RS-19-084, Relief Request Associated with the Third Ten-Year Inservice Inspection Program Interval
| ML19239A156 | |
| Person / Time | |
|---|---|
| Site: | Braidwood |
| Issue date: | 08/27/2019 |
| From: | Demetrius Murray Exelon Generation Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| RS-19-084 | |
| Download: ML19239A156 (63) | |
Text
{{#Wiki_filter:Exelon Generation RS-19-084 August27,2019 U.S. Nuclear Regulatory Commission ATTN : Document Control Desk Washington, DC 20555-001 Braidwood Station, Units 1 and 2 4300 Winfield Road Warrenville, IL 60555 630 657 2000 Office 10 CFR 50.55a Renewed Facility Operating License Nos. NPF-72 and NPF-77 NRC Docket Nos. STN-50-456 and STN-50-457
Subject:
Relief Request Associated with the Third Ten-Year lnservice Inspection Program Interval In accordance with 10 CFR 50.55a, "Codes and standards," paragraph (g)(5)(iii), Exelon Generation Company, LLC, (EGC) hereby requests NRC approval of the attached relief request associated with the Third 10-year lnservice Inspection (ISi) Program Interval for Braidwood Station, Units 1 and 2. The third interval of the Braidwood Station ISi program complies with the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel (B&PV) Code, Section XI, "Rules for lnservice Inspection of Nuclear Power Plant Components," 2001 Edition with 2003 Addenda and ASME B&PV Code, Section XI, 1998 Edition subject to conditions specified in 10 CFR 50.55a(b )(2)(xxi). NRC approval of the attached relief is requested on the basis that 100% examination coverage of required surfaces and volumes of Class 1 and 2 components has been determined to be impractical. Due to the original design and/or the base metal materials associated with the specified welds, it is not feasible to effectively perform examinations of 100% of the volume of these welds. provides the details of the 10 CFR 50.55a request. EGC requests approval of this relief request by August 27, 2020. There are no regulatory commitments contained within this letter.
August27,2019 U. S. Nuclear Regulatory Commission Page 2 Should you have any questions concerning this letter, please contact Mrs. Linda Palutsis at (630) 657-2821. ~-ly-J., Dwi Murray Sr. Manager Licensing Exelon Generation Company, LLC Attachments:
- 1. 1 O CFR 50.55a Request Number 13R-18
- 2. Braidwood Station Unit 1 Third ISi Interval Limited Coverage NOE Reports
- 3. Braidwood Station Unit 2 Third ISi Interval Limited Coverage NOE Reports cc:
NRC Regional Administrator, Region Ill NRC Senior Resident Inspector, Braidwood Station NRR Project Manager, Braidwood Station Illinois Emergency Management Agency - Division of Nuclear Safety
ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFRSO.SSa(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 1 of 9)
- 1.
ASME Code Component(s) Affected Code Class:
Reference:
Examination Category: Item Number:
== Description:== Component Number: 1&2 IWB-2500, Table IWB-2500-1, IWC-2500, Table IWC-2500-1, ASME Code Case N-460 ASME Code Case N-578-1, Table 1 B-D, C-A, R-A B3.110, B3.140, Cl.30, Rl.11, Rl.20 Limited Examination Coverage See Tables BR-18.1 and BR-18.2 for a list of Component IDs
- 2.
Applicable Code Edition and Addenda
The Braidwood Station, Units 1 and 2, Third Interval Inservice Inspection (ISI) program was based on the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel (B&PV) Code, Section XI, 2001 Edition through the 2003 Addenda and ASME B&PV Code, Section XI, 1998 Edition subject to conditions specified in 10 CFR 50.55a(b )(2)(xxi). Braidwood maintains the responsibility to ensure exams were performed in accordance with the requirements of ASME, Section XI, Appendix VIII, "Performance Demonstration for Ultrasonic Examinations Systems," as amended and mandated by 10 CFR 50.55a and as modified by the Performance Demonstration Initiative (PDI) Program Description. In the case of limited examinations, additional best effort examinations are performed to attain additional examination coverage. Tables BR-18.1 and BR-18.2 identify the best effort examinations are performed in accordance with the requirements of ASME, Section XI, Appendix VIII.
- 3.
Applicable Code Requirement
The extent of examination requirement for Examination Category B-D, Item Number B3.110, per Table IWB-2500-1, requires a volumetric examination of all nozzle-to-vessel welds. In accordance with 10 CFR 50.55a(b)(2)(xxi) and ASME B&PV Code, Section XI, 1998 Edition, the extent of examination requirement for Examination Category B-D, Item Number B3.140, per Table IWB-2500-1, requires a volumetric examination of all nozzle inside radius sections. The extent of examination requirement for Examination Category C-A, Item Number C 1.30, per Table IWC-2500-1, requires a volumetric examination of the tubesheet-to-shell weld. The extent of examination requirement for Examination Category R-A, Item Number Rl.11 and Rl.20, per Table 1 of ASME Code Case N-578-1, requires a volumetric examination of essentially 100% of the length of the Risk Informed Inservice Inspection (RI-ISI) weld. Relief Request BR-01 was submitted and approved by the NRC through a Safety Evaluation (SE) dated November 5, 2009 (ADAMS Accession No. ML093070271) in order to utilize EPRI Topical Report (TR) 112657 Rev. B-A, as supplemented by ASME Code Case N-578-1.
ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFRSO.SSa(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 2 of9) Braidwood adopted ASME Code Case N-460 ("Alternative Examination Coverage for Class 1 and Class 2 Welds, Section XI, Division l "), which defines "essentially 100%" as greater than 90% coverage of the examination volume or surface area, as applicable. The 90% minimum coverage was applied to all surface and volumetric examinations required by ASME Section XI.
- 4.
Impracticality of Compliance Pursuant to 10 CFR 50.55a(g)(5)(iii), relief is requested on the basis that conformance with these code requirements is impractical as conformance would require extensive structural modifications to the component or surrounding structure. Due to the original design of these components, it is not feasible to effectively perform the examinations to the extent required for welds and inner radius sections, greater than 90% of the volume and/or area. Therefore, relief is requested on the basis that the ASME Section XI Code requirements to examine these components are impractical due to physical obstructions, plant location, and/or component geometry. Braidwood is unable to satisfy the ASME Section XI Code requirement to perform a volumetric examination of these components due to the physical component configuration, interference from permanent plant equipment, single-sided access, etc. Braidwood would incur significant engineering, material, and installation efforts to perform such modifications without a compensating increase in the level of quality and safety. For the RI-ISI weld population, Examination Category R-A welds, submitted in this relief request, a case by case review was performed to determine whether additional or alternative welds could have been examined to supplement the reduced volumetric coverage examination. It was determined that there were no other welds to select that would have resulted in better coverage. This determination was made based on comparison of configurations, delta core damage frequency (CDF) values, the systems involved, and inspection history. During outages, when situations were identified where coverage was an issue, Braidwood personnel reviewed the systems for alternatives. Tables BR-18.1 and BR-18.2 provide a summary of the examination limitations for each component for which relief is requested. The tables also indicate the outage the component was examined, the coverage percentage obtained for each component, and other pertinent design information. These tables are the cumulative lists of all the limited ASME Section XI examinations performed during the second and third periods of the Third ISI Interval. Attachments 2 and 3 provide coverage plots which were extracted from the non-destructive examination (NDE) summary sheets that detail the examination limitations. Based on the above, Braidwood requests relief to perform examinations without achieving code compliance coverage when required coverage is impractical.
- 5.
Burden Caused by Compliance Compliance with the applicable ASME Section XI Code volumetric examination requirements can only be accomplished by redesigning and refabricating the subject and/or surrounding
ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFRSO.SSa(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 3 of9) components. Based on this, the ASME Section XI Code requirements are deemed impractical in accordance with 10 CFR 50.55a(g)(5)(iii).
- 6.
Proposed Alternative and Basis for Use Braidwood has performed the ASME Section XI Code required examinations to the maximum extent possible (Code Coverage), or best effort, which are documented in Tables BR-18.1 and BR-18.2. Due to physical interferences causing these limitations, there are no alternative examination techniques currently available to increase coverage. There were no cases in any of the listed examination components where outside diameter surface features (i.e., weld crowns, weld shrinkage, surface roughness, etc.) could have been conditioned to obtain the required coverage without major modification to the components. As a minimum, all components received the required volumetric examination to the extent practical due to limited or lack of access. Additionally, VT-2 examinations were and will continue to be performed on the applicable components throughout the interval through the required system pressure tests (examinations required by ASME Section XI and Generic Letter 88-05, "Boric Acid Corrosion of Carbon Steel Reactor Pressure Boundary Components in PWR Plants"). The absence of any observed leakage provides additional assurance that the structural integrity of the subject components will be maintained throughout the remainder of the interval.
- 7.
Duration of Proposed Alternative: Relief is requested for the Second and Third Periods of the Third Ten-Year ISi Interval for Braidwood, Units 1and2. The Third Ten-Year ISi Interval end dates are August 28, 2018 and November 4, 2018 for Units 1 and 2, respectively. The First Period relief request of the Third Ten-Year ISi Interval (13R-10) was submitted and approved on January 30, 2013 (ADAMS Accession No. ML13016A515).
- 8.
Precedents Similar relief requests have been approved for: Byron Station, Units 1and2 Third Inservice Inspection Relief Requests BR-12 and BR-15 was authorized per NRC SE dated January 25, 2018 (ADAMS Accession No. MLl 7349A960). Watts Bar Nuclear Plant, Unit 1 Second Inservice Inspection Relief Request 1-ISI-21 was authorized per NRC SE dated April 12, 2019 (ADAMS Accession No. ML19071A009). Limerick Generating Station, Units 1 and 2 Third Inservice Inspection Relief Request BR-23 was authorized per NRC SE dated August 7, 2018 (ADAMS Accession No. ML18192Cl 72). Surry Power Station, Unit 2 Fourth Inservice Inspection Relief Requests LMT-ROl, LMT-C02, and LMT-C03 were authorized per NRC SE dated February 17, 2017 (ADAMS Accession No. ML16365Al 18).
Exam Weld Component ID Description Requirements (System)' (Figure No.) and Method Elbow-to-IWC-2500-7(a) 1Sl-39-08 Valve Weld Volumetric (SI} (UT} Valve-to-Pipe IWC-2500-7(a) 1Sl-39-08A Weld Volumetric (SI) (UT) Elbow-to-IWC-2500-7(a) 1Sl-39-25 Valve Weld Volumetric (SI) (UT) Valve-to-Pipe IWC-2500-7(a) 1Sl-39-25A Weld Volumetric (SI) (UT) Pipe-to-Valve IWC-2500-7(a) 1Sl-39-25B Weld Volumetric (SI) (UT) 1CV-22-30 Valve-to-Pipe IWC-2500-7(a) (1CV109-Weld Volumetric 4/FW-1) (CV) (UT) Exam ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFR50.55a(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 4 of9) Table 13R-18.1 Braidwood, Unit 1 List of Components with Limited Examination Coverage Normal Operating Exam Angle/ Category I Outage Material of Diameter/ Conditions Frequency (MHz) I Actual Item Examined Construction Thickness (Pressure I Mode Coverage Number Temperature) R-A 2485 psig o* 14.00 I Long A1R16 SA 376 TP304 4"" / 0.531 "" 45* I 2.25 1 Shear 50.0% R1.20 176 deg-F 60" 12.00 I Long. R-A SA 376 TP304 2485 psig o* 14.00 I Long A1R16 4"" / 0.531 "" 45* I 2.25 1 Shear 50.0% R1.20 176 deg-F 60" I 2.00 I Long. o* 14.00 I Long R-A SA 376 TP304 2485 psig 45* I 2.25 1 Shear R1.20 A1R16 4"" / 0.531 "" 176 deg-F 60" / 2.00 I Long. 50.0% 45* I 5.00 I Shear o* 14.00 I Long R-A SA 376 TP304 2485 psig 45* I 2.25 1 Shear R1.20 A1R16 4"" / 0.531 "" 176 deg-F 60" / 2.00 I Long. 50.0% R-A SA 376 TP304 2485 psig 45* I 2.25 I Shear R1.20 A1R16 4"" / 0.531 "" 176 deg-F 60" / 2.00 I Long. 50.0% R-A SA 376 TP304 2485 psig 45* I 2.25 I Shear R1.20 A1R18 4"" / 0.531 "" 200 deg-F 60" / 2.00 I Long. 50.0% Appendix VIII Remarks Qualified Exam Examination was limited due to valve Yes configuration and one-sided exam. (Att. 2 Pg. Nos. 2 & 3) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 2 Pg. Nos. 4 & 5) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 2 Pg. Nos. 6 - 8) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 2 Pg. Nos. 9 & 10) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 2 Pg. Nos. 11 & 12) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 2 Pg. Nos. 13 & 14) Notes:
- 1.
The following systems and their abbreviations are listed here: Auxiliary Feedwater (AF), Chemical and Volume Control System (CV), Pressurizer PRT (RY), Feedwater (FW), Reactor Coolant (RC), Safety Injection (SI)
Exam Weld Component ID Description Requirements (System)' (Figure No.) and Method Nozzle N 1-to-IW8-2500-7 1PZR-01-N1 PZR Shell Volumetric Weld (UT} (RY) Nozzle N4A-IW8-2500-7 1PZR to-PZR Head Volumetric N4A Weld (UT) (RY) Exam ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFR50.55a(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 5of9) Table 13R-18.1 Braidwood, Unit 1 List of Components with Limited Examination Coverage Normal Operating Exam Angle/ Category I Outage Material of Diameter/ Conditions Frequency (MHz) I Actual Item Examined Construction Thickness (Pressure I Mode Coverage Number Temperature) o* 12.25 1 Long 8-D A1R19 Alloy 182/82 14" / 3.1 " 2485 psig 45* I 2.25 1 Shear 74.7% 83.110 680 deg-F 60" I 2.25 1 Shear o* / 2.25 / Long 8-D A1R19 Weld Overlay 6" / 3.1" 2485 psig 45* I 2.25 1 Shear 68.7% 83.110 - Alloy 52/52M 680 deg-F 60" I 2.25 I Shear Appendix VIII Remarks Qualified Exam Examination limited in the "w" Yes dimension of 6.0" at 290" due to proximity of heater penetration tubes. (Att. 2 Pg. Nos. 15 & 16) Examination limited due to nozzle Yes configuration. (Att. 2 Pg. Nos. 17 & 18) Notes:
- 1.
