ML060950596: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 19: Line 19:


=Text=
=Text=
{{#Wiki_filter:XI.M27 Fire Water System 1 AUDIT W ORKSHEET  GALL R EPORT AMP PLANT: ______________________________
{{#Wiki_filter:AUDIT WORKSHEET GALL REPORT AMP PLANT: ______________________________
LRA AMP: __________________________
LRA AMP: __________________________                                                       REVIEWER: ______________________
R EVIEWER: ______________________
GALL AMP: XI.M27, Fire Water System                                                       DATE: __________________________
GALL AMP: XI.M27, Fire Water System DATE: __________________________
Program               Auditable GALL Criteria                                             Documentation of Audit Finding Element Program               A. This aging management program (AMP) applies to water-           Consistent with GALL AMP:      Yes  No Description          based fire protection systems that consist of sprinklers, nozzles, Document(s) used to confirm Criteria:
Program Element Auditable GALL Criteria Documentation of Audit Finding Program Description A. This aging management program (AMP) applies to water-based fire protection systems that consist of sprinklers, nozzles, fittings, valves, hydrants, hose stations, standpipes, water storage tanks, and aboveground and underground piping and components that are tested in accordance with the applicable National Fire Protection Association (NFPA) codes and standards. Such testing assures the minimum functionality of the systems. Also, these systems are normally maintained at required operating pressure and monitored such that loss of system pressure is immediately detected and corrective actions initiated. Consistent with GALL AMP:
fittings, valves, hydrants, hose stations, standpipes, water storage tanks, and aboveground and underground piping and components that are tested in accordance with the applicable National Fire Protection Association (NFPA) codes and               Comment:
Yes  No Document(s) used to confirm Criteria:
standards. Such testing assures the minimum functionality of the systems. Also, these systems are normally maintained at required operating pressure and monitored such that loss of system pressure is immediately detected and corrective actions initiated.
Comment: " B. A sample of sprinkler heads is to be inspected by using the guidance of NFPA 25 "Inspection, Testing and Maintenance of Water-Based Fire Protection Systems" (1998 Edition), Section 2-3.1.1, or NFPA 25 (2002 Edition), Section 5.3.1.1.1. This NFPA section states "where sprinklers have been in place for 50 years, they shall be replaced or representative samples from one or more sample areas shall be submitted to a recognized testing laboratory for field service testing." It also contains guidance to perform this sampling every 10 years after the initial field service testing. Consistent with GALL AMP:
B. A sample of sprinkler heads is to be inspected by using the     Consistent with GALL AMP:      Yes  No guidance of NFPA 25 Inspection, Testing and Maintenance of         Document(s) used to confirm Criteria:
Yes  No Document(s) used to confirm Criteria:
Water-Based Fire Protection Systems (1998 Edition), Section 2-3.1.1, or NFPA 25 (2002 Edition), Section 5.3.1.1.1. This NFPA section states where sprinklers have been in place for 50 years, they shall be replaced or representative samples from       Comment:
one or more sample areas shall be submitted to a recognized testing laboratory for field service testing. It also contains guidance to perform this sampling every 10 years after the initial field service testing.
XI.M27 Fire Water System                                                                1


