ML060950596: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(StriderTol Bot change)
 
(One intermediate revision by the same user not shown)
Line 19: Line 19:


=Text=
=Text=
{{#Wiki_filter:AUDIT WORKSHEET GALL REPORT AMP PLANT: ______________________________
{{#Wiki_filter:XI.M27 Fire Water System 1
LRA AMP: __________________________                                                       REVIEWER: ______________________
AUDIT WORKSHEET GALL REPORT AMP PLANT: ______________________________
GALL AMP: XI.M27, Fire Water System                                                       DATE: __________________________
LRA AMP: __________________________
Program               Auditable GALL Criteria                                             Documentation of Audit Finding Element Program               A. This aging management program (AMP) applies to water-           Consistent with GALL AMP:      Yes  No Description          based fire protection systems that consist of sprinklers, nozzles, Document(s) used to confirm Criteria:
REVIEWER: ______________________
fittings, valves, hydrants, hose stations, standpipes, water storage tanks, and aboveground and underground piping and components that are tested in accordance with the applicable National Fire Protection Association (NFPA) codes and               Comment:
GALL AMP: XI.M27, Fire Water System DATE: __________________________
standards. Such testing assures the minimum functionality of the systems. Also, these systems are normally maintained at required operating pressure and monitored such that loss of system pressure is immediately detected and corrective actions initiated.
Program Element Auditable GALL Criteria Documentation of Audit Finding Program Description A. This aging management program (AMP) applies to water-based fire protection systems that consist of sprinklers, nozzles, fittings, valves, hydrants, hose stations, standpipes, water storage tanks, and aboveground and underground piping and components that are tested in accordance with the applicable National Fire Protection Association (NFPA) codes and standards. Such testing assures the minimum functionality of the systems. Also, these systems are normally maintained at required operating pressure and monitored such that loss of system pressure is immediately detected and corrective actions initiated.
B. A sample of sprinkler heads is to be inspected by using the     Consistent with GALL AMP:      Yes  No guidance of NFPA 25 Inspection, Testing and Maintenance of         Document(s) used to confirm Criteria:
Consistent with GALL AMP:
Water-Based Fire Protection Systems (1998 Edition), Section 2-3.1.1, or NFPA 25 (2002 Edition), Section 5.3.1.1.1. This NFPA section states where sprinklers have been in place for 50 years, they shall be replaced or representative samples from       Comment:
Yes No Document(s) used to confirm Criteria:
one or more sample areas shall be submitted to a recognized testing laboratory for field service testing. It also contains guidance to perform this sampling every 10 years after the initial field service testing.
Comment:
XI.M27 Fire Water System                                                                1
B. A sample of sprinkler heads is to be inspected by using the guidance of NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems (1998 Edition), Section 2-3.1.1, or NFPA 25 (2002 Edition), Section 5.3.1.1.1. This NFPA section states where sprinklers have been in place for 50 years, they shall be replaced or representative samples from one or more sample areas shall be submitted to a recognized testing laboratory for field service testing. It also contains guidance to perform this sampling every 10 years after the initial field service testing.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:


