{{#Wiki_filter:Attachment 3 to ULNRC-06780 Page 1 of 11 Revised Technical Specification Pages (Markup) | {{#Wiki_filter:Attachment 3 to ULNRC -06780 Page 1 of 11 | ||
Revised Technical Specification Pages (Markup) | |||
(10 pages follow this cover sheet) | (10 pages follow this cover sheet) | ||
CompletionTimes 1.3 | |||
1.3 Completion Times | |||
EXAMPLES EXAMPLE 1.3-3 (continued) | |||
ACTIONS COMPLETION CONDITION REQUIRED ACTION TIME | |||
A One A.1 Restore Function X7 days Function X train to OPERABLE train status. AND inoperable. | |||
10 days from discovery of failure to meet the LCO | |||
B. One B.1 Restore Function Y 72 hours Function Y train to OPERABLE train status. AND inoperable. | |||
10 days from discovery of failure to meet the LCO | |||
C. One C.1 Restore Function X72 hours Function X train to OPERABLE train status. | |||
inoperable. | inoperable. | ||
OR AND C.2 Restore Function Y 72 hours One | OR AND C.2 Restore Function Y 72 hours One train to OPERABLE Function Y status. | ||
train inoperable. | train inoperable. | ||
(continued) | (continued) | ||
CALLAWAY | CALLAWAY 1.3-6 Amendment 133 PLANT RTS Instrumentation 3.3.1 | ||
TABLE 3.3.1-1 (page 5 of 8) | |||
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED | Reactor Trip System Instrumentation | ||
APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONSCONDITIONS CHANNELS REQUIREMENTS VALUE(a) | |||
: 16. Turbine Trip | : 16. Turbine Trip | ||
: a. | : a. L o w Fluid Oil1(j) 3 O M SR 3.3.1.10 539.42 psig | ||
: b. Turbine | |||
: 17. Safety | Pressure S R 3.3.1.15 | ||
: b. Turbine Stop1(j) 4 PN SR 3.3.1.10 1% open Valve Closure SR 3.3.1.15 | |||
: 17. Safety Injection1, 2 2 trains QP SR 3.3.1.14 NA (SI) Input from Engineered Safety Feature Actuation System (ESFAS) | |||
: 18. Reactor Trip System Interlocks | : 18. Reactor Trip System Interlocks | ||
: a. | : a. Intermediate2(e) 2 SR SR 3.3.1.11 6E-11 amp Range SR 3.3.1.13 Neutron Flux, P-6 | ||
: b. Low Power | : b. Low Power 1 1 per train TS SR 3.3.1.5 NA Reactor Trips Block, P-7 | ||
: c. Power | : c. Power Range1 4 TS SR 3.3.1.11 51.3% RTP Neutron Flux, SR 3.3.1.13 P-8 | ||
: d. Power Range 1 | : d. Power Range 1 4 TS SR 3.3.1.11 53.3% RTP Neutron Flux, SR 3.3.1.13 P-9 | ||
(a) The Allowable Value defines the limiting safety system setting except for Trip Functions 14.a and 14.b (the Nominal Trip Setpoint defines the limiting safety system setting for these Trip Functions). See the Bases for the Nominal Trip Setpoints. | |||
(e) Below the P-6 (Intermediate Range Neutron Flux) interlock. | (e) Below the P-6 (Intermediate Range Neutron Flux) interlock. | ||
(j) Above the P-9 (Power Range Neutron Flux) interlock. | (j) Above the P-9 (Power Range Neutron Flux) interlock. | ||
RTS Instrumentation 3.3.1 TABLE 3.3.1-1 (page 6 of 8) | CALLAWAY PLANT 3.3-23 Amendment No. 202 RTS Instrumentation 3.3.1 | ||
Reactor Trip System Instrumentation APPLICABLE MODES OR OTHER SPECIFIED | |||
TABLE 3.3.1-1 (page 6 of 8) | |||
Reactor Trip System Instrumentation | |||
APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONSCONDITIONS CHANNELS REQUIREMENTS VALUE(a) | |||
: 18. Reactor Trip System Interlocks | : 18. Reactor Trip System Interlocks | ||
: e. Power | : e. Power 1, 2 4 SR SR 3.3.1.11 6.7% RTP and Range SR 3.3.1.13 12.4% RTP Neutron Flux, P-10 | ||
: f. Turbine | : f. Turbine 1 2 TS SR 3.3.1.10 12.4% turbine Impulse SR 3.3.1.13 power Pressure, P-13 | ||
