The inspectors identified a finding of verThe inspectors identified a finding of very low significance, for the failure to follow procedure NP 7.7.22, Service Water and Fire Protection Inspection Program. Specifically, Section 4.10, Degraded Component Characterization and System Failure Analysis, step 4.10.1 states, in part, the extent of pipe wall degradation shall be characterized by volumetric non-destructive examination (NDE) for subsequent flaw evaluation. The licensee identified pipe corrosion on November 28, 2012, and failed to characterize it by volumetric NDE.iled to characterize it by volumetric NDE.  +
23:59:59, 31 March 2018  +
05000266  +  and 05000301  +
23:59:59, 31 March 2018  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.