Program               Auditable GALL Criteria                                             Documentation of Audit Finding Element C. The fire protection system piping is to be subjected to         Consistent with GALL AMP:      Yes  No required flow testing in accordance with guidance in NFPA 25 to     Document(s) used to confirm Criteria:
XI.M27 Fire Water System 2
verify design pressure or evaluated for wall thickness (e.g., non-intrusive volumetric testing or plant maintenance visual inspections) to ensure that aging effects are managed and that wall thickness is within acceptable limits. These inspections are   Comment:
Program Element Auditable GALL Criteria Documentation of Audit Finding C. The fire protection system piping is to be subjected to required flow testing in accordance with guidance in NFPA 25 to verify design pressure or evaluated for wall thickness (e.g., non-intrusive volumetric testing or plant maintenance visual inspections) to ensure that aging effects are managed and that wall thickness is within acceptable limits. These inspections are performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. The plant-specific inspection intervals are to be determined by engineering evaluation of the fire protection piping to ensure that degradation will be detected before the loss of intended function. The purpose of the full flow testing and wall thickness evaluations is to ensure that corrosion, MIC, or biofouling is managed such that the system function is maintained.
performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. The plant-specific inspection intervals are to be determined by engineering evaluation of the fire protection piping to ensure that degradation will be detected before the loss of intended function. The purpose of the full flow testing and wall thickness evaluations is to ensure that corrosion, MIC, or biofouling is managed such that the system function is maintained.
Consistent with GALL AMP:
: 1. Scope of           A. The AMP focuses on managing loss of material due to             Consistent with GALL AMP:      Yes  No Program              corrosion, MIC, or biofouling of carbon steel and cast-iron         Document(s) used to confirm Criteria:
Yes No Document(s) used to confirm Criteria:
components in fire protection systems exposed to water. Hose stations and standpipes are considered as piping in the AMP.
Comment:
: 1. Scope of Program A. The AMP focuses on managing loss of material due to corrosion, MIC, or biofouling of carbon steel and cast-iron components in fire protection systems exposed to water. Hose stations and standpipes are considered as piping in the AMP.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment
Comment
: 2. Preventive         A. To ensure no significant corrosion, MIC, or biofouling has       Consistent with GALL AMP:      Yes  No Actions              occurred in water-based fire protection systems, periodic           Document(s) used to confirm Criteria:
: 2. Preventive Actions A. To ensure no significant corrosion, MIC, or biofouling has occurred in water-based fire protection systems, periodic flushing, system performance testing, and inspections may be conducted.
flushing, system performance testing, and inspections may be conducted.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:
Comment:
: 3. Parameters         A. Loss of material due to corrosion and biofouling could reduce   Consistent with GALL AMP:      Yes  No Monitored/            wall thickness of the fire protection piping system and result in   Document(s) used to confirm Criteria:
: 3. Parameters Monitored/
Inspected            system failure. Therefore, the parameters monitored are the systems ability to maintain pressure and internal system corrosion conditions.
Inspected A. Loss of material due to corrosion and biofouling could reduce wall thickness of the fire protection piping system and result in system failure. Therefore, the parameters monitored are the systems ability to maintain pressure and internal system corrosion conditions.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:
 
XI.M27 Fire Water System 3
Program Element Auditable GALL Criteria Documentation of Audit Finding B. Periodic flow testing of the fire water system is performed using the guidelines of NFPA 25, or wall thickness evaluations may be performed to ensure that the system maintains its intended function.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:
Comment:
XI.M27 Fire Water System                                                                2
: 4. Detection of Aging Effects A. Fire protection system testing is performed to assure that the system functions by maintaining required operating pressures.
Wall thickness evaluations of fire protection piping are performed on system components using non-intrusive techniques (e.g., volumetric testing) to identify evidence of loss of material due to corrosion. These inspections are performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. As an alternative to non-intrusive testing, the plant maintenance process may include a visual inspection of the internal surface of the fire protection piping upon each entry to the system for routine or corrective maintenance, as long as it can be demonstrated that inspections are performed (based on past maintenance history) on a representative number of locations on a reasonable basis. These inspections must be capable of evaluating (1) wall thickness to ensure against catastrophic failure and (2) the inner diameter of the piping as it applies to the design flow of the fire protection system. If the environmental and material conditions that exist on the interior surface of the below grade fire protection piping are similar to the conditions that exist within the above grade fire protection piping, the results of the inspections of the above grade fire protection piping can be extrapolated to evaluate the condition of below grade fire protection piping. If not, additional inspection activities are needed to ensure that the intended function of below grade fire protection piping will be maintained consistent with the current licensing basis for the period of extended operation. Continuous system pressure monitoring, system flow Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:


Program               Auditable GALL Criteria                                               Documentation of Audit Finding Element B. Periodic flow testing of the fire water system is performed        Consistent with GALL AMP:       Yes   No using the guidelines of NFPA 25, or wall thickness evaluations        Document(s) used to confirm Criteria:
XI.M27 Fire Water System 4
may be performed to ensure that the system maintains its intended function.
Program Element Auditable GALL Criteria Documentation of Audit Finding testing, and wall thickness evaluations of piping are effective means to ensure that corrosion and biofouling are not occurring and the systems intended function is maintained.
B. General requirements of existing fire protection programs include testing and maintenance of fire detection and protection systems and surveillance procedures to ensure that fire detectors, as well as fire protection systems and components are operable.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:
Comment:
: 4. Detection of       A. Fire protection system testing is performed to assure that the    Consistent with GALL AMP:       Yes   No Aging Effects        system functions by maintaining required operating pressures.        Document(s) used to confirm Criteria:
C. Visual inspection of yard fire hydrants performed annually in accordance with NFPA 25 ensures timely detection of signs of degradation, such as corrosion. Fire hydrant hose hydrostatic tests, gasket inspections, and fire hydrant flow tests, performed annually, ensure that fire hydrants can perform their intended function and provide opportunities for degradation to be detected before a loss of intended function can occur.
Wall thickness evaluations of fire protection piping are performed on system components using non-intrusive techniques (e.g., volumetric testing) to identify evidence of loss of material due to corrosion. These inspections are performed        Comment:
Consistent with GALL AMP:
before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. As an alternative to non-intrusive testing, the plant maintenance process may include a visual inspection of the internal surface of the fire protection piping upon each entry to the system for routine or corrective maintenance, as long as it can be demonstrated that inspections are performed (based on past maintenance history) on a representative number of locations on a reasonable basis. These inspections must be capable of evaluating (1) wall thickness to ensure against catastrophic failure and (2) the inner diameter of the piping as it applies to the design flow of the fire protection system. If the environmental and material conditions that exist on the interior surface of the below grade fire protection piping are similar to the conditions that exist within the above grade fire protection piping, the results of the inspections of the above grade fire protection piping can be extrapolated to evaluate the condition of below grade fire protection piping. If not, additional inspection activities are needed to ensure that the intended function of below grade fire protection piping will be maintained consistent with the current licensing basis for the period of extended operation. Continuous system pressure monitoring, system flow XI.M27 Fire Water System                                                                  3
Yes No Document(s) used to confirm Criteria:
Comment:
D. Sprinkler heads are inspected before the end of the 50-year sprinkler head service life and at 10-year intervals thereafter during the extended period of operation to ensure that signs of degradation, such as corrosion, are detected in a timely manner.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:
: 5. Monitoring and Trending A. System discharge pressure is monitored continuously.
Results of system performance testing are monitored and trended as specified by the associated plant commitments pertaining to NFPA codes and standards. Degradation identified by non-intrusive or internal inspection is evaluated.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:


Program               Auditable GALL Criteria                                             Documentation of Audit Finding Element testing, and wall thickness evaluations of piping are effective means to ensure that corrosion and biofouling are not occurring and the systems intended function is maintained.
XI.M27 Fire Water System 5
B. General requirements of existing fire protection programs        Consistent with GALL AMP:       Yes   No include testing and maintenance of fire detection and protection    Document(s) used to confirm Criteria:
Program Element Auditable GALL Criteria Documentation of Audit Finding
systems and surveillance procedures to ensure that fire detectors, as well as fire protection systems and components are operable.
: 6. Acceptance Criteria A. The acceptance criteria are (a) the ability of a fire protection system to maintain required pressure, (b) no unacceptable signs of degradation observed during non-intrusive or visual assessment of internal system conditions, and (c) that no biofouling exists in the sprinkler systems that could cause corrosion in the sprinkler heads.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:
Comment:
C. Visual inspection of yard fire hydrants performed annually in    Consistent with GALL AMP:      Yes  No accordance with NFPA 25 ensures timely detection of signs of        Document(s) used to confirm Criteria:
: 7. Corrective Actions A. Repair and replacement actions are initiated as necessary.
degradation, such as corrosion. Fire hydrant hose hydrostatic tests, gasket inspections, and fire hydrant flow tests, performed annually, ensure that fire hydrants can perform their intended function and provide opportunities for degradation to be            Comment:
For fire water systems and components identified within scope that are subject to an AMR for license renewal, the applicants 10 CFR Part 50, Appendix B, program is used for corrective actions, confirmation process, and administrative controls for aging management during the period of extended operation. As discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable to address the corrective actions, confirmation process, and administrative controls.
detected before a loss of intended function can occur.
Consistent with GALL AMP:
D. Sprinkler heads are inspected before the end of the 50-year      Consistent with GALL AMP:       Yes   No sprinkler head service life and at 10-year intervals thereafter    Document(s) used to confirm Criteria:
Yes No Document(s) used to confirm Criteria:
during the extended period of operation to ensure that signs of degradation, such as corrosion, are detected in a timely manner.
Comment:
Comment:
: 5. Monitoring        A. System discharge pressure is monitored continuously.             Consistent with GALL AMP:       Yes   No and Trending          Results of system performance testing are monitored and            Document(s) used to confirm Criteria:
: 8.
trended as specified by the associated plant commitments pertaining to NFPA codes and standards. Degradation identified by non-intrusive or internal inspection is evaluated.
Confirmation Process A. See Item 7, above.
Consistent with GALL AMP:
Yes No Document(s) used to confirm Criteria:
Comment:
Comment:
XI.M27 Fire Water System                                                                4
: 9.
 
