MONTHYEARML20091E2011991-10-24024 October 1991
[table view]Technical Evaluation Rept Palo Verde Nuclear Generating Station,Station Blackout Evaluation ML17306A4621992-02-11011 February 1992 Forwards Safety Evaluation Accepting Licensee 890414-910831 Responses & Proposed Method of Dealing W/Station Blackout Rule Upon Receipt of Confirmation That Recommendations Documented in Evaluation Will Be Implemented ML17306A8501992-07-28028 July 1992 Forwards Supplemental Safety Evaluation for Station Blackout for Facility.Requests Revision of Commitment to Include Load Test During Operability Test within 30-days ML17306B0291992-10-0202 October 1992 Responds to NRC SER Based on Util Response to Station Blackout Rule Re Periodic Testing of Alternate Ac Sources. Util Proposes to Perform 18-month Interval Test of Gas Turbine Generators During Refueling Outages ML17306B2261993-01-0404 January 1993 Forwards Sser Concluding That Load Testing of Alternate Ac Sources on Approx Yearly Basis Will Not Provide Sufficient Data Base to Demonstrate Required 95% Reliability of Gas Turbine Generators Under Load.Response Requested ML17306B3991993-04-14014 April 1993 Forwards Sser Accepting Monthly Starts & semi-annual Load Tests of Alternate AC Sources Re Licensee Implementation of SBO Rule ML17310B0181994-01-25025 January 1994 Reports Installation & Testing of SBO AC Sources Standby Gas Turbine Generators Complete,Including Connection of Generators to Unit 1 Electrical Bus 1992-07-28 | |