: 19. Reactor Trip | : 19. Reactor Trip SR 3.3.1.4 NA Breakers (RTBs)(k) 1, 2 2 trains RQ 3(b), 4(b), 5(b) 2 trains C SR 3.3.1.4 NA | ||
: 20. Reactor Trip | : 20. Reactor Trip 1, 2 1 each per U SR 3.3.1.4 NA Breaker RTB Undervoltage and Shunt Trip 3(b), 4(b), 5(b) 1 each per C SR 3.3.1.4 NA Mechanisms (k) RTB | ||
: 21. Automatic Trip | : 21. Automatic Trip 1, 2 2 trains QP SR 3.3.1.5 NA Logic 3(b), 4(b), 5(b) 2 trains C SR 3.3.1.5 NA | ||
(a) The Allowable Value defines the limiting safety system setting except for Trip Functions 14.a and 14.b (the Nominal Trip Setpoint defines the limiting safety system setting for these Trip Functions). See the Bases for the Nominal Trip Setpoints. | |||
(b) With Rod Control System capable of rod withdrawal or one or more rods not fully inserted. | (b) With Rod Control System capable of rod withdrawal or one or more rods not fully inserted. | ||
(k) Including any reactor trip bypass breakers that are racked in and closed for bypassing an RTB. | (k) Including any reactor trip bypass breakers that are racked in and closed for bypassing an RTB. | ||
ESFAS Instrumentation 3.3.2 ACTIONS (continued) | CALLAWAY PLANT 3.3-24 Amendment No. 202 ESFAS Instrumentation 3.3.2 | ||
CONDITION | |||
inoperable. | ACTIONS (continued) | ||
H.1 | CONDITION REQUIRED ACTION COMPLETION TIME H. One or more trains --------------------------NOTE----------------------- | ||
inoperable. One train may be bypassed for up to 4 hours for surveillance testing provided the other train is OPERABLE. | |||
H.1 Declare associated Immediately Pressurizer PORV(s) inoperable. | |||
I. One channel inoperable. --------------------------NOTE----------------------- | I. One channel inoperable. --------------------------NOTE----------------------- | ||
The inoperable channel may be bypassed for up to 12 hours for surveillance testing of other channels. | The inoperable channel may be bypassed for up to 12 hours for surveillance testing of other channels. | ||
I.1 | I.1 Place channel in trip. 72 hours OR In accordance with the Risk Informed Completion Time Program OR I.2 Be in MODE 3. 78 hours J. One channel inoperable. --------------------------NOTE----------------------- | ||
The inoperable channel may be bypassed for up to 2 hours for surveillance testing of other channels. | The inoperable channel may be bypassed for up to 2 hours for surveillance testing of other channels. | ||
J.1 | J.1 Place channel in trip. 24 hours OR In accordance with the Risk Informed Completion Time Program OR J.2 Be in MODE 3. 30 hours | ||
ECCS - Operating 3.5.2 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) 3.5.2 ECCS - Operating LCO 3.5.2 | CALLAWAY PLANT 3.3-31 Amendment No. 202 ECCS - Operating 3.5.2 | ||
: 1. | 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) | ||
: 2. | |||
APPLICABILITY: | 3.5.2 ECCS - Operating | ||
ACTIONS CONDITION | |||
OR AND In accordance with At least 100% of the ECCS | LCO 3.5.2 Two ECCS trains shall be OPERABLE. | ||
B. Required Action and | |||
AND B.2 | ------------------------------------------- NOTES -------------------------------------------- | ||
: 1. In MODE 3, both safety injection (SI) pump flow paths may be isolated by closing the isolation valves for up to 2 hours to perform pressure isolation valve testing per SR 3.4.14.1. | |||
: 2. Operation in MODE 3 with ECCS pumps made incapable of injecting, pursuant to LCO 3.4.12, Cold Overpressure Mitigation System, is allowed for up to 4 hours or until the temperature o f all | |||
