Text
Bok90f1 k~.Final Status Survey Final Report Phase IV Appendix A8 Survey Unit Release Record 9106-0008, Discharge Canal November 2006 CYAPCO FINAL STATUS SURVEY RELEASE RECORD DISCHARGE CANAL SURVEY UNIT 9106-0008 Prepared By: Reviewed By: FSSEnineer~
Date: Date: j F, ,ngineer Approved By: CAIr Date:" Technical Support Manager Revision 0 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD TABLE OF CONTENTS 1. SURVEY UNIT DESCRIPTION
.................................................................
3 2. CLASSIFICATION BASIS ......................................................................
3 3. DATA QUALITY OBJECTIVES (DQO) ....................................................
5 4. SURVEY DESIG N .....................................................................................
8 5. SURVEY IMPLEMENTATION
................................................................
11 6. SURVEY RESULTS ...............................................................................
12 7. QUALITY CONTROL .............................................................................
13 8. INVESTIGATIONS AND RESULTS ......................................................
14 9. REMEDIATION AND RESULTS .............................................................
14 10. CHANGES FROM THE FINAL STATUS SURVEY PLAN .....................
14 11. DATA QUALITY ASSESSMENT (DQA) .................................................
14 12. A NO M A LIES ...........................................................................................
15 13. CO NCLUSIO N .......................................................................................
15 14. ATTACHM ENTS .....................................................................................
16 14.1 Attachment 1 -Figures (7 pages including cover)14.2 Attachment 2 -Sample and Statistical Data (203 pages including covers)Revision 0 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD SURVEY UNIT DESCRIPTION Survey Unit 9106-0008 (Discharge Canal) is designated as Final Status Survey (FSS) Class 2 and consists of approximately 9,763 m 2 (2.41 acres) of water covered sediment in an area located approximately 0.92 miles from the reference coordinate system benchmark used at the Haddam Neck Plant (HNP)(see Attachment 1, Figure 1). The Discharge Canal is a man-made mile long waterway that runs parallel to, and ultimately communicates with the Connecticut River. The Discharge Canal is subdivided into fifteen (15) survey units including two (2) permanent wetland areas for FSS purposes.
The survey unit is bounded as follows: Discharge Canal Survey Unit 9106-0007 is to the north (called north as orientated with the north to south flow of the Connecticut River), Survey Area 9523 is to the east, Discharge Canal Survey Unit 9106-0009 is to the south and South Peninsula Survey Area 9531 (formerly a part of 9530) is to the west. The survey unit comprises the canal sediments to the deeper of three feet or the original construction depth and it extends up the canal banks to the mean high water level.The reference coordinates associated with this survey unit are E019 through E026 by S143 through S153 (refer to License Termination Plan Section 5.4.4).The reference coordinates provide the maximum dimensions of a rectangle containing this survey unit. Some areas contained in this rectangle may not be part of this survey unit. The boundary of the survey unit was defined using a Global Positioning System (GPS) based on the Connecticut State Plane System North American Datum (NAD) 1927.2. CLASSIFICATION BASIS The survey unit was classified in accordance with Procedure RPM 5.1-10,"Survey Unit Classification. " The historical information, scoping analyses and characterization results provided sufficient data to designate Survey Unit 9106-0008 as Class 2 in May 2006.The "Classification Basis Summary" conducted for this survey unit consisted of: a) A review of the 10CFR50.75 (g) (1) database, b) A review of the "Initial Characterization Report" and the "Historic Site Assessment (HSA) Supplement, " c) Historic and current survey records review, d) Visual inspections and a "walkdown." e) Formal or informal interviews with cognizant personnel.
A review of the 1OCFR50.75(g)(1) database report identified a number of events that may have impacted this survey unit. In 1986, samples were taken from the legacy dredge spoils removed in 1979 dredged spoils area and from recently dredged canal sediment.
The sample analyses indicated that the Revision 0 3 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD concentrations of Cs-137, Co-60 and other radionuclides were a small fraction of the DCGLs for those nuclides that could be identified by gamma spectroscopy. (refer to NE-86-RA-1142 dated 11-13-86).
None the available historical information reviewed would support a conclusion that any residual activity in this survey unit is likely to be present at concentrations greater than the respective DCGLs.Additional information was provided by several historical documents, including the "Results of Scoping Survey", (completed 9/1/98), the "Historical Site Assessment", and the HSA Supplement (dated 6-30-00).
These documents presented the results of several sediment samples taken in 1997. These sample results indicated concentrations of 0.5 pCi/g for Co-60, 0.024pCi/g for Cs-134 and 0.722 pCi/g for Cs-137.An initial characterization survey was implemented during April and May of 2004. However, none of the sampling fell inside the footprint of 9106-0008.
In an adjacent Survey Unit (9106-0009) six (6) samples from three (3) locations were obtained by biased sampling throughout the area. The samples were analyzed off-site by gamma spectroscopy and with radiochemical analyses for Sr-90 and Tritium. Hard-to-Detect analyses were also conducted on one (1) of the six (6) samples. The only plant-related dosimetrically significant radionuclides identified in the samples were Cs-137, Cobalt-60 and Ni-63. No samples indicated radioactive material in quantities above the ten (10) mrem/yr design DCGL. Cobalt-60 accounted for the majority of the dose in these samples with a maximum concentration of 0.57 pCi/g.A final characterization was performed by Site Closure personnel in April of 2006. Six (6) sediment samples from six (6) locations were taken. All of the samples were analyzed by gamma spectroscopy.
Based on the initial and final characterization results, the radionuclides of concern identified in the sample data for FSS planning purposes were Cesium-137, Cobalt-60 and Ni-63. Since HTD analyses were not performed for all radionuclides of interest during characterization, additional HTD analyses were performed as a part of the FSS.The statistics for each of the radionuclides of concern are listed in Table 1.Additionally, since Sr-90 was a radionuclide of concern in an adjacent Survey Unit (9106-0007), it was decided that testing for this isotope was an appropriate conservatism.
Revision 0 4 Revision 0 4 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD minimum value: -4.YiL-UJ -i ./4L-U4 -I .tLt+UU Maximum Value: 2.5 1E-01 5.87E-01 3.47E+O1 Mean: 1.39E-01 3.28E-01 1.65E+01 Median: 1.42E-01 3.1 OE-01 1.65E+0 I Standard Deviation:
9.84E-02 2.09E-01 2.57E+O1 NOTE: The Operational DCGLs are 6.01 pCi/g for Cs-137, 2.90 pCi/g for Co-60 and 549 for Ni-63; these are used in conjunction with the unity rule to achieve nineteen (19)mnremn/yr TEDE.The FSS Engineer performed a visual inspection and walk-down during May 2006 to assess the physical condition of the survey unit, evaluate access points and travel paths and identify potentially hazardous conditions.
Based upon the historical information and the results of radiological surveys performed during characterization, it was concluded that there was a low probability for residual radioactivity to be present in this survey unit in concentrations greater than the Operational DCGLs justifying a final survey unit classification of Class 2 (refer to Section 3).3. DATA QUALITY OBJECTIVES (DQO)FSS design and planning is based on the Data Quality Objective (DQO) process as described by the LTP, Procedure RPM 5.1-11, "Preparation of Final Status Survey Plan, " and the "Multi-Agency Radiation Survey and Site Investigation Manual" (MARSSIM).
A summary of the main features of the DQO process are provided herein.The DQO process incorporates hypothesis testing and probabilistic sampling distributions to control decision errors during data analysis.
Hypothesis testing is a process based on the scientific method that compares a baseline condition to an alternate condition.
The baseline condition is technically known as the null hypothesis.
Hypothesis testing rests on the premise that the null hypothesis is true and that sufficient evidence must be provided for rejection.
In designing the survey plan, the underlying assumption, or null hypothesis was that residual activity in the survey unit exceeded the release criteria.
Rejection of the null hypothesis would satisfy the release criteria objective of the FSS.The primary objective of the Final Status Survey Plan (FSSP) was to demonstrate that the level of residual radioactivity in Survey Unit 9106-0008 did not exceed the release criteria specified in the LTP and that the potential dose from residual radioactivity is As Low As Reasonably Achievable (ALARA).Revision 0 5 Revision 0 5 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD A fundamental precursor to survey design is to establish a relationship between the release criteria and some measurable quantity.
This is done through the development of Derived Concentration Guideline Levels (DCGLs). The DCGLs represent the concentration of radioactivity above background, equivalent to a dose-based release criterion and is presented in terms of surface or mass activity concentrations.
Chapter 6 of the LTP describes in detail the modeling used to develop the DCGLs for soil (called Base Case Soil DCGL), for existing groundwater radioactivity and for future groundwater radioactivity that will be contributed by building foundations and footings.As described in detail in the LTP, the dose model applied to the discharge canal presumes that the canal sediments are dredged to a depth of three (3) feet below the top of the sediment layer and spread for the planting of crops per the Resident Farmer Scenario.
Consequently, the soil DCGLs are directly applied to the canal sediment media.The DCGLs presented in Chapter 6 of the LTP were developed for exposures from three (3) components, that is, residual radioactivity in soil, existing groundwater radioactivity, and future groundwater radioactivity from the burial of concrete foundations or footings from site buildings containing residual radioactivity.
Equation 1 shows the mathematical relationship between the three (3) components and the total dose.Equation 1: HTotal=Hsoil (sediment)
+ HExisting GW + HFuture GW The total dose under the LTP criteria is twenty-five (25) mrem/yr TEDE from all three components.
The allowable total dose under the Connecticut Department of Environmental Protection (CTDEP) radiological remediation standard for Connecticut Yankee (CY) is nineteen (19) mrem/yr TEDE. To satisfy both the LTP and CY CTDEP criteria, the dose from soil must be reduced when using the groundwater dose values discussed above.This survey unit is not affected by either existing groundwater or by future groundwater (reference CY memo ISC 06-024). Therefore, dose contribution from both existing and future groundwater is zero (0) mremryr TEDE, based on field data.Equation 2: 19 mrem/yr 1 otal= 19 mrem/yrsoil+0 mrem/yrExisting GW+O mrem/yrFuture GW The allowable dose for sediment in this survey unit is nineteen (19) mrem/yr TEDE as shown by Equation 2 above. The concentration of residual radioactivity resulting in nineteen (19) mrem/yr TEDE is designated as the Operational DCGL, and has been established for the radionuclides of concern Revision 0 6 Revision 0 6 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD as provided in Table 2. Note: the survey design used a much smaller value for investigation than the Operational DCGL provided by Table 2 to conservatively account for the contribution to the total dose from existing and future groundwater which had not been established at the time of planning the FSS.STable 2 -Radiorniidlide SpecificRseCs Bc SoiCl (( ,Oeaini C~and Required Minimium Dfetetable Concentrations Radionuclide
() BaseCase Soil Operational DCGL Required NDC DCGL (g~i/g) (2) (jpCi/g 3 (3)J(p c i/g)S H-3 4.12E+02 3.13E+02 1.65E+01 C-14 5.66E+00 4.30E+00 2.26E-01 Mn-54 1.74E+01 1.32E+O1 6.96E-01 Fe-55 2.74E+04 2.08E+04 1.1OE+03 Co-60 3.81E+00 2.90E+00 1.52E-01 Ni-63 7.23 E+02 5.49E+02 2.89E+OI Sr-90 1.55E+00 1.18E+00 6.20E-02 Nb-94 7.12E+00 5.41 E+00 2.85E-0 I Tc-99 1.26E+01 9.58E+00 5.04E-0 I Ag- 108m 7.14E+00 5.43 E+00 2.86E-01 Cs- 134 4.67E+00 3.55E+00 1.87E-01 Cs-137 7.91E+00 6.01E+00 3.16E-0 I Eu- 152 1.01E+01 7.68E+00 4.04E-01 Eu-154 9.29E+00 7.06E+00 3.72E-01 Eu- 155 3.92E+02 2.98E+02 1.57E+01 Pu-238 2.96E+01 2.25E+01 1.18E+00 Pu-239/240 2.67E+01 2.03 E+0I 1.07E+00 Pu-241 8.70E+02 6.61E+02 3.48E+0I Am-241 (5) 2.58E+01 1.96E+O1 1.03E+00 Cm-243/244 2.90E+O1 2.20E+O1 1.16E+00 (1) Bold indicates those radionuclides considered to be Hard to Detect (HTD)(2) The Base Case Soil DCGLs for soil are specified by the LTP in Chapter 6 and are equivalent to twenty-five (25) mrem/yr TEDE (3) The Operational DCGL is equivalent to nineteen (19) mrem/yr TEDE (4) The required MDC is equivalent to one (1) mrem/yr TEDE (5) Americium-241 can be analyzed by gamma and alpha spectroscopy and is considered to be Easy to Detect (ETD). The preferred result is the alpha spectroscopy's when both analyses are performed.
Another important facet of the DQO process is to identify the radionuclides of concern and determine the concentration variability.
Characterization was completed in April of 2006 as discussed in Section 2. Cesium-137, Cobalt-60 Revision 0 7 Revision 0 7 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD and Nickel-63 were found to be the predominate radionuclides of concern. The basic statistical quantities (i.e., mean, standard deviation, median) for Cs-137, Co-60 and Ni-63 are provided in Table 1.Laboratory DQOs and analysis results were to be reported as actual calculated results. Results reported as less than Minimum Detectable Concentration
(<MDC) would not be accepted for FSS. Sample report summaries were to include unique sample identification, analytical method, radionuclide, result, and uncertainty of two standard deviations, laboratory data qualifiers, units, and the required and observed MDC.4. SURVEY DESIGN The level of effort associated with planning a survey is based on the complexity of the survey and nature of the hazards. To assist the FSS Engineers when preparing survey plans for FSS, guidance is provided in Procedure RPM 5.1-11,"Preparation of Final Status Survey Plans". By design, the FSSP meets the ALARA criteria for soils as specified in Chapter 4 of the LTP. The FSSP uses an integrated sample design that combines scanning surveys and sampling which can be either random or biased.Characterization was performed by Site Closure personnel in April and May 2006 to determine existing conditions and obtain radiological data for Final Status Survey (FSS). The DQO process determined that Cs-137, Co-60, Sr-90 and Ni-63 would be the radionuclides of concern (refer to Section 3). The sum of fractions or unity rule would be used with the individual Operational DCGLs because multiple radionuclides (Cs-137, Co-60, Sr-90 and Ni-63) were considered in the survey design. Other radionuclides identified during FSS would be evaluated to ensure adequate survey design and compliance with the unity rule.Surrogate DCGLs were not required for this survey unit based on process knowledge from FSS of nearby adjacent areas and via screening process described in LTP Section 5.4.7.2, "Gross Activity DCGLs". Sr-90 concentrations in sediment and soil were ascertained by direct analysis.Radionuclide screening or de-selection is a process where an individual radionuclide or aggregate may be considered insignificant and eliminated from the FSS. The criteria for de-selection are concentrations that are less than 5%for individual radionuclides and that are less than 10% for the aggregate of all radionuclides that are de-selected.
This process was applied to analysis data for this survey unit.The Elevated Measurement Comparison (EMC) did not apply to this survey unit since the survey unit is a Class 2 and discrete, elevated areas of contamination were not expected.The Sign Test was selected as the non-parametric statistical test. The use of the Sign Test did not require the selection or use of a background reference area, Revision 0 8 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD which simplified survey design and implementation.
This approach was conservative since it included background Cs-137 as part of the sample set.The number of sediment samples for FSS was determined in accordance with Procedure RPM 5.1-12, "Determination of the Number of Samples for Final Status Survey. " The Lower Bound of the Gray Region (LBGR) was set in accordance with Procedure RPM 5.1-11 to 0.5 to maintain the relative shift (A/a) in the range of 1 and 3. The resulting relative shift was 3.0. A Prospective Power Curve was generated using COMPASS, a software package developed under the sponsorship of the United States Nuclear Regulatory Commission (USNRC) for implementation of the MARSSIM in support of the decommissioning license termination rule (10 CFR 20, Subpart E). The result of the COMPASS computer run showed adequate power for the survey design.This indicates that the survey unit has a high probability of rejecting the null hypothesis, assuming that the characterization data are representative of the FSS results. Survey design specified fourteen (14) sediment core samples for non-parametric statistical testing.The grid pattern and locations of the sediment samples were determined using Visual Sample Plan (VSP) in accordance with Procedure RPM 5.1-14,"Identifying, and Marking Surface Sample Locations for Final Status Survey. " Visual Sample Plan was created by Pacific Northwest National Laboratory (PNNL) for the United States Department of Energy. A systematic triangular grid pattern with a random starting point was selected for sample design, which is appropriate for a Class 2 area.Sample locations were identified using AutoCAD-LT, a commercially available plotting software package with coordinates consistent with the Connecticut State Plane System. These coordinates were integrated with a GPS to locate sample locations in the field. Sample Measurement Locations for the design are listed with the GPS coordinates in Table 3.Revision 0 9 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Table 3 -Sample MI-asir~enient Locations with Associated GPS Coordinates Designationl Northing ~ Eakstin 9106-0008-001F 234825.31 672724.61 9106-0008-002F 234825.31 672817.80 9106-0008-003F 234744.60 672771.20 9106-0008-004F 234744.60 672864.40 9106-0008-005F 234663.89 672817.80 9106-0008-006F 234663.89 672911.00 9106-0008-007F 234583.17 672864.40 9106-0008-008F 234583.17 672957.60 9106-0008-009F 234502.46 672911.00 9106-0008-01OF 234502.46 673004.20 9106-0008-01 IF 234421.75 672957.60 9106-0008-012F 234421.75 673050.79 9106-0008-013F 234341.04 673004.20 9106-0008-014F 234341.04 673097.39 Four (4) sediment samples were analyzed for the full suite of radionuclides specified in Table 1, exceeding the requirement to analyze 5% of the sample population for HTD analysis specified in procedure RPM 5.1-11. Two (2) of the four (4) samples were randomly selected using the Microsoft Excel"RAND" function.
The two (2) samples exhibiting the highest observed radionuclide concentrations by gamma analyses were also selected.The implementation of survey specific quality control measures as referenced by Procedure RPM 5.1-24, "Split Sample Assessment for Final Status Survey, " included the collection of two (2) sediment samples for "split sample" analysis by the off-site laboratory.
These locations were selected randomly using the Microsoft Excel "RAND" function.
The number of quality control samples exceeded the 5% requirement.
The LTP specifies that scanning is not required for the FSS of the Discharge Canal. Table 4 provides a synopsis of the survey design.Revision 0 10 Revision 0 10 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD survey unit Lana Area 9,763 m2 Based on AutoCAD-LT and Visual Sample Plan calculations Type 1 and Type 2 errors were 0.05, Number of 14 sigma was 0.166 the LBGR was set to Measurements 0.5 to maintain Relative Shift in the range of 1 and 3, Relative Shift was 3.0 Grid Spacing 28.4 m Based on triangular grid 3.16 pCi/g Cs-137 Design DCGL 1.52 pCi/g Co-60 To achieve ten (10) mrem/yr TEDE 0.62 pCi/g Sr-90 289 pCi/g Ni-63 6.01 pCi/g Cs-137 To achieve nineteen (19) mrem/yr Operational 2.90 pCi/g Co-60 TEDE (2) to demonstrate compliance DCGL 1.18 pCi/g Sr-90 with Equation 2 of this Release Record 549 pCi/g Ni-63 Scan Coverage N/A The LTP exempts this area Sediment 6.01 pCi/gCs-137 Investigation 2.90 pCi/g Co-60 The Operational DCGL meets the LTP Level 1.18 pCi/g Sr-90 criteria for a Class 2 survey unit 549 pCi/g Ni-63 (1) The survey design used a much smaller value for investigation than the Operational DCGL provided by Table 2 as the total dose from existing and future groundwater had not been established at the time of planning the FSS 5. SURVEY IMPLEMENTATION Final status survey field activities were conducted under Work Plan and Inspection Record (WP&IR) 2006-0021.
The WP&IR package included a detailed FSSP, job safety analysis, job planning checklist and related procedures for reference.
Daily briefings were conducted to discuss the expectations for job performance and the safety aspects of the survey. The "Daily Survey Journal" was used to document field activities and other information pertaining to the FSS.Measurement locations were identified in North American Datum (NAD) 1927 coordinates that were supplied to the sampling vendor, Ocean Survey, Inc.(OSI) of Old Saybrook, Connecticut.
Discharge Canal sampling was accomplished using direct push technology to collect composite samples of bottom and mean high water mark sediments.
Sediment cores from the Discharge Canal were obtained by OSI using a vibrating corer that is platform mounted on a sampling vessel. The core barrel was a three (3) inch diameter thin-walled aluminum tube which also served as a core liner (ten (10) feet or less). A core catcher was available to prevent the sample from sliding out of the bottom of the tube. Vessel positioning and the determination of sample Revision 0 I1I Revision 0 11 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD locations were accomplished using a GPS interfaced with a navigation and data logging system.After extraction, water was drained from above the sample by drilling holes above the sediment.
The liner was cut, capped, sealed, labeled and turned over to site personnel who processed and controlled the samples under Chain of Custody (COC) protocols in accordance with procedure RPM 5.1-5, "Chain of Custody for Final Status Survey Samples. " Rinsing of the barrel and associated equipment was performed between sampling events. New aluminum tubes were used for each sample to prevent cross-contamination of subsequent samples.The Fourteen (14) sediment samples were collected and packaged in accordance with Haddam Neck Plant (HNP) Procedure RPM 5.1-3,"Collection of Sample Media for Final Status Survey". Samples were controlled, transported, stored, and transferred to the off-site laboratory using COC protocols.
Four (4) samples (9106-0008-006F, 9106-0008-007F, 9106-0008-008F and 9106-0008-012F) were selected for HTD radionuclide analysis by the off-site laboratory.
The implementation of survey specific quality control measures included the collection of two (2) split samples at locations 9106-0008-006F and 9106-0008-01 OF for "split sample" analysis by the off-site laboratory.
- 6. SURVEY RESULTS The off-site laboratory employed for the radiological analyses of samples was General Engineering Laboratories (GEL) -Charleston, South Carolina.
The laboratory analyzed the fourteen (14) samples taken for non-parametric statistical testing and the associated duplicates using gamma spectroscopy.
Sr-90 was analyzed by gas flow proportional counting.
All analyses were performed to the required MDC.Cesium-137 was identified in nine (9), Co-60 was identified in seven (7), Sr-90 was identified in two (2) and Ni-63 in none of the fourteen (14) samples. The results reported for the remaining sample analyses indicated that activity was present at levels approaching or below the established detection limits in the remaining samples collected and analyzed for non-parametric testing.Several other radionuclides which were positively identified (i.e., a result greater than two (2) standard deviations uncertainty) could be de-selected or excluded using the 5% and 10% rule described in Section 5.4.7.2 of the LTP.The off-site laboratory also processed four (4) samples for full HTD analysis as required by the sample plan. The requested analyses included alpha spectroscopy and liquid scintillation depending upon the radionuclide and the Revision 0 12 Revision 0 12 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD measurement method. All analyses were performed to the required MDC. Five (5) of the HTD radionuclides met the acceptance criteria for detection (i.e., a result greater than two standard deviations uncertainty) in more than one (1)sample; however, each of the positive results for HTD radionuclides could be de-selected based on the 5% and 10% rules.None of the sample results exceeded the Operational DCGL or required further investigation.
A summary of the sample results is provided in Table 5.9106-0008-001 F 3.96E-01 1.33E-01 5.79E-03 2.33E-01 1.17E-01 9106-0008-002F
-8.91 E-03 7.77E-03 2.03E-02 -4.84E+00 1.84E-02 9106-0008-003F 2.05E-01 3.24E-0 1 1. 12E-02 -2.74E+00 1.55E-01 9106-0008-004F 4.32E-02 0.00E+00 -6.19E-03
-1.80E+00 1.94E-03 9106-0008-005F 2.66E-01 2.75E-02 8.28E-04 -8.58E-01 5.44E-02 9106-0008-006F 4.92E-01 7.79E-01 5.59E-03 2.28E+00 3.55E-01 9106-0008-007F 2.29E-02 2.68E-02 -8.81E-04
-2.33E+00 1.23E-02 9106-0008-008F 4.72E-01 9.17E-01 -2.69E-03
-4.12E-01 3.92E-01 9106-0008-009F 1.55E-02 -1.08E-02
-5.90E-03
-2.05E+00
-6.15E-03 9106-0008-01OF 3.36E-01 2.46E-0I 3.47E-03 1.23E-01 1.44E-01 9106-0008-01IF 6.76E-02 1.22E-01 1.93E-02 -3.34E+00 6.97E-02 9106-0008-012F 1.84E-01 1.79E-01 -1.92E-02 8.39E-01 7.61 E-02 9106-0008-013F 1.03E-02 2.99E-02 9.80E-03 -2.70E+00 2.03E-02 9106-0008-014F
-3.89E-03
-1.45E-02 5.40E-03 -1.72E+00
-1.07E-03 (1) The Operational DCGLs from Table 2 are 6.01 pCi/g for Cs-137, 2.90 pCi/g for Co-60, 1.18 for Sr-90 and 549 for Ni-63; these are used in conjunction with the unity rule to achieve nineteen (19) mrem/yr TEDE.Biased sampling was not called for in the sample plan.7. QUALITY CONTROL The two (2) split samples taken for QC were analyzed by the off-site laboratory.
The data were evaluated using USNRC acceptance criteria specified in Inspection Procedure 84750 and as detailed in HNP Procedure RPM 5.1-24,"Split Sample Assessment for Final Status Survey. " Split-sample number 9106-0008-006F/S did not meet the comparison criterion for Co-60. A possible cause for this anomaly could be the presence of Co-60 in the form of discrete particles.
Such a physical form does not lend itself to homogenous mixing in a sediment matrix and, therefore, is not necessarily an indicator of inadequate sampling or sample preparation methodology.
In this sample, K-40, a natural radioisotope, was found to be present at an acceptable level of agreement, therefore, the comparison was determined to be acceptable.
Additionally, Cs-137 did meet the comparison criteria for the sample results.Revision 0 13 Revision 0 13 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD However, Ni-63 and Sr-90 had resolutions of zero (0) and one (1) respectively and values <4 have not been addressed in NRC Inspection Procedure 84750.Therefore, a determination of the acceptability for resolution values of <4 can not be made.For the second QC split sample number 9106-0008-O1OF/S there was an acceptable level of agreement between the samples for CO-60 and Cs-137. In this sample, K-40, a natural radioisotope, was found to be present at an acceptable level of agreement, therefore, the comparison was determined to be acceptable.
However, Ni-63 and Sr-90 had resolutions of zero (0) and one (1)respectively and resolution values of <4 have not been addressed in NRC Inspection Procedure 84750. Therefore, a determination of the acceptability for values <4 can not be made.The sample analysis vendor, GEL, maintained quality control and quality assurance plans as part of normal operation.
Refer to Attachment 2 for data and data quality analysis results.8. INVESTIGATIONS AND RESULTS No Investigations were required to be performed since none of the sample results exceeded the investigation levels.9. REMEDIATION AND RESULTS Historically, no radiological remedial action as described by MARSSIM Section 5.4 was performed in this survey unit prior to or as a result of the FSS. Health Physics TSD BCY-HP-0078, "ALARA Evaluation of Soil Remediation in Support of Final Status Survey, " determined that remediation beyond that required to meet the release criteria to be unnecessary and that the remaining residual radioactivity in sediment was ALARA.10. CHANGES FROM THE FINAL STATUS SURVEY PLAN The survey was designed to ten (10) mrem/yr TEDE which was conservative and necessary at the time of FSS planning.
It is no longer required as the total dose from existing and future groundwater has been established.
The dose for sediment used to demonstrate compliance with the LTP criteria is nineteen (19)mremlyr TEDE as discussed in Section 2 of this Release Record.11. DATA QUALITY ASSESSMENT (DQA)The DQO sample design and data were reviewed in accordance with Procedure RPM 5.1-23, "Data Quality Assessment. " The sample design had adequate power as indicated by the Retrospective Power Curve. The Sign Test was performed on the data and compared to the original assumptions of the DQOs.The evaluation of the Sign Test results indicates that the survey unit passes the unrestricted release criterion, thus, the null hypothesis is rejected.Revision 0 14 Revision 0 14 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Documentation was complete and legible. Surveys and sample collection were consistent with the DQOs and were sufficient to ensure that the survey unit was properly designated as Class 2.The preliminary data review consisted of calculating basic statistical quantities (e.g., mean, median, standard deviation).
The standard deviation was slightly more than the value used for the survey design. This is represented by the shift in the retrospective power curve as shown in Attachment 2f. This would indicate a need to change the original LBGR in order to maintain the number of samples at fourteen (14) to meet the Operational DCGL. However, the value of the LBGR is not a critical issue as the survey unit has passed the statistical test, and the mean and median values are well below the Operational DCGL when used in conjunction with the unity rule. Also, the retrospective power curve shows that a sufficient number of samples were collected to achieve the desired power. Therefore, the survey unit meets the unrestricted release criterion with adequate power as required by the DQOs.The range of the data, about 3.1 standard deviations, was not unusually large.The difference between the mean and median was 30% of the standard deviation which indicates some skewness in the data. The data was represented graphically through posting plots, a frequency plot, and a quantile plot. The frequency plot shows some positive skewness as confirmed by the calculated skew of 1.58.All data, assessments, and graphical representations are provided in Attachment 2.12. ANOMALIES The anomaly associated with the disagreement between the field splits has been discussed in Section 7. The source of the disagreement for Co-60 was likely due to Co-60 being present in the form of discrete particles.
Such a physical form does not lend itself to homogenous mixing in a sediment matrix.13. CONCLUSION Survey Unit 9106-0008 has demonstrated compliance with the dose based, unrestricted release criterion.
The sample data passed the Sign Test and the null hypothesis was rejected.
The ALARA criteria for soils as specified in Chapter 4 of the LTP were achieved.
Reclassification and remediation of this survey unit was not required.Graphical representation of data indicates some positive skewness that is probably due to localized differences in particulate deposition rates, hydraulic velocity and sedimentation rates. The Retrospective Power Curve generated using COMPASS shows adequate power was achieved.