The following systems and their abbreviations are listed here: Auxiliary Feedwater (AF), Chemical and Volume Control System (CV), Pressurizer PRT (RY), Feedwater (FW), Reactor Coolant (RC), Safety Injection (SI)
Exam Weld Component ID Description Requirements (System)' (Figure No.) and Method Elbow-to-IWC-2500-7(a) 2Sl-39-11 Valve Weld Volumetric (SI) (UT) Valve-to-Pipe IWC-2500-7(a) 2Sl-39-11A Weld Volumetric (SI) (UT) Elbow-to-IWC-2500-7(a) 2Sl-39-28 Valve Weld Volumetric (SI) (UT) Valve-to-Pipe IWC-2500-7(a) 2Sl-39-28A Weld Volumetric (SI) (UT) Pipe-to-Valve IWC-2500-7(a) 2Sl-39-288 Weld Volumetric (SI) (UT) Nozzle N48-IW8-2500-7 2PZR to-PZR Shell Volumetric N48 Weld (UT) (RY) Exam ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFR50.55a(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 6of9) Table 13R-18.2 Braidwood, Unit 2 List of Components with Limited Examination Coverage Normal Operating Category I Outage Material of Diameter/ Conditions Exam Angle/ Actual Item Examined Construction Thickness (Pressure I Frequency I Mode Coverage Number Temperature) R-A SA 376 TP304 2485 psig o* 14.00 I Long A2R16 4" / 0.531 " 45° I 2.25 1 Shear 50.0% R1.20 176 deg-F 60° / 2.00 I Long. R-A SA 376 TP304 2485 psig o* 14.00 I Long A2R16 4" / 0.531 " 45° I 2.25 1 Shear 50.0% R1.20 176 deg-F 60° / 2.00 I Long. o* 14.00 I Long R-A SA 376 TP304 2485 psig 45° I 2.25 1 Shear R1.20 A2R16 4" / 0.531 " 176 deg-F 60° I 2.25 I Shear 50.0% 70° I 2.25 1 Shear 60° I 2.00 I Long. R-A SA 376 TP304 2485 psig o* 14.00 I Long R1.20 A2R16 4" / 0.531 " 176 deg-F 45° I 2.25 I Shear 50.0% 60° / 2.00 I Long. o* 14.00 I Long R-A SA 376 TP304 2485 psig 45° I 2.25 1 Shear R1.20 A2R16 4" / 0.531 " 176 deg-F 60° I 2.25 1 Shear 50.0% 60° / 2.00 I Long. 8-D A2R17 Alloy 182/82 91.5" / 2485 psig 45° I 2.25 1 Shear 88.5% 83.110 2.0625" 680 deg-F o* I 2.25 1 Long Appendix VIII Remarks Qualified Exam Examination was limited due to valve Yes configuration and one-sided exam. (Att. 3 Pg. Nos. 2 & 3) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 3 Pg. Nos. 4 & 5) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 3 Pg. Nos. 6 & 7) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 3 Pg. Nos. 8 & 9) Examination was limited due to valve Yes configuration and one-sided exam. (Att. 3 Pg. Nos. 10 & 11) Examination was limited due to nozzle Yes configuration and one-sided exam. (Att. 3 Pg. Nos. 12 & 13) Notes:
- 1.
The following systems and their abbreviations are listed here: Auxiliary Feedwater (AF), Chemical and Volume Control System (CV), Pressurizer PRT (RY), Feedwater (FW), Reactor Coolant (RC), Safety Injection (SI)
Exam Weld Component ID Description Requirements (System)' (Figure No.) and Method Nozzle N4C-IWB-2500-7 2PZR to-PZR Shell Volumetric N4C Weld (RY) (UT) Elbow-to-SG IWC-2500-7(a) 2FW-09-25 2RC01BAAF Volumetric Nozzle Weld (UT) (FW) Nozzle N1-to-IWB-2500-7 2PZR-01-N1 PZR Shell Volumetric Weld (UT) (RY) Primary 2SG Nozzle Inner IWB-2500-7 Radius Volumetric SGN-01A Section (UT) (RC) Tubesheet-IWC-2500-2 2SG to-Barrel Volumetric SGC-02 Weld (UT) (RC) 2AF-03-23 Elbow-to-IWC-2500-7(a) Flange Weld Volumetric (FW-1) (AF) (UT) Exam ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFR50.55a(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 7of9) Table 13R-18.2 Braidwood, Unit 2 List of Components with Limited Examination Coverage Normal Operating Category I Outage Material of Diameter/ Conditions Exam Angle/ Actual Item Examined Construction Thickness (Pressure I Frequency I Mode Coverage Number Temperature) B-D A2R17 Alloy 182/82 91.5" / 2485 psig 45° I 2.25 I Shear 88.5% 83.1 10 2.0625" 680 deg-F 0° / 2.25 / Long 45° / 5.00 I Shear R-A A2R18 SA-106 6" / 0.719" 1185 psig 60° I 5.00 I Shear 87.3% R1.11 SMLS Gr.B 567 deg-F 70° I 5.00 I Shear B-D A2R19 Alloy 182/82 26.10" / 2485 psig 45° I 2.25 I Shear 59.2% 83.110 2.5625" 680 deg-F 60° I 2.25 I Shear B-D SA-216 29" / 2485 psig A2R19 33° I 2.25 I Long 85.0% 83.140 GrWCC 3.1875" 680 deg-F 0° / 2.25 / Long C-A A2R20 E8018-C3 11.3' / 2485 psig 45° I 2.25 I Shear 88.4% C1.30 3.3125" 680 deg-F 60° I 2.251 Shear R-A 2015 1185 psig 45° I 5.00 I Shear SA-106 4" / 0.337" 60° I 5.00 I Shear 87% R1.20 (PSI) 100 deg-F 70° I 5.00 I Shear Appendix VIII Remarks Qualified Exam Examination was limited due to nozzle Yes configuration and one-sided exam. (Att. 3 Pg. Nos. 14 & 15) Examination was limited due to nozzle Yes configuration. (Att. 3 Pg. No. 16) Examination was limited due to nozzle configuration and the proximity of Yes heater penetration tubes. Coverage plot taken from NDE Data Sheet A2R13-UT-025. (Att. 3 Pg. No. 17) Examination was limited due to a permanent structure for 30" out of the Yes total 205". (Att. 3 Pg. No. 18) Examination was limited due to Yes component configuration. (Att. 3 Pg. Nos. 19 & 20) Examination was limited due to Yes component configuration. (Att. 3 Pg. No. 21) Notes:
- 1.
The following systems and their abbreviations are listed here: Auxiliary Feedwater (AF), Chemical and Volume Control System (CV), Pressurizer PRT (RY), Feedwater (FW), Reactor Coolant (RC), Safety Injection (SI)
Component ID 2AF-03-24 (FW-2) 2AF-04-20 (FW-3) 2AF-04-21 (FW-4) 2AF-02-23 (FW-1) 2AF-02-24 (FW-2) 2AF-01-24 (FW-3) Notes:
- 1.
Exam Weld Description Requirements (System)' (Figure No.) and Method Flange-to-IWC-2500-7(a) Elbow Weld Volumetric (AF) (UT) Elbow-to-IWC-2500-7(a) Flange Weld Volumetric (AF) (UT) Flange-to-IWC-2500-7(a) Elbow Weld Volumetric (AF) (UT) Elbow-to-IWC-2500-7(a) Flange Weld Volumetric (AF) (UT) Flange-to-IWC-2500-7(a) Elbow Weld Volumetric (AF) (UT) Elbow-to-IWC-2500-7(a) Flange Weld Volumetric (AF) (UT) Exam ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFR50.55a(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 8of9) Table 13R-18.2 Braidwood, Unit 2 List of Components with Limited Examination Coverage Normal Operating Category I Outage Material of Diameter/ Conditions Exam Angle/ Actual Item Examined Construction Thickness (Pressure I Frequency I Mode Coverage Number Temperature) R-A 2015 1185 psig 45' I 5.00 I Shear SA-106 4" / 0.337" 60' I 5.00 I Shear 87% R1.20 (PSI) 100 deg-F 70' I 5.00 I Shear R-A 2015 1185 psig 45' I 5.00 I Shear SA-106 4" / 0.337" 60' I 5.00 I Shear 88% R1.20 (PSI) 100 deg-F 70' I 5.00 I Shear R-A 2015 1185 psig 45' I 5.00 I Shear R1.20 (PSI) SA-106 4" / 0.337" 100 deg-F 60' I 5.00 I Shear 88% 70' I 5.00 I Shear R-A 2015 1185 psig 45' I 5.00 I Shear SA-106 4" / 0.337" 60' I 5.00 I Shear 90% R1.20 (PSI) 100 deg-F 70' I 5.00 I Shear R-A 2015 1185 psig 45' I 5.00 I Shear SA-106 4" / 0.337" 60' I 5.00 I Shear 90% R1.20 (PSI) 100 deg-F 70' I 5.00 I Shear R-A 2015 1185 psig 45' I 5.00 I Shear SA-106 4" / 0.337" 60' I 5.00 I Shear 90% R1.20 (PSI) 100 deg-F 70' I 5.00 I Shear Appendix VIII Remarks Qualified Exam Examination was limited due to Yes component configuration. (Att. 3 Pg. No. 22) Examination was limited due to Yes component configuration. (Att. 3 Pg. No. 23) Examination was limited due to Yes component configuration. (Att. 3 Pg. No. 24) Examination was limited due to Yes component configuration. (Att. 3 Pg. No. 25) Examination was limited due to Yes component configuration. (Att. 3 Pg. No. 26) Examination was limited due to Yes component configuration. (Att. 3 Pg. No. 27) The following systems and their abbreviations are listed here: Auxiliary Feedwater (AF), Chemical and Volume Control System (CV), Pressurizer PRT (RY), Feedwater (FW), Reactor Coolant (RC), Safety Injection (SI)
Exam Weld Component ID Description Requirements (System)' (Figure No.) and Method 2AF-01-25 Flange-to-IWC-2500-7(a) Elbow Weld Volumetric (FW-4) (AF) (UT) Exam ATTACHMENT 1 10 CFR 50.SSa Request Number 13R-18 Relief Requested in Accordance with 10CFR50.55a(g)(S)(iii) --Inservice Inspection Impracticality-- Revision 0 (Page 9of9) Table 13R-18.2 Braidwood, Unit 2 List of Components with Limited Examination Coverage Normal Operating Category I Outage Material of Diameter/ Conditions Exam Angle/ Actual Item Examined Construction Thickness (Pressure I Frequency I Mode Coverage Number Temperature) R-A 2015 1185 psig 45' I 5.00 I Shear SA-106 4" / 0.337" 60' I 5.00 I Shear 89% R1.20 (PSI) 100 deg-F 70' I 5.00 I Shear Appendix VIII Remarks Qualified Exam Examination was limited due to Yes component configuration. (Att. 3 Pg. No. 28) Valve-to-Tee IWC-2500-7(a) 45' I 2.251 Shear Examination was limited due to 2CV-21-58 R-A 2015 2485 psig 60' I 2.25 I Shear (FW-1) 2CV-21-57 (FW-2) 2CV-21-56 (FW-2) Notes:
- 1.
