SVP-06-057, Day Post Outage ISI Letter
| ML062020425 | |
| Person / Time | |
|---|---|
| Site: | Quad Cities |
| Issue date: | 07/14/2006 |
| From: | Tulon T Exelon Generation Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| SVP-06-057 | |
| Download: ML062020425 (84) | |
Text
Exeli fl.ýn Exelon Generation Company, LLC www.exeloncorp.com Nuclea-r Quad Cities Nuclear Power Station 22710 206's Avenue North Cordova, IL 61242-9740 1 OCFR5O.55a SVP-06-057 July 14, 2006 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Quad Cities Nuclear Power Station Unit 2 Renewed Facility Operating License No. DPR-30 NRC Docket No. 50-265
Subject:
90-Day Post Outage ISI Letter Enclosed is the Quad Cities Nuclear Power Station Unit 2 Post-Outage (90 day) Summary Report for Inservice Inspection examinations and Repair/Replacement activities conducted from the end of the March 2004 refueling outage through the April 2006 refueling outage.
This report is due within 90 days after the end of the Unit 2 April 2006 refueling outage, which is July 16, 2006. This report documents examinations performed during the first period of the fourth inspection interval.
This report is submitted in accordance with the requirements of ASME Section Xl, Article IWA-6200, "Requirements."
If there are any questions or comments concerning this letter, please refer them to Mr. Wally Beck, Regulatory Assurance Manager, at (309) 227-2800.
Sincerely, Ti thy J. Tulon SVice President 0 ad Cities Nuclear Power Station
Attachment:
Quad Cities Nuclear Power Station - Unit 2 Post Outage (90 day) Summary Report cc:
Regional Administrator - NRC Region III NRC Senior Resident Inspector - Quad Cities Nuclear Power Station
ATTACHMENT Quad Cities Nuclear Power Station-Unit 2 Post Outage (90 day) Summary Report June 22, 2006
Quad Cities Nuclear Power Station - Unit 2 Post Outage (90 Day) Summary Report June 22, 2006 Refueling Outage Q2R18 Outage Start Date: March 24, 2006 Outage End Date: April 18, 2006 Commercial Service Date: March 10, 1973 22710 206tI Avenue North, Cordova, IL 61242 Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Prepared by:,-AýJ2'
- /x/4 4x~
Reviewed by:
~
~
z/
Reviewed by:
-/
,4
/2/'
Reviewed by:Z5ýS6Xýri,~t' 1:12216C Approved by:
Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 300 Exelon Way Unit 2 1
Kennett Square, PA 19348 22710 20 6t Avenue North, Commercial Service Date March 10, 1973 Cordova,.IL 61242 Table of Contents
1.0 INTRODUCTION
3
- 1. 1.
OUTAGE, PERIOD AND INTERVAL START AND END DATES....................................................
3 1.2.
EXAMIINATION PROGRAM REQUIREMENTS.......................................................................
3 2.0 NIS-l FORM..............................................................................................................
4 3.0 ABSTRACT OF EXAMINATIONS, CONDITIONS NOTED AND CORRECTIVE MEASURES...... 6 3.1.
SECTrIONXI EXAMINATIONS
SUMMARY
6 3.2.
BWRVIP-75/GENERic LETTER 88-01.............................................................................
7 3.3.
INVESSEL INSPECTIONS (IVI).......................................................................................
7 Table 3. 1-1 Quad Cities Unit 2 ASME Section Xl Outage Scope.........................................
9 Table 3.1-IA Quad Cities Unit 2 ASME Section X1 Limited Coverage Scope...........................
11 Table 3.1-2 Quad Cities Unit 2 Pressure Testing Stuninarty.............................................
12 Table 3.1-3 Quad Cities Unit 2 Snubber Functional Tests...............................................
13 Table 3.1-4 Quad Cities Unit 2 Conditions Noted and Corrective A ctions.............................
14 Table 3.3 Number and Percentage of Examninations C'omnpleted....................................S1 4.0 REPAIR / REPLACEMENT
SUMMARY
16 4.1.
NIS-2 INDEX........................................................................................................
16 Table 4.1-1.........................................................................................................
16 4.2.
NIS-2 FORMS........................................................................................................
19 2 of 19
Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 300 Exelon Way Unit 2 1
Kennett Square, PA 19348 22710 20 6 h Avenue North, Commercial Service Date March 10, 1973 Cordova, IL 61242 1.0 Introduction 1.1.
Outage, Period and Interval Start and End Dates This Inservice Inspection Summary Report addresses examinations performed between the end of the previous refueling outage March 28, 2004 through the end of the most recent refueling outage. This most recent refueling outage was the 1 8 'h refueling outage for Quad Cities Nuclear Power Station Unit Two. The outage started March 24, 2006 and was completed April 18, 2006 when the unit returned to service.
This refuieling outage was the second outage during the first inspection period of the fourth inspection interval, which began on March 10, 2003. The first inspection period of the fourth inspection interval ends with this refueling outage on April 18, 2006. This report covers examinations performed to the first period, fourth interval requirements.
Tests, examinations, repairs and/or replacements associated with American Society of Mechanical Engineers (ASME) Code,Section XI were witnessed or otherwise verified by the Authorized Nuclear Inservice Inspectors. Non-ASME Section XI or augmented examinations were not witnessed or otherwise verified by the Authorized Nuclear Inservice Inspectors and are marked "Not Required" or "N/A" on the applicable examination reports.
The Authorized Nuclear Inservice Inspectors are inspectors of the Hartford Steam Boiler Inspection & Insurance Company of Connecticut (HS B-CT). The HSB-CT Regional Office is located at 2443 Warrenville Road Suite 500, Lisle, Illinois, 60532-987 1.
1.2.
Examination Program Requirements The examination requirements of ASME Boiler and Pressure Vessel Code,Section XI, Division 1, "Rules for Inservice Inspection of Nuclear Power Plant Components", 1995 Edition through 1996 Addenda were implemented for Class 1, 2 and 3 components except where written relief has been granted by the NRC. Written relief, in the form of Relief Request 14R-02 approving Risk Informed Inservice Inspection (RI-ISI) as an inspection program alternative for Code Categories B-F, B-J, C-F7-i and C-F7-2, was utilized during Q2R 18. The ultrasonic examination volumes for RI-ISI components were increased, from the Section XI requirements, to meet the RI-ISI Program.
The ultrasonic examination requirements of ASME Boiler and Pressure Vessel Code,Section XI, Appendix VIII, 1995 Edition with Addenda through 1996, as required by 10 CFR 50.55a, "Codes and Standards", and amended by the Federal Register Notice 64 FR 5 1370 dated September 22, 1999 is executed through the Performance Demonstration Initiative (PDI) Program according to the schedule defined in 10 CFR 50.55a(g)(6)(ii)(C),
for wrought austenitic piping welds, ferritic piping welds, bolts/studs, reactor vessel welds, nozzle to vessel welds, nozzle inside radius sections and full structural overlaid wrought austenitic piping welds.
3 of 19
Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 2 06 1h Avenue North, Cordova, IL 61242 2.0 NIS-1 Form FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules
- 1. Owner Exelon Generation Company, L.L.C., 300 Exelon Way, Kennett Square, PA 19348 (Name and Address of Owner)
- 2. Plant
-Quad Cities Nuclear Power Station, 22710 2 06t1h Avenue North, Cordova, IL 61242 (Name and Address of Owner)
- 3. Plant Unit Two
- 4. Owner Certificate of Authorization (if required)
N/A N/A
- 5. Commercial Service Date 3/10/73
- 6. National Board Number for Unit
- 7. Components Inspected Component or Manufacturer Manufacturer State or National Appurtenance Or Installer or Installer Province No.
Board No.
Serial No.
Reactor Pressure Chicago Bridge & Iron T-22 B0075000 N/A Vessel Reactor Recirculation Dravo Corp.
N/A - See Table 3. 1-1 N/A N/A Core Spray Grinnell N/A -See Table 3. 1-1 N/A N/A Feedwater Grinnell N/A - See Table 3. 1-1 N/A N/A Main Steam Grinnell N/A - See Table 3. 1-1 N/A N/A Residual Heat Grinnell N/A - See Table 3. 1-1 N/A N/A Removal Control Rod Drive Grinnell N/A - See Table 3. 1-1 N/A N/A High Pressure Coolant Grinnell N/A - See Table 3. 1-1 N/A N/A InjectionIIIII Note: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/22 in. x I1 12 in.,
(2) information in items I through 6 on this report is included on each sheet unless they are coded N/A, and (3) each sheet is numbered and the number of sheets is recorded at the bottom of this form.
4 of 19
'Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 2 0 6 1h Ave nue North, Cordova, IL 61242 FORM NIS-1 (Back)
- 8. Examination Dates:
- 9. Inspection Period Identification:
3/28/04 to 4/18/06 1 " Period - From 3/10/03 to 4/18/06 for the 4 1h Interval
- 10. Inspection Interval Identification:
4th Interval - From 3/10/03 to 3/9/13
- 11. Applicable Edition of Section XI 1995 Addenda 1996
- 12. Date/Revision of Inspection Plan:
11/29/05 Revision 2 (4 1h Interval)
- 13. Abstract of Examination and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See Section 3.0 and Tables 3.1-1. 3.1-I A. 3.1-2. 3.1-3. 3.1-4. and 3.3.
- 14. Abstract of Results of Examinations and Tests. See Section-3.0Oand Tables 3.1-1 3. 1-1IA. 3.1-2, 3.1-3. 3.1-4. and 3.3
- 15. Abstract of Corrective Measures. See Section 3.0 and Table 3.1-4.
We certify that a) the statement made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the ASME Code,Section XI.
Certificate of Authorization No. (if applicable)
Date Oto - 2..S 20 6('
Signed N/A Exp Exelon Corporation iiration Date
/N/A Owner By Qumdý=
V I
CERTIFICATE OF INSERVICE INSPECTION 1, the under signed, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of
- Illinois, and employed by Hartford Steam Boiler of Connecticut of Connecticut have inspected the components described in the Owner's Report during the period 3/28/04 To 4/18/06
,and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any wvarranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
72-, 6-U-1" Commissions IL 1005 National Board, State, Province, and Endorsements L-1 Inspector's-St&Katu()
Date23 200 6 5 of 19
'Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 300 Exelon Way Unit 2 1
Kennett Square, PA 19348 22710 2 06t Avenue North, Commercial Service Date March 10, 1973 Cordova, IL 61242 3.0 Abstract of Examinations, Conditions Noted and Corrective Measures 3.1.
Section X1 Examinations Summary A combination of ultrasonic (UT), liquid penetrant (PT), magnetic particle (MT) and visual (VT) testing were performed prior to and during the 18 1h refueling outage on ISI Program components. Examinations were performed by General Electric (GE), IHI Southwest Technologies (lSwT), and Exelon Nuclear personnel. Volumetric and surface examinations were compared with the recorded results of previous examinations for applicable Class 1, 2 and RI-ISI components. ISI inspections comprised of 35 volumetric (16 were RI-ISI, Category R-A welds), 4 surface examinations and 24 visual examinations were performed on Class 1, 2 and RI-IS! components. Thirteen of the visual exams were subsequent exams due to IWF-2200(b) for corrective action from Q2R 17. Code cases used for IST or Repair/Replacement activities are listed in the ISI Program Plan.
The 13 subsequent exams as required by IWF-2200(b) were a result of the "As-Found" cold settings being out of tolerance for both Constant Spring Can Component Supports and Flued Head Anchors that did not meet acceptance criteria during Q2R17. The subsequent examinations found no additional relevant conditions.
Table 3.1-4A, "Quad Cities Unit 2 ASME Section XI Limited Coverage Summary" contains the volumetric examinations that did not meet coverage requirements of ASME Section XI Code (i.e. greater than 90 percent of the specified examination volume). These exams were limited by design specific geometry. Accessibility could not be improved.
Four of the exams were on nozzle welds that have received relief for exam limitations in the past. The four nozzle welds coverage increased over the previous interval exams. The last limited exam was for exam category R-A where previous single sided access coverage had achieved 100% when including only 1/4" of base metal. Risk informed inspection requirements increased base metal to 1/22" causing this single sided exam coverage to decrease in total examinable volume. Relief requests as required by 10 CFR 50.55a(g)5(iii) and 50.55a(g)5(iv) will be generated and submitted within twelve (12) months following the end of the inspection interval.
A portion of the reactor vessel vertical welds were examined during Q2R17 in accordance with the requirements of I OCFR5O.55a "Codes and Standards" regarding the section entitled "Augmented Examination of Reactor Vessel". The remaining reactor vessel vertical welds were examined during Q2R 18.
Pressure testing VT-2 examinations not related to repair/replacement activities are documented in Table 3.1-2, "Quad Cities Unit 2 Pressure Testing Summary". The Class 1 Vessel Leakage Test and the Reactor Vessel Head Flange Seal Leak Detection System Test were performed in accordance with the 1995 Edition 1996 Addenda of the ASME Code for the first period of the fourth Interval.
Exelon personnel performed functional tests on a total of fifteen (15) snubbers for operability per the Service Life Monitoring/Failure Trending Sample and ASME OM Code 6 of 19
- Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 300 Exelon Way Unit 2 Kennett Square, PA 19348 22710 20 6 'h Avenue North, Commercial Service Date March 10, 1973 Cordova, IL 61242 Subsection ISTD. Nine (9) of the fifteen (15) snubbers were ASME Section XI Code designated. Of the fifteen (15) snubbers tested, one was found unacceptable for continued operation (IR# 471469). An additional nine (9) snubbers were tested for expanded sampling due to snubber failure. Eight (8) of the nine (9) expanded sample snubbers were ASME Section XI Code designated. Of the additional nine (9) snubbers tested, two (2) snubbers were found unacceptable for continued operation (IR# 472956 and 472989). The three (3) unacceptable snubbers were replaced with like-for-like units. Snubber testing activities are summarized in Table 3.1-3, "Quad Cities Unit 2 Snubber Functional Tests".
Table 3.1-4 "Quad Cities Unit 2 Conditions Noted and Corrective Actions" summarizes the conditions noted during the examinations and corrective measures taken prior to returning the unit to service.
Table 3.3 identifies number and percentage of examinations completed in the fourth interval.
NRC performed an audit of the Inservice Inspection (IS 1) Program during Q2R1 8 (IR 05000254(265)/2006004). No findings were noted.
3.2. BWRVIP-75/Generic Letter 88-01 Augmented examinations required by Generic Letter 88-01, "NRC Position on Intergranular Stress'Corrosion Cracking (IGSCC) in BWR Austentic Stainless Steel Piping" and BWRVIP-75, "BWR Vessel and Internals Project Technical Bases for Revisions to Generic Letter 88-01 Inspection Schedules", were implemented in the previous outage Q2RI 7. No exams were performed this outage.
3.3. Invessel Inspections (IVI)
To implement the requirements of the Boiling Water Reactor Vessel Internials Program, (BWRVIP), GE was contracted to perform the In-Vessel Visual Inspections (IVVI). The following components and assemblies were examined: Jet Pump Assemblies in accordance with the BWR Jet Pump Assembly Inspection and Flaw Evaluations Guidelines (BWRVIP-41 -A), Core Spray Internal Piping in accordance with the BWR Core Spray Internals Inspection and Flaw Evaluation Guidelines (BWRVIP-1 8-A), Core Shroud Ring Segment Vertical Welds in accordance with the BWR Core Shroud Inspection and Flaw Inspection Guideline (BWRVIP-76), Reactor Pressure Vessel attachments associated with the Feedwater Spargers and steam dryer wall support lugs in accordance with the BWR Vessel ID Weld Inspection and Flaw Evaluation Guidelines (BWRVIP-48-A), and Control Rod Guide Tubes in accordance with BWR Vessel and Internals Project Boiling Water Reactor Lower Plenum Inspection and Flaw Evaluation Guidelines (BWRVIP-47-A).
A 1 0-year re-inspection of the core shroud repair hardware (tie rods) was performed during Q2Rl 8. Additional detailed inspections were performed in accordance with GE and BWRVIP recommendations in response to recent findings at Plant Hatch. No recordable indications wvere identified.
7 of 19
'Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 300 Exelon Way Unit 2 Kennett Square, PA 19348 22710 2 06 1h Avenue North, Commercial Service Date March 10, 1973 Cordova, IL 61242 zone of circumferential weld H-5 (IR 475862). These indications do not pose a challenge to the structural integrity of the core support ring since the shroud stabilizers (tie rods) structurally reinforce welds HI through H7. Another indication was found on the top surface of the Shroud Head Flange ring (IR 475332). The indication appeared to be a scratch or small gouge. It did not line up with any probable heat affected zone and did not have any depth when viewed from the vertical surface.
During the IVVI examinations four (4) jet Pumps were identified with evidence of main wedge (WVD-1) movement. GE Indication Notification Reports (INRs) and Exelon Issue Reports (IRs) were generated to document these conditions (IR 474814, IR 475009, IR 474491 and IR 474070). Additional inspections were performed as required by BWRVIP-41 -A including supplemental visual inspections of the affected jet pumps to confirm overall pump integrity. The most severe wedge movement (on Jet Pump #07) was corrected via a planned restrainer bracket replacement under WO 823272-01. Quad Cities shall continue to monitor the condition of jet pump wedges during future IVVI visual inspections.
Seven of eight Feedwater Sparger End Bracket pins were welded into place during Q2R 18.
This was a planned activity in response to a missing nut on a Feedwater Sparger End Bracket pin identified during Q2R 17, which was welded into place during Q2R 17. In addition, two of the pinheads were observed to be wearing into the bracket hardware during Q2R18 due to flow-induced vibration (IR 474497). This is not a concern for the immediate future. The worst worn bracket still has greater than 90% of its original thickness remaining. Quad Cities will continue to monitor this condition. In the meantime, long-term repair options are being evaluated.
8 of 19
'Exelon Generation Company, L.L.C.