The survey unit was properly designated as a Class 2 survey unit.Revision 0 15 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD The dose contribution from sediment is 1.9 mrem/yr TEDE based on the average concentration of the samples used for non-parametric statistical sampling.This survey unit is not affected by existing groundwater (reference CY memo ISC 06-024). It has been determined that the dose contribution from groundwater sources is bounded by zero (0) mrem/yr TEDE.This survey unit is also not considered impacted by future groundwater radioactive contamination, as there are no concrete foundations or footings containing residual radioactive material within the groundwater saturated zone in the area (reference CY memo ISC 06-024). The dose contribution from future groundwater, the third dose component is, therefore, zero (0) mrem/yr TEDE.The average total dose from residual radioactivity in this survey unit, including that from sediment, will not exceed 1.9 mrem/yr Total Effective Dose Equivalent (TEDE).14. ATTACHMENTS 14.1 Attachment 1 -Figures 14.2 Attachment 2 -Sample and Statistical Data Revision 0 16 Revision 0 16 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Attachment 1 Figures (6 pages)
'I..0 420 840 M,=== I Feet NOW d poww~u"m sNA2Cmwe-Connect'cut Yankee Atomic Power Company Site Map With Reference To Survey Unit 9106-0008 I 1 4 0 K 0 3 5 B 0 10 9 B 0 12 Nce lbodbw am i 11 0 13 0 0 30 60 c FWee Connecticut Yankee Atomic Power Company 9106-0008 Final SWus Survey Design 00.003 0.6 30 .40 Fe9 Connet2cu Yake0tmc.oe3Cmay36e By R Figure0015 3 91600 FnlSatsSreyDs Cesum-37Pstig Pot ~tbCI200 E.S0.184t 0.324 o~~~.0275 0"'06 .91 7 , 0K Locaton-.000.179 NOWt 012-0.0145 Cook.nobzam 0.290 30 60 0 ~Feet Connecticut Yankee Atomic Power Compay Date By Rev.Figure 4 9106-0008 Final Status Survey Design Cobalt-60 Posting Plot October 2006 E. Swgcnt 0 0.0058 0 4-0 0.01 12 0.0008 0 9 0.0035 Sample Locatio-0.0059 0-0.0192 No-CnMIEWam.
h NAD27~0.0193 0 0.0098 0 0 30 60! Feel Connecticut Yankee Atomic Power Company 9106-0008 Final Status Survey Design Strondum-90 Posting Plot 0.233 0 7-2.74-0.858 0 0 0.123 sawle Lomdom-2.05 10 9 0.839 Note comia mum-3.34 9-2.70 9 0 30 60 I Fee't Connecticut Yankee Atomic Power Company 9106-0008 Fiual Satus Survey Design Nickel-63 Posting Plot DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Attachment 2 Sample and Statistical Data DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Attachment 2a Sample Data (178 Pages)
General Narrative CASE NARRATIVE For CONNECTICUT YANKEE RE: Sediment PO# 002332 Work Order: 163741 SDG: MSR #06-0743 June 19, 2006 Laboratory Identification:
General Engineering Laboratories, LLC Mailing Address: P.O. Box 30712 Charleston, South Carolina 29417 Express Mail Delivery and Shipping Address: 2040 Savage Road Charleston, South Carolina 29407 Telephone Number: (843) 556-8171 Summary: Sample receipt The sample(s) for this Project arrived at General Engineering Laboratories, LLC, (GEL)in Charleston, South Carolina on May 26, 2006. All sample containers arrived without any visible signs of tampering or breakage.
The chain of custody contained the proper documentation and signatures.
The laboratory received the following sample(s):
Sample ID Client Sample ID 163741001 9106-0008-OOIF 163741002 9106-0008-003F 163741003 9106-0008-004F 163741004 9106-0008-005F 163741005 9106-0008-006F 163741006 9106-0008-006FS 163741007 9106-0008-002F 163741008 9106-0008-007F GENERAL ENGINEERING LABORATORIES, LLC a Member of THE GEL GROUP INC.Page 2 of 75 P.O. Box 30712
- Charleston, SC 29417
- 2040 Savage Road (29407)Phone (843) 556-8171 ° Fax (843) 766-1178
- www.gel.com Sample ID Client Sample ID 163741009 9106-0008-008F 163741010 9106-0008-009F 163741011 9106-0008-OIOF 163741012 9106-0008-OIOFS 163741013 9106-0008-011F 163741014 9106-0008-013F 163741015 9106-0008-014F 163741016 9106-0008-012F Items of Note: There are no items of note.Case Narrative:
Sample analyses were conducted using methodology as outlined in General Engineering Laboratories (GEL) Standard Operating Procedures.
Any technical or administrative problems during analysis, data review, and reduction are listed below by analytical parameter.
Analytical Request: Fourteen sediment samples were analyzed for FSSGAM, Sr-90 and Ni-63.Two sediment samples were analyzed for FSSALL.Internal Chain of Custody: Custody was maintained for the sample(s).
Data Package: The enclosed data package contains the following sections:
Case Narrative, Chain of Custody and Supporting Documentation and all analytical fractions.
I certify that this data package is in compliance with the SOW, both technically and for completeness, for other than the conditions detailed above. Release of the data contained in this hard copy data package has been authorized by the Laboratory Manager or a designee, as verified by the following signature.
Cheryl Jones Project Manager GENERAL ENGINEERING LABORATORIES, LLC a Member of THE GEL GROUP, INC.P.O. Box 30712 ° Charleston, SC 29417 -2040 Savage Road (29407)Page 3 of 75 Phone (843) 556-8171
- Fax (843) 766-1178
- www.gel.com Chain of Custody and Supporting Documentation Page 4 of 75 Health Physics Procedure GPP-GGGR-R5104-003 -Attachment B-CY-001 Major Healh Pysis Prcedre PP-GGR-5 104-03-Atacmen B-CY-0 1 ajo SChain of Custody FormN.206037 Connecticut Yankee Atomic Power CompanyCu, No. 2006-00367 362 Injun Hollow Road, East Hampton, CT 06424 / 3'q,/. _____860-267-255616374t
_roject Name: Haddam Neck Decommissioning Analyses Requested Lab Use Only Contact Name & Phone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 ? 0 e 843 556 8171. Attn. Cheryl Jones C .Priority:
0 30 D. Ej 14 D. [] 7 D. Container Sample Size-Media Type &Type Sample Designation Date Time Code Code Code Comment, Preservation Lab Sample ID 9106-0008-OOIF 5/05/06 11:13 SE C BP X X X Transferred from COC # 2006-00324 9106-0008-003F 5/5/06 13:35 SE C BP x x x Transferred from COC # 2006-00325 9106-0008-004F 5/5/06 13:51 SE C BP X X X Transferred from COC # 2006-00325 9106-0008-005F 5/5/06 14:17 SE C BP X X X Transferred from COC # 2006-00325 9106-0008-006F 5/5/06 14:36 SE C BP X X x Transferred from COC # 2006-00325 9106-0008-006FS 5/5106 14:36 SE C BP x x x Transferred from COC # 2006-00325 9106-0008-007F 5/5/06 15:03 SE C BP x Transferred from COC # 2006-00325 9106-0008-002F 5/5/06 13:10 SE C BP x X X Transferred from COC # 2006-00325 NOTES: PO #: 002332 MSR#: 06-7O,3 SSWP#NA Z LTP QA E] Radwaste QA E] Non QA 1) elinqdshe Date/Time
- 2) e ived ate/Time 3) ieinquished By \\J Date/Time
- 4) Re eive y hate/Time Samples Shipped Via:[ Fed Ex El up~s El Hand El Other Bill of Lading #Internal Container Temp.: -Deg. C Custody Sealed?YEO NO Custody Seal Intact?YOI NO Health Physics Procedure GPP-GGGR-R5104-003-Attachment B-CY-001 Major~Chain of Custody Form Connecticut Yankee Atomic Power Company No. 2006-00366 362 Injun Hollow Road, East Hampton, CT 06424 o 860-267-2556 S0-oject Name: Haddam Neck Decommissioning Analyses Requested Lab Use Only Contact Name & lPhone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 0, 843 556 8171. Attn. Cheryl Jones r Uý Z Priority:
Z 30 D. E] 14 D. E] 7 D. Container Sample Size-Media Type &Type Sample Designation Date Time Code Code Code Comment, Preservation Lab Sample ID ,.? 9106-0008-008F 5/08/06 08:01 SE C BP X x x Transferred from COC # 2006-00327
)10 9106-0008-009F 5/08/06 08:32 SE C BP X X X Transferred from COC # 2006-00327 Oil 9106-0008-01 OF 5/08/06 09:09 SE C BP X X X Transferred from COC # 2006-00327
)11 9106-0008-O1OFS 5/08/06 09:09 SE C BP X X X Transferred from COC # 2006-00327)It 9106-0008-01IF 5/08/06 09:30 SE C BP X X X Transferred from COC # 2006-00327
,1k 9106-0008-012F 5/08/06 09:53 SE C BP X Transferred from COC # 2006-00327 9106-0008-013F 5/08/06 10:16 SE C BP X x x Transferred from COC # 2006-00327 9106-0008-014F 5/08/06 10:47 SE C BP X X x Transferred from COC # 2006-00327 NOTES: PO #: 002332 MSR #: 06- 6 7 q.3 SSWP# NA Z LTP QA LI Radwaste QA El Non QA Samples Shipped Via:[ Fed Ex[] UPS El Hand 0l Other Bill of Lading #Internal Container Temp.: '41 Deg. C Custody Sealed?Y 0 N31 Custody Seal Intact?Y5' No 1) Relinquished By Date/Time
- 2) Received By Date/Time C) 10444se By Dt/ e/2 4), Reeie a " /3) Relinquished By Date/Time
- 4) Received By Date/Time Connecticut Yankee 1 37'4I 1 Statement of Work for Analytical Lab Services -CY-ISC-SOW-001 Figure 1. Sample Check-in List Date/lime Received:
A5~u1Oto DA? L SDG#: Ae5 % c43 Work Order Number: \ ( \" 4 Shipping Container ID: V) 0 '1' JOIiP& Chain of Custody # 0 O C)o. 0OO3 wq>" 1. *Custody Seals. od shipping container intact? *Yes [V"o (I 2. Custody Seals dated and signed? Yes[ j No [.-3. Chain-of-Custo.'Jy record present? Yes I ]4. Cooler temperature
/ -" 5. Vermiculite/packing materials is: Wet [ I Dry [, ] P 6.' Number of samples in shipping container:
t 7. Sample holding times exceeded?
Yes [] No 8. Samples have--hazard labels--,custody seals /'appropriate sample labels 9. Samples are-."_2z1in good condition
.leaking_broken -have air bubbles 10. Were any anomalies identified in sample receipt? Yes [ ] No [, '11..Description of anomalies (include sample numbers): Telephoned to:__ __ _ _ __ __ _____"__"_"__
_On By -.Page7 of 75 0 SAMPLE RECEIPT & REVIEW FORM V on onl 1 CClimt: IOASDGIARCOC/WO*I Order-Received:
ca 0 , jM(ARev/ew (ensure non-conforming items we resolved prior to siping): Received By: ____)_Sample Receipt Criteria CommentslQualiflers (Required for Non-Conforming Items)1 Shipping containers received intact / icle Awplicable:
seals broken damaged comainer leaking container oter (descrb)and sealed?Samples requiring cold Circle Coolant I ke bags blue ace dry ice jox odher describe)2 preservation within (4 +1- 2 C)? /Record preservation method. _.__C Chain of custody documents 3included with shipment?Sample containers intact and Circle Applicable:
seals broken damaged container leaking container ether (descrit)sealed? _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _5 Samples requiring chemical / Samp ID's. conainers affected and observed pit preservation at proper pH?VOA vials free of headspace
/ In's ciners affected: (defined as < 6mm bubble)?Are Encore containers present?7 (If yes. immediately deliver to VOA laboratory) 8 Samples received within holding / Id's and tests affected: time?Sample ID's on COC match ID's Sample ID's and comaines affected: on bottles? /Date & time on COC match date /sampl ID's afetd& time on bottles? /_Number of containers received / ampl ID'i match number indicated on COG?COC form is properly signed in 2 relinquished/received sections?_
14 Air Bill ,Tracking
- 's, &Additional Comnents S 6l t k1 o?* --', RSORADReceiptI
- -Suspected .Haurd In o m to *If > x2 area background is obsered on samples identified as 'non , Suspected Hazard Information Z) uI regulated/non-radioactiveP, contact the Radiation Safetygroup for further'_x 1 ,1 investigation.
I A7lRadiologicaI Classification?
I ,/ ,..:... r .... .. .--,1 ... I P~~CB Regulated?
-5hippd as DOT L'Hazardous C Material?
If yes, contact Waste Manager or E-SH Manager..-
t~-~~lazard Class Shipped: IN#: Initials (9 cr/6 Date: rM (or YMA) view of Hazard classification:
ragv 0 U1 /.j/
Connecticut Yankee Statement of Work for Analytical Lab Services -CY-ISC-SOW-00I Figure 1. Sample Check-in List Date/Time Received:
S/!2.Ult 602)SDG# A _Work Order Number:-Shipping Container ID: "19tI Z 1112 Chain of Custody# ' .1. Custody Seals o6 shipping container intact?- Yes k[' o [ ]2. Custody Seals dated and signed? Yes L,9o []3. Chaia-of-Custody record present? " es LI,,o [ I 4. Cooler temperature
- 5. Vermiculite/packing materials is: Wet ['l 6. Number of samples in shipping container:
h I'h 7. Sample holding times exceeded?
Yes-[ ] No 8. Samples have: tape ___hazard labels_custody seals _ appropriate sample labels 9. Samples are'.."in good condition leaking-broken -* have air bubbles 10. Were any anomalies identified in sample receipt? Yes [] No 11. Description of anomalies. (include sample numbers):
.*O Sample Custodian/Laboratory: (oel,24-iC,,7 Date:_ _ _2-______, _Telephoned to: On By Page 9 of 75 ESAMPLE RECEIPT & REVIEW FORM 0"pI ' RSAMPLEMus ol Client- Y an kp&SDGIARCOCtWork Order: ho3741 '/Date Received:
jPM(A) Review (ensure non-conforming items are resolved prior to signing): Sample Receipt Criteria > Z CommentslQualifrers (Required for Non-Conforming Items)Shipping containers received intact Circle Applicable:
seals broken damaged container leaking container other (describe) and sealed? _/_ _I_ _ _ L%Samples requiring cold Circle Coolant ice bags blue ice dry ice other describe)2 preservation within (4 +/- 2 C)?Record preservation method.3 Chain of custody documents included with shipment?4 Sample containers intact and Circle Applicable:
seals broken damaged container leaking container other (describe) sealed? ________________________________
5 Samples requiring chemical Sample ID's. containers affected and observed pH: preservation at proper pH?6 VOA vials free of headspace Sample ID's and containers affected: (defined as < 6mm bubble)?Are Encore containers present?7 (If yes, immediately deliver to VOA laboratory) 8 Samples received within holding Id's aJ tests affecied: 8 lime? _9 Sample ID's on COC match ID's Sample ID's and containers affected: on bottles? " Date & time on COC match date Sample ID's affected: 0 & time on bottles?l Number of containers received Sample ID's affected: match number indicated on COC?COC form is properly signed in n o4- Kj .,'tiq.1/
I's.d 2 relinquished/received sections?4 Air Bill ,Tracking
- 's,& & L'" 4 /13"5 Additional Comments" V RSO RADReceiptl#
r- *If > x2 area background is observed on samples identified as "non-Suspected Hazard Information V C ,regulated/non-radioactive".
contact the Radiation Safety group for further=- x , investigation.
A Radiological Classification?
Maximum Counts Observed*:
.PCB3 Regulated?
Comments: Shipped as DMT Hazardous C Material?
If yes, contact Waste Hazard Class Shipped: Manager or ESH Manager. IUN#: PM (or PMA) review of Hazard classification:
Initials ) Date: Page 10 01 75 I RADIOLOGICAL ANALYSIS Page 11 of 75 Radiochemistry Case Narrative Connecticut Yankee Atomic Power Co. (YANK)Work Order 163741 Method/Analysis Information Product: Alphaspec Am241, Cm, Solid ALL FSS Analytical Method: DOE EML HASL-300, Am-05-RC Modified Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 537411 534049 534048 Sample ID 163741008 163741016 1201110207 1201110208 1201110209 1201110210 Client ID 9106-0008-007F 9106-0008-012F Method Blank (MB)163741008(9106-0008-007F)
Sample Duplicate (DUP)163741008(9106-0008-007F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-01 1 REV# 14.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Page 12 of 75 Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163741008 (9106-0008-007F).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Manual Integration No manual integrations were performed on data in this batch.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Page 13 of 75 Product: Alphaspec Pu, Solid-ALL FSS Analytical Method: Prep Method: DOE EML HASL-300, Pu- 11-RC Modified Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 537412 534049 534048 Sample ID 163741008 163741016 1201110215 1201110216 1201110217 1201110218 Client ID 9106-0008-007F 9106-0008-012F Method Blank (MB)163741008(9106-0008-007F)
Sample Duplicate (DUP)163741008(9106-0008-007F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-01 1 REV# 14.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163741008 (9106-0008-007F).
QC Information All of the QC samples met the required acceptance limits.Page 14 of 75 Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Manual Integration No manual integrations were performed on data in this batch.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Liquid Scint Pu241, Solid-ALL FSS DOE EML HASL-300, Pu- I1-RC Modified Analytical Method: Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 537417 534049 534048 Page 15 of 75 Sample ID Client ID 163741008 9106-0008-007F 163741016 9106-0008-012F 1201110229 Method Blank (MB)1201110230 163741008(9106-0008-007F)
Sample Duplicate (DUP)1201110231 163741008(9106-0008-007F)
Matrix Spike (MS)1201110232 Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-035 REV# 8.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QCQ Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163741008 (9106-0008-007F).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from Page 16 of 75 referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Manual Integration No manual integrations were performed on data in this batch.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Gamma,Solid-FSS GAM & ALL FSS Analytical Method: Prep Method: Analytical Batch Number: Prep Batch Number: Sample ID 163741001 163741002 163741003 163741004 163741005 163741006 163741007 163741008 163741009 163741010 163741011 163741012 163741013 163741014 163741015 163741016 1201102649 1201102650 1201102651 EML HASL 300,4.5.2.3 Dry Soil Prep 534130 534048 Client ID 9106-0008-0OlF 9106-0008-003F 9106-0008-004F 9106-0008-005F 9106-0008-006F 9106-0008-006FS 9106-0008-002F 9106-0008-007F 9106-0008-008F 9106-0008-009F 9106-0008-01OF 9106-0008-01OFS 9106-0008-01 IF 9106-0008-013F 9106-0008-014F 9106-0008-012F Method Blank (MB)163741001(9106-0008-001 F) Sample Duplicate (DUP)Laboratory Control Sample (LCS)Page 17 of 75 SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-013 REV# 11.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QCQ Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163741001 (9106-0008-001F).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments The relative percent difference for Pb-214, in samples 1201102650 (9106-0008-001F) and 163741001 (9106-0008-001F), does not meet the standard requirements.
However, when a relative error ratio is calculated, precision is shown at 2.38.Page 18 of 75 Qualifier information Qualifier UI U'UI Reason Data rejected due to high Full-Width Half-Maximum.
Data rejected due to interference.
Data rejected due to low abundance.
Analyte Potassium-40 Europium-155 Manganese-54 Cesium- 134 Sample 1201102649 163741016 163741004 163741005 163741007 163741013 163741014 163741016 1201102650 163741003 Cobalt-60 Method/Analysis Information Product: Analytical Method: Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: GFPC, Sr90, solid-ALL FSS EPA 905.0 Modified Ash Soil Prep Dry Soil Prep 536483 534049 534048 Page 19 of 75 Sample ID 163741001 163741002 163741003 163741004 163741005 163741006 163741007 163741008 163741009 163741010 163741011 163741012 163741013 163741014 163741015 163741016 1201108056 1201108057 1201108058 1201108059 Client ID 9106-0008-OOIF 9106-0008-003F 9106-0008-004F 9106-0008-005F 9106-0008-006F 9106-0008-006FS 9106-0008-002F 9106-0008-007F 9106-0008-008F 9106-0008-009F 9106-0008-01OF 9106-0008-01OFS 9106-0008-01 IF 9106-0008-013F 9106-0008-014F 9106-0008-012F Method Blank (MB)163741001(9106-0008-001F)
Sample Duplicate (DUP)163741001(9106-0008-001 F) Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-004 REV# 10.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Ouality Control (OC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163741001 (9106-0008-001F).
QC Information All of the QC samples met the required acceptance limits.Page 20 of 75 Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis Samples 163741001 (9106-0008-001F), 163741005 (9106-0008-006F) and 163741011 (9106-0008-01OF) were recounted due to high MDAs.Chemical Recoveries All chemical recoveries meet the required acceptance limits for this sample set.Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from.referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Liquid Scint Tc99, Solid-ALL FSS Analytical Method: Analytical Batch Number: Sample ID 163741008 163741016 1201107610 1201107611 1201107612 1201107613 DOE EML HASL-300, Tc-02-RC Modified 536314 Client ID 9106-0008-007F 9106-0008-012F Method Blank (MB)163741008(9106-0008-007F)
Sample Duplicate (DUP)163741008(9106-0008-007F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Page 21 of 75 Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-005 REV# 13.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163741008 (9106-0008-007F).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Page 22 of 75 Product: Liquid Scint Fe55, Solid-ALL FSS DOE RESL Fe-1, Modified Analytical Method: Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 538969 534049 534048 Sample ID 163741008 163741016 1201113887 1201113888 1201113889 1201113890 Client ID 9106-0008-007F 9106-0008-012F Method Blank (MB)163741008(9106-0008-007F)
Sample Duplicate (DUP)163741008(9106-0008-007F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-040 REV# 3.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163741008 (9106-0008-007F).
QC Information Page 23 of 75 All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Liquid Scint Ni63, Solid-ALL FSS Analytical Method: DOE RESL Ni-1, Modified Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 538365 534049 534048 Page 24 of 75 Sample ID 163741001 163741002 163741003 163741004 163741005 163741006 163741007 163741008 163741009 163741010 163741011 163741012 163741013 163741014 163741015 163741016 1201112555 1201112556 1201112557 1201112558 Client ID 9106-0008-001F 9106-0008-003F 9106-0008-004F 9106-0008-005F 9106-0008-006F 9106-0008-006FS 9106-0008-002F 9106-0008-007F 9106-0008-008F 9106-0008-009F 9106-0008-01OF 9106-0008-01OFS 9106-0008-01 IF 9106-0008-013F 9106-0008-014F 9106-0008-012F Method Blank (MB)163741003(9106-0008-004F)
Sample Duplicate (DUP)163741003(9106-0008-004F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-022 REV# 8.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163741003 (9106-0008-004F).
QC Information All of the QC samples met the required acceptance limits.Page 25 of 75 Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: LSC, Tritium Dist, Solid-HTD2,ALL FSS Analytical Method: Analytical Batch Number: Sample ID 163741008 163741016 1201106885 1201106886 1201106887 1201106888 EPA 906.0 Modified 535984 Client ID 9106-0008-007F 9106-0008-012F Method Blank (MB)163626016(9106-0007-001 F) Sample Duplicate (DUP)163626016(9106-0007-00 IF) Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-002 REV# 12.Page 26 of 75 Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 163626016 (9106-0007-001F).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Page 27 of 75 Product: Liquid Scint C14, Solid AII,FSS Analytical Method: Analytical Batch Number: Sample ID 163741008 163741016 1201104384 1201104385 1201104386 1201104387 EPA EERF C-01 Modified 534837 Client ID 9106-0008-007F 9106-0008-012F Method Blank (MB)162335019(9106-0003-014F)
Sample Duplicate (DUP)162335019(9106-0003-014F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-003 REV# 8.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 162335019 (9106-0003-014F).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for.this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Page 28 of 75 Sample Re-prep/Re-analysis Samples 1201104385 (9106-0003-014F) and 163741016 (9106-0008-012F) were recounted due to high MDAs. Samples were reprepped due to low/high recovery.Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Certification Statement Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless otherwise noted in the analytical case narrative.
Review Validation:
GEL requires all analytical data to be verified by a qualified data validator.
In addition, all data designated for CLP or CLP-like packaging will receive a third level validation upon completion of the data package.The following data validator verified the information presented in this case narrative:
Reviewer/Date:
K4 -9 Page 29 of 75 SAMPLE DATA
SUMMARY
Page 30 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Report for YANKOOI Connecticut Yankee Atomic Power Co.Client SDG: MSR#06-0743 GEL Work Order: 163741 The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria** Analyte is a surrogate compound U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification ND The analyte concentration is not detected above the reporting limit.The above sample is reported on a dry weight basis except where prohibited by the analytical procedure.
Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless qualified on the Certificate of Analysis.This data report has been prepared and reviewed in accordance with General Engineering Laboratories, LLC standard operating procedures.