Weld Volumetric R1.20 (PSI) A312/TP304 4" / 0.531" 200 deg-F 70' I 2.251 Shear 20.7% Yes component configuration. (CV) (UT) 60° I 2.00 I Long (Att. 3 Pg. Nos. 29 & 30) Tee-to-Pipe IWC-2500-?(a) 45' I 2.25 I Shear Examination was limited due to R-A 2015 2485 psig 60' I 2.25 I Shear Weld Volumetric R1.20 (PSI) A312/ TP304 4" / 0.531" 200 deg-F 70' I 2.25 I Shear 83.3% Yes component configuration. (CV) (UT) 60° I 2.00 I Long (Att. 3 Pg. Nos. 31 & 32) Pipe-to-Tee IWC-2500-?(a) 45' I 2.251 Shear Examination was limited due to R-A 2015 2485 psig 60' I 2.251 Shear Weld Volumetric R1.20 (PSI) A312/ TP304 4" / 0.531" 200 deg-F 70' I 2.251 Shear 83.3% Yes component configuration. (CV) (UT) 60° I 2.00 I Long (Att. 3 Pg. Nos. 33 & 34) The following systems and their abbreviations are listed here: Auxiliary Feedwater (AF), Chemical and Volume Control System (CV), Pressurizer PRT (RY), Feedwater (FW), Reactor Coolant (RC), Safety Injection (SI)
ATTACHMENT 2 Braidwood Station Unit 1 Third Inservice Inspection (ISi) Interval Limited Coverage Non-Destructive Examination (NDE) Reports Page 1 of 18
r'\\ ~ - .W.~~pync: ol ~\\'* ~ t i r1 ah n*"'I "' E l..-: ri ~ Cnmp./lft~ Plant I Unit Braidwood / 1 Company Exelon Comp I System FW#8/SI Procedure No_ EXE-PDl-UT-2 Rev I Chng. No. 710 Cal. Block No. 22572 Cal. Block Temp. 72°F Thermometer S/N: SAP 106886 Size 4" Sch_ 160/0.531" "T' Ref. Block: I NIA I D Ferritic [!] Austenitic Each Major CRT Div. = 0.17" Cal. Direction: OAxial D Gire. [!] Both Scan Area: _L_toWeld II to Weld EB Code Category: R-A Code Item: R120 .IS.t Wc..ld ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limi,ted\\Coverage NDE Reports Calibration Data Sheet Data Sheet# A1R16-026 1 Page 2 of 4 N1 tch Cal. Checks Time Initial Calib. 10:06 Initial Calib. Date 04/16/2012 Intermediate N/A Search Unit #1 Intermediate N/A Manufacture: KBA Serial No.: oosRol5 Final Calib. 12:08 No. of Elements: 1 Size: 0.25" Shape: Round Final Calib. Date 04/16/2012 Freq. 2.25 MHz Style: CompG Exam Angle: 45° Mode: Shear Couplant Measured Ang-r;;:-- 43° Type: Ultragel II Wedge Style: MSWQC Batch: 09225 Search Unit Cable INDICATIONS EXAM 1 sr-3~~o8 ACCESS FLAW NON RELEVANT SENS. Type: RG-174 Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) Length: 6' No. of Con.: 0 FW#8 1 Sided x x 40.7 Instrument Settings Remarks I Reason for lncomQlete Scan(s) COMPONENT TEMP:63_°F Increased exam volume due to RI-ISi requirements_ See attached coverage plot. 50% Make I Model: GEIT USN 60 SW Code coverage achieved due lo one side exam. Serial No.: SAP 105204 Probe Delay: 4.0300 Range:
- 1. 7" M'tl Cal I Vel: 0.1234 Pulser:
Square Damping: soo-Reject: 0% PRF: Auto High Freq: 2.25 MHz Filter: Fixed Mode: Dual Off Examiners: Joseph Sert~,£ Rectify: Fullwave Voltage: 450 Level II Date 04/16/2012 Pulse Width: 220 ns JasonJ. J~-'" - '"""Z-leve I II Date 04/16/2012 Display Delay: 0 / ZJ..u,.J K * ~ L vl I1T /fl f:j(rt Reference Sensitivity (dB) WesDyne Reviewer I Date: Axial: 28.7 dB Circ: 28.7 dB Fi he~ Evaluation Required? Yes [!]No FSDH Sensitivity: NIA EXELON LEVEL Ill REVIEW I DATE n I \\ \\ \\ \\
- ~ Smoh un;l#2 Manufact Serial No No. of Eleme ts:
Size: Shape Freq. \\ Style: Exam Angle: ~Te\\-- Mode: Measured Angle: Wedge Style: \\ Search nit Cable N A Type: Length: No. con.: Instrument S ttings Make I Model: Serial No.: \\ Probe Delay: Range. M'tl Cal I Vel: Pulser: Damping: Reject: \\ PRF: Freq: \\ Filter: Mode: \\ Rectify: Voltage: -\\-- Pulse Width: Display Delay: \\ Reference Sensitivity (dB) Axial: Gire: FSDH Sensitivity: \\ A--,, 0 ~ ~ "'-\\~*\\L.- ANll REVIEW/ D~ ~. / L
- l:-?7
~ ~.20 - 2 ()/~ Page 2 of 18
ATTACHMENT 2 Braidwood Station Unit 1 ~ Third ISi Interval Limit@d. Covera~e NDE Reports ~*--- .------1 \\ f., f I ,~a : WcSDVnc uL TRASONIC EXAMINI.\\. hoN SKETCH SHEET Data Pkg.#: Alk. v-026
- .. 'I-.'*~'t'".1!>:,u-~:* ;J:~<-h<i:: ~ *n:: ::..:..,~*
Plant/Unit : Braidwood I 1 Iso. Drwg: 1Sl-39 Weld I Component ID Number: ~osmon 0 Crown Height: Flush 1 U.1:> 2 0.1/ Cro,,11 Width:
- 0. 75" 3
U./4 4 0.71 Diameter: 4.0" 5 i\\'R 6 i\\'R Weld Length 14.25" 7 8 i\\'R NR 9 NR Ir* "EL'OoW COMMENTS: Paae 4 of 4 Comp I System FW # 8 I SI IS! We.I~ FW # 8 I 5r-3 '} -08 9U 180
- 21u VVeld
- W e ld E dgo Cen t erlin e I
- 2.5"
- I
- 2.5"
- I m 00 @:I$
@:J 0~ m Too/\\ I I ~Toe Up Strvem ( - ) Sid* Elbow Component VPiL'VE I FLOVV ) IS I I OI r>. - Do""" S troorn ( +) Sir;;h, Valve Component EXA!vUf\\1£R: ~ <~ Lv. ll DATE 4/16/2012 Lv. II DATE: 4/ 16/2012 Joseph Serth REVIEWER: tlw-oJK, ~ Lv.JIJ'DATE qhfffl?.. Authorized Inspection Agency c:Za::a, ~.,,,..;" DATE ¢°-60-&c>U Lv:JiL REVIEWER: DATE: '-l..,;le;-/~ Page 3 of 18
ATTACHMENT 2 Braidwood Station Unit 1 n Third ISi Interval Limite~verage NDE Reports -~.W.i,;~.~ync Calibration Data Sheet l, \\*;.qi11Qt.. ~....... El*ctrir; c.. m p<lTIY Plant I Unit Braidwood 11 Data Sheet# A1R16-025 1 h" Company Exelon Page 2 of 4 N tch Comp I System FW#8A I SI Procedure No. EXE-PDl-UT-2 Cal. Checks Time Rev I Chng. No. 710 Cal. Block No. 22572 Initial Calib. 10:06 Cal. Block Temp. 72°F Thermometer SIN: SAP 106886 Initial Calib. Date 0411612012 Size 4.. Sch. 160 I 0.531" "T" Ref. Block: I Intermediate NIA I D Ferritic [!] Austenilic NIA Search Unit #1 Each Major CRT Div. = 0.17" Intermediate NIA Manufacture: KBA Serial No.: ommm:s Cal. Direction: DAxia1 D Circ. [!] Both Final Calib. No. of Elements: 1 12:08 Size: 0.25" Shape: Round Scan Area: __L_toWeld EH 0411612012 Freq. 2.25 MHz Style: CompG II to Weld Final Calib. Date Exam Angle: 45° Mode: Shear Couplant Measured Ang~ 43°. Code Category: R-A Code Item: R120 Type: Ultragel II Wedge Style: MSWQC rs1 we-1ol Batch: 09225 Search Unit Cable t sr-S7-o8A. INDICATIONS EXAM ACCESS FLAW NON RELEVANT SENS. Type: RG-174 Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) Length: 6' No. of Con.: 0 FW#SA 1 Sided x x 40.7 Instrument Settings Remarks I Reason for lncomglete Scan(s) COMPONENT TEMP:63_°F Increased exam volume due to RI-ISi requirements. See attached coverage plot. 50% Make I Model: GEIT USN 60 SW Code coverage achieved due to one side exam. Serial No.: SAP 105204 Probe Delay: 4.0300 Range:
- 1. 7" M'tl Cal I Vel: 0.1234 Pulser:
Square Damping: soo-Reject: 0% PRF: Auto High Freq: 2.25 MHz Filler: Fixed Mode: Dual Off Examiners: Joseph Se~,/_, Rectify: Fullwave Voltage: 450 Level II Date 04/16/2012 Pulse Width: 220 ns --- Jason J. J~ing°'S'-'-__,.... - ~lllll II Date 04/16/2012 Display Delay: 0 CJ.1,,.,.I. k.~ L., l llt / [j t/n Reference Sensitivity (dB) WesDyne Reviewer I Date: Axial: 28.7 dB Circ: 28.7 dB ~ation Required? Yes [!]No FSDH Sensitivit}t: NIA EXELOtJ LEVEL Ill REVIEW I DA TE _.,,., --, t'\\ * ('\\ ANll REVIEW I DA TE /'/,,-/ _...,_~ _/?, "m" ""-\\'\\*\\"t. 'l.J ~,,.__ Page 4 of 18 {\\ \\ \\ \\ \\ \\
- ~ s.. ~" """.,
Manufac Serial No No. of Eleme\\s. Size* Shape Freq. \\ Style: Exam Angle: ciTe\\-- Mode: Measured Angle: Wedge Style: \\ Search nit Cable N A Type: Length: No. f Con.: Instrument S ttings Make I Model: Serial No.: \\ Probe Delay: Range. M'tl Cal I Vel: Pulser: Damping: Reject: \\ PRF: Freq: \\ Filter: Mode: \\ Rectify: Voltage : ~ Pulse Width: Display Delay: Reference Sensitivity (dB) Axial: Circ: FSDH Sensitivity: \\ /¥-..iv-~/2
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports "'\\,-~~-~~~~~~-~~~~~~~--r* ".---~~~~~-~~~~~~~~~~~~,,-{ *
- ~~
- 025 it Plant/Unit :
Braidwood / 1 Comp I System FW#8A I SI Iso. Drwg: 1$1-39 .r..sr vJcid Weld I Component ID Number: FW#8A ISI-3'1-0BA \\/Veld
- Weld Edge Centerline I*
2.s - .. 1.. 2.s-
- I t-'OSIUOn u
l1U IOU .J!IU Isl 1 I'~" m 0 m 14-1 16-1 m ~ ~ Crown Height: Flush 2 I"" --\\' ~ ~ ( Toa I Toa 0.80" 3 ll~r< ) I Cro,,11 Width: 4 I"'" I Up St1Wern (-) Side 5 0.64" Oovvn St1-oam (+) Side Diameter: 4.0" 6 0.56" 0.53" I 14.25" 7 FLOW Weld Length: 8 0.53" 9 0.52" Valve Pipe Component Component 1 I rt
- 1.
i !l ~. ~ .:r (f ~C \\ ~ \\.. Vf. ~ \\>.::;.? E
- -\\
. }.,,), ct.. ~-
- -tt.r *.
u~c qss~tt:
- - ~
J. .l * \\ J,p \\ /~?I'/ .,./'/ ~/~ - - "\\ / l/~ '.r-it.{__ ~. ~
- ~ *u _ _ _
COMMENTS: /.l EXA.i\\.11NER: ~,,.,- ~ .J Lv. II DATE 4/16/2012 EXAMINER:
- _;--=-~-*
~ Lv. II DATE: 4/16/2012 mt JaseEh serth Print Jason J. Jennings REVIEWER ~ P, ~ Lv. 'nr'DA TE 't/ ~ '/ 17-. REVTEWER: A-t'-- Q 71_. Lv. F DA TE:~ -20 *IC:. I Authorized Inspection Agency ~;b;z_~ DATE q. ;(o *.,7,t>/2:, Page 5 of 18
ATTACHMENT 2 Braidwood Station Unit 1 \\...J Third ISi Interval Limited-coverage NDE Reports u ~ ! .W..~~pync Calibration Data Sheet A \\\\"tt ~ti.i9 h~)u :.,.- Elr.c tnc C.o m11.. 11y Plant I Unit Company Comp I System Procedure No. Rev I Chng. No. Cal. Block No. Cal. Block Temp. Thermometer SIN: Size 4" Sch. Ref. Block: SAPN/A D Each Major CRT Div.= Braidwood I 1 Exelon FW#25 I SI EXE-PDl-UT-2 710 SAP 105091 63°F SAP 106886 160 I 0.531" "T" ~~~~~~~~~ Ferritic [!] Austenitic 0.2" Cal. Direction: Scan Area: (!]Axial D Circ. O Both _j__ to Weld (!] II toWeld D Data Sheet# Page _...,.$,__ __ Cal. Checks Initial Calib. Initial Calib. Date Intermediate Intermediate Final Calib. Final Calib. Date A1R16-029 of 8 Time 11 :30 411612012 NIA NIA 12:10 411612012 Couplant Code Category: _.B+/- Code Item: R120 Type: Ultragel II --- Batch: 09225 INDICATIONS EXAM .r:sr wc1d \\SL-3Cf-z.:;- ACCESS FLAW NON RELEVANT SENS. Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) FW#25 1 Sided x x 66 Remarks I Reason for Incomplete Scan(s) COMPONENT TEMP:__fil°F 50% Code coverage achieved due to one side exam. 60°RL did not see any indications in the area of the flaw. Scanning was limited due to lift off at weld area.
