Browse wiki

Jump to navigation Jump to search
Inspectors identified a Green NCV of 10 CFInspectors identified a Green NCV of 10 CFR 50.65(a)(2) when control area ventilation (CAV) radiation monitor (RM) performance was not being effectively controlled through appropriate PM. Specifically, there were repetitive foil issues and a repeat maintenance preventable functional failure (RMPFF) during the monitoring period. PSEG placed the system in monitoring under 10 CFR 50.65(a)(1) and entered this in their CAP. The issue was more than minor since it was associated with the barrier performance attribute of the Barrier Integrity cornerstone and adversely affected its objective to provide reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. The finding was screened in accordance with IMC 0609, Attachment 4 and Appendix A, Exhibit 3, where it screened to Green since it only represented a degradation of the radiological barrier function provided for the control room. The finding has a cross-cutting aspect in Human Performance, Conservative Bias, in that licensees take timely action to address degraded conditions commensurate with their safety significance and take a conservative approach to decision making. conservative approach to decision making.  +
23:59:59, 31 December 2015  +
05000272  +
23:59:59, 31 December 2015  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
04:23:08, 22 February 2018  +
23:59:59, 31 December 2015  +
Inadequate Maintenance Effectiveness of Control Room Ventilation Radiation Monitors  +