Program              Auditable GALL Criteria                                            Documentation of Audit Finding Element C. The fire protection system piping is to be subjected to          Consistent with GALL AMP:      Yes  No required flow testing in accordance with guidance in NFPA 25 to    Document(s) used to confirm Criteria:
verify design pressure or evaluated for wall thickness (e.g., non-intrusive volumetric testing or plant maintenance visual inspections) to ensure that aging effects are managed and that wall thickness is within acceptable limits. These inspections are  Comment:
performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. The plant-specific inspection intervals are to be determined by engineering evaluation of the fire protection piping to ensure that degradation will be detected before the loss of intended function. The purpose of the full flow testing and wall thickness evaluations is to ensure that corrosion, MIC, or biofouling is managed such that the system function is maintained.
: 1. Scope of          A. The AMP focuses on managing loss of material due to              Consistent with GALL AMP:      Yes  No Program              corrosion, MIC, or biofouling of carbon steel and cast-iron        Document(s) used to confirm Criteria:
components in fire protection systems exposed to water. Hose stations and standpipes are considered as piping in the AMP.
Comment
: 2. Preventive        A. To ensure no significant corrosion, MIC, or biofouling has      Consistent with GALL AMP:      Yes  No Actions              occurred in water-based fire protection systems, periodic          Document(s) used to confirm Criteria:
flushing, system performance testing, and inspections may be conducted.
Comment:
Comment:
XI.M27 Fire Water System 2 Program Element Auditable GALL Criteria Documentation of Audit Finding  " C. The fire protection system piping is to be subjected to required flow testing in accordance with guidance in NFPA 25 to verify design pressure or evaluated for wall thickness (e.g., non-intrusive volumetric testing or plant maintenance visual inspections) to ensure that aging effects are managed and that wall thickness is within acceptable limits. These inspections are performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. The plant-specific inspection intervals are to be determined by engineering evaluation of the fire protection piping to ensure that degradation will be detected before the loss of intended function. The purpose of the full flow testing and wall thickness evaluations is to ensure that corrosion, MIC, or biofouling is managed such that the system function is maintained. Consistent with GALL AMP:
: 3. Parameters        A. Loss of material due to corrosion and biofouling could reduce    Consistent with GALL AMP:       Yes   No Monitored/            wall thickness of the fire protection piping system and result in  Document(s) used to confirm Criteria:
Yes No Document(s) used to confirm Criteria:
Inspected            system failure. Therefore, the parameters monitored are the systems ability to maintain pressure and internal system corrosion conditions.
Comment: 1. Scope of Program  A. The AMP focuses on managing loss of material due to corrosion, MIC, or biofouling of carbon steel and cast-iron components in fire protection systems exposed to water. Hose stations and standpipes are considered as piping in the AMP. Consistent with GALL AMP:
Comment:
Yes  No Document(s) used to confirm Criteria:
XI.M27 Fire Water System                                                                2


Comment 2. Preventive Actions A. To ensure no significant corrosion, MIC, or biofouling has occurred in water-based fire protection systems, periodic flushing, system performance testing, and inspections may be conducted. Consistent with GALL AMP:
Program              Auditable GALL Criteria                                              Documentation of Audit Finding Element B. Periodic flow testing of the fire water system is performed        Consistent with GALL AMP:      Yes  No using the guidelines of NFPA 25, or wall thickness evaluations        Document(s) used to confirm Criteria:
Yes No Document(s) used to confirm Criteria:  
may be performed to ensure that the system maintains its intended function.
Comment:
: 4. Detection of      A. Fire protection system testing is performed to assure that the    Consistent with GALL AMP:       Yes   No Aging Effects        system functions by maintaining required operating pressures.        Document(s) used to confirm Criteria:
Wall thickness evaluations of fire protection piping are performed on system components using non-intrusive techniques (e.g., volumetric testing) to identify evidence of loss of material due to corrosion. These inspections are performed        Comment:
before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. As an alternative to non-intrusive testing, the plant maintenance process may include a visual inspection of the internal surface of the fire protection piping upon each entry to the system for routine or corrective maintenance, as long as it can be demonstrated that inspections are performed (based on past maintenance history) on a representative number of locations on a reasonable basis. These inspections must be capable of evaluating (1) wall thickness to ensure against catastrophic failure and (2) the inner diameter of the piping as it applies to the design flow of the fire protection system. If the environmental and material conditions that exist on the interior surface of the below grade fire protection piping are similar to the conditions that exist within the above grade fire protection piping, the results of the inspections of the above grade fire protection piping can be extrapolated to evaluate the condition of below grade fire protection piping. If not, additional inspection activities are needed to ensure that the intended function of below grade fire protection piping will be maintained consistent with the current licensing basis for the period of extended operation. Continuous system pressure monitoring, system flow XI.M27 Fire Water System                                                                  3