*/
v Examiners: Jo~h Sertil--~.. Level II Date 4/16/2012 Jason J. ~vel Ii Date 4/16/2012 WesDyneReviewer/Date: ~ K, ~ Lv/111' l.//z,/rz.. Furthe,.,. valuation Required? 0Yes DNo EXELON LEVEL 111 REVIEW I DATE In A* r.... Search Unit #2 Manufacture: RTD Serial No.: 08-375 No. of Elements: 2 Size: 2(7x10) Shape Reel. Freq. 2.o MHz Style: TRI:::A-2" Exam Angle: 60° Mode: Long Measured Ang~ 58_0 __ Wedge Style: Integral Search Unit Cable Type: RG-174 Length: 6' No. of Con.: 0 Instrument Settings Make I Model: GEIT USN 60 SW Serial No.: SAP 105204 Probe Delay: 8.01 Range: 2.0" M'tl Cal I Vel: 0.2270 Pulser: square-- Damping: ~Reject: 0% PRF: Auto High Freq: 2.0 MHz Filter: Fixed Mode: Dual On Rectify: Fullwave Voltage: 450 Pulse Width: 250 ns Display Delay: o Reference Sensitivity (dB) Axial: 66.0 dB Gire: NIA NSDH Sensitivity: NIA u \\1 I I I I I I I I I I I\\ \\ ' I\\ \\ Search Unit #2 Size: Freq. Exam ng e: Measured Angle:\\--------- Wedge Style: Search 'µnit Cable N\\A Type: Length: No.'Clf Con.: Instrument Settings Make I Model: ____ -+------ Serial No.: Probe Delay: M'tl Cal I Vel: Range* Pulser: Damping: Reject:-+---- PRF: Freq: Filter: Mode: Rectify: Voltag_e_: --...--- Pulse Width: Display Delay: Reference Sensitivity (dB) Axial: Circ: NSDH Sensitivity: \\,
- (J( ):nr '-\\*l-1-rt ANllREVIEW/r~
....:t\\"'V'\\. \\,._... fl.*hn1f\\U..-~Q.. 1of e ~...U;*k.,,.4-J t1J&... /"J,11* ~... o;.ii**l.. Page 6 of 18
) {SI We.Id I S.t-3q~z.q Component Number: Indication Number: ASME Table Utilized: . ASME Code Class: ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports Nuclear ATTACHMENT 3 ASME Planar Flaw Evaluation Form p 1 f 2 aqe 0 FW-25 Exam Report #: A 1 R16-029
- 1 I lt3 Flaw Type:
D Surface l8l IWB-3514-2 Examination Type: D lnservice l8l D Class 1 ASME Section XI Code Year: 2001 I 2003 Addenda l8l Class 2 Acceptable: l8l Yes D No Rounding off of values shall be performed as follows: ER-AA-335-010 Revision 2 Page 13 of 21 Subsurface Preservice Express "a", "I", t", Min Depth and Max Depth per paragraph 4.1.1 I Allowable Flaw% to paragraph 4.1.3 "d", "2d", "0.4d", "S", "a/I", "alt", "Y" per paragraph 4.1.2 "t" 0.65 l8l UT Thickness at location excluding cladding D Nominal Wall Thickness "I" 1.0 (Flaw length) Min Depth: 0.40 x = ~ Max Depth: 0.50 x = 0.48" D 1*1 Leg Sound Path x Cos Angle= Depth D 2nc1 Leg 2t(Sound Path x Cos Angle)= Depth D Plotted from cross sectional sketch 181 Thru Wall Sizing D Transducer Resolution - Reference note prior to 4.1.1 "S" 0.15 0.65 0.50 = 0.15 = " S" Minimum Flaw Distance to closest component surface = "S" "2d" 0.10 0.50 0.40 = 0.10 = "2d" Max Depth minus Min Depth= "2d" "0.4d" 0.02 0.10 I 2 = 0.05 x 0.4 = 0.02 = "0.4d" (2d I 2) 0.4 = "0.4d" Flaw Type: l8l " Subsurface" if S~ 0.4d D "Surface" if S<0.4d, a=2d plus S "d" 0.05 0.10 I 2 = 0.05 = "d" " 2d" divided by 2 = "d" "a" 0.05 " a" equals "d" for subsurface or "2d" plus "S" for surface "Y" 1.0 Shall not exceed 1.00 "S" /"a" = " Y" 0.10 I 0.05 = 2.0 = "Y" " Y" functions to reduce the allowable flaw size as the distance to the surface decreases "all" 0.05 Shall Not Exceed 0.50 0.05 I 1.0 = 0.05 "a/t" I 7.7% I Actual Flaw % 0.05 I 0.65 = 0.077 x 100 I 8.6% I Allowable Flaw % Linear Interpolation Performed: D Yes l8l No See Attached Work Sheet: D Yes l8l No Comments: Indication #1 & #3 are the same indications. Linear interpolation was not performed. The a/I of 0.05 has an alt of 9.6Y for a thickness of 0.312" and 8.6Y for a thickness of 1.0" The actual alt of 7.7% is less than the conservative value of 8.6%. Preparer: Jav Miller A~ JI\\* 0 U Date: 04121112 Reviewer: ~* }'.'7~0d~ L. -t,..1-e, ( Date: "l zdr2-ANll: ~ l-..<. Date: 4\\ "1-1 \\,.,__ I Page 7 of 18
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports ~ ~ \\ \\. /
- Pa
.w~~.. ~vn= ULTRASONIC EXAMI~TION SKETCH SHEET
- .. 'f"I*~.. t 1~*~>h
- :1o*:.:J ;s:-:.:-fri:: ;,.:.,,: :::;:.* '*:*
Plant/Unit: lso. Drwg: Braidwood I 1 Comp I System FW # 25 I SI Weld I Component ID Number: COMMENTS: Crown Height: Crown Width: Flush 0.80" Diameter: I 4.0" Weld Length: 14.25" 1Sl-39 ISI Wdd Fw#2s / sr-sq-z.s Fos1t1on u !iU H:lU LfU 1 0.f ::t 2 ll.rn Toe 3 10./ti 4 I0.1~ 5 NR Up S tr**tn {* ) Side 6 NR 7 NR 8 NR 9 NR Elbow Componont I.. \\ f' ELG Ow __.t:-........ \\ftr\\.YE ~ -- \\_~, ~\\I I Lv. II DATE 4116/2012 VVeld FLOVV -<?.,. ~--.. EXAMINE~ Print J<*~vu *. *~*uu;*p~ REVIEWER: ~ ./-.~ Lv.fl/ DATE., -***..... REVIEWER: v- ~ DATE Page 8 of 18 4\\ "1-\\.\\,._.. . \\ Data Pkg.#: A1Uo29 Paae 8 of 8
- W old Edgo D o-n S tr*Mrn ( -+) S ide#
Valve Compon!!iii Lv. II DATi:: 4/ 16/20 12 Lv. DATE: '-f. Zl*IZ.
ATTACHMENT 2 Braidwood Station Unit 1 ("\\ Third ISi Interval Limite~erage NDE Reports ~ .W.~~.~yn~ Calibration Data Sheet ~ \\ \\*.. ~tin a h..,,,,.,.. El<><.:rir. C nn' 1~n v Plant I Unit Braidwood I 1 Data Sheet# A1R16-027 1 ~" Company Exelon Page 2 of 4 N tch Comp I System FW#25A/ SI Procedure No. EXE-PDl-UT-2 Cal. Checks Time Rev I Chng. No. 710 Cal. Block No. 22572 Initial Calib. 10:06 Cal. Block Temp. 72°F Thermometer SIN: SAP 106886 Initial Calib. Date 04/16/2012 Size 4" Sch. 160 I 0.531 " T" Ref. Block: I lntenmediate N/A N/A I D Ferritic [!) Austenitic Search Unit #1 Each Major CRT Div. = 0.17" Intermediate N/A Manufacture: KBA Serial No.: OMRO!' Cal. Direction: OAxial D Gire. [!) Both Final Calib. 12:08 No. of Elements: 1 Size: 0.25" Shape: Round Scan Area: _j_toWeld fE Final Calib. Date 04/16/2012 Freq. 2.25 MHz Style: CompG II to Weld Exam Angle: 45° Mode: Shear Couplant Measured Ang~ 43° Code Category: R-A Code Item: R120 Type: Ultragel II Wedge Style: MSWQC rsr we.iei Batch: 09225 Search Unit Cable \\ sr:-.3°r-l5A INDICATIONS EXAM ACCESS FLAW NON RELEVANT SENS. Type: RG-174 Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) Length: 6' No. of Con.: 0 FW# 25A 1 Sided x x 40.7 Instrument Settings Remarks I Reason for lncomQlete Scan(s) COMPONENT TEMP:63_ °F Increased exam volume due to RI-ISi requirements. See attached coverage plot. 50% Make I Model: GEIT USN 60 SW Code coverage achieved due to one side exam. Serial No.: SAP 105204 Probe Delay: 4.0300 Range: 1.7" M'tl Cal I Vel: 0.1234 Pulser: Square Damping: ~ Reject: 0% PRF: Auto High Freq: 2.25 MHz Filter: Fixed Mode: Dual Off Examiners: Josepfl.?ert~~ ~ Rectify: Fullwave Voltage: ~ Level II Date 04/16/2012 Pulse Width: 220 ns Jason J. J~~~el~ 11 Date 04/16/2012 Display Delay: 0 ~ X.~ ~'r.Lm-I "/11/n Reference Sensitivity (dB) WesDyne Reviewer I Date: Axial: 28.7 dB Circ: 28.7 dB urthe:_ Evaluation Required? DYes [~}o FSDH Sensitivity: N/A ~. \\ I \\ \\ \\ \\
- ~ s"" un;l#2 Manufact Serial No No. of Eleme ts:
Size: Shape Freq. \\ Style: Exam Angle: gie\\-- Mode: Measured Angle: Wedge Style: \\ Search nit Cable N A Type: Length: No. Con.: Instrument S ttings Make I Model: Serial No.: \\ Probe Delay: Range. M'tl Cal I Vel: Pulser: Damping: Reject: \\ PRF: Freq: \\ Filter: Mode: \\ Rectify: Voltage: -\\--- Pulse Width: Display Delay: \\ Reference Sensitivity (dB) Axial: Circ: FSDH Sensitivity: \\ EXELON LEVEL Ill REVIEW I DATE A--i 1A'.' () ') ~ ~-IG.-\\?- ANll REVIEW I DA Ta /7 * / 'f/,,Ao- ~a '_/ "74," Page 9 of 18
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports (
- ~ ~
.W~~'~ync ULTRASONIC EXAMl~ATION SKETCH SHEET Data Pkg. #: Alk.10-027
- ~ '.~*J.~, t i~*~J! Y.*C**;Y ; J
- *c.hk Z':*n:i : :.:**~~*
Paae 4 of 4 Plant/Unit : Braidwood I 1 Comp I System FW # 25A I SI Iso. Drwg: 1Sl-39 I sr IAf-c ld Centerline FW#25A I sr-~-lSA \\/Veld
- Weld Edge Weld I Component ID Number:
Pos1t1on 0 90 180 270 2.s* 2.s-
- I 1
mm 0@:1~ ~-*-*-,.,._ ~ 2 3 4 5 6 0.57" Crown Height: Flush Crown Width: 0.85" Diameter: 4.0" 7 0.53" 8 U.53" Weld Length: I_ 14.25" 9 0.52" ,.,~-1 ..l.S!: Valve Component -l::.::.~:cs-v ?-...t.. vt;_ I FLOVV p ' ? r:. (..\\.- (,t> '~~~ t"'i .>t ' f------~~t COMMENTS: ~ // EXAM!Nl~~- ~ Lv. II DATE \\ .,,./ / / ~.,,.. ,,.~ !:'.,,.--~~ r': ~-----~-~~~*
- ~/~---~~~=
4/16/2012 EXAMINER: ~ Lv. II Pipe Component DATE: 4/ 16/2012 ~ ~rth Print Jason J. Jennings REVIEWER: ~.!. ?..J4._ Lv.II( DATE "l/z,/t-z REV1EWER: .c4=='\\ ~ Lv. -::m:- DATE: l.(*?o--n.. I ~ ~ 1 Authorized Inspection AgencyL ~: DATE 9:M*2il"/12.. Page 10 of 18
("\\ ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limit~overage NDE Reports {\\ ""1.Wi;~_~ynie Calibration Data Sheet Plant I u~~;--,;"""""'
- El><> <ic Cnm;n;:idwood I 1 Data Sheet#
A1R16-099 n A ~- \\ Company Exelon Page 3 of 4 1----+---11---+--+----1--+--+----1--1 Comp I System FW #25B I SI 1t--+----11---+--+----1-+--+----1-+--1 Procedure No. EXE-PDl-UT-2 C I Ch k r* \\ Rev I Chng. No. 7 / a* a
- ec s 1me t-1'-t\\-+--+---+-t---+---+-t-----i Cal. Block No.
22572 I *t* IC l'b
- 16. 16
\\ Cal. Block Temp. 7 4 °F rn *a a 1
- 1----+---11---+--+----1-+--+----1--1 Thermometer SIN:
SAP 106886 \\ Size 4.. Sch. 160 10_531.. "T" Initial Cahb. Date 412912012 t---t-'r\\-+---+-t---t--+---+-t---+--1 Ref. Block: I .~ SAP 103552 1. _D Ferritic [!] ~ustenitic Intermediate 17:55 . Search Unit #2 Search Unit #2 Each Maior CRT Div. - 0.2 1 t
- d. t NIA Manufacture.
RTD Manufact n erme ia e Serial No.: 08-375 Serial No Cal. Direction: 0Axial D Circ. D Both No. of Elements: L No. of Eleme1.t,...s-: -------- Final Cahb. 18:35 Size: 2(7x10) Shape Rect. Size: ...,.s.,.h_a_p_e ___ _ Scan Area: _[_to Weld 0 F. I C I' 2 Freq. 2.0 MHz Style: TRCA-2 Freq. \\ Style: 11 to Weld D ma a ib. Date 41291201 Exam Angle: 60° Mode: Long Exam Angie: __l__ Mode: Couplant Measured Angle: 58° Measured Ang~ Code Category: R-A Code Item: R01.20 Type:
- Ultragel II Wedge Style:
Integral Wedge Style: 1--,------- Batch: 09225 I sr-s~ -2 $ Search Unit Cable Search nit Cable INDICATIONS EXAM N A ACCESS FLAW NON RELEVANT SENS. Type: RG-174 Type: -----,,........+->-=----- Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) Length: 6' No. of Con.: __ O_ Length: No. 1 ~on FW#25B*I 1Sided X X 58 Instrument Settings Instrument S ttmgs Remarks I Reason for Incomplete Scan(s} COMPONENT TEMP: 76°F 60°RL utilized for one sided exam. 50% Code coverage achieved due to single sided Make I Model: GEIT USN 60 SW Make I Model: ____ --+---- exam. Serial No.: SAP 105204 Serial No.: \\ Probe Delay: 8.01 Range: 2.0" Probe Delay: Range M'tl Cal I Vel: 0.2270 Pulser: square-M'tl Cal I Vel: --- Pulser: Damping: ~Reject: 0% Damping: --- Reject: \\ PRF: Auto High Freq: 2.0 MHz PRF: Freq: -+\\--- Filter: Fixed Mode: Dual On Filter: Mode: _._.,_ \\ __ ~ .J ,,,,/ Rectify: Fullwave Voltage: 450 Rectify: Voltage: _l____ Examiners: Joseph Serth<:::_/,.... a Level II Date 412912012 Pulse Width: 250 ns Pulse Width: ~ NIA ./' ~ Level NIA Date NIA Display Delay: 0 Display Delay: \\ '¥A. J I> ??JJL L /""' IJ/ ~~ 7/~ Re_ference Sensitivity (d.B) Reforence Sensitivity (d_B) WesDyne Reviewer I Date: ~ f, ~ V ~ ""f/ ~ /I '-... Axial: 66.0 dB C1rc: NIA Axial: Gire: Further Evaluation Required? DYes [!)No NSOH Sensitivity:3.2div@80%@58.0dB NSDH Sensitivity: \\ EXELON LEVEL Ill REVIEW I OATE (\\ ANll REVIEW I DATE./7 ~ /") /. .A-~ n v-m:. M-~o*rz.. r~/. '"""'.r~,, /~Jo.~;i,., Page 11 of 18
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports r ( \\ r \\
- ~a: *~-~~-~ync ULTRASONIC EXAl\\'IINrtfION SKETCH SHEET Data Pkg. #: AIR... -099 Paae 4
of 4 Plant/Unit : Braidwood/ 1 Comp I System FW # 25EH SI Iso. Dnvg: 1 Sl-39 c::t ~.,..,, I SJ: Wei 0 . w o1d E d g o Weld I Component ID Number: FW#258 I St.-3<1-250 ce~=~~ne t"'OSIUOn v '1V 1ov .!.IV I
- 2.s -
- .-1,*
2.s -
- I u...,
CD m m f4"l 1 5 1 wi m ~ 0 Crown Height: Flush 2 u.:it /. Toe_,.,,,,\\ i -..._T~ } 90" 3 0.:J( I Crown Width:
- 0.