---------------------------------------------------------------------------------------------------RCS cold legs exceeds 375°F, whichever comes first. | |||
APPLICABILITY: MODES 1, 2, and 3. | |||
ACTIONS | |||
CONDITION REQUIRED ACTION COMPLETION TIME | |||
A. One or more trains A.1 Restore train(s) to 72 hours inoperable. OPERABLE status. OR AND In accordance with At least 100% of the ECCS the Risk Informed flow equivalent to a single Completion Time OPERABLE ECCS train Program available. | |||
B. Required Action and B.1 Be in MODE 3. 6 hours associated Completion Time not met. | |||
AND | |||
B.2 Be in MODE 4. 12 hours | |||
CALLAWAY PLANT 3.5-4 Amendment No. 202 MSIVs, MSIVBVs, and MSLPDIVs 3.7.2 | |||
3.7 PLANT SYSTEMS | |||
3.7.2 Main Steam Isolation Valves (MSIVs), Main Steam Isolation Valve Bypass Valves (MSIVBVs), and Main Steam Low Point Drain Isolation Valves (MSLPDIVs) | |||
LCO 3.7.2 The MSIV and its associated actuator trains, the MSIVBV, and the MSLPDIV in each of the four main steam lines shall be OPERABLE. | |||
APPLICABILITY: For the MSIV and its associated actuator trains in each main steam line: | |||
MODE 1, MODE 2 and 3 except when the MSIV is closed and de-activated. | MODE 1, MODE 2 and 3 except when the MSIV is closed and de-activated. | ||
For the MSIVBV in each main steam line: | For the MSIVBV in each main steam line: | ||
MODES 1, 2, and 3 except when: | MODES 1, 2, and 3 except when: | ||
: a. MSIVBV is closed and de-activated, or | : a. MSIVBV is closed and de-activated, or | ||
: b. MSIVBV is closed and isolated by a closed manual valve, or | : b. MSIVBV is closed and isolated by a closed manual valve, or | ||
: c. MSIVBV is isolated by two closed manual valves. | : c. MSIVBV is isolated by two closed manual valves. | ||
For the MSLPDIV in each main steam line: | For the MSLPDIV in each main steam line: | ||
MODES 1, 2, and 3 except when: | MODES 1, 2, and 3 except when: | ||
: a. MSLPDIV is closed and de-activated, or | : a. MSLPDIV is closed and de-activated, or | ||
: b. MSLPDIV is closed and isolated by a closed manual valve, or | : b. MSLPDIV is closed and isolated by a closed manual valve, or | ||
: c. MSLPDIV is isolated by two closed manual valves. | : c. MSLPDIV is isolated by two closed manual valves. | ||
ACTIONS CONDITION | |||
ACTIONS | |||
CONDITION REQUIRED ACTION COMPLETION TIME | |||
A. One MSIV actuator train A.1 Restore MSIV actuator 72 hours inoperable. train to OPERABLE OR status. | |||
In accordance with the Risk Informed Completion Time Program (continued) | In accordance with the Risk Informed Completion Time Program (continued) | ||
AFW System 3.7.5 3.7 PLANT SYSTEMS 3.7.5 Auxiliary Feedwater (AFW) System LCO 3.7.5 | CALLAWAY PLANT 3.7-5 Amendment No. 197 AFW System 3.7.5 | ||
APPLICABILITY: | |||
3.7 PLANT SYSTEMS | |||
3.7.5 Auxiliary Feedwater (AFW) System | |||
LCO 3.7.5 Three AFW trains shall be OPERABLE. | |||
APPLICABILITY: MODE 1, 2, and 3. | |||
ACTIONS | ACTIONS | ||
-----------------------------------------------------------------NOTE----------------------------------------------------------------- | -----------------------------------------------------------------NOTE----------------------------------------------------------------- | ||
LCO 3.0.4.b is not applicable when entering MODE 1. | LCO 3.0.4.b is not applicable when entering MODE 1. | ||
CONDITION | |||
OR inoperable. | CONDITION REQUIRED ACTION COMPLETION TIME | ||