300 Exelon Way Ken nett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 2 06 1h Avenue North, Cordova, IL 61242 Table 3.1-1 Quad Cities Unit 2
__________ASME SectionX O tge Scpe 4th Interval)
Drawing Component Class Category Item Inspection Date Results NI-3121 SUIT. 2 RPV-VSCI-317 I
B-A B3I.12 UT 4/02/06 NRI M-3121 SUIT. 2 RPV-VSCI-197 I
B-A B3I.12 UT 4/02/06 NRI NI-3121 SUIT.2 RPV-VSCI-261 I
B-A BI.12 UT 4/02/06 NRI NI-3121 SUIT. 2 RPV-VSCI-77 I
B-A BI.12 UT 4/02/06 NRI M-3121 SUIT. 2 RPV-NIRA-01II I
B-A 13I.12 UT 4/02/06 NRI M-3121 SHIT. 2 RPV-VSC2-141 I
B-A B3I.12 UT 4/02/06 NRI M-3121 SHT. 2 RPV-VSC2-22 I
B-A B3I.12 UT 4/02/06 NRI M-3121 SUIT. 2 RPV-VSC3-197 I
B-A B3I.12 UT 4/02/06 NRI M-3121 SHIT. 2 RPV-VSC3-317 I
B-A BI.12 UT 4/02/06 NRI M-3121 SHT. 2 RPV-VSC3-77 I
B-A 13I.12 UT 4/02/06 NRI NI-3121 SUIT. 2 RPV.CWV-C4FLG I
B-A B 1.30 UT 4/02/06 NRI M-3121 SUT. 2 NIA NOZ I
B-D B3.90 UT 4/01/06 NRI M-3121 SHIT. 2 N2B3 NOZ I
B-D B3.90 UT 4/01/06 NRI MI-3121 SUIT. 2 N2D NOZ I
B-D B3.90 UT 4/02/06 NRI NI-3121 SHIT. 2 N2E NOZ I
B-D B3.90 UT 4/04/06 NRI M-3121 SHT. 2 NIA IRS I
B-D B3.100 UT 4/01/06 NRI M-3121 SHIT. 2 N213 IRS I
B-D B3.100 UT 4/01/06 NRI M-3121 SI-IT. 2 N2D) IRS I
B-D B3.100 UT 4/02/06 NRI M-3121ISUT. 2 N2E IRS I
B-D B3.100 UT 4/04/06 NRI M3115SUIT. I REACTOR HEAD I
B-G-2 B7.50 VT-I1 3/31/06 NRI N6A FLANGE I______
M315 SUIT. I REACTOR HEAD I
B7.50 VT-I1 3/31/06 NRI N613 FLANGE B-G-2 N13115 SI-IT. I REACTOR HEAD I
B-G-2 B7.50 VT-I1 3/.31/06 NRI N7 FLANGE____
N13113 SUIT. 3 DECON FLANGE I
B-G-2 B7.50 VT-I 3/30/06 NRI 3(A)
M31 13 SHIT. 3 DECON FLANGE I
B-G-2 B7.50 VT-I1 3/30/06 NRI 3(B)
I_____
NI-31 11 SHT. I 300113-WV-102A I
B-K BI10.20 MT 3/31/06 NRI M-3113 SHT. 2 0200-W-133A I
B-K BI10.40 PT 4/03/06 NRI N/A RPV INTERIOR I
B-N-I B 13.10 VT-3 4/14/06 ACCEPrABLE N/A RPV INTERNALS I
B-N-2 B 13.20 VT-I1 4/14/06 ACCEFTABLE M-3 136 SHIT. 7 I008A-W-203A 2
C-C C3.20 MT 3/21/06 NRI M-3136 SHT. 9 1024A-W-201 A 2
C-C C3.20 PT 3/21/06 NRI M-3114SUIT. I 1403-M-104 I
F-A F1.10 VT-3 4/01/06 NRI M-31I11 SHIT. I 3204C-WV-IOlA&B I
F-A FI.10 VT-3 4/01/06 NRI M-31 If SI-IT. I 3001B-W-I02A&B I
F-A FI.10 j
VT-3 3/29/06 NRI NI-3136 SUT. 8 I013A-W-201 2
F-A FI.20 VT-3 3/16/06 NRI M-3 137 SUIT. 4 2304-M-209 2
F-A 17I.20 VT-3 3/28/06 NRI M-3135 SUIT.4 1403-M-203 2
F-A F1.20 VT-3 3/24/06 NRI M-3136 SUIT. 6 1006A-W-201 2
F-A FI.20 VT-3 3/21/06 ACCEPTABLE M-3 137 SI-T. 4 2304-G-205 2
F-A FI.20 VT-3 3/17/06 NRI I-3113SUIT. 3 10200-W-127A&B 2
F-A IFI.40 VT-3 4/02/06 NRI 9 of 19
'Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 20 6t1h Avenue North, Cordova, IL 61242 Table 3.1-1 Quad Cities Unit 2 Drawing Component Class Category Item Inspection Date Results NI-31135SUT. 3 0200-%V-128A&B 2
F-A F1.40 VT-3 4102106 NRI NI-3113SUIT. 3 0200-W-129A&B 2
F-A 17I.40 VT-3 4/02/06 NRI M-3136SUIT. 6 1008A-3 I
R-A R1.1lI UT-E (RISI EXPA.NDED) 3/22/06 NRI M-3136SUIT. 7 1010-6 1
R-A RIAlI UT-E (RISI EXPANDED) 3/23/06 NRI M-3 112 SUIT. 2 32C-S2 I
R-A RI. II UT-E (R ISk EXPANDED) 3/30/06 NRI M-3136 SHT. 6 1008A-17 1
R-A RIAlI UT-E (RISI EXPANDED) 3/22/06 NRI M-31365SUT. 4 1006C-3 I
R-A RI.1lI UT-E (RISI EXPANDED) 3/2 1/06 NRI M-3136 SUIT. 4 100813-1 1
R-A RIAlI UT-E (RISI EXPANDED) 3/21/06 NRI M-3136 SfT. 4 1006C-4 I
R-A RI I UT-E tRISI EXPANDED) 3/21/06
- NRI M-3136SUIT. 6 1008A-16 I
R-A R1.1lI UT-E (RISI EXPANDED) 3/22/06 NRI M-311lI SH-T. 2 32A-FI I I
R-A RIAlI UT-E (RISI EXPANDED) 3/29/06 NRI M-31 11 SUIT. 1 30A-SIO I
R-A R 1.20 UT-E (RISI EXPANDED) 3/29/06 NRI M-31Ill SUIT. I 3013-SO I
R-A RI 1.20 UT-E (RISK EXPANDED) 3/30/06 NRI M-31 11 SUIT. I 30A-S9 I
R-A R1.20 UT-E (RISk EXPANDED) 3/29/06 NRI M-3111 SHIT. 2 30C-S 18 1
R-A RI1.20 UT-E RISI EXPANDED) 3/31/0)6 NRI M-31Ill SUIT. 1 30A-S I I I
R-A RI 1.20 UT-E (RISI EXPANDED),
4/05A)6 NRI M-31 11 SIMT.2 30C-S 19 1
R-A RI1.20 UT-E (RISI EXPANDED) 3/29/06 NRI NI-3111I SUIT. I 30A-FI I
R-A RI1.20 UT-E (RISk EXPANDED) 3/30/06 NRI
-Subsequent Exams Due to IWF-2200(b)
M-31122SUT.lI 320413-W-101 I
F-A 171.10 VT-3 3/31/06 NRI M-3112 SUIT. 2 3204A-W-I02 I
F-A F71.1 VT-3 3/31/06 NRI M-3112 SUIT. 2 3204A-M-l0I I
F-A FI.10 VT-3 3/31/06 NRI M-31l11 SUIT. I 300IB-W-I03 I
F-A 17I.10 VT-3 3/29/06 NRI M-31I11 SHIT. I 3001B-M-106 I
F-A FLI.I VT-3 3/30/06 NRI NI-3118 SUIT. I 2305-M-104 I
F-A 171.10 VT-3 3/28/06 ACCEPTABLE M-3112SUIT. 2 3204A-M-104 I
F-A F7I.10 VT-3 3/30/06 ACCEPTABLE M-3111 SHIT. 2 300IC-NI-106 I
F-A FI.10 VT-3 3/30/06 NRI M-3111 SHIT.2 300ID-M-105 I
F-A 17I.10 VT-3 3/30/06 NRI M-31I11 SUIT. I 30OIA-NI-105 I
F-A F7I.10 VT-3 3/30/06 NRI M-3112 SUIT. I 3204B-M-103 I
F-A 171.10 VT-3 3/30/06 ACCEPTABLE M-3111 SUIT.2 300IC-W-l02A&B I
F-A F1.10 VT-3 3/29/06 NRI NI-3111 SilT. I 3001 B-W-104A&B I
F-A FI.IO VT-3 3/28/06 NRI 10 of 19
-Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 2 0 6 1h Avenue North, Cordova, IL 61242 Table 3.1-1A Quad Cities Unit 2 t
ASNM Section XI Limited Coverage Summary (4t Interval)
Drawing Component Class Category Item Inspection ASNME % Coverage M-3111 SHT.2 30C-S18' I
R-A RI1.20 UT 71 M-3121 SHT.2 RPV-VSCI-197 2 I
B-A BI.12 UT 38 M-3121 SFIT.12 RPV-VSC2-22' I
B-A BI.12 UT 66 M-3121 SHT. 2 RPV-VSC3-77 2 I
B-A B1.12 UT 82 NI-3121 SHT. 2 RPV-VSC3-197' I
B-A B1.12 UT 75 NI-3121 SHT. 2 RPV-VSC3-317' I
B-A B1.12 UT 79 M-3121ISIT. 2 NIANOZ2 I
B-D B3.90 UT 21 M-3 12 1 61-T. 2 N213 NOZ2 I
B-D B3.90 UT 37 M-3121 SHT. 2 N21)NOZ 2 I
B-D B3.90 UT 37 M-3I21 SHT. 2 N2E NOZ2 I
B-D B3.90UT3 1NOTE: Previous coverage on this wveld using '/4" of base metal wvas considered to be essentially 100%. Risk informed inspection increased base metal to 1/2"' causing this single sided access exam to decrease in the total examinable volume. 30C-S 18 has been removed and replaced with 30C-S 1 8R with new preservice inspections under the Acoustic Side Branch Modification.
2 NOTE:
These welds were limited during the 3rdinterval and were granted relief under Exelon Relief Request CR-20 and CR-32. Coverage was equal or greater under new examination.
I I of 19
.Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 2 0 6 1h Avenue North, Cordova, IL 61242 Table 3.1-2 Quad Cities Unit 2 Pressure Testing Summary (4th Interval)
Component Inspection Category Item Procedure/
Completion Relief Remarks
________________Number Report Date Request RCasIadB15.10, CS0210 Class I & 2 RXClssI nd Visual, VT-2 B-P 15.50, 15.60, QCS00-804113/06 14R1-07 System leakage Class 2 15.70 VT Report VT-4 Test b
NIO IRS Visual, VT-2 B-D B3.100 QCOS 0201-08 04113/06 1411-0 i Class I System VT Report VT2-047
_____________leakage Test CoeSry Visual, VT-2 B-P B
VT.5,157 Repo 020 -047 04/13/06 14R1-07 Class I System Class I VT.0 Re5.707204 leakac Test RHR Class I Visual, VT-2 B-P B 15..50, 15.70 QCOS 0201 -08 04/13/06 1411-07 Class I System
_________________VT Report VT2-047 leakage Test Reactor Vessel Lie203-1 Visual, VT-2 C-H C7.30, C7.70 099pr QR8BP-0/00 1411-05 Hed Flange Seal and 2-0234-I109 Leak Detection
__________System Core Spray Visual, VT-2 C-I-I C7.30, C7.50, VT2-277 10/18/05 14R-07 Class 2 System C7.70 VT2-266 09/08/05 Leakage Test CRD Visual, VT-2 C-H C7.10,0C.30, VT2-040 02/09/06 14R-06, 14R-Class 2 System C7.70 VT-018 01/10/06 07 Leakage Test ECCS Torus VsaV-H C73,7.0VT2-035 0 1/20/06 14R107 Class 2 System Suction Viul T2 CH 03,C.0VT2-28I 10/21/05 Leakage Test ECCS Fill Visual, VT-2 C-H C7.30,0C.50, VT2-279 10/2 1/05 14R1-07 Class 2 System C7.70 Leakage Test VT2-287 11/16/05 HPCI Visual, VT-2 C-11 C7.307.0, VT2-237*
10/21/05 1411-07 Class 2 System C7.7 VT2237*05/1/05Leakage Test
~~~~~~~~*QCTS 0762-02 V72-042*
02/13/06 V17-0 16 01/06/06' RHR Visual, VT-2 C-H C7.30, 07.50, VT2.002*
0 1/05/06 14R-07 Class 2 System C7.70 VT2-27 I 09/23/05 Leakage Test VT2-239 05/12/05
_________ __________*QCI-S 762 -07 TIC 1358 VT'2-043 2/24/06 VT2-014 01/06/06 SBLC Visual, VT-2 C-4 C7.30,0C.50, VT2-0I3 01/06/06 14R-07 Class 2 Systemn C7.70 VT-2-233*
05/I1I/05 Leakage Test VT'2-257 12/10/04
___________*QCTS 50762-08 Scram C0.10,0C.30, QCOS 0201-08 Class 2 System Discharge Visual, VT-2 C-H C..0 VT Report VT2-225 03/26/04 1411-07 Leakage Test Volume I______
J_______
I____I____I___I_
i 12 of 19
- Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 2 0 6 1h Avenue North, Cordova, IL 61242 Table 3.1-3 Quad Cities Unit 2 Snubber Functional Tests (4 th Interval)
Drawing Component TIS Number Class Category Ie Inspection Tested Rsut M-1026D-3l1 10 12A-W-102' 2-006 I
F-A F7I.40 Fr 04-Apr-06 PASS M-1026D-319 101213-W-101 2-008 1
F-A FI.40 Fr 28-Mar-06 PASS M-1022D-270 0200-W-109 A&B 2-013 1
F-A FI.40 FT 3 1-Mar-06 PASS M-1022D-271 0200-W-128 A&B 2-014 1
F-A FI.40 FT 29-Mar-06 PASS NM-1024D3-7 1307-M-106' 2-042 I
F-A FI1.40 FT 30-Mar-06 FAIL M-328E Sht. 2 3001A-M-l01.2 2-055 1
F-A 171.40 FT 28-Mlar-06 PASS M-3280 Slit. 8 2305-M-101.2' 2-076 1
F-A FI.40 FT 29-Mlar-06 PASS M-328G Slt. 9 2305-NI-l0l.l 2-077 1
F-A F1.40 FT 28-Miar-06 FAIL M-328G Slt. 22 2305-M-102.1' 2-078 1
F-A FI.40 FT 30-Mar-06 FAIL M-1802-O4Sht. 1,2 1025-NI-219 2-097 2
F-A FI.20 FT 22-Miar-06 PASS M-1802-26Slit. 1, 2 1025-M-201 2-102 2
F-A FI.20 FT 23-Mar-06 PASS M-1813-03 2306-Nt-206.1 2-114 2
F-A FI.20 FT 20-Mar-06 PASS M-1017D-59 2305-M-207' 2-120 2
F-A FI.20 FT 30-Mar-06 PASS M-1806-04 101513-M-203 A&B' 2-126 2
F-A FI.20 FT 04-Apr-06 PASS M-1806-04 101513-M-203 A&B' 2-127 2
F-A F1.20 FT 04-Apr-06 PASS M-1806-07 101513-M-201.1 2-128 2
F-A FI.20 FT 2 1 -Mar-06 PASS M-1813-06 2306-M-201' 2-143 2
F-A F7I.20 FT 02-Apr-06 PASS M-329B Slit. 6 N/A 2-026 NA NA NA FT 28-Mar-06 PASS M-1026D-93 N/A 2-036 NA NA NA FT 20-Mar-06 PASS M-1023D-57 N/A 2-038 NA NA NA FT 28-Mar-06 PASS M-1020D-502 Sht.
N/A' 2-040 NA NA NA FT 03-Apr-06 PASS M-328F Slt. 15 N/A 2-065 NA NA NA FT 28-Mar-06 PASS NI-1814-04 N/A 2-116 NA NA NA FT 2 1-Mar-06 PASS M-1815-02 Sht. 1, 2 N/A 2-119 NA NA NA FT 23-Mar-06 IPASS
'NT:These snubbers were tested as part of the expanded sample testing as a result of functional test failures (IR's 00471469, 00472956, and 00472989).
13 of 19
.Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 2 0 6 1h Avenue North, Cordova, IL 61242 Table 3.1-4 Quad Cities Unit 2 Conditions Noted and Corrective Actions (4 th Interval)
Cornponent ID Description/I Resolution Pressure Test During the Unit 2 Class I Leakage Test the listed components were identified to be leaking.
Corrective actions were taken as followvs:
Corrective actions completed "B" Recirculation Pump Flange.
Engineering evaluation (EC # 0000335753) was performed (as permitted by Relief Request 14R-07) on the 2B Recirculation Pump and determined the leakage to be acceptable.
Reference VT report #t VT2-047 dated 04/13/06 2-3299-129 Flange leak Issue Report 478659 Tightened Flange 2-0220-44 Flange leak Issue Report 478644 Repaired Valve
_HCU Vlv Flange leaks Reference EC 359753 evaluating Leakage Observed Report VT2-0 18 Visual Inspections As a result of inspections in accordance with ASME Section Xl IWVE 1992 Edition, 1992 Containment Penetrations XlI and Addenda degraded moisture barriers on penetrations XlI and X2 were identified. XlI and X2 X2 Moisture Barriers were repaired under Work Order ft 907825.
_________________________In Vessel Inspections Core Shroud Ring Segments Indications were observed on two of the core shroud rings during Q2R 18. At the Core Support Flange Ring, multiple crack-like indications were observed at the heat affected zone of circumferential weld H-5 (ER 475862). These indications do not pose a challenge to the structural integrity of the core support ring since the shroud stabilizers (tie rods) structurally reinforce welds H I through 1-17. Another indication was found on the top surface of the Shroud Head Flange ring (IR 475332). The indication appeared to be a scratch or small gouge. It did not line uip with any probable heat affected zone and did not have any depth when viewed from the vertical surface.
let Pump WD-I Vedge Wear During the IVV I visual examinations four (4) jet pumps were identified wvith evidence of main wedge (WD-l1) movement. GE Indication Notification Reports (INRs) and Exelon Issue Reports (IRs) were generated to document these conditions (IR 474814, IR 475009, IR 474491 and IR 474070). Additional inspections were performed as required by BWRVIP-41 a including supplemental visual inspections of the affected jet pumps to confirm overall pump integrity. The most severe wedge movement (on Jet Pump #07) was corrected via a planned restrainer bracket replacement under WO 823272-01. Quad Cities shall continue to monitor the condition of jet pump wedges during future IVV I visual inspections.
Feedwater Sparger End Brackets Seven of eight Feedwater Sparger End Bracket pins were welded into place dturing Q211 18.