4 .0.54** I 5 0.56" Up Stroa"1 (-) Sid* I Dovvn Stroorn ( + ) S ichl Diameter: 4.0" 6 o.63" 1--........:;7---+--N"" 'R-+---+---+--~ F~OIN Weld Length: 14.25" 8 NR i----=g-----r.cN'"' ' R,.---t----t--~---1 Pipe Valve Component Component pt P E v;*~ L vF, ~" '4 \\.-- 4,ol\\t- .. ~- ~.. c
- ..,'i j
<, ~** h. i j T . :§.. ' '"' ~
- ~/- _. ~ -
l ' ~ 4 - ~*- ** \\..,...,,..... !f..lt... ----~-~- COMMENTS: _T_a_ke_n_a_t_0_ 0 _S_ta_m_._p. _______________________________________ --1 EXAMINER-..//.. //"d._ Lv. fl DATE 4/29/2012 EXAMINER: NIA Lv. N/A DATE: N/A ~n~ ~ Print REVIEWER: ~}?. ~ Lv'llr DATE t.//,!o /ii; REVIEWER: A- (\\." 0 0 Lv..J!L DATE: Lf*30*1'2> Authorized Inspection Agency
- ~
~-- DATE ~ c5a -,Zo/;?... Page 12 of 18
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports ,,E;;7 IEX 1t: tUOHllL UT Calibratior, 1amination Site/Unit: BRW Procedure: EXE-PDl-UT-1 Summary No.: 1CV109-4/FW-1 Procedure Rev.: 7 Workscope: PSI Work Order No.: 01692235-31 Code: ASME 2001 Edition/ 2003 Addenda Cat./ltem: NIA Location: Outage No.: N/A Report No.: UT-A1R18-017 Page: of 4 CV Room Drawing No.: FX-12
== Description:== ..:V:..:a:.:lv.:.e:*..:.P..:.i::.p.:.e __________________________________ _ System ID: CV
:::-:-~-::::------:-:::-:--:-::--
Component ID: 1CV109-4/FW-1 Size/Length: 4" Thickness/Diameter: 0.53" / 4" Limitations: Single sided exam due to valve configuration. Start Time: 1800 Finish Time: 1840 Instrument Settings Search Unit Cal. Axial Orientated Search Unit Time Date Serial No.: SAP 105421 Serial No.: 009J59 Checks Calibration Signal Sweep Sound Path Manufacturer: GEIT Manufacturer: KB-Aerotech Initial Cal. 1730 4/10/2015 Reflector Amplitude% Division Model: USN SO SW Linearity: A1R18-L-003 Size: Model: Comp-G Inter. Cal. 1805 4/10/2015 1.O" ID Notch 80% 9.3 1.38" 0.25" Delay: Range: 1.5" Inter. Cal. N/A 4.6203 Freq.: 2.25 MHz Center Freq.: NIA Inter. Cal. NIA M'tl CalNel: 0.1241 Pulser Type: Square Exam Angle: 45° Squint Angle: NIA Final Cal. 1900 4110/2015 Damping: 500 Ohms Reject: 0% Measured Angle: 44° Mode: Shear PRF: Auto High SU Freq.: 2.25 MHz Couplant Exit Point 0.25"
- of Elements:
1 -- Cal. Batch: 13M026 Circumferential Orientated Search Unit Frequency: 2.25 MHz Rectify: Fullwave Config.: Single Focus: NIA Type: Ultragel II Calibration Signal Sweep Sound Path Voltage: 450 Pulse Width: 220 Shape: Round Contour: NIA Reflector Amplitude % Division Mfg.: Sonotech Wedge Style: MSW QC Exam Batch: 13M026 NIA NIA NIA N/A Ax. Gain (dB): 24.5 Gire. Gain (dB): NIA Search Unit Cable Type: Ultragel II 1 Screen Div. = 0.15 in. of Sound Path Type: RG-174 Length: 6' No. Conn.: 0 Mfg.: Sonotech Calibration Block Scan Coverage Upstream O Downstream~ Scan dB: ~ Reference Block Reference/Simulator Block Cal. Block No. 22572 Gain Signal Sweep Thickness 0.5" to 2.0" Dia.: 0 cw~ CCW ~ Scan dB: 36.5 Serial No.: SAP 103552 SS dB Reflector Amplitude "lo Division Sound Path Cal. Blk. Temp. 10* Temp. Tool: SAP 30015737 Exam Surface: OD -- Type: 1" Angle Beam 24.5 NSDH 47% 2.9 0.43" Comp. Temp. 76° Temp. Tool: SAP 30015737 Surface Condition: Ground Smooth Recordable lndication(s): Yes n No I.II (If Yes Ref. Attached Ultrasonic Indication Report.) Results: Accept~ Reject O Info O Comments: NRI. Scan speed reduced to maintain contact on branch. Percent Of Coverage Obtained > 90%: 50% Examiner Lev~I 11-PD~ Michael, Dickey ~ Examiner NIA Other Level NIA NIA Reviewed Previous Data: NIA Signature Date I Reviewer 4/10/2015 James Delbusso, Level Ill Signature Date I Site Review Signature Date L-= ~ ~.*.-t-iJ\\ t-1 Page 13 of 18 Omr. Signature Date 4/10/2015 Date '-HI-IS-Date 4-\\\\-\\ ~
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports
- " Exelon,,
Summary No.: 1CV109-4/FW-1 Sketch or Photo: Vo.Ive oo Supplemental Report Coverq5e Pio-+ FVJ-1 £. f.o6 Rl.. \\_I '(oLj /.p II I ~:'JS Lj:>O , s-*~ea .s-~~" i.AtJ a, lolt. 4-o ~e.i C.orv~au,, G~v..se i r.J 4-ee. b r<Mi<;.>. Cie.s+ E.,.+;,,"ic_,of" £ f_o~tot.r..!- Covero.'S~ '-/ ,(p4q I si" Page 14 of 18 Tee. Report No.: UT-A1 R18-017 Page: 4 of 4
Summary No.: 1-803.110.0015 ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports Supplemental Report Report No.: A1R19-UT-023 Page: 4 of 5 Examiner: Steinbauer, Tr~4evel : 11-PDI NIA Level: NIA Reviewer: Delbusso, James Level Ill ate: 913012016 Examiner: Site Review: Other: NIA Level: NIA ANll Review: Comments: 1PZR-01-N1 NOTE: Axial scans limited to a "w" dimension of 6.0" from nozzle taper for 66" (290°) due to proximity of heater penetration tubes. Scans were not limited for 16" (70°). Total Weld Volume: 1305.85 in' (Volume obtained from Report# A1R13-UT-015). UPST Coverage Missed: 270.2 in' Coverage Achieved: 79.3% 1305.85 in' - 270.2 in'= 1035.65 in' 1035.65 in'l1305.85 in'= 0.793 0.793 x 100 = 79.3% DNST Coverage Missed: 711.76 in* Coverage Achieved: 45.5% 1305.85 in' - 711.76 in'= 594.09 in' 594.09 in' 11305.85 in' = 0.455 0.455 x 100 = 45.5% cw Coverage Missed: 169.74 in' Coverage Achieved: 87.0% 1305.85 in' -169.74 in*= 1136.11 in' 1136.11in'11305.85 in'= 0.870 0.870 x 100 = 87.0% ccw Coverage Missed: 169.74 in' Coverage Achieved: 87.0% 1305.85 in* -169.74 in* = 1136.11 in* 1136.11 in' 11305.85 in* = 0.870 0.870 x 100 = 87.0% TOTAL COVERAGE (79.3 + 45.5 + 87.0 + 87.0) 14 = 74.7% Page 15 of 18
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports r.:::> ~ c.d.A r'~ t...... - l~"'"""-:... v ~ ~ *:- Supplemental Report Report No.: A1R19-UT-023 p z;;;:;:::;:*:** Page: 5 of 5 Summary No. : 1-803.110.0015 Examiner: Steinbauer, T~ Examiner: ~N~l~A..:_ _______________ _ Site Review: Level: 11-PDI Level: NIA Reviewer: Other: _;N~l'.!:A:-._ _____________ _ Level: NIA t T ANll Review: 1b4. ttktf.Mt @~- Date: 913012016 Date: ;o U Date: /()-()1.. ~I~ Comments: 1PZR-01-N1 T & C taken from previous Report# A1R13-UT-015 1-PZll.*OI* NI Sketch or Photo: ~012..1.~ ~s* ~ ] w.4." l Page 16 of 18 'IS"' vr 1 \\ \\ ..,..II, Pt1"'7'4A'T101.J TcJ(S.l:.!t. ~ ,..~J<J.t..N~~~ Ai.I.JD C.OIJ'1'"0t>fl 'TJ;K,S:~ J=R.O,., PR.1:.\\/1cu...) p4rA. fUPolf."r d ~ A'"" ~ tlT # 0 15 Dit-rf:.P JO
- l"i
- 01 WU,0 L~N'6r)./ : f:J;.0"
-'".+" You.,.,1:. "oo/: 'I.,,. (,JS..&.D *f')UC.k""t-S ; 'J.~S ** ..,.".,..~~..,.,t.o ""°'"Ui't~: 1'!i.os.t5,.... 1
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports Supplemental Report Summary No.: ~~~~~~----,,,,.--...:._--;o~:-.:;.-.::.._ Examiner: Examiner: NIA Other: NIA Comments: 1PZR-01-N4A 0° - Scan 100% volume. 45° - Scanned in all four directions. 60° - Scanned upstream. Total Weld Area: (3.3 + 2.7) / 2 = 3.0 3.0 x 4.5 = 13.5 in*. UPST Coverage Missed: 0.63 in2 Coverage Achieved: 95.3% 11-PDI Level: N/A Level: N/A Reviewer: 13.5 in2 - 0.63 in2 = 12.87 in2 12.87 in2 / 13.5 in2 = 0.953 in2 0.953 x 100 = 95.3% DNST Coverage Missed: 8.35 in2 '.:overage Achieved: 38.1% 13.5 in2 - 8.35 in2 = 5.15 in2 5.15in 2 /13.5 in2 = 0.381 in2 0.381x100 = 38.1% cw Coverage Missed: 3.96 in2 Coverage Achieved: 70.6% 13.5 in2 - 3.96 in2 = 9.54 in2 9.54 in2 / 13.5 in2 = 0.706 ln2 0.706 x 100 = 70.6% ccw Coverage Missed: 3.96 in* Coverage Achieved : 70.6% 13.5 in2 - 3.96 in2 = 9.54 in2 9.54 in2 / 13.5 in2 = 0.706 in2 0.706 x 100 = 70.6% TOTAL COVERAGE (95.3 + 38.1 + 70.6 + 70.6) / 4 = 68.7% Page 17 of 18 Report No.: A1R19-UT-024 Page: 4 of 5 te: 9/30/2016 1.:./0~1~/Jc Date: t~*o1 *Ml4z
ATTACHMENT 2 Braidwood Station Unit 1 Third ISi Interval Limited Coverage NDE Reports _;;~~):::/ E.
