. n .. . .Un.- Sheet I of 2 Address
- 2. Plant McGuire Nuclear rStation Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1925900-05 Address Work Order 0 (or Repair/Replacernent Organization P.O. No , lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Name Type Code Symbol Stamp:
Authorization No.:
526. South Church Street,.Char.lotte,.N.C._28.20 1-.0.0.6
.-.. N/A Address Expiration Date:
- 4. Identification of System NS - Containment Spray
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped ComponentIntle (esoN)
Name ofManufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-NS-4516 Duke Energy N/A N/A N/A N/A installed
- 7. Description of Work Replaced Com ponent/Part/A ppurte. ance Additional Description Installed items 8 (3x3x3/8 angle), 9 (3/8 x 5 x 8 plate), and 10 (3/8 x 3 3/4 x 7 1/16 plate) on hanger 2MCR-NS-4516 per EC101538.
FI Pneumatic F Nominal Operation Pressure r7 Exempt F Other F- Pressure .PSI Test Temp. OF
- 8. Tests Conducted: Hydrostatic Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 8 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2563-01.00 Support/Restraint Sketch/Drawing No(s).: 2MCR-NS-4516 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: EC101538 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 'FL Grass, Quality Assurance Technical Specialist .,,/ .- Date .March 16 20 I Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
.North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period
.to - /-3 Z/ and state that to the best ofmy knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective rnefsures described in this Owner's Report. Furthermore, neither the I pector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fr onnected with this pection.
JF Swan F", . Commissions :NC 1524, N-I National Board, State, Province, and Endorsements Date 6/
( Inspector's Signature 20o//
FORM NIS-2 OWNER'S REPORT FOl% JPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xi I. Owner DukeEnergy Carolin.as, Lt_LQ ------Date 3/27/2011 526 South Church Street, Charlotte, NC,282012 .. - Sheet of 2 Address
- 2. Plant McGuire Nuc~lear Station Unit 2 N'arne 12700 Hagers Ferr..Ty Road Huntersv ille, NC 28078 1927185-02 Address Work Order N(or Repair!Replacement Organization P 0. No., lob NoJ,etc.)
- 3. Work Performed by Duke Energy !Carolinas, LLC Narne Type Code Symbol Stamp:
Authorization No.:
5.26. South Church Street, Charlotte, N.C_9820 I-1006 Address Expiration Date:
- 4. Identification of System WL - Liquid Waste Recycle System
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity 1998_Edition with the 1-999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No)
WL system Duke Energy N/A 76 N/A 1982 Installed Yes 1_______________ 1 .1 __________ 1: [ ____ I__________ _____
- 7. Description of Work Rep laced Component/PartUAppunrteance Additional Description -Replaced disc and yoke on valve 2WL 1302.
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F Exempt F Other F Pressure 15 PSI Test Temp. amb OF Description (Optional): test performed per procedure PT/2/A/4200/00 .C by OPS. This ptipingoi openendedtocontainment and only sees system pressure for accide...
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: MCFI-2WL206 Flow Diagram No(s).: MCIFD-2565-0 1.00 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCM-1205.01-0246.001 & 002 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist
- Date March 27 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
.North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period 3 to- .Z*L/i .'L , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the In ctor nor his employer shiall be liable in any manner for any personal inijury or property damage or a loss of any kind arising from or nnected with this inspection.
JF Swan /.Commissions NC 1524, N-I
.Inspector's Signature National Board, State, Province, and Endorsements Date 20_fl
FORM NIS-2 OWNER'S REPORT FORK 'AIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LLC - Date 3/21/2011 526 South Church Street, Charlotte,.NC, 28201 . Sheet I of 2 Address
- 2. Plant McGuire. Nuclear. Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC. 2.80.78 192919 8-06 Address 1929198-06 Work Order # (or Repair/Replacement Organization P.O No, lob No, etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC 1T',
,*,"a*c.. t^le .... N/A Name I ype: Code S.ymbol Oatml~p; Authorization No.:
526 South Church Street, Charlotte, NC 2820 1-1006 Address Expiration Date: N/A
- 4. Identification of System NV - Chernical and Volume Control
- 5. (a) Applicable Construction Code ASME Il 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000.Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected. ASME Code Name of Manufacturer National Other Year Removed, or Stamped ComponentName oManufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2MCR-NV-5192 Duke Energy N/A N/A N/A N/A Installed No
- 7. Description of Work Re.placed Co mpQoDpertIn
/Pappt enance.