Administrative Controls A. See Item 7, above.
Program              Auditable GALL Criteria                                              Documentation of Audit Finding Element
Consistent with GALL AMP:
: 6. Acceptance        A. The acceptance criteria are (a) the ability of a fire protection  Consistent with GALL AMP:      Yes  No Criteria              system to maintain required pressure, (b) no unacceptable signs Document(s) used to confirm Criteria:
Yes No Document(s) used to confirm Criteria:
of degradation observed during non-intrusive or visual assessment of internal system conditions, and (c) that no biofouling exists in the sprinkler systems that could cause corrosion in the sprinkler heads.                                    Comment:
Comment:
: 7. Corrective        A. Repair and replacement actions are initiated as necessary.        Consistent with GALL AMP:      Yes  No Actions              For fire water systems and components identified within scope        Document(s) used to confirm Criteria:
: 10. Operating Experience A. Water-based fire protection systems designed, inspected, tested and maintained in accordance with the NFPA minimum standards have demonstrated reliable performance.
that are subject to an AMR for license renewal, the applicants 10 CFR Part 50, Appendix B, program is used for corrective actions, confirmation process, and administrative controls for aging management during the period of extended operation. As          Comment:
Consistent with GALL AMP:
discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable to address the corrective actions, confirmation process, and administrative controls.
Yes No Document(s) used to confirm Criteria:
: 8.                    A. See Item 7, above.                                                 Consistent with GALL AMP:      Yes  No Confirmation                                                                                Document(s) used to confirm Criteria:
Process Comment:
: 9.                    A. See Item 7, above.                                                Consistent with GALL AMP:      Yes   No Administrative                                                                              Document(s) used to confirm Criteria:
Controls Comment:
: 10. Operating         A. Water-based fire protection systems designed, inspected,           Consistent with GALL AMP:      Yes  No Experience            tested and maintained in accordance with the NFPA minimum             Document(s) used to confirm Criteria:
standards have demonstrated reliable performance.
XI.M27 Fire Water System                                                                  5
 
Program              Auditable GALL Criteria  Documentation of Audit Finding Element Comment:
XI.M27 Fire Water System                      6
 
EXCEPTIONS Item          Program Elements      LRA Exception Description  Basis for Accepting Exception  Documents Reviewed Number                                                                                          (Identifier, Para.# and/or Page #)
1.
2.


ENHANCEMENTS Item          Program Elements      LRA Enhancement Description Basis for Accepting Enhancement Documents Reviewed Number                                                                                          (Identifier, Para.# and/or Page #)
XI.M27 Fire Water System 6
1.
Program Element Auditable GALL Criteria Documentation of Audit Finding Comment:
2.