In accordance with the Risk Informed Completion Time Program AND 10 days from discovery of failure to meet the LCO B. One ESW supply to turbine | |||
OR inoperable. | A. One steam supply to A.1 Restore steam supply to 7 days turbine driven AFW pump OPERABLE status. OR inoperable. | ||
In accordance with the Risk Informed Completion Time Program AND 10 days from discovery of failure to meet the LCO | |||
B. One ESW supply to turbine B.1 Restore ESW supply to 72 hours driven AFW pump OPERABLE status. OR inoperable. | |||
In accordance with the Risk Informed Completion Time Program AND 10 days from discovery of failure to meet the LCO (continued) | In accordance with the Risk Informed Completion Time Program AND 10 days from discovery of failure to meet the LCO (continued) | ||
AC Sources - Operating 3.8.1 ACTIONS (continued) | CALLAWAY PLANT 3.7-15 Amendment No. 198 AC Sources - Operating 3.8.1 | ||
CONDITION | |||
OR (continued) | ACTIONS (continued) | ||
In accordance with the Risk Informed Completion Time Program D. One offsite circuit | CONDITION REQUIRED ACTION COMPLETION TIME | ||
inoperable. | |||
Enter applicable Conditions and Required Actions of LCO 3.8.9, | C. Two offsite circuits C.2 Restore one offsite circuit 24 hours inoperable. to OPERABLE status. OR (continued) | ||
AC power source to any train. | In accordance with the Risk Informed Completion Time Program | ||
D.1 | |||
D. One offsite circuit ----------------------NOTE------------------- | |||
inoperable. Enter applicable Conditions and AND Required Actions of LCO 3.8.9, Distribution Systems - Operating, One DG inoperable. when Condition D is entered with no AC power source to any train. | |||
D.1 Restore offsite circuit to 12 hours OPERABLE status. OR | |||
In accordance with the Risk Informed Completion Time Program | |||
OR | |||
D.2 Restore DG to 12 hours OPERABLE status. OR | |||
In accordance with the Risk Informed Completion Time Program | |||
E. Two DGs inoperable. E.1 Restore one DG to 2 hours OPERABLE status. | |||
(continued) | (continued) | ||
AC Sources - Operating 3.8.1 ACTIONS (continued) | CALLAWAY PLANT 3.8.5 Amendment No. 186 AC Sources - Operating 3.8.1 | ||
CONDITION | |||
AND F.2 | ACTIONS (continued) | ||
CONDITION REQUIRED ACTION COMPLETION TIME | |||
G.2 | |||
SURVEILLANCE REQUIREMENTS SURVEILLANCE | F. One required LSELS F.1 Declare the affected DG Immediately inoperable. and offsite circuit inoperable. | ||
CALLAWAY PLANT | |||
AND | |||
F.2 Restore required LSELS 12 hours to OPERABLE status. OR | |||
In accordance with the Risk Informed Completion Time Program | |||
G. Required Action and G.1 Be in MODE 3. 6 hours associated Completion Time of Condition A, B, C, D, E, AND or F not met. | |||
G.2 Be in MODE 5. 36 hours | |||
H. Three or more AC sources H.1 Enter LCO 3.0.3. Immediately inoperable. | |||
SURVEILLANCE REQUIREMENTS | |||
SURVEILLANCE FREQUENCY | |||
SR 3.8.1.1 Verify correct breaker alignment and indicated power In accordance availability for each required offsite circuit. with the Surveillance Frequency Control Program (continued) | |||
CALLAWAY PLANT 3.8-6 Amendment No. 202 Distribution Systems - Operating 3.8.9 ACTIONS (continued) | |||
CONDITION REQUIRED ACTION COMPLETION TIME | |||
C. One DC electrical power C.1 Restore DC electrical 2 hours distribution subsystem power distribution OR inoperable. subsystem to OPERABLE status. In accordance with the Risk Informed Completion Time Program AND 16 hours from discovery of failure to meet LCO | |||