This was a planned activity in response to a missing nut on a Feedwater Sparger End Bracket pin identif ied during Q2R 17. In addition, two of the pinheads were observed to be wearing into the bracket hardware during Q2R 18 due to flow-induced vibration (IR 474497). This is not a concern for the immediate future. The worst worn bracket still has greater than 90% of its original thickness remaining. Quad Cities will continue to monitor this condition. In the meantime, a long-term repair options are being evaluated.
Engineering Evaluation EC 360359 determined that all of the indications are acceptable for at least one cycle of continued operation.
14 of 19
- Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 206"' Avenue North, Cordova, IL 61242 Table 3.3 Quad Cities Unit 2 Category Exams Completed in Q21118 Exams Completed to Date Total Exam~s in the Interval Percentage Complete for Interval B-A 4 11 15 25 60 B-D) 8 20 58 34 B-GIl' 0
5 6
83 B-G-2 5
7 19 37 B-K 2
4 9
44 B-L-2' Not Applicable Not Applicable Not Applicable Not Applicable B-M-2' I
I 1
100 B-N-I 2 I
I 1
100 B-N-2' I
I 1
100 B-04 0
0 2
0 B-P' I
I 1
100 C-A 0
I 4
25 C-B 6 6
8 14 57 C-C 2
3 10 30 C-H' I
I 1
100 F-A 11 34 91 37 R-A 16 34 98 35
'Note:
Category B-G-1I is for reactor vessel studs and nuts. Items in this category are repeated each period and may 2
result in greater than the limiting percentage of exams.
32oe Category B-N-I and B-N-2 are inspected each period.
4 Note:
Category B-P and C-H exams are tracked under Table 3.1-2.
Noe Exam Category B-A and B-0 are scheduled to coincide with previous interval to maintain ten year interval between exams and are performed in accordance with I10CFR50.55a Period completion percentage does not apply.
'Nt:Categories B-L-2, and B-M-2 are inspected and credited under the Repair/Replacement Program only when 6
the component is disassembled.
Note:
Categories C-B components are examined during the performance of the system pressure test each inspection period and can result in greater than the limiting percentage of exams. Some of VT-2 for item number C2.33 were completed during 10/24/05 maintenance outage.
15 of 19
Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 4.0 Repair / Replacement Summary 4.1 NIS-2 Index Quad Cities Nuclear Power Station Unit 2 22710 2 06 1h Avenue North, Cordova, IL 61242 Table 4.1-1 Quad Cities Unit 2 NIS-2 List Program Number Component EPN Work Request Number ASNIE X1 Class or Purchase Order 01-056 0-Spare-V26 99225877-02 1________
02-149 0-Spare-V25 00410536-01 1____
03-056 &061 2-0203-2A 99149021-01,11 1___
03-084 2-0203-2D 00905448-01 1____
04-092 0-Spare-V-26 00638775-03 1____
04-093 0-Spare -V26 00638775-04 1________
05-019 2-0203-3A 00741114-01 1
05-057 0-Spare-V25 00749529-02 1 &2 05-059 2-0203-3A 00741114-09 1___
05-061 2-020 1-N6A 00732708-181 05-063 2-3001-A56 008 10572-011 05-064 2-0300-34-55 00809436-01 1____
05-065 2-0201-1 00687492-02 1____
05-070 0-Spare-V25 00749530-02 1 &2 05-073 2-1001-67C 00634293-01 2
05-076 2-1001-67B 00634292-01 2
05-083 2-0300-26-23 00678367-01 1
05-084 2-0300-10-31 00678367-02 1
05 -090 0-Spare-V25 00797734-02 1 &2 05-094 2-0300-38-11 00678367-031 05-095 2-0300-30-07 00678367-041 05-096 2-0300-38-03 00678367-05 1 ____
05-097 2-0300-38-07 00678367-06 1____
05-098 2-0300-38-IS 00678367-07 I1____
05-099 2-0300-18-27 00678367-08 I1____
05-100 2-0300-22-39 00678367-09 1 ____
05-101 2-0300-22-31 00678367-10 1
05-102 2-0300-26-07 00678367-Il I
05-103 2-0300-30-39 00678367-12 I
05-104 2-0300-42-07 00678367-13 1________
05-105 2-0300-46-11 00678367-141 05-106 2-0300-46-23 00678367-I5 1____
05-107 2-0300-58-27 00678367-16 I1____
05-108 2-0300- 10-27 00678367-17 1____
05-109 2-0300-18-39 00678367-18 1
05-110 2-0300-14-39 00678367-19 1 ____
05-1 11 2-0300-30-35 00678367-20 1 ____
05-1 12 2-1402-28B 0071 1451-02 2
05-I113 12-2301-23 1
00790545-02 2
05-1 14 12-1001-36B 1
00683075-01 2
16 of 19
- Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 20 6 Ih Avenue North, Cordova, IL 61242 Table 4.1-1 Quad Cities Unit 2 NIS-2 List Program Number Component EPN Work Request Number ASME XI Class or PurchaseOrder 05-115 2-1699-9 00765109-02 2
05-1 17 2-3007C-1.5" 00701257-01 1 _
05-118 2-3007D-1.5" 00701258-01 1________
05-119 2-2330-1.5" 00701259-01 1____
05-120 2-300713 1.5" 00701256-01 1 ____
05-121,06-077 2-1001-125C 00732429-03,01 2
05-127 & 128 2-I1106A 00738096-03,01 2
05-134,06-083, 06-2-2301-74 00774917-01 2
085 05-139 2-1001-34B 00454494-01 2
06-003 2-0203-413 00812173-01 1
06-004 2-0203-4A 00812172-011 06-005 2-0203-417 00729408-01 1____
06-006 2-0203-4E 00729090-01 1________
06-007 2-0203-313 00789813-01 1
06-0 13 2-0203-3D3 00883853-011 06-021 TS-2-28 00886262-01 1________
06-022 2-300 1-A55 00656068-01 1
06-025 2-0203-4C 00885318-01 1___
06-026 2-0203-413 00885319-01 1________
06-027 2-0203-4G 00885320-01 1________
06-028 2-0203 00885321-01 1____
06-034 2-0203-3E 00789812-01 1________
06-039 0-Spare-V26 00902278-01 1________
06-040 0-Spare-V26 00902278-02 1
06-041 0-Spare-V26 0090227 8-03 1
06-043 2-0203-4A thru H 00885018-131 2-0203-313 thru E__________
06-044
~2-0203-3CID850841 06-044
~2-0203-4C/D/G/H850841 06-045
~2-0203-3B/E850-11 06-045
~2-0203-4AIB/EIF88081I 06-049 0-5 pare-D I5 PO# 707 Re!. 1515471 06-050 0-Spare-D 15 PO# 707 Re!. 151547 1
06-051 0-5 pare-D 15 PO# 707 Re!. 151547 1____
06-052 0-Spare-D 15 PO# 707 Rel. 1515471 06-053 0-Spare-DIS5 PO# 707 Ret. 151547 1___
06-054 0-Spare-D 15 PO# 707 Ret. 151547 1____
06-055 0-Spare-D 15 PO# 707 Rel. 151547 1 ____
06-056 0-Spare-DIS5 PO# 707 Rel. 151547 1
06-057 0-Spare-D 15 PO# 707 Re!. 151547 1___
06-058 0-Spare-DIS5 PO# 707 Re!. 151547 1
06-059 0-Spare-D 15 PO# 707 Rel. 151547 1
06-060 0-Spare-D 15 PO# 707 Rel. 151547 1
06-061 0-Spare-D15 PO# 707 Ret. 151547 1
06-062 0-Spare-DI5 PO# 707 Rel. 151547 I
17 of 19
Exelon Generation Company, L.L.C.
300 Exelon Way Ken nett Square, PA 19348 Commercial Service Date March 10, 1973 Quad Cities Nuclear Power Station Unit 2 22710 20 6tIh Avenue North, Cordova, IL 61242 Table 4.1-1 Quad Cities Unit 2 NIS-2 List Program Number Component EPN Work Request Number ASME XI Class or Purchase Order 06-063 0-Spare-D15 PO# 707 Ret. 151547 1____
06-064 0-Spare-D 15 PO# 707 Rel. 151547 1
06-065 0-Spare-D 15 PO# 707 Rel. 151547 1___
06-066 0-Spare-D 15 PO# 707 Re]. 15!5471 06-067 0-Spare-D 15 PO# 707 Rel. 151547 1
06-068 0-Spare-DIS5 PO# 707 Rel. 151547 06-070 2-2305-77 00656074-011 06-071 2-0220-2 00905901-01 2
06-075 2-1001-125A 00832684-01 2
06-076 2-1001-125B 007761 13-01 2
06-078 2-2305-78 00906180-01 1
06-079 TS-2-042 00906183-01 1
06-082 TS-2-127 00907358-01 2
06-086 2-0203-3A 008 18566-071 06-125 210-599242367-02 2
18 of 19
.Exelon Generation Company, L.L.C.
300 Exelon Way Kennett Square, PA 19348 Commercial Service Date March 10, 1973 4.2 NIS-2 Forms (Attached)
Quad Cities Nuclear Power Station Unit 2 22710 2 06 Ih Avenue North, Cordova, IL 61242 19 of 19
FORM NIS-2 OWNERS REPORT OF REPAIR OR REP~LACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
02/19/03 Sheet:
I of I Unit:
0 Pro~gram Number 01-056 WOII99225877-02 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam: Class I (spare)
- 5. (a) Applicable Construction Code: "USAS B3-31.1 1965 Edition, None Addenda, N/LA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1989 Edition,.N/A. Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Component Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Code M fr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Electromatic Relief Valve Dresser BK 7069 N/A 0-Spare-V26 N/A Replacement No
- 8. Tests Conducted:
Hydrostatic El Pneumatic E]
Nominal Operating Pressure E Other El Pressure ___ psi Test Temp._
' F
- 9. Remarks: No pressure testing required.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replcement conforms to the rules ofASME Code,* Section XI rearor replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of A orization No.
N/A Expiration Date N/A Signed
--4,5 e c
>r~n Date A-~4
/a/
20 0Z
\\\\ner or Ow~ner's Designree, TIitle CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois, and employed by IISB3 CT of Connecticut _have inspected the components described in this Owner's Report during the period
(.4(?S-10 (
to
^.elf '165M
, and state that to the best of my knowl~edge and belief, the owvner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section X1.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Fur-thermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
I~
Commissions
-Commissions JL1 /525O National Board. State. Pro~ince.
and Endorsenments Inspectors Signatur/'
/-- -V Date 20 O,$r Date 20 C)Y
FORM NIS.2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
3/3/2006 Sheet:
I of I Unit:
0 Program No.02-149 W'O 00410536-01 Repair Organization P.O. No., Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Feedwater, Class I (Spare)
- 5. (a) Applicable Construction Code: USAS B3 1.1 1967 Edition, None Addenda, N/
Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1989 Edition, None Addenda, N-496-1I Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Check Valve Crane N/A N/A I0-spare-V25 N/A Repaired No
8 " 'ts Conducted:
Hydrostatic E]
Pneumatic 11 Nominal Operating Pressure E3 Other E]
Pressure ___
psi Test Temp.
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair conforms to the rules of ASME Code,Section XI Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App~ B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed NW Al Mati" tývr DteY4
,,S 20 O~p IV Oneror Oner Lkignet.Tit CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT. of Connecticut have inspected the components described in this Ownier's Report during the period
/~A -
o4/16
,adsaeta otebs fmy knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or
)roperty damage or a loss of any kind arising from or connected with this inspection.
Commissions 1-f.1ipstor% Signaturc Z11. /0 Co
(/()
NatkmnaI Board. Sm~e. Pnnmimwe. ~and Endom~menis 20 20
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. O~ner:
Exelon Generation Company. LLC 41300 Winfield Road W~arrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
05/25/2006 Sheet:
I of I Unit:
2 Program No.03-056. 03-061 WO 09914902I-t). - Ii Repair Or-ant/ation P.O. No.. Joh No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam. Class 1
- 5. (a) Applicable Construction Code: ASA B3 1.1 1955 Edition. NIA Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mlfrs. Ser.
Nat'l Other Year Repaired.
ASNIE Component Mfr.
No.
Bid.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
ValIve Exelon N/A N/A 2-0203-2A N/A Repaired No
- 7. Description of Work: Overhauled valve in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic E:
Pneumatic 1:
Nominal Operating PressureQ Other 0 Pressure ____
psi Test Temp.
- 9. Remarks: Appendix J testing.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair conforms to the rules of ASNIE C'ode. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Fxelon Nuclear I 0CFR5() App B. 0 A Program Certificate ot* Authorization No.
N/A.
Expiration Date N/A Signed ________________
Pepe__________Date O
CERTI FICATE OF INSER VICE INSPECTI[ON
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel inspctbors and the State olf Illirtoi
.and employed hy IS13 (1'. of Connecticut
-have inspected the comnponents described in this Ownecr~s Report (lUring the period 1,211a. to
________.and state that to the best ofiny knowledge and belief' the owner has performned examinations and taketi corrective mecasures described in this Oýner~s Report in accordanice the requirements of the ASNIE Code.Section X.
w.
By signing thIiis cert ificate. neither the inspector nor Iiis employer makes any warranty. ex~pressed or implied, concerning thie exam iinat ions and corrective measures dlescribedl in this Owner's Report. Furthermuore, neither the Inspeetor nor his employer shall be liable in any mnitmer for any personal inljury or prop, t Ilaag or a loss of any kind arising fromn or connected with this inspection.
- -I C/(J N.6)11.11a M~:
i.le. tfl1vIICe. and ktrcIa Da.te 6114ý2
- 0) 66
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/18/2006 Sheet:
I of I Unit:
2 Program No.03-084 WO 905448-01 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASA B31.1 1955 Edition, N/A Addenda,.N/A. Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Valve Exelon N/A N/A 2-0203-2D N/A Repaired No
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic E5 Nominal Operating Pressure5 Other Z Pressure ___
psi Test Temp.
'F
- 9. Remarks:
Appendix J testing.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed ________________________te-Date Macy 1'
200(,
CERTIFICATE OF INSER VICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HISB CT. of Connecticut
_have inspected the components described in this Owner's Report during the period
/.R 114-l.6-A to c'641,/oA and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
~ ~*(/( ~Commissions
/
/00h 4
N.itkonaI nD,,uJ State. Proince. aKIn Eidurciwnns
FORMN NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
04/6/2006 Sheet:
I of I Unit:
0 Program No.04-092 WO 00638775 Repair Organization P.O. No.. Job No.. ect.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. identification (it System Spare Electromatic Relief Valve. Class 1
- 5. (a) Applicable Construction Code:
tJSAS 1331.1 1967 Edition. N/A Addenda. N/A Code Case (b) Applicable Edition of Section X1 Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or code No.
Replacement Stamped (Yes or Relief Valve Dresser IND.
BX-00293
_____ N/A_____ I_____
_______________Relacmen No
- 7. Description of Work: Seal weld the insert ring disc retainer plate to the valve cage in accordance wvith WV.O.
- 8. Tests Conducted:
Hydrostatic El Pneumnatic E:
Nominal Operating, Pressure El Other Pressure psi Test Temp.____ '17
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statcmicnts made in this report are correct and this replacement conforms to the niles of ASME Codec. Section Xi repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App 13.-0 A Prouram Certificate of Authorization No.
N/A Expiration Date N/A Sine Wnrb we' eind CERTIFICATE OF INSER VICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and thle State of Illinois.and employed by I-ISB C7. of Connectictut have inspected the components dlescribed in this Owner's Report during the period /,j/-.e76t
-14 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective meaUsures described in this Owner~s Report in accordance the requirenments ofllte ASME Code.Section XI.
By signing this certificate. neither the inspector nor his employer miakes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall he liable in any manner for any personal inljury or property- (damage or a loss of any kind arising from or connectcd with this inspection.
y/(J Nawn.d fInniae.and hido,.-twnt, 20 04-
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASNIE Code Section XI I. Owner:
Exelon Generation Company, LLC 4300 Win field Road Warrenville. 11. 60555 2.Plant:
Quiad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242
- 3. Work Per-formed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
04/6/2006 Sheet:
I of I Unit:
0 Program No.04-093 WO 00638775-04 Repair Organization K.O. No.. Joh No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System Spare Electromatic Relief Valve, Class 1
- 5. (a) Applicable Con.struction Code: USAS Bl31.1 I 967/ASNE Section Ill 1 980,.1995 E-dition.
1980. 1996 Addenda, N/A Code CaSe (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A_ Code Case
- 6. Identification oftComponents Repaired or Replaced, and Replacement Components:
Name of Name of Mlfrs. Ser.
Nat'l Other Year
- Repaired, ASMNE Component Mifr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Relief Valve Dresser IND.
BX-00293 IN/A I
-Spare-V26
-r N/A Replacement No
- 7. Description of Work: -Performed EPRI 2 to I wveld on body to pipe weld in accordance with the W.O.
- 8. Tests Conducted:
Hydrostatic 1:
Pneulmatic 1:
Nominal Operating Pressure El Other 51 Pressure ____
psi Test Temp. -
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conformris to the rules of ASNIE Code. Sect ion X I repair or reptacemient Type of Code Symbol Stamp N/A - Exclon Nuiclear I OCFR50 App R. 0 A Proeram Certificate of Authorization No.
N/A Expiration Date NIA Signed CWIIJ tz-,
_Date A~-i~
20 Z)&
CERTIFICATE OF INSER VICE INSPECTION
- 1. the undersigined. holding a valid comm~lfission issued by the National Board of Boiler and pressure Vcsscl Inspectors and the State oh Illinois
.and employed by HSB CT. of Connecticuti have inspected thc components described in this Owner's Report during the period
/ZZZ/
4_1:, to
.and state that to thie best of my knowledge and belief. the owner has performed examinations and taken corrective m~easutres described in this Owneiir's Report in accordance the requirenicnts of the ASME Code. Section Xh.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owncr's Report. Furthermore, neither the Inspector nor his employer shall he liable in any manner for any personal injury or property damage or a loss of any kinid arisinge from or connected with this inspection.
Date tlý 121 N.I it ulI lI trd. St aw. PI',~in1VV. JI1ki [ tit],r,.miv I%
Date
'1 /~i20
FORM NIS.2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by tile Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
02/20/2006 Sheet:
I of I Unit:
2 Program No.05-019 WO 7411 14-01 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Sect. 111 1968 Edition. Winter 1968 Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
____No)~
Valve Exelon N/A N/A 2-0203-3A N/A Replacement No
- 7. Description of Work: -Replaced valve in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic nl Nominal Operating Pressuire Other Q Pressure ____
psi Test Temp.