DOCUMENT REVIEWED DURING AUDIT Document Number             Identifier (number)       Title                                                 Revision and/or Date 1.
XI.M27 Fire Water System 7
2.
EXCEPTIONS Item Number Program Elements LRA Exception Description Basis for Accepting Exception Documents Reviewed (Identifier, Para.# and/or Page #)
3.
: 1.
4.
: 2.
.
ENHANCEMENTS Item Number Program Elements LRA Enhancement Description Basis for Accepting Enhancement Documents Reviewed (Identifier, Para.# and/or Page #)
XI.M27 Fire Water System                                                  7}}
: 1.
: 2.
DOCUMENT REVIEWED DURING AUDIT Document Number Identifier (number)
Title Revision and/or Date
: 1.
: 2.
: 3.
: 4.  
.}}

Latest revision as of 10:15, 15 January 2025

GALL AMP: XI.M27, Fire Water System (Audit Worksheet GALL Report AMP)
ML060950596
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 03/22/2006
From: Morgan M
NRC/NRR/ADRO/DLR/RLRC
To:
Office of Nuclear Reactor Regulation
morgan M NRR/NRC/DLR/RLRA, 415-2232
Shared Package
ML060950189 List: ... further results
References
%dam200611, TAC MC9668
Download: ML060950596 (5)


Text

XI.M27 Fire Water System 1

AUDIT WORKSHEET GALL REPORT AMP PLANT: ______________________________

LRA AMP: __________________________

REVIEWER: ______________________

GALL AMP: XI.M27, Fire Water System DATE: __________________________

Program Element Auditable GALL Criteria Documentation of Audit Finding Program Description A. This aging management program (AMP) applies to water-based fire protection systems that consist of sprinklers, nozzles, fittings, valves, hydrants, hose stations, standpipes, water storage tanks, and aboveground and underground piping and components that are tested in accordance with the applicable National Fire Protection Association (NFPA) codes and standards. Such testing assures the minimum functionality of the systems. Also, these systems are normally maintained at required operating pressure and monitored such that loss of system pressure is immediately detected and corrective actions initiated.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

B. A sample of sprinkler heads is to be inspected by using the guidance of NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection Systems (1998 Edition), Section 2-3.1.1, or NFPA 25 (2002 Edition), Section 5.3.1.1.1. This NFPA section states where sprinklers have been in place for 50 years, they shall be replaced or representative samples from one or more sample areas shall be submitted to a recognized testing laboratory for field service testing. It also contains guidance to perform this sampling every 10 years after the initial field service testing.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

XI.M27 Fire Water System 2

Program Element Auditable GALL Criteria Documentation of Audit Finding C. The fire protection system piping is to be subjected to required flow testing in accordance with guidance in NFPA 25 to verify design pressure or evaluated for wall thickness (e.g., non-intrusive volumetric testing or plant maintenance visual inspections) to ensure that aging effects are managed and that wall thickness is within acceptable limits. These inspections are performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. The plant-specific inspection intervals are to be determined by engineering evaluation of the fire protection piping to ensure that degradation will be detected before the loss of intended function. The purpose of the full flow testing and wall thickness evaluations is to ensure that corrosion, MIC, or biofouling is managed such that the system function is maintained.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

1. Scope of Program A. The AMP focuses on managing loss of material due to corrosion, MIC, or biofouling of carbon steel and cast-iron components in fire protection systems exposed to water. Hose stations and standpipes are considered as piping in the AMP.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment

2. Preventive Actions A. To ensure no significant corrosion, MIC, or biofouling has occurred in water-based fire protection systems, periodic flushing, system performance testing, and inspections may be conducted.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

3. Parameters Monitored/

Inspected A. Loss of material due to corrosion and biofouling could reduce wall thickness of the fire protection piping system and result in system failure. Therefore, the parameters monitored are the systems ability to maintain pressure and internal system corrosion conditions.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

XI.M27 Fire Water System 3

Program Element Auditable GALL Criteria Documentation of Audit Finding B. Periodic flow testing of the fire water system is performed using the guidelines of NFPA 25, or wall thickness evaluations may be performed to ensure that the system maintains its intended function.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

4. Detection of Aging Effects A. Fire protection system testing is performed to assure that the system functions by maintaining required operating pressures.