D. Required Action and D.1 Be in MODE 3. 6 hours associated Completion Time not met. AND | |||
D.2 Be in MODE 5. 36 hours | |||
E. Two trains with inoperable E.1 Enter LCO 3.0.3. Immediately distribution subsystems that result in a loss of safety function. | |||
SURVEILLANCE REQUIREMENTS | |||
SURVEILLANCE FREQUENCY | |||
SR 3.8.9.1 Verify correct breaker alignments and voltage to In accordance required AC, DC, and AC vital bus electrical power with the distribution subsystems. Surveillance Frequency Control Program | |||
CALLAWAY PLANT 3.8-39 Amendment No. 202}} | |||
Revision as of 16:15, 15 November 2024
| ML22334A259 | |
| Person / Time | |
|---|---|
| Site: | Callaway |
| Issue date: | 11/30/2022 |
| From: | Ameren Missouri, Union Electric Co |
| To: | Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML22334A255 | List: |
| References | |
| ULNRC-06780 | |
| Download: ML22334A259 (1) | |
Text
Attachment 3 to ULNRC -06780 Page 1 of 11
Revised Technical Specification Pages (Markup)
(10 pages follow this cover sheet)
CompletionTimes 1.3
1.3 Completion Times
EXAMPLES EXAMPLE 1.3-3 (continued)
ACTIONS COMPLETION CONDITION REQUIRED ACTION TIME
A One A.1 Restore Function X7 days Function X train to OPERABLE train status. AND inoperable.
10 days from discovery of failure to meet the LCO
B. One B.1 Restore Function Y 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Function Y train to OPERABLE train status. AND inoperable.
10 days from discovery of failure to meet the LCO
C. One C.1 Restore Function X72 hours Function X train to OPERABLE train status.
OR AND C.2 Restore Function Y 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> One train to OPERABLE Function Y status.
train inoperable.
(continued)
CALLAWAY 1.3-6 Amendment 133 PLANT RTS Instrumentation 3.3.1
TABLE 3.3.1-1 (page 5 of 8)
Reactor Trip System Instrumentation
APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONSCONDITIONS CHANNELS REQUIREMENTS VALUE(a)
- 16. Turbine Trip
- a. L o w Fluid Oil1(j) 3 O M SR 3.3.1.10 539.42 psig
Pressure S R 3.3.1.15
- 17. Safety Injection1, 2 2 trains QP SR 3.3.1.14 NA (SI) Input from Engineered Safety Feature Actuation System (ESFAS)
- 18. Reactor Trip System Interlocks
- b. Low Power 1 1 per train TS SR 3.3.1.5 NA Reactor Trips Block, P-7
(a) The Allowable Value defines the limiting safety system setting except for Trip Functions 14.a and 14.b (the Nominal Trip Setpoint defines the limiting safety system setting for these Trip Functions). See the Bases for the Nominal Trip Setpoints.
(e) Below the P-6 (Intermediate Range Neutron Flux) interlock.
(j) Above the P-9 (Power Range Neutron Flux) interlock.
CALLAWAY PLANT 3.3-23 Amendment No. 202 RTS Instrumentation 3.3.1
TABLE 3.3.1-1 (page 6 of 8)
Reactor Trip System Instrumentation
APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONSCONDITIONS CHANNELS REQUIREMENTS VALUE(a)
- 18. Reactor Trip System Interlocks
- 19. Reactor Trip SR 3.3.1.4 NA Breakers (RTBs)(k) 1, 2 2 trains RQ 3(b), 4(b), 5(b) 2 trains C SR 3.3.1.4 NA
- 20. Reactor Trip 1, 2 1 each per U SR 3.3.1.4 NA Breaker RTB Undervoltage and Shunt Trip 3(b), 4(b), 5(b) 1 each per C SR 3.3.1.4 NA Mechanisms (k) RTB
- 21. Automatic Trip 1, 2 2 trains QP SR 3.3.1.5 NA Logic 3(b), 4(b), 5(b) 2 trains C SR 3.3.1.5 NA
(a) The Allowable Value defines the limiting safety system setting except for Trip Functions 14.a and 14.b (the Nominal Trip Setpoint defines the limiting safety system setting for these Trip Functions). See the Bases for the Nominal Trip Setpoints.