Please direct any questions to your Project Manager, Cheryl Jones.Reviewed by Page 31 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: 9106-0008-001F Proiect: YANK01204 Sample ID: 163741001 Client ID: YANKOO Matrix: SE Vol. Recv.: Collect Date: 05-MAY-06 Receive Date: 26-MAY-06 Collector:
Client Moisture:
38.9%Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma,Solid-FSS GAM& ALL FSS Actinium-228 Americium-241 U Bismuth-212 Bismuth-214 Cesium-134 U Cesium-137 Cobalt-60 Europium-152 U Europium-154 U Europium-155 U Lead-212 Lead-214 Manganese-54 U Niobium-94 U-0 Potassium-40 Radium-226 Silver-108m U Thallium-208 Rad Gas Flow Proportional Counting GFPC, SO9O, solid-ALL FSS Strontium-90 U Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 0.817 0.0431 0.570 0.568 0.0314 0.396 0.133 0.00717 0.040 0.0854 0.772 0.585 0.0123.000522 12.1 0.568 0.00495 0.300+/-0.177+/-0.0977+/-0.292+/-0.0877+/-0.0354+/-0.0588+/-0.0554+/-0.0581+/-0.0643+/-0.0769+/-0.0707+/-0.0841+/-0.0261+/-0.0212+/-0.950+/-0.0877+/-0.0195+/-0.0497 0.0585 0.0813 0.144 0.0366 0.0253 0.0193 0.0195 0.0513 0.0578 0.0548 0.0295 0.0353 0.0208 0.0176 0.178 0.0366 0.0171 0.0177+/-0.177+/-0.0977+/-0.292+/-0.0877+/-0.0354+/-0.0588+/-0.0554+/-0.0581+/-0.0643+/-0.0769+/-0.0707+/-0.0841+/-0.0261+/-0.0212+/-0.950+/-0.0877+/-0.0195+/-0.0497 0.128 0.168 0.309 0.0777 0.0538 0.0412 0.0431 0.108 0.127 0.113 0.0615 0.0742 0.0446 0.0375 0.396 0.0777 0.0361 0.0379 0.0264 12.9 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJHI 06/15/06 1544 534130 1 BXFI 06/22/06 1035 536483 2 SLNI 06/20/06 0726 538365 3 0.00579 +/-0.0116 0.0116 +/-0.0116 0.233 +/-7.56 6.34 +/-7.56 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Ash Soil Prep Ash Soil Prep, GL-RAD-A-021B LXM2 05/28/06 1209 534049 Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM1 05/26/06 1530 534048 The following Analytical Methods were performed Method Description Page 32 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-00IF Project: YANK01204 Sample ID: 163741001 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd I EML HASL 300, 4.5.2.3 2 EPA 905.0 Modified 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 72 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 72 (25%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 33 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificnte of Analvqiq Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-003F 163741002 SE 05-MAY-06 26-MAY-06 Client 57.6%Project: YANK01204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma,Solid-FSS GAM & ALL FSS Actinium-228 1.09 Americium-241 U 0.0256 Bismuth-212 0.673 Bismuth-214 0.775 Cesium-134 U 0.0459 Cesium-137 0.205 Cobalt-60 0.324 Europium-152 U 0.020 Europium-154 U 0.00145 Europium-155 U 0.0192 Lead-212 1.16 Lead-214 0.886 Manganese-54 U 0.0289 Niobium-94 U -0.0236 Potassium-40 16.2 Radium-226 0.775 Silver-108m U 0.00754 Thallium-208 0.337 Rad Gas Flow Proportional Counting+/-0.203+/-0.140+/-0.467+/-0.123+/-0.0366+/-0.0706+/-0.0774+/-0.073+/-0.104+/-0.074+/-0.083+/-0.110+/-0.0456+/-0.0269+/-1.14+/-0.123+/-0.0258+/-0.0676 0.0952 0.082 0.181 0.0437 0.0321 0.0227 0.0292 0.0599 0.0855 0.0571 0.033 0.0409 0.0244 0.0208 0.223 0.0437 0.0209 0.0222+/-0.203+/-0.140+/-0.467+/-0.123+/-0.0366+/-0.0706+/-0.0774+/-0.073+/-0.104+/-0.074+/-0.083+/-0.110+/-0.0456+/-0.0269+/-1.14+/-0.123+/-0.0258+/-0.0676 0.201 0.169 0.382 0.0917 0.0672 0.0479 0.0625 0.124 0.182 0.117 0.0682 0.0851 0.0516 0.0439 0.487 0.0917 0.0437 0.0468 0.0387 9.92 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/15/06 1544 534130 1 GFPC, Sr90, solid-ALL FSS Strontium-90 L Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 L.0.0112 +/-0.0174 0.0173 +/-0.0174-2.74 +/-5.74 4.87 +/-5.74 BXFI 06/18/06 1006 536483 2 SLN1 06/20/06 0813 538365 3 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Ash Soil Prep Ash Soil Prep, GL-RAD-A-021B LXM2 05/28/06 1209 534049 Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM1 05/26/06 1530 534048 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 Page 34 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-003F Project: YANK01204 Sample ID: 163741002 Client ID: YANKOOI Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 2 EPA 905.0 Modified 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 71 (25%- 125%)Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 83 (25%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 35 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd Contact: Project: East Hampton, Connecticut 06424 Mr. Jack McCarthy Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-004F 163741003 SE 05-MAY-06 26-MAY-06 Client 63.5%Proiect: Client ID: Vol. Recv.: YANKO 1204 YANKOO I Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma,Solid-FSS GAM & ALL FSS Actinium-228 1.02 Americium-241 U 0.0417 Bismuth-212 0.935 Bismuth-214 0.581 Cesium-134 U 0.0381 Cesium-137 0.0432 Cobalt-60 UI 0.00 Europium-152 U -0.00954 Europium-154 U -0.0501 Europium-155 U 0.0526 Lead-212 0.937 Lead-214 0.739 Manganese-54 U -0.0116 Niobium-94 U 0.00493 Potassium-40 13.6 Radium-226 0.581 Silver-108m U -0.0039 Thallium-208 0.234 Rad Gas Flow Proportional Counting GFPC, Sr90, solid-ALL FSS Strontium-90 U -0.00619 Rad Liquid Scintillation Analysis+/-0.200+/-0.0743+/-0.288+/-0.112+/-0.0469+/-0.036+/-0.0268+/-0.0498+/-0.0608+/-0.0739+/-0.0965+/-0.119+/-0.0212+/-0.018+/-1.14+/-0.112+/-0.0169+/-0.0565 0.0517 0.0608 0.128 0.0343 0.0215 0.016 0.0258 0.0406 0.0457 0.0508 0.0253 0.0286 0.017 0.0153 0.136 0.0343 0.0136 0.0157+/-0.200+/-0.0743+/-0.288+/-0.112+/-0.0469+/-0.036+/-0.0268+/-0.0498+/-0.0608+/-0.0739+/-0.0965+/-0.119+/-0.0212+/-0.018+/-1.14+/-0.112+/-0.0169+/-0.0565 0.109 0.125 0.269 0.0712 0.0448 0.0334 0.0538 0.0841 0.0975 0.104 0.052 0.0594 0.0357 0.0319 0.295 0.0712 0.0283 0.0328 0.0354 8.29 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/15/06 1544 534130 1 BXFI 06/18/06 1006 536483 2 SLN1 06/20/06 0901 538365 3+/-0.0127 0.0157 +/-0.0127 Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U -1.8 +/-4.81 4.07 +/-4.81 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Ash Soil Prep Ash Soil Prep, GL-RAD-A-021B LXM2 05/28/06 1209 534049 Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/26/06 1530 534048 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 Page 36 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-004F Project: YANKO 1204 Sample ID: 163741003 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 2 EPA 905.0 Modified 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 74 (25%-/125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 78 (25%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 37 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: Report Date: June 23, 2006 9106-0008-005F 163741004 SE 05-MAY-06 26-MAY-06 Client 57.1%Proiect: Client ID: Vol. Recv.: YANK01204 YANK001 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma, Solid-FSS GAM & ALL FSS Actinium-228 Americium-241 U-(Bismuth-212 Bismuth-214 Cesium-134 U Cesium-137 Cobalt-60 U Europium-152 U Europium-154 U Europium-155 U Lead-212 Lead-214 Manganese-54 UI Niobium-94 U Potassium-40 Radium-226 Silver-108m U Thallium-208 Rad Gas Flow Proportional Counting GFPC, S90, solid-ALL FSS Strontium-90 U C Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 0.859 0.000334 0.612 0.792 0.0388 0.266 0.0275-0.0306 0.0128 0.0403 0.757 0.677 0.00-0.0242 12.4 0.792-0.0184 0.262+/-0.224+/-0.0393+/-0.380+/-0.157+/-0.0682+/-0.0822+/-0.0345+/-0.0864+/-0.0977+/-0.0709+/-0.122+/-0.132+/-0.0953+/-0.030+/-1.44+/-0.157+/-0.0271+/-0.0789 0.0761 0.0331 0.239 0.0434 0.0328 0.0282 0.0314 0.0714 0.0818 0.0602 0.0365 0.0501 0.0265 0.0222 0.265 0.0434 0.0214 0.0219+/-0.224+/-0.0393+/-0.380+/-0.157+/-0.0682+/-0.0822+/-0.0345+/-0.0864+/-0.0977+/-0.0709+/-0.122+/-0.132+/-0.0953+/-0.030+/-1.44+/-0.157+/-0.0271+/-0.0789 0.170 0.0687 0.512 0.0941 0.0708 0.0607 0.0696 0.150 0.182 0.125 0.0764 0.106 0.0579 0.0482 0.598 0.0941 0.0458 0.0478 0.0376 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/15/06 1650 534130 1 BXFI 06/18/06 1006 536483 2 SLNI 06/20/06 0948 538365 3 1.000828 +/-0.0152 0.0169 +/-0.0152-0.858 +/-4.37 3.69 +/-4.37 7.51 pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Ash Soil Prep Ash Soil Prep, GL-RAD-A-021B LXM2 05/28/06 1209 534049 Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/26/06 1530 534048 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 Page 38 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-005F Project: YANK01204 Sample ID: 163741004 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 2 EPA 905.0 Modified 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 78 (25%-125%o)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 80 (25%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 39 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analyvis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-006F 163741005 SE 05-MAY-06 26-MAY-06 Client 30.9%Proiect: Client ID: Vol. Recv.: YANKO 1204 YANK001 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma, Solid-FSS GAM & ALL FSS Actinium-228 0.813 Americium-241 U 0.0977 Bismuth-212 0.817 Bismuth-214 0.624 Cesium-134 Ut 0.00 Cesium-137 0.492 Cobalt-60 0.779 Europium-152 U -0.0151 Europium-154 U 0.000763 Europium-155 U 0.0672 Lead-212 0.873 Lead-214 0.720 Manganese-54 U 0.0138 Niobium-94 U -0.00895 Potassium-40 13.7 Radium-226 0.624 Silver-108m U 0.00177 Thallium-208 0.298 Rad Gas Flow Proportional Counting+/-0.227+/-0.116+/-0.336+/-0.109+/-0.0387+/-0.0725+/-0.098+/-0.0601+/-0.0759+/-0.0612+/-0.0951+/-0.120+/-0.0283+/-0.0211+/-1.37+/-0.109+/-0.0192+/-0.0652 0.0748 0.0927 0.146 0.0355 0.0266 0.0214 0.0183 0.0488 0.0637 0.0565 0.030 0.0351 0.0242 0.0171 0.145 0.0355 0.0168 0.0195+/-0.227+/-0.116+/-0.336+/-0.109+/-0.0387+/-0.0725+/-0.098+/-0.0601+/-0.0759+/-0.0612+/-0.0951+/-0.120+/-0.0283+/-0.0211+/-1.37+/-0.109+/-0.0192+/-0.0652 0.160 0.191 0.311 0.0751 0.0562 0.0452 0.0405 0.102 0.138 0.116 0.0622 0.0735 0.0511 0.0363 0.330 0.0751 0.0354 0.0413 0.0302 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/15/06 1838 534130 1 GFPC, Sr90, solid-ALL FSS Strontium-90 Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63* 0.00559 +/-0.013 0.0132 +/-0.013 U 2.28 +/-10.1 8.45 +/-10.1 BXFI 06/22/06 1035 536483 2 SLNI 06/20/06 1035 538365 3 17.2 pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Ash Soil Prep Ash Soil Prep, GL-RAD-A-021B LXM2 05/28/06 1209 534049 Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/26/06 1530 534048 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 Page 40 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-006F Project: YANK01204 Sample ID: 163741005 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 2 EPA 905.0 Modified 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 59 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 54 (25%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 41 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company : Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-006FS 163741006 SE 05-MAY-06 26-MAY-06 Client 40.3%Project: YANK01204 Client ID: YANKOOI Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis GammaSolid-FSS GAM & ALL FSS Actinium-228 1.01 Americium-241 U 0.0585 Bismuth-212 0.587 Bismuth-214 0.694 Cesium-134 U 0.0331 Cesium-137 0.601 Cobalt-60 1.34 Europium-152 U 0.00817 Europium-154 U -0.0337 Europium-155 U 0.106 Lead-212 0.866 Lead-214 0.763 Manganese-54 U 0.0198 Niobium-94 U -0.0228 Potassium-40 14.9 Radium-226 0.694 Silver- 108m U-0.000651 Thallium-208 0.360 Rad Gas Flow Proportional Counting+/-0.284+/-0.0523+/-0.428+/-0.162+/-0.0414+/-0.100+/-0.140+/-0.0797+/-0.0957+/-0.115+/-0.135+/-0.147+/-0.0388+/-0.0306+/-1.49+/-0.162+/-0.0283+/-0.073 0.111 0.0334 0.199 0.0485 0.0374 0.0292 0.024 0.0688 0.0757 0.0619 0.0461 0.0479 0.0343 0.0233 0.237 0.0485 0.0239 0.0275+/-0.284+/-0.0523+/-0.428+/-0.162+/-0.0414+/-0.100+/-0.140+/-0.0797+/-0.0957+/-0.115+/-0.135+/-0.147+/-0.0388+/-0.0306+/- 1.49+/-0.162+/-0.0283+/-0.073 0.236 0.0689 0.427 0.103 0.0791 0.0619 0.0539 0.144 0.167 0.128 0.0951 0.101 0.0728 0.0499 0.532 0.103 0.0504 0.0585 0.0355 10.4 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJHI 06/15/06 1953 534130 1 GFPC, Sr9O, solid-ALL FSS Strontium-90 t Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 t.0.000875 +/-0.0141 0.0156 +/-0.0141 0.188 +/-6.10 5.12 +/-6.10 BXF1 06/18/06 1007 536483 2 SLNI 06/20/06 1122 538365 3 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Ash Soil Prep Ash Soil Prep, GL-RAD-A-021B LXM2 05/28/06 1209 534049 Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/26/06 1530 534048 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 Page 42 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-006FS Project: YANKO 1204 Sample ID: 163741006 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 2 EPA 905.0 Modified 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 71 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 84 (25%-125o)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below.the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 43 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-002F 163741007 SE 05-MAY-06 26-MAY-06 Client 40.6%Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma,Solid-FSS GAM & ALL FSS Actinium-228 1.20 Americium-241 U -0.0887 Bismuth-212 0.731 Bismuth-214 0.791 Cesium-134 UI 0.00 Cesium-137 U -0.00891 Cobalt-60 U 0.00777 Europium-152 U -0.00544 Europium-154 U 0.0213 Europium-155 U 0.0635 Lead-212 1.24 Lead-214 0.965 Manganese-54 U 0.0116 Niobium-94 U 0.000167 Potassium-40 18.2 Radium-226 0.791 Silver-108m U -0.00521 Thallium-208 0.332 Rad Gas Flow Proportional Counting+1-0.150+/-0.0966+/-0.231+/-0.0864+/-0.022+/-0.0193+/-0.0188+/-0.0415+/-0.0532+/-0.0805+/-0.0603+/-0.081+/-0.0185+/-0.016+/-0.772+/-0.0864+/-0.0142+/-0.0409 0.0467 0.0733 0.102 0.0249 0.0171 0.0132 0.0156 0.035 0.0443 0.0424 0.0209 0.0252 0.016 0.0129 0.121 0.0249 0.0117 0.0136+1-0.150+/-0.0966+/-0.231+/-0.0864+/-0.022+/-0.0193+/-0.0188+/-0.0415+/-0.0532+/-0.0805+/-0.0603+/-0.081+/-0.0185+/-0.016+/-0.772+/-0.0864+/-0.0142+/-0.0409 0.0976 0.150 0.213 0.0516 0.0355 0.0275 0.0329 0.0722 0.0929 0.0869 0.0429 0.0519 0.0331 0.0268 0.257 0.0516 0.0242 0.0281 0.0413 9.53 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJHI 06/15/06 1953 534130 1 GFPC, SO9O, solid-ALL FSS Strontium-90 1 Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 L J 0.0203 +/-0.0201 0.0182 +/-0.0201-4.84 +/-5.47 4.68 +/-5.47 BXF1 06/18/06 1007 536483 2 SLNI 06/20/06 1209 538365 3 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Ash Soil Prep Ash Soil Prep, GL-RAD-A-021B LXM2 05/28/06 1209 534049 Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/26/06 1530 534048 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 Page 44 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-002F Project: YANK01204 Sample ID: 163741007 Client ID: YANKOOI Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 2 EPA 905.0 Modified 3 DOE RESL Ni-1, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 65 (25%/-,125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 84 (25%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 45 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-007F 163741008 SE 05-MAY-06 26-MAY-06 Client 36.4%Proiect: YANK01204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.Curium-242 U Curium-243/244 U 0.0 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U Plutonium-239/240 U -(Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U Rad Gamma Spec Analysis Gamma,Solid-FSS GAM & ALL FSS Actinium-228 Americium-241 U I Bismuth-212 Bismuth-214 Cesium-134 U 0.Cesium-137 U 0.Cobalt-60 U 0.Europium-152 U 0.Europium-154 U 0.Europium-155 U 0.Lead-212 Lead-214 Manganese-54 U 0.Niobium-94 U -0.0 Potassium-40 Radium-226 (Silver-108m U 0.0 Thallium-208 (Rad Gas Flow Proportional Counting GFPC, Sr9O, solid-ALL FSS Strontium-90 U-0.00 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U Liquid Scint C14, Solid AllFSS+/-0.0968+/-0.0738+/-0.0669 0.062 0.00 0.0622+/-0.097+/-0.0738+/-0.0669 0.209 0.102 0.210 0.151 0.734 pCi/g pCi/g pCi/g pCi/g pCi/g 0.00 +/-0.110 0.00 +/-0.110).226 +/-0.163 0.292 +/-0.165 4.08 +/-6.18 5.06 +/-6.19 10.4 pCi/g+/-0.175+/-0.113+/-0.278+/-0.095+/-0.0399+/-0.0249+/-0.0279+/-0.0559+/-0.066+/-0.107+/-0.0898+/-0.106+/-0.0291+/-0.0196+/-1.34+/-0.095+/-0.0168+/-0.0465 0.0766 0.0936 0.166 0.0335 0.0228 0.0227 0.0241 0.0502 0.0605 0.0529 0.0301 0.035 0.0202 0.0158 0.166 0.0335 0.0149 0.0196+/-0.175+/-0.113+/-0.278+/-0.095+/-0.0399+/-0.0249+/-0.0279+/-0.0559+/-0.066+/-0.107+/-0.0898+/-0.106+/-0.0291+/-0.0196+/-1.34+/-0.095+/-0.0168+/-0.0465 0.165 0.194 0.355 0.0718 0.049 0.0481 0.0529 0.106 0.133 0.110 0.0627 0.074 0.0437 0.0342 0.378 0.0718 0.032 0.0418 0.038 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g JXG1 06/16/06 1312 537411 1 JXGI 06/16/06 0928 537412 2 JXGI 06/20/06 1900 537417 3 MJH1 06/15/06 2141 534130 4 BXFI 06/18/06 1007 536483 5 NXPI 06/17/06 1609 535984 6 0881 +/-0.0151 0.0171 +/-0.0151 4.94 +/-6.95 5.56 +/-6.95 11.7 pCi/g Page 46 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: 9106-0008-007F 163741008 Project: YANK01204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Liquid Scintillation Analysis Liquid Scint C14, SolidAllFSS Carbon-14 U -0.015 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U 21.1 Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U -2.33 Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.196+/-0.126 0.106 +/-0.126+/-18.3 13.0 +/-18.5+/-5.91 5.00 +/-5.91+/-0.227 0.184 +/-0.227 0.216 27.4 pCi/g pCi/g ATH2 06/04/06 0432 534837 7 SLNI 06/21/06 0813 538969 8 SLNI 06/20/06 1256 538365 9 SXEI 06/14/06 1714 536314 10 10.2 pCi/g 0.380 pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Ash Soil Prep Ash Soil Prep, GL-RAD-A-021B LXM2 05/28/06 1209 534049 Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM1 05/26/06 1530 534048 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu-I I-RC Modified 3 DOE EML HASL-300, Pu- 11-RC Modified 4 EML HASL 300, 4.5.2.3 5 EPA 905.0 Modified 6 EPA 906.0 Modified 7 EPA EERF C-01 Modified 8 DOE RESL Fe-I, Modified 9 DOE RESL Ni-l, Modified 10 DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL F5 GFPC, Sr90, solid-ALL FSS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS 83 47 94 79 83 80 (15%-125%)
(15%-125%)
(25%-I125%)
(25%-I125%)
(15o/6-125%)
(25%-125%)
Page 47 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-007F Project: YANK01204 Sample ID: 163741008 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Carrier/Tracer Recovery Liquid Scint Tc99, Solid-ALL FS 84 (15%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 48 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company : Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd Contact: Project: East Hampton, Connecticut 06424 Mr. Jack McCarthy Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-008F 163741009 SE 08-MAY-06 26-MAY-06 Client 38.6%Project: Client ID: Vol. Recv.: YANKO 1204 YANK001 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma, Solid-FSS GAM & ALL FSS Actinium-228 0.974 Americium-241 U 0.0456 Bismuth-212 0.779 Bismuth-214 0.569 Cesium-134 U 0.0547 Cesium-137 0.472 Cobalt-60 0.917 Europium-152 U -0.0108 Europium-154 U 0.0271 Europium-155 U 0.00728 Lead-212 0.929 Lead-214 0.729 Manganese-54 U 0.030 Niobium-94 U 0.026 Potassium-40 14.5 Radium-226 0.569 Silver-108m U 0.00585 Thallium-208 0.274 Rad Gas Flow Proportional Counting GFPC, Sr9O, solid-ALL FSS Strontium-90 U -0.00269 Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U -0.412+/-0.257+/-0.101+/-0.439+/-0.134+/-0.0378+/-0.0788+/-0.101+/-0.0749+/-0.0787+/-0.0765+/-0.106+/-0.114+/-0.0293+/-0.0265+1-1.35+/-0.134+/-0.0218+/-0.0702 0.075 0.0814 0.173 0.0421 0.0286 0.023 0.0202 0.056 0.0671 0.0657 0.0331 0.0402 0.0266 0.0202 0.191 0.0421 0.0188 0.0206+/-0.257+/-0.101+/-0.439+/-0.134+/-0.0378+/-0.0788+/-0.101+/-0.0749+/-0.0787+/-0.0765+/-0.106+/-0.114+/-0.0293+/-0.0265+/-1.35+/-0.134+/-0.0218+/-0.0702 0.161 0.169 0.368 0.0889 0.0605 0.0488 0.0446 0.118 0.145 0.136 0.069 0.0845 0.0564 0.0428 0.422 0.0889 0.0398 0.0439 0.0476 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/15/06 2153 534130 1 BXFI 06/18/06 1007 536483 2 SLNI 06/20/06 1343 538365 3+/-0.0189 0.0216 +/-0.0189+/-8.90 7.48 +/-8.90 15.2 pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/28/06 1412 534097 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 2 EPA 905.0 Modified Page 49 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-008F Project: YANKO 1204 Sample ID: 163741009 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 74 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 57 (25%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.U1 Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier* QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 50 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd Contact: Project: East Hampton, Connecticut 06424 Mr. Jack McCarthy Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-009F 163741010 SE 08-MAY-06 26-MAY-06 Client 36.8%Project: Client ID: Vol. Recv.: YANKO 1204 YANK001 Parameter (Rad Gamma Spec Analysis:ualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Gamma,Solid-FSS GAM & ALL FSS Actinium-228 Americium-241 U Bismuth-212 Bismuth-214 Cesium-134 U Cesium-137 U Cobalt-60 U Europium-152 U Europium-154 U Europium-155 U Lead-212 Lead-214 Manganese-54 U Niobium-94 U Potassium-40 Radium-226 Silver-108m U Thallium-208 Rad Gas Flow Proportional Counting GFPC, Sr9O, solid-ALL FSS Strontium-90 U Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 0.741-0.0785 0.596 0.667 0.0506 0.0155-0.0108-0.0723-0.051 0.0418 0.813 0.782-0.0123 0.014 14.8 0.667-0.0119 0.306+/-0.207+/-0.124+/-0.368+/-0.109+/-0.0431+/-0.0231+/-0.0254+/-0.0543+/-0.0695+/-0.0558+/-0.0899+/-0.120+/-0.0257+/-0.0192+/-1.41+/-0.109+/-0.0163+/-0.0596 0.0619 0.0788 0.134 0.0311 0.0244 0.0183 0.0202 0.0406 0.0535 0.0512 0.0284 0.0326 0.0204 0.017 0.147 0.0311 0.0135 0.0159+/-0.207+/-0.124+/-0.368+/-0.109+/-0.0431+/-0.0231+/-0.0254+/-0.0543+/-0.0695+/-0.0558+/-0.0899+/-0.120+/-0.0257+/-0.0192+/-1.41+/-0.109+/-0.0163+/-0.0596 0.134 0.163 0.287 0.0663 0.0516 0.039 0.0443 0.0856 0.117 0.106 0.0589 0.0685 0.0435 0.0361 0.333 0.0663 0.0287 0.0339 0.0443 17.9 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/16/06 0622 534130 1 BXF1 06/18/06 1101 536483 2 SLN1 06/20/06 1430 538365 3-0.0059 +/-0.0171 0.0202 +/-0.0171-2.05 +/-10.4 8.80 +/-10.4 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/28/06 1412 534097 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 2 EPA 905.0 Modified Page 51 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-009F Proiect: YANKO 1204 Sample ID: 163741010 Client ID: YANKOOl Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 75 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 52 (25%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 52 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: 9106-0008-010F Project: YANKO1204 Sample ID: 163741011 Client ID: YANK001 Matrix: SE Vol. Recv.: Collect Date: 08-MAY-06 Receive Date: 26-MAY-06 Collector:
Client Moisture:
42.1%Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma,Solid FSS GAM & ALL FSS Actinium-228 Americium-241 U Bismuth-212 Bismuth-214 Cesium-134 U Cesium-137 Cobalt-60 Europium-152 U Europium-154 U -Europium-155 U Lead-212 Lead-214 Manganese-54 U Niobium-94 U -Potassium-40 Radium-226 Silver-108m U Thallium-208 Rad Gas Flow Proportional Counting GFPC, S90, solid-ALL FSS Strontium-90 U Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 0.840 0.0195 0.758 0.662 0.047 0.336 0.246-0.0238-0.00597 0.0474 0.887 0.705 0.00134 0.00916 12.5 0.662 0.0162 0.316+/-0.226+/-0.0317+/-0.371+/-0.138+/-0.0343+/-0.0689+1-0.0501+/-0.0624+/-0.0975+/-0.0837+/-0.124+/-0.116+/-0.0286+/-0.026+/-1.26+/-0.138+/-0.0222+/-0.0704 0.0786 0.0282 0.162 0.0422 0.0272 0.0223 0.0226 0.0526 0.0691 0.0461 0.0287 0.0397 0.0245 0.0207 0.187 0.0422 0.0196 0.0195+/-0.226+/-0.0317+/-0.371+/-0.138+/-0.0343+/-0.0689+1-0.0501+/-0.0624+/-0.0975+/-0.0837+/-0.124+/-0.116+/-0.0286+/-0.026+/-1.26+/-0.138+/-0.0222+/-0.0704 0.168 0.0579 0.345 0.0889 0.0577 0.0472 0.0494 0.110 0.150 0.0952 0.0596 0.0828 0.0521 0.0439 0.415 0.0889 0.0411 0.0415 0.0288 10.2 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJHI 06/16/06 0622 534130 1 BXF1 06/22/06 1046 536483 2 SLN1 06/20/06 1517 538365 3 0.00347 +/-0.0121 0.0128 +/-0.0121 0.123 +/-5.98 5.02 +/-5.98 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/28/06 1412 534097 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 Page 53 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: 9106-0008-OIOF 163741011 Project: Client ID: Vol. Recv.: YANKO 1204 YANKOOI Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 2 EPA 905.0 Modified 3 DOE RESL Ni-1, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS Liquid Scint Ni63, Solid-ALL FS 69 84 (25%-125%)
(25%-/125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 54 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-010FS 163741012 SE 08-MAY-06 26-MAY-06 Client 41.1%Project: Client ID: Vol. Recv.: YANK01204 YANKOO1 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis GammaSolid-FSS GAM & ALL FSS Actinium-228 0.834 Americium-241 U 0.0216 Bismuth-212 0.657 Bismuth-214 0.640 Cesium-134 U 0.0478 Cesium-137 0.302 Cobalt-60 0.328 Europium-152 U 0.0241 Europium-154 U -0.0192 Europium-155 U 0.0699 Lead-212 0.826 Lead-214 0.705 Manganese-54 U 0.014 Niobium-94 U -0.00643 Potassium-40 12.7 Radium-226 0.640 Silver-108m U-0.000137 Thallium-208 0.257 Rad Gas Flow Proportional Counting+/-0.216+/-0.0277+/-0.246+/-0.127+/-0.0354+/-0.0573+/-0.0592+/-0.0519+/-0.0711+/-0.049+/-0.112+/-0.106+/-0.0231+/-0.0227+/-1.18+/-0.127+/-0.0191+/-0.0533 0.0744 0.0248 0.145 0.0335 0.0239 0.0214 0.0204 0.0457 0.0575 0.0436 0.0257 0.0338 0.0185 0.0183 0.161 0.0335 0.0163 0.0193+/-0.216+/-0.0277+/-0.246+/-0.127+/-0.0354+/-0.0573+/-0.0592+/-0.0519+/-0.0711+/-0.049+/-0.112+/-0.106+/-0.0231+/-0.0227+/-1.18+/-0.127+/-0.0191+/-0.0533 0.157 0.0509 0.306 0.0706 0.0503 0.0448 0.044 0.0952 0.124 0.0894 0.053 0.0704 0.0394 0.0385 0.355 0.0706 0.034 0.0406 0.0387 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/15/06 2338 534130 1 GFPC, Sr90, solid-ALL FSS Strontium-90 U Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 L 0.00859 +/-0.017 0.0174 +/-0.017 , -1.63 +/-6.69 5.65 +/-6.69 BXF1 06/18/06 1101 536483 2 SLNI 06/20/06 1604 538365 3 11.5 pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/28/06 1412 534097 The following Analytical Methods were performed Method Description 1 2 EML HASL 300, 4.5.2.3 EPA 905.0 Modified Page 55 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-010FS Project: YANK01204 Sample ID: 163741012 Client ID: YANKOOI Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units -DF Analyst Date Time Batch Mtd 3 DOE RESL Ni-I, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 78 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 81 (25%- 125%)Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UT Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 56 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-01 IF 163741013 SE 08-MAY-06 26-MAY-06 Client 65.1%Proiect: Client ID: Vol. Recv.: YANKO 1204 YANK001 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma,Solid-FSS GAM & ALL FSS Actinium-228 Americium-241 U Bismuth-212 U Bismuth-214 Cesium-134 UI Cesium-137 U Cobalt-60 Europium-152 U Europium-154 U Europium-155 Lead-212 Lead-214 Manganese-54 U Niobium-94 U Potassium-40 Radium-226 Silver-108m U Thallium-208 Rad Gas Flow Proportional Counting GFPC, SO9O, solid-ALL FSS Strontium-90 U Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 0.894-0.0065 0.385 0.528 0.00 0.0676 0.122-0.0509-0.0134 0.186 1.01 0.842 0.0352-0.0177 16.3 0.528-0.0176 0.314+/-0.285+/-0.0527+/-0.499+/-0.139+/-0.0499+/-0.0621+/-0.0837+/-0.102+/-0.124+/-0.145+/-0.0964+/-0.147+/-0.0459+/-0.0382+/-1.25+/-0.139+/-0.0361+/-0.0793 0.121 0.043 0.263 0.0646 0.0436 0.038 0.0368 0.0819 0.103 0.076 0.0434 0.0595 0.0393 0.0309 0.275 0.0646 0.0285 0.0353+/-0.285+/-0.0527+/-0.499+/-0.139+/-0.0499+/-0.0621+/-0.0837+/-0.102+/-0.124+/-0.145+/-0.0964+/-0.147+/-0.0459+/-0.0382+/-1.25+/-0.139+/-0.0361+/-0.0793 0.255 0.088 0.551 0.135 0.091 0.079 0.0784 0.170 0.218 0.156 0.0896 0.123 0.0822 0.0647 0.598 0.135 0.0592 0.0736 0.0344 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/15/06 2338 534130 1 BXFI 06/18/06 1106 536483 2 SLN1 06/20/06 1651 538365 3 0.0193 +/-0.017 0.0153 +/-0.017-3.34 +/-6.23 5.29 +/-6.23 10.8 pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM1 05/28/06 1412 534097 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 2 EPA 905.0 Modified Page 57 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address: 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: 9106-0008-01IF 163741013 Project: YANK01204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 3 DOE RESL Ni-1, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS Liquid Scint Ni63, Solid-ALL FS 77 89 (25%- 125%)(25%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 58 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-013F 163741014 SE 08-MAY-06 26-MAY-06 Client 61.4%Project: YANK01204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma,Solid-FSS GAM & ALL FSS Actinium-228 Americium-241 U Bismuth-212 Bismuth-214 Cesium-134 UI Cesium-137 U Cobalt-60 U Europium-152 U Europium-154 U Europium-155 U Lead-212 Lead-214 Manganese-54 U Niobium-94 U Potassium-40 Radium-226 Silver-108m U Thallium-208 Rad Gas Flow Proportional Counting GFPC, Sr9O, solid-ALL FSS Strontium-90 U Rad Liquid Scintillation Analysis Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 1.21 0.0448 0.622 0.871 0.00 0.0103 0.0299-0.0772 0.0345 0.0901 1.15 1.00 0.0151 0.0107 19.2 0.871 0.0111 0.313+/-0.250+/-0.116+/-0.272+/-0.154+/-0.0417+/-0.0281+/-0.0305+/-0.0721+/-0.0915+/-0.087+/-0.129+/-0.172+/-0.0301+/-0.0253+/-1.60+/-0.154+/-0.0239+/-0.0665 0.0775 0.0842 0.166 0.0439 0.0281 0.0232 0.0268 0.0554 0.0761 0.0707 0.0377 0.041 0.0256 0.0216 0.185 0.0439 0.0198 0.0232+/-0.250+/-0.116+/-0.272+/-0.154+/-0.0417+/-0.02 81+/-0.0305+/-0.0721+/-0.0915+/-0.087+/-0.129+/-0.172+/-0.0301+/-0.0253+/- 1.60+/-0.154+/-0.0239+/-0.0665 0.165 0.173 0.352 0.0922 0.0593 0.0489 0.0573 0.116 0.163 0.146 0.0779 0.0856 0.0541 0.0454 0.408 0.0922 0.0416 0.0487 0.0353 10.3 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJH1 06/15/06 2354 534130 1 BXFI 06/18/06 1106 536483 2 SLNI 06/20/06 1738 538365 3 0.0098 +/-0.0158 0.0157 +/-0.0158-2.7 +/-5.98 5.07 +/-5.98 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM1 05/28/06 1412 534097 The following Analytical Methods were performed Method Description 1 EML HASL 300, 4.5.2.3 2 EPA 905.0 Modified Page 59 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-013F Proiect: YANK01204 Sample ID: 163741014 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 3 DOE RESL Ni-1, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 77 (25%-/125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 83 (25%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 60 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address: 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-014F 163741015 SE 08-MAY-06 26-MAY-06 Client 54.1%Project: Client ID: Vol. Recv.: YANK01204 YANK001 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Gamma Spec Analysis Gamma,Solid-FSS GAM & ALL FSS Actinium-228 0.829 Americium-241 U -0.00581 Bismuth-212 0.447 Bismuth-214 0.758 Cesium-134 U 0.0414 Cesium-137 U -0.00389 Cobalt-60 U -0.0145 Europium-152 U 0.00738 Europium-154 U -0.0016 Europium-155 U 0.0316 Lead-212 1.01 Lead-214 0.746 Manganese-54 U -0.00360!Niobium-94 U -0.00521 Potassium-40 14.7 Radium-226 0.758 Silver-108m U 0.000405 Thallium-208 0.326 Rad Gas Flow Proportional Counting GFPC, Sr9O, solid-ALL FSS Strontium-90 U 0.0054 Rad Liquid Scintillation Analysis+/-0.225+/-0.113+/-0.261+/-0.126+/-0.0279+/-0.0232+/-0.0239+/-0.0586+/-0.076+/-0.0628+/-0.109+/-0.119+/-0.027+/-0.0228+/-1.47+/-0.126+/-0.0194+/-0.0564 0.0682 0.089 0.161 0.0375 0.0252 0.0189 0.0182 0.0474 0.0629 0.0545 0.0282 0.0365 0.0217 0.0184 0.205 0.0375 0.0165 0.0209+/-0.225+/-0.113+/-0.261+/-0.126+/-0.0279+/-0.0232+/-0.0239+/-0.0586+/-0.076+/-0.0628+/-0.109+/-0.119+/-0.027+/-0.0228+/-1.47+/-0.126+/-0.0194+/-0.0564 0.147 0.184 0.342 0.0792 0.0533 0.0402 0.0404 0.0995 0.137 0.113 0.0587 0.0763 0.0461 0.0391 0.450 0.0792 0.0348 0.0441 0.0357 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g MJHI 06/15/06 2346 534130 1 BXFI 06/18/06 1106 536483 2 SLN1 06/20/06 1825 538365 3+/-0.0153 0.0161 +/-0.0153 Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U -1.72 +/-7.06 5.96 +/-7.06 12.1 pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM1 05/28/06 1412 534097 The following Analytical Methods were performed Method Description I EML HASL 300, 4.5.2.3 2 EPA 905.0 Modified Page 61 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-014F Proiect: YANKO 1204 Sample ID: 163741015 ClientID:
YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 3 DOE RESL Ni-1, Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 82 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Ni63, Solid-ALL FS 79 (25%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 62 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -wwwgel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-012F 163741016 SE 08-MAY-06 26-MAY-06 Client 26.1%Project: Client ID: Vol. Recv.: YANKO 1204 YANK001 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U Curium-242 U Curium-243/244 U Alphaspec Pu, Solid-ALL FSS Plutonium-238 U Plutonium-239/240 U Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U Rad Gamma Spec Analysis Gamma,Solid-FSS GAM & ALL FSS Actinium-228 Americium-241 U-0.Bismuth-212 Bismuth-214 Cesium-134 UI Cesium-137 Cobalt-60 Europium-152 U Europium-154 U Europium-155 UI Lead-212 Lead-214 Manganese-54 U Niobium-94 U Potassium-40 Radium-226 Silver-108m U -(Thallium-208 Rad Gas Flow Proportional Counting 0.0299 0.0126 0.0383+1-0.151+/-0.0957+/-0.218 0.144 0.089 0.218+1-0.151+/-0.0957+/-0.218 0.392 0.300 0.540 0.0875 0.234 pCi/g pCi/g pCi/g pCi/g pCi/g 0.00 +/-0.0633 0.0335 +/-0.0944 0.00 +/-0.0633 0.0735 +/-0.0945-0.179 +/-10.9 9.12 +/-10.9 18.8 pCi/g 0.685 000535 0.589 0.445 0.00 0.184 0.179 0.0299 0.0105 0.00 0.723 0.586 0.003 0.00892 11.7 0.445 0.00372 0.221+/-0.143+/-0.0924+/-0.310+/-0.0688+/-0.0301+/-0.0341+/-0.0378+/-0.0402+/-0.0393+/-0.0573+/-0.0792+/-0.0847+/-0.0149+/-0.0123+/-0.969+/-0.0688+/-0.0119+/-0.0359 0.0394 0.0773 0.087 0.023 0.0151 0.0108 0.0132 0.0309 0.0338 0.0318 0.0193 0.0213 0.0125 0.0107 0.0946 0.023 0.0103 0.0107+/-0.143+/-0.0924+/-0.310+/-0.0688+/-0.0301+/-0.0341+/-0.0378+/-0.0402+/-0.0393+/-0.0573+/-0.0792+/-0.0847+/-0.0149+/-0.0123+/-0.969+/-0.0688+/-0.0119+/-0.0359 0.0829 0.159 0.182 0.0477 0.0313 0.0226 0.028 0.0637 0.0718 0.0653 0.0396 0.0441 0.0261 0.0223 0.205 0.0477 0.0213 0.0223 0.0418 10.7 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g JXGI 06/16/06 0803 537411 1 JXGI 06/16/06 0928 537412 2 JXGI 06/20/06 1931 537417 3 MJHI 06/16/06 0623 534130 4 BXF1 06/18/06 1109 536483 5 NXPI 06/17/06 1626 535984 6 GFPC, Sr90, solid-ALL FSS Strontium-90 U -0.Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U 0 Liquid Scint C14, Solid AIIFSS 0192 +/-0.0141 0.0192 +/-0.0141.839+/-6.11 5.08 +/-6.11 Page 63 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: June 23, 2006 Client Sample ID: Sample ID: 9106-0008-012F 163741016 Project: YANK01204 Client ID: YANKOOI Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Liquid Scintillation Analysis Liquid Scint C4, SolidAllFSS Carbon-14 U 0.Liquid Scint Fe55, Solid-ALL FSS Iron-55 U -Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U -Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U -0.0+/-0.117 0.095 +/-0.117-3.6 +/-17.5 13.4 +/-17.5 2.17 +/-8.55 7.22 +/-8.55 182 +/-0.216 0.182 +/-0.216 0.193 28.2 14.7 0.375 pCi/g pCi/g pCi/g pCi/g ATH2 06/05/06 2139 534837 7 SLN1 06/21/06 0829 538969 8 SLNI 06/20/06 1912 538365 9 SXEI 06/14/06 1730 536314 10 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXMI 05/28/06 1412 534097 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu-I I-RC Modified 3 DOE EML HASL-300, Pu-I I-RC Modified 4 EML HASL 300, 4.5.2.3 5 EPA 905.0 Modified 6 EPA 906.0 Modified 7 EPA EERF C-01 Modified 8 DOE RESL Fe-I, Modified 9 DOE RESL Ni-l, Modified 10 DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS GFPC, Sr90, solid-ALL FSS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS 76 89 52 85 91 63 83 (15%-125%)
(15%-125%)
(25%-.125%)
(25%-.125%)
(15%-125%)
(25%- 125%)(15°-125%)
Page 64 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: June 23, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0008-012F Proiect: YANK01204 Sample ID: 163741016 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier* QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 65 of 75 I.QUALITY CONTROL DATA I Page 66 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Client : Connecticut Yankee Atomic Power 362 Injun Hollow Rd Report Date: June 23, 2006 Page 1 of 9 East Hampton, Connecticut Contact: Mr. Jack McCarthy Workorder:
163741 Pormnomo Samnie Aiinal Oi C Units RPD%REC% Range Anist Date Time Rad Alpha Spec Batch 537411 QC1201110208 Americium-241 Curium-242 Curium-243/244 QCI201110210 Americium-241 163741008 DUP LCS Curium-242 Curium-243/244 QCI201110207 MB Americium-241 Curium-242 Curium-243/244 QC1201110209 163741008 MS Americium-241 Curium-242 Curium-243/244 U 0.0496 Uncert: +/-0.0968 TPU: +/-0.097 U 0.00 Uncert: +/-0.0738 TPU: +/-0.0738 U 0.00883 Uncert: +/-0.0669 TPU: +/-0.0669 13.0 Uncert: TPU: Uncert: TPU: 15.9 Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: 13.6 U 0.0496 Uncert: +/-0.0968 TPU: +/-0.097 U 0.00 Uncert: +/-0.0738 TPU: +/-0.0738 16.7 U 0.00883 Uncert: +/-0.0669 TPU: +/-0.0669 U 0.0424+/-0.116+/-0.116 U -0.0313+/-0.0354+/-0.0357 U -0.0933+/-0.126+/-0.126 12.7+/-1.35+/-2.20 U 0.0293+/-0.0778+/-0.0779 15.4+/-1.50+/-2.59 U -0.0328+/-0.0912+/-0.0914 U -0.0112+/-0.022+/-0.022 U -0.129+/-0.123+/-0.124 pCi/g 16 pCi/g 200 pCi/g 242 pCi/g (0% -100%) JXGI 06/16/06 08:03 (0%- 100%)(0%- 100%)98 (75%-125%)
pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 97 (75%-125%)
U 13.4+/-1.46+/-2.36 0.0255+/-0.102+/-0.102 16.3+/-1.62+/-2.79 99 (75%-125%)
98 (75%-125%)
Batch 537412 QCI201110216 163741008 DUP Plutonium-238 U 0.00 U 0.00 pCi/g 0 (0% -100%) JXG1 06/16/06 09:28 Page 67 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
163741 Page 2 of 9 Parmname Rad Alpha Spec Batch NOM Sample Qual QC Units RPD%REC% Range Anist Date Time 537412 Plutonium-239/240 QCI201110218 LCS Plutonium-238 Plutonium-239/240 QCI201110215 MB Plutonium-238 Plutonium-239/240 QC1201110217 163741008 MS Plutonium-238 Uncert: +/-0.110 TPU: +/-0.110 U -0.226 Uncert: +/-0.163 TPU: +/-0.165 Uncert: TPU: 12.0 Uncert: TPU: Uncert: TPU: Uncert: TPU: U 0.00 Uncert: +/-0.110 TPU: +/-0.110 12.6 U -0.226 Uncert: +/-0.163 TPU: +/-0.165 U 4.08 Uncert" +/-6.18+/-0.0615+/-0.0615 U 0.0326+/-0.0917+/-0.0918 U 0.0301+/-0.0797+/-0.0798 10.9+/-1.29+/-1.77 U 0.0798+/-0.0991+/-0.0995 U 0.044+/-0.0824+/-0.0826 pCi/g 267 (0%- 100%)(75%-125%)
pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 91 (75%-125%)
U 0.00901+/-0.0856+/-0.0856 10.7+/-1.08+/-1.51 (75%-125%)
Plutonium-239/240 85 (75%-125%)
Batch 537417 QC1201110230 163741008 DUP Plutonium-241 QC1201110232 LCS Plutonium-241 QC1201110229 MB Plutonium-241 QC1201110231 163741008 MS Plutonium-241 Rad Gamma Spec Batch 534130 QC1201102650 163741001 DUP Actinium-228 U -4.3+/-8.53+/-8.54 pCi/g 0 (0% -100%) JXG1 06/20/06 20:33 TPU:+/-6.19 140 Uncert: TPU: Uncert: TPU: 142 U Uncert: TPU: 144+/-10.8+/-17.7 U -2.16+/-6.46+/-6.47 pCilg pCilg pCilg 102 (75%-125%)
06/20/06 21:36 06/20/06 20:02 06/20/06 21:05 4.08+/-6.18+/-6.19 129+/-9.07+/-14.8 91 (75%-125%)
0.817+/-0.177 Uncert: 0.702+/-0.147+/-0.147 pCi/g 15 (0% -100%) MJHI 06/16/06 06:30 Page 68 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
163741 Page 3 of 9 Parmname NOM Samole Oual OC Units RPD%REC% Range AnIst Date Time Rad Gamma Spec Batch 534130 Americium-241 Bismuth-212 Bismuth-214 Cesium- 134 Cesium-137 Cobalt-60 Europium-152 Europium-154 Europium-155 TPU: +/-0.177 U 0.0431 Uncert: +/-0.0977 TPU: +/-0.0977 0.570 Uncert: +/-0.292 TPU: +/-0.292 0.568 Uncert: +/-0.0877 TPU: +/-0.0877 U 0.0314 Uncert: +/-0.0354 TPU: +/-0.0354 0.396 Uncert: +/-0.0588 TPU: +/-0.0588 0.133 Uncert: +/-0.0554 TPU: +/-0.0554 U 0.00717 Uncert: +/-0.0581 TPU: +/-0.0581 U 0.040 Uncert: +/-0.0643 TPU: +/-0.0643 U 0.0854 Uncert: +/-0.0769 TPU: +/-0.0769 0.772 Uncert: +/-0.0707 TPU: +/-0.0707 0.585 Uncert: +/-0.0841 TPU: +/-0.0841 U 0.0123 Uncert: +/-0.0261 TPU: +/-0.0261 U -0.000522 Uncert: +/-0.0212 TPU: +/-0.0212 12.1 Uncert: +/-0.950 TPU: +/-0.950 0.568 Uncert: +/-0.0877 TPU: +/-0.0877 U 0.00495 Uncert: +/-0.0195 U 0.0617+/-0.0702+/-0.0702 0.607+/-0.297+/-0.297 0.650+/-0.103+/-0.103 UI 0.0349+/-0.0245+/-0.0245 0.363+/-0.0539+/-0.0539 0.105+/-0.0405+/-0.0405 U -0.0343+/-0.061+/-0.061 U -0.0163+/-0.0693+/-0.0693 U 0.0232+/-0.0784+/-0.0784 0.808+/-0.0864+/-0.0864 0.742+/-0.099+/-0.099 U 0.0098+/-0.022+/-0.022 U 0.00495+/-0.0175+/-0.0175 12.1+/-1.08+/-1.08 0.650+/-0.103+/-0.103 U 0.0141+/-0.018 pCi/g 36 pCi/g 6 pCi/g 14 pCi/g 11 pCi/g 9 pCi/g 24 pCi/g 306 pCi/g 475 pCi/g 115 pCi/g 5 pCi/g 24 pCi/g 22 pCi/g 247 pCi/g 0 pCi/g 14 pCi/g 96 (0%- 100%)(0%- 100%)(0%- 100%)(0%- 100%)(0% -100%)(0%- 100%)(0%- 100%)(0% -100%)(0%- 100%)(0%- 20%)(0%- 20%)(0%- 100%)(0%- 100%)(0%- 20%)(0%- 100%)(0% -100%)Lead-212 Lead-214 Manganese-54 Niobium-94 Potassium-40 Radium-226 Silver- 108m Page 69 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
163741 Page 4 of 9 Parmname NOM Samnle Oual QC Units RPD%REC% Range Anist Date Time Rad Gamma Spec Batch 534130 Thallium-208 TPU: +/-0.0195 0.300 Uncert: +/-0.0497 TPU: +/-0.0497+/-0.018 0.295+/-0.0475+/-0.0475 pCi/g 2 (0%- 100%)QCI201102651 Actinium-228 Americium-24 1 Bismuth-212 LCS Bismuth-214 Cesium- 134 Cesium- 137 Cobalt-60 Europium-152 Europium-154 Europium-155 Uncert: TPU: 23.4 Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: 9.63 Uncert: TPU: 15.0 Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: U 0.235+/-0.581+/-0.581 23.0+/-2.46+/-2.46 U 0.778+/-1.12+/-1.12 U -0.171+/-0.298+/-0.298 U 0.0723+/-0.160+/-0.160 10.5+/-0.824+/-0.824 15.1+/- 1.08+/-1.08 U 0.042+/-0.334+/-0.334 U 0.289+/-0.325+/-0.325 U -0.257+/-0.387+/-0.387 U -0.101+/-0.189+/-0.189 U 0.233+/-0.248+/-0.248 U 0.0621+/-0.149+/-0.149 U -0.0598+/-0.129+/-0.129 U 0.576 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 109 (75%-125%)
101 (75%-125%)
98 (75%-125%)
06/16/06 06:31 Lead-212 Lead-214 Manganese-54 Niobium-94 Potassium-40 Page 70 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
163741 Page 5 of 9 Parmname Rad Gamma Spec Batch 534130 NOM Sample Qual QC Units RPD% REC% Range Anist Date Time Radium-226 Silver-108m Thallium-208 QC1201102649 Actinium-228 Americium-241 MB Bismuth-212 Bismuth-214 Cesium- 134 Cesium-137 Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU:+/-1.23+/-1.23 U -0.171+/-0.298+/-0.298 U -0.0434+/-0.123+/-0.123 U 0.144+/-0.146+/-0.146 U 0.0712+/-0.0472+/-0.0472 U 0.00139+/-0.0249+/-0.0249 U 0.0152+/-0.166+/-0.166 U 0.0175+/-0.0261+/-0.0261 U 0.00016+/-0.0151+/-0.0151 U -0.00376+/-0.0123+/-0.0123 U 0.00528+/-0.0137+/-0.0137 U -0.0157+/-0.0336+/-0.0336 U -0.0124+/-0.0325+/-0.0325 U 0.00213+/-0.031+/-0.031 U 0.000337+/-0.0331+/-0.0331 U 0.0225+/-0.0398+/-0.0398 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 06/16/06 06:23 (75%-125%)
Cobalt-60 Europium-152 Europium-154 Europium-155 Lead-2l2 Lead-214 Page 71 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
163741 Page 7 of 9 Parmname Rad Liquid Scintillation Batch 534837 NOM Samnle Oual OC Units RPD%REC% Range AnIst Date Time Uncert: TPU: QC1201104386 162335019 MS Carbon-14 7.13 U Uncert: TPU: 0.0228+/-0.110+/-0110 Batch 535984 QC1201106886 163626016 DUP Tritium+/-0.125+/-0.125 7.04+/-0.249+/-0.272-1.57+/-7.27+/-7.27 55.2+/-9.22+/-9.27 pCi/g 99 (75%-125%)
06/04/06 07:36 U 0.738 Uncert: +/-6.97 TPU: +/-6.97 U pCi/g 0 (0%- 100%) NXP1 06/17/06 17:31 QCI201106888 Tritium LCS QC1201106885 MB Tritium 52.7 Uncert: TPU: Uncert: TPU: 53.0 U Uncert: TPU: U -0.845+/-5.81+/-5.81 pCi/g pCi/g pCi/g 105 (75%-125%)
06/17/06 18:04 06/17/06 17:15 06/17/06 17:47 QC1201106887 163626016 MS Tritium 0.738+/-6.97+/-6.97 Batch 536314 QC1201107611 163741008 DUP Technetium-99 QC1201107613 LCS Technetium-99 QC0201107610 MB Technetium-99 QC1201107612 163741008 MS Technetium-99 U 0.196 Uncert: +/-0.227 TPU: +/-0.227 U 44.6+/-8.62+/-8.66 0.273+/-0.233+/-0.233 11.5+/-0.471+/-0.540 84 (75%-125%)
pCi/g 0 (0% -100%) SXEI 13.1 Uncert: TPU: Uncert: TPU: 12.7 U Uncert: TPU: U 0.090+/-0.200+/-0.200 pCi/g pCi/g pCi/g 87 (75%-125%)
06/14/06 18:37 06/14/06 19:11 06/14/06 18:20 06/14/06 18:54 0.196+/-0.227+/-0.227 Batch 538365 QC1201112556 163741003 DUP Nickel-63 QC1201112558 LCS Nickel-63 U -1.8 Uncert: +/-4.81 TPU: +/-4.81 U 11.2+/-0.494+/-0.557-2.43+/-6.00+/-6.00 287+/-13.5+1-15.5 88 (75%-125%)
pCi/g 0 (0% -100%) SLN 1 06/20/06 20:47 06/20/06 21:50 356 Uncert: TPU: pCi/g 81 (75%-125%)
Page 73 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
163741 Parmname Rad Gamma Spec Batch 534130 Manganese-54 Niobium-94 Potassium-40 Radium-226 Page 6 of 9 REC% Range AnIst Date Time NOM Samnle Oual QC Units RPD%Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: U -0.00637+/-0.0124+/-0.0124 U -0.00531+/-0.0115+/-0.0115 UI 0.00+/-0.267+/-0.267 U 0.0175+/-0.0261+/-0.0261 U -0.00282+/-0.0119+/-0.0119 U 0.000804+/-0.0171+/-0.0171 PCilg pCi/g pCilg pCi/g pCilg pCi/g Silver- 108m Thallium-208 Rad Gas Flow Batch 536483 QC1201108057 Strontium-90 163741001 DUP U 0.00579 Uncert: +/-0.0116 TPU: +/-0.0116 U QC1201108059 LCS Strontium-90 QC1201108056 MB Strontium-90 QC1201108058 163741001 MS Strontium-90 0.0106+/-0.0165+/-0.0165 1.41+/-0.100+/-0.109 pCi/g 0 (0% -100%) BXFI 1.43 Uncert: TPU: Uncert: TPU: 1.44 U Uncert: TPU: U -0.0118+/-0.0102+/-0.0102 pCi/g pCi/g pCi/g 99 (75%-125%)
06/18/06 11:09 06/18/06 10:06 06/18/06 11:09 06/18/06 11:09 0.00579+/-0.0116+/-0.0116 1.23+/-0.0952+/-0.102 86 (75%-125%)
Rad Liquid Scintillation Batch 534837 QCI201104385 Carbon- 14 162335019 DUP U 0.0228 Uncert: +/-0.110 TPU: +/-0.110 U QC1201104387 LCS Carbon-14 0.0418+/-0.121+/-0.121 6.52+/-0.238+/-0.259 pCi/g 0 (0% -100%) ATH2 6.66 Uncert: TPU: pCi/g 98 (75%-125%)
06/05/06 22:40 06/04/06 08:22 06/04/06 06:04 QC1201104384 MB Carbon- 14 U 0.0371 pCi/g Page 72 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
163741 Page 8 of 9 OC Units RPD% REC% Ranee Anlst Parm name NOM Samnle Oual Date Time Rad Liquid Scintillation Batch 538365 QC1201112555 MB Nickel-63 Uncert: TPU: U -1.14+/-3.95+/-3.95 pCi/g pCi/g 06/20/06 20:00 06/20/06 21:33 QC1201112557 163741003 MS Nickel-63 413 U Uncert: TPU:-1.8+/-4.81+/-4.81 Batch 538969 QC1201113888 163741008 DUP Iron-55 QC1201113890 LCS Iron-55 QC1201113887 MB Iron-55 QC1201113889 163741008 MS Iron-55 U 21.1 Uncert: +/-18.3 TPU: +/-18.5 U 347+/-16.5+/-19.3-1.03+/-16.3+/-16.3 529+/-44.0+/-86.2 84 (75%-125%)
pCi/g 0 (0%- 100%) SLNI 575 Uncert: TPU: Uncert: TPU: 594 U Uncert: TPU: U 5.38+/-26.8+/-26.8 pCi/g pCi/g pCi/g 92 (75%-125%)
06/21/06 10:23 06/21/06 10:40 06/21/06 09:51 06/21/06 10:07 21.1+/-18.3+/-18.5 546+/-33.8+/-74.0 92 (75%-125%)
Notes: The Qualifiers in this report are defined as follows:*A B BD C D H J N/A R U UI X Y A quality control analyte recovery is outside of specified acceptance criteria Result is less than value reported Result is greater than value reported The TIC is a suspected aldol-condensation product Target analyte was detected in the associated blank Results are either below the MDC or tracer recovery is low Analyte has been confirmed by GC/MS analysis Results are reported from a diluted aliquot of the sample Analytical holding time was exceeded Value is estimated Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more Sample results are rejected Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.Gamma Spectroscopy--Uncertain identification Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier QC Samples were not spiked with this compound RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL Page 74 of 75 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
163741 Page 9 of 9 Parmname NOM Sample Qual QC Units RPD% REC% Range AnIst Date Time h Preparation or preservation holding time was exceeded N/A indicates that spike recovery limits do not apply when sample concentration exceeds spike cone. by a factor of 4 or more.** Indicates analyte is a surrogate compound.A The Relative Percent Difference (RPD) obtained from the sample duplicate (DUP) is evaluated against the acceptence criteria when the sample is greater than five times (5X) the contract required detection limit (RL). In cases where either the sample or duplicate value is less than 5X the RL, a control limit of +/- the RL is used to evaluate the DUP result.For PS, PSD, and SDILT results, the values listed are the measured amounts, not final concentrations.
Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless qualified on the QC Summary.Page 75 of 75 General Narrative Page 1 of 105 CASE NARRATIVE For CONNECTICUT YANKEE RE: Soil PO# 002332 Work Order: 168404 SDG: MSR #06-0652, 06-0675, 06-0687, 06-0688, 06-0707, 06-0743, 06-0755 August 15, 2006 Laboratory Identification:
General Engineering Laboratories, LLC Mailing Address: P.O. Box 30712 Charleston, South Carolina 29417 Express Mail Delivery and Shipping Address: 2040 Savage Road Charleston, South Carolina 29407 Telephone Number: (843) 556-8171 Summary: Sample receipt The sample(s) for this Project arrived at General Engineering Laboratories, LLC, (GEL)in Charleston, South Carolina on May 5, May 9, May 12, May 17, May 26, June 2, June 8, 2006. All sample containers arrived without any visible signs of tampering or breakage.
The chain of custody contained the proper documentation and signatures.
The laboratory received the following sample(s):
Sample ID Client Sample ID 168404001 9106-0002-007F 168404002 9106-0002-01 IF 168404003 9106-0003-004F 168404004 9106-0003-015F 168404005 9106-0004-005F 168404006 9106-0004-015F 168404007 9106-0005-01 OF 168404008 9106-0005-014F 168404009 9106-0006-005F GENERAL ENGINEERING LABORATORIES, LLC a Member of THE GEL GROUP, INC.P.O. Box 30712 -Charleston, SC 29417 ° 2040 Savage Road (29407)Page 2 of 105 Phone (843) 556-8171 -Fax (843) 766-1178
- www.gel.com 168404010 9106-0008-006F 168404011 9106-0008-008F 168404012 9106-0009-002F 168404013 9106-0009-017F 168404014 9106-0010-OOIF 16840401.5 9106-0010-012F Items of Note: At the request of Dale Randall on July 20, 2006, GEL analyzed the above samples according to the spreadsheet in the attached email.Case Narrative:
Sample analyses were conducted using methodology as outlined in General Engineering Laboratories (GEL) Standard Operating Procedures.
Any technical or administrative problems during analysis, data review, and reduction are listed below by analytical parameter.
Analytical Request: Seven soil samples were reanalyzed for FSSALL, except gamma and Sr-90.Four soil samples were reanalyzed for FSSALL, except gamma and Ni-63.Two soil samples were reanalyzed for FSSALL, except gamma.Two soil samples were reanalyzed for FSALL, except gamma, Sr-90 and Ni-63.Internal Chain of Custody: Custody was maintained for the sample(s).
Data Package: The enclosed data package contains the following sections:
Case Narrative, Chain of Custody and Supporting Documentation and all analytical fractions.
I certify that this data package is in compliance with the SOW, both technically and for completeness, for other than the conditions detailed above. Release of the data contained in this hard copy data package has been authorized by the Laboratory Manager or a designee, as verified by the following signature.
Cheryl Jones Project Manager GENERAL ENGINEERING LABORATORIES, LLC a Member of THE GEL GROUP INC.P.O. Box 30712 ° Charleston, SC 29417 ° 2040 Savage Road (29407)Phone (843) 556-8171
- Fax (843) 766-1178
- www.gel.com Page 3 of 105.I :
Additional HTD analyses
Subject:
Additional HTD analyses From: "Dale Randall" <randall @cyapco.com>
Date: Thu, 20 Jul 2006 11:04:54 -0400 I U 8'4 0 (4'(, To: "Cheryl Jones" <cj @gel.corn>
CC: "Clyde Newson" <Newson@CYAPCO.com>, "John McCarthy" <McCarthy@CYAPCO.com>
Cheryl: Per our earlier discussion, attached is a list of samples that we would like to have analyzed to the FSSALL protocol.
I have included a list of test protocols performed on each sample to date. Once you have had an opportunity to determine our options for each sample please call or e-mail me at your convenience.
Thank You, Dale (860) 267-3133 Content-Description:
GEL FSSALL analyses request.xls GEL FSSALL analyses request.xls Content-Type:
Content-Encoding:
application/vnd.ms-excel base64 Page 4 of 105 I of I 8/2/2006 7:04 PM flnnR To be done Previous VGEL ID CY sample location IDs FSS Gamn Sr-90 Ni-63 Am Pu Sr9O Pu241 Fe55 Ni63 Tc99 H3 C14 164220008 9106-0002-007F x x x x x x x x x x 31 164220012 9106-0002-011F x x x x x x x x x x U,162335004 9106-0003-004F x x x x x x x x x x-162335014 9106-0003-015F x x x x x x x x x x 162832015 9106-0004-005F x x x x x x x x x x 162832009 9106-0004-015F x x x x x x x x x x 162485008 9106-0005-01 OF x x x x x x x x x x 162485011 9106-0005-014F x x x x _ _ x x x x x x 162850014 9106-0006-005F x x x x x x x x x x 163741005 9106-0008-006F x x x x x x x x x x 163741009 9106-0008-008F x x x x x x x x x x 164542008 9106-0009-002F x x x x x x x x x x 164542003 9106-0009-017F x x x x x x x x x x 163105009 9106-0010-001F x x x x x x x _ _x x x 163105016 9106-0010-012F x x x x x x x x x-..--. ---
Chain of Custody and Supporting Documentation Page 6 of 105 Health Physics Procedure ev S:q 0 L(GPP-GGGR-RS 104-003-Attachment B-CY-001 Major 0 tJ.Connecticut Yankee Atomic Power Company Chain of Custody Form No. 2006-00371 362 Injun Hollow Road, East Hampton, CT 06424 860-267-2556
_____________________
Project Name: Haddam Neck Decommissioning Analyses Requested Lab Use Only Contact Name & Phone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 843 556 8171. Attn. Cheryl Jones 5 M .Priority:
Z 30 D. [] 14 D. [] 7 D. Container Media Type &Type C PL Sample Designation Date Time Code Code Code Comment, Preservation Lab Sample ID 9106-0002-OOIF 5/17/06 10:42 SE C BP xx Transferred from COC 2006-003 57 9106-0002-002F 5/18/06 09:43 SE C BP -x -Transferred from CCC 2006-003 61 9106-0002-003F 5/18/06 10:14 SE C BP X X Transferred from COC 2006-00361 91i06-0002-004F 5/18/06 10:39 SE C BP X X Transferred from COC 2006-00361 9106-0002-005F 5/18/06 12:49 SE C BP X X Transferred from COC 2006-00364 9106-0002-006F 5/18/06 13:14 SE C BP X X _ _Transferred fromn 2006-00364 9106-0002-006FS 5/18/06 13:14 SE C BP X X -Transferred from COC 2006-00364 9106-0002-007F 5/18/06 13:37 SE C BP X X Transferred from COC 2006-00364 9106-0002-008F 5/18/06 14:04 SE C BP .x Transferred from COC 2006-00364 NOTES: PO #: 002332 MSR #: 06- SSWP# NA [ LTP QA [] Radwaste QA E Non QA Samples Shipped Via: Internal 9 Fed Ex Container C UPS Temp.: Deg. C EHand Custody Sealed?I e uDate/Time
- 2) 1.ived By Date/Time Custody Seal 1ý"gelintuiiQ BýJ Date/Time
- 4) Received By Date/Time YO_ _ No_ _Bill of Lading 5) Relinquished By Date/Time
- 6) Received By Date/Time 79)" 'YM{5' 57/C)
Health Physics Procedure GPP-GGGR-R5104-003 -Attachment B-CY-00 I Maj or Heallt Phsc Prcdr GP-GG-510-0 -tahmnI-C-0I ao It'CD 001 Chain of Custody Form No. 2006-00372 Connecticut Yankee Atomic Power Company 362 Injun Hollow Road, East Hampton, CT 06424 Project Name: -ddam Neck Decommissioning Analyses Requested
_ Lab Use Only Contact Name & Phone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 843 556 8171. Attn. Cheryl Jones n I L Priority:
Z 30 D. [] 14 D.E] 7 D. Container Sample Size-Media Type &Type Sample Designation Date Time Code Code Code Comment, Preservation Lab Sample ID 9106-0002-009F 5/18/06 14:28 SE C BP x Transferred from COC 2006-00364 9106-0002-01OF 5/18/06 14:50 SE C BP X x Transferred from COC 2006-00364 9106-0002-011F 5/19/06 08:10 SE C BP x x Transferred from COC 2006-00365 9106-0002-012F 5/19/06 08:31 SE C BP X x Transferred from COC 2006-00365 9106-0002-013F 5/19/06 09:00 SE C BP x x Transferred from COC 2006-00365 9106-0002-014F 5/19/06 09:58 SE C BP X x Transferred from COC 2006-00365 9106-0002-014FS 5/19/06 09:58 SE C BP X X Transferred from COC 2006-00365 9106-0002-015F 5/19/06 10:29 SE C BP x x Transferred from COC 2006-00365 9106-0002-016F 5/19/06 13:19 SE C BP I 3 Transferrd from CxC 2006-00365 NOTES: PO #: 002332 MSR #: 06- SSWP# NA g LTP QA E] Radwaste QA E] Non QA Samples Shipped Via: Internal 09'5 7 Fed Ex Container UPS Temp.: Deg. C E) Hand Custody Sealed?1 ,Relin! ihe'wi Date/Time
- 2) Reýived By Data/Time Custody Seal 4 ~ f []..Q /~ Other intact?3)% Kelinquished By Date/Time
- 4) Received By Date/Time YO NO Bill of Lading #5) Relinquished By Date/Time
- 6) Received By Date/Time q9"'V 4 7t?
Connecticut Yankee Statement of Work for Analytical Lab Services ..CY-ISC-SOW-001 Figure 1. Sample Check-in List Date/Time Received:
to 0: SDG#: ._ (o Work Order Number: '2 O ".Shipping Cdatainer IDý207 Lf! 5'5 7/0 Chain of Custody# O 4, o- 9.1. Custody Seals oti shipping container intact?. Yes No []2. Custody Seals dated and signed? Yes No[.3. Chain-of-Custody record present? Yes j/\No[ " 4. Cooler temperature
- 5. Vermiculite/packing materials is: Wet [ ] Dry ].,Number of samples in shipping container:
t 7. Sample holding times exceeded?
Yes No 8. Sampl&s have:-tape -hazard labels-K custody seals -appropriate sample labels 9. Samples are:.*)Cjin good condition -leaking-broken .-'" "have air bubbles ICA-10.11.Were any anomalies identified in sample receipt?.Description of anomalies (include sample numbers): Yes'[ ] NoXI Saample. Custodian/Laboratory:
Dam.. Date ..-D Telephoned to: On By Page 9 of 105 Connecticut Yankee Statement of Work for Analytical Lab Services rv'..j-cy-ISC-SOW-001.CY-lsC-sow-ool Figure 1. Sample Check-in List DateiTime Receivedý " SDG#: A LO G 0 SýWork Order Number: Io.r"" W " Shipping Cdntainer IDn:ý " LN 5 -59T Chain of Custody'#
-O3'_I. Custody Seals on" shipping container intact? -Yes No [ ]2. Custody Seals dated and signed? Yes No []3. ..Yes No [..3. Chain-of-Custody record present? Yes No[.4. Cooler temperature OP .-5. Vermiculite/packing materials is: Wet [ ] Dry [, ]6.: Number of samples in shipping container:.