Additional Description replaced bolting material in pipe clamp on hanger 2MCR-NV-5192
- 8. Tests Conducted: Hydrostatic r Pneumatic F- Nominal Operation Pressure Fl Exempt FW Other F Pressure PSI Test Temp. _ I' Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASME.C ass_2 Weld Isometric Drawing No(s).:N/
Flow Diagram No(s).: .N/A Support/Restraint Sketch/Drawing No(s).: 2MCR-NV-5 192 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2NV201-002 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist , Date March 21 , 2 011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by, Hartford Steam Boiler Inspection and Insurance Company of
.Connecticut have inspected the components described in this Owner's Report during the period
-S- / -/-. to . 2"
" Z. , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner' Report. Furthermore, neither the In ctor nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from connected with this inspectin.
JF Swan Commissions ýNC 1524, N-I Inspector's Signature National Board, State, Province, and Endorsements IDate Dat . -2 , 20//'L
FORM NIS-2 OWNER'S REPORT FOR K AIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASRIE Code Section X I I. Owner Duke Energy Carolinas, Lt LC Date 3/20/2011 526 South Church Street, Charlotte, NC,-282.01 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road,. Hunt.ersville, NC 28078 01930670-89 Address Work Order # (or Repair/Replacement Organization P.O. No., lob No.. etc.)
- 3. Work Performed by Duke Energy Carolinas, LL.C N/A Type Code Symbol Stamp:
Name Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006..
Address Expiration Date: N/A
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the .1999 and 200.0 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identifittcatin nf C'nmn"ctnentt Corrected, ASME Code Name of' Manufacturer National Other Year Removed, or Stamped Component Name of N'lanttrer Serial No. Board No. Identification Built Installed (Yes or No) 2MCA-NV-5405 Duke Energy 3565 N/A N/A N/A Removed No 2MCA-NV-5405 Duke Energy 30700004/010 N/A N/A N/A Installed No
- 7. Description of Work Repplaced Component/Part/Appurtenance Additional Description re placed snubber on hanger 2MCA-NV-5405
- 8. Tests Conducted: Hydrostatic " Pneumatic "- Nominal Operation Pressure F Exempt F" Other F- Pressure PSI Test Temp. _ (
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2. of 2 Component Line Size: 2 in. (nominal) System Class: ASNE Class 2 Weld Isometric Drawing No(s).: N/A Flow Diagram No(s).: MCFD-2554-03.01 Support/Restraint Sketch/Drawing No(s).: 2MCA-NV-5405 Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2*NV-_53-0001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist - ".*,,, - Date March 20 ")011 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Confpany of Connecticut have inspected the components described in this Owner's Report during the period
/ / to 3- 2.- 2 -2/1 ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the spector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from r connected with this inspection.
JF Swanot -Commissions NC1524, N-I
-j 2--2--Signature_.. / *Inspector's 20/
National Board, State. Province, and Endorsements
FORM NIS-2 OWNER'S REPORT FOi £PAIR/REPLACEMENT ACTIVITY As Required hy the Provisions of rhe AS ME Code Section XI
- 1. Owner Duke Energy Carolinas, LLC Date 4/3/2011 526 South Church Street, Charlotte, NC, 28201 Sheet 1 of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersvit!e_.NC 28Q78 1932306-02 Address Work Order # (or Repair/Replacement Organization P.O. No., lob No, etc )
- 3. Work Performed by Duke Energy Carolinas_,_L.C N/A Name Type Code Symbol Stamp:
Authorization No.: N/A 526 South.Chturch Street, Charlotte,.NC.28201-1.00_6 Address Expiration Date: N/A
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME 111 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section X I used for Repair/Replacement Activity 1998 Editjon with the 1999 and 2..00.0 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Corn onents Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name of Manufacturer Serial No. Board No. Identification Built Installed (Yes or No) 2NV248 Kerotest ATH7-4 38542 N/A 1991 Installed Yes
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description replaced disc on valve 2NV248.
