ML18095A733

From kanterella
Revision as of 05:52, 3 February 2020 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search
Proposed Tech Spec 4.7.1.5 & Table 2.2-5 Allowing Continued Use of 8 MSIV Stroke Time During 10th Fuel Cycle
ML18095A733
Person / Time
Site: Salem PSEG icon.png
Issue date: 02/01/1991
From:
Public Service Enterprise Group
To:
Shared Package
ML18095A732 List:
References
NUDOCS 9102080144
Download: ML18095A733 (3)


Text

' .

INITIATING SIGNAL AND FUNCTION TABLE 3.3-5 (Continued~

ENGINEERED SAFETY FEATURES RESPONSE TIMES RESPONSE TIME IN SECONDS

3. Pressurizer Pressure-I.ow
a. Safety Injection (ECCS) s 21.0< 1 >;12.0< 2 >
b. Reactor Trip (from SI) s 2.0
c. Feedwater Isolation s 7.0
d. Containment Isolation - Phase "A" s 18.0< 2 >
e. Containment Ventilation Isolation Not Applicable
f. Auxiliary Feedwater Pumps < 60
g. Service Water System ~ 49.0< 1 >;13.'0°< 2 >
4. Differential Pressure Betwee.n Steam Lines-High
a. Safety Inj action (ECCS') s ~2.0< 2 >;22.0< 3 >
b. Reactor Trip (from SI) s 2.0
c. Feedwater Isolation s 7 .0
d. Containment Isolation - Phase ~A" s ~17 .-0 ( 2.> /2 7.0 ( 3 )
e. Containment Ventilation Isolation Not Applicable
f. *Auxiliary Feedwater Pumps s 60
g. Service Water System s 13.0< 2 >/48.0< 3 >
5. Steam Flow in Two Steam Lines - High Coincident with Tavg -- Low-Low
a. Safety InJection (ECCS) s 15.75< 2 >;25,75< 3 >
b. Reactor Trip (from SI) s 5.75
c. Feedwater Isolation s 10.75
d. Containment Isolation - Phase "A" s 20.15< 2 >;30.15< 3 >
e. Containment Ventilation Isolation Not. Applicable
f. Auxiliary Feedwater Pumps s 61.75 .
g. Service Water System s 15.75< >;50.15< 3 >

2

h. St.eam Line Isolation s 10.75 *
  • Sl3.75 until restart following t~ta refueling outage.

0 SALEM - UNIT 1 3/4 3-28 Amendment No. 112

"t

  • TABLE 3.3-5 (Continue~

ENGINEERED SAFETY FEATURES RESPONSE TIMES INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS

6. Steam Flow in Two Steam Lines-High Coincident with Steam Line Pressure - Low
a. Safety Injection (ECCS) s 12.0< 2 );22.0< 3 )
b. Reactor Trip (from SI) s 2.0
c. Feedwater Isolation s 7.0
d. Containment Isolation-Phase "A" s 17.0< 2 );21.0< 3 )
e. Containment Ventilation Isolation Not Applicable
f. 0 Auxiliary Feedwater Pumps s 60 .*
g. Service ~at~r System s 14.~~ 2 )/48.0( 3 )
h. * *. Steam Line IsOlatfon s 8.0*
7. Containment Pressur~--High-High
a. Containment Spray s ~5.0 b.* Containment Isolation-Phase "B". Not Applicable
c. Steam Line Isolation s 7.0 *
d. *C9ntainment Fan Cooler s 40.0.
8. Steam Generator Water Level--High-High
a. Turbine Trip s 2.5
b. Feedwater Isolation s 11.0*
9. Steam Generator Water Level--Low-Low
a. Motor-Driven Auxiliary_ *:Feed~ater Pumps(4) s 60.0
b. Turbine-Driven Auxiliary Feedwater Pumps(5) s 60.0 lte£+h I SlO.O seconds until restart following the ~*refueling outage.

SALEM - UNIT 1 3/4 3-29 Amendment No. 112

PLANT SYSTEMS MAIN STEAM LINE ISOLATION VALVES LIMITING CONDITION FOR OPERATION 3.7.1.S Each main steam line isolation valve shall be OPERABLE.

APPLICABILITY: MODES 1, 2 and 3.

ACTION; MODES 1 - With one main steam line isolation valve inoperable, POWER OPERATION may continue provided the inoperable valve is either restored to OPERABLE status or closed within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />; otherwise, be in HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ..

MODES 2 - With one main steam line isolation ~alve inoperable, and 3 sub~equent operation in MODES 1, 2 or 3 may proceeA:provided;

. a. The isolation valve h maintained closed.

b. The. provisions of Specification 3.0.4 ar~n6t applicable.

Otherwise, be in HOT SHUTDOWN within. the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.7.l\S Each main steam line isolation v1lve shall be demonstrated OPERABLE by verifying full closure within 5 seconds when tested pursuant to o Specification 4.0.5.

    • 8 seconds until restart following t!e!a!s~ refueling outage.

0 SALEM - UNIT 1 3/4 7-10 Amendment No. 112