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASNIE Code. Section Xl repair or replacenment Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50) App B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed t-0Z 204A1 P^"
C'o Dt CERTIFICATE OF INSER VICE INSPECTION L. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut
.have inspected the components described in this Owner's Report during the period 1 211416/o5 to OXZ304and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this' Owner's Report in accordance the requirements of the ASME Code. Section Xi.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of ny kind arising from or connected with this inspection.
____________________________________Commissions
'-fnspetr..
signatuire Date 621h3 V
V Nati'uil 13tiard. Stare. Pri.vne. anrd Endoreamint%
20 C' (~
20 V 6
FORMN NIS.2 OWNERS REP~ORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
03/20/2006 Sheet:
I of I Unit:
0 Program No.05-057 WO 00749529-02 Repair Organi7ation P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Feedwater, Class I or 2
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda.
N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Compon.ents:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASMIE Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Valve Exelon N/A N/A r0-SPARE-V25 N/A Replacement No
- 7. Description of Work: Realaced valve disc hard-facing by machinine and welding in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic Pneumatic Nominal Operating Pressure 5l Other 5 Pressure ____
psi Test Temp.
O___
F
- 9. Remarks:. None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this rcport are correct and this replacement conforms to the rules of ASNIE Code.Section XI repair or replacenment Type of Code Symbol Stamp N/A - Exelon Nuclear IO0CFR5() Ann B. 0 A Proura Certificate of Authorization No.
NIA Expiration Date N/A Signed Cp-jmP--,-VV.-
Dt m$'4ecl 14
-200CPn Tnerbr~wner'Asignece.
itic CERTIFICATE OF INSER VICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors-and the State of Illinois
. and employed by FHSB CT. of Connecticut
-have inspected the components described in this Owner's Report during the period AA114-1o*..
to Jz/271e,6
,and state that to thc best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code. Section Xl.
By signing this certiFicate. ncither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Rcport. Furthermore. neither the Inspector nor his employer shall be liable in any nmanner for anmy personal injury or property damage or a loss of any kind arising from or connected with this inspection.
C (
"r-i4 Commissions
/
~ 6 irspdo 1 Lrtire Nj.,,,
I I,rd. Sli it. hu ince. amli I oxhwrememl n:111-fl~~iit' 00flV(,
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
02/20/2006 Sheet:
I of I Unit:
2 Program No.05-059 WO 7411 14-09 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Sect. HI1 1968 Edition. -Winter 1968 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. -N/A Code Case
- 6. Identification of Componcnts Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Set.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Valve i
Exelon N/A 1 N/A I
2-0203-3A
-t N/A i
Replacement No
- 7. Description of Work: Installed hvdranuits on Target Rock relief valve in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic 13 Nominal Operating Pressure El Other' El Pressure ____
psi Test Temnp.
F
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE WVe certify (hat the statements made in this report are correct and this replacement conforms to the rules of ASME Code. Section Xl repair or replacemnent Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed 1
A-L
'2 ae 0
-20 Oe CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
.and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period
/2/~O~
to
/3/6
.and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- C: s 2
r,
~
Commissions
/Z -
O Date 5/Z3 20 C,
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASMIE Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 227 10 206th Ave. North. Cordova. IL 61242
- 3. Work Per-formed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 612-42 Date:
03/20/2006 Sheet:
I of I Unit:
2 Program No.05-061 WO000732708-18 Repaii-Oiganitatioii P.O. No., Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Vessel. Class 1
- 5. (a) Applicable Construction Code: ASMIE Section 111 1965 Edition, Summer 1965, Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:. 1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of M~frs. Ser.
Nat'l Other Year
- Repaired, ASNIE Component Mfr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Flange assembly Exelon
_N/A N/A 12-0201-N6A N/A Replacement No
- 7. escipton f Wrk:Insalld fane and special fasteners for dIryer monitornng instrumentation in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic F]
Pneumatic El Nominal Operating Pressure Other El Pressure
-___ psi Test Temp.
-___ 'F
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report arc correct and this replacement conforms to the ruilcs of ASNIE Code.Section XI repair or replaceencit Type of Code Symbol Stamp N/A - Exelon Nuclear I 0CFR5O App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed.fi&
Lj, L k !5
-C A$P ate Waea.
/71
.200(l-V/O~fner otwnier'sD Mighee. Titk e
CERTIFICATE OF INSER VICE INSPECTION
- 1. thie undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois. and employed by IISB CT'. of Connecticut
-have inspected the components described in this Owner's Report during the period alil-to and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective m'ea'sures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranity. expressed or implied, concerning the examinations and corrective meaCISUres described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or propcrty damage or a loss of any kitnd arising from or connected with this inspection.
f'(
(?LCommissions~
lsirectw, Signmute 3 //- 41' V(ý NalwnJ R."Ird.
111m wce. and I 'Id"I !Ilwjlfý 34e/
2006&
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/23/2005 Sheet:
1 of I Unit:
2 Program No.05-063 WO 00810572-01 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: USAS B3 1.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:_______________
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Snubber Clamp Exelon N/A N/A 12-3001-A56 N/A Replacement No
- 7. Description of Work: Replaced missing snubber clamp nut in accordance with the Work Order.
- 8. Tests Conducted:
Hydrostatic F]
Pneumatic 11 Nominal Operating Pressure El Other E]
Pressure psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
_MAjUL'.-
6p rJPro,-
Date mVI y 200 oL V Owntr or Ownier's De~igntc, Tit
/
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commidssion issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut
_have inspected the components described in this Owner's Report during the period 1-41V-1a6.
to 2L-b-tijP,6 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASMVE Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any wvarranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspcctor nor his employer shall be liable in any manner for any personal injury or property damage or a loss oankind arising from or connected with this inspection.
77 e)(
Cmi~n'
~
/
/~
AI-V.
_________________________________________________________a_
lnsrýfors Sigmiture 1
Date
'Vet -Ile 2, Njt4,11.nJ 13uxud. Stat,Ie piviine. and EdrsWieicnris Date '-/'Ve 2/200
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, Il. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
02/21/2006 Sheet:
I of I Unit:
2 Program No. 05-064_WO 809436-01 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class 1
- 5. (a) Applicable Construction Code: ASME Sect. 1I111974 Edition, Winter 1975 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996~ Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Control Rod Drive Exelon N/A N/
2-0300-34-55 N/A Replacement No
- 8. Tests Conducted:
Hydrostatic []
Pneumatic E]
Nominal Operating Pressure E Other El Pressure psi Test Temnp.
- 9. Remarks: None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this jepiacement conforms to the rules of ASME Code, Section Xl repair or repra-cement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Ap B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
'1 A im e
ývy-Date 21
- 20CC, CERTIFICATE OF INSER VICE INSPECTION 1, the undersigned, holding a valid commidssion issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT. of Connecticut
-have inspected the components dcscribed in this Owner's Report during the period 42t/Lto 0 414ejL
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective nksures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this ccrtificatc, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
')
60'1 Commissions 16i / e0&6
$;:istencp Sfig~ai
, :ý /,Z3 U()0 National Boant, State, Province. and Endorsenrnts D~ate
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASNIE Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenvilic, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
3/2/2006 Sheet:
I of I Unit:
2 Pro.-ram No.05-065 WVO 00687492-02 Repaiir Org iziation P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Vessel, Class 1
- 5. (a) Applicable Construction Code: ASME Sect. III Class A 1965 Edition. Summer 1965 Addenda, N/A Code Case (b) Applicable Edition of Section Xf Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of' Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component M fr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Reactor Vessel Chicago Bridge & Iron T22 N/A 2-0201-I 1970 Replacement Yes
- 8. Tests Conducted:
Hydrostatic [E Pneumatic []
Nominal Operating PressureL Other Qj Pressure
_ psi Test Temnp.
'17
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE WVe certif'y that the statements imade iii this report are correct and this replacement conformis to the rules of ASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Autthorization No.
N/A Expiration Date N/A Signed rlW -ý,m PO~vp XpveG-Date ma1i~
f 20 O&
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding,- a %alid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
.and employed by I-SB CT..of Connecticut
.have inspected the components described in this Owner's Report during the period AYAVf4 VLC to
.3q0 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective tmeasures described in this Owncr's Report in accordance thie reqJuirements oif the ASME Code,Section XI.
By signing this certificate, neither the inspector nor-his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owtner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injulry or property damage or a loss fa arising from or connected with this inspection.
((L
~ t '
-,Commissions
/60__________
Date...
3/
2o C,
FORMN NIS.2 OWNERS REPORT OF REPAIR OR REPLACEMNENT As Required by the Provisions (if ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordo% a. IL 61242 Date:
Sheet:
Unit:
04/6/2006 1 of I Program No.05-070 WO 00749530 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System Spare Feed Water Check Valve. Class I or 2
- 5. (a) Applicable Construction Code: USAS 133 1.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda.
N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Nanie of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Valve Disc Crane Nuclear N/A N/A I 0-Spare-V25 N/A Replacement No
- 7. Description of Work: Replaced the hard facine on the disc in accordance with WV.O.
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure E]
Other Eý Pressure
____psi Test Temp.
-___ 'F
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASIE Code.Section XI repair or replacement Type of Code S) mbol Stanip N/A - Exelon Nuclear I OCFR50 AL\\on B. 0 A Prograin Certificate of Authorization No.
N/A Expiration Date N/A Signed AhLP-,
Date Ap~,-;
1 2y V wror Owner's Mine i
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issuted by the National Board of Boiler and Pressure Vessel Inspectors and thie State of Illinois
. and employed hy IISB CT. of Connecticut
-have inspected the components described in this Owner's Report during the period
/3L,ý. lc5-to 41/.S' /c'(.
. and state that to the best ofinmy knowledge and belief. the owner has performed examinations and taken corrective measures described in this Owvner's Report in accordance the requirements of the ASMIE Code. Section XlI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measuires described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected wvith this inspection.
2~( (
K~/t7 L'r,
_Commissions
/-
/
6
. In,1voor, Si-puturc 20 ol)/
N.vional flntrd. Stme. I'm, ince.and I
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, I L 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/22/2005 Sheet:
I of 1 Unit:
2 Program No.05-073 WO 00634293 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Residual Heat Removal, Class 2
- 5. (a) Applicable Construction Code: -USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Check Valve CS Valve CO.-
N/A N/A 12-1001-67C N/A Replacement No
- 7. Description of Work: -Replaced the valve in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic 1:
Pneumatic El Nominal Operating Pressure Other E]
Pressure ____
psi Test Temp.
'17
- 9. Remarks: None CERTIFICATE OF COM PLIANCE WVe certify that the statements made in this report are correct and this replacement conforms to the rules of ASMIE Code.Section Xl repair or replacemient Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signedric or Owner' ~Designec.rlehe
, vDa L
2' 20O CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT. of Connecticut
-have inspected the components described in this Owner's Report during the period a&/6ý -- to
. and state that to the best of my knowledge and belief. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
I______&( ___________L_____Commissions
£Al- /ft~
Date A Z4.'
20 OS__
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exe Ion Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/22/2005 Sheet:
I of, I Unit:
2 Program No.05-076 WO 00634292 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Residual Heat Removal, Class 2
- 5. (a) Applicable Construction Code: -USAS B3 1.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or NoNo Check Valve CS Valve CO.
N/A N/A 12-1001-67B N/A Replacement No
- 7. Description of Work: -Replaced the check valve in accordance with the WNO.
Tests Conducted:
Hydrostatic E]
Pneumatic E]
Nominal Operating Pressure El Other LI Pressure ____
psi Test Temp.
-__ '17
- 9. Remarks: IR 355917 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed sI0siebjtj Pey3 5!:ipv Date JUL b ZI 20 02.
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by I-SB CT. of Connecticut
_have inspected the components described in this Owner's Report during the period C,5/
a /CS; to
_C7 tJ/O
, and state that to the best of my knowledge and belief, thle owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
I_____________________
Commissions 3t-1sz.
/
s.pcvors Sig~f~lurc j u,L,,
zs-National Board. Slatc. Provinm mid Emlorwinem%
20
-,5
IORNI NIS-2 OWNERS REIPORT OF REPAIR OR REPLACEMEINT As Required by the Provisions of ASM\\E Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242
- 3. Work Performed by:
Qu~ad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
5/4/2006 Sheet:
I of 3 Unit:
2 Programn No. Various. WO 00678367 Repair Organizat ion P.O. No.. Joh Mo.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Control Rod Drive,. Class I
- 5. Ia Apj dicable Consi-isuctioit COdIC: Comiponenit: AsNIIE sect io 111 1 905 Edition.
W-1965 AddenC1da.
N/A COdIC Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Comiponents Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or SeeAtt._A No)__
- 7. Description of W ork: -Replaced Control Rod Drives and bolting in accordance with thle NV.O.
- 8. Tests Conducted:
Hydrostatic E1 Pneumatic 1:
Nominal Operating Pressutre ED OtherE]
Pressure ___
psi Test Temp.
- 9. Remarks:
None CERTIFICATEu OF COMPLIANCE We certif3' that tie statemients iiade in this report are correct and this reLIj4cemnjit conformis to the rules ut ASME Code.Section XI repair or replacement Type of Code.Symibol Stamrp N/A - Fxefon Noclear I OCIFIRS5!Ap~p.
A Prognim____
Certificate of' Author01ization No.
N/A Expiration Date N/A Signed COA
(
Mr
~~
- e.
Dt a
p 200(,.
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigncd. holding a valid commission issued by thie National Board of Boiler and Pressure Vessel Inspectors and t(li Staite of Iffllois and emrployed by I ISB CT.of Connect icut -have inrspected Ithe comiponents described in thiis Ownier's Repor)it during, tlie pertiod a21y!Z,._6 to 25Z Z6
.- anidstatelthatttoithelhest of mly knIowledgeC.andLIbel i~e1tie ownerlhas performiiedlexaminaii~tionisanid taken corrective rifeas'ures described in thi's Owner's Report in accordance the requirements of tile ASME Code. Section Xl.
By signing this certificate, tneither the inspector nor his emiployer makes any warranty, expressed or imiplied. concerning the examiinations and corrective mneasures described in this Owner's Report. Furthermore, nieither tlie Inspector tior hisciemployeir shlil be liable in any manner for any personal injury or property damiage or a loss of any kind arising fromt or connected with this inispection.
~~~Comimissions 14.-/CC~-_______
Riteatm u/flw IZ/
udo 2t) ( 7 Date 2)711",
C-,
)
__ (V 0
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT (Supplement)
As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 Date:
5/4/2006 Sheet:
2 of 3 Unit:
2 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Program No. Various. WO 00678367 Repair Organi/iz'ti ou P.O. No., Job No.. etc.
Type Code Symbol Stamp:
None
- 3. Work Performed by:
Quad Cities Generating Station Authorization No.:
None 22710 206th Ave. North, Cordova, IL 61242 Expiration Date:
N/A
- 4. Idlentification of System: Control Rod Drive. Class 1
- 5. (a) Applicable Construction Code: Component: ASME Section 111 1965 Edition.
WV-1965 Addenda. N/A Code Case (h)Applicable Edition of Section XI Utilized for Rcpairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case Attachment A Name of Name of Mlfrs. Ser.
Nat'l Other Y'ear Repaired.
ASME Program Component M fr.
No.
Bd.
Identification Built Replaced. or Code No.
No.
Replacement Stamped (Yes or
_____No)
Control Rod Drive GE Nuclear S/N: 1203 N/A 2-0300-26-23 N/A Replacement Yes05-083 Energy Control Rod Drive GE Nuclear S/N: 1824 N/A 2-0300-10-31 N/A Replacement Yes05-084 Energy____________
Control Rod Drive GE Nuclear S/N: 565 N/A 2-0300-38-Il N/A Replacement Yes05-094 Energy Control Rod Drive GE Nuclear S/N: 6184 N/A 2-0300-30-07 N/A Replacement Yes05-095 Energy Control Rod Drive GE Nuclear S/N: 1940 N/A 2-0300-39-0)3 N/A Replacement Yes05-096 Energy Control Rod Drive GE Nuclear S/N: 676 N/A 2-0300-38-07 N/A Replacement Yes05-097 Energy Control Rod Drive GE Nuclear S/N: 331 N/A 2-0300-38-15 N/A Replacement Yes05-098 Energy Control Rod Drive GE Nuclear S/N: 163 N/A 2-0300-18-27 N/A Replacement Yes05-099 Energ~y I_____________
Control Rod Drive GE Nuclear S/N: 558 N/A 2-0300-22-39 N/A Replacement Yes05-100 Energy_____
Control Rod Drive GE Nuclear S/N: 484 N/A 2-0300-22-31 N/A Replacement Yes05-101 Energy Control Rod Drive GE Nuclear S/N: 370 N/A 2-0300-26-07 N/A Replacement Yes05-102 Energy Control Rod Drive GE Nuclear S/N: 9350 N/A 2-0300-30-39 N/A Replacement Yes05-103 Energy Control Rod Drive GE Nuclear S/N: 6473 N/A 2-0300-42-07 N/A Rcplacement Yes05-104 Energy Control Rod Drive GE Nuclear S/N: 637 N/A 2-0300-46-I1I N/A Replacement Yes05-105 Energy Control Rod Drive GE Nuclear S/N: 1451 N/A 2-0300-46-23 N/A Replacement Yes05-106 P__
Energy I__________
FORM NIS-2 OWNE.RS REPORT OF REPAIR OR REPLACEMENT (Supplement)
As Required hy thle Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 227 10 206th Ave. North, Cordova. IL 61242 Date:
5/4/2006 Sheet:
3 of 3 Unit:
2 Program No. Various. WO 00678367 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None
- 3. Work Performed by:
Quad Cities Generating Station Authorization No.:
None 22710 206th Ave. North. Cordova, IL 61242 Expiration Date:
N/A
- 4. Identification of System: Control Rod Drive, Class 1
- 5. (a) Applicable Construction Code: Component: ASMF. Section 111 1965 Edition.
W-1965 Addenda. N/A Code Case (h) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASNIE Program Component Mfr.
No.
Bd.
Identifieation Built Replaced, or code No.
No.