- ~c: to r1._
Supplemental Report Summary No.: 1-803.110.0013 ~ Examiner: Steinbauer, Troy~ Level: 11-PDI Reviewer: Examiner: NIA ~ Level: N/A Site Review: Other: N/A Level: N/A ANI I Review: Comments: 1PZR-01-N4A T & C taken from previous Report# A1R12-UT-081. a,JOl.'t..i..'C Sketch or Photo I PZR*Ol-N'r'A
- 1~
~ 7 ~"'-... I. I I I I 'l.s""'-- -------- 45"? Page 18 of 18 Report No.: Page: A1R19-UT-024 5 of 5 Date: 9/30/2016 Date: le(c.c., b.a!-t Date: ID. OJ *J.,(J/(,,
- r>1 i c1'/.Jfl.-'~
AuO c.o"'roc.1A r*.u-~.FitOI'\\ PU\\/JCl'tl..S OATA. HP*R1° d : _AIR l').*uT-Olt'I 01tnt> O<l/21/ 0" {~ t'ZR lltAC
ATTACHMENT 3 Braidwood Station Unit 2 Third Inservice Inspection (ISi) Interval Limited Coverage Non-Destructive Examination (NDE) Reports Page 1 of34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~.w.~~~yn~ Calibration Data Sheet A Wos.tlnghous.o Uoctric Comp.-my Plant I Unit Braidwood I 2 Data Sheet# A2R16-UT-004 1-. Company Exelon Page 3 of 4 Comp I System SW# 11 /SI Procedure No. EXE-PDl-UT-2 ~~ Rev I Chng. No. 071 None Cal. Checks Time Cal. Block No. 22572 Initial Calib. 1315 Cal. Block Temp. 73°F Thermometer SIN: SAP 106898 Initial Calib. Date 10115/2012 Size 4" Sch. 160 I 0.531" "T' Ref. Block: I SAP 103772 I D Ferritic ~Austenitic Intermediate 1810 Search Unit #1 Each Major CRT Div. =
- 0. II Intermediate N/A Manufacture:
RTD Serial No.: CS-:375 Cal. Direction: OAxial D Gire. [!) Both No. of Elements: 2 Final Calib. 1940 Size: 2 (7 x 10) Shape: Rect Scan Area: _J_toWeld Ej Freq. 2.0 MHz Style: TRLA II to Weld Final Calib. Date 10/15/2012 Exam Angle: 60° Mode: [ong Couplant Measured Ang~ 60° Code Category: R-A Code Item: R1.20 Type: Ultragel II Wedge Style: Integral Batch: 11625 Search Unit Cable I.SL We..lol 2. SI-39-/ f INDICATIONS EXAM ACCESS FLAW NON RELEVANT SENS. Type: RG-174 Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) Length: 6' No. of Con.: 0 Single 2SI08CA-4" I SW# 11 Sided x x 61.S Instrument Settings Remarks I Reason for lncomglete Scan{s) COMPONENT TEMP:_l§°F Supplemental 60° RL examination due to single side access. Increased exam Make I Model: GEIT USN 60 SW volume due to RI-ISi requirements, see attached coverage plot. Root geometry Serial No.: SAP 105203 observed intermittent 360° below recordable levels. No recordable indications. Probe Delay: 7.8778 Range: 3.0" 50% code coverage achieved due to one sided exam. M'tl Cal I Vel: 0.2285 Pulser: Square Damping: ~ Reject: 0% PRF: Auto High Freq: 2.0 MHz Filter: Fixed Mode: Dual On ---=- Rectify: Fullwave Voltage: 450 Examiners: Jason J. Jennings Level II Date 10/15/2012 Pulse Width: 250 ns -- NIA Level N7A Date NIA Display Delay: 0.00 WesDyne Reviewer I Date: -U-4 & r4f:.: 4.g l'c:l-,,_ l:J-Reference Sensitivity (dB) Axial: 61.5 dB Circ: 61.5 dB Further E).aluation Required? Oves (!]No FSDH Sensitivity: 4.8div@70%@55.5dB EXELON LEVEL 111 REVIEW I DATE ./1__... \\r....
- n U_ Iii 10- ~*-rz.
NII REVIEW I DATE /2_./_ _,_n _ /1 ~.,,/,_..__.,.. Page 2 of 34 l}JO# /Lf 50738-0I \\ \\ \\ \\ \\ \\
- ~
Sea<eh Unlt#2 Manufact Serial No No. of Eleme\\s: Size: Shape Freq. \\ Style: Exam Angle: ~~Mode: Measured Angle: Wedge Style: \\ Search nit Cable N A Type: Length: No. Con.: Instrument S ttings Make I Model: Serial No.: \\ Probe Delay: Range\\ M'tl Cal I Vel: ---Pulser: Damping: Reiect: \\ PRF: Freq: \\ Filter: Mode: \\ Rectify: Voltage: -\\--- Pulse Width: Display Delay: \\ Reference Sensitivity (dB) Axial: Circ: FSDH Sensitivity: \\ /i>*,,7.1. :liJt:z..
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~!"-~~~yn;: ULTRASONIC EXAMThA TION SKETCH SHEET Data Pkg. #: A2R1o-UT-004 A Wo*tinghouno Eloctrfe Compa ny Plant/Unit: Braidwood I 2 Comp I System SW# 11 I SI Iso. Drwg: 2Sl-39, Sheet 1 Weld I Component ID Number: 2SI08CA-4" I SW# 11 I. 5[ L>Je.lcl 2. SI -3 '1-1 I oo goo 180° COMMENTS: Crown Height: Flush Crown Width: 0.95" Diameter: 4.0" Weld Length: I 14.56" Width 0.95" 0.96" 0.98" VStamp UPST Elbow 1.82 1.85" 1.65" os111on 2 3 4 5 6 7 8 9 amp DNST Valve NIA NIA NIA Up Stream (-) Side Elbow Component ELSoW fLo~ I,, 1.0
- l.o
~ ~ Paae 4 of 4 Wo#=- ll.f 5o736-ol Weld Centerline I FLOW
- Wold Edge Down Stream ( +) S ide Valve Component VALVE
~u.~ L'-"'e.... °C:}(.c....,.....*""""~ ~°"' -i--"10-"ZH' EXAMINER: ---=----- ~ Lv. II DATE 1011512012 EXAMINER: NIA Lv. NIA DATE: NIA Print Jason J. Jennings REVIEWER :~ ~ Lv.zz.z: DATE It> - I~ -I~ REVIEWER: Lv. ~ DATE: \\o-z.\\*\\-Z Authorized Inspection Agency ace ---z??~ DATE /c)*.:u *.&)/:t.. Page 3 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~w.~~pyn~ Calibration Data Sheet \\f'JO-rf' /l..f S0138-ol AWostinghouao Eloc1rlc Compnny \\ Plant I Unit Braidwood / 2 Data Sheet# A2R16-UT-005 1- -* Company Exelon Page 3 of 4 Comp I System SW# 11A/ SI Procedure No. EXE-PDl-UT-2 J~ Cal. Checks Time \\ Rev I Chng. No. 071 None \\ Cal. Block No. 22572 Initial Calib. 1315 \\ Cal. Block Temp. 73°F Thermometer SIN: SAP 106898 Initial Calib. Date 10/15/2012 \\ Size 4" Sch. 160 I 0.531" "T' \\ Ref. Block: I SAP 103772 I D Ferritic ())Austenitic Intermediate 1810 Search Unit #1 ~...... """"' Each Major CRT Div. = 0.3" Intermediate N/A Manufacture: RTD Manufact Serial No.: OB-375 Serial No Cal. Direction: OAxial D Circ. [)) Both Final Calib. No. of Elements: 2 No. of Eleme\\s: 1940 Size: 2 (7 x 10) Shape: Rect Size: Shape Scan Area: _J_toWeld t3 Freq. 2.0 MHz Style: TRLA Freq. \\ Style: II to Weld Final Calib. Date 10/15/2012 Exam Angle: so* Mode: [ong Exam Angle: ~rt--- Mode: Couplant Measured Ang~ 60° Measured Angle: Code Category: R-A Code Item: R1.20 Type: Ultragel II Wedge Style: lnte~ral Wedge Style: \\ Batch: 11625 Search Unit Cable Search nit Cable
- r:.s.t WG-id z sr-s'1-llA INDICATIONS EXAM N A ACCESS FLAW NON RELEVANT SENS.
Type: RG-174 Type: Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) Length: 6' No. of Con.: 0 Length: No. Con.: single 2SI08CA-4" I SW# 11A Sided x x 61.5 Instrument Settings Instrument S ttings Remarks I Reason for lncom11lete Scan(s) COMPONENT TEMP:...1§°F Supplemental 60° RL examination due to single side access. Increased exam Make I Model: GEIT USN 60 SW Make I Model: volume due to RI-ISi requirements, see attached coverage plot. Root geometry Serial No.: SAP 105203 Serial No.: \\ observed intermittent 360° below recordable levels. No recordable indications. Probe Delay: 7.8778 Range: 3.0" Probe Delay: Range\\ 50% code coverage achieved due to one sided exam. M'tl Cal I Vel: 0.2285 Pulser: Square M'tl Cal I Vel: ---Pulser: Damping: ~ Reject: 0% Damping: Reject: \\ PRF: Auto High Freq: 2.0MHz PRF: Freq: \\ Filter: Fixed Mode: Dual On Filter: Mode: \\ ~ Rectify: Fullwave Voltage: 450 Rectify: Voltage: --\\- Examiners: Jason J. Jennings Level II Date 10/15/2012 Pulse Width: 250 ns -- Pulse Width: NIA Level NIA Date N7A Display Delay: 0.00 Display Delay: \\ WesDyne Reviewer I Date: -M',,;,/-£? &,_ tJ..,. i,_u. fir t,O - li'-/ b Reference Sensitivity (dB) Reference Sensitivity (dB) Axial: 61.5 dB Circ: 61.5 dB Axial: Circ: Y-Further E~luation Required? Yes 0No FSDH Sensitivity: 4.8div@70%@55.5dB FSDH Sensitivity: \\ EXELON LEVEL Ill REVIEW I OATE .~ (\\ U-nr *t>*'1l*lt. iNll REVIEW/ OATE/2,/ 2/?~ .A /0. :2. ( *.Li) 1-:Z.. Page 4 of 34
~..... ~~-~ync A Woo,tinghou!lo Eloctric Company ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ULTRASONIC EXAMII\\iA. TION SKETCH SHEET Data Pkg. #: A2R1o-UT-005 Pace 4 of 4 Plant/Unit: Braidwood I 2 Comp I System SW#11AISI Wo#: 1Lf5 oisB-ot Iso. Drwg: 2Sl-39, Sheet 1 Weld I Component ID Number: x:sr Weld zsr-'3~-11A Weld
- Weld Edgo 2SI08CA-4" I SW# 11A Centerline 1..
2.5" .. 1.. 2.5"
- I l"'OSl!IOn u
':IU IOU "'u r5l 1 NIA NIA NIA NIA [!] [3:J rn [4-1 Wl m [)) m Crown Height: Flush 2 NIA NIA NIA NIA
- --\\ i --.
~ 3 11'</A ~own St,..,om (+) Side Crown Width: 0.90" NIA ) I 4 NIA NIA NIA \\Up Stream (-) Side 5 10.0ilJ 10.0/U 0.001 1u....... Diameter: 4.0" 6 10.!l!l!I" 0.!l'llJ' 0.!l'l.l 10.!l!l.J' 7 10.:m'> u,,,,,, u.,,o,, 10.!H!!' I Weld Length: 14.31" 8 10.501" U.!1.JI 0.!10'1 10.,, *., FLOW 9 10.:mu 0.!!4" O.:.nu 10.,,.,, Valve Pipe ~omponent ~omponent V~\\..VE' FLOW ~!.~E: Il.o" l.O I ~ '>\\~~ l\\S% (01 / 7 Datum o v Stamp v ~uimp """"u Location Width UPST DNST TDC Valve Pipe oo 0.90" NIA 2.02" goo 0.90" NIA 1.95" 180° 0.90" NIA 1.55" 'LIU O.tsti" NIA 2.U-' COMMENTS: NIA = Areas due to valve confiauration. ~"'.:le. \\_\\,.....e.. c "'C..~""'""'"~--~...( - \\b*t.\\*l"t. EXAMINER: - ~ Lv. II DATE I OII 512012 EXAMINER: NIA Lv. NIA DATE: NIA Print Jason J. Jennin~s Print REVIEWER: *-a-~/,4~ Lv. ~ATE /t:J -If/ - / z. REVIEWER: .11 -- \\f\\... ri D Lv. \\U DATE: \\o*J\\*\\-Z... \\ Authorized Inspection Agency LZ-4 ??-?~ DATE /t>*.:?t*Aut_-z Page 5 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~w.~~pyn~ Calibration Data Sheet WO#= A Wostlnghouso Eloctrtc Company Plant I Unit Braidwood / 2 Data Sheet# A2R16-UT-007 Company Exelon Page 5 of 8 Comp I System SW# 28 /SI Procedure No. EXE-PDl-UT-2 ~~ Rev I Chng. No. 071 None Cal. Checks Time Cal. Block No. 22572 Initial Calib. 1315 Cal. Block Temp. 73°F Thermometer S/N: SAP 106898 Initial Calib. Date 10/15/2012 Size 4" Sch. 160 I 0.531" "T' Ref. Block: I Intermediate SAP 103772 I D Ferritic [!] Austenitic 1810 Search Unit #1 Each Major CRT Div. = 0.3" Intermediate N/A Manufacture: RTD Serial No.: 0!!-~7!i Cal. Direction: DAxia1 D Circ. [!) Both Final Calib. No. of Elements: 2 1940 Size: 2 (7 x 10) Shape: Rect Scan Area: _j_toWeld E:I Final Calib. Date Freq. 2.0 MHz Style: TRLA II to Weld 10/15/2012 Exam Angle: 60° Mode: [ong Couplant Measured Ang~ 60° Code Category: R-A Code Item: R1.20 Type: Ultragel II Wedge Style: Integral Batch: 11625 Search Unit Cable rsr l,\\JeJc.{ 2S[-3'1-28 ACCESS INDICAllONS EXAM FLAW NON RELEVANT SENS. Type: RG-174 Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) Length: 6' No. of Con.: 0 Single 2SI08CB-4" I SW# 28 Sided x x 61.5 Instrument Settings Remarks I Reason for lncom~lete Scan(s} COMPONENT TEMP:_H°F Supplemental 60° RL examination due to single side access. Increased exam Make I Model: GEIT USN 60 SW volume due to RI-ISi requirements, see attached coverage plot. Root geometry Serial No.: SAP 105203 observed intermittent 360° below recordable levels. No recordable indications. Probe Delay: 7.8778 Range: 3.0" Square 50% code coverage achieved due to one sided exam. M'tl Cal I Vel: 0.2285 Pulser: Damping: soo-0% Reject: PRF: Auto High Freq: 2.0 MHz Filter: Fixed Mode: Dual On ~ Rectify: Fullwave Voltage: 450 Examiners: Jason J. Jennings Level II Date 10/15/2012 Pulse Width: 250 ns NIA Level NIA Date NIA Display Delay: 0.00 Reference Sensitivity (dB) WesDyne Reviewer I Date: Axial: 61.5 dB Circ: 61.5 dB l'f~o7BB-o/ \\ \\ \\ \\ \\