Comment: 3. Parameters Monitored/ Inspected A. Loss of material due to corrosion and biofouling could reduce wall thickness of the fire protection piping system and result in system failure. Therefore, the parameters monitored are the system's ability to maintain pressure and internal system corrosion conditions. Consistent with GALL AMP:
Program              Auditable GALL Criteria                                            Documentation of Audit Finding Element testing, and wall thickness evaluations of piping are effective means to ensure that corrosion and biofouling are not occurring and the systems intended function is maintained.
Yes No Document(s) used to confirm Criteria:
B. General requirements of existing fire protection programs        Consistent with GALL AMP:      Yes  No include testing and maintenance of fire detection and protection   Document(s) used to confirm Criteria:
systems and surveillance procedures to ensure that fire detectors, as well as fire protection systems and components are operable.
Comment:
C. Visual inspection of yard fire hydrants performed annually in    Consistent with GALL AMP:      Yes  No accordance with NFPA 25 ensures timely detection of signs of        Document(s) used to confirm Criteria:
degradation, such as corrosion. Fire hydrant hose hydrostatic tests, gasket inspections, and fire hydrant flow tests, performed annually, ensure that fire hydrants can perform their intended function and provide opportunities for degradation to be            Comment:
detected before a loss of intended function can occur.
D. Sprinkler heads are inspected before the end of the 50-year      Consistent with GALL AMP:       Yes   No sprinkler head service life and at 10-year intervals thereafter    Document(s) used to confirm Criteria:
during the extended period of operation to ensure that signs of degradation, such as corrosion, are detected in a timely manner.
Comment:
Comment:
XI.M27 Fire Water System 3 Program Element Auditable GALL Criteria Documentation of Audit Finding  " B. Periodic flow testing of the fire water system is performed using the guidelines of NFPA 25, or wall thickness evaluations may be performed to ensure that the system maintains its intended function. Consistent with GALL AMP:
: 5. Monitoring        A. System discharge pressure is monitored continuously.             Consistent with GALL AMP:       Yes   No and Trending          Results of system performance testing are monitored and            Document(s) used to confirm Criteria:
Yes No Document(s) used to confirm Criteria:
trended as specified by the associated plant commitments pertaining to NFPA codes and standards. Degradation identified by non-intrusive or internal inspection is evaluated.
Comment: 4. Detection of Aging Effects A. Fire protection system testing is performed to assure that the system functions by maintaining required operating pressures.
Wall thickness evaluations of fire protection piping are performed on system components using non-intrusive techniques (e.g., volumetric testing) to identify evidence of loss of material due to corrosion. These inspections are performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. As an alternative to non-intrusive testing, the plant maintenance process may include a visual inspection of the internal surface of the fire protection piping upon each entry to the system for routine or corrective maintenance, as long as it can be demonstrated that inspections are performed (based on past maintenance history) on a representative number of locations on a reasonable basis. These inspections must be capable of evaluating (1) wall thickness to ensure against catastrophic failure and (2) the inner diameter of the piping as it applies to the design flow of the fire protection system. If the environmental and material conditions that exist on the interior surface of the below grade fire protection piping are similar to the conditions that exist within the above grade fire protection piping, the results of the inspections of the above grade fire protection piping can be extrapolated to evaluate the condition of below grade fire protection piping. If not, additional inspection activities are needed to ensure that the intended function of below grade fire protection piping will be maintained consistent with the current licensing basis for the period of extended operation. Continuous system pressure monitoring, system flow Consistent with GALL AMP:
Yes  No Document(s) used to confirm Criteria:
 
Comment:
Comment:
XI.M27 Fire Water System 4 Program Element Auditable GALL Criteria Documentation of Audit Finding  testing, and wall thickness evaluations of piping are effective means to ensure that corrosion and biofouling are not occurring and the system's intended function is maintained. " B. General requirements of existing fire protection programs include testing and maintenance of fire detection and protection systems and surveillance procedures to ensure that fire detectors, as well as fire protection systems and components are operable. Consistent with GALL AMP:
XI.M27 Fire Water System                                                               4
Yes  No Document(s) used to confirm Criteria:


Comment: " C. Visual inspection of yard fire hydrants performed annually in accordance with NFPA 25 ensures timely detection of signs of degradation, such as corrosion. Fire hydrant hose hydrostatic tests, gasket inspections, and fire hydrant flow tests, performed annually, ensure that fire hydrants can perform their intended function and provide opportunities for degradation to be detected before a loss of intended function can occur. Consistent with GALL AMP:
Program              Auditable GALL Criteria                                              Documentation of Audit Finding Element
Yes No Document(s) used to confirm Criteria:  
: 6. Acceptance        A. The acceptance criteria are (a) the ability of a fire protection  Consistent with GALL AMP:      Yes  No Criteria              system to maintain required pressure, (b) no unacceptable signs Document(s) used to confirm Criteria:
of degradation observed during non-intrusive or visual assessment of internal system conditions, and (c) that no biofouling exists in the sprinkler systems that could cause corrosion in the sprinkler heads.                                    Comment:
: 7. Corrective        A. Repair and replacement actions are initiated as necessary.         Consistent with GALL AMP:      Yes  No Actions              For fire water systems and components identified within scope        Document(s) used to confirm Criteria:
that are subject to an AMR for license renewal, the applicants 10 CFR Part 50, Appendix B, program is used for corrective actions, confirmation process, and administrative controls for aging management during the period of extended operation. As          Comment:
discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable to address the corrective actions, confirmation process, and administrative controls.
: 8.                    A. See Item 7, above.                                                Consistent with GALL AMP:      Yes  No Confirmation                                                                                Document(s) used to confirm Criteria:
Process Comment:
: 9.                    A. See Item 7, above.                                                Consistent with GALL AMP:      Yes  No Administrative                                                                              Document(s) used to confirm Criteria:
Controls Comment:
: 10. Operating        A. Water-based fire protection systems designed, inspected,          Consistent with GALL AMP:      Yes   No Experience            tested and maintained in accordance with the NFPA minimum            Document(s) used to confirm Criteria:
standards have demonstrated reliable performance.
XI.M27 Fire Water System                                                                  5