(b) With Rod Control System capable of rod withdrawal or one or more rods not fully inserted.
(k) Including any reactor trip bypass breakers that are racked in and closed for bypassing an RTB.
CALLAWAY PLANT 3.3-24 Amendment No. 202 ESFAS Instrumentation 3.3.2
ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME H. One or more trains --------------------------NOTE-----------------------
inoperable. One train may be bypassed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for surveillance testing provided the other train is OPERABLE.
H.1 Declare associated Immediately Pressurizer PORV(s) inoperable.
I. One channel inoperable. --------------------------NOTE-----------------------
The inoperable channel may be bypassed for up to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for surveillance testing of other channels.
I.1 Place channel in trip. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OR In accordance with the Risk Informed Completion Time Program OR I.2 Be in MODE 3. 78 hours9.027778e-4 days <br />0.0217 hours <br />1.289683e-4 weeks <br />2.9679e-5 months <br /> J. One channel inoperable. --------------------------NOTE-----------------------
The inoperable channel may be bypassed for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> for surveillance testing of other channels.
J.1 Place channel in trip. 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> OR In accordance with the Risk Informed Completion Time Program OR J.2 Be in MODE 3. 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />
CALLAWAY PLANT 3.3-31 Amendment No. 202 ECCS - Operating 3.5.2
3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS)
3.5.2 ECCS - Operating
LCO 3.5.2 Two ECCS trains shall be OPERABLE.
NOTES --------------------------------------------
- 1. In MODE 3, both safety injection (SI) pump flow paths may be isolated by closing the isolation valves for up to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> to perform pressure isolation valve testing per SR 3.4.14.1.
- 2. Operation in MODE 3 with ECCS pumps made incapable of injecting, pursuant to LCO 3.4.12, Cold Overpressure Mitigation System, is allowed for up to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or until the temperature o f all
RCS cold legs exceeds 375°F, whichever comes first.
APPLICABILITY: MODES 1, 2, and 3.
ACTIONS
CONDITION REQUIRED ACTION COMPLETION TIME
A. One or more trains A.1 Restore train(s) to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> inoperable. OPERABLE status. OR AND In accordance with At least 100% of the ECCS the Risk Informed flow equivalent to a single Completion Time OPERABLE ECCS train Program available.
B. Required Action and B.1 Be in MODE 3. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.
AND
B.2 Be in MODE 4. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />
CALLAWAY PLANT 3.5-4 Amendment No. 202 MSIVs, MSIVBVs, and MSLPDIVs 3.7.2
3.7 PLANT SYSTEMS
3.7.2 Main Steam Isolation Valves (MSIVs), Main Steam Isolation Valve Bypass Valves (MSIVBVs), and Main Steam Low Point Drain Isolation Valves (MSLPDIVs)
LCO 3.7.2 The MSIV and its associated actuator trains, the MSIVBV, and the MSLPDIV in each of the four main steam lines shall be OPERABLE.
APPLICABILITY: For the MSIV and its associated actuator trains in each main steam line:
MODE 1, MODE 2 and 3 except when the MSIV is closed and de-activated.
For the MSIVBV in each main steam line:
MODES 1, 2, and 3 except when:
- a. MSIVBV is closed and de-activated, or
- b. MSIVBV is closed and isolated by a closed manual valve, or
- c. MSIVBV is isolated by two closed manual valves.
For the MSLPDIV in each main steam line:
MODES 1, 2, and 3 except when:
- a. MSLPDIV is closed and de-activated, or
- b. MSLPDIV is closed and isolated by a closed manual valve, or
- c. MSLPDIV is isolated by two closed manual valves.