__" 7. Sample holding times exceeded?
Yes No 8. Sl ta hazard labels-custody seals -appropriate sample labels 9, Samples are:'good condition " leaking-broken i--_._have air bubbles 10. Were any anomalies identified in sample receipt? Yes [ NoO 11. Description of anomalies (include sample numbers): Sample Custodian/Laboratory:-./:,j
ý i4 Date:_ ___________
Telephoned to: On. By.~jy.Page 10 of105
~SAMPLE RECEIPT & REVIEW F 0 §~PM use only ORM I Date Reevd L PM (A) Review (ensure Ron-C011ontimifg items are resolved prior to signing);eReceived By:0-Sample Receipt Criteria Comments/Qualifiers (Required for Non-Conforming Items)Shipping containers received intact Circle Applicable:
seals broken damaged comainr conainer other (descibe)1 and sealed? .n Samples requiring cold Circk Coolant # ice bags blue ice dry ice none oiler desribe)2 preservation within (4 +1- 2 C)?Record preservation inethod. /Chain of custody documents included with shipment?
,1___Sample containers intact and Cirkle Applicable-,s broken damaged container leaking container other (descrbie) sealed? ,_s Samples requiring chemical if l iD's. containers affected and observed pH: 5preservation at proper pH?- -6 VOA vials free of headspace Sample ID's and containers affected: (defined as < 6mm bubble)? ___Are Encore containers present?7 (If yes, immediately deliver to VOA laboratory)
Samples received wi 'holding Id's and ei affected: time? .__,,_9 Sample ID's COC match ID's Sample ID's ando affected:-on bottles?.,_
Date & me on COC match date Samp1 ID's affected: 10-& ti on bottles?Nu ber of containers received Sample ID's affected: match number indicated on COC?COC form is properly signed in 12 relinquished/received sections?
Co0__&_ _ __0_0_(e -_, 14 Air Bill ,Tracking
- s, &Additional Comments i , RSORADReceipt#
____________
Suspected Hazard Information
- If > x2 area background is observed on samples identified as "non-Z to regulated/non-radioactive", contact the Radiation Safety group for further Z investigation.
A Radiological Classification?
Maximum Counts Observed*:
- p-1 B PCB Regulated?
_,/_ Comments: Shipped as DOI" Hazardous C Material?
If yes, contact Waste Hazard Class Shipped: Manager or ESH Manager. I/ N#: PM (or PMA) review of Hazard class tication-:
Initials Date: -(Page 11 of 105
- SAMPLE RECEIPT & REVIEW FORM 0 Client:(o, f yr" l SDIAlRCOCIWork Order: / .. ..Date Received:
"' CA, o 0( 0PM(A) Review {ere non-onror g I are resolved prior to sipi.,g): Received BY: Sample Receipt Criteria i Comments/Quialifiers equired for Non-Conforming Items)Shipping containers received intact Circle Applicable:
seals broke damaged container leaking container odier (describe) and sealed? .....__Samples requiring cold Circle Coolant # i76ags blue ice dry ice none other describe)2[preservation within (4 +/- 2 Q)?Reco~rd preservation method. /. ...3 Chain of custody documents/
included with shipment?
- I..Sample containers intact and Cie pplicable:
seals broken damaged container leaking container other (describe) 4sealed? 7 4/......5 Samples requiring chemical ample ID's. containers affected and observed pH: preservation at proper pH? ._ ,_.VOA vials free of headspace Sanple ID's and containers affected: (defined as < 6mm bubble)? _ _.... .Are Encore containers present?7 (If yes, immediately deliver to VOA laborato Samples received within holdin Id's and Tests affected: time? _ _._,__9 Sample ID's on COC ma c ID's Sample ID's and containers affected: on bottles? r 10 Date & time on COC tch date Sample ID's affected:& time on bottles?Number of containe received Sample ID's affected: match number idic ted on COC?COC form is pro,-y signed in relinquished/recived sections?
Coc- ZOO(,, --9(_ .Air Bill Tracking #'s, &Additional Comments'a V 'a RSO RAD Receipt#S e Hzr If > x2 area background is observed on samples identified as "non-Suspected Hazard Information 'regulated/non-radioactive", contact the Radiation Safety group for furtherinvestigation.
A adiological lassi fcation. Maximum Counts Observed-:
- B Regulated?
/ Comments: hippe as 00771 azardous c Material?
If yes, contact Waste Hazard Class Shipped: Manager or ESH Manager. UN#: PM (or PMA) review of Hazard classification:
ntials Date: Pg12f15 Page 12 of 105 Health Physics Procedure GPP-GGGR-R5104-003-Attachment B-CY-00 1 Major Chain of Custody Form N.20-01 Connecticut Yankee Atomic Power Company No. 2006-00312362 Injun Hollow Road, East Hampton, CT 06424__.......___abUse__l__.""__./" ', "35 ./.-W860-267-2536
_____________________________________________
Project Name: Haddam Neck Decommissioning Analyses Requested L. ..ab. Use Only Contact Name & Phone: 'Com.nnts.
Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC, 29407 t 9.843 556 8171. Attn. Cheryl Jones V Cn Priority:
Z 30 D.[] 14 D. [17 D. Container Sample Size-Media Type &Type 'Sample Designation Date Time Code Code Code Comment, Preservation Lab Sam.plei IP.9106-0003-OO1F 4/24/06 14:13 SE C 13P X Transferred from COC2006-00221 I" 9106-0003-002F 4/24/06 14:39 SE C BP X Transferred from COC2006-00221 6'9106-0003-003F 4/24/06 15:01 SE C 1P X Transferred from CoC2006-00221 9106-0003-004F 4/25/06 08:41 SE C 13P X Transferred from COC2006-00223 9106-0003-004FS 4/25/06 08:41 SE C l3P x Transferred from COC2006-00223 9106-0003-005F 4/25/06 09:21 SE C BP X fTransferred from COC2006-00223 9106-0003-006F 4/25/06 09:46 SE C BP X Transferred from COC2006-00223 9106-0003-007F 4/25/06 10:28 SE C BP x Transferred from COC2006-00223 9106-0003-008F 4/25/06 11:15 SE C BP X Transferred from COC2006-00223 NOTES: PO : 002332 MSR #- 0 6-°O SSWP# NA [ LTP QA (I Radwaste QA l Non QA Samples Shipped Via: 4,tern'1 Co6fi"er Combined samples 9106-0003-003F taken on 4/25/06 @08:19 and 9106-0003-003FB taken on 4/25106@ 08:19 in order to have sufficient sample for ounting. Fed Ex-' Deg,. C'U PS .. : ,...- .....Hand ." d' tdSealed.,'..'
- 1) Relinquished By Date/Time
- 2) iee~ved By 1 Date Time :CUStdy .Seal Intat?3) Relinquished By Date/Time
- 4) Received By Dale/Time 110). Other :1 .-Bill of Lading # ' .5) Relinquished By Date/Time
- 6) Received By Date/Time
.9-920- '502o 024 ."
Health Pbysics Procedure GPP-GGGR-R5104-003 -Attachment B-CY-001 Major Health Physics Procedure GPP-GGGR-R5 104-003 -Attachment B-CY-00 1 Major CD Ito 00 01L OR-Chain of Custody FormNo206031 Connecticut Yankee Atomic Power CompanyC No. 2006-00313 362 Injun Hollow Road, East Hampton, CT 06424 / .2iz 860-267-2556
-,35,'-. / 04-." 'Z5 o/Project Name: Haddam Neck Decommissioning Analyses Requested
.-Contact Name & Phone:
<,.-Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 J 843 556 8171. Attn. Cheryl Jones Priority:
Z 30 D. El 14 D. D 7 D. Container Sample Size-Media Type &Type .-.Sample Designation Date Time Code Code Code Comment, Preservation L41 S 9106-0003-009F 4/25/06 13:00 SE C BP x Transferred from COC 2006-00236 9106-0003-01OF 4/25/06 13:23 SE C BP x Transferredfrom COC2006-00236
-.-9106-0003-01OFS 4/25/06 13:23 SE C BP X Transferred from COC 2006-00236 9106-0003-012F 4/25/06 15:12 SE C BP X Transferred from COC 2006-00236 9106-0003-013F 4/25/06 14:21 SE C BP x Transferred from COC 2006-00236 9106-0003-014F 4/25/06 14:48 SE C BP x Transferred from COC 2006-00236 9106-0003-015F 4/26/06 08:16 SE C BP x Transferred from COC 2006-00237 " .; 9106-0003-016F 4/26/06 09:41 SE C BP X Transferred from COC 2006-00237 I 9106-0003-017F 4/26/06 09:18 SE C BP X Transferred from CVU 2006-00237 to oil-9106-0003-018F 4/26/06 08:59 SE IC I BP xI Transferred from COC 2006-00237
~-4-4-4-4~-~
-4 ~.. ... F ... .i 7 .. ..NOTES: PO #: 002332 MSR#: 0 6-0 SSWP#NA Z LTPQA [] Radwaste.QA
[] Non QA I) Relinquished By Date/Time
- 2) eceived By Date/Time/Tieo 4) Re y eTi 3) Relinquished By Date/Time
- 4) Received By 'Date/Time Samples Shipped Via:[ Fed Ex El uPs 0- Hand[] Other Bill of Lading #7 ZO-012 /7-S'e' 9"Intact?Y'Teni N Connecticut Yankee Statement of Work for Analytical Lab Services .CY-ISC-SOW-OO
-. Figure 1. Sample Check-in List Date/Time Received:
.) , .0 " SDG#: -4A.-&O )- &(J'-Work Order Number: I (Z- 3 5 Shipping Ccntaifer ID: 1UP6 55c1L0 O4 1 Chainof CustodY# AQCQ(o" 605 14. , 0,,. q o03 1.(.1. Custody Seals od shipping container intact?...
Yes. ] No I 2. Custody Seals dated and signed? Yes [ ] No 3. Chain-of-Custody record present? Yesp No [ ]4. Cooler temperature ) .5. Vermiculite/packing materials is: Wet [] Dry _I] "Ft-, 6. Number of samples in shipping container:
[7. Sample holding times exceeded?
Yes [ No-tape -----hazard labels_ZcUstody seals .appropriate sample labels 9. Samples are-good condition 2 lJeaking-broken ___have air bubbles 10. Were any anomalies identified in sample receipt? Yes [ ] No Qc2 11.. Description of anomalies (include sample numbers): Sample Custodian/Laboratory: (Ii)- (4 Crv; t CC- DatewL" Telephoned to: _On By Page 15 of 105 SAMLERECEIPT
& REVIEW FORM 54rRt5%' PM we only! '2 3 ICient: 4 SDG/ARCOC/Work Order: Date Received:
re? 5/1516 itPM(A) Review (ensure non-cont g iems are resolved prior to signing): Received By: ( i.v -c....Sample Receipt Criteria Z Comments/Qualifiers (Required for Non-Conforming Items)I Shipping containers received intact Circl Applicable:
seals broken damaged container leaking container otlier (describe) and sealed? ___ __ __Coolant_#_icebagsblueicedryice Samples requiring cold Circl Coolnt I cc bags blue c dy ice noe 2 preservation within (4 +/- 2 C)? de" Record preservation method. Pen"___Chain of custody documents included with shipment?
,_, _, Sample containers intact and Circle Applicable:
stab broken damaged container leaking conainer other (describe) sealed?Samples requiring chemical Sample ID's. containers affected and observed pH: preservation at proper pH? .........
..VOA vials free of headspace Sample ID's and containers affected: (defined as < 6mm bubble)?Are Encore containers present?7 (If yes, immediately deliver to VOA laborator_)
Samples received within holding Id's and tests affected.time?Sample ID's on COC match ID's Sample ID's and containers affected--
on bottles?Date & time on COC match date ample I's affected:& time on bottles?Number of containers received Sampl ID's affected: match number indicated on COC__?_V_1 COC form is properly signed in relinquished/received sections?Air Bill ,Tracking
- 's, & F9 Z d .'0 1 Additional Comments t b 0"D V -4 lRSO RAD Receipt #Suspected Hazard Information
_ *If> x2 area background is observed on samples identified as "wn-Z. &I regulated/non-radioactive", contact the Radiation Safety group for further_ __ investigation.
Radiological Classification?
Maximum Counts Observed*:
Shipped as DUT Haaous C Material?
If yes, contact Waste #Hazard Class Shipped: Manager or ESH Manager. AN1 PM (or PMA) review of Hazard classification:
Initials Date: 77t'o[Page 16 of 105 61 F' #I I ,
GPP-GGGR-R5 104-003 -Attachment B-CY-00 1 Major Health Physics Procedure Connecticut Yankee Atomic Power Company 362 Injun Hollow Road, East Hampton, CT 06424 I-Project Name: Haddamn Neck DecommissiC
-22ontact Name & Phone: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 843 556 8171. Attn. Cheryl Jones Priority:
0 30 D. [] 14 D. L 7 D.Samples Shipped Via:[ Fed Ex ri ups El Hand El Other Bill of Lading #
Health Physs Pro6edure GPP-GGGR-R5104-003-Attachment B-CY-00 1 Major' t Yankee Atomic Power Company": Injun Hollow Road, East Hampton, CT 06424 I Neck Contact Name & Phone: Jack McCarthy" 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 843 556 8171. Attn. Cheryl Jones Priority:
M 30 D.E] 14 D. E] 7 D.Samples Shipped Via:[ Fed Ex E ups[] Hand E1 Other Bill of Lading #
Connecticut Yankee Statement of Work for Analytical Lab Services CY-ISC-sOw-001 Figure 1. Sample Check-in List Datc/Timc Reccived: -/d .G. .., SDG#: 44,5 R:' 4-0 -049 Work Order Number: -.Shipping Container ID: 7"14 5 Z- i Chain of Custody #I. Custody Seals on shipping container intact?2. Custody Seals dated and signed?3. Chain-of-Custody record present?4. Cooler temperature
- 5. Vermiculite/packing materials is: 6. Number of samples in shipping container:
- 7. Sample holding times exceeded?Li-CY-ISC-SOW-001 ,x7 o .ig- 6 oss -Yes No [Yes No []Yes No [J Wet Y Dry [ ]Yes [] No 8. Samples have:_ tape hazard labels._,rcustody seals __ appropriate sample labels 9. Samples are: in good condition
_ leaking broken have air bubbles 10. Were any anomalies identified in sample receipt? Yes No []Il. Description of anomalies (include sample numbers): Sample Custodian/Laborato ry: Telephoned to: On Date: 9'.By By___________
Paqe 45 of 56 Page 19 of 105
.Connecticut Yankee Statement of Work for Analytical Lab Services CY-Isc-SOW-O01 Figure 1. Sample Check-in List.Date/Time Received:
."/i .1 a " "* SDG#: J-- -Work Order Number:-_
I___ ___-._ _ __ __ __Shipping Cdhtainer ID- Chain ofCustody#
_(_._ _ -_0_ 334!. 1. Custody Seals. odnshipping container intact? Yes [Y No 2. Custody Seals dated and signed? Yes [] .No 3. Chain-of-Custody record present? Yes ' No [1 4. Cooler temperature r*'5. .Vermiculite/packing materials is: Wet [fPlDiy t\ " 6- Number ofsamples in shipping contain'er
- 7. Sample holding times exceeded?8.. Samples have-:.Weretany amedtdi hazard labels..esciptoy seaalise appropriate Sample labels 9. S am ples are:anL: t. -..r .--.__7_~~In good conition.,,_ .-brkem :. " " have air bubbles 1. ""Tlephrned any t o:_____ ___________n_
__r e c ei p t .? Y e s N.eci ti on .. a om lies...' ..Page 20 of 105 ."" .- "
SAMPLE RECEIPT & REVIEW FORM CONTINUATION FORM-Fed F2. oý.-_ -.) ...-. , , --(aI ____ -_______ I ( ") S, itv-l ~ql q 3 5 cmls _,-I -o 2,('ao .i-,-u-s_ 5 cL 'QOOZ SAs o n I Page 21 of 105 SAMPLE RECEIPT & REVIEW FORM a, PM use only Client: 7rl" SDGIARCOC/Work Order: /: ' 3.-Date Received: .PM(A) Review (ensure non-conforming items are resolved prior to signing&:[Received By: 1'./h .Sample Receipt Criteria 4 CommentsfQualifiers (Required for Non-Conforming Items)1 Shipping containers received intact Circle Applicable:
seals broken damaged container leaking container other (describe) and sealed? x Samples requiring cold Circle Coolant # ire bags blue ice dry ice none o&ter describe)2 preservation within (4 +1- 2 C)?Record preservation method. _ _. ....3 Chain of custody documents included w ith shipm ent? _ _seals_ broke _ _ _ _ _ _ _ _ __c_ _ _ _ _ _ _ _ _ _ _ _ _ _4 Sample containers intact and Ciwle Applicable:
seals broken damaged container It oter (describe) sealed? At .<A 910o(- 0oooi- oi0 E 5 Samples requiring chemical Sample UD's. containes affected and observed pH: preservation at proper pH?,6 JVOA vials free of headspace Sample ID's and conltainers affected: (defined as < 6mm bubble)?_
_ _ _ _ _ _ _ _ _ _Are Encore containers present?7 (If yes, immediately deliver to VOA laboratory)
Samples received within holding 1d's and tests affected: time?9 Sample ID's on COC match ID's Smpl I's a coninr affect:" on bottles?Date & time on COC match date S ID's affected: 0& time on bottles? ,____Number of containers received 1iD's afecWd: match number indicated on COC?12 COC form is properly signed in relinquished/received sections?
X _eac. Ao4, Air Bill ,Tracking F's, &Additional Comments Suspected~
Hmr womton 9. *If > x2 are background is observed on samtples identified as -zr regulatetnon-radioactiveo, contact the Radiation Safety group forfurther
_______ investigation.
A Raidio~lognkal CLaissilic.Aton?
Mxmum Counts Observed*7 I as'. Ha-arous C Material?
If yes, contact Waste " " /hppd Manager or ESH Manager. UN#: P/0 t-V9 "'wof Hazard classification:
Initials 4_ Date: // (UI 0 SAMPLE RECEIPT & REVIEW FORM 0 PM use only Cfient- j,'dV o t, 9SDG/ARCOC/Work Order: /LZM-, Date Receied: ~~ PM(A) Review ¶ esum ma oufonn ft am resolved prior to signing): ReceivedBy:
(2 t pe"j c_____Sample Receipt Criteria Comments/Quali'ers (Required for Non-Conforming Items)Shipping containers received intact -ircle Applicable:
seals broken damaged comainer leaking coalmoer oWier (describe) and sealed? .... ._ _ _,_, Samples requiring cold Circle Coolant # ice bags blue ice dry ice aojar descrile)2 preservation within (4 +/- 2 C)?' Record preservation method. tv 3 included shipment?
... ..... )Chain Of Custody documents .U~ S. bX 0 N q-)U 4 includedwithishieentpV de : sn ~ damaged container leaking coaitaaer ,odier(decne Sample containers intact and 4-als bjen ine ig c s Samples requiring chemical mple IDas. conainers affected and observed pH: preservation at proper pH? .......VOA vials free of headspace le ID's an cairs .ffecm:-(defined as < 6mm bubble)? ....Are Encore containers present?7 (If yes, immediately deliver to VOA laboratory)
_8 Samples received within holding Id's and ests affected: time?Sample ID's on COC match ID's Sample ID's am cnftainms affected: on bottles?Date & time on COC match date Sample ID's affecd:"'& time on bottles?NNumber of containers received Sample ID's affected: match number indicated on COC?COC form is properly signed in " CtGS CLvy., vLi :V \Ct relinquished/received sections?14 Air Bill ,Tracking
- 's, & i u---. ..Additional Commaents v T R50 RAD ReceiptI i a q *"f > x2 area background is observed on samples identified as .non-Suspected Hazard Information Q 3: ,a 'L regulated/non-radioactive, contact the Radiation Safety group for further__ _ _ _ _ _ _ __ _ _ _ _ _ _ investigation.
A Radiological Classification?
Maximum Counts Observed*:
BICB Regulated?
I iComan.: iShipped as MIT Hazardous Material?
If yes, contact Waste Hazard Class Shipped: Manager or ESH Manager. UNI: PM (or PMA) review of Hazard classification:
Initials _ Date: _ Y Health Physics Procedure GPP-GGGR-R5104-003 -Attachment B-CY-001 Major Healh Pysis Pocedre PP-GGRR5 14-03 -ttahmen B-Y-III ajo Connecticut Yankee Atomic Power Company 362 Injun Hollow Road, East Hampton, CT 06424 860-267-2556 Project Name: Haddam Neck Decommissic Contact Name & Phone: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 843 556 8171. Attn. Cheryl Jones Priority:030 D. [] 14 D. M7D.Samples Shipped Via: S Fed Ex El ups M Hand nI Other Bill of Lading # [7qc 9/9
- Connecticut Yankee Statement of Work for Analytical Lab Services Figure 1. Sample Check-in List Date/Time Received-h SD -G#: kkS -- -&Work Order Number: \ L %"/Shipping Cdhtainer ID -'A" C .' 5'J q Chain of Custody#.1. Custody Seals oii shipping container intact?..2. Custody Seals dated and signed?3. Chain-of-Custody record present?° 4. Coolerteprature I ' ( 1 '1 5. Vermiculite/packing materials is: 6. Number of samples in shipping container:
- 7. Sample holding times exceeded?-CY-ISC-SOW-001-Yes Yes 'KNo H.Yes L4'No I I Wet [,'Dry W i, Yes[] No 10. Were any anomalies identified insample receipt? " "Yes [] No 11. .Description of anomalies (include sample numbers): Jude sapl numbers Page 25 of 105.,r SAMPLE RECEIPT & REVIEW FORM PM use only CSDG/ARCOCIWork Order. /G 2-(t85 Date Received:
PM(A) Review (ensure non-coformlg items are resolved prior to signing): Received B Vi Sample Receipt Criteria Z Comments/Qualifiers (Required for Non-Conforming Items)N1, Shipping containers received intact Circle Applicable:
seals broken damaged container leaking container other (describe) al~sealed?
..Samp requiring cold Circle Coolant # ice bags blue ice dry ice none other describe)2 preservati within (4 +/- 2 C)?Record preserv *on method.3IChain of custody d nts included with shipment?4 Sample containers intact and Circle Applicable:
seals broken damaged container leaking comainer other (describe) sealed?Samples requiring chemical Sample containes affected and observed pH: preservation at proper pH? , _ __ ___IDsanticontainersaffected:
- 6. VOA vials free of headspace
' aN c S(defined as < 6mm bubble)?jAre Encore containers present?"6 7 (If yes, immediately deliver to VOA laboratory) 8 Samples received within holding id's and es afeed time?9 Sample ID's on COC match ID's Sample ID's and containers affected: on bottles?Date & time on COC match date Sample ID's affected: 101& time on bottles?n1lNumber of containers received Sample ID's affected: match number indicated on COC?12 COC form is properly signed in relinquished/received sections?1 4 Air Bill ,Tracking
- 's, & fd.( "qic ' [ 9 5- 4,-- /7 --Additional Comments 42t493 w-c ,([ .-, T RSO RAD Receipt #>S dHaar Information lIf > x2 area background is observed on samples identified as *non-Suspected Hzazard Io a 0 regulated/non-radioactive".
contact the Radiation Safety group for further I investigation.
A Radiological Classificatimo
-Maximum Counts Observed*:
IB P C B Rte g u la te d ? _ _ Cor s'hipped as DUt Hazardous C Material?
If yes, contact Waste Hazard Class Shipped: Manager or ESH Manager. UN#: PM (or PMA) review of Hazard classitication.
Initials Date: rav /-Doi.I..V/
Health Physics Procedure GPP-GGGR-R5104-003-Attachment B-CY-001 Major Connecticut Yankee Atomic Power Company 362 Injun Hollow Road, East Hampton, CT 06424.860-267-2556 iroject Name: Haddam Neck Decommissioning
ýContact Name & Phone: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 843 556 8171. Attn. Cheryl Jones Priority:
Z 30 D. [] 14 D. M 7 D.Samples Shipped Via:[ Fed Ex LI uPS El Hand El Other Bill of Lading #* ?.92 fo- .1el-Connecticut Yankee Statement of Work for Analytical Lab Services .CY-ISC-SOW-001 Figure 1. Sample Check-in List.Date/Time Received':
.--_(I SDG#: AA Work Order Number.. _"_____________l._" Shipping CdhtainerlID--t, ~Q~CCt5X Chain of Custqdy# S et ( riý- sk -I. Custody Seals. owishipping container intact?... -Yes JNof4)2. Custody Seals dated and signed? Yes [I No I3. Chin-of-Custody record prýsent? .Yes [1.4. Cooler temperature
= o1-.5. Vermiculite/packing materials is: Wet p) Dry f], 6: Number of samples in shipping container:. ) (7. Sample holding times cxceded? Yes [] No.Samples h.ve.'-hazard label-custody seals -appropriate sample labels 9. Samples are..A" good condition -leaking Sbroken * + have air bubbles 10. Were any anomalies identified in sample receipt? Yes []No 11 Description of anomalies (incluesml ubr:______________
Sample CustOdianAa rtory f, 4 -Dae3 ~ J I l" ph' n " to: '-' " ~Date- Z5 T elep h o n ed to : ... :' -." ..- --Page 28 of 105
-NG/4;ýSAMPLE RECEIPT & REVIEW FORM 4 ofoon.,yy Client. SDG/ARCOC/Work Order: ((,Zn2 , &(,Z7e5.Date Received:
J-/ _PM(A) Review (ensure nn,-conforin u m reoved prior to uigming): Received By: C iQ.ev I' cm ,j, I,.,, M, I_,,___ _ -_,_.. ..Sample Receipt Criteria 4 Z Z Comments/Qualiirns (Required for Non-Conforming items)1 Shipping containers received intact Applkable:
scab broken damaged omaine, leaking contae otiler (desabe)and sealed?Samples requiring cold Circle Coolait # ie bags bte- ice dry ic e aej) oier descrie)2 preservation within (4 +1- 2 C)?Record preservation method. .0 C_>Chain of custody documents
/ C£.S oax -o w *included with shipment?
I/ I eeSample containers intact and p/C th damaged coai/er leakit, co-taiq nr oi (dicnribe)
S Samples requiring chemical n/ yile iD's. coimn,, affected and oberved pH: a preservation at proper pH? ....6 VOA vials free of headspace Sample ID's and coainers affected: (defined as < 6mm bubble)? ......Are Encore containers present?7 (If yes, immediately deliver to VOA laboratory) 8 Samples received within holding vd'3 and tests affected: lime?4 9 Sample ID's on COC match ID's S Sample ID's and couainme affected: on bottles?10 Date & time on COC match date Samnple ID's allecto:& time on bottles?Number of containers received Sml w's affi : match number indicated on COC?COC form is properly signedin in Ct ,s C,.L-12 relinquished/received sections?
u Air Bill ,Tracking
- 's, & , ( Additional Comments I V RSOR AD Receipt SS *If > x2 area background is observed on samples idenified as *non-Suspected HaZard Information -g.~regulatd/non-radioactive*, contact the Radiation Safety gru for fi rte ad_19 investigation.
A Radiological Classification?
-Maximum Counts Observede:
B CB Regulated?
Comments: Shipped as IX r Hazardous C Material?
Ifyes, contact Waste , Hazard Class Shipped: Manager or ESH Manager. UN#: PM (or PMA) review of Hazard classification:
Pý, IG Q,, V3 I'Zin"ntal ae 1'7 r,ý %J Y ,-ii,,i Ilh 5 SAMPLE RECEIPT & REVIEW FORM CONTINUATION FORM.'IAAIkA,7 943 2, 16 Z 50-~ 8 6q0 -op nin (C)(4hN 5 ccide-v h ad nkt Page 30 of 105.1 ;," in,'
Health Physics Procedure GPP-GGGR-R5104-003 -Attachment B-CY-00 I Major-c 0 0 Connecticut Yankee Atomic Power Company Chain of Custody Form No. 2006-00367 362 Injun Hollow Road, East Hampton, CT 06424 860-267-2556
.. /[,3-7 Project Name: Haddam Neck Decommissioning
-.-.Analyses Requested Lab Use Only Contact Name & Phone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 843 5 56 817 1. Attn. Cheryl Jones r .Priority:
Z 30 D. [] 14 D. [] 7 D. Container Sample Size-Dae T Media Type &Type on Sample Designation Date Time Code Code Code Comment Preservation Lab Sample ID 9106-0008-OO1F 5/05/06 11:13 SE C BP X x x Transferred from COC # 2006-00324 9106-0008-003F 5/5/06 13:35 SE C BP x x x Transferred from COC # 2006-00325 9106-0008-004F 5/5/06 13:51 SE C BP x x x Transferred from COC # 2006-00325 9106-0008-005F 5/5/06 14:17 SE C BP X x x Transferred from COC # 2006-00325 9106-0008-006F 5/5/06 14:36 SE C BP x x X Transferred from COC # 2006-00325 9106-0008-006FS 5/5/06 14:36 SE C BP X x x Transferred from COC # 2006-00325 9106-000.-007F 5/5/06 15:03 SE C BP X TransferredfromCOC#2006-00325 9106-0008-002F 5/5/06 13:10 SE C BP X X X Transferred from COC # 2006-00325 9106-0608-002F_______
1 5116 1:01S P xx xTanfre rmCC#20-02 NOTES: PO #: 002332 MSR#: 06-0710 SSWP#NA SLTP QA E Radwaste QA E] Non QA 1 , I i 3) ik mnquished By \J Date/Time~-Z6~12'r J~Tme~Samples Shipped Via: Z Fed Ex FEUPS[ Hand El Other Bill of Lading #R 215 57 /z/ 6 lC2_Custody Seal Intact?Internal Container Temp.: __ Deg. C Custody Sealed?YO NO , .- -P -!Date/Time I 4)
" D hate/Time YO NO Health Physics Procedure GPP-GGGR-R5104-003-Attachment B-CY-001 Major~Chain of Custody Form~No. 2006-00366 C Connecticut Yankee Atomic Power Company W 362 Injun Hollow Road, East Hampton, CT 06424860-267-2556 163-7 L__IV.Project Name: Haddam Neck Decommissioning Analyses Requested Lab Use Only Contact Name & hone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories o m 2040 Savage Road. Charleston SC. 29407 843 556 817 1. Attn. Cheryl Jones z Priority:
Z 30 D. [] 14 D. ] 7 D. Container Sample Size-Media Type &Type Sample Designation Date Time Code Code Code Comment, Preservation Lab Sample ID (p 9106-0008-008F.
5/08/06 08:01 SE C BP X x x ___ __ Transferred from COC # 2006-00327 010 9106-0008-009F 5/08/06 08:32 SE C BP X X X Transferred from COC # 2006-00327 D11 9106-0008-01OF 5/08/06 09:09 SE C BP x x x Transferred from COC # 2006-00327 9106-0008-010FS 5/08/06 09:09 SE C BP x x X Transferred from COC # 2006-00327)oi 9106-0008-01OF 5/08/06 09:30 SE C BP X X X Transferred from COC #2006-00327)Itf~ 9106-0008-012lF 5/08/06 09:530 SE C B3P x x Transferred from COC # 2006-00327)I ý 9106-0008-012F 5/08/06 09:53 ...SE C BP X Transfered from COC N 2006-00327
)1t 9106-0008-013F 5/08/06 10:16 SE C BP X X X Transferred from COC #2006-00327 05 9106-0008-014F 5/08/06 10:47 SE C BP X X X Transferred from COC # 2006-00327 NOTES: PO #: 002332 MSR #: 06- SSWP#NA 0 LTP QA[I Radwaste QA[I Non QA Samples Shipped Via: M Fed Ex mi UPs E Hand E Other Bill of Lading #Internal Container Temp.: -4 1 Deg. C Custody Sealed?Y[0 N)'Custody Seal Intact?Y 9 NO 1) Relinquished By Date/Time
- 2) Received By Date/Time 3) Relinquished By Date/Time
- 4) Received By Date/Time Connecticut Yankee "(0371 4" /Statement of Work for Analytical Lab Services -CY-ISC-SOW-001 Figure 1. Sample Check-in List.Date/Time Received:
]Ii..t .,.SDG#: Work Order Number:__Shipping Cchitainer ID:. ." ' I Chain of Custody# O00 -0C)3 *0q 1. Custody Seals. or! shipping container intact?.. -Yes i'TRo []2. Custody Seals dated and signed? Yes[ ]No [I 3. Chain-of-Custoly record present? Yes [_1o [4 ]4. Cooler .temperature
- 5. Vermiculite/packing materials is: Wet [ Dry -, ] IlVAf 6"' Number of samples in shipping container:
"__Sample holding times exceeded?