- 8. Tests Conducted: Hydrostatic F Pneumatic F- Nominal Operation Pressure F.. Exempt F Other F- Pressure PSI . Test Temp. __
Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASIME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 - in. (nominal) System Class: ASME Class 2 Weld Isometric Drawing No(s).: MCFI-2NV294 Flow Diagram No(s).: MCFD-2554-03-.OO Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCM 1205.01-0042.001, MCSRD-2NV350 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date April 3 , 20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of
- Connecticut have inspected the components described in this Owner's Report during the period
-t to , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XL.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither t Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from r connected with this .1sectio '
JF Swan J -/ ,.,," Commissions NC 1524, N-I lop, Sinatr'l--
Inspctors ational Board, State, Province, and Endorsements Date20L
FORM NIS-2 OWNER'S REPORT FO, 7PAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke- Energy Carolinas, LLC . Date 4/3/2011
.52.6._South Church Street, Charlotte,.NC, 28201 Sheet I of 2 Address
- 2. Plant. McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1933815-07 Address Work Order N (or Repair/Replacement Organizaton P1 No., lob No., etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC Name Type Code Symbol Stamp:
Authorization No.:
526 South Church Street, Charlotte, NC 28201-1006 Address Expiration Date:
- 4. Identification of System NI - Safety Injection
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Sumnmer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Namie of' Manufacturer National Other Year Removed, or Stamped CoN eponent of tvla cturer Serial No. Board No. Identification Built Installed (Yes or No) 2N171 Walworth A0148 209 N/A 1974 Installed Yes
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description replaced disc and bonnet nuts on valve 2N17 1.
- 8. Tests Conducted: Hydrostatic r Pneumatic r Nominal Operation Pressure F Exempt I Other F Pressure 2235 PSI Test Temp. 535 OF Description (Optional): test performed per procedure MP/0/A/7650/076_against work order 0 924575-01 _(Class A Walk -Down for 2EOC20)
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI 9.. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 10 in. (nominal) System Class: ASME Class I Weld Isometric Drawing No(s).: MCFI-2NV254 Flow Diagram No(s).: MCFD-2562-02.00 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Date April 3 20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
,North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of
- Connecticut have inspected the components described in this Owner's Report during the period S.to- , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and.corrective measures described in this Owner's eport. Furthermore, neither the Insp or nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from o fonnected with this inspection.
JF Swan Commissions ,NC 1524, N-1 I tor's r Nitional Board, State, Province, and Endorsements Date q "" 20
FORM NIS-2 OWNER'S REPORT FO. .EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke Energy Carolinas, LL *C Date 4/3/2011
.526._South Church Street,, Charlotte,. NC_,..2820]1 ...... Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 1.2700 Hagers.Ferry. Road, Huuntersville._NC 28078 1972897-02 Address Work Order N (or Repair/Replacement Organization P.O. No , lob No, etc.)