ACTIONS
CONDITION REQUIRED ACTION COMPLETION TIME
A. One MSIV actuator train A.1 Restore MSIV actuator 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> inoperable. train to OPERABLE OR status.
In accordance with the Risk Informed Completion Time Program (continued)
CALLAWAY PLANT 3.7-5 Amendment No. 197 AFW System 3.7.5
3.7 PLANT SYSTEMS
3.7.5 Auxiliary Feedwater (AFW) System
LCO 3.7.5 Three AFW trains shall be OPERABLE.
APPLICABILITY: MODE 1, 2, and 3.
ACTIONS
NOTE-----------------------------------------------------------------
LCO 3.0.4.b is not applicable when entering MODE 1.
CONDITION REQUIRED ACTION COMPLETION TIME
A. One steam supply to A.1 Restore steam supply to 7 days turbine driven AFW pump OPERABLE status. OR inoperable.
In accordance with the Risk Informed Completion Time Program AND 10 days from discovery of failure to meet the LCO
B. One ESW supply to turbine B.1 Restore ESW supply to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> driven AFW pump OPERABLE status. OR inoperable.
In accordance with the Risk Informed Completion Time Program AND 10 days from discovery of failure to meet the LCO (continued)
CALLAWAY PLANT 3.7-15 Amendment No. 198 AC Sources - Operating 3.8.1
ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME
C. Two offsite circuits C.2 Restore one offsite circuit 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> inoperable. to OPERABLE status. OR (continued)
In accordance with the Risk Informed Completion Time Program
D. One offsite circuit ----------------------NOTE-------------------
inoperable. Enter applicable Conditions and AND Required Actions of LCO 3.8.9, Distribution Systems - Operating, One DG inoperable. when Condition D is entered with no AC power source to any train.
D.1 Restore offsite circuit to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> OPERABLE status. OR
In accordance with the Risk Informed Completion Time Program
D.2 Restore DG to 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> OPERABLE status. OR
In accordance with the Risk Informed Completion Time Program
E. Two DGs inoperable. E.1 Restore one DG to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> OPERABLE status.
(continued)
CALLAWAY PLANT 3.8.5 Amendment No. 186 AC Sources - Operating 3.8.1
ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME
F. One required LSELS F.1 Declare the affected DG Immediately inoperable. and offsite circuit inoperable.
AND
F.2 Restore required LSELS 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> to OPERABLE status. OR
In accordance with the Risk Informed Completion Time Program
G. Required Action and G.1 Be in MODE 3. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A, B, C, D, E, AND or F not met.
G.2 Be in MODE 5. 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />
H. Three or more AC sources H.1 Enter LCO 3.0.3. Immediately inoperable.
SURVEILLANCE REQUIREMENTS
SURVEILLANCE FREQUENCY
SR 3.8.1.1 Verify correct breaker alignment and indicated power In accordance availability for each required offsite circuit. with the Surveillance Frequency Control Program (continued)
CALLAWAY PLANT 3.8-6 Amendment No. 202 Distribution Systems - Operating 3.8.9 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME
C. One DC electrical power C.1 Restore DC electrical 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> distribution subsystem power distribution OR inoperable. subsystem to OPERABLE status. In accordance with the Risk Informed Completion Time Program AND 16 hours1.851852e-4 days <br />0.00444 hours <br />2.645503e-5 weeks <br />6.088e-6 months <br /> from discovery of failure to meet LCO
D. Required Action and D.1 Be in MODE 3. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met. AND
D.2 Be in MODE 5. 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />
E. Two trains with inoperable E.1 Enter LCO 3.0.3. Immediately distribution subsystems that result in a loss of safety function.
SURVEILLANCE REQUIREMENTS
SURVEILLANCE FREQUENCY
SR 3.8.9.1 Verify correct breaker alignments and voltage to In accordance required AC, DC, and AC vital bus electrical power with the distribution subsystems. Surveillance Frequency Control Program
CALLAWAY PLANT 3.8-39 Amendment No. 202