- ~
Seo<Ch un;t #2 Manufact Serial No No. of Eleme\\s: Size: Shape Freq. \\ Style: Exam Angie: l~ Mode: Measured Angle: Wedge Style: \\ Search nit Cable N A Type: Length: No. Con.: Instrument S ttings Make I Model: Serial No.: \\ Probe Delay: --- Range. --- M'tl Cal /Vel: Pulser: Damping: Reject: \\ PRF: Freq: \\ Filter: Mode: \\ Rectify: Voltage: -\\-- Pulse Width: Display Delay: Reference Sensitivity (dB) Axial: Circ: ~~~ ~,,.az:: 1'4'-lK-/b Further Evaluation Required? Yes 0No FSDH Sensitivity: 4.8div@70%@55.5d8 FSDH Sensitivity: \\ EXELON LEVEL m REVIEW I DATE A~ to:. (') <J""m""",o-~-:z.-\\-z. rNll REVIEW I DATE /?_/ '~ ~ .:;2;?? .-.._,. ro.,z3..lt)/;2. Page 6 of 34
~..... ~~pynii A Woetinghouno Electric Company ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ULTRASONIC EXAMl~ATION SKETCH SHEET Data Pkg.#: A2R16-UT-007 Page 8 of 8 Plant/Unit : Braidwood I 2 Comp I System SW# 281 SI WO# lr5o738-o/ Iso. Drwg: 2Sl-39, Sheet 1 Weld I Component ID Number: I.SI Wc-fd ZSI-3'J-2B Weld
- weld Edge 2SI08CB-4" I SW# 28 Centerline I*
2.5"' .. 1.. 2.s* .. I t'OSltlOn u l:IU HIU uu 1 0.844" 0.702" 0.632" 0.651" [TI m @] Wl r5l [6-1 m @] @:] Crown Height: Flush 2 U.<>.><> IU.<i99" 0.639" u.<i5J'" ,_,.....\\ i -- ~ 3 u.1..... IU.rnu 1u.u.. u u.u" Toe Crown Width: 1.00" 0.717" 0.693" ) I 4 0.643" 0.716" I Up Stream (-) Sid& 4.0" 5 0.664" 10.6J9 10....... 0.541" Oown Stream (+) Side Diameter: 6 ['jfl\\ IN/A I""" 1'011\\ 7 l~IA NII\\ 1N/A IN/A l Weld Length: 14.50" 8 N/A
- 1'0/A IN/A IN/A FLOW 9
NIA 1'/A 11'/A 11'/A Elbow Valve i:omponent i:omponent 11.0" EL\\?.OW FLOW ~ Vr>.'1-V~ I i t.o" -l '~'i.50 .') ~>.tjSf} ~ n uatum u YYl#IQ VStamp ~ - v ;:,tamp Location Width UPST DNST TDC Elbow Valve oo 1.00" 1.85" NIA 90° 1.00" 1.25" NIA 180° 0.90" 1.70" NIA 270° 0.90" 1.60" NIA Base Line Examination. COMMENTS: NIA = Areas due to valve configuration. EXAMINER: Lv. II DATE 1011512012 EXAMINER: NIA Lv. NIA DATE: NIA Print Jason J. Jennin~s Print NIA REVIEWER: 7ff ~tf!.. ~ Lv. nr DATE /t!')-f46-I l-REVIEWER: ..,,{_if\\... () 0 Lv.l\\f" DATE: IO*:l~*l"Z. ~LP~ I I Authorized Inspection Agency DATE /u*g3.ao12. ,...... Page 7 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~w.~~pyn~ Calibration Data Sheet wo-tt-A Wostlnghouso Eloctrtc Comp..'lny Plant I Unit Braidwood I 2 Data Sheet# A2R16-UT-006 Company Exelon Page 3 of 4 Comp I System SW#28AISI Procedure No. EXE-PDl-UT-2 J~ Rev I Chng. No. 071 None Cal. Cheeks Time Cal. Block No. 22572 Initial Calib. 1315 Cal. Block Temp. 73°F Thermometer SIN: SAP 106898 Initial Calib. Date 1011512012 Size 4" Sch. 160 I 0.531" 'T' RAf. Block: I SAP 103772 I D Ferritic [!] Austenitic Intermediate 1810 Search Unit #1 Each Major CRT Div. = 0.3" Intermediate NIA Manufacture: RTD Serial No.: 0!!-~75 Cal. Direction: OAxial D Circ. [!] Both Final Calib. No. of Elements: 2 1940 Size: 2 (7 x 10) Shape: Reel Scan Area: _J__toWeld E:3 Final Calib. Date 1011512012 Freq. 2.0 MHz Style: TRLA II to Weld Exam Angle: 60° Mode: [ong Couplant Measured Ang~ so* Code Category: R-A Code Item: R1.20 Type: Ultragel II Wedge Style: Integral Batch: 11625 Search Unit Cable LSI WcJof 25! 28A INDICATIONS EXAM ACCESS FLAW NON RELEVANT SENS. Type: RG-174 Examination Area I Weld YES NO YES (>50% Ref.) NO (dB) Length: 6' No. of Con.: 0 Single 2SI08CB-4" I SW# 28A Sided x x 61.5 Instrument Settings Remarks I Reason for lncom1:1lete Scan(s} COMPONENT TEMP:_.H°F Supplemental 60° RL examination due to single side access. Increased exam Make I Model: GEIT USN 60 SW volume due to RI-ISi requirements, see attached coverage plot. Root geometry Serial No.: SAP 105203 observed intermittent 360° below recordable levels. No recordable indications. Probe Delay: 7.8778 Range: 3.0" 50% code coverage achieved due to one sided exam. M'tl Cal I Vel: 0.2285 Pulser: Square Damping: ~ 0% Reject: PRF: Auto Hi!lh Freq: 2.0 MHz Filler: Fixed Mode: Dual On ~ Rectify: Fullwave Voltage: 450 Examiners: Jason J. Jennings - Level II Date 10/15/2012 Pulse Width: 250 ns NIA Level til7A Date tilt A Display Delay: 0.00 Reference Sensitivity (dB) WesDyne Reviewer I Date: Axial: 61.5 dB Circ: 61.5 dB ftf~OT38-o/ \\ \\ \\ \\ \\Seo.ch Unit#2 Manufact Serial No No. of Eleme\\s: Size: Shape Freq. \\ Style: Exam Angle: 1re\\-- Mode: Measured Angle: Wedge Style: \\ Search nit Cable N A Type: Length: No. Con.: Instrument S ttings Make I Model: Serial No.: \\ Probe Delay: --- Range. --- M'tl Cal I Vel: Pulser: Damping: Reject: \\ PRF: Freq: \\ Filter: Mode: \\ Rectify: Voltage: -\\- Pulse Width: Display Delay: \\ Reference Sensitivity (dB) Axial: Circ: B~~~F ~,.zzr ttJ. 1f:- 1,_ Furthe!:._Evaluation Required? DYes [!)No FSDH Sensitivity: 4.8div@70%@55.5dB FSDH Sensitivity: \\ EXELON LEVEL 111 REVIEW I DATE ..A-'\\ v...~ o U:m,o -~1-*i. rNll REVIEW I DATE /2_/ ?:::h~..: /c).. ::u. 2.:), 2.. Page 8 of 34
~w.~~pync A Wootinghouno Electric Compnny ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ULTRASONIC EXAMJI\\jATION SKETCH SHEET Data Pkg. #: A2R16-UT-006 Page 4 of 4 Plant/Unit: Braidwood I 2 Comp I System SW#28AISI Wo# /lf5o73B-Of Iso. Drwg:
~
2Sl-39, Sheet 1 Weld I Component ID Number: 2SI08CB-4" I SW# 28A J:sr wdol 2SI.-3'1-2BA Weld Centerline '"Weld Edge Datum o Location TDC oo goo 180° 270" COMMENTS: Crown Height: Flush Crown Width: 0.75" Diameter: 4.0" Weld Length: 14.37" vve1a V Stamp Width UPST Valve 0.75" NIA 0.75" NIA 0.80" NIA O.tso' NIA Position 1 2 3 4 5 6 7 8 9 V5tamp DNST Pipe 2.25" 2.00" 2.00" 2.uu** !IU ll:IU N/A N/A I \\.O" \\... o __ I NIA = Areas due to valve configuration. ?'- ~ Lv. II DATE 1011512012 Print Jason J. Jennings REVIEWER:~,(""'J"j!,A"°_.....: Lv...ZZZ: DATE 14-/g - I :J- "LfU N/A Vf\\Lv'E: I 2.s* 2 s** I m m m m rn L ~-**,_,._ o-~--,., _ ~ Valve COmponeilf I FLOW FLOW Gi:. * ~~ 1\\5~
- . 7 v
Pipe Component ~fE" 't>c..~c. L\\.ne. E)t4~\\,'('lC.,~~~ ~""' U**Z\\*I~ EXAMINER: NIA Lv. NIA DATE: NIA Print NIA REVIEWER: ~ =<\\ V\\--.3:.J. Lv. ""Til DATE: fo*.1.\\*l"l.. \\ J Authorized Inspection Agency ~ 22? '-62.- DATE /iJ -p.,,. ;:i..y,a._ Page 9 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~ .W.~~pyn;: Calibration Data Sheet IAJO #=- /4507 3 B-o/ A Woatfnghouno Etoc1tic CompcutY \\ Plant I Unit Braidwood I 2 Data Sheet# A2R16-UT-035 tl1 Company Exelon Page 4 of 7 Comp I System FW# 28BI SI Procedure No. EXE-PDl-UT-2 Cal. Checks Time \\ Rev I Chng. No. 071 None --- ti \\ Cal. Block No. 22572 Initial Calib. 0734 \\ Cal. Block Temp. 73°F Thermometer SIN: SAP 106898 Initial Calib. Date 1012712012 \\ Size 4" Sch. 16010.531" T' \\ Ref. Block: I SAP 103552 I D Ferritic [!) Austenitic Intermediate 1044 Search Unit #1
- ~ s.. ~h un;t#2 Each Major CRT Div. =
0.3" Intermediate NIA Manufacture: RTD Manufact Serial No.: OS-:J7!5 Serial No Cal. Direction: OAxial D Circ. [!) Both Final Calib. 1318 No. of Elements: 2 No. of Eleme\\s: Size: 2 ~7 x 10) Shape: Rect Size: Shape Scan Area: _j_toWeld E:I Final Calib. Date 1012712012 Freq. 2.0 MHz Style: TRLA Freq. \\ Style: II to Weld Exam Angle: 60° Mode: [ong Exam Angie: ;:i~ Mode: Couplant Measured Angie:- 60° Measured Angle: Code Category: R-A Code Item: R1.20 Type: Ultragel II Wedge Style: lnte!jral Wedge Style: \\ Batch: 11625 Search Unit Cable Search nit Cable J:"S[ l/Jdd 2SF3Cf-28B INDICATIONS EXAM N A ACCESS FLAW NON RELEVANT SENS. Type: RG-174 Type: Examination Area I Weld YES NO YES {>50% Ref.) NO (dB) Length: 6' No. of Con.: 0 Length: NO. Con.: single 2SI08CB-4" I FW # 288 Sided x x 49.8 Instrument Settings Instrument S ttings Remarks I Reason for lncomQlete Scan(s} COMPONENT TEMP :~*F Scan gain levels set to maintain an ID response between 5% and 20% FSH. This Make I Model: GEIT USN 58L SW Make I Model: exceeds the 12d8 requirements of RI-ISi. No recordable indications. Supplemental Serial No.: SAP 106946 Serial No.: \\ 60°RL examination due to single side access. 50% code coverage achieved. Probe Delay: 6.93 Range: 3.0" Probe Delay: Range\\ M'tl Cal I Vel: 0.2231 Pulser: Square M'tl Cal I Vel:==Pulser: Damping: ~ Reject: 0% Damping: Reject: \\ PRF: Auto High Freq: 2.0 MHz PRF: Freq: \\ Filter: Fixed Mode: Dual On Filter: Mode: \\ Examiners: Robert Glesener,,(,tf'-,.)~el Rectify: Fullwave Voltage: 450 Rectify: Voltage: -\\---- II Date 1012712012 Pulse Width: 250 ns --- Pulse Width: NIA Level NIA Date NIA Display Delay: 0.00 Display Delay: \\ -a...r1l h-~** lw..zzz. /()-&_'J..-/1_ Reference Sensitivity (dB) Reference Sensitivity (dB) WesDyne Reviewer I Date: Axial: 61.8 dB Circ: 61.8 dB Axial: Circ: Further Evaluation Required? Oves 0No FSDH Sensitivity: 4.9div@47%@49.8dB FSDH Sensitivity: \\ EXELON LEVEL Ill REVIEW I DATE .... \\I\\.' ()~-r.;-,.,...... _,., ANll REVIEW I DATE L 'vt... l ~*. \\ 0 \\ ""U\\ \\ \\ '- Page 10 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~JV.~~pyni: ULTRASONIC EXAMII'IATION SKETCH SHEET Data Pkg.#: A2R1o-UT-035 A Wostinghouno Eloctric Cam pony Page 7 of 7 Plant/Unit : Braidwood I 2 Comp I System FW # 288 I SI vJo# 145 0738-0J Iso. Drwg: 2Sl-39, Sheet 1 .r:sr We-Id 2ST-s7-2.BB Weld I Component ID Number: 2SI08CB-4" I FW # 288 Weld Centerline
- Weld Edge 90° 180° COMMENTS:
EXAMINER: REVIEWER: I Pos1!1on u 1 0.55" Crown Height: Flush 2 Crown Width: 1.05" 3 4 Diameter: 4.0" 5 6 Weld Length: 15.0" 7 8 9 J.O" 1.0" V Stamp mp Width UPST DNST Pi e Valve 1.05" 1.93" NIA 1.00" 1.95" NIA 0.95" 2.15" NIA NIA due to valve confi9uration. ~M-::3~.ll DATE Print Robert Glesener l:IU 11m 0.52" 0.54" 0/5 roe-o< lSA I 1012612012 7f?t;,t:p 48~ Lv;,,lZFDATE 10-~9-/.t. uu I 2 s-2 5" I 0.58" mrnm mrnm Up Streem (-) S fde Down Stream ( +) Side I ---._ EXAMlNER: REVIEWER: Pipe component I FLOW
- Valve Component P;pe..
f..lbciw Va.Ive-Yf5' 6ds £&.~ I ~r- "'\\. NIA Print ------ -\\--- V\\. () 0 v "'i Lv. NIA DATE: NIA Lv. ~ DATE: \\t>*~-\\~ Authorized Inspection Agency }__ L Ao DATE \\ "'\\ ~ \\\\--- ' Page 11 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~Exelon, Supplemental Report Report No.: A2R17-UT-005 Page: 3 of 4 Summary No.: 2-803.110.0011 Examiner: Michael, Dickey~~ Level: 11-PDI Reviewer: Date: Examiner: N/A Level: N/A Site Review: Jay Miller Date: Other: N/A Level: NIA ANll Review: Date: 0,.. 1 ;;i. * ::>t:> /,1 Comments: I Component ID: 2PZR-01-N4B, EWH 8-19-19 I Total coverage required= 4.2" x 2.7" = 11.34" 1.2" x 3.0" x 0.5" = 1.8" Total= 13.14" Missing axial (Facing Nozzle and away from nozzle) 99% (Facing up)+ 59.9% (Facing down)= 158.9o/a/2 = 79.5% Missing circ (Facing CW and CCW) 97.5% (CW)+ 97.5% (CCW) = 195°/a/2 = 97.5% 79.5% (Axial)+ 97.5% (Circ) = 177°/a/2 = 88.5% T & C Taken from previous data report number A2R15-UT-034. Page 12 of 34
-=" Exelon° Summary No.: 2-803.110.0011 Sketch or Photo: ('r\\",~\\ ~ -............ - 1\\-"ic..l ~ ~\\~~t--z-\\~ ~ """\\<::.~i.~ ~i.c-c ~~ ~u)~~~ / ~\\.~~\\~ J\\.x.icJ h..c.\\~ f\\UJO\\'t ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Supplemental Report !component ID: 2PZR-01-N4B, EWH 8-19-19 1 I / -......_\\ Page 13 of 34 Report No.: A2R17-UT-005 Page: 4 of 4 ./ ---,,
ATTACHMENT 3
B""'r~ay,id-w~oodStation Un..-..i-t-'-"2~--
Third ISi Interval Limited Coverage NDE Reports ~Exelon,, Supplemental Report Summary No.: 2-803.110.0012 Report No.: A2R17-UT-006 Page: 3 of 4 Examiner: Michael, Dickey ~ (Y'\\iC\\JLevel: II-POI Reviewer: Date: S -14 *If Examiner: N/A Level: N/A Site Review: Jay Miller Date: S"'-\\\\-l ~ Other: N/A Level: NIA ANll Review: Act...,,,., /YI. P........:*... (,?,.4.:2'22fi?....- Date: o~-. 1.;z. 2...l l'f Comments: !component ID: 2PZR-01-N4C, EWH 8-19-19 I Total coverage required= 4.2" x 2.7" = 11.34" 1.2" x 3.0" x 0.5" = 1.8" Total= 13.14" Missing axial (Facing Nozzle and away from nozzle) 99% (Facing up)+ 59.9% (Facing down)= 158.9%/2 = 79.5% Missing circ (Facing CW and CCW) 97.5% (CW)+ 97.5% (CCW) = 195"/o/2 = 97.5% 79.5% (Axial)+ 97.5% (Circ) = 177°/o/2 = 88.5% T & C Taken from previous data report number A2R15-UT-034. Page 14 of 34
- ' Exelon.
Summary No.: 2-803.110.0012 Sketch or Photo: M '1~\\ ~ -..........._ _ 1\\-"ic.J ~ ~\\~~l-c-\\e
==::> <V'\\\\~<"i.\\~ ~i.rc ~~ Cu.),~l() / ~~~~\\~ ~x.icJ 'h-..c..\\ ~ "~"' '1 ./----. ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Supplemental Report !component ID: 2PZR-01-N4C, EWH 8-19-19 I I " \\.. /""-, Page 15 of 34 Report No.: A2R17-UT-006 Page: 4 of 4
~Exelon. ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Supplemental Report Report No.: A2R18-UT-015 Summary No.: 2-R01.11.2032 ~~~~~~~~~~~ Examiner: Salley, Michael m f S Level: II Examiner: N/A Level: N/A ~~~~~~~~~- Other: NIA CW'Blffl5rder: 01757348-01 Weld: 2FW-09-25 Sketch 1 : Coverage Plot Sketch or Photo: 0.75" Leve I: N/A Page: 4 of 4 Reviewer: L ~ ~ate: 10/1+./ls Site Review: ::r.....,M;\\\\e.<" 1"1 ~ TII" Date: 10 *1'S'**~ ANll Review: L~ !'-AA u.\\i3-A~ &.i l w...__ Date: '"' \\ '~ \\,s-Flow No Axial Exam: 0.25(0.55 + 0.4)/2 ~x02)12=015in' o Exam Area: (0.25 x 0.25) + 0.8(0.25 + 0.20)/2 + 0.55(0.20 + 0.25)/2 + (0.9 x 0.25) = 0.59 in 2 Axial Coverage: (0.59 - 0.15) I 0.59 = 74.6% Circ Coverage: 100% Total Coverage: (74.6 + 100)/2 = 87.3% Weld Crown Width: 1.3" Counterbore US: 1.35" From Root Counterbore OS: None Detected 0 I Page 16 of 34 1" 2" 3" I
"'estinghouse LIMITATION TO EXAMINATION lNT BRAIDWOOD UNIT 2 SKETCH 2PZR-01 iTEM/COMPONENT PZR I PZR-Surge Nozzle
- MINER~£~
tommy:JCkSon, evei II PROCEDURE EXE-ISl-210, Rev. 0, FCN NIA DATE 5/3/2008 .ATEDTO: UT x PT MT VT !DENT.NO. 2PZR-01-N1 >VIDE GENERAL INFORMATION TO DESCRIBE APPROXIMATE SIZE, LOCATION AND TYPE OF LIMITATION. A2R13-UT -025 Page 4 of 6 Cb. '"'E:.,.., E.9' p Cl-\\~~~\\ \\()I lv~s "!:> oz.i. Lt:. >ATE .,,,K'_ cL,IN'""'-- s:- /-<:)~ \\ \\ \\ I I I 'vJ E.LO ~ i...~z..~-0\\-\\4 \\ D~~"'""t-.), -t-o Sc..~LE.. " I I c_ov C:.RA<:>E :: \\ \\ \\ .S. \\-\\ ELL. ~-'\\.)._ 01.. \\ \\ \\ \\ ANllREVIEWDATE ~ s-?:...oi?' \\ \\ \\ \\ \\ \\ \\
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Exelon. Limitation Record Site/Unit: BRW 2 Procedure: EXE-ISl-52 Outage No.: A2R19 ~~~~~~~~~~~ ~~~~~~~~ Summary No.: 2-803.140.0019 Procedure Rev.: 2 FCN-01 Report No.: A2R19-UT-020 ~~~~~~~~~~~ Workscope: ISi Work Order No.: 01894635-01 Page: 2 of 2 ~~~~~~~~~~~ Description of Limitation: Permanent Structure Limits Examination for 30" of 205" total inches. 85% Coverage !component ID: 2SG-01-SGN-01A, EWH 8-19-19 I Limitations removal requirements: Radiation field: Examiner Level Serth, Joseph P. Examiner N/A Other NIA Level Level NIA Date Reviewer 4/30/2017 Date Signature Date Page 18 of 34 Signature Date 5/1/2017
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports - Exelon Summary No.: 2-C01.30.0010 Examiner: _D_a_v-is-, -P-h-il-ip-8-. --~ -~-- -C??--,,,. ~--- / Examiner:....:N..::l.:..A'---------------- Other:....:N..::l.:..A=---------------- Comments: 2SG-01-SGC-02 Sketch or Photo: c.o* 45* 'L 1" l(s* '4~E. Supplemental Report Report No.: A2R20-UT-064 Page: 4 of 5 Level: 11-PDI Reviewer: Delbusso, James WesDyne Level Ill Date: 1011612018 Level: NIA Site Review: Hall, Kevin Exelon Level Ill Date: l!:::! I l '2-- ( q3 Level: NIA ANll Review: kf..,.,.,n. p,..,.~ /ZL..J??'-1?...- Date: /d*/l*;l.J/I/ 1: 45° -1"'i-~ \\ I I I j: I \\ I \\ Page 19 of 34
- 45.
c.o* 3.!>.. l
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Exelon Supplemental Report Report No.: A2R20-UT-064 Summary No.: 2-C01.30.0010 Examiner: Davis, Philip B. ~ .r Level: 11-PDI Reviewer: Delbusso, James WesDyne Level Ill Examiner:...:N..::/.:..A:..._ _____________ _ Level: NIA Site Review: Hall, Kevin Exelon Level Ill Other: -'N-"/'-A'---------------- Level: N/A ANll Review: 11t::i2tt-Jff7,f':,,-..,._ ~~- Comments: 2SG-01-SGC-02 Limitations due to configuration. 3-18" HAND HOLES, 10" INSPECTION COVER & 4" BRANCH CONNECTION LIMIT STUD BARREL SIDE SCAN. Page: 5 of 5 Date: 10/16/2018 Date: \\dte, (18 Date: 1-'*t?t *...z.<>li: 3-9", 1-10"1NSPECTION COVERS, 7" BRANCH CONNETION, 7" ID PLATE & 6" PLUG BRANCH CONNECTION LIMIT TUBE SHEET SIDE SCAN. 3-9" INSPECTION COVERS & 10" INSPECTION COVER LIMITS CIRC SCANS. Sketch or Photo: Weld Length - 427.5' STU.8 Bfll?R.El IB W CLD'i. TuBE 5HU1 PBoLr 't8ol.T
- ZNSP£<T1o;J CovEH
- I
/8° q 8fl~t'C/{ c.,,,,, ii 1 W[U> p11D ~Pp/.llif JI.(, J, 2 >. H .ifIO 9'" 88.4"/o Coverage Limitations on stud barrel side - 68.0" (84.1 %) Limitation for tube sheet side - 57.0" (86.7%) Limitations for circ scans - 37.0" (91.3%) x 2 111" 881.J* + If Bo Lr I"'.Sl'I cr10,_, covE-' <1.e--10 1e"' Bn11,,,11 Coµ,,;. ~1:1. &/lAldf t:..oN,,.J, -It ;/, ye,1.r IA1$/'Eff",v cov Et<
- 17 PJ.utr 8'111,..tH Cl~t
5'" 0 5" 0 ~ s" 5 Page 20 of 34 ea.c* + 'fBo,("f .r;vs~tt'fto/tl c.oVE~
- ll.2.5-"U.
18 IJJf.L (l P-'~
- ll",78
~21-~
- 'JO T
_ 91_ - - _,-,..------*-** ~ .. J.. " l Plut-- 81111,,.~tt (ON,,). dJ.(*O
ATTACHMENT 3 Braidwood Station Un.~i,_.,_ t_..._2 __ Third ISi Interval Limited Coverage NDE Reports ~" Exelon. Supplemental Report Report No.: UT-2015-001 Page: 4 of 6 . Sumrnary_f\\lo,: NIA........ *- Sketch or Photo: !component ID: 2AF-03-23, EWH 8-19-19 I 1 _/ Work Package: 01782044-01 o 1" 2" 3" Weld: FW-1 I I Sketch 1 : Coverage Plot Weld Crown Width: 0.9" Counterbore US: None Counterbore OS: None Profile @ LO (Extrados) Scanned across weld with 45° probe, coverage credit on far side of weld take with higher angles. Flow Flange 0.35" 0.35" 0.45" Note: 70° used to obtain remaining coverage, scan limited to area shown. Coverage Cale: Axial Coverage = 100% Circ Coverage= 1.4" of 1.9" exam box width= 74% Total= (100% + 74%)/2 = 87% ~~ (!:./,.,-,~ 11* /?/Ck-t",/J'-~ d?fmc_:L-ANI I ANll REVIEW 1.o ~l t< REVIEW DATE j_ ~~l----- Page 21 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~* Exelon. Supplemental Report Report No.: UT *2015-002 , mmary No.: N/A Page: 4 of 6 ( Sketch or Photo: !Component ID: 2AF-03-24, EWH 8-19-19 I Work Package: 01782044-01 o 1.. 2" 3" Weld: FW-2 ._I Sketch 1: Coverage Plot Weld Crown Width: 0.9" Counterbore US: None Counterbore OS: None Profile@ LO (Extrados) Scanned across weld with 45° probe, coverage credit on far side of weld taken with higher angles. Flow Note: 70° used to obtain remaining coverage, scan limited to area shown. Circ Coverage Coverage Cale: Axial Coverage = 100% tJ../,µ/.t I/. ~c~a.N Circ Coverage= 1.4" of 1.9" exam box width= 74% d1'f /??t.:fo- ... _EX_f.o!_U,. !- I/~-. ~o - /-_'?__.. Total= (100% + 74%)/2 = 87% ANI I ANll REVIEW Lot~\\\\' REVIEW DATEL~ l.A*. . Page 22 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~Exelon Supplemental Report Report No.: UT-2015-003 Page: 4 of 6 Summary -No.~ N/A - - ** / ) Sketch or Photo: !component ID: 2AF-04-20, EWH 8-19-19 I Work Package: 01782044-01 o 1,, 2" 3" Weld: FW-3\\ Sketch 1 : Coverage Plot Weld Crