A self-revealing, non-cited violation of TA self-revealing, non-cited violation of Technical Specification 5.4 Procedures, was identified for the failure to provide an adequate procedure for installing the 2A service water (SW) pump motor cable connections. As a result, the connection degraded over time, which degraded the Raychem insulation that caused the circuit breaker to trip on overcurrent. The licensee repaired the 2A SW pump motor cable connection under WO SNC717176 and returned the pump to service on October 16, 2015. This event was entered in the licensees corrective action program with CR 10135057. The performance deficiency was more than minor because it was associated with the procedure quality attribute of the mitigating systems cornerstone and adversely affected the cornerstone objective because the inadequate procedure resulted in the pump circuit breaker trip due to an overcurrent condition. The significance of this finding was determined to be of very low safety significance (Green). This finding was associated with the cross-cutting aspect of Evaluation in the Problem Identification and Resolution area.roblem Identification and Resolution area.  +
23:59:59, 31 December 2015  +
05000364  +
23:59:59, 31 December 2015  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
12:58:46, 25 September 2017  +
23:59:59, 31 December 2015  +
Failure to Provide Adequate Instructions for the 2A Service Water Pump Motor Cable Connections  +