Wall thickness evaluations of fire protection piping are performed on system components using non-intrusive techniques (e.g., volumetric testing) to identify evidence of loss of material due to corrosion. These inspections are performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. As an alternative to non-intrusive testing, the plant maintenance process may include a visual inspection of the internal surface of the fire protection piping upon each entry to the system for routine or corrective maintenance, as long as it can be demonstrated that inspections are performed (based on past maintenance history) on a representative number of locations on a reasonable basis. These inspections must be capable of evaluating (1) wall thickness to ensure against catastrophic failure and (2) the inner diameter of the piping as it applies to the design flow of the fire protection system. If the environmental and material conditions that exist on the interior surface of the below grade fire protection piping are similar to the conditions that exist within the above grade fire protection piping, the results of the inspections of the above grade fire protection piping can be extrapolated to evaluate the condition of below grade fire protection piping. If not, additional inspection activities are needed to ensure that the intended function of below grade fire protection piping will be maintained consistent with the current licensing basis for the period of extended operation. Continuous system pressure monitoring, system flow Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

XI.M27 Fire Water System 4

Program Element Auditable GALL Criteria Documentation of Audit Finding testing, and wall thickness evaluations of piping are effective means to ensure that corrosion and biofouling are not occurring and the systems intended function is maintained.

B. General requirements of existing fire protection programs include testing and maintenance of fire detection and protection systems and surveillance procedures to ensure that fire detectors, as well as fire protection systems and components are operable.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

C. Visual inspection of yard fire hydrants performed annually in accordance with NFPA 25 ensures timely detection of signs of degradation, such as corrosion. Fire hydrant hose hydrostatic tests, gasket inspections, and fire hydrant flow tests, performed annually, ensure that fire hydrants can perform their intended function and provide opportunities for degradation to be detected before a loss of intended function can occur.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

D. Sprinkler heads are inspected before the end of the 50-year sprinkler head service life and at 10-year intervals thereafter during the extended period of operation to ensure that signs of degradation, such as corrosion, are detected in a timely manner.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

5. Monitoring and Trending A. System discharge pressure is monitored continuously.

Results of system performance testing are monitored and trended as specified by the associated plant commitments pertaining to NFPA codes and standards. Degradation identified by non-intrusive or internal inspection is evaluated.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

XI.M27 Fire Water System 5

Program Element Auditable GALL Criteria Documentation of Audit Finding

6. Acceptance Criteria A. The acceptance criteria are (a) the ability of a fire protection system to maintain required pressure, (b) no unacceptable signs of degradation observed during non-intrusive or visual assessment of internal system conditions, and (c) that no biofouling exists in the sprinkler systems that could cause corrosion in the sprinkler heads.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

7. Corrective Actions A. Repair and replacement actions are initiated as necessary.

For fire water systems and components identified within scope that are subject to an AMR for license renewal, the applicants 10 CFR Part 50, Appendix B, program is used for corrective actions, confirmation process, and administrative controls for aging management during the period of extended operation. As discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable to address the corrective actions, confirmation process, and administrative controls.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

8.

Confirmation Process A. See Item 7, above.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

9.

Administrative Controls A. See Item 7, above.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

Comment:

10. Operating Experience A. Water-based fire protection systems designed, inspected, tested and maintained in accordance with the NFPA minimum standards have demonstrated reliable performance.

Consistent with GALL AMP:

Yes No Document(s) used to confirm Criteria:

XI.M27 Fire Water System 6

Program Element Auditable GALL Criteria Documentation of Audit Finding Comment:

XI.M27 Fire Water System 7

EXCEPTIONS Item Number Program Elements LRA Exception Description Basis for Accepting Exception Documents Reviewed (Identifier, Para.# and/or Page #)

1.
2.

ENHANCEMENTS Item Number Program Elements LRA Enhancement Description Basis for Accepting Enhancement Documents Reviewed (Identifier, Para.# and/or Page #)

1.
2.

DOCUMENT REVIEWED DURING AUDIT Document Number Identifier (number)

Title Revision and/or Date

1.
2.
3.
4.

.