TXX-6104, Interim Deficiency Rept CP-86-73 Re Installation of ASME Snubber Attachment Brackets.Initially Reported on 861020. Evaluation Continuing.Next Rept Anticipated by 861223

From kanterella
(Redirected from TXX-6104)
Jump to navigation Jump to search
Interim Deficiency Rept CP-86-73 Re Installation of ASME Snubber Attachment Brackets.Initially Reported on 861020. Evaluation Continuing.Next Rept Anticipated by 861223
ML20214J339
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 11/19/1986
From: Counsil W
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To: Johnson E
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
CP-86-73, TXX-6104, NUDOCS 8612010264
Download: ML20214J339 (1)


Text

_ _ _ _ _ _ _ _ _ _

Log # TXX-6104 File # 10110 903.9 TEXAS UTILITIES GENERATING COMPANY SKYWAY TOWER. 400 NORTH OLIVE STREarr. LB. 81. DALLAB. TEXA8 76301 November 19, 1986 Eis,".hfff.UA,

@ @ @ [l g fh NOV 2 41986 Mr. Eric H. Johnson, Director Division of Reactor Safety and Projects U. S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76011

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKETS NOS. 50-445 AND 50-446 ASME SNUBBER ATTACHMENT BRACKETS SDAP,:

CP-86-73 (INTERIM REPORT)

Dear Mr. Johnson:

On October 20, 1986, we verbally notified your Mr. Ian Barnes of a deficiency involving installation of ASME snubber attachment brackets. This is an interim report of a potentially reportable item under the provisions of 10CFR50.55(e).

A drawing review of all ASME snubbers was conducted to verify the adequacy of swing clearances. 1063 snubbers were identified as having attachment brackets with attributes which could potentially result in restricted movement and/or binding of the snubber. As a result of field examination, the number of snubbers of concern has been reduced to 165. These remaining snubbers require additional field checks to complete the evaluation.

We are continuing our evaluation of this issue and anticipate submitting our next report by December 23, 1986.

i Very truly yours, Vil0V W. G. Counsil

/

BSD/amb c - NRC Region IV (0 + 1 copy)

Director, Inspection & Enforcement (15 copies)

U. S. Nuclear Regulatory Commission Washington, D.C. 20555

/i(I 8612010264 861119 PDR ADOCK 05000445

)h {

S PDR a unrustox or rms cruu urum nrcrauc cosumr a y QO L