Yes [ ] No.8. Samples hav6:*hazard labels.Z.-custody seals /appropriate sample labels 9. Samples are: S ..~ good condition
"_leaking broken -have air bubbles 10. Were any anomalies identified in sample receipt? Yes [ ] No 1...Description of anomalies (include sample numbers):* ..: -, .....Telephoned to:__________________By" On______ __'Page 33 Of 105 0 SAMPLE RECEIPT & REVIEW FORM a,& time onCOC match date ne on bottles?ber of containers received h number indicated on COC?form is properly signed in I 1f ADRcep x2 area backrground is obevd ; ronaples idestiJfd as noah.1= 11u =ate~n~dioactjy'.
contact the Radiation Safety group for furthe Maxizmm Courits Observed*:
~: lfMd ; ssSipped:? ifyes, contact Waste , or ESH Manager.Iniials Page 34 of 105 SAMLERECEIPT
& REVIEW FORM r..tn monly ICilent: Y an ku& JSDG/ARCOC/Work Order: 5 Date Received:
12 PM(A) Review (ensure mon-conforming ite are resolved prior to signing): Received By: C .( ,'t _ _ _ _ _ _ _ _ _...Sample Receipt Criteria > 4 4 Comments/Qualiners (Required for Non-Conforming Items)Shipping containers received intact Circle Applicable:
seals broken damaged container leaking container other (describe) and sealed? do Samples requiring cold Circle Coolat # ice bags blue ice dry ice odwr describe 2 preservation within (4 +/- 2 C)?Record preservation method.Chain of custody documents l included with shipment?
____________________________
4 Sample containers intact and Circle Applicable:
seals broken damaged container leaking container odw (describe) sealed?_1 Samples requiring chemical Sample ID's. containers affected and observed pH: 5preservation at proper pH? __________________________
6 VOA vials free of headspace Sample ID's and containers affected: (defined as < 6mm bubble)? _Are Encore containers present?7 (If yes, immediately deliver to .VOA laboratory)
Samples received within holding Id's and esew affected.8time? _________________________
9onSamplebsID's on CO match ID's Sample ID's and containers affected: I&Date & time on COC match date Sample ID's affected: 10; & time on bottles? __________________________
Number of containers received Sample ID's affected: match number indicated on COC? I COC form is properly signed in " q ci-F Iu.tiA'qt4.1/5,.d 12 relinquished/received sections?1 4 A ir B ill ,T ra c k in g # 's , & '"r -I" t2,t ..,' ( 1L t e Additional Comments T RSO RAD Receipt #___ ________SIf > x2 area background is observed on samplesidenifi-d as -non-Suspected Hazard Information 0 --regulated/non-radioactive'.
contact the Radiation Safety group for further ,.. E investigation.
A Radiological Classification?
Maximum Counts Observed*:
ipped as DO)1Hazardous Haza Class Shipped: C Material?
If yes, contact Waste ad s d Manager or ESH Manager. N J I PM (or PMA) review of Hazard class iication:
Initials e Date: I I Page 35 of 105 J(~,3-1qI~
Connecticut Yankee Statement of Work for Analytical Lab Services .CY-ISc-Sow-001 Figure 1. Sample Check-in List DatefTime.Received:
s"z_4 t3G2 (j, SDG#: Work Order Number: Shipping Cdntainer ID: 57 1 S i 112 Chain of Custody # "C6ao Lajce 1. Custody Seals oui shipping container intact? Yes Fi o I I 2. Custody Seals dated and signed? Yes *,4fo [ ].3. Chaia-of-Custody record present? Yes Ld,4,o [I 4. Cooler temperature "6 5. Vermiculite/packing materials is: Wet VDry [I1 6. Number of samples in shipping container:
C 7. Sample holding times exceeded?
Yes-[ ] No 8. Samples have:-p ___hazard labels cuody seals ___appropriate sample labels 9. Samples arpe:.J_ý_in good condition
____leaking broken ___have air bubbles 10. Were any anomalies
- identified in sample receipt? Yes [ ] No [-<1. Description of anomalies (nldsapenumbers):A.
Sample Custodian/Laboratory:
tr Date.:. -Telephoned to: .On By Page 36 of 105" .11 .,
Health Physics Procedure 1&45-149 -A GPP-GGGR-R5104-003-Attachment B-CY-00 I Major I CD W5__Chain of Custody Form Connecticut Yankee Atomic Power Company 362 Injun Hollow Road, East Hampton, CT 06424 No. 2006-00380 Project Name: Haddam Neck Decommissioning Analyses Requested
-LabUse Onl.Y..Contact Name & Phone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 (. <843 556 8171. Attn. Cheryl Jones Col .Priority:
Z 30 D. E] 14 D. 0 7 D. Container Media Sample Size-Media Type &Type .I .__Sample Designation Date Time Code Code Code Comment, Preservation Lab Sample ID iA 9106-0009-016F 5/15/06 13:28 SE C BP X X Transferred from COC 2006-00352 0 9106-0009-016FS 5/15/06 13:28 SE C BP x x Transferred from COC 2006-00352 9106-0009-017F 5/15/06 14:03 SE C BP X X Transferred from COC 2006-00352 04 9106-0009-01 IF 5/15/06 08:05 SE C BP x Transferred from COC 2006-00351 pq 9106-0009-013F 5/15/06 08:35 SE C BP X X Transferred from COC 2006-00351 V5 9106-0009-013FS 5/15/06 08:35 SE C BP X X --j- Transferred from COC 2006-00351 Di1 9106-0009-014F 5/15/06 08:59 SE C BP x --I -Transferred from CCC 2006-003519106-0009-015F 5/15/06 09:36 SE C BP X X Transferred from COC 2006-00351 I NOTES: P04:002332 MSR #: 0 6-0/' SSWP#NA SLTP QA El Radwaste QA El Non QA 1) Relinquised By Date/Time
- 2) R i d Date/Time 3) Relinquished By Date/Time
- 4) ReleiveA By Date/Time Samples Shipped Via:[E Fed Ex[] UPS El Hand El Other Bill of Lading#3-l ýv-/? 3 Internal Container Temp.: __ Deg. C Custody Sealed?YO NO Custody Seal Intact?YE N-Health Physics Procedure 1110-a g-4.1 I GPP-GGGR-R5104-003-Attachment B-CY-001 Major I -I '~' ~ I C$Connecticut Yankee Atomic Power Company Chain of Custody Form No. 2006-00381 362 Injun Hollow Road, East Hampton, CT 06424 860-267-2556" Project Name: Haddam Neck Decommissioning Analyses Requested Lab Use Only Contact Name & Phone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 0, 843 556 8171. Attn. Cheryl Jones Priority:
Z 30 D. [] 14 D. E] 7 D. Container Sample Size-Media Type &Type Sample Designation Date Time Code Code Code Comment, Preservation Lab Sample ID"-9106-0009-OF 5/11/06 13:22 SE C BP x X Transferred from COC 20D6-00347 1 9106-0009-002F 5/11/06 13:46 SE C BP x X Transferred from COC 2006-00347 I 9106-0009-003F 5/11/06 14:06 SE C BP x x Transferred from COC 2006-00347 9106-0009-004F 5/11/06 14:30 SE C BP X X Transferred from COC 2006-00347 it 9106-0009-005F 5/11/06 14:55 SE C BP X X Transferred from COC 2006-00347 1, 9106-0009-007F 5/12/06 07:44 SE C BP X X Transferred from COC 2006-00348
- 3. 9106-0009-008F 5/12/06 08:16 SE C BP X X Transferred from COC 2006-00348 9106-0009-009F 5/12/06 08:35 SE C BP X X Transferred from COC 2006-00348 cf 9106-0009-00F 5/12/06 09:07 SE C BP X X Transferred from COC 2006-00348 a'0(01 6(0(NOTES: PO #: 002332 MSR #: 06-SSWP# NA 0 LTP QA El Radwaste QA El Non QA 1) Reeinquisned By Jft7 r79,,otf Date/Time 2) Re:cZe* vVe ýyý I -Date/Time/,,, od Samples Shipped Via:[ Fed Ex El UPS El Hand El Other Bill of Lading #tq?1 /y- zJ7Yl Internal Container Temp.: __ Deg. C Custody Sealed?YO] N[D Custody Seal Intact?Y 0 ND 1 3) Relinquished By Date/Time
- 4) Receiived By / Date/Time I ,'-Pzd-~r~
4-UV146 1 Y ( Ito Connecticut Yankee Statement of Work for Analytical Lab Services-CY-ISC-SOW-O01 Figure 1. Sami Date/rime Received: " -0 , SDG#: Ma Work Order Number: Shipping Container ID:i,-'/-" 3 1. Custody Seals o6f shipping container intact?.2. Custody Seals dated and signed?3. Chain-of-Custody record present?4. Cooler tenmperature
- 5. Vermiculite/packing materials is: 6. ,Number of samples in shipping container:
- 7. Sample holding times ex:eeded?)le Check-in List.Oo(Chain of Custody #2,009 -aO "3 &'L,.-Yes LINo [1 Yes[ Noo Yes 4 No []Wet JDry4 Yes No (I 10. Were any anomalies identified in sample receipt? Yes [ No 11., Description of anomalies (include sample numbers): Sample. Custodian/Laboratory:
Date.: G 2LOC Telephoned to: On By 'Page 39 of 105 Health Physics Procedure GPP-GGGR-RS5104-003-Attachment B-CY-001 Major Connecticut Yankee Atomic Power Company Chain of Custody Form No. 2006-00349 362 Injun Hollow Road, East Hampton, CT 06424 860-267-2556 Project Name: Haddam Neck Decommissioning Analyses Requested Lab Use Only Contact Name & Phone: Comments: Jack McCarthy 860-267-2556 Ext. 3024 Analytical Lab (Name, City, State)General Engineering Laboratories 2040 Savage Road. Charleston SC. 29407 .843 556 8171. Attn. Cheryl Jones C z Priority:
Z 30 D. [] 14 D. F1 7 D. Container Media Type &Type Sample Designation Date Time Code Code Code I Comment, Preservation Lab Sample ID-9106-0010-OOIF 5/04/06 10:49 SE C BP X X Transferred from COC 2006-00321 0 9106-0010-002F 5/04/06 11:12 SE C BP X X TransferredfromCOC 2006-00321 it 9106-0010-004F 5/04/06 12:48 SE C BP X x Transferred from COC 2006-00321 i 9106-0010-006F 5/04/06 13:34 SE C BP X X Transfrred from COC 2006-00321 13 9106-0010-007F 5/04/06 13:21 SE C BP X X Transferred from COC 2006-00321 it 9106-0010-009F 5/04/06 14:01 SE C BP X x Transferred from COC 2006-00321
-9106-0010-OIOF 5/04/06 14:21 SE C BP X X Trasfemed from COC 2006-00321 9 9106-0010-012F 5/04/06 14:44 SE C BP X X Transferred from COC 2006-00321 9106-0010-013F 5/04/06 15:06 SE C BP X Tramsferred from COC 2006-00321 0 8 a'I NOTES: PO #: 002332 MSR#: 06- 0707 SSWP#NA Z LTP QA El Radwaste QA Dl Non QA 1) RelinquisheBy Date/Ti e 2) Received y Date/Time 3)Relinquished By DateTime 4) Receved By ate/Time Samples Shipped Via: Z Fed Ex 0l UPS El Hand Dl Other Bill of Lading #3qo4- 3 )15- g--tf Internal Container Temp.: /j7Deg. C CustodySealed?
Y E" N 0 Custody Seal Intact?Y 9--N 0 Connecticut Yankee Statement of Work for Analytical Lab Services cY-lSG-sow-Qol Figure 1. Sample Check-in List Date/Time Received:
_ L17 /.o b SDG#: N... 4p-07/3"7 Work Order Number: Shipping Cdntainer ID: 311 t .,l SS Chain of Custody#.I. Custody Seals ori shipping container intact?2. Custody Seals dated and signed?3. Chain-of-Custody record present?4. Cooler temperature
_U7' C 5. Vermiculite/packing materials is: 6. Number of samples in shipping container:
- 7. Sample holding times exceeded?CY-/SC-SOW-001 2OWL- 60397-Yes No []Yesj- No [ J.Yes No 1]Wet 9. Dry '.Yes [ ] No 8. Samples have'_tape -----hazard labels..._z ustody seals -appropriate sample labels 9. Samples are:!.-in good condition
.eaking-broken .have air bubbles 10. Were any anomalies identified in sample receipt? Yes [ No ix]11...Description of anomalies (include sample numbers):
._Samnple CustodianLaboratory: ) Date: V"--O(Telephoned to: } On By -Page 41 of 105-1111 t SAMPLE RECEIPT & REVIEW FORM OR ' use only Client: 1 aSDG/ARCOC/Work Order: Date Received:
5- 1Z L PM(A) Review ( 4e 1 g items are resolved prior to signing): Received By: &uv" [Sample Receipt Criteria Com ents/Qualifiers (Required for Non-Conforming Items)Shipping containers received intact Circle Applicable:
seals broken damaged container leaking coruaincr other (describe) and sealed? I Samples requiring cold / Circle Coolant # ice bags blue ice dry ice other decbe)2 preservation within (4 +/- 2 C)?Record preservation method.Chain of custody documents included with shipment?_
4 Sample containers intact and Circle Applicable:
seals broken damaged container leaking container other (describe).sealed?I Samples requiring chemical Sample ID's. containers affected and observed pH: preservation at proper pH? .1 6 VOA vials free of headspace Sample ID's and containers affected: (defined as < 6mm bubble)?Are Encore containers present?7 (If yes, immediately deliver to VOA laboratory) 8 Samples received within holding Id's and tests affected: time?Sample ID's on COC match ID's Sample ID's and containers affected: on bottles?Date & time on COC match date Sample ID's affected:& time on bottles? _Number of containers received Sane ID's affected: match number indicated on COC? _COC form is properly signed in 1 relinquished/received sections?Air Bill ,Tracking
- 's, & (.r-Ill Additional CommentsU RSO RAD Receipt #SJ H a I m *If > x2 area background is observed on samples identified as "non-S U U regulated/non-radioactive", contact the Radiation Safety group for further__ 9 investigation.
A IRadiological Classification?a V Maximum Counts Observed*:
in*% 46-~IPCB Regulated?
V Commnents:
Shipped as D01 Hazardous C Material?
If yes, contact Waste ""Hazard Class Shipped:]Manager or ESH Manager. UN#: PM (or PMA) review of Hazard classification:
Initials e -Date: /', .P. Z Page 42 of 105 List of current GEL Certifications as of 15 August 2006 State Alaska-Arizona Arkansas CLIA California Colorado Connecticu t..Dept. of Navy EPA Florida/NELAP Georgia Idaho Illinois Indiana Kansas Kentucky IMaryland Massachusetts Certification UST-062 AZ0668 0651 42D09040k6 01151 CA GenEngLabs PH-0169 NFESC 413 WG-15J E87156 (FL/NELAP)
N/A... .... s -o o 29.. .. ... , C-SC-01 10 E-10332 90129 270 M-SCO12 SCI 11501 233 68-485 1012000111658501/10i20002
__02934
-..... S-52597 .......l N/A N/A 00151 C223 Michigan Nevada New Jersey New York North Carolina North Carolina Drinking W North Dakota Oklahoma Pennsylvania
___South Carolina Tennessee Texas U.S. Dept. of Agriculture US Army Corps of Engineer Utah Vermont Virginia Washington Page 43 of 105 RADIOLOGICAL ANALYSIS Page 44 of 105 Radiochemistry Case Narrative Connecticut Yankee Atomic Power Co. (YANK)Work Order 168404 Method/Analysis Information Product: Alphaspec Am241, Cm, Solid ALL FSS Analytical Method: DOE EML HASL-300, Am-05-RC Modified Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 555696 554650 554649 Sample ID 168404001 168404002 168404003 168404004 168404005 168404006 168404007 168404008 168404011 168404012 168404013 168404014 168404015 1201153129 1201153130 1201153131 1201153132 Client ID 9106-0002-007F 9106-0002-01 IF 9106-0003-004F 9106-0003-015F 9106-0004-005F 9106-0004-015F 9106-0005-OIOF 9106-0005-014F 9106-0008-008F 9106-0009-002F 9106-0009-017F 9106-0010-001F 9106-0010-012F Method Blank (MB)168340011(9304-01-005C)
Sample Duplicate (DUP)168340011(9304-01-005C)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-01 1 REV# 14.Page 45 of 105 Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168340011 (9304-01-005C).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis Sample 168404003 (9106-0003-004F) was recounted due to high MDA.Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Manual Integration No manual integrations were performed on data in this batch.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Page 46 of 105 Product: Alphaspec Am241, Cm, Solid ALL FSS DOE EML HASL-300, Am-05-RC Modified Analytical Method: Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 557837 554650 554649 Sample ID 168404009 168404010 1201158316 1201158317 1201158318 1201158319 Client ID 9106-0006-005F 9106-0008-006F.Method Blank (MB)168404009(9106-0006-005F)
Sample Duplicate (DUP)168404009(9106-0006-005F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-01 1 REV# 14.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168404009 (9106-0006-005F).
QC Information Page 47 of 105 All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Manual Integration No manual integrations were performed on data in this batch.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Alphaspec Pu, Solid-ALL FSS Analytical Method: DOE EML HASL-300, Pu-I -RC Modified Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 555697 554650 554649 Page 48 of 105 Sample ID 168404001 168404002 168404003 168404004 168404005 168404006 168404007 168404008 168404009 168404010 168404011 168404012 168404013 168404014 168404015 1201153133 1201153134 1201153135 1201153136 Client ID 9106-0002-007F 9106-0002-01 IF 9106-0003-004F 9106-0003-015F 9106-0004-005F 9106-0004-015F 9106-0005-01OF 9106-0005-014F 9106-0006-005F 9106-0008-006F 9106-0008-008F 9106-0009-002F 9106-0009-017F 9106-0010-OO1F 9106-0010-012F Method Blank (MB)168340011(9304-01-005C)
Sample Duplicate (DUP)168340011(9304-01-005C)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-01 1 REV# 14.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168340011 (9304-01-005C).
QC Information All of the QC samples met the required acceptance limits.Page 49 of 105 Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Manual Integration No manual integrations were performed on data in this batch.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Liquid Scint Pu241, Solid-ALL FSS DOE EML HASL-300, Pu-1i -RC Modified Analytical Method: Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 555698 554650 554649 Page 50 of 105 Sample ID 168404001 168404002 168404003 168404004 168404005 168404006 168404007 168404008 168404009 168404010 168404011 168404012 168404013 168404014 168404015 1201153137 1201153138 1201153139 1201153140 Client ID 9106-0002-007F 9106-0002-01 1F 9106-0003-004F 9106-0003-015F 9106-0004-005F 9106-0004-015F 9106-0005-01OF 9106-0005-014F 9106-0006-005F 9106-0008-006F 9106-0008-008F 9106-0009-002F 9106-0009-017F 9106-0010-001F 9106-0010-012F Method Blank (MB)168340011(9304-01-005C)
Sample Duplicate (DUP)168340011(9304-01-005C)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-035 REV# 8.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (OC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168340011 (9304-01-005C).
QC Information All of the QC samples met the required acceptance limits.Page 51 of 105 Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Manual Integration No manual integrations were performed on data in this batch.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: GFPC, Sr90, solid-ALL FSS Analytical Method: EPA 905.0 Modified Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 556350 554650 554649 Page 52 of 105 Sample ID 168404003 168404004 168404012 168404013 168404014 168404015 1201154644 1201154645 1201154646 1201154647 Client ID 9106-0003-004F 9106-0003-015F 9106-0009-002F 9106-0009-017F 9106-0010-001F 9106-0010-012F Method Blank (MB)168404003(9106-0003-004F)
Sample Duplicate (DUP)168404003(9106-0003-004F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-004 REV# 10.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168404003 (9106-0003-004F).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Page 53 of 105 Chemical Recoveries All chemical recoveries meet the required acceptance limits for this sample set.Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Samples 1201154644 (MB), 1201154645 (9106-0003-004F), 1201154646 (9106-0003-004F), 1201154647 (LCS), 168404003 (9106-0003-004F), 168404004 (9106-0003-015F), 168404012 (9106-0009-002F), 168404013 (9106-0009-017F), 168404014 (9106-0010-001F) and 168404015 (9106-0010-012F) were dried and reweighed due to low matrix spike/laboratory control sample recovery.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Liquid Scint Tc99, Solid-ALL FSS Analytical Method: DOE EML HASL-300, Tc-02-RC Modified Analytical Batch Number: 554580 Page 54 of 105 Sample ID 168404001 168404002 168404003 168404004 168404005 168404006 168404007 168404008 168404009 168404010 168404011 168404012 168404013 168404014 168404015 1201150561 1201150562 1201150563 1201150564 Client ID 9106-0002-007F 9106-0002-01 IF 9106-0003-004F 9106-0003-015F 9106-0004-005F 9106-0004-015F 9106-0005-OIOF 9106-0005-014F 9106-0006-005F 9106-0008-006F 9106-0008-008F 9106-0009-002F 9106-0009-017F 9106-0010-001F 9106-0010-012F Method Blank (MB)168340012(9304-02-003C)
Sample Duplicate (DUP)168340012(9304-02-003C)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-005 REV# 13.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168340012 (9304-02-003C).
QC Information All of the QC samples met the required acceptance limits.Page 55 of 105 Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Liquid Scint Fe55, Solid-ALL FSS Analytical Method: DOE RESL Fe-1, Modified Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 555722 554650 554649 Page 56 of 105 Sample ID 168404001 168404002 168404003 168404004 168404005 168404006 168404007 168404008 168404009 168404010 168404011 168404012 168404013 168404014 168404015 1201153222 1201153223 1201153224 1201153225 Client ID 9106-0002-007F 9106-0002-01 IF 9106-0003-004F 9106-0003-015F 9106-0004-005F 9106-0004-015F 9106-0005-O1OF 9106-0005-014F 9106-0006-005F 9106-0008-006F 9106-0008-008F 9106-0009-002F 9106-0009-017F 9106-0010-OO1F 9106-0010-012F Method Blank (MB)168340012(9304-02-003C)
Sample Duplicate (DUP)168340012(9304-02-003C)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-040 REV# 3.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (0C0 Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168340012 (9304-02-003C).
QC Information All of the QC samples met the required acceptance limits.Page 57 of 105 Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Liquid Scint Ni63, Solid-ALL FSS Analytical Method: DOE RESL Ni-1, Modified Prep Method: Dry Soil Prep GL-RAD-A-021 Method: Analytical Batch Number: Prep Batch Number: Dry Soil Prep GL-RAD-A-021 Batch Number: Ash Soil Prep Dry Soil Prep 555723 554650 554649 Page 58 of 105 Sample ID 168404001 168404002 168404003 168404004 168404005 168404006 168404007 168404008 168404009 1201153226 1201153227 1201153228 1201153229 Client ID 9106-0002-007F 9106-0002-01 IF 9106-0003-004F 9106-0003-015F 9106-0004-005F 9106-0004-015F 9106-0005-OIOF 9106-0005-014F 9106-0006-005F Method Blank (MB)168340012(9304-02-003C)
Sample Duplicate (DUP)168340012(9304-02-003C)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-022 REV# 8.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168340012 (9304-02-003C).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Page 59 of 105 Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Analytical Method: Analytical Batch Number: Sample ID 168404001 168404002 168404003 168404004 168404005 168404006 168404007 168404008 168404009 168404010 168404011 168404012 168404013 168404014 168404015 1201150569 1201150570 1201150571 1201150572 LSC, Tritium Dist, Solid-HTD2,ALL FSS EPA 906.0 Modified 554582 Client ID 9106-0002-007F 9106-0002-01 IF 9106-0003-004F 9106-0003-015F 9106-0004-005F 9106-0004-015F 9106-0005-OIOF 9106-0005-014F 9106-0006-005F 9106-0008-006F 9106-0008-008F 9106-0009-002F 9106-0009-017F 9106-0010-OO1F 9106-0010-012F Method Blank (MB)168340011(9304-01-005C)
Sample Duplicate (DUP)168340011(9304-01-005C)
Matrix Spike (MS)Laboratory Control Sample (LCS)Page 60 of 105 SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-002 REV# 12.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168340011 (9304-01-005C).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis Sample 168404010 (9106-0008-006F) was recounted due to high MDA.Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Page 61 of 105 Qualifier information Manual qualifiers were not required.Method/Analysis Information Product: Liquid Scint C14, Solid AII,FSS Analytical Method: Analytical Batch Number: Sample ID 168404001 168404002 168404003 168404004 168404005 168404006 168404007 168404008 168404009 168404010 168404011 168404012 168404013 168404014 168404015 1201150573 1201150574 1201150575 1201150576 EPA EERF C-01 Modified 554583 Client ID 9106-0002-007F 9106-0002-01 IF 9106-0003-004F 9106-0003-015F 9106-0004-005F 9106-0004-015F 9106-0005-OIOF 9106-0005-014F 9106-0006-005F 9106-0008-006F 9106-0008-008F 9106-0009-002F 9106-0009-017F 9106-0010-001F 9106-0010-012F Method Blank (MB)168404003(9106-0003-004F)
Sample Duplicate (DUP)168404003(9106-0003-004F)
Matrix Spike (MS)Laboratory Control Sample (LCS)SOP Reference Procedure for preparation, analysis and reporting of analytical data are controlled by General Engineering Laboratories, LLC as Standard Operating Procedure (SOP). The data discussed in this narrative has been analyzed in accordance with GL-RAD-A-003 REV# 8.Calibration Information:
Calibration Information All initial and continuing calibration requirements have been met.Standards Information Standard solution(s) for these analyses are NIST traceable and used before the expiration date(s).Page 62 of 105 Sample Geometry All counting sources were prepared in the same geometry as the calibration standards.
Quality Control (QC) Information:
Blank Information The blank volume is representative of the sample volume in this batch.Designated QC The following sample was used for QC: 168404003 (9106-0003-004F).
QC Information All of the QC samples met the required acceptance limits.Technical Information:
Holding Time All sample procedures for this sample set were performed within the required holding time.Preparation Information All preparation criteria have been met for these analyses.Sample Re-prep/Re-analysis None of the samples in this sample set required reprep or reanalysis.
Miscellaneous Information:
NCR Documentation Nonconformance reports are generated to document any procedural anomalies that may deviate from referenced SOP or contractual documents.
A nonconformance report (NCR) was not generated for this SDG.Additional Comments Additional comments were not required for this sample set.Qualifier information Manual qualifiers were not required.Certification Statement Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless otherwise noted in the analytical case narrative.
Review Validation:
GEL requires all analytical data to be verified by a qualified data validator.
In addition, all data designated for CLP or CLP-like packaging will receive a third level validation upon completion of the data package.Page 63 of 105 The following data validator verified the information presented in this case narrative:
Reviewer/Date:
6--9/Z4§z%
z Page 64 of 105 SAMPLE DATA
SUMMARY
Page 65 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Report for YANKOO Connecticut Yankee Atomic Power Co.Client SDG: 168404 GEL Work Order: 168404 The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria** Analyte is a surrogate compound U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.ND The analyte concentration is not detected above the detection limit.The above sample is reported on a dry weight basis except where prohibited by the analytical procedure.
Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless qualified on the Certificate of Analysis.This data report has been prepared and reviewed in accordance with General Engineering Laboratories, LLC standard operating procedures.