Replacement Stamped (Yes or
____No)
Control Rod Drive GE Nuclear S/N: 7069 N/A 2-0300-58-27 N/A Replacement Yes05-107 Energy Control Rod Drive GE Nuclear S/N: 57 1A N/A 2-0300-10-27 N/A Replacement Yes05-108 Energy Control Rod Drive GE Nuclear S/N: 156 N/A 2-0300-18-39 N/A Replacement Yes05-109 Energy Control Rod Drive GE Nuclear S/N: A4564 N/A 2-0300-14-39 N/A Replacement Yes (05-I110 Energy Control Rod Drive GE Nuclear SIN: 1924 N/A 2-0300-30-35 N/A Replacement Yes 015-111I Energy I______
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL. 61242 Date:
03/20/2006 Sheet:
I of I Unit:
0 Program No.05-090 WO 00797734-02 Repair Organization p.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Feedwater, Class I or 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Valve Exelon N/A N/A 10-SPARE-V25 N/A Replacement No
- 7. Description of Work: Replaced valve disc hard-facing by machining and welding in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic Q1 Pneumatic E5 Nominal Operating Pressure E]
Other 51 Pressure psi Test Temp.
F
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IlOCFR50 ApR B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed 6!wtn eo%6rsr
-ieDate Atlart.. vj,)
200(o CERTIFICATE OF INSER VICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut.have inspected the components described in this Owner's Report during the period ~
to 3/19. /06
, and state that to the best of my knowledge and belief, the owner has performed examnainad taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
7IziŽ19 K2 Commidssions It/4~&
Natkonal NBomi. State, Province, and Endtrsententst Date 34
FORM NIS-2 OWNERS REPORT OF REP~AIR OR REPLACEMENT As Required by the Provisions of ASNIE Coce Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242
- 3. Work-Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
06/09/2006 Sheet:
I of I Unit:
2 Prooram No.05-112 W0 0071 1451-02 Repair Or~anization P.O. No.. Jot' No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: High Pressure Coolant Injection, Class 2
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda.
N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mvfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or
______TL_
9932___
No)
Relief Valve Dresser TL935 1N/A I
2-1402-28B--
N/A Replacement Yes
- 7. Description of Work: Replaced the relief valve in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic E3 Pneulmatic 1:
Nominal Operating Pressure ED Other E]
Pressure
-_ psi Test Temp.
-_ 'F
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that (fhe statements made in this report are correct and this replacement conflormisto thierules of ASME CodicSection Xl repai~r or replacemecnt Type ot Code Symbol Stamp N/A - Exelon Nuclear I0CF*R5O App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed ______________________
Date _____________
(e CERTIFICATE OF INSERVICE INSPECTION I. the undersigned. holding a valid commission issued hy the National Board of Boiler and Pressure Vessel Inspectors and (lie State of Illinois and cmploycd by I18(I'B.T of Connecticut_ have inspected the comnponents described in this Owner's Report during t he period Al/~//1/
to 04/1 476and state that to thle best of my knowledge and belief*, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requircmnents of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer inakes any warranty, expressed or iimplied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neithcr the Inspector nor his employer shall be liable in any inanner for any personal injury or property damiage or a loss of any kind arising from or connected with this inspection.
151-V ý Commissions
/Z.~"~
IiI.p~ u..r' *.i.'n iIur~
(I, Ni6ail Board. Snie, Pim ince. jml Vrdorýenwju,
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xl
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
4-20-2006 Sheet:
I of I Unit:
2 Program No.05-113 WO 00790545-02 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: High Pressure Coolant Injection, Class 2
- 5. (a) Applicable Construction Code: Section VilI Div. 1 1967 Edition, N/~A. Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Mfr.
No.
B~d.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Relief Valve Dresser TP21765 rN/A 2-2301-23 N/A Replacement Yes
- 7. Description of Work: Replaced the relief valve in accordance with the W.O.
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure E0 Other El Pressure
-___ psi Test Temp.
F
- 9. Remarks: N/A CERTIFICATE OF COMPLIANCE We certify (hit (hc statements made in this report are correct and this replacement. conforms to ihe rules of ASME Code, Section X1 repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed orLQ m" V-Date
!A~ri - 20 Ot CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid comnmission issued by thc National Board of Boiler and Pressure Vessel Inspectors and the Stale of Illinois
. and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report dutring the period /~L/.S.to !2
~
and state that to the best of my knowledge and belief, thc owner has performed examinations and taken corrective measu res described in this Owner's Report in accordance the requirements of the ASME Code. Section XlI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinlations and corrective measures described in this Owner's Report. Furthermore. nteither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
,-Jdxoo% Sgrwure U
0NaikmanIkktl3wd.
5t~dc, Pmirwinc.
and Endomrtivent, Date 4-200
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
06/20/2006 Sheet:
I of I Unit:
2 Program No. 05-I 14 W0 00683075-01 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identitication of System: Residual Heat Removal. Class 2
- 5. (a) Applicable Construction Code:
IJSAS 133 1.11 1967 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASMIE Component Mfllr.
No.
Bd.
Identification Built Replaced. or code No.
Replacement Stamped (Yes or Globe Valve Crane N/A N/A 12-1001-3613 N/
Replacement NO0
- 7. Description of Work: Replaced plug assembly in accordance with the W.O.
- 8. Tests ConduIcted:
Hydrostatic 1:
Pneumatic 1:
Nominal Operating Pressure El Other [D Pressure Test Temp. *F
- 9. Remarks: Performed Appendix J Testing.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to thc rules of ASME Code.Section XI repair or replacenment Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR5O Arp B3. 0 A Protram Certificate of Authorization No.
N/A Expiration Date N/A Signed Pr~o, r
Date j
1A
-21 20 lo~
VJ 0+ ne rQnrs sgc.i CERTIFICATE OF INSER VICE INSPECTION
- 1. the undersigned. holdinge a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
.and employe~d by tHSB3 C.of Connecticut have inspected the components describcd in this Owner's Report during the period (0/ /1o toC1
, atid state that to the best ofiny knowledge and belief, the owner has performied examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASMIE Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any marnner for any personal injury or property daniage or a loss of any kind arising from or connected with this inspection.
~ ~ ~)
.()6~t.~~w/eCommissions IL/Z-f, A/2.
-C/o jjmrd.stafe, I'mince.atid Cilorýrvws 20
FORM NIS-2 OWNERS REPORT OF REPIAIR OR REP'LACEMENT-,N-As Required by tile provisions or ASIME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 1I. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Qulad Cities Generating Station 22710 206111 Ave. North. Cordova, IL 61242 Date:
4-11-20306 Sheet:
I of I Unit:
2 program No. 05-11I5 WO 0(07651I09 Repair Organizatioii P.O. No.. Job No.. dc Type Code Symbol Stamip:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: High Pressure Coolant Injection. Class 2
- 5. (a) Applicable Construction Code: Section Vill 1967 Edition, N/A Addenda, N/A Code Case (h~ Aplicale Eition (If SectionI Xl Uliii ied for Repairs or Replacements:
100-5 Edition.
1 006 *VhkndnI.
N/A\\ Code Cawe
- 6. Identification of'Comnponents Repaired or Replaced, and Replacement Components:
Name of' Name of Mlfrs. Ser.
Nat'l Other Year
- Repaired, ASNIE Component MvIf'r.
No.
B~d.
Identification Built Replaced. or code No.
Replacement Stamped (Yes or
__________________ _____________________N o)____
o Relief Valve Consolidated/Dresser 1 L91267 1N/A 2-1699-9 N/A Replacement Yes
- 7. Description of Work: Replaced the relief valve in accordance with thle XV.O.
- 8. Tests Conducted:
I-I drostati c l
Pneumatic Nominal Operating-PressureE Other [D Pressure 44.4 psi Test Temp. Amibiant '17
- 9. Remarks: Performed Appendix J etie CERTIFICATE OF COMPLIANCE We cert i l that thle statements miade in thIiis report a1re correct and this re placement con tbrms to the rules ol'ASN IE Code. Sect ion XlI repair or reptacelilleit Type of Code Symbol Staninp N/A - F xelon Nuclear I (OCUR5() A pp B. 0 A program Certilleate of* Authorization No.
N/A Expiration Date N/A Signed R -05We Date Api
~
20 0 CERTIFICATrE OF INSERVICE INSPECTION
- 1. thle undersigned. hold ing at valid commnission issued 1by fihe National Board of Boiler aiid pressure Vessel Inspectors and thie State of' Illinois
.andemiployed by 115 BC(T. oh Con liec icut haive inspected 11 conipont~enits describdct inIi iis O% ncr's Rep~ort dun agi, thie period
/~//~to
!9//
zz--X, -and state that to the best of mny knowledge and belief". thie owner has performed examinations and taken corrective mecasuires described in this Owner's Report in accordance the requirements ot the ASME Code,Section XI.
By signing this certiticate, weither the inspector nor his employer makes any warranty. expressed or implied. concerning thle examinations and corrective measures described in this Owner's Report. Furthermore, neither thle Inspector nor his employer shiall be liahle in any manner for any personal injury or property damnage or a loss of' any kind arising fromt or coninected with this inspection.
Th~~{'(
~
commissions/
/c Date 0-:
Nmi......
I 1.,I. SI..
L 1""".,,
"1.
It 210(c6
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/10/2006 Sheet:
1 of I Unit:
2 Program No.05-117 WO 00701257-01 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System Main Steam, Class 1
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda,.N/A. Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
199 Edition, 199622 Addenda, N-4 16-2 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N )
Piping Exelon N/A N/A I2-3007C.1.5' N/A Replacement No
- 7. Description of Work: Replaced piping with chrome-moly piping in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic []
Pneumatic []
Nominal Operating Pressure0 OtherE5 Pressure
_ psi Test Temp.
F
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I1OCFR50 AP B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed or o
vya-Dt 1
W Ity 10 20 Cifo CERTIFICATE OF INSER VICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
- and employed by 1-SB CT. of Connecticut have inspected the components described in this Owner's Report during the period Z~ 2 E to.-- 1 4
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective nl'asu'res descnibed in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
~~7Z~f)
C; Commissions
~a
.inspectors Signature (J 0 206 National Board, State, Province, and Endorsements Date Date
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/1012006 Sheet:
I of 1 Unit:
2 Program No.05-118 WO 00701258-0 1 Repair Organization P.0- No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System Main Steam, Class 1
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1.995 Edition, 1996~ Addenda, N-416-2 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Piping Exelon N/A N/A I2-3007D-1.5" N/A Replacement No
- 7. Description of Work: Replaced piping with chrome-moly piping in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic Q Pneumatic 5]
Nominal Operating Pressure 19 Other 5 Pressure psi Test Temp.
F
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed _I Jv-Au-kP--,:,pS Dt tu 1
2004~
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT. of Connecticut
-have inspected the components described in this Owner's Report during the period 12VZL1oA*L to ýý and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
~~
~Commissions
/LZ/OS 61~pectors Signature V
C/
National Board, State, Province. arid Endorsefrntnr Date 20.0/_06_
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
05/6/2006 Sheet:
I of I Unit:
2 Program No. 05-I119 WO 00701259-01 Repair Organization P.O. No., Job No.. etc, Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System High Pressure Coolant Injection, Class 1
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition.
N/A Addenda.
N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N-416-2 Code Case
- 6. Identification of Comportents Repaired or Replaced, and Replcem~ent~ Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Piping Exelon N/A N/A 1
2-2330-1.5" N/A Replacement No
- 7. Description of Work: Replaced 12iping with chrome-moly Pip~ing iniaccordance with the WO.
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic El Nominal Operating Pressure El Other FE Pressure ___
psi Test Temp.____ IF
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report arc correct and this re lacement conforms to thc rusles of ASME Code. Section Xl repair or rejplacernlLnt Type of Code Symbol Stamp N/A - Exelon Nuclear I 0CFR5() App B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed (2Mr, DaeeA 200t CERTIFICATE OF INSER VICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois. and employed by HFSB CT. of, Conttecticut
.have inspected the components described in this Owner's Report during the period
-A /
e-/to./C and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report is) accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures descrihed in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be l iable in any manner for any personal injury or property damnage or a loss of any darsn from or connected with this inspection.
ýý -
1-.
=
Commissions
&~
dij~.nii MitiIhil Bor.Ire icemeh 1owy1 111 I.-...~2
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/10/2006 Sheet:
I of I Unit:
2 Program No.05-120 WO 00701256-01 Repair Organization P.O. No., Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System Main Steam, Class 1
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A
- Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 19962 Addenda, N-416-2 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Coinponents:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Piping Exelon N/A N/A I2-3007B-1.5" N/A Replacement No
- 7. Description of Work: Replaced 12iping with chrome-moly piping in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic Ml Nominal Operating Pressure Other E]
Pressure psi Test Temp.
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed ('*AATA$M tnpw
-Date Wi y t
20.04, CERTIFICATE OF INSER VICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT. of Connecticut
_have inspected the components described in this Owner's Report during the period 4
-1 to
.:'/1c'/O6, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described iný this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
__7,_________0__(_____
Commissions
/Z-
/'
k-- !nup-ectors Signature
(/(
Natuioa Board, State. Province. aind Endlorsernents Date
.XY/I 2006
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section X1
- 1. Owner:
Exe Ion Generation Company. LLC 4300 Winfield Road
'Varrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242
- 3. Work Perfoirmed by:
Qutad Cities Generating Station 2 2710 206th Ave. North, Cordova, IL 61242 Date:
4/15/2006 Sheet:
I of I Unit:
2 Programn No.06-077 & 05-121 W00)0732429 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of' System: Residual Heat Removal. Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Editions. N/A Addenda, N/A Code Case (hi Applicable Edition of Section XT Utili7.ed for Repairs or Replacements:
1995 Edition.
1996 Addenda. N-4 16-3 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Componcnts:
Name of Name of Mlfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component IMfr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Relief Valve Dresser TP30710fJ N/A 12-1001-125C N/A Replacement Yes
- 7. Description of Work: Replaced the flange bolting, pinpe, and flange in accordance with the \\V.O.
- 8. Tests Conducted:
Hydrostatic 51 Pneumatic 5:
Nominal Operating Pressure Other E]
Pressuire ____
psi Test Temp. -
'F
- 9. Remarks:
None.
CERTIFICATE OF COIMPLIANCE We certify that the statemnents made in this report are correct and this replacement Conforms to 111C' Rules of ASNIE Code.Section XI repair or replacemient Type of' Code Symbol Stamp N/A - Exelon Nuclear I OCFR50) App B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed ___________________________
Date ApI1 "Z
00(p CERTIFICATE OF INS ER VICE INSPECTION
- 1. the undersigned. holding a valid commission issued by thie National Board of Boiler and Pressure Vessel Inspectors and the State of 11Jinoi-andemnployed by 1158(1'. of Coninecticut
_havc inspected the components described in thiis Own-er's Repor-tduiring, the period
/111 /ýOs to 412/L
. and state that to the best of'my knowledge and belief, the owner has perf'ormed examinations and taken corrective measures described in thiis Owner's Report in accordance the requirements of the MNJvE Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concernin~g the examinations and corrective measures described in this Owner's Report. Furthermiore. necither the Inspector nor his employer shall he liable in any manner t'or any personal injury or property (lanlage or a loss of any kind arising from or connected with this inspection.
'7IIII~--"c' t~dttt&Commissions
/,
/(_
Date Z_
C/(-)
N.6,,Ial hwd. Slal,-. ri-mce.aml hidoi.wnwill, 20 C' 6.
10 C2Z_
FORM NIS.2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Wan-enville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
4/2/2006 Sheet:
I of I Unit:
2 Program No.05-127 & 05-128 WO 00738096 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Standby Liquid Control, Class 2
- 5. (a) Applicable Construction Code: IJSAS B31.1 1967 Edition, N/A Addenda, NACode Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
______________No)
Trigger Assembly Contax Buffalo Corp.
132 N/A 2-I1106A UTNK.
Replacement No Inlet Plug Contax Buffalo Corp.
N/A N/A 2-1 106A UNK.
Replacement No
- 7. Description of Work: Replaced the trigger assembly and inlet plug, in accordance with the W.O.
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic El Nominal Operating Pressure0 Other E Pressure ____
psi Test Temp.
1
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the niles of ASME Code. Section Xl repair or replacement Type of Codc Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B.' Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed co k-s I 9&"
'Z5~..-
ae A e 20(OC&
CERTIFICATE OF INSERVICE INSPECTION t, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of
- Illinoit, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period
/ý? /t9/o5 to _ h /oLb
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective mneasures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By Signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or properIdamage, o a loss of0 4 ndaiin=rm or connected with this inspection.
C rmmkqinnc
//_ /04ta*
I Date 4-L/3 V /c Natkm~gu 8oxtrd. State. Pnmvin~c.
and Egidt.r~,,nts 20676-
FORM NIS-2 OWNERS REPORT OF REPAIR OR REIPLACEMENT As Required by the Provisions of ASIME Code Section XI I. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Perrormed by:
Quad Cities Generating,- Station 22710 206th Ave. North. Cordova, IL 61242 Date:
4/15/2006 Sheet:
I of I Unit:
2 Program No.06-083 06-085 & 05-134 WO 00774917 Repair Orgainization P.O. No.. Joh No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: High Pressure Coolant Injection. Class 2
- 5. (a) Applicable ConstruIction Code:
LJSAS 1331.1 1967 Editions, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI (Irtili~ed for Repairs or Replacemeonts: -1905 Edlition.
1096 Addendal.
N/A ('ode CaIse
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Scr.
Nat'l Other Year Repaired.
ASME Component MkIfr.
No.
B~d.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Cheek Valve Exelon N/A N/A 2-2301-74 N/A Replacement No
- 7. Description of Work: -Replaced the flange holtiniz. phie. and tack wvelded fthe nut to disc in accordance with the WO.
- 8. Tests Conducted:
Hlydrostatic 0 Other 0 Pressure Pneumatic E]
Nominal Operating Pressure psi Test Temp.
-__ 'F
- 9. Remarks:
It is not considered a Category A valve and is not leakaize tested since tlie steamn exhaust line terminates below the minimumir wa~'ter le~vel in the saimpressioni nool providiniv a nuaif ifed water seatl nr AnntundiK J CERTIFICATE OF COMPLIANCE WVe certify thiat the statements made in this rcport are correct and this repilacement conforms to the rulies of ASINIF3 Code.Section XI repair or reptdeclneft Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. Q A Pro-gram Certificate of Authorization No.