- 3. Work Performed by Duke Energy Carolinas, LLC kr/A Type Code Symbol Stamp: "'
Name Authorization No.: N/A 526 South Church Street, Charlotte, NC 28.201-10.066. Da:N/A Address Expiration Date:
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME III 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity *1998 Edition with .the 1999. and.2000 .Ad0denda (c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected. ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Installed (Yes or NO)
Name of Manufacturer Serial No. Board No. Identification Built NV Piping Duke Energy N/A 80 N/A 1982 Installed Yes
- 7. Description of Work Add New Compo_.e(nt/Part/Appurtienance/ýWeld Additional Description mtade.weld repair on weld NV2FW 183-28
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F Exempt F Other F Pressure 2514 PSI Test Temp. 90.6 OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the AS ME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASME C-lass 2 Weld Isometric Drawing No(s).: MCFI-2NV183 Flow Diagram No(s).: MCIFD-2554-01.01 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist Z/ Date April 3 ,20 11 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by Hartford Steam Boiler Inspection and Insurance Company of Connecticut have inspected the components described in this Owner's Report during the period to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fromor connected with this inspect JF Swanl _.. 0- -j2- I .n,,.-. Commissions NC 1524, N- l Inspector'sonal Board, State Province, and Endorsements Date0 *//-.S , 20.__
FORM NIS-2 OWNER'S REPORT FO, .EPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Cede Section XI
- 1. Owner Duke Energy Carolinas, LILC Date 4/3/2011 526 South Church Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear-Station Unit 2 Namne 12700 Hagers Ferry Road, Huuntersville, NC 28078 1973388-05 Address Work Order 9 (or Repair/Replacement Organization P.O No lob No., etc
- 3. Work Performed by Duke Energy Carolinas, LLC Tvpe Code Symbol Stamp: NiA Name Authorization No.: N/A 526 South Church Street, Charlotte,_NC_.8_20 1-1006 N/A Address Expiration Date:
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME 111 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section XI used for Repair/Replacement Activity 1998 Edition with the 1999 and 2000 Addenda (c) Applicable Section Xl Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Y'ear Removed, or Stamped Component Name of ManUfacturer Serial No. Board No. Identification Built Installed (Yes or No)
NV Piping Duke Energy N/A 80 N/A 1982 Installed Yes
- 7. Description of Work Re placed Component/Part/Appurtenance Additional Description Welds NV2FW293-12, 38, and 39 were cut out and remade
- 8. Tests Conducted: Hydrostatic - Pneumatic F Nominal Operation Pressure Exempt F Other F Pressure 2500 PSI Test Temp. 90.6 OF Description (Optional):
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 2 in. (nominal) System Class: ASME.Cl1a.ss.2 Weld Isometric Drawing No(s).: MCFI-2NV293 Flow Diagram No(s).: MCF D-2554-03.00 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form:
Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify, that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist -. :-x Date April 3 20.1L Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
- North Carolina and employed by !Hartford Steam Boiler Inspection and Insurance Company of
ýConnecticut have inspected the components described in this Owner's Report during the period
-to V- 5; - and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the lpector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fr*om oconnected with this inspection.
Swan .-. Commissions NC1524, N-I
/Inspector's Signature 11/National Board, State, Province, and Endorsements Date ), °_ 20 /
FORM NIS-2 OWNER'S REPORT FOR PAIRIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 1. Owner Duke.Energy Carolinas, LL C Date 4/19/2011 526 South Church. Street, Charlotte, NC, 28201 Sheet I of 2 Address
- 2. Plant McGuire Nuclear Station Unit 2 Name 12700 Hagers Ferry Road, Huntersville, NC 28078 1974289-02 Address Work Order fP(or Repair/Replacement Organization P 0. No lob No., etc
- 3. Work Performed by Duke Energy Carolinas, LLC N/A Narne Type Code Symbol Stamp:
Authorization No.: N/A 526 South Church Street, Charlotte, NC 28201-1006 N/A Address Expiration Date:
- 4. Identification of System NV - Chemical and Volume Control
- 5. (a) Applicable Construction Code ASME II1 19 71 Edition, Summer and Winter Addenda, N/A Code Case (b) Applicable Edition of Section Xl used for Repair/Replacement Activity 19918 Edition with the. 1999 and 200...Adden~da.
(c) Applicable Section XI Code Case(s) N/A
- 6. Identification of Components Corrected, ASME Code Name of Manufacturer National Other Year Removed, or Stamped Component Name otMantacturer Serial No. Board No. Identification Built Installed (Yes or No)
.NV Piping Duke Energy N/A 80 N/A 1982 Installed Yes
- 7. Description of Work Replaced Component/Part/Appurtenance Additional Description Rep!aced bolting material in flange down stream of valve 2NV810.
- 8. Tests Conducted: Hydrostatic F Pneumatic F Nominal Operation Pressure F' Exempt F Other F Pressure 2235 PSI Test Temp. 535 OF Description (Optional): test performed per procedure MP/0/A/07650/076 on w/o 1924575 (Class A walk-down for 2EOC20)
FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI
- 9. Remarks (Should Include the Following Information, as Applicable): Sheet 2 of 2 Component Line Size: 1 1/2 in. (nominal) System Class: ASME_Class I Weld Isometric Drawing No(s).: MCFI-2NV275 Flow Diagram No(s).: MCFD- 2554-0 1.00 Support/Restraint Sketch/Drawing No(s).: N/A Other Applicable Information (e.g., W.O. No., EC No.) if not included elsewhere on NIS-2 Form: MCSRD-2NV-206-001 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed FL Grass, Quality Assurance Technical Specialist . Date April 19 :, 2011 Owner or Owner's Designee, Tttle CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by .Hartford Steam Boiler Inspection and Insurance Company of
- .Connecticut have inspected the components described in this Owner's Report during the period
_-, 2-.6 -" 1 to Iand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthemore, neither the Ins ector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from /connected with this inspection.
JF Swan 10 -. - Cnmmissions NBI 1473-NC1524, N-I Inspector's Signature - National Board, State, Province, and Endorsements Date/ 2)0 Y
6.0 PressureTestina Second Period- Third JO-Year Interval There is (1) Class I (Category B-P) pressure test zone that requires pressure testing each refueling outage. Table 6-1 shows a completion status of the Class I (Category B-P) pressure test zone conducted during refueling cycle EOC 20. There was no through-wall leakage observed during this pressure test.
Table 6-1 DetailedClass I Listing EOC20 Zone Completion EOC20 VT-2 Number Boundary Dwg Status Examination Date Code Cases Used 2NC-001L-A MC-ISIL-2553-01.00 Complete 04/01/2011 None MC-ISIL-2553-02.00 MC-ISIL-2553-02.01 MC-ISIL-2554-01.00 MC-ISIL-2554-01.01 MC-ISIL-2554-01.02 MC-ISIL-2561-01.00 MC-ISIL-2562-01.00 MC-ISIL-2562-02.00 MC-ISIL-2562-02.01 MC-ISIL-2562-03.00 I____ _ MC-ISIL-2562-03.01 I I There are (66) Risk Informed Segments (Category R-A) that are required to receive a pressure test each refueling cycle. Table 6-2 shows a completion status of the (66)
Risk Informed Segments pressure tested during refueling cycle EOC 20. There was no through-wall leakage observed during these pressure tests.
Table 6-2 DetailedRisk Informed PressureTest Listing EOC20 Zone Segment Completion EOC20 VT-2 Number Boundary Dwp Number Status Examination Date I 2NC-001L-A MC-ISIL-2553-01.00 NC-18 Complete 04/01/2011 2 MC-ISIL-2553-02.00 NC-19 3 MC-ISIL-2554-01.00 NC-20 4 MC-ISIL-2554-01.01 NC-21 5 MC-ISIL-2562-01.00 NC-23 6 NC-086 7 NC-89 8 NC-90 9 NC-054 10 1 NC-055 I EOC 20 / Outage 5 Page 1 of 6 McGuire Unit 2 Revision 0 Section 6 - Third Ten-Year Interval May 25, 2011
Table 6-2 DetailedRisk Informed PressureTest Listing EOC20 Zone Segment Completion EOC20 VT-2 Number Boundary Dwg Number Status Examination Date 11 2NC-0I1L-A NC-056 12 (Continued) NV-033A 13 NV-033B 14 NV-034A 15 NV-034B 16 NV-037 17 NV-038 18 NV-041A 19 NV-041B 20 NV-042A 21 NV-042B 22 NV-030A 23 NV-030B 24 NV-032A 25 NV-032B 26 NV-035 27 NV-036 28 NV-039A 29 NV-039B 30 NV-040A 31 NV-040B 32 NI-068 33 NI-069 34 NI-070 35 NI-071 36 2RI-001 L-B MC-ISIL-2554-01.00 NI-063B Complete 04/02/2011 37 MC-ISIL-2554-01.01 ND-008C 38 MC-ISIL-2554-01.02 ND-009C 39 MC-ISIL-2554-01.03 NV-002AB 40 MC-ISIL-2554-03.00 NV-002C 41 MC-ISIL-2554-03.01 NV-002D 42 MC-ISIL-2561-01.00 NV-011A 43 MC-ISIL-2562-01.00 NV-019B 44 MC-ISIL-2562-03.00 NV-019C 45 NV-019D 46 NV-019E 47 NV-019AA 48 U .,.
NV-019AB J A EOC 20/ Outage 5 Page 2 of 6 McGuire Unit 2 Revision 0 Section 6 - Third Ten-Year Interval May 25, 2011
Table 6-2 DetailedRisk Informed PressureTest IUstng EOC20 Zone Segment Completion EOC20 VT-2 Number Boundary Dwg Number Status Examination Date 49 2RI-001 L-B NV-019AD 50 (Continued) NV-020AA 51 NV-020AB 52 NV-020AD 53 NV-020AE 54 NV-021A 55 NV-021B 56 NV026 57 NV027 58 NV-028 59 NV-029 60 NV-080A 61 NV-080B 62 NV-084A 63 NV-084B 64 NV-084C 65 NV-108A 66 1 NV-109 EOC 20 / Outage 5 Page 3 of 6 McGuire Unit 2 Revision 0 Section 6 - Third Ten-Year Interval May 25, 2011
There are (35) Class 2 (Category C-H) pressure test zones that require pressure testing once each Inspection Period. Table 6-3 shows a completion status of the (35) Class 2 (Category C-H) pressure tests zones that require pressure testing for the Second Period of the Third Ten-Year Interval (from 03/01/07 through 07/15/11). There was no through-wall leakage observed during these pressure tests.
Table 6-3 DetailedClass 2 Second PeriodListing VT-2 Code Examination Cases Zone Number Boundary Dwg Completion Status Date Used 1 2BB-040L-B MC-ISIL-2580-01.00 Incomplete N/A 2 2BB-074L-B MC-ISIL-2572-03.00 Complete 10/0912009 None MC-ISIL-2580-01.00 MC-ISIL-2584-01.00 3 2CA-040L-B MC-ISIL-2592-01.00 Incomplete N/A 4 2CA-043L-B MC-ISIL-2584-01.00 Incomplete N/A MC-ISIL-2591-01.01 MC-ISIL-2592-01.00 MC-ISIL-2617-01.00 5 2FW-007L-B MC-ISIL-2554-03.00 Complete 11/10/2010 None MC-ISIL-2554-03.01 MC-ISIL-2561-01.00 MC-ISIL-2562-03.00 MC-ISIL-2563-01.00 MC-ISIL-2571 -01.00 6 2NC-001L-A MC-ISIL-2553-01.00 Complete 04/10/2008 None MC-ISIL-2553-02.00 MC-ISIL-2554-01.00 MC-ISIL-2554-01.01 7 2ND-009L-B MC-ISIL-2554-01.02 Incomplete N/A MC-ISIL-2561-01.00 MC-ISIL-2562-03.00 MC-ISIL-2562-03.01 MC-ISIL-2563-01.00 MC-ISIL-2571-01.00 MC-ISIL-2572-01.00 EOC 20 / Outage 5 Page 4 of 6 McGuire Unit 2 Revision 0 Section 6 - Third Ten-Year Interval May 25, 2011
Table 6-3 DetailedClass 2 Second PeriodListin g VT-2 Code Zone Number Boundary Dwg Completion Status Examination Cases I Date Used 8 2ND-010L-B MC-ISIL-2561-01.00 Incomplete NIA MC-ISIL-2562-03.01 MC-ISIL-2563-01.00 9 2NI-012L-B MC-ISIL-2562-02.00 Complete 04/08/2008 None MC-ISIL-2572-01.01 10 2NI-013L-B MC-ISIL-2562-02.01 Complete 04108/2008 None MC-ISIL-2572-01.01 11 2NI-014L-B MC-ISIL-2562-02.01 Complete 04/03/2008 None MC-ISIL-2562-03.00 12 2NI-015L-B MC-ISIL-2562-03.00 Incomplete N/A 13 2NI-016L-B MC-ISIL-2562-03.00 Complete 11/01/2010 None 14 2NI-017L-B MC-ISIL-2562-03.00 Incomplete N/A MC-ISIL-2562-03.01 15 2NI-01 8L-B MC-ISIL-2562-03.01 Complete 03104/2011 None 16 2NI-060L-B MC-ISIL-2562-03.00 Complete 10/05/2009 None 17 2NI-061 L-B MC*-ISIL-2562-01.00W Complete 02/25/2011 None 18 2NI-062L-B MC-ISIL-2562-01.00 Incomplete N/A 19 2NM-026L-B MC-ISIL-2572-01.01 Complete 10/09/2009 None 20 2NM-027L-B MC-ISIL-2572-03.00 Incomplete N/A 21 2NS-019L-B MC-ISIL-2563-01.00 Complete 01/1412011 None 22 2NS-020L-B MC-ISIL-2563-01.00 Complete 12/02/2010 None 23 2NV-003L-B MC-ISIL-2554-01.00 Incomplete N/A MC-ISIL-2554-01.01 MC-ISIL-2554-01.02 MC-ISIL-2554-01.03 24 2NV-004L-B MC-ISIL-1 554-05.00 Incomplete N/A MC-ISIL-2554-01.00 MC-ISIL-2554-01.01 MC-ISIL-2554-01.02 MC-ISIL-2554-02.00 MC-ISIL-2554-02.01 EOC 20 / Outage 5 Page 5 of 6 McGuire Unit 2 Revision 0 Section 6 - Third Ten-Year Interval May 25, 2011
Table 6-3 DetailedClass 2 Second PeriodListing VT-2 Code Zone Number Boundary Dwg Completion Status Examination Cases Date Used 24 2NV-004L-B MC-ISIL-2554-03.00 Incomplete N/A MC-ISIL-2554-03.01 MC-ISIL-2561-01.00 MC-ISIL-2562-01.00 MC-ISIL-2562-03.00 25 2NV-005L-B MC-ISIL-2554-01.02 Incomplete N/A 26 2NV-006L-B MC-ISIL-2554-03.00 Complete 02/02/2011 None 27 2NV-008L-B MC-ISIL-2554-01.02 Complete 10/4/2009 None 28 2NV-011L-B MC-ISIL-2554-03.01 Complete 10/18/2010 N'ri" 29 2RN-044L-B MC-ISIL-2574-04.00 Incomplete N/A 30 2RV-048L-B MC-ISIL-2604-03.00 Complete 08/30/2010 None 31 2SA-047L-B MC-ISIL-2593-01.02 Incomplete N/A 32 2SM-040L-B MC-ISIL-2591-01.01 Incomplete N/A MC-ISIL-2593-01.00 MC-ISIL-2593-01 .03 33 2SM-045L-B MC-ISIL-2593-01.00 Complete 09/20/2010 None
(.
MC-ISIL-2593-01.02 MC-ISIL-2593-01.03 34 2SM-046L-B MC-ISIL-2593-01.00 Complete 09/20/2010 None MC-ISIL-2593-01.03 35 2YA-063L-B MC-ISIL-2617-01.00 Incomplete N/A Section 6 Prepared By: Date:
Section 6 Revirwed By: Dae:
(, "N EOC 20 / Outage 5 Page 6 of 6 McGuire Unit 2 Revision 0 Section 6 - Third Ten-Year Interval May 25, 2011