Please direct any questions to your Project Manager, Cheryl Jones.Reviewed by Page 66 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: 9106-0002-007F Project: YANK01204 Sample ID: 168404001 Client ID: YANK001 Matrix: SE Vol. Recv.: Collect Date: 18-MAY-06 Receive Date: 02-JUN-06 Collector:
Client Moisture:
20.9%Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0 Curium-242 U Curium-243/244 U -0.(Alphaspec Pu, Solid-ALL FSS Plutonium-238 U Plutonium-239/240 U 0 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U Liquid Scint C14, SolidAllFSS Carbon- 14 U 0 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U.0762 0.00 10853 0.199.0341+/-0.102+/-0.0995+/-0.0717 0.00 0.00 0.0405+/-0.102+/-0.0995+/-0.0717 0.0956 0.138 0.177 0.444 0.323 10.7+/-0.228 0.181 +/-0.229+/-0.129 0.120 +/-0.129 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 10.0 +/-6.64 5.08 +/-6.72 4.17 +/-6.67 5.28 +/-6.67 BXLI 08/11/06 1336 555696 1 BXL1 08/11/06 1633 555697 2 BXLI 08/16/06 1220 555698 3 DFAI 08/09/06 1128 554582 4 ATH2 08/09/06 0324 554583 5 MXPI 08/12/06 1633 555722 6 MXPI 08/11/06 0738 555723 7 EGD1 08/11/06 2027 554580 8 11.4 pCi/g.0813+/-0.0797 0.0634 +/-0.0797 0.132 65.9 pCi/g pCi/g 9.90 +/-48.1 32.0 +/-48.1 7.02 +/-6.39 5.18 +/-6.40).139 +/-0.213 0.173 +/-0.213 10.6 pCi/g 0.360 pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 3 4 DOE EML HASL-300, Pu-I I-RC Modified DOE EML HASL-300, Pu- 11-RC Modified EPA 906.0 Modified Page 67 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0002-007F 168404001 Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 5 6 7 8 EPA EERF C-01 Modified DOE RESL Fe-I, Modified DOE RESL Ni-I, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS Recovery%80 100 98 75 76 74 Acceptable Limits (15%-125%)
(15%-125%)
(25%-/125%/o)
(15%-125%)
(25%-125%)
(15/-,125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 68 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0002-01IF 168404002 SE 19-MAY-06 02-JUN-06 Client 17.4%Proiect: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.120 Curium-242 U -0.0146 Curium-243/244 U -0.0103 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U 0.0121 Plutonium-239/240 U 0.0254 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U 6.72 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U -0.521 Liquid Scint C14, SolidAllFSS Carbon- 14 U 0.023 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U 3.93 Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 7.52 Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.173+/-0.154+/-0.122+/-0.0861 0.0683 0.0692 0.0487+/-0.155+/-0.123+/-0.0862+/-0.125 0.127 +/-0.125+/-0.0675 0.0381 +/-0.0675+/-7.02 5.56 +/-7.05+/-7.03 5.94 +/-7.03+/-0.0828 0.0685 +/-0.0828+/-47.7 31.9 +/-47.7+/-5.81 4.68 +/-5.81+/-0.203 0.164 +/-0.203 0.251 0.303 0.213 0.344 0.167 11.7 12.8 0.143 65.7 9.60 0.341 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1336 555696 1 BXLI 08/11/06 1633 555697 2 BXLI 08/16/06 1237 555698 3 DFAI 08/09/06 1143 554582 4 ATH2 08/09/06 0426 554583 5 MXPI 08/12/06 1649 555722 6 MXPI 08/11/06 0825 555723 7 EGDI 08/11/06 2043 554580 8 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 3 4 5 DOE EML HASL-300, Pu-11-RC Modified DOE EML HASL-300, Pu-I I-RC Modified EPA 906.0 Modified EPA EERF C-01 Modified Page 69 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0002-01IF 168404002 Project: YANKO 1204 Client ID: YANKOOl Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 6 7 8 DOE RESL Fe-I, Modified DOE RESL Ni-I, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS Recovery%76 100 88 72 76 79 Acceptable Limits (15%-125%)
(15%-125%)
(25%-I125%)
(150/-125%/o)
(25%-I125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 70 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: Report Date: August 21, 2006 9106-0003-004F 168404003 SE 25-APR-06 05-MAY-06 Client 23.5%Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U -0.027 Curium-242 U 0.112 Curium-243/244 U 0.0217 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U 0.061 Plutonium-239/240 U 0.0551 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U 8.31 Rad Gas Flow Proportional Counting GFPC, Sr90, solid-ALL FSS Strontium-90 U -0.00343 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U 0.603 Liquid Scint C14, SolidAll,FSS Carbon-14 U 0.0937 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U 7.68 Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 5.74 Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U -0.0643 Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd+/-0.117+/-0.315+/-0.206+/-0.189+/-0.103+/-5.73 0.153 0.245 0.205 0.176 0.0584 4.40+/-0.117+1-0.315+/-0.206+/-0.189+/-0.103+/-5.78+/-0.0203 0.0172 +/-0.0203 0.488 0.781 0.594 0.449 0.215 9.25 0.036 14.8 0.134 70.4 13.6 0.351 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/13/06 0819 555696 1 BXLI 08/11/06 1633 555697 2 BXLI 08/16/06 1253 555698 3 BXF1 08/14/06 0834 556350 4+/-8.25+/-0.0813+/-51.2+/-7.12+/-0.198 6.87 0.0642 34.2 6.58 0.169+/-8.25+/-0.0813+/-51.2+/-7.13+/-0.198 DFA1 ATH2 MXPI MXPI EGD1 08/09/06 1159 554582 08/09/06 0529 554583 08/12/06 1706 555722 08/11/06 0912 555723 08/11/06 2059 554580 5 6 7 8 9 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu-I I-RC Modified Page 71 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0003-004F 168404003 Proiect: Client ID: Vol. Recv.: YANK01204 YANK001 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 3 DOE EML HASL-300, Pu-I I-RC Modified 4 5 6 7 8 9 EPA 905.0 Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE RESL Fe-I, Modified DOE RESL Ni-I, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FýGFPC, Sr90, solid-ALL FSS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS 42 92 113 59 71 83 76 (15°/o- 125%/6)(15%-125%)
(25%-/125%)
(25%/- 125%)(15%/.-125%)
(25%-I125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded Page 72 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0003-004F 168404003 Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd The above sample is reported on a dry weight basis.Page 73 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: Report Date: August 21, 2006 9106-0003-015F 168404004 SE 25-APR-06 05-MAY-06 Client 22.5%Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.0456 Curium-242 U 0.113 Curium-243/244 U 0.180 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U 0.0196 Plutonium-239/240 U 0.0326 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U 6.63 Rad Gas Flow Proportional Counting GFPC, So9o, solid-ALL FSS Strontium-90 U 0.00477 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U 1.03 Liquid Scint C14, Solid AllFSS Carbon-14 0.156 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U -9.99 Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U 0.939 Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.237 Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd+1-0.155+/-0.181+/-0.239+/-0.121+/-0.0639+/-6.19 0.139 0.0733 0.181 0.118 0.00 4.86+1-0.155+/-0.182+/-0.240+/-0.121+/-0.064+/-6.22+/-0.0216 0.0179 +/-0.0216 0.387 0.321 0.472 0.324 0.0884 10.2 0.0375 12.6 0.146 59.2 21.6 0.353 pCi/g pCi/g pCi/g pCi/g.pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXL1 08/11/06 1633 555697 2 BXLI 08/16/06 1309 555698 3 BXFI 08/14/06 0834 556350 4+/-7.06+/-0.0912+/-42.7+/-10.1+/-0.213 5.85 0.0699 28.7 10.3 0.170+/-7.06+/-0.0913+/-42.7+/-10.1+/-0.213 DFAI ATH2 MXP1 MXPI EGD1 08/09/06 1215 554582 08/09/06 0632 554583 08/12/06 1722 555722 08/11/06 1001 555723 08/11/06 2115 554580 5 6 7 8 9 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu-I I-RC Modified Page 74 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0003-015F 168404004 Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter 3 4 5 6 7 8 9 Qualifier Result Uncertainty DOE EML HASL-300, Pu-I I-RC Modified EPA 905.0 Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE RESL Fe-I, Modified DOE RESL Ni-I, Modified DOE EML HASL-300, Tc-02-RC Modified LC TPU MDA Units DF Analyst Date Time Batch Mtd Surrogate/Tracer recovery Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS GFPC, Sr90, solid-ALL FSS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS Recovery%78 94 101 58 75 62 75 Acceptable Limits (15%-125%)
(150/-1250/%)
(25%-/125%)
(25%-125%)
(15%-125%)
(250/-125%)
(15%/-125%/)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded Page 75 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0003-015F 168404004 Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd The above sample is reported on a dry weight basis.Page 76 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: Report Date: August 21, 2006 9106-0004-005F 168404005 SE 03-MAY-06 12-MAY-06 Client 15.4%Proiect: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Re Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U -0 Curium-242 U -0.1 Curium-243/244 U -0.1 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U -0.1 Plutonium-239/2 4 0 U -0.1 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U 0 Liquid Scint C14, SolidAllFSS Carbon-14 0 Liquid Scint Fe55, Solid-ALL FSS lron-55 U -Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.(esult Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd.036 0169 0129 0217 0708 9.52.854.347 1.57 6.39 0198+/-0.123+/-0.033+/-0.227+/-0.163+/-0.0791+/-6.00+/-5.88+/-0.097+/-46.0+/-7.62+/-0.187 0.157 0.080 0.247 0.181 0.128 4.57 4.87 0.0674 30.7 7.40 0.156+/-0.123+/-0.0331+/-0.227+/-0.163+/-0.0795+/-6.07+/-5.88+/-0.0972+/-46.0+/-7.62+/-0.187 0.437 0.350 0.619 0.444 0.337 9.61 10.5 0.141 63.2 15.5 0.324 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXLI 08/11/06 1633 555697 2 BXLI 08/16/06 1326 555698 3 DFAI ATH2 MXPI MXPI EGDI 08/09/06 1231 554582 08/09/06 0734 554583 08/12/06 1738 555722 08/11/06 1017 555723 08/11/06 2131 554580 4 5 6 7 8 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu-I I-RC Modified 3 DOE EML HASL-300, Pu-1 I-RC Modified 4 EPA 906.0 Modified 5 EPA EERF C-01 Modified Page 77 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Client Sample ID: Sample ID: 9106-0004-005F 168404005 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 6 DOE RESL Fe-I, Modified 7 8 DOE RESL Ni-I, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS 65 95 105 78 80 80 (15%-125%)
(15%-125%)
(25%-/125%)
(15%-1 25%)(25%-125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier* QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 78 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: Report Date: August 21, 2006 9106-0004-015F 168404006 SE 03-MAY-06 12-MAY-06 Client 26.5%Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Ri Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.Curium-242 U -0.Curium-243/244 U -0.Alphaspec Pu, Solid-ALL FSS Plutonium-238 U 0.Plutonium-239/240 U -0 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U Liquid Scint C14, SolidA/lFSS Carbon- 14 U 0.'Liquid Scint Fe55, Solid-ALL FSS lron-55 U Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.1 esult Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 0823 0154 0994 0466 1.142 6.64-2.9 0352 1.88 3.88 0894+/-0.203+/-0.0301+/-0.251+/-0.213+/-0.108+/-6.53+/-7.59+/-0.0868+/-46.8+/-7.46+/-0.198 0.178 0.0729 0.300 0.210 0.191 5.16 6.60 0.0713 31.3 7.40 0.163+/-0.203+/-0.0302+/-0.251+/-0.213+/-0.109+/-6.57+/-7.59+/-0.0868+/-46.8+/-7.46+/-0.198 0.469 0.319 0.713 0.521 0.483 10.8 14.2 0.149 64.4 15.5 0.338 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXLI 08/11/06 1633 555697 2 BXLI 08/16/06 1342 555698 3 DFA I ATH2 MXPI MXPI EGD1 08/09/06 1247 554582 08/09/06 0837 554583 08/12/06 1754 555722 08/11/06 1033 555723 08/11/06 2147 554580 4 5 6 7 8 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu-11-RC Modified 3 DOE EML HASL-300, Pu-I I-RC Modified 4 EPA 906.0 Modified 5 EPA EERF C-01 Modified Page 79 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0004-015F 168404006 Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 6 7 8 DOE RESL Fe-I, Modified DOE RESL Ni-1, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FýLiquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS Recovery%72 72 94 73 80 78 Acceptable Limits (15%-125%)
(15%-125/%)
(25%-/125%)
(15%-125%)
(25%-/125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 80 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0005-01 OF 168404007 SE 02-MAY-06 09-MAY-06 Client 56.2%Project: Client ID: Vol. Recv.: YANKO 1204 YANK001 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U Curium-242 U -Curium-243/244 U -Alphaspec Pu, Solid-ALL FSS Plutonium-238 U Plutonium-239/240 U Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U Rad Liquid Scintillation Analysis-0.128-0.0115-0.0333 0.0548 0.0195+/-0.0939+/-0.128+/-0.122 0.142 +/-0.0942 0.147 +/-0.128 0.149 +/-0.122 0.385 0.450 0.401 0.403 0.322 pCi/g pCi/g pCi/g pCi/g pCi/g+/-0.169 0.158 +/-0.170+/-0.121 0.117 +/-0.121 10.4 +/-6.89 5.27 +/-6.97 0.00 +/-6.86 5.76 +/-6.86 11.1 pCi/g LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U BXLI 08/11/06 1434 555696 1 BXLI 08/11/06 1633 555697 2 BXL1 08/16/06 1358 555698 3 DFAI 08/09/06 1303 554582 4 ATH2 08/09/06 1017 554583 5 MXPI 08/12/06 1811 555722 6 MXPI 08/11/06 1049 555723 7 EGD1 08/11/06 2203 554580 8 Liquid Scint C14, SolidAllFSS Carbon-14 U Liquid Scint Fe55, Solid-ALL FSS Iron-55 U Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U Liquid Scint Tc99, Solid ALL FSS Technetium-99 U 0.0636+/-0.0801 0.0644 +/-0.0801 36.1 +/-44.1 28.7 +/-44.1 7.26 +/-10.2 10.0 +/-10.2-0.05 +/-0.199 0.169 +/-0.199 12.4 0.135 59.0 20.9 0.351 pCi/g pCi/g pCi/g pCi/g pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description 1 2 3 4 5 DOE EML HASL-300, Am-05-RC Modified DOE EML HASL-300, Pu-I I-RC Modified DOE EML HASL-300, Pu-I I-RC Modified EPA 906.0 Modified EPA EERF C-01 Modified Page 81 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company : Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0005-OIOF 168404007 Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 6 7 8 DOE RESL Fe-I, Modified DOE RESL Ni-I, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FýLiquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS Recovery%85 91 92 81 64 77 Acceptable Limits (15%-125%)
(15%-125%)
(25%- 125%)(15%-125%)
(25%-.125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 82 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0005-014F 168404008 SE 02-MAY-06 09-MAY-06 Client 32.3%Proiect: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.0(Curium-242 U -Curium-243/244 U 0.1 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U -0.1 Plutonium-239/240 U -0.1 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U Liquid Scint C14, SolidAllFSS Carbon-14 U 0.1 Liquid Scint Fe55, Solid-ALL FSS lron-55 U Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U -0 0591 0.04 0634+/-0.219+/-0.0554+/-0.261 0.231 +/-0.219 0.134 +/-0.0557 0.249 +/-0.261 0694 +/-0.106 0.160 +/-0.106 0287 +/-0.098 0.127 +/-0.0981 4.68 +/-8.01 6.48 +/-8.02 6.02 +/-6.38 4.90 +/-6.38 0892 +/-0.0827 0.0655 +/-0.0827 19.8 +/-46.3 30.6 +/-46.3 5.41 +/-7.91 7.77 +/-7.91.134 +/-0.192 0.167 +/-0.192 0.608 0.494 0.646 0.434 0.369 13.6 10.6 0.137 62.9 16.2 0.346 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXL1 08/11/06 1633 555697 2 BXLI 08/16/06 1415 555698 3 DFAI 08/09/06 1319 554582 4 ATH2 08/09/06 1424 554583 5 MXPI 08/12/06 1827 555722 6 MXPI 08/11/06 1106 555723 7 EGDI 08/11/06 2218 554580 8 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 3 4 5 DOE EML HASL-300, Pu-I I-RC Modified DOE EML HASL-300, Pu-11-RC Modified EPA 906.0 Modified EPA EERF C-01 Modified Page 83 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0005-014F 168404008 Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 6 DOE RESL Fe-I, Modified 7 8 DOE RESL Ni-l, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FýLiquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS 50 61 74 76 76 75 (15%-125%)
(15%-125%)
(25%-125%)
(15%-/I25%)
(25%-6125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 84 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0006-005F 168404009 SE 28-APR-06 12-MAY-06 Client 16.5%Proiect: Client ID: Vol. Recv.: YANK01204 YANKOO I Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U -0.Curium-242 U -0.'Curium-243/244 U -0.Alphaspec Pu, Solid-ALL FSS Plutonium-238 U 0.Plutonium-239/240 U 0.01 Liquid Scint Pu241, Solid ALL FSS Plutonium-241 U Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U -Liquid Scint C14, SolidAllFSS Carbon-14 0 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U Liquid Scint Ni63, Solid-ALL FSS Nickel-63 U Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U -0.0(0851 0253 0479 0183 0122+/-0.136+/-0.0495+/-0.0542 0.106 +/-0.136 0.120 +/-0.0496 0.131 +/-0.0545 0.390 0.525 0.443 0.303 0.221 9.82 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g+/-0.113 0.110 +/-0.113+/-0.0662 0.0694 +/-0.0662 4.43 +/-5.83 4.67 +/-5.85 2.02 +/-6.67 5.76 +/-6.67'.142 +/-0.0798 0.061 +/-0.0799 12.6 +/-47.6 31.7 +/-47.6 7.70 +/-9.56 9.31 +/-9.56 0659 +/-0.185 0.156 +/-0.185 BXLI 08/16/06 0949 557837 1 BXLI 08/11/06 1633 555697 3 BXLI 08/16/06 1431 555698 4 DFAl 08/09/06 1335 554582 5 ATH2 08/09/06 1719 554583 6 MXPI 08/12/06 1843 555722 7 MXPI 08/11/06 1122 555723 8 EGDI 08/11/062234 554580 9 12.4 pCi/g 0.127 65.3 19.5 0.323 pCi/g pCi/g pCi/g pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Am-05-RC Modified 3 DOE EML HASL-300, Pu-I 1-RC Modified 4 DOE EML HASL-300, Pu-I I-RC Modified 5 EPA 906.0 Modified Page 85 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0006-005F 168404009 Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 6 7 8 9 EPA EERF C-01 Modified DOE RESL Fe-I, Modified DOE RESL Ni-I, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Ni63, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS Recovery%76 93 105 72 64 81 Acceptable Limits (15%-125%)
(15%-125%)
(25%-.125%)
(15%-/125%)
(25%-/125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 86 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0008-006F 168404010 SE 05-MAY-06 26-MAY-06 Client 34.8%Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U I Curium-242 U I Curium-243/244 U -0.Alphaspec Pu, Solid-ALL FSS Plutonium-238 U -0.Plutonium-239/240 U 0.0 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U Liquid Scint C14, SolidAllFSS Carbon-14 U Liquid Scint Fe55, Solid-ALL FSS Iron-55 U Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U+/-0.195+/-0.202+/-0.0316+/-0.0711+/-0.113 0.0758 0.00 0.0766+/-0.196+/-0.203+/-0.0317 0.332 0.280 0.335 0.275 0.317 9.75 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 0.0967 +/-0.0712 0.118 +/-0.113 14.9 +/-6.37 4.64 +/-6.51 0.00 +/-6.06 5.09 +/-6.06).107 +/-0.0846 0.0664 +/-0.0846 15.1 +/-41.4 27.5 +/-41.4).258 +/-0.225 0.179 +/-0.225 BXLI 08/16/06 0949 557837 1 BXLI 08/11/06 1633 555697 3 BXLI 08/16/06 1447 555698 4 DFAI 08/10/06 2150 554582 5 ATH2 08/09/06 1822 554583 6 MXPI 08/12/06 1900 555722 7 EGDI 08/11/06 2251 554580 8 10.7 pCi/g 0.139 56.6 0.373 pCi/g pCi/g pCi/g The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description 1 2 3 4 5 6 7 DOE EML HASL-300, Am-05-RC Modified DOE EML HASL-300, Am-05-RC Modified DOE EML HASL-300, Pu-I I-RC Modified DOE EML HASL-300, Pu-I I-RC Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE RESL Fe-I, Modified Page 87 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0008-006F 168404010 Project: YANK01204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 8 DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%Acceptable Limits Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS 77 94 103 72 71 (15%-125%)
(15%-125%)
(25%-6125%)
(15%-125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.Ul Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 88 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: 9106-0008-008F Project: YANK01204 Sample ID: 168404011 Client ID: YANKOOI Matrix: SE Vol. Recv.: Collect Date: 08-MAY-06 Receive Date: 26-MAY-06 Collector:
Client Moisture:
35.7%Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.Curium-242 U -0.Curium-243/244 U -0.Alphaspec Pu, Solid-ALL FSS Plutonium-238 U -0.Plutonium-239/240 U -0.Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U Liquid Scint C14, SolidAllFSS Carbon-14 U -0.Liquid Scint Fe55, Solid-ALL FSS lron-55 U -Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.+/-0.192+/-0.142+/-0.202 0.152 +/-0.193 0.132 +/-0.142 0.240 +/-0.203+/-0.096 0.125 +/-0.096+/-0.114 0.137 +/-0.114 11.5 +/-6.72 5.08 +/-6.80 0.00 +/-5.92 4.97 +/-5.92 0238 +/-0.0745 0.0636 +/-0.0745-10.7 +/-40.9 27.5 +/-40.9 0956 +/-0.211 0.174 +/-0.211 0.426 0.446 0.603 0.328 0.353 10.7 10.7 0.133 56.8 0.361 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXLI 08/11/06 1633 555697 2 BXLI 08/16/06 1504 555698 3 DFAI 08/09/06 1407 554582 4 ATH2 08/09/06 1924 554583 5 MXPI 08/12/06 1916 555722 6 EGDI 08/11/06 2307 554580 7 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description 1 2 3 4 5 6 DOE EML HASL-300, Am-05-RC Modified DOE EML HASL-300, Pu-1 I-RC Modified DOE EML HASL-300, Pu-I 1-RC Modified EPA 906.0 Modified EPA EERF C-01 Modified DOE,RESL Fe-I, Modified Page 89 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Client Sample ID: Sample ID: 9106-0008-008F 168404011 Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 7 DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALl Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS 65 98 96 76 74 (15%/-125%)
(15%-125%)
(25%-/125%)
(15%-125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 90 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company : Connecticut Yankee Atomic Power Address 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0009-002F 168404012 SE 11-MAY-06 08-JUN-06 Client 33%Parameter Qualifier Result Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U -0.00144 Curium-242 U 0.0192 Curium-243/244 U 0.013 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U -0.00587 Plutonium-239/240 U 0.0186 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 13.6 Rad Gas Flow Proportional Counting GFPC, So9o, solid-ALL FSS Strontium-90 U 0.0151 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U 4.12 Liquid Scint C14, Solid A/lFSS Carbon-14 U 0.046 Liquid Scint Fe55, Solid ALL FSS Iron-55 U 12.9 Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.078 Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd+1-0.155+/-0.145+/-0.268+/-0.0493+/-0.0492+/-6.90 0.166 0.135 0.281 0.0279 0.0278 5.13+/-0.155+/-0.145+/-0.268+/-0.0494+/-0.0493+/-7.01+/-0.0146 0.0114 +/-0.0146 0.458 0.455 0.687 0.122 0.122 10.8 0.0242 14.5 0.128 55.2 0.348 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXLI 08/11/06 1632 555697 2 BXLI 08/16/06 1520 555698 3 BXF1 08/14/06 0834 556350 4+/-8.36+/-0.0755+/-40.6+/-0.203 6.70 0.0613 26.8 0.168+/-8.36+/-0.0755+/-40.6+/-0.203 DFA1 ATH2 MXPI EGD1 08/09/06 1422 554582 08/09/06 2027 554583 08/12/06 1932 555722 08/11/06 2323 554580 5 6 7 8 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description 1 DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu-I I-RC Modified 3 DOE EML HASL-300, Pu-I I-RC Modified 4 EPA 905.0 Modified Page 91 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0009-002F 168404012 Project: YANKO 1204 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 5 6 7 8 EPA 906.0 Modified EPA EERF C-01 Modified DOE RESL Fe-I, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL F5 GFPC, Sr90, solid-ALL FSS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS Recovery%61 98 94 69 81 75 Acceptable Limits (15%-125%)
(15%-125%)
(25%- 125%o)(25%-/125%)
(15%-125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or.Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 92 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: Report Date: August 21, 2006 9106-0009-017F 168404013 SE 15-MAY-06 08-JUN-06 Client 28.4%Proiect: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.0755 Curium-242 U 0.0957 Curium-243/244 U -0.073 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U -0.00629 Plutonium-239/240 U 0.0262 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 13.3 Rad Gas Flow Proportional Counting GFPC, Sr90, solid-ALL FSS Strontium-90 U 0.0205 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U 0.583 Liquid Scint C14, SolidAllFSS Carbon-14 U 0.0271 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U -61.9 Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.0628 Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd+/-0.242+/-0.220+/-0.214+/-0.0529+/-0.0513+/-6.66 0.230 0.171 0.256 0.0299 0.00 4.95+/-0.243+/-0.220+/-0.214+/-0.0529+/-0.0514+/-6.77 0.574 0.509 0.627 0.131 0.0709 10.4 0.0246 14.4 0.131 210 0.343+1-0.0151 0.0116 +/-0.0151 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXLI 08/11/06 1632 555697 2 BXLI 08/16/06 1536 555698 3 BXF1 08/14/06 0833 556350 4+/-7.98+/-0.0759+/-150+/-0.200 6.65 0.0625 102 0.165+/-7.98+/-0.0759+/-150+/-0.200 DFA I ATH2 MXPI EGDI 08/09/06 1438 554582 08/09/06 2129 554583 08/12/06 1949 555722 08/11/06 2338 554580 5 6 7 8 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu- 11-RC Modified 3 DOE EML HASL-300, Pu-I I-RC Modified 4 EPA 905.0 Modified Page 93 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: August 21, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0009-017F Project: YANK01204 Sample ID: 168404013 Client ID: YANK001 Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 5 EPA 906.0 Modified 6 EPA EERF C-01 Modified 7 DOE RESL Fe-1, Modified 8 DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Americium-243 Alphaspec Am241, Cm, Solid ALL 64 (15%-/125%)
Plutonium-242 Alphaspec Pu, Solid-ALL FSS 91 (15%-125%)
Carrier/Tracer Recovery Liquid Scint Pu241, Solid-ALL FS 96 (25%-125%)
Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 72 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Fe55, Solid-ALL FS 73 (15%-125%)
Carrier/Tracer Recovery Liquid Scint Tc99, Solid-ALL FS 79 (15%- 125%)Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 94 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.corn Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: 9106-0010-00IF 168404014 SE 04-MAY-06 17-MAY-06 Client 27.3%Proiect: YANKO 1204 Client ID: YANKOOI Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.00677 Curium-242 U 0.0854 Curium-243/244 U 0.0361 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U 0.173 Plutonium-239/240 U -0.0342 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 13.0 Rad Gas Flow Proportional Counting GFPC, Sr90, solid-ALL FSS Strontium-90 U -0.0128 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U 0.548 Liquid Scint C14, SolidAllFSS Carbon-14 U 0.0555 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U -18.1 Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.134+/-0.227+/-0.167+/-0.242 0.238 +/-0.227 0.00 +/-0.168 0.241 +/-0.242+/-0.181 0.143 +/-0.182+/-0.0865 0.0951 +/-0.0866+/-6.44 4.78 +/-6.54+/-0.0141 0.0125 +/-0.0141+/-7.50 6.25 +/-7.50+/-0.0809 0.0655 +/-0.0809+/-47.6 32.3 +/-47.6+/-0.205 0.167 +/-0.205 0.628 0.231 0.634 0.331 0.235 10.0 0.0262 13.5 0.137 66.6 0.347 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXLI 08/11/06 2250 555697 2 BXLI 08/16/06 1553 555698 3 BXFI 08/14/06 0833 556350 4 DFAI 08/09/06 1454 554582 5 ATH2 08/09/06 2232 554583 6 MXPI 08/12/06 2005 555722 7 EGDI 08/11/06 2354 554580 8 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description 1 2 3 4 DOE EML HASL-300, Am-05-RC Modified DOE EML HASL-300, Pu-I I-RC Modified DOE EML HASL-300, Pu-I I-RC Modified EPA 905.0 Modified Page 95 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Report Date: August 21, 2006 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: 9106-0010-00IF Project: YANK01204 Sample ID: 168404014 Client ID: YANKOOI Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 5 EPA 906.0 Modified 6 EPA EERF C-01 Modified 7 DOE RESL Fe-1, Modified 8 DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Test Recovery%