N/A Expiration Date NIA Signed gnýFz ývv-Date A6pril JW 0(
(A--ner ofr Owner's Des~ogniee, Pith.I CERTIFICATE OF INSER VICE INSPECTION
- 1. the Uondersigend. holding a valid cornionission issued by thie National Board of Boiler and PreCssure Vessel inspectors and tho. State of Illinois
.and employed byLISF CT. of Connecticut ha~ve inspectedthie comiponentistdescribedI in this Owner's Report during the period to
__________toiV-2_06 and state that to [lhe best of my knowledge aod belief. tlie owvner has performed examinations and taken corrective m~easuires described in this Owner's Report in accordIance thre requirements of lhc ASlE Code.Section XI By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning tire exam~inations and~ corrective measures described in this Owvner's Report. Furthermore, neither thie Inspector nor his employer shall be liable in any mianner fnor anry personal injury or property (laniage or a loss of at k ind arisinrg fromn or connected with th is inspect ion.
__ /2
- _6~~.~Commissions
/
ce Sipature Date Date ~ /, 4P,/2/L 2, 2t)N~arr'.i Ihm.rd. Sgrtme.
Pro,, wr, md1. I nd,I..,,,,cin
FORM NIS.2 OWNERS REPORT OF REPAIR OR REPLACEMENT As ReqUired by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 430(0 Winfieldi Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. 11L 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
05/09/20t06 Sheet:
I ot I Unit:
2 Program No.05-139 NV0454494-01 Repair Or-an izat ion p.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Residual Heat Removal, Class 2
- 5. (a) Applicable Construction Code: USAS B3 1.1 1967 Edition. N/A -Addenda.
N/A Code Case (h) Applicable Editio ti fSection Xl Ut ilized tor-Repairs orI Replacemlents:
199)~5 I-dition.
I1996 Addenda.
N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name ot Name ot Mkfrs. Ser.
Nat'l Other Year
- Repaired, ASMIE Component Mfr.
No.
MI.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No))
Valve Crane Val ve Co.
N/A N/A I2-1001l-34B3 N/A Repaired No
- 7. Description of WVork: Replaced %yecle.in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic L:
Pneumatic E:
Nominal Operating Pressure 13 Other E]
Pressure psi Test Temp.
'17
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE We cert ify t hat the statements iiiatle ill thlis report tire correct and thlis relair ctiloritbins to thie rules of AS. lrE (loe.S ectiofi Xl repair or replace Fe-nt Type of Code Symbol Stamp N/A - E~xelon Nuclear I OCFR50) App B. 0 A program Certificate of Authorization No.
N/A Expiration Date N/A Signed C~f ff~
j n5-,j!!jtPool Date WAY I G.
20 0(4 CERTIFICATE OF INSERVICE INSPECTION I. thie undersiuned. hokline a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors an h tt r Illinois
.and emiployed hy I ISB CT.oif Connecticut
.have itnspected the components described iti this Owner's Report dutring t he period "244&
11o -/K'
~6.-and state that to the best ol my knowledge and belief. theimvner has perfonmed examinations and taken corrective measures described inl this Owner's Report in accordance the requirements of thie ASME Code.Section XI.
fly signing thlis certilicate. neither the inspector nor his employer mnakes any warranty. expressed or implied, concerning the examinations and corrective mecasures descrihed in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any tuanner for any personal injutry or property damiage or a loss ol.any kind arising frotm or connected with this inspection.
".?~~-2'~r'c-Comnmissions
/.C'e~ 7 C9
~
t Date fel
/0) 2toe2A
FORMI NIS..2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
06/06/2006 Sheet:
I of I Unit:
2 Program No.06-003 WO 00812173-01 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Section 111 1965, 1968 Edition.
N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Corponents Repaired or Replaced, and Re placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Safety Valve Consolidated Valve IBL 1132 1N/A 2-0203-413 N/A Replacement Yes
- 7. Description of Work: Replaced Safety Valve in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic E:
Pneumatic [E Nominal Operating Pressure ED Other E]
Pressure psi Test Temp.
-___ 'F
- 9. Remarks:
IR# 00497311 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASNIE Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed 45ro0erssinee.rt0 WEc Date 20d.~
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board or Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by FISB CT. of Connecticut
_have inspected the components described in this Owner's Report du ring the period
/2h'?/e'f. to 6ii' and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective nmeasures described in this Owner's Report in accordance the requirements of the ASMIE Code,Section XI.
By signing (his certificate. neither the inspector nor his employer makes any warranty. expresscd or implied, concerning the examinations and correccthve measures described in this Owner's Report. Furthermore, neither thie Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
7~.~f: 6 2'/~x-?-Commissions
/-ee' Date K
z.206'(
FORMN NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road XWarrenville. 11. 60555 2.Plant:
Quad Cities Generating~ Station 2271I0 206th Ave. North. Cordova. IL 612421
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
Sheet:
Unit:
04/28/2006 1 of 1 2
Programn No.06-004 WO 008 12172-01 Repair Organi~alion P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of'System: Main Steamo. Class I
- 5. (a) Applicable Construction Code: USAS 1331.1 1967/1ASME. Sect. 111 1965. 1968 Edition.
N/A Addenda.
N/A\\ Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Cor ponents Repa~ired or Replaced, and Re placement Comnponents:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Mfr.
No.
B~d.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Safety Valve Consolidated Valve IBK 7164 1N/A 2-0203-4A N/A Replacement Yes-_
- 7. Description of Work: Replaced Safety Valve in accordance with the W'O.
- 8. Tests Conducted:
Hydrostatic 5l Pneumatic E]
Nominal Operating Pressure0 Other 5 Pressure ___ psi Test Temp.
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements mnade *in this report are correct and this replacement conforms to the rules ot ASME Code. Section Xl repair or replacemenit Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50) App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signe~d rA
-\\
fi!,P-j
ývn aeM i02,(
CERTIFICATE OF INSER VICE INSPECTION
- 1. the undersigned. holding a %alid commission issued hy thie National Board of* Boiler and Pressure Vessel Inspectors an h tt f
Ilni.adepoc yIS
fCnetct have inspected thle components described in this Owner's Report during the period,/qC3to J'/1' /^6
. and state that to thie hest of' my knowledge and bel iel. [he owner has performed examinlat ions and taken correct ive mneasures dcscribed i n this 0%% er's Report in accordanice the rcqu irecnte s ol1 the ASMNIE Code. Sect ion Xl1.
By signing this certiticate. neither the inspector nor his employer makes any %arranty. expressed or implied, concerning thle examinations and corrective mecastures described in this Owner's Report. Fuirthermnore, neither the Inspector nor his enmployer shiall be liable in any manner f'or any personal injury or property darrage or a loss of any kind arising fromn or connected with this inspection.
>YJc
-Coninlissions
/Z_
/0 0 5' p
M ilinna I I'loan L Suie.
ji it I I j it it%
Date 20 Rite 20" 6
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
06/06/2006 Sheet:
I of I Unit:
2 Program No).06-005 WVO 00729408-01 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Section 111 1965. 1968 Edition.
N/A -Addenda.
N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda.
N/A Code Case
- 6. Identification of Coinportents Repaired or Replaced, and Rpae~ment Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Safety Valve Consolidated Valve IBK 6251 1N/A 2-0203-4F -r N/A 1
Replacement Yes
- 7. Description of Work: Replaced Safety Valve in accordance with the WO.
- 8. Tests Cond ticted:
Hydrostatic fl Pneumatic El Nominal Operating Pressure ED Other E]
Pressure ___ psi Test Temp.
F
- 9. Remarks:
IR# 00497311 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App' B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed _________________________
Date
.U%-200(0 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period
/ Z21C6 to 4694_;__/_0____. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code,Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
/ý K414 Commissions A.-
/- ~
Date 20 _ýý Date 20 e'~~
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 1l. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
04/24/2006 Sheet:
I of I Unit:
2 Program No.06-006 WO 00729090-01 Repair Organizationi P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: USAS 1331.1 1967/ASME Sect. 111 1965. 1968 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Compontents Repaired or Replaced, and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
A SM E Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Safety Valve Consolidated Valve IBL 1120 N/A 2-2034E N/A Replacement Yes
- 7. Description of Work: Replaced Safety Valve in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic []
Nominal Operating Pressure OtherE]
Pressure ___
psi Test Temp. -
'F
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code, Section Xl repair or replacemient Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. -0 A Progranm Certificate of Authorization No.
N/A Expiration Date N/A Signed ('# M+C g 09MI-1' r-l t S
_Date L44o Pl 20 0G' V
Oky~eor orwner's Designee. Tict CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State otf Illinois
- and employed by. H-SBCT. of Connecticut have inspected the components described in this Owner's Report during the period
/ý2_ý tMo OS-11 'Z!
,Aand state that to the best of my knowledge and belief, the owner has perfornncd examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
.7ýýCOtrC6"mmissions
/4~ /oO.5-1...j;nl% cgtunrsc
.mtr(~C
,.U Nalimol Bonad. Siatt.
i',',ine and edrcih~tems Date ln~q
/
2006~
FORMI NIS-2 OWVNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Excion Generation Company, LLC 4300 Wintield Road Warrenville, 11. 60555
.. Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
06/06/2006 Sheet:
I of I Unit:
2 Program No.06-007 W'O 00789813-01 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam. Class 1
- 5. (a) Applicable Construction Code:
ASMJE Section 111 1990. 1995 Edition.
1.980, 996 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name ot Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or o)
Electromatic Relief Dresser Industries BX-00)290 N/A 2-0203-313NK Replacement No Valve I__________
1______
- 8. Tests Conducted:
Hydrostatic E1 Pneumatic E]
Nominal Operating Pressure ID Other 5-Pressure psi Test Temp.
-___ 'F
- 9. Remarks: IR# 00497311 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Datte N/A Signed LW :D atP-e ae 20 c~
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board or Boiler and Pressure Vessel Inspectors andl the State of Illinois
.and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Reportduring ihe period
///12-/1Z-to..6l~_
and state that to the best of my knowledge and belie f, the owner has pcrformed examinations and taken corrective ineasu'res described in this Owner's Report in accordance the requirements of the ASIME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measuires described in this Owner's Report. Furthermore, neither the Inspector nor his enmployer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
(1
/§~-41r14 Commissions iaVtrvow Si~imi ur C/(5/
Nalk'nal Board. Nute. N"illce. and Evd. qe V 1011, Date 5/2-20
- k
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, IL. 60555 2.Plant:
Quad Cities Gencrating Station 22710 206th Ave. North. Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
03-06-2006 Sheet:
I of I Unit:
2 Program No.06-013 W'O 00883853-01 Repair Or-anization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Section 111 1980. 1995 Edition.
12+/-980 996 Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
B3d.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Electromatic Relief Dresser Industries BY-94632 N/A 2-0203-3D)
UNK.
Replacement No Valve I__________
I______
1___
1________
- 8. Tests Conducted:
Hydrostatic 5Pneumatic 51 Nominal Operating Pressure0 Other 5]
Pressure ____ psi Test Temp. -
'F
- 9. Remarks: None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASNIE Code. Section Xl repair or replacemrent Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 A121 B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
'p'-Date 7200(o CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by HSB CT. of Connecticut
.have inspected the components described in this Owner's Report during thce priodl /f.~L~
to -3/7/C6/
.and state that to the best of my knowledge and belief, the owner has performed exanminations and taken corrcctive measures described in this Owner's Report in accordance the requirements of the ASMIE Code.Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures descrihed in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
,-~YJ~
(.
~Z~I1t1'Commissions
/L- /
ciNjiio"il Boird. Sue 'ilwe iik.o~wt Date 7
-/220
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
Sheet:
Unit:
05/6/2006 I of 1 2
Program No.06-021 WO 00886262-01 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: USAS 133I.1 I I967/Section 1 1965 Edition.
N/A Addenda.
N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Coinp(nents Repaired or Replaced, and Replaement Components:
Name of Name of MVfrs. Ser.
Nat'l Other Year Repaired.
ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N )
Snubber Lisega Hydraulic 161310/36 1N/A TS-2-28 N/A Replacement No
- 7. Description of Work: Replaced load pin in accordance with the WNO.
- 8. Tests Conducted:
Hydrostatic 51 Pneumatic E5 Nominal Operating Pressure 5l Other 5 Pressure psi Test Temp.
-___ *1
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statemnent made in this report are eorrcct and this replacement contorms to the niles of AS\\IE (ode.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Ap B3. Q A Progcram Certificate of Authorization No.
N/A Expiration Date N/A Signed ______________________e-,-
Date
&L14 20 CC CERTIFICATE OF INSERVICE INSPECTION
- 1. thie undersigned, holdinga a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois. and enmploycd by FHSB CT'. or Connecticut
_have inspected the components described in this Owner's Report (luring the period 12,,&410i-to A'.1,o04V6.and state that to the best of my knowledge and belief. the owner has performed examinations and takeni corrective measures descrihed in this Owner's Report in accordance the requirements of the ASME Code,Section X L By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examninat ions and corrective measures described in this Owner's Report. Furthermore. neither (he Inspector nor his employer shall be liable in any mnanner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
a rK -
(,7eZI.1 Commissions
/L/'
4 la 97dor Signnir (Jo N~ano Bagij Ohrd. St~ate.
Provmince'.
anid L ~i...lnremem Date 2t) (~6 Date 20(o
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exclon Generation Company, LLC 4300 Winfield Road
%Varrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242
- 3. Work Perfor~med by:
Quad Cities Generating Station 2 2710 206th Ave. North, Cordova. IL 61242 Date:
06/19/2006 Sheet:
I of I Unit:
2 Program No.06-022 WO 00656068-01 Repair Organi/iatj,1 P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: USAS B31.1 1967/Section 1 1965 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Ident ificatio n of Compontents Repaired or Replaced, and Replaement* Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME-Component M fr.
No.
BdI.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Snubber Lisega HyIdraulic 1613(X)/62 IN/A 2-300 1-A55 N/A Replacement No
- 7. Description of Work: Replaced load pins in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic flPneumatic El Nominal Operating Pressure Other Pressure psi Test Temp.
F
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statemnents mnade in this report are correct and this replacement conforms to the rules ol ASMIE Code. Section Xl repair or reptacuninclt Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 A pp B. Q A Progra~m Certificate ot Authorization No.
N/A Expiration Date NIA Sgned C&
~
re,-
aeJvie.
-go_
CERTIFICATE OF INSER VICE INSPECTION
- 1. the uindersignedo, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Illimnois andenmployed by IsB cmr. t Connecticut have inspected the components described in this O0ý.ner's Report during the period IC6 to 6h'/ 06
.and state that to the best of my knowledge and belief, the owner has performned examinations and taken corrective measures described in this Ownier~s Report in accordance the requirements of the ASMNE Code. Section XlI.
By signing this certificate, neither the inspector nor his employer mnakes any warranty. expressed or implied. concerning thie examinatiotns and( corrective mecasures dlescribed in this Owner's Report. Ftrthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arisitng fromn or connected with this inspection.
Commissions
/' /Oe76~
Date k1-/
1 20 2(
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEM-NENT As Required by the provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. 11L 61242 Date:
5/10/2006 Sheet:
I of I Unit:
2 Program No.06-025 WO 008853 18-01 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam. Class 1
- 5. (a) Applicaide Cunsti uction Codc: ( 'SAS 1331.1 I 967,',SIE Sect. 111 1965, 196S Edition.
VA Addenda. N,,\\ Codc Ca.',e (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Corn ponents Re paired or Replaced, and Re placement Comnponents:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASMIE Component Mfr.
No.
Bd.
Identification Bu1.ilt Replaced, or Code No.
Replacement Stamped (Yes or No)
Safety Valve Co'nsolidated Valve IBK 7163 1N/A 2-0203-4C N/A Replacement Yes
- 7. Description of Work: Replaced the inlet bolting in accordance with the WO.
- 8. Tests Conducted:
H-ydlrostatic E]
Pneumatic L:
Nominal Operating Pressure El Other E]
Pressure ___
psi Test Temp.
-__ *F
- 9. Remarks:
N/A.
CERTIFICATE OF COMIPLIANCE We certify that the statements made in this report are correct and this re lacement conforms to thie rutles of ASME Code. Section Xt repair. or replaccement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Programn Certificate of Authorization No.
N/A Expiration Date N/A Signed CjAL6 P
1 v
rr Date AAAy
(
200(,-
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holditie a valid commission issued by (lhe National Board of Boiler and pressutre Vessel inspectors and the State or Illinois
, and employed by tHSB CT. or Connecticut have inspected the componlents described inti his Owner's Report duringc-thie period
/2//~
to ~3//Y and state that to thie best of my knowledge and belier. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements ofithe ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer muakes any warranty, expressed or implied, concerning the examinations and corrective mecasures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shiall be liable in any manner for any personal injury or prq erty ýdamage or a loss of any kind arising from or conniected with this inspection.
tic~~Sipamr-t L/
u N~mi 11,,g j i'rd Stae Vik.
IS.
iflf..t emc Date Z_________
- 21) 0
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEM, IENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generauingz Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generatin-g Station 22710 206th Ave. North. Cordova. IL 61242 Date:
5/10/2006 Sheet:
I of I Unit:
2 Program No.06-026 WVO 008853 19-0)1 Repair Or-aniization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
- 4. Identification of System: Main Steam. Class 1
- 5. (a) Ap~plicable Construction Code:
U SAS 1331I.1 I 967;/\\S\\IE Sect. 111 I1065, I 96S Edition, N,',%.\\ddLrrda. N,'.\\ Cude Ca.se (b) Applicable Edition of Section XI Utilized for Repairs or Replace mentIs:
1995 Edition, 1 996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or eplaced. and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASN/E Component Mfr.
No.
Bd.
Identification Btuilt Replaced, or Code No.
Replacement Stamped (Yes or No)
Safety Valve Consolidated Valve IBK 6266 1N/A 2-0203-4D N/A Replacement Yes
- 7. Description of Work: Replaced the inlet bolting in accordance with thie WO.
- 8. Tests Conducted:
Hydrostatic Pneumatic ENominal Operating, PressureE Other E]
Pressure ___ psi Test Temp.
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We ccrt i fy that thle statements made in this report are correct a nd th is replacement conforms Ito the rules of ASNME Code,.Section XI rcpairor replaeniiciil Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50) App B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed W-L aieIIy' Dt 200&
CERTIFICATE OF INSER VICE INSPECTION I, the uindersigired. holdine a Valid comimission issued by the National Board of Boiler and pressure Vessel Inspectors and the State of Illinois
.and employed by HSI3 CT. of Connecticut have inspected thie components describcd in this Owner's Report duiring thie period hZJ//4//,57 to 71121C6.... and state that to the best of my knowledge and belief, the owner has performed exanrinations and taken corrective nmeasures described in this Owner's Report in accordance thie rcquirenrents of the ASNIE Code, Section X1.