Comment: " D. Sprinkler heads are inspected before the end of the 50-year sprinkler head service life and at 10-year intervals thereafter during the extended period of operation to ensure that signs of degradation, such as corrosion, are detected in a timely manner. Consistent with GALL AMP:
Program              Auditable GALL Criteria   Documentation of Audit Finding Element Comment:
Yes  No Document(s) used to confirm Criteria:
XI.M27 Fire Water System                     6
 
Comment: 5. Monitoring and Trending A. System discharge pressure is monitored continuously. Results of system performance testing are monitored and trended as specified by the associated plant commitments pertaining to NFPA codes and standards. Degradation identified by non-intrusive or internal inspection is evaluated. Consistent with GALL AMP:
Yes  No Document(s) used to confirm Criteria:
Comment:
XI.M27 Fire Water System 5 Program Element Auditable GALL Criteria Documentation of Audit Finding  6. Acceptance Criteria A. The acceptance criteria are (a) the ability of a fire protection system to maintain required pressure, (b) no unacceptable signs of degradation observed during non-intrusive or visual assessment of internal system conditions, and (c) that no biofouling exists in the sprinkler systems that could cause corrosion in the sprinkler heads. Consistent with GALL AMP:
Yes  No Document(s) used to confirm Criteria:
Comment: 7. Corrective Actions A. Repair and replacement actions are initiated as necessary. For fire water systems and components identified within scope that are subject to an AMR for license renewal, the applicant's 10 CFR Part 50, Appendix B, program is used for corrective actions, confirmation process, and administrative controls for aging management during the period of extended operation. As discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable to address the corrective actions, confirmation process, and administrative controls. Consistent with GALL AMP:
Yes  No Document(s) used to confirm Criteria:
Comment: 8. Confirmation Process A. See Item 7, above. Consistent with GALL AMP:
Yes  No Document(s) used to confirm Criteria:


Comment: 9.
EXCEPTIONS Item          Program Elements      LRA Exception Description  Basis for Accepting Exception  Documents Reviewed Number                                                                                          (Identifier, Para.# and/or Page #)
Administrative Controls A. See Item 7, above. Consistent with GALL AMP:
1.
Yes  No Document(s) used to confirm Criteria:
2.


Comment: 10. Operating Experience A. Water-based fire protection systems designed, inspected, tested and maintained in accordance with the NFPA minimum standards have demonstrated reliable performance. Consistent with GALL AMP:
ENHANCEMENTS Item          Program Elements      LRA Enhancement Description Basis for Accepting Enhancement Documents Reviewed Number                                                                                          (Identifier, Para.# and/or Page #)
Yes  No Document(s) used to confirm Criteria:
1.
2.


XI.M27 Fire Water System 6 Program Element Auditable GALL Criteria Documentation of Audit Finding  Comment:
DOCUMENT REVIEWED DURING AUDIT Document Number             Identifier (number)       Title                                                 Revision and/or Date 1.
XI.M27 Fire Water System 7 EXCEPTIONS  Item Number Program Elements LRA Exception Description Basis for Accepting Exception Documents Reviewed  (Identifier, Para.# and/or Page #) 1. 2.    -
2.
ENHANCEMENTS Item Number Program Elements LRA Enhancement Description Basis for Accepting Enhancement Documents Reviewed  (Identifier, Para.# and/or Page #) 1. 2.    -
3.
DOCUMENT REVIEWED D URING A UDIT  Document Number Identifier (number) Title Revision and/or Date 1. 2. 3. 4.   -.}}
4.
.
XI.M27 Fire Water System                                                  7}}

Revision as of 20:18, 23 November 2019

2006/03/22-GALL AMP: XI.M27, Fire Water System (Audit Worksheet GALL Report AMP)
ML060950596
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 03/22/2006
From: Morgan M
NRC/NRR/ADRO/DLR/RLRC
To:
Office of Nuclear Reactor Regulation
morgan M NRR/NRC/DLR/RLRA, 415-2232
Shared Package
ML060950189 List: ... further results
References
%dam200611, TAC MC9668
Download: ML060950596 (5)


Text

AUDIT WORKSHEET GALL REPORT AMP PLANT: ______________________________

LRA AMP: __________________________ REVIEWER: ______________________

GALL AMP: XI.M27, Fire Water System DATE: __________________________

Program Auditable GALL Criteria Documentation of Audit Finding Element Program A. This aging management program (AMP) applies to water- Consistent with GALL AMP: Yes No Description based fire protection systems that consist of sprinklers, nozzles, Document(s) used to confirm Criteria:

fittings, valves, hydrants, hose stations, standpipes, water storage tanks, and aboveground and underground piping and components that are tested in accordance with the applicable National Fire Protection Association (NFPA) codes and Comment:

standards. Such testing assures the minimum functionality of the systems. Also, these systems are normally maintained at required operating pressure and monitored such that loss of system pressure is immediately detected and corrective actions initiated.

B. A sample of sprinkler heads is to be inspected by using the Consistent with GALL AMP: Yes No guidance of NFPA 25 Inspection, Testing and Maintenance of Document(s) used to confirm Criteria:

Water-Based Fire Protection Systems (1998 Edition), Section 2-3.1.1, or NFPA 25 (2002 Edition), Section 5.3.1.1.1. This NFPA section states where sprinklers have been in place for 50 years, they shall be replaced or representative samples from Comment:

one or more sample areas shall be submitted to a recognized testing laboratory for field service testing. It also contains guidance to perform this sampling every 10 years after the initial field service testing.

XI.M27 Fire Water System 1

Program Auditable GALL Criteria Documentation of Audit Finding Element C. The fire protection system piping is to be subjected to Consistent with GALL AMP: Yes No required flow testing in accordance with guidance in NFPA 25 to Document(s) used to confirm Criteria:

verify design pressure or evaluated for wall thickness (e.g., non-intrusive volumetric testing or plant maintenance visual inspections) to ensure that aging effects are managed and that wall thickness is within acceptable limits. These inspections are Comment:

performed before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. The plant-specific inspection intervals are to be determined by engineering evaluation of the fire protection piping to ensure that degradation will be detected before the loss of intended function. The purpose of the full flow testing and wall thickness evaluations is to ensure that corrosion, MIC, or biofouling is managed such that the system function is maintained.

1. Scope of A. The AMP focuses on managing loss of material due to Consistent with GALL AMP: Yes No Program corrosion, MIC, or biofouling of carbon steel and cast-iron Document(s) used to confirm Criteria:

components in fire protection systems exposed to water. Hose stations and standpipes are considered as piping in the AMP.

Comment

2. Preventive A. To ensure no significant corrosion, MIC, or biofouling has Consistent with GALL AMP: Yes No Actions occurred in water-based fire protection systems, periodic Document(s) used to confirm Criteria:

flushing, system performance testing, and inspections may be conducted.

Comment:

3. Parameters A. Loss of material due to corrosion and biofouling could reduce Consistent with GALL AMP: Yes No Monitored/ wall thickness of the fire protection piping system and result in Document(s) used to confirm Criteria:

Inspected system failure. Therefore, the parameters monitored are the systems ability to maintain pressure and internal system corrosion conditions.

Comment:

XI.M27 Fire Water System 2

Program Auditable GALL Criteria Documentation of Audit Finding Element B. Periodic flow testing of the fire water system is performed Consistent with GALL AMP: Yes No using the guidelines of NFPA 25, or wall thickness evaluations Document(s) used to confirm Criteria:

may be performed to ensure that the system maintains its intended function.

Comment:

4. Detection of A. Fire protection system testing is performed to assure that the Consistent with GALL AMP: Yes No Aging Effects system functions by maintaining required operating pressures. Document(s) used to confirm Criteria:

Wall thickness evaluations of fire protection piping are performed on system components using non-intrusive techniques (e.g., volumetric testing) to identify evidence of loss of material due to corrosion. These inspections are performed Comment:

before the end of the current operating term and at plant-specific intervals thereafter during the period of extended operation. As an alternative to non-intrusive testing, the plant maintenance process may include a visual inspection of the internal surface of the fire protection piping upon each entry to the system for routine or corrective maintenance, as long as it can be demonstrated that inspections are performed (based on past maintenance history) on a representative number of locations on a reasonable basis. These inspections must be capable of evaluating (1) wall thickness to ensure against catastrophic failure and (2) the inner diameter of the piping as it applies to the design flow of the fire protection system. If the environmental and material conditions that exist on the interior surface of the below grade fire protection piping are similar to the conditions that exist within the above grade fire protection piping, the results of the inspections of the above grade fire protection piping can be extrapolated to evaluate the condition of below grade fire protection piping. If not, additional inspection activities are needed to ensure that the intended function of below grade fire protection piping will be maintained consistent with the current licensing basis for the period of extended operation. Continuous system pressure monitoring, system flow XI.M27 Fire Water System 3

Program Auditable GALL Criteria Documentation of Audit Finding Element testing, and wall thickness evaluations of piping are effective means to ensure that corrosion and biofouling are not occurring and the systems intended function is maintained.

B. General requirements of existing fire protection programs Consistent with GALL AMP: Yes No include testing and maintenance of fire detection and protection Document(s) used to confirm Criteria:

systems and surveillance procedures to ensure that fire detectors, as well as fire protection systems and components are operable.

Comment:

C. Visual inspection of yard fire hydrants performed annually in Consistent with GALL AMP: Yes No accordance with NFPA 25 ensures timely detection of signs of Document(s) used to confirm Criteria:

degradation, such as corrosion. Fire hydrant hose hydrostatic tests, gasket inspections, and fire hydrant flow tests, performed annually, ensure that fire hydrants can perform their intended function and provide opportunities for degradation to be Comment:

detected before a loss of intended function can occur.

D. Sprinkler heads are inspected before the end of the 50-year Consistent with GALL AMP: Yes No sprinkler head service life and at 10-year intervals thereafter Document(s) used to confirm Criteria:

during the extended period of operation to ensure that signs of degradation, such as corrosion, are detected in a timely manner.

Comment:

5. Monitoring A. System discharge pressure is monitored continuously. Consistent with GALL AMP: Yes No and Trending Results of system performance testing are monitored and Document(s) used to confirm Criteria:

trended as specified by the associated plant commitments pertaining to NFPA codes and standards. Degradation identified by non-intrusive or internal inspection is evaluated.

Comment:

XI.M27 Fire Water System 4

Program Auditable GALL Criteria Documentation of Audit Finding Element

6. Acceptance A. The acceptance criteria are (a) the ability of a fire protection Consistent with GALL AMP: Yes No Criteria system to maintain required pressure, (b) no unacceptable signs Document(s) used to confirm Criteria:

of degradation observed during non-intrusive or visual assessment of internal system conditions, and (c) that no biofouling exists in the sprinkler systems that could cause corrosion in the sprinkler heads. Comment:

7. Corrective A. Repair and replacement actions are initiated as necessary. Consistent with GALL AMP: Yes No Actions For fire water systems and components identified within scope Document(s) used to confirm Criteria:

that are subject to an AMR for license renewal, the applicants 10 CFR Part 50, Appendix B, program is used for corrective actions, confirmation process, and administrative controls for aging management during the period of extended operation. As Comment:

discussed in the appendix to this report, the staff finds the requirements of 10 CFR Part 50, Appendix B, acceptable to address the corrective actions, confirmation process, and administrative controls.

8. A. See Item 7, above. Consistent with GALL AMP: Yes No Confirmation Document(s) used to confirm Criteria:

Process Comment:

9. A. See Item 7, above. Consistent with GALL AMP: Yes No Administrative Document(s) used to confirm Criteria:

Controls Comment:

10. Operating A. Water-based fire protection systems designed, inspected, Consistent with GALL AMP: Yes No Experience tested and maintained in accordance with the NFPA minimum Document(s) used to confirm Criteria:

standards have demonstrated reliable performance.

XI.M27 Fire Water System 5

Program Auditable GALL Criteria Documentation of Audit Finding Element Comment:

XI.M27 Fire Water System 6

EXCEPTIONS Item Program Elements LRA Exception Description Basis for Accepting Exception Documents Reviewed Number (Identifier, Para.# and/or Page #)

1.

2.

ENHANCEMENTS Item Program Elements LRA Enhancement Description Basis for Accepting Enhancement Documents Reviewed Number (Identifier, Para.# and/or Page #)

1.

2.

DOCUMENT REVIEWED DURING AUDIT Document Number Identifier (number) Title Revision and/or Date 1.

2.

3.

4.

.

XI.M27 Fire Water System 7