- ML20079N553 + (ML20079N553)
- 05000348/LER-1983-002-03, /03L-0:on 830128,source Range Detector NI-31 Declared Inoperable Due to Low Detector Voltage.Caused by Setpoint Drift.High Voltage Power Supply Adjusted & Detector Returned to Svc + (ML20079N556)
- ML20079N557 + (ML20079N557)
- 05000366/LER-1983-137-03, /03L-0:on 831221 & 22,personnel Determined Safety Relief Valve Tailpipe Temp Recorder 2B21-R614 Inoperable. Caused by Failed Chart Drive Motor & Failed Chart Drive Idler Gear.Replacement Parts Installed + (ML20079N558)
- 05000416/LER-1983-112-03, While Troubleshooting Nssss/Eccs Initiation Circuitry Re Improper Operation of E12F087B & F025B,partial LOCA Occurred.Caused by Error in Work Order.Changes Underway + (ML20079N559)
- ML20079N561 + (ML20079N561)
- 05000416/LER-1983-039-99, /99X-0:on 830112,during Cold Shutdown,Halon Panel 1H13P911 Detector a Alarmed & Would Not Reset.Hourly Fire Watch Established.Corrective Maint Underway + (ML20079N563)
- 05000348/LER-1983-007, Forwards LER 83-007/03L-0 + (ML20079N571)
- ML20079N573 + (ML20079N573)
- 05000321/LER-1983-113-03, /03L-0:on 831220,surveillance Personnel Noted Reactor Bldg Exhaust Vent Radiation Monitors 1D11-K609 A,B & C Inoperable.Caused by Monitors 1D11-K609 A,B & C Out of Calibr.Monitors Recalibr + (ML20079N577)
- 2CAN028316, Responds to Re Schedule for Core Protection Computer Mods to Correct Low Power Density Penalty Factor.Correction Will Be Provided During Next Software Update.Schedule Should Be Available by 830530 + (ML20079N578)
- 05000348/LER-1983-007-03, /03L-0:on 830114,electrical Penetration Q1T52B038-B Failed Local Leak Rate Test.Caused by O-ring Damage at Inner Seal from Repairs During Previous Refueling outage.O-rings Replaced + (ML20079N581)
- ML20079N582 + (ML20079N582)
- A830027, Forwards Public Version of Rev 2 to Emergency Plan Implementing Procedure 5.7.2, Notification of Unusual Event. W/O Encl + (ML20079N589)
- ML20079N590 + (ML20079N590)
- ML20079N593 + (ML20079N593)
- ML20079N595 + (ML20079N595)
- 0CAN028316, Application for Amend to Licenses DPR-51 & NPF-6,changing Tech Specs Section 6 to Require Annual Reporting of Safety & Relief Valve Challenges,In Response to NRC 820920 Generic Ltr 82-16 + (ML20079N598)
- ML20079N601 + (ML20079N601)
- ML20079N603 + (ML20079N603)
- ML20079N609 + (ML20079N609)
- ML20079N610 + (ML20079N610)
- ML20079N613 + (ML20079N613)
- 05000237/LER-1983-083-03, /03L-0:on 831226,while Lowering Suppression Pool Level,Lpci 1501-3B Valve Tripped Thermally.Caused by Underrated Overload Heaters (GE CR 123 L1.74A) in Valve Motor Overload Assembly.Heaters Replaced + (ML20079N626)
- 05000416/LER-1983-040, Forwards LER 83-040/03L-0 + (ML20079N629)
- 05000416/LER-1983-090-01, Inlet Valve to Reactor Water Cleanup Sys Nonregenerative HX Discovered Closed. Caused by Valve Isolation When Relay Removed During Limiting Safety Sys Setting Troubleshooting + (ML20079N639)
- 05000416/LER-1983-040-03, /03L-0:on 830127,smoke Detector in Zone Covering Elevation 139 Ft in Auxiliary Bldg Covered to Perform Welding in Area & Prevent Actuation of Alarm.Caused by Planned Maint Activities.Smoke Detector Uncovered + (ML20079N643)
- ML20079N645 + (ML20079N645)
- 05000324/LER-1983-015, Forwards LER 83-015/03L-0 + (ML20079N647)
- IR 05000397/1983003 + (ML20079N654)
- 05000348/LER-1983-090-03, /03L-0:on 831224,radiation Monitors R-11 & R12 Declared Inoperable When Vacuum Pump Tripped.Caused by Flow Rate Set Too High.Method for Adjusting Flow Rate Revised & Monitors Returned to Svc + (ML20079N662)
- ML20079N668 + (ML20079N668)
- 05000348/LER-1983-091-03, /03L-0:on 831226,radiation Monitor R-5 Declared Inoperable Due to Erroneous Indication.Caused by Faulty Connection.Connection Repaired & Monitor Declared Operable + (ML20079N670)
- 05000296/LER-1983-006, Forwards LER 83-006/03L-0 + (ML20079N671)
- 05000334/LER-1983-007, Forwards LER 83-007/04T-0 + (ML20079N675)
- 05000348/LER-1983-092-03, /03L-0:on 831225,instrumentation Channel Associated W/Pressure Transmitter PT-494 Declared Inoperable.Caused by Localized Freezing in Sensing Lines Due to Cold Weather.Lines Thawed Out + (ML20079N677)
- ML20079N681 + (ML20079N681)
- ML20079N685 + (ML20079N685)
- 05000324/LER-1983-015-03, /03L-0:on 830123,reactor Recirculation Pump 2A Tripped.Caused by ATWS Reactor Pressure Instrument 2-B21-PS-NO45C Actuation Below Tech Spec Limit.Instrument Replaced + (ML20079N686)
- ML20079N688 + (ML20079N688)
- 05000296/LER-1983-007, Forwards LER 83-007/03L-0 + (ML20079N692)
- 05000348/LER-1983-065-03, /03L-0:on 831227,instrumentation Channel Associated W/Temp Indicator TI-432D Declared Inoperable. Caused by Drift of Lead/Lag Card Gain.Card Replaced & Channel Declared Operable + (ML20079N695)
- 05000334/LER-1983-007-04, /04T-0:on 830214,tritium Activity in Fourth Quarter 1982 Composite of Weekly Grab Samples Collected in Oh River Downstream of Effluent Found to Be Above ETS Limits.Amend to ETS Submitted to Increase Acceptable Limit + (ML20079N697)
- W3P84-0213, Requests Review of Encl Safety Info Booklet.Distribution to Public Scheduled for Early Mar 1984.W/two Oversize Charts. Aperture Cards Are Available in PDR + (ML20079N699)
- ML20079N701 + (ML20079N701)
- 05000296/LER-1983-007-03, /03L-0:on 830128,during Monthly Vibration Checks, Generator/Flywheel Ball Bearing Developed High Vibration Levels.Cause Suspected to Be Normal Wear.Bearing Replaced + (ML20079N704)
- 05000296/LER-1983-006-03, /03L-0:on 830128,during Shutdown,While Performing Monthly Vibration Tests on 480-volt Reactor Motor Operated Valve Motor Generator Sets,High Vibration Readings Detected. Caused by Leak in Seal Ring.Coupling & Rings Replaced + (ML20079N707)
- ML20079N711 + (ML20079N711)
- 05000366/LER-1983-139-03, /03L-0:on 831214,position of Vacuum Breaker 2T48-F323C Could Not Be Confirmed Due to Blown Position Indicator Light Fuse 2T48-F1.Caused by Shorted Valve Position Switch.Switch & Fuse Replaced + (ML20079N713)
- ML20079N723 + (ML20079N723)
- ML20079N727 + (ML20079N727)