By signing this certificate, neither the inspector nor-Iis employer makes any warranty, expressed or implied, concerning the examinations arnd corrcctive measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall he liable in any miarner lbr any personal injury or property damage or a loss of any kind arising frnm or connected with this inspection.
2 (2
~ ~~~
Commnissionrs
/
/C6 Date
=a 3 2001C6
FORM'8 NIS.2 OWNNERS REPORT OF REPAIR OR REPLACEIME'NT As Required by the Provisions of ASMlvE Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Win field Road Warrenville, 1I. 60555 Date:
Sheet:
Unit:
5/10/2006 I ot 1 2
2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 227 10 206th Ave. North. Cordova, IL 61242 program No.06-027 WO 00885320-01 Repair Or.-anization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification (if System: M'ain Steam. Class I
- 5. (a) Applicablc Construction Code: r SAS 1l331.1 I 9671ASNIE Scct. 1(( 1965. 1968 Edition.
NIA A\\ddenda, N/A Codc Case Mb Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda.
N/A Code Case
- 6. Identification of Cor uponents Re paired or Replaced, and Re placement Comnponents:
Name of
'f Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASMvE Component Mlfr.
No.
Bd.
Identification Built Replaced, or Code INo.
Replacement Stamped I
(Yes or No)
Safety Valve Consolidated Valve IBK 6529 1N/A 2-0203-4G N/A Replac-em-ent Yes
- 7. Description of Work: Replaced the inilet bolting in accordlance with the W'O.
- 8. Tests Conducted:
Hydrostatic E]
PneumaticEL Nominal Operating Pressure Other E]
Pressure ___ psi Test Temp.
- 9. Remarks:
N/A.
CERTIFICATE OF COMIPLIANCE We certify that [lhe statements made in this report are correct and this replacement coniformis to thierulesotf AS\\IE Codle.Section iXl r-cpair 01 I eilaccentei Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Programn Certificate of Au~thorization No.
N/A Expiration Date N/A Signed A h\\
qI
-Dt200C.
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issucd by tile National Board of Boiler and Pressure Vessel Inspectors and 1he State of Illinois and employed by 14SB CTr. of Connecticut
-have inspected the components described in this Owner's Report during the period 4V /C to
.. and state that ito the best of my knowledgecand belief, thie owner has perfornmed examinations and takeni Corrective measures descrihed i thINS Owner's Report in accordance thie requirements of the ASME Code. Section Xl.
By signing, this certificate, neither the inspector nor his employer inakes any warranty. expressed or impJlied. concerning thie examinations and corrective mecasures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner For any personal injury or property damiage or a loss of any kind arising from or connected with this inspection.
Comissions
/-/ce' Date I
/ '?,
2 0
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEINIENT As Required by the Provisions of ASMIE Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road WVarrenviIle, 11. 60555 2.Plant:
Quad Cities Generating Station 227101 206th Ave. North, Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 227 10 206th Ave. North. Cordova. IL 61242 Date:
5/10/2(006 Sheet:
I of I Unit:
2 Program No.06-028 WO 0088532 1-01 Repair Or-anizariorr P.O. No.. Joh No.. etc.
Type Code Symbol Stamnp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steami. Class 1
- 5. (a) Applicable Comnstrtctior Code:
I JSAS 1331.1 1 9.07',\\SME Sect. 111 1965. 196S Edition.
N,',\\
- Addenlda, NIA Cude Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, I1996 Addenda, N/A Code Case
- 6. Identitication of Coin ponenits Repaired or Replaced, and Re placement Components:
Name of Name of Mlfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
B3d.
Identification Built Replaced, or Code No.
Replacement Stampcd (Yes or No)
Safety Valve Consolidated Valve IBK 6278 1N/A 2-0203-41 N/A Replacement I
Yes
- 7. Description of Work: Replaced tile inlet holling, in accordance with thle WO.
- 8. Tests Conducted:
Hydrostatic Fl Pneumatic [:
Nominal Operating Pressure Other Ej Pressure ___ psi Test Temnp.
'1
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify (fhat the statements made in this report are correct and this r placem~ent conforms to the rules of ASME Code.Section XI repair or id laccinicnt Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certiticate of Authorization No.
N/A Expiration Date N/A Signed 9AhP-v
-Date A
II/
20 vc-CERTIFICATFE OF INSER VICE INSP~ECTION I. thle irodersi-ied, holding a valid commission issued by the National Board of Boiler and pressure Vessel Inspectors amnd the Starte of Illinois
.and employed by fISf CT. of Confeledicit~ have inspected the components described in this Owner's Report durrince tlie period I/I, tA L Q4o to and state that to tlie best of my knowledgearid belief. the owner has p~erformied examniiations ard taken Corrective rneastrrcs described in this Ow ner's Report in accordance thie requriremnents of the ASME Code,Section XI.
By signing this certilicate. neither thle inspector nor his employer makes any warranty, expressed or implied, concerning thie examinations and eorrective measures described in this Owner's Report. Furthermore. neither [ihe Inspector nor his employer shiall be liable in any mariner for any personal injury or property damiage or a loss of any kind arising from or connected with this inspection.
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road WVarrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Per-formed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
06/06/2006 Sheet:
I of I Unit:
2 Program No.06-034 WO 00789812-c/
Repair Organization P.O. No., Job No. etcX, ni ýVtnm 8
NoAne
,I Tune ('ndp ~vmh Authorization No.:
Expiration Date:
None N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Section 111 1980. 1995 Edition.
1980,2.1996j Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Electromatic Relief Dresser Industries BK-7062 N/A 2-0203-3E UNK.
Replacement No Vailv I
I I___
1__
1__
- 7. Description of Work: Replaced the ERV in accordance with the WVO.
- 8. Tests Conducted:
Hydrostatic E5 Pneumatic 5 Nominal Operating Pressure Other E]
Pressure ____
psi Test Temp.____ 'F
- 9. Remarks: IR# 00497311 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report arc correct and this replacement conforms to the rules of ASNIE Code. Scction XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Proe.ramn Certificate of Authorization No.
N/A Expiration Date N/A Signed L/pýk I
f, Date J
e 20A -
CERTIFICATE OF INSERVICE INSPECTION 1, the uindersioned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois
. and employed hy HSB CT. of Connecticut
.have inspcctcd the components described in this Owner's Report (luring the period 4~lall
-Zo to
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code. Section X1.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall he l iable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
omm-issions
/
nr~t
~20 er' Z"
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by thle Provisions of ASME Code Section XI
- 1. Ow-ncr:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generatin g Station 227 10 206th Ave. North. Cordova, IL 61242
- 3. Work Perf'ornmed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/24/21006 Sheet:
I of I Unit:
2 Program No.06-039 WO W0902278-01 Rcpair Organization P.O. No.. Jot) No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
- 4. Identification (if System: Main Steam. Class 1
- 5. (a) Applicable Construction Code: ASMIE Section 111 1980. 1995 Edition.
1980 1996 Addenda. NIA\\
Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1 995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Compontents Re paired or Replaced. and Re placement Coinponents:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component M fr.
No.
B~d.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or
-Spare____
V-26__
N/A_
No)
Safety Valve Consolidated Valve BK 7062 N/1-paeV2 N/A Relae0n Yes
- 7. Description of W~ork: Replaced drain line weld at the main valve flange in accordance with tile "WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic 1:
Nonminal Operating Pressure E Other 51 Pressure ___
psi Test Temp.
'1
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE Wec certify' that the statements made in this report arc correct and this replacement conformis to the rullcs of AS.ME Code.Sect ion XlI repair or replacem~ent Type of Code Symbol Stamp N/A - Fixelon Nuclear I OCFR50) App B. 0 A Program Certificate of Authorization No.
NIA Expiration Date N/A Signed 04A\\1 r-y:5R4 Date ___________
20 06 CERTIFICATE OF INSER VICE INSPECTION
- 1. the uindersiened. holdinge a valid commnission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of-Illitnois
.and emiployed by 1ISB C7'. of Conniecticut
'have inspected the comiponents described in this Owner's Rcport during the period / /~c*
to
.and state that to the best of mny knowledge and belief, thie owner has performned examtinations and taken corrective mecasuires described ill this Owner's Report in accordance the requiremnents of the ASME Code. Section Xl.
By signing this certificate. neither thie inspector nor-his eniployer mnakes any warranty. expressed or imiplied, concerning the examiinat ions and corrective mecasures dlescribed inl this Owner's Report. Furthermore, neither [lie Inspector nor his emnployer shall he liable in any marnner for any personal injury or property damiage or a loss of any kind arising fromt or connected with this inspection.
I(sý41 i~h.111 I 'r' P
CO 11d I
FORMN NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by thie Provisions of ASNIE-Code Section X1 I. Owner:
Exelon Generation Company, L.LC 43(0) Winfieldl Road W'arrenville. 11. 60555 2ý.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 612-42
- 3. Work Performed by:
Quad Cities Generating Station 227 10 206th Ave. North. Cordova. 11. 61242 Date:
05/24/2006 Sheet:
I of I Unit:
2 Proiorarm No.06-040 WVO 00902278-02 Repaiir Orgisantiaon 11.0. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Idlentification of System: Mfain Steam. Class 1
- 5. (a) Applicable Construction Code:
ASMJE Section IfI1 1980. 1995 Edition, 1980,l1996 Addenda. N/A Code Case Nb Applicable Edition ot Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Comportents Repaired or Replaced. and Re placement Components:
Name of Name of Mlfrs. Ser.
Nat'l Other Year
- Repaired, ASIME Component Mfr.
No.
13d.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Safety Valve Consolidated Valve 1BX 00290 1N/A 0 -Spare V-26
-[
N/A Replacement Yes
- 7. Description of Work: Replaced drain line weld at the main valve tlange in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic 5:
Nominal Operating Pressure5 Other 5 Pressure ___
psi Test Temp.____ '17
- 9. Remarks:
N/A.
CERTIFICATE OF COMNPLIANCE We certifly that the statements made in this report are correct and this replacement corlonlims to thle rules of ASMIE Code. Scct ion X I rpiorrepL~icecniciiL Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50) Apr) B. Q A Prog'ram Certificate of Autlhorization No.
NIA Expiration Date NIA Signed C#Aýý i5ý! r' 2
-Tex :5L'p^-
Date ______1__4_---_______
CERTIFICATE OF INSERVICE INSP3ECTION
- 1. thie undersigned. holding a valid commission issiiedl by the National Board ol'Boiler and Pressure Vessel Inspectors aind the State of*
.and employed by I ISB CT. of Coninecticutithazve inspected the comiponients(lescribed in this Ownejr's Repor-t duing-ii the period
/5*to i,2/
adsae th )
t the best of my knowledgecand belief, the owner has performed examinationsanld taken correct ive measures described in thlis Owner's Report in accordance the reqlu cireneits of the AS ME Code. Sect ion Xl1.
By signing, this certifticate. neiltier thle inspector nor his employer makes any wvarrunty. expressed or im ptlied. concerning the examinations and correct i e mneasuires described ill this Owilers Report. Furthermore, neither the Inspector nor his employer shall be liable in any mnanner Ibor any personal injuiry or property damage or a loss of any kind arising fromn or connected with this inspection.
S-
-fK'& ~
ntiiuivoii~
/Z.
Si fl:t it' S
loi1(7 Nafi-w.d k4,f Date
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASNIE Code Section XI I. Owner:
Exelon Generation Company, LLC 4300) Winfield Road Warrenville, 11. 60555 2.Pl1ant:
Quad Cities Generating Station 227 10 206th Ave. North. Cordova. IL 612142
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
05/24/2006 Sheet:
I of I Unit:
2 program No.06-041 WO 0W902278-03 Repair Orp:ni;.irion P.O. No., Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None Non le N/A-,
- 4. Identification of System: Main Steam. Class I
- 5. (a) Applicable Construction Code: ASME Section III 1980. 1995 Edition.
1980, 196 Addenda. N/A Code Case (b) Applicable Edition of Sectioni XI Utilized for Repairs or Replacements:
19~95 Edition.
1996 Addenda. NIA Code Case
- 6. Ident ificat ion of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mlfrs. Ser.
Nat'l Other Year Repaired.
ASIME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Safety Valve Consolidated Valve IBK 7072 1N/A 0 -Spare V-26 N/A Replacement Yes
- 7. Description of Work: Replaced dIrain line weld at the main valv'e flange in accordance with the WO.
- 8. Tests ConduIcted:
Hydrostatic 5Pneumatic 5Nominal Operating Pressure5 Other 5I Pressure ___
psi Trest Temp.
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We ecrtitl'ythat the staitemientsimade in this repoitti are orrtcet and this replacement conforms to [lie ril's ofASME Code. Section Xl repair orleptaccitici ii Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 Ann B. 0 A Proturam Certificate of Authorization No.
N/A Expiration Date N/A\\
Signed 1ý,ýý
ýv Date 0A'L
%1) 20 C)(,
4 0
tn r rOwner's Vpc,'Fe.it4' CERTIFICATE OF INSERVICE INSPECTION I. thle undersignied. holding a valid commission i5ssued by the National Board of Boiler and pressure Vessel Inspectors and the State of Illinois and employed hy I 15 CT. of Connecticut
-have inspected the comptonentsd(eserihed in this Own ter's Report during, the period J:/Yý06 to
.and st ate (hat to t he best of my knowledge and hel ief. thle owner has performecd ex aminat ions and takena correct ive measures described in this Owner's Report in accordanice the requirements ofr thle ASMN1E Code. Sect ion X L By signing,Ii is certiticatle. nei ther thle inspector ot-o his employer makes any warranty, expressed or i mnpl iedl. concernin tI lie exan limiiat ions at d correcti ie measures described in this OW ter's Report. Fu rthermore. neither [lie Inispector nor his eiiiployer shlilI he liable in any man ner t'or ;my personal iniju ry or property laninaie or a loss o kind arising from or connected with this inspection.
r(
7,4 Commissions 141-4:70 I~
372~
N-1111111-11 M IJI'll. S1.110.
JIM I 210 ("A~
FORMI NIS-2 OWVNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Wintield Road WVarrenvi1Ie. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
5/23/2006 Sheet:
I of I Unit:
2 Program No.06-043 W'O 00885018-13 Repair Organitation P.O. No., Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identitication of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASME Section 1 1965 Edition.
Summer 1966 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda.
N/A Code Case
- 7. Description of Work: Installed bolting in acoustic side branch blind flanges in accordance with the WO.
- 8. Tests ConduIcted:
Pneumatic Q:
Nominal Operating Pressure Other Fl Pressure ___ psi Test Temp.
'1
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are corrct and this replacement cunlborms to the i-tiles of ASME Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App 1B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed AAJ 1:4 6J-/
D ate 2______0(0___
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and thc State of Illinois
, and employed by HSB (1'. of Connecticuti-havc inspected the components dlescribed in this Owner's Report during the ~
Y175 pro to6
/0
.ansttthto otebsoftynolde and belief. the owner has perforined examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASMIE Code. Sectioni Xl.
By signing this certificate. neither the inspector nor his employer makes anty warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any mianner for any persomnal injury or property damage or a loss of any kind arising from or connected wkith this inspection.
h~csignlature i 7~ 7*)
Natimul 11oaid. State. hinince.and hidorý-ivwm, Date Date 2006 K
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
0 xelon Generation Company, LLC
.4300 Winfield Road VWarrcrnville, 11. 60555 2.Plant:
Quad Cities Generating Station 2 2710 206th Ave. North. Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 2 2710 206th Ave. North. Cordova, IL 61242 Date:
06/0)2/200)6 Sheet:
I of 1 Unit:
2 Program No.06-044 WO 8850!18-04 Repair Organization 11.O. No., Jot) No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam. Class 1
- 5. (a) Applicable Construction Code: ASME Section 1 1965 Edition, Summer 1966 Addenda, N/A Code Case (b) Applicable Edition of Section XI UtMilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N-416-3 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Safety Val ve Exelon N/A N/A 2-0203-3C/D N/A Replaced No Standie I_________
I_________
2-0203-4C/D/GIH I____
I________
- 7. Description of Work: Installed acoustic side branch assemblies on south ERV and SRV standpipes in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic 5l Nominal Operating Pressure0 Other []
Pressure psi Test Temp.
- 9. Remarks:
System leakage test.
CERTIFICATE OF COMPLIANCE We certify that the statemnents made in this report are correct and this rep~lacement conforms ito the rules otf ASME Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOQCFR5O App B. 0 A Program Certiticate of Au~thorization No.
N/A Expiration Date N/A Signed C AAbU, F-^
'djvp/'r
-Date
\\Jv n e-.
200(o~
CERTIFICATE OF INSER VICE INSPECTION
- 1. the undersig-ned, holding a valid commission issued by thle National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HISB CT. of Connecticut have inspected the conmponents described in this Owner's Report duringl-the period to KA -6 and state that to the best of my knowledge and belief, the ow~ner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASINIE Code. Section X1.
By signing this certificate, neither the inspector nor his employcr makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any mnanner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions
- ._ýKrjvaor, Signmure
,--7ý.
w 0
2 Nal i.nul fl'ird. Solto. hiniiiw.
ir Elnd-.ýn'1 0,0(,
Date l~
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owvner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
06/02/2006 Sheet:
I of I Unit:
2 Program No.06-045 WO 88501 I8-01 Repair Organizationl P.O. No., Jot) No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Section 1 1965 Edition, Summer 1966 Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N-416-3 Code Case
- 6. Identitication of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Mfr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or N)
Safety Valve Exelon N/A N/A 2-0203-313/E N/A Replaced No Standpe I__I__I 2-0203-4A1/EI I____
- 7. Description of Work: Installed acoustic side branch assemblies on south ERV and SRV standpipes in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic []
Nominal Operating Pressure 19 Other nl Pressure psi Test Temp. -
'F
- 9. Remarks:
System leakage test.
CERTIFICATE OF COMPLIANCE We certify that the statements mado in this report are correct and Ihis replacement conforms to thle rule,. of ASMIE Code. Section Xl repair or replacemniit Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Lf t
0
-t!j 6pyr
-Date Juvi.
6Z
-20.o&
CERTIFICATE OF INSER VICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by IISB C7. of Connecticut have inspected the components described in this Owner's Report during the period
/.Z//-
o7 to 46/A /4'
. and state that to the best of my knowledge and belief. the owner has performed examinations and taken corrective mea~sures described in this Owner's Report in accordance the requlirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property dama~ge or a loss faikn arisine from or connected with this inspection.
nlx-, it -r, Sipix tire Date AZ ntýý V 61
.N.6mal Board. Suie. [I'm ince. jod Eiklorement, 20 i2 ý,
FORMN NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMIENT As Required by the Provisions of ASME Code Section XI 1.- Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
04/5/2006 Sheet:
I of 3 Unit: 0 PO# 707REL. 1297REC 151547 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Spare Control Rod Drive, Class 1
- 5. (a) Applicable ConStruCtionl Code: Component: ASNIE Section 111 1965 Edition, WV-1965
- Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda.
N/A Code Case
- 6. Identification of Compontents Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or SeeAtt._A No)__
- 7. Description of Work: Refuirbished the Control Rod Drive as reqiuired by the P0
- 8. Tests Conducted:
Hydrostatic El Pneumatic E]
Nominal Operating Pressure El Other I Pressure
_psi Test Temp.
-___ 'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASMIE Code,Section XI repair or replacement Type of Code Symbol Stamip N/A - Exelon Nuclear I0OCFR50 A12V B. Q A Programn Certificate of Authorization No.
N/A Expiration Date N/A Signed A
p77P-Date 4pruil 120 c
CERTIFICATE OF INSER VICE INSPECTION 1, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report duiring tlie period 4/o to 1r L
/6
, and state that to the best of my knowled-e and belief, the owner has performed examinations and taken corrective measures described in (his Owner's Report in accordance the requirements of the ASIME Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or propert 1damnage or a loss of any kind arising from or connected with this inspection.
.1r_-
Commissions
/&.*
,,I-- // ý,r 20 06 4-/i--f 20 0
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT (Supplement)
As Required by the Provisions of ASME Codc Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
04/5/2006 Sheet:
2 of 3 Unit:
0 PO# 707 REL. I 2947/REC 151547 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None
- 3. Work Performed by:
Quad Cities Generating Station Authorization No.:
None 22710 206th Ave. North, Cordova, IL 61242 Expiration Date:
N/A
- 4. Identification of System: Spare Control Rod Drive. Class I
- 5. (a) Applicable Construction Code: Component: ASME Section 111 1965 Edition.
W-1965 Addenda.
N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, I996 Addenda.
N/A Code Case Attachment A Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Program Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
No.
Replacement Stamped (Yes or
___No)
Control Rod Drive GE Nuclear S/N: 156 N/A 0- Spare-DIS5 N/A Replacement Yes06-049 Energy Control Rod Drive GE Nuclear S/N: 163 N/A 0- Spare-DI15 N/A Replacement Yes06-050 Energy Control Rod Drive GE Nuclear S/N: 331 N/A 0- Spare-D 15 N/A Replacement Yes06-051 Energy Control Rod Drive GE Nuclear S/N:370 N/A 0- Spare-D 15 N/A Replacement Yes06-052 Energy Control Rod Drive GE Nuclear S/N:484 N/A 0- Spare-D15 N/A Replacement Yes06-053 Energy Control Rod Drive GE Nuclear S/N: 558 N/A 0- Spare-DI15 N/A Replacement Yes06-054 Energy_________
Control Rod Drive GE Nuclear S/N: 565 N/A 0- Spare-DI15 N/A Replacement Yes06-055 Energy Control Rod Drive GE Nuclear S/N: 57 1A N/A 0- Spare-DI15 N/A Replacement Yes06-056 Energy Control Rod Drive GE Nuclear S/N: 637 N/A 0- Spare-D 15 N/A Replacement Yes06-057 Energy____
Control Rod Drive GE Nuclear S/N: 676 N/A 0- Spare-DI15 N/A Replacement Yes06-058 Energy Control Rod Drive GE Nuclear S/N: 1203 N/A 0- Spare-DI15 N/A Replacement Yes06-059 Energy Control Rod Drive GE Nuclear S/N: 1451 N/A 0- Spare-DI15 N/A Replacement Yes06-060 Energy Control Rod Drive GE Nuclear SIN: 1824 N/A 0- Spare-DI15 N/A Replacement Yes06-061 Energy Control Rod Drive GE Nuclear S/N: 1924 N/A 0- Spare-D 15 N/A Replacement Yes06-062 Energy I______
Control Rod Drive GE Nuclear S/N: 1940 N/A 10- Spare-DI15 N/A Replacement Yes06-063 Energy I______
I_______
I_____
I-__
I
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT (Supplement)
As Required by the Provisions of ASME Code Section XI L. Owner:
Exelon Generation Company, LLC 4300 Winfield Road WVarrenville. 11. 60555 Date:
04/5/2006 Sheet:
3 of 3 Unit:
0 2.Plant:
Quad Cities Generating Station PO# 707 REL. I 2947/REC 151547 22710 206th Ave. North, Cordova. IL 61242 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None
- 3. Work Performed by:
Quad Cities Generating Station Authorization No.:
None 22710 206th Ave. North, Cordova. IL 61242 Expiration Date:
N/A
- 4. Identification of System: Spare Control Rod Drive, Class 1
- 5. (a) Applicable Construction Code: Component: ASNIE Section 111 1965 Edition, W-1965 Addenda.
N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Program Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
No.
Replacement Stamped (Yes or No)
Control Rod Drive GE Nuclear S/N: 6184 N/A 0- Spare-DI15 N/A Replacement Yes06-064 Energy Control Rod Drive GE Nuclear SIN:6473 N/A 0- Spare-D 15 N/A Replacement Yes06-065 Energy Control Rod Drive GE Nuclear S/N: 7069 N/A 0- Spare-DI15 N/A Replacement Yes06-066 Energy Control Rod Drive GE Nuclear S/N: 9350 N/A 0- Spare-DI15 N/A Replacement Yes06-067 Energy Control Rod Drive GE Nuclear S/N: A4564 N/A 0- Spare-DI15 N/A Replacement Yes06-068 Energy
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMIENT As Required by the Provisions of ASMIE Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Wvarrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
06/08/2006 Sheet:
I of I Unit:
2 Program No.06-070 WNO W0656074-01 Repair Organization P.O. No., Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: High Pressure Coolant Injection. Class 1
- 5. (a) Applicable Construction Code: ASME Section 1 1965 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized Ibr Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Cor ponents Repaired or Replaced, and Re placement Cornponents:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mvfir.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Snubber PSA 12752 N/A 2-2305-77 N/A Replacement..
No
- 7. Description of Work: -Replaced snubber in accordance with the WNO.
- 8. Tests Conducted:
Hydrostatic E3 Pneumatic Q1 Nominal Operating Pressure Other E Pressure psi Test Temp.
F
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASNIE Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Anp B. 0 A Program Certificate of Authorization No.
N/A
__Expiration Date N/A Signed orb
/L.LŽ l!-Date
___________20-06, M~
~
re' t-ge,1l CERTIFICATE OF INSERVICE INSPECTION
- 1. the unodersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
.and employed by HSB Cl7. of Connecticut
-have inspected the componenits dcscribed in this Owner's Report during the period
-5 to 6
,and state that to the best of my knowlecdge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and correcti've measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
.(~
'4-.
Commissions
/-/C7 Date
/21, 20 0 ýS
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/09/2006 Sheet:
1 of I Unit:
I Program No.06-071 WO 905901-01 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 2
- 5. (a) Applicable Construction Code: USAS B3 1.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996
- Addenda, N/A Codc Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Valve Anchor Darling N/A N/A 2-0220-2 N/A Repaired
-No
- 7. Description of Work: -Overhauled valve in accordance wvith the WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure E Other [D Pressure psi Test Temp.
- 9. Remarks:
Appendix J test.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Ap B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Aj,1 Pro f!
at
'1 20 D(*
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period to
- L4L-t../:i to
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective'measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kid arising from or connected with this inspection.
Commissions Q. -b )
vetrs Signature Nalkinal Niard. State. Proviner.aml Endor,&n)cru%
Dat Dah
/
200C (7
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road vVarrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
6/28/2006 Sheet:
I of I Unit:
2 Prog(-ram No. 06.075 WO 00832684-01 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Residual Heat Removal. Class 2
- 5. (a) Applicable Construction Code: -USAS 1331.1 1967 Editions, N/A Addenda,.N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N-416-3 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component rvfr.
No.
B~d.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Relief Valve CONSOLIDATED TP-34857 N/A 2-1001-125A N/A Replacement Yes I
VALVE CORP
- 7. Description of Work: Replaced valve, flange, and bolting in accordance with the \\V.O.
- 8. Tests CondUCted:
Hydrostatic E5 Pneumatic 5:
Nominal Operating Pressure Other 5 Pressure psi Test Temp.
-___ 'F
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE We certify dhat the statements nmadc in this report are correct and this replacement conforms to (lie rules of ASNME Codce.Section X I repair or replacernent Type of Code Symbol Stamp N/A - E--xelon Nuclear I0CFR5O App 13. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed fY5kAij/
owi
&-t Date
~
Q%
320(o~
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of -5... and employed by-I-ISB CT. of Connecticut t have inspected the components described in this Owner's Report during the period to and state that to the best ofimy knowledge and belief, the owner has performed examinations and taken corrective mneasures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any mnanner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- Commissions 25I A M Date 20f'
(
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMIENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Wijnfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
6/08/2006 Sheet:
I of I Unit:
2 Program No.06-076 WO 00776113-01 Repair Organhi-aiion P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Residual Heat Removal, Class 2
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Editions, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N-416-3 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mifrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mf1r.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve DeerTP 32874 1N/A 1 2-1001-125B3 N/
ReplacementYe
- 7. Description of Work: Replaced the fiange bolting. pipe, and flange in accordance with the WV.O.
- 8. Tests Conducted:
Hydrostatic 1:
Pneumatic El Nominal Operating, Pressure 19 Other 5 Pressure psi Test Temp.
-___ 'F
- 9. Remarks:
None.
CERTIFICATE OF COMPLIANCE We certify that thc statements made in (his report are correct and this replacement conforms to the rules of ASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I QCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed qqJ&lIE 9
200CC' CERTIFICATE OF INSER VICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
.and employed by I-ISB C7..f Connecticut
_have inspected the components described in this Owner's Report during the period 0
4//2Z/O6
. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective meaisures described in this Owner's Rcport in accordance the requirements of the ASME Code,Section XI.
By signintg this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be l iable in any mnanner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
j~) ~
Commissions
,'~
/ -. "- ý (a
Na6mil Board. Slaw. Pn-,ince..Ind Endo"ment, I
FORM NTS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASMIE Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Qulad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
QUad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
06/19/2006 Sheet:
I of I Unit:
21 Program No.06-078 WO 00906180-01 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification oftSystem: High Pressure Coolant Injection. Class I
- 5. (a) Applicable ConstruIction Code: USAS 1331.1I 1967 Editions, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda.
N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfi-s. Ser-.
Nat'l Other Year
- Repaired, ASME Component Mifr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
___________~-7
_771777T_
No)
Snubber Basic-PSA INC.
40258 N/A 2/2305-7
/
Replacement No
- 7. Description of Work: Replaced snubber in accordance with the WV.O.
- 8. Tests Conducted:
Hlydrostatic E3 PneuIma1tic El Nominal Operating Pressure El Other fl Pressure ____
psi Test Temp. ____
'F
- 9. Remarks:
None.
CERTIFICATE OF COMIPLIANCE WVe certi fy that the statements made in this report are correct and this replacement conforms to the rule1s of AS.ME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I 0CFR5() App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Qfg AAL 5Lf..
Pre 5apy
..... Date
~
Jvve- '20 0(o t/
w)%ntror wnLi'A)s,,iL il CERTIFICATE OF INSERVICE INSPECTION I. the undersig-ned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
.and emrployed by IISB Ci. of Connectieut
.have inspected thc components described in this Owner's Report (luring the period /
5/i4L_.*.
to 1,210 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective mecasures described in this Owner's Report in accordance the requirements of ihe ASMIE Code,Section XI.
By signing this certificate, neither ihe inspector nor-his employer makes any warranty. expressed or imiplied. concerning the examinations and corrective measures (lescribed in this Owner's Report. Furthermiore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or propert damg or aoso any kind arising from or connected with this inspection.
(1
~Commissions I
Rite 4 Izi 20 Nil flu Iluurd. 51.uI'. Pfl,,flk,.. md huid 'r.~IlkIui I Dal 20-
FORMN NIS-2 OWNERS REPORT OF REP.1AIR OR REPLACEMNENT As ReqJUired by the Provisions of ASME Code Section X1
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating, Station 22710 206th Ave. North, Cordova. IL 61242
- 3. W~ork Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
05/6/2006 Sheet:
I of I Unit:
2 Program No.06-079 WO 009061 83-01 Repair Or-aili/ation P.O. No.. Job No.. etc.
Type Code Symbol Stamip:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Reactor Core Isolaion Cooling. Class I
- 5. Gt)Ap\\plicaible Constiuotioo Ctode; LTSAS 1331.1 1 967 Edition.
NNi,\\
Addenda. N/A Code CI.SC (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. _N/A Code Case
- 6. Identification of Com-ponents Re paired or Replaced, and Re placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASNIE Component Mfr.
No.
Bd.
Identification Bu~ilt Replaced, or Code No.
Replacement Stamped (Yes or SubrPSA 30696 N/A TS-2-042 N/A Replacement No)
S. Tests Conducted:
Hydrostatic El Pnieumatic E]
Nominal Operating Pressure Other E Pressure ___
psi Test Temp.
-___ '17
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this T1placement conformis to thie rules of ASME Code S ecionXi repair or replacementi Type of Code Synmbol Stamnp N/A - Fxclon Nuclear I OCFR50 A pp B.QAProgram Certificate of Authorization No.
N/A Expiration Date N/A Signed f________
___ 4______________Date I)200 o
V 04tier(ir wne's~kidic.tl CERTIFICATE OF INSER VICE INSPECTION
- 1. ( lie uindersigned, hold i aia valid comminission issued by the National Board ut Boiler and Pressure Vessel Inspectors and the State of Illinois andemiployed by 'HSBC(T.of Connecticut have inspected the components described in this Owner's Report during-
[lhe period C
to and state that to the best of my knowledge and belief, (the owner has perfornied examiinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASMIE Code. Section Xl.
By signing this certilicate. neither thie inspector nor his employer makes any warranty, expressed or implied, concerning thie examinations and corrective measures described in this Owner's Report. Furthermiore, neither the Inspector nor his employer shall be liable in any manner for any p~ersonal injury or property damnage or a loss of any kind arising fromt or connected with this inspection.
(*'_________________Commtiissions
/-4 Ir 1r-~riSi
.,.ii Ir.i~rrk.diV
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As ReqUired by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
QUad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
05/6/2006 Sheet:
I of I Unit:
2 Program No.06-082 WVO M0907358-01 Repazir Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Residual Heat Removal. Class 2
- 5. (a) Applicable Construction Code:
USAS B331.1 1967 Edition.
N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or epaead lcmn Components:
Name of Name of Mvfrs. Ser.
Nat'l Other Year Repaired.
ASME Component M fr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or Snubber PSA 14007 N/A TS-2-127 N/A Replacemn No)
- 7. Description of Work: -Replaced load pin in accordance with the WO.
- 8. Tests ConduIcted:
Hydrostatic El Pneumatic El Nominal Operating Pressuire El Other E]
Pressure psi Test Temp.
-___ 'F
- 9. Remarks:
N/A.
CERTIFICATE OF COMPLIANCE We certify that the statemecnts mande in this report ire corr-cct and this replacement cnifoiirns to the tilcs ofASME.Code1.
Scction XI repair or reptacenient Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Progcram Certificate Of Au~thorization No.
N/A Expiration Date N/A Signed N___________________________Date K M20 PC-CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois., atnd employed by IISB CT. of Connecticut
-have inspected the components described in this Owner's Report during the period 11L4Z1.5 to !5-1olc-6, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective mneasures decscrihedl in this Owner's Report in accordance the requirements of the ASME Code.Section X I.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concernling the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspcctor nor his employer shall be liable in any mianner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_______________________-P___Comtmissions
/Oa" Date
<"/,20 C! 1
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 227101 206th Ave. North. Cordova, IL 61242 Date:
4/15/2006 Sheet:
I of I Unit:
2 Program No.06-086 W0008 18566 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam. Class 1
- 5. (a) Applicable Construction Code: ASME Sect. 111 1968 Editions, Winter 1968 Addenda, N/Ak Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Relief Valve Target Rock N/A N/A 2-0203-3A N/A Replacement No
- 7. Description of Work: Replaced the bolting in accordance with the WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure E Other E]
Pressure ____
psi Test Temp.
F
- 9. Remarks:
None.
CERTIFICATE OF COMIPLIANCE We certify that the statements made in this report are correct and this replaceme.nt conforms to the nulcs of ASME Codc. Scction XI rearo cp 'lacnicl Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed I
l6 j /A!-o Date (0
I 200(01 CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boilcr and Pressure Vessel Inspectors and the State of Ill~jinis..
andcemployed by HSB Cl. of Connecticut have inspected the components described in this Owner's Report during the period 1-1 I2-05 to 41-171c,6, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this ecertit icte. neither the inspector nur his employer makes any warranty. exprcsscd or implied. concerning the cxaminations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in ainy manner for any personal injury or property damitgc or a loss of ay darsng from or connected with this inspction.
_______________Cmmsson g
oa k.l.'I6dr<%r Signrnuir Date 4 1//-7
(/ C)
NMiih'nl Rourd. Swjit. h',whince. and lEndurciuncni, 20 0A
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions ot ASMvE Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Axe. North. Cordiova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
00/16/2006 Sheet:
I of I Unit:
2 Program No.06-125 WO 99242367-02 Repair Or.-anization P.O. No.. ioh No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Core Spray. Class 2
- 5. (a) Applicable Construction Code: USAS 1331.1 1967 Editions, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edlition, 1996 Addenda, N/A Code Case
- 6. Idlentification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
lBd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or No)
Pipe Support Exelon i
N/A iN/A ji 2-1810-35 N/r A Repair No
- 7. Description of Work: -Welded stiffening plate to 2ipe support.
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure f Other E] ____Pressure
____psi Test Temp.____
'F
- 9. Remarks: IR# 501724 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair conforms ito the rules of ASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Protram Certificate of Authorization No.
N/A Expiration Date NIA Signed __________________________
-Date 2004 CE~RTI FICATE OF INSERV'ICE INSPE'CTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois
.andcemployed by IISB (.T.of Connccticut
-have inspected the components described in this 0wner~s Report during the period I4ý/ ZL6*' to 0 4LZ
.'. and state that to the best or my knowledge and belief, the owner has performed examinations and taken corrective measures described in ths Owner's Report in accordance the requirenments or the ASMIE Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
commissions
/-
/
0