05000266/FIN-2018001-01: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
| (One intermediate revision by the same user not shown) | |||
| Line 5: | Line 5: | ||
| finding integer = 01 | | finding integer = 01 | ||
| quarter = 2018Q1 | | quarter = 2018Q1 | ||
| IR section = | | IR section = 1R04 | ||
| finding type = Finding | | finding type = Finding | ||
| significance = | | significance = Green | ||
| cornerstone = Mitigating Systems | | cornerstone = Mitigating Systems | ||
| violation of = | | violation of = | ||
| identified by = NRC | | identified by = NRC | ||
| Inspection procedure = IP | | Inspection procedure = IP 71111.04 | ||
| Inspector = | | Inspector = T Hartman, K Barclay, G Edwards, M Holmberg, J Cameron | ||
| CCA = | | CCA = | ||
| INPO aspect = | | INPO aspect = PI.2 | ||
| description = The inspectors identified a finding of very low significance, for the failure to follow procedure NP 7.7.22, Service Water and Fire Protection Inspection Program. Specifically, Section 4.10, Degraded Component Characterization and System Failure Analysis, step 4.10.1 states, in part, the extent of pipe wall degradation shall be characterized by volumetric non-destructive examination (NDE) for subsequent flaw evaluation. The licensee identified pipe corrosion on November 28, 2012, and failed to characterize it by volumetric NDE. | | description = The inspectors identified a finding of very low significance, for the failure to follow procedure NP 7.7.22, Service Water and Fire Protection Inspection Program. Specifically, Section 4.10, Degraded Component Characterization and System Failure Analysis, step 4.10.1 states, in part, the extent of pipe wall degradation shall be characterized by volumetric non-destructive examination (NDE) for subsequent flaw evaluation. The licensee identified pipe corrosion on November 28, 2012, and failed to characterize it by volumetric NDE. | ||
}} | }} | ||
Latest revision as of 17:34, 10 September 2018
| Site: | Point Beach |
|---|---|
| Report | IR 05000266/2018001 Section 1R04 |
| Date counted | Mar 31, 2018 (2018Q1) |
| Type: | Finding: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.04 |
| Inspectors (proximate) | T Hartman K Barclay G Edwards M Holmberg J Cameron |
| INPO aspect | PI.2 |
| ' | |