Acceptable Limits Americium-243 Alphaspec Am241, Cm, Solid ALL 50 (15%-0125%)
Plutonium-242 Alphaspec Pu, Solid-ALL FSS 85 (15%-125%)
Carrier/Tracer Recovery Liquid Scint Pu241 Solid-ALL Fý 99 (25%-125%)
Carrier/Tracer Recovery GFPC, Sr90, solid-ALL FSS 74 (25%-125%)
Carrier/Tracer Recovery Liquid Scint Fe55, Solid-ALL FS 70 (15%- 125%)Carrier/Tracer Recovery Liquid Scint Tc99, Solid-ALL FS 75 (15°/o- 125%)Notes: The Qualifiers in this report are defined as follows* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 96 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Client Sample ID: Sample ID: Matrix: Collect Date: Receive Date: Collector:
Moisture: Report Date: August 21, 2006 9106-0010-012F 168404015 SE 04-MAY-06 17-MAY-06 Client 28.1%Proiect: YANKO 1204 Client ID: YANKOOl Vol. Recv.: Parameter Qualifier Result Rad Alpha Spec Analysis Alphaspec Am241, Cm, Solid ALL FSS Americium-241 U 0.110 Curium-242 U -0.0547 Curium-243/244 U -0.126 Alphaspec Pu, Solid-ALL FSS Plutonium-238 U -0.00157 Plutonium-239/240 U 0.0867 Liquid Scint Pu241, Solid-ALL FSS Plutonium-241 U 8.31 Rad Gas Flow Proportional Counting GFPC, Sr90, solid-ALL FSS Strontium-90 U -0.00771 Rad Liquid Scintillation Analysis LSC, Tritium Dist, Solid-HTD2,ALL FSS Tritium U 0.896 Liquid Scint C14, Solid AllFSS Carbon-14 U 0.0162 Liquid Scint Fe55, Solid-ALL FSS Iron-55 U 23.3 Liquid Scint Tc99, Solid-ALL FSS Technetium-99 U 0.0577 Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd+/-0.184+/-0.141+/-0.184+/-0.126+/-0.0869+/-6.16 0.140 0.192 0.245 0.122 0.0406 4.77+/-0.184+/-0.141+/-0.185+/-0.126+/-0.0872+/-6.21+/-0.0144 0.0124 +/-0.0144 0.386 0.544 0.597 0.291 0.128 10.0 0.0263 11.0 0.132 67.0 0.354 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g BXLI 08/11/06 1434 555696 1 BXLI 08/11/06 2250 555697 2 BXLI 08/16/06 1609 555698 3 BXFI 08/14/06 0833 556350 4+/-6.17+/-0.0763+/-49.3+/-0.206 5.11 0.0633 32.5 0.171+/-6.17+/-0.0763+/-49.3+/-0.206 DFA I ATH2 MXPI EGDI 08/09/06 1510 554582 08/09/06 2334 554583 08/12/06 2021 555722 08/12/06 0010 554580 5 6 7 8 The following Prep Methods were performed Method Description Analyst Date Time Prep Batch Dry Soil Prep Dry Soil Prep GL-RAD-A-021 LXM2 08/03/06 1534 554649 The following Analytical Methods were performed Method Description I DOE EML HASL-300, Am-05-RC Modified 2 DOE EML HASL-300, Pu-I 1-RC Modified 3 DOE EML HASL-300, Pu-I 1-RC Modified 4 EPA 905.0 Modified Page 97 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Certificate of Analysis Company: Connecticut Yankee Atomic Power Address : 362 Injun Hollow Rd East Hampton, Connecticut 06424 Contact: Mr. Jack McCarthy Project: Soils PO# 002332 Report Date: August 21, 2006 Client Sample ID: Sample ID: 9106-0010-012F 168404015 Project: YANKO 1204 Client ID: YANKOO Vol. Recv.: Parameter Qualifier Result Uncertainty LC TPU MDA Units DF Analyst Date Time Batch Mtd 5 6 7 8 EPA 906.0 Modified EPA EERF C-01 Modified DOE RESL Fe-I, Modified DOE EML HASL-300, Tc-02-RC Modified Surrogate/Tracer recovery Americium-243 Plutonium-242 Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Carrier/Tracer Recovery Alphaspec Am241, Cm, Solid ALL Alphaspec Pu, Solid-ALL FSS Liquid Scint Pu241, Solid-ALL FS GFPC, Sr90, solid-ALL FSS Liquid Scint Fe55, Solid-ALL FS Liquid Scint Tc99, Solid-ALL FS Recovery%81 91 99 68 74 75 Acceptable Limits (15%-125%)
(15%-125%)
(25%-125%)
(25%- 125%)(15%-125%)
(15%-125%)
Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported> Result is greater than value reported A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded The above sample is reported on a dry weight basis.Page 98 of 105 I.QUALITY CONTROL DATA Page 99 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Client : Connecticut Yankee Atomic Power 362 Injun Hollow Rd Report Date: August 21, 2006 Page 1 of 6 East Hampton, Connecticut Contact: Mr. Jack McCarthy Workorder:
168404 Parmname Rad Alpha Spec Batch NOM Sample Qual QC Units RPD%REC% Range Anlst Date Time 555696 QC1201153130 Americium-241 Curium-242 Curium-243/244 QCI201153132 Americium-241 Curium-242 Curium-243/244 QC1201153129 Americium-241 Curium-242 Curium-243/244 QC1201153131 Americium-241 168340011 DUP U -0.000522 Uncert: +/-0.0385 TPU: +/-0.0385 U 0.00 Uncert: +/-0.0756 TPU: +/-0.0756 U -0.0177 Uncert: +/-0.0764 TPU: +/-0.0765 LCS MB 12.8 Uncert: TPU: Uncert: TPU: 15.5 Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU: U 0.0578+/-0.278+/-0.279 U -0.0405+/-0.0562+/-0.0565 U -0.0517+/-0.257+/-0.257 12.8+/-1.84+/-2.70 U -0.0328+/-0.0454+/-0.0457 14.3+/-1.94+/-2.92 U 0.0471+/-0.157+/-0.157 U -0.0469+/-0.0459+/-0.0464 U -0.00385+/-0.210+/-0.210 pCi/g 204 pCi/g 200 pCi/g 98 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 92 (75%-125%)
(0%- 100%) BXLI 08/11/06 14:34 (0%- 100%)(0%- 100%)100 (75%-125%)
168340011 MS Curium-242 13.3 U -0.000522 Uncert: +/-0.0385 TPU: +/-0.0385 U 0.00 Uncert: +/-0.0756 TPU: +/-0.0756 16.1 U -0.0177 Uncert: +/-0.0764 TPU: +/-0.0765 U 12.0+/-1.38+/-2.08 0.0427+/-0.0837+/-0.0839 15.9+/-1.58+/-2.61 91 (75%-125%)
Curium-243/244 99 (75%-125%)
Batch 555697 QC1201153134 168340011 DUP Plutonium-238 U -0.0155 U 0.0237 pCi/g 956 (0%- 100%) BXLI 08/11/06 22:51 Page 100 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
168404 Page 2 of 6 Parmname NOM Sample Qual QC Units RPD% REC% Range Anist Date Time Rad Alpha Spec Batch 555697 Plutoniurn-239/240 QC1201153136 LCS Plutonium-238 Plutonium-239/240 QC 1201153133 MB Plutonium-238 Uncert: +/-0.0215 TPU: +/-0.0216 U 0.0414 Uncert: +/-0.0934 TPU: +/-0.0935 Uncert: TPU: 11.8 Uncert: TPU: U+/-0.0465+/-0.0466-0.0489+/-0.124+/-0.124 pCi/g 2410 (0%- 100%)(75%- 125%)U 0.155+/-0.141+/-0.142 11.5+/-0.856+/-1.32 U 0.0552+/-0.186+/-0.186 U -0.0978+/-0.0892+/-0.0899 Plutonium-239/240 QC1201153135 168340011 MS Plutonium-238 Plutoniumn-239/240 Uncert: TPU: Uncert: TPU: pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 98 (75%-125%)
08/11/06 22:50 U -0.0155 Uncert: +/-0.0215 TPU: +/-0.0216 12.3 u 0.0414 Uncert: +/-0.0934 TPU: +/-0.0935 U 7.28 Uncert: +/-6.30 TPU: +/-6.35 U 0.0539+/-0.112+/-0.112 10.3+/-0.796+/-1.19 (75%-125%)
08/11/06 22:51 84 (75%-125%)
Batch 555698 QC1201153138 168340011 DUP Plutonium-241 QCI201153140 LCS Plutonium-241 QC1201153137 MB Plutonium-241 QC1201153139 168340011 MS Plutonium-241 U 10.1+/-6.39+/-6.46 pCi/g 0 (0% -100%) BXLI 137 Uncert: TPU: Uncert: TPU: 138 U Uncert: TPU: 145+/-12.5+/-19.9 U 8.57+/-6.93+/-6.98 pCi/g pCi/g pCi/g 106 (75%-125%)
08/16/06 16:41 08/16/06 17:14 08/16/06 16:25 08/16/06 16:58 7.28+/-6.30+/-6.35 Batch 557837 142+/-12.4+/-19.7 0.167+/-0.220+/-0.221 0.241 103 (75%-125%)
QC1201158317 168404009 DUP Americium-241 Curium-242 U -0.0851 Uncen: +/-0.136 TPU: +/-0.136 U -0.0253 U U pCi/g 616 pCi/g 247 (0% -100%) BXLI (0%- 100%)08/16/06 09:49 Page 101 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
168404 Page 3 of 6 Parmname NOM Samnle Oual QC Units RPD%REC% Range Anist Date Time Rad Alpha Spec Batch 557837 Curium-243/244 QC1201158319 Americium-241 Curium-242 Curium-243/244 QC1201158316 Americium-241 Uncert: +/-0.0495 TPU: +/-0.0496 U -0.0479 Uncert: +/-0.0542 TPU: +/-0.0545 LCS MB 24.5 Uncert: TPU: Uncert: TPU: 29.7 Uncert: TPU: Uncert: TPU: Uncert: TPU: Uncert: TPU:+/-0.334+/-0.335 U 0.0761+/-0.149+/-0.149 25.4+/-2.47+/-4.16 U 0.0477+/-0.127+/-0.127 27.0+/-2.54+/-4.38 U 0.234+/-0.275+/-0.277 U 0.00+/-0.152+/-0.152 U -0.0551+/-0.0624+/-0.0628 29.1+/-2.97+/-5.01 U 0.126+/-0.247+/-0.248 31.7+/-3.12+/-5.39 pCi/g 879 Curium-242 Curium-243/244 QC1201158318 168404009 MS Americium-241 Curium-242 Curium-243/244 pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g pCi/g 91 (75%-125%)
(0%- 100%)104 (75%-125%)
26.4 U -0.0851 Uncerl: +/-0.136 TPU: +/-0.136 U -0.0253 Uncert: +/-0.0495 TPU: +/-0.0496 32.4 U -0.0479 Uncert: +/-0.0542 TPU: +/-0.0545 110 (75%-125%)
98 (75%-125%)
Rad Gas Flow Batch 556350 QC1201154645 168404003 DUP Strontium-90 QC1201154647 LCS Strontium-90 QC1201154644 MB Strontium-90 U -0.00343 Uncert: +/-0.0203 TPU: +/-0.0203 1.56 Uncert: TPU: U -0.00637+/-0.0152+/-0.0152 1.30+/-0.0563+/-0.088 I U 0.0176+/-0.018+/-0.018 pCi/g 0 (0% -100%) BXFI 08/14/06 08:33 pCi/g pCi/g 83 (75%-125%)
Uncert: TPU: Page 102 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
168404 Page 4 of 6 REC% Range AnIst Date Time Parmname NOM Sample Qual QC Units RPD%Rad Gas Flow Batch 556350 QC1201154646 168404003 MS Strontium-90 Rad Liquid Scintillation Batch 554580 QC1201150562 168340012 DUP Technetium-99 QC1201150564 LCS Technetium-99 QCI201150561 MB Technetium-99 QC1201150563 168340012 MS Technetium-99 1.58 U Uncert: TPU:-0.00343+/-0.0203+/-0.0203 1.29+/-0.0535+/-0.0813 pCi/g 82 (75%-125%)
U 0.0338 Uncert: +/-0.192 TPU: +/-0.192 U 0.266+/-0.226+/-0.226 13.6+/-0.496+/-0.599 pCi/g 0 (0% -100%) EGDI 13.1 Uncert: TPU: Uncert: TPU: 13.0 U Uncert: TPU: U 0.0311+/-0.177+/-0.177 pCi/g pCi/g pCilg 103 (75%-125%)
08/12/06 00:42 08/12/06 01:14 08/12/06 00:26 08/12/06 00:58 0.0338+/-0.192+/-0.192 12.0+/-0.523+/-0.602 92 (75%-125%)
Batch 554582 QC1201150570 168340011 DUP Tritium QC1201150572 LCS Tritium QC1201150569 MB Tritium QC1201150571 168340011 MS Tritium U 1.77 Uncert: +/-8.20 TPU: +/-8.20 U 1.62+/-7.47+/-7.47 pCi/g 0 (0% -100%) DFA I 68.3 Uncert: TPU: Uncert: TPU: 61.3 U Uncert: TPU: 76.2+/-14.0+/-14.1 U 0.586+/-8.01+/-8.01 pCilg pCilg pCi/g Il1 (75%-125%)
08/09/06 15:42 08/09/06 16:14 08/09/06 15:26 08/09/06 15:58 1.77+/-8.20+/-8.20 61.8+/-12.2+/-12.3 101 (75%-125%)
Batch 554583 QC1201150574 168404003 DUP Carbon- 14 QC1201150576 LCS Carbon- 14 U 0.0937 Uncert: +/-0.0813 TPU: +/-0.0813 U 0.0422+/-0.075+/-0.0751 7.14+/-0.508+/-0.520 pCi/g 0 (0% -100%) ATH2 08/10/06 01:39 7.27 Uncert: TPU: pCi/g 98 (75%-125%)
08/10/06 03:00 QC1201150573 MB Page 103 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com Workorder:
168404 Parmname Rad Liquid Scintillation Batch 554583 Carbon- 14 QC1201150575 168404003 MS Carbon-14 Batch 555722 QC1201153223 168340012 DUP lron-55 QC1201153225 LCS Iron-55 QC1201153222 MB Iron-55 QC1201153224 168340012 MS Iron-55 Batch 555723 QC1201153227 168340012 DUP Nickel-63 NOM Uncert: TPU 15.1 Uncert: TPU Uncert: TPU 641 Uncert: TPU Uncert: TPU 717 Uncert: TPU QC Summary Sample Qual QC U -0.0315+/-0.0776+/-0.0776 U 0.0937 13.8+/-0.0813
+/-1.00+/-0.0813
+/-1.03 U -26.5 U 5.83+/-65.1 +/-36.9+/-65.1 +/-36.9 660+/-56.2+/-67.2 U 18.2+/-39.6+/-39.6 U -26.5 688+/-65.1 +/-60.2+/-65.1 +/-71.6 U 3.79 U 6.68 Page 5 of 6 Units RPD% REC% Range Anist Date Time pCi/g pCi/g 92 (75%-125%)
08/10/06 02:43 pCi/g pCi/g pCi/g pCi/g (0% -100%) vIxPI 103 (75%-125%)
96 (75%-125%)
08/12/06 20:54 08/12/06 21:27 08/12/06 20:38 08/12/06 21:11 08/11/06 11:55 08/11/06 12:27 08/11/06 11:38 08/11/06 12:11 Uncert: +/-5.39 +/TPU: +/-5.40 +/QC1201153229 LCS Nickel-63 512 Uncert: +/TPU: +/-QC1201153226 MB Nickel-63 U Uncert: +/-TPU: +/-QC1201153228 168340012 MS Nickel-63 530 U 3.79 Uncert: +/-5.39 +/-TPU: +/-5.40 +/-Notes: The Qualifiers in this report are defined as follows:* A quality control analyte recovery is outside of specified acceptance criteria< Result is less than value reported Result is greater than value reported-7.43-7.43 479-22.4-27.1 15.7 9.92-9.93 511 23.5 28.7 pCi/g pCi/g pCi/g pCi/g 0 (0% -100%) viXPI 94 (75%-125%)
96 (75%-125%)
Page 104 of 105 GENERAL ENGINEERING LABORATORIES, LLC 2040 Savage Road Charleston SC 29407 -(843) 556-8171 -www.gel.com QC Summary Workorder:
168404 Page 6 of 6 Parmname NOM Sample Qual QC Units RPD% REC% Range Anist Date Time A The TIC is a suspected aldol-condensation product B Target analyte was detected in the associated blank BD Results are either below the MDC or tracer recovery is low C Analyte has been confirmed by GC/MS analysis D Results are reported from a diluted aliquot of the sample H Analytical holding time was exceeded J Value is estimated N/A Spike recovery limits do not apply. Sample concentration exceeds spike concentration by 4X or more R Sample results are rejected U Analyte was analyzed for, but not detected above the MDL, MDA, or LOD.UI Gamma Spectroscopy--Uncertain identification X Consult Case Narrative, Data Summary package, or Project Manager concerning this qualifier Y QC Samples were not spiked with this compound A RPD of sample and duplicate evaluated using +/-RL. Concentrations are <5X the RL h Preparation or preservation holding time was exceeded N/A indicates that spike recovery limits do not apply when sample concentration exceeds spike cone. by a factor of 4 or more.** Indicates analyte is a surrogate compound.^ The Relative Percent Difference (RPD) obtained from the sample duplicate (DUP) is evaluated against the acceptence criteria when the sample is greater than five times (5X) the contract required detection limit (RL). In cases where either the sample or duplicate value is less than 5X the RL, a control limit of +/- the RL is used to evaluate the DUP result.For PS, PSD, and SDILT results, the values listed are the measured amounts, not final concentrations.
Where the analytical method has been performed under NELAP certification, the analysis has met all of the requirements of the NELAC standard unless qualified on the QC Summary.Page 105 of 105 DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Attachment 2b Split Sample Assessment Forms (2 Pages)
Connecticut Yankee Decommissioning Project Health Physics Procedure 24265-000-GPR-GGGR-R5124-000 Attachment A Split Sample Assessment Form Survey Area Survey 0008 Survey Discharge Canal#: 9106 Unit #: Unit Name: Sample Plan or WPIR#: 2006-021 SML #: 9106-0008-006 Sample
Description:
Comparison of split samples collected from sample measurement location #03 and analyzed using gamma spectroscopy by an off-site vendor laboratory.
The standard sample was 9106-0008-006F the comparison sample was 9106-0008-006FS.
STANDARD COMPARISON Radionuclide Activity Standard Resolution Agreement Activity Standard Comparison Acceptable (Y/N)Value Error Range Value Error Ratio Cs-137 4.92E-01 3.63E-02 14 0.6- 1.66 6.01E-01 5.OOE-02 1.22 Y Co-60 7.79E-01 4.90E-02 16 0.75 -1.33 1.34E+00 7.OOE-02 1.72 N Sr-90 5.59E-03 6.50E-03 I NONE- 8.75E-04 7.05E-03 0.16 N/A Ni-63 2.28E+00 5.05E+00 0 NONE 1.88E-01 3.05E+00 0.08 N/A K-40 1.37E+01 6.85E-01 20 0.75- 1.33 1.49E+01 7.45E-01 1.09 Y tomments/Correcuve -ActI1os:
In consileratlon o1 ,Mr-J0 m, I,4 63 results, guidance for agreement ranges, obtained from USNRC Inspection Procedure 84750, does not address resolution ratios less than 4, therefore, a determination of acceptability for such rations cannot be made. Co-60 has a likelyhood to be present in the sample matrix in particulate form, one would not neccassarily expect it to be homogenuously mixed from processing of the sample-split aliqot. Since Cs-137 and K-40 were found to be present at an acceptable levels of agreement, no further action is warranted.
I able is provideu to snow acceptance criteria used to assess split samples.Resolution I Agreement Range 4 8 16 51 7 15 50 200> 200 0.50 0.60 0.75 0.80 0.85 2.00 1.66 1.33 1.25 1.18 Performed By: WPIR -Work Plan and Inspection Record SML -Sample Measurement Location designation Page I of I Connecticut Yankee Decommissioning Project Health Physics Procedure 24265-000-GPR-GGGR-R5124-000 Attachment A Split Sample Assessment Form Survey 9106 Survey 0008 Survey Unit Dis Area#: Unit #: Name: charge Canal Sample Plan or WPIR#: 2006-0021 SML #: 9106-0008-010 Sample
Description:
Comparison of split samples collected from sample measurement location #10 and analyzed using gamma spectroscopy by an off-site vendor laboratory.
The standard sample was 9106-0008-01OF the comparison sample was 9106-0008-01 OFS.STANDARD COMPARI SON Radionuclide Activity Standard Resolution Agreement Activity Standard Comparison Acceptable Value Error Range Value Error Ratio (Y/N)Cs-137 3.36E-01 3.45E-02 10 0.6- 1.66 3.02E-01 2.87E-02 0.90 Y Co-60 2.46E-01 2.51E-02 10 0.6- 1.66 3.28E-01 2.96E-02 1.33 Y Sr-90 3.47E-03 6.05E-03 I NONE 8.59E-03 8.50E-03 2.48 N/A Ni-63 1.23E-01 2.99E+00 0 NONE -1.63E+00 3.35E+00 -13.25 N/A K-40 1.37E+01 6.85E-01 20 0.75 1.33 1.49E+0I 7.45E-01 1.09 Y Comments/Corrective Actions: In consideration of Sr-90 & Ni-63 results, guidance for agreement ranges, obtained from USNRC Inspection Procedure 84750, does not address resolution ratios less than 4, therefore, a determination of acceptability for such rations cannot be made. Since Cs-137, Co 60 and K-40 were found to be present at an acceptable levels of agreement, no further action is warranted.
Table is provided to show acceptance criteria used to assess split samples.Resolution Agreement Range 4 8 16 51 7 15 0.50 0.60 50 200> 200 0.75 0.80 0.85 2.00 1.66 1.33 1.25 1.18 Performed By: WPIR -Work Plan and Inspection Record SML -Sample Measurement Location designation Page I of I DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Attachment 2c Preliminary Data Form (1 Page)
Health Physics Procedure GPP-GGGR-R5121-001 Attachment B, Rev. CY-001 MAJOR Preliminary Data Review Form -Samples for the Sign Test Survey Unit: 9106- 0008 Survey Unit Name: Discharge Canal Classification:
Survey Media: Type of Survey: Type of Measurement:
Number of Measurements:
Operational DCGL: 2 Soil Final Status Survey Radionuclide Specific 14 1 BASIC STATISTICAL QUANTITIES Cs-137 Co-60 Sr-90 Ni-63 Minimum Value: -8.91E-03
-1.45E-02
-1.92E-02
-4.84E+00 Maximum Value: 4.92E-01 9.17E-01 2.03E-02 2.28E+00 Mean: 1.78E-01 1.98E-01 3.34E-03 -1.38E+00 Median: 1.26E-01 7.60E-02 4.44E-03 -1.76E+00 Standard Deviation:
1.85E-01 2.95E-01 1.04E-02 1.87E+00 RADIONUCLIDE CONCENTRATION (pCi/g)NUMBER 9106-0008-001 F 9106-0008-002F 9106-0008-003F 9106-0008-004F 9106-0008-005F 9106-0008-006F 9106-0008-007F 9106-0008-008F 9106-0008-009F 9106-0008-01OF 9106-0008-011 F 9106-0008-012F 9106-0008-013F 9106-0008-014F Performed By: Independent Review: Cs-137 3.96E-01-8.91 E-03 2.05E-01 4.32E-02 2.66E-01 4.92E-01 2.29E-02 4.72E-01 1.55E-02 3.36E-01 6.76E-02 1.84E-01 1.03E-02-3.89E-03 Co-60 1.33E-01 7.77E-03 3.24E-01 O.OOE+00 2.75E-02 7.79E-01 2.68E-02 9.17E-01-1.08E-02 2.46E-01 1.22E-01 1.79E-01 2.99E-02-1.45E-02 Sr-90 5.79E-03 2.03E-02 1.12E-02-6.19E-03 8.28E-04 5.59E-03-8.81 E-04-2.69E-03-5.90E-03 3.47E-03 1.93E-02-1.92E-02 9.80E-03 5.40E-03 Ni-63 2.33E-01-4.84E+00-2.74E+00-1.80E+00-8.58E-01 2.28E+00-2.33E+00-4.12E-01-2.05E+00 1.23E-01-3.34E+00 8.39E-01-2.70E+00-1.72E+00 A'Date: 10o-31-0o4 Date: 0// /Oz-J ar DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Attachment 2d Graphical Representation of Data (8 Pages)
Health Physics Procedure GGGR-R5123-Rev.CY-001 Attachment C Health Physics Procedure GGGR-R5123-Rev.CY-OO1 Attachment C Quantile Plot For Cesium -137 Survey Unit: 9106-0008 Survey Unit Name: Discharge Canal Mean: 1.78E-01 pCi/g 6.OOE-01 5.OOE-01 " -O 4.OOE-01 ---, 0.0 3.OOE-01 .2.OOE-01= 1.OOE-01 0) O.OOE+00 ---__ "-1.OOE-01 2'"2 40 60 8 '1 Percentage Cs-1 37 Rank Percentage
-8.91 E-03 1 4 %-3.89E-03 2 11 %1.03E-02 3 18 %1.55E-02 4 25 %2.29E-02 5 32 %4.32E-02 6 39 %6.76E-02 7 46 %1.84E-01 8 54 %2.05E-01 9 61 %2.66E-01 10 68 %3.36E-01 11 75 %3.96E-01 12 82 %4.72E-01 13 89 %4.92E-01 14 96 %Prepared By: Reviewed By: Date: 31-0 1 Date: //6" Health Physics Procedure GGGR-R5123-Rev.CY-001 Attachment C Health Physics Procedure GGGR-R5 123-Rev.CY-001 Attachment C Quantile Plot For Cobalt -60 Survey Unit: Survey Unit Name: Mean: 9106-0008 Discharge Canal 1.98E-01 pCi/g 1.OOE+00-,_ 8.OOE-01 -E 6.OOE-01 0 4.00E-01 2.OOE-01 *0 0.OOE+00 --, 2_ _- -----20 4 60 80-2.PcE-01en Percentage Co-60 Rank Percentage
-1.45E-02 1 .4 %-1.08E-02 2 11 %O.OOE+00 3 18 %7.77E-03 4 25 %2.68E-02 5 32 %2.75E-02 6 39 %2.99E-02 7 46 %1.22E-01 8 54 %1.33E-01 9 61 %1.79E-01 10 68 %2.46E-01 11 75 %3.24E-01 12 82 %7.79E-01 13 89 %9.17E-01 14 96 %Prepared By: Reviewed By: 4~4b Date: Date: /1111/ 61K Health Physics Procedure GGGR-R5123-Rev.CY-001 Attachment C Health Physics Procedure GGGR-R5123-Rev.CY-0O1 Attachment C Quantile Plot For Strontium
-90 Survey Unit: 9106-0008 Survey Unit Name: Discharge Canal Mean: 3.34E-03 pCi/g 2.50E-02 2.OOE-02 -- -1.50E-02'.) 1.OOE-02 _ -0.r-5.00E-03
-,* *0 0.0OE+00 ----5.OOE-03
--0 ;L0 -- 0~-1.00E-02_
0 C3-1.50E-02
--2.OOE-02
--2.50E-02 Percentage Sr-90 Rank Percentage
-1.92E-02 1 4 %-6.19E-03 2 11 %-5.90E-03 3 18 %-2.69E-03 4 25 %-8.81 E-04 5 32 %8.28E-04 6 39 %3.47E-03 7 46 %5.40E-03 8 54 %5.59E-03 9 61 %5.79E-03 10 68 %9.80E-03 11 75 %1.12E-02 12 82 %1.93E-02 13 89 %2.03E-02 14 96 %Prepared By: Reviewed By: Date: Date: /1 / :
Health Physics Procedure GGGR-R5123-Rev.CY-001 Attachment C Quantile Plot For Nickel -63 Survey Unit: 9106-0008 Survey Unit Name: Discharge Canal Mean: -1.38E+00 pCi/g 2.50E-02 2.OOE-02 --1.50E-02-1.OOE-02 C.r- 5.OOE-03 O.OOE+02 -S-5.OOE-03 T~0 T - -@ -40 4)S-1.OOE-02
-_---0 0 -1.50E-02
-- ---- ---_- --2.OOE-02
-_-__ _-2.50E-02 Percentage Ni-63 Rank Percentage
-4.84E+00 1 4 %-3.34E+00 2 11 %-2.74E+00 3 18 %-2.70E+00 4 25 %-2.33E+00 5 32 %-2.05E+00 6 39 %-1.80E+00 7 46 %-1.72E+00 8 54 %-8.58E-01 9 61 %-4.12E-01 10 68 %1.23E-01 11 75 %2.33E-01 12 82 %8.39E-01 13 89 %2.28E+00 14 96 %Prepared By: Date: Date: Reviewed By:
Health Physics Procedure GGGR-R5123-Rev.CY-001 Attachment C Frequency Plot For Cesium-137 Survey Unit: 9106-0008 Survey Unit Name: Discharge Canal Mean: 0.178 pCi/g 6 5 --4-4 22* .ME 0 0.00 0.10 0.20 0.30 0.40 0.50 Upper End Value (pCilg)Upper End Observation Observation
%Value Frequency Frequency 0.00 2 14%0.10 5 36%0.20 1 7%0.30 2 14%0.40 2 14%0.50 2 14%Total 14 100%Prepared By: Date: 10- 31 -VýReviewed By: Date: / / , Z6/1 Health Physics Procedure GGGR-R5123-Rev.CY-001 Attachment C Frequency Plot For Cobalt-60 Survey Unit: 9106-0008 Survey Unit Name: Discharge Canal Mean: 0.198 pCi/g 10 8 G) 6 C" 4-2f 0 i I 0.00 0.25 0.50 0.75 1.00 Upper End Value (pCi/g)Upper End Observation Observation
%Value Frequency Frequency 0.00 3 21%0.25 8 57%0.50 1 7%0.75 0 0%1.00 2 14%Total 14 100%Prepared By: 61 ýIz Date: /0-3/-o" Date: 1(1 £~l,4*~2 Reviewed By:
Health Physics Procedure GGGR-R5123-Rev.CY-001 Attachment C Frequency Plot For Strontium-90 Survey Unit: 9106-0008 Survey Unit Name: Discharge Canal Mean: 0.003 pCi/g 6 5 O2 U- 0 i I W .1 I N -L 0.000 0.005 0.010 0.015 0.020 0.025 Upper End Value (pCi/g)Upper End Observation Observation
%Value Frequency Frequency 0.000 5 36%0.005 2 14%0.010 4 29%0.015 1 7%0.020 1 7%0.025 1 7%Total 14 100%Prepared By: Date: ,-/-OýReviewed By:Dt //Date: /1, Health Physics Procedure GGGR-R5123-Rev.CY-001 Attachment C Frequency Plot For Nickel-63 Survey Unit: Survey Unit Name: 9106-0008 Discharge Canal Mean: -1.380 pCi/g 5>4-03 U-0-2-3.00 -2.00 -1.00 0.00 1.00 2.00 3.00 Upper End Value (pCi/g)Observatio Observation Upper End n %Value Frequency Frequency-3.00 2 14%-2.00 4 29%-1.00 2 14%0.00 2 14%1.00 3 21%2.00 0 0%3.00 1 7%Total 14 100%Prepared By: Date: &f/- / -o Reviewed By: _D Date: //ZýA/,
DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Attachment 2e Sign Test Calculation (1 Page)
Health Physics Procedure 3PP-GGGR-R512 1 -000 Attachment A, Rev. CY-00 I MAJOR Health Physics Procedure 3PP-GGGR-R5121-000 Attachment A, Rev. CY-OQi MAJOR Sign Test Calculation Sheet For Multiple Radionuclisdes rvey Unit Numb, 9106-0008 rvey Unit Name: Discharge Canal WP&IR#: 2006-021 Classification
- 2 TYPE I (cc error):0.05 TYPE I (3 error):0.05 Radionuclides:
Cs-137 Co-60 Sr-90 Ni-63 Survey Design DCGL (pCi/g): 6.01 2.9 1.18 549 Results Cs-137 Results Co-60 Results Sr-90 Results Ni-63 Weighted Sum DCGL-Result Sign (Wi)3.96E-01 1.33E-01 1.33E-01 1.33E-01 1. 17E-01 8.83E-01 1-8.91E-03 7.77E-03 7.77E-03 7.77E-03 1.84E-02 9.82E-01 1 2.05E-01 3.24E-01 3.24E-01 3.24E-01 1.55E-01 8.45E-01 1 4.32E-02 0.OOE+00 0.OOE+00 0.OOE+00 1.94E-03 9.98E-01 1 2.66E-01 2.75E-02 2.75E-02 2.75E-02 5.44E-02 9.46E-01 1 4.92E-01 7.79E-01 7.79E-01 7.79E-01 3.55E-01 6.45E-01 1 2.29E-02 2.68E-02 2.68E-02 2.68E-02 1.23E-02 9.88E-01 1 4.72E-01 9.17E-01 9.17E-01 9.17E-01 3.92E-01 6.08E-01 1 1.55E-02 -1.08E-02
-1.08E-02
-1.08E-02
-6.15E-03 1.00E+00 1 3.36E-01 2.46E-01 2.46E-01 2.46E-01 1.44E-01 8.56E-01 1 6.76E-02 1.22E-01 1.22E-01 1.22E-01 6.97E-02 9.30E-01 1 1.84E-01 1.79E-01 1.79E-01 1.79E-01 7.61E-02 9.24E-01 1 1.03E-02 2.99E-02 2.99E-02 2.99E-02 2.03E-02 9.80E-01 1-3.89E-03
-1.45E-02
-1.45E-02
-1.45E-02
-1.07E-03 1.00E+00 1 Number of Positive Differences (S+): 14 Critical Value: 11 Survey Unit: Meets Acceptance Criterion Performed By: ( Date: I9- ?/-061 pendent Review: _ ___ -Date: Page 1 of I DISCHARGE CANAL SURVEY UNIT 9106-0008 RELEASE RECORD Attachment 2f COMPASS DQA Surface Soil Report with Retrospective Power Curve (4 Pages)
DQA Surface Soil Report Assessment Summary Site: Planner(s):
Survey Unit Name: Report Number: Survey Unit Samples: Reference Area Samples: Test Performed:
Judgmental Samples: Assessment
==
Conclusion:==
9106-0008 (19 mrem/yr)Dale Randall 9106-0008 1 14 0 Sign Test Result: Not Performed 0 EMC Result: Not Performed Reject Null Hypothesis (Survey Unit PASSES)Retrospective Power Curve U 1~=C, I.1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 iI_ijzi ":_,1T --_0.0 0.2 0.4 0.6 0.8 1.0 Unity Rule Sum-of-Ratios, including background
--Prospective Power U 1-beta ....Actual Power-LBGR --Estimated Power DCGL --- -Retrospective Power 1.2 COMPASS vi.0.0 111112006 Page 1
~DQA Surface Soil Report Survey Unit Data NOTE: Type = "S" indicates survey unit sample.Type = "R" indicates reference area sample.Sample Number 9106-0008-001 F 9106-0008-002F 9106-0008-003F 9106-0008-004F 9106-0008-005F 9106-0008-006F 9106-0008-007F 9106-0008-008F 9106-0008-009F 9106-0008-01 OF 9106-0008-011 F 9106-0008-012F 9106-0008-013F 9106-0008-014F Sample Number 9106-0008-001 F 9106-0008-002F 9106-0008-003F 9106-0008-004F 9106-0008-005F 9106-0008-006F 9106-0008-007F 9106-0008-008F 9106-0008-009F 9106-0008-01OF 9106-0008-011F 9106-0008-012F 9106-0008-013F 9106-0008-014F Type S S S S S S S S S S S S S S Type S S S S S S S S S S S S S S Co-60 (pCi/g)0.13 0.01 0.32 0 0.03 0.78 0.03 0.92-0.01 0.25 0.12 0.18 0.03-0.01 Cs-137 (pCi/g)0.4-0.01 0.2 0.04 0.27 0.49 0.02 0.47 0.02 0.34 0.07 0.18 0.01 0 Ni-63 (pCilg)0.23-4.84-2.74-1.8-0.86 2.28-2.33-0.41-2.05 0.12-3.34 0.84-2.7-1.72 SrY-90 (pCi/g)0.01 0.02 0.01-0.01 0 0.01 0 0-0.01 0 0.02-0.02 0.01 0.01 COMPASS v1.0.0.P 1111112006 Page 2 DQA Surface Soil Report Modified Data (Unity Rule SOR)NOTE: Type = "S" indicates survey unit sample.Type = "R" indicates reference area sample.Sample Number 9106-0008-001 F 9106-0008-002F 9106-0008-003F 9106-0008-004F 9106-0008-005F 9106-0008-006F 9106-0008-007F 9106-0008-008F 9106-0008-009F 9106-0008-01OF 9106-0008-011F 9106-0008-012F 9106-0008-013F 9106-0008-014F Type S S S S S S S S S S S S S S Sum-of-Ratios (SOR)0.12 0.01 0.15 0 0.05 0.36 0.01 0.39-0.01 0.14 0.06 0.08 0.02 0 COMPASS vl.0.0 1111112006 Page 3
'K3 DQA Surface Soil Report Basic Statistical Quantities Summary Statistic Survey Unit Background DQO Results Sample Number 14 N/A N=13 Mean (SOR) 0.10 N/A 0.17 Median (SOR) 0.06 N/A N/A Std Dev (SOR) 0.13 N/A 0.09 High Value (SOR) 0.39 N/A N/A Low Value (SOR) -0.01 N/A N/A COMPASS v1.0.0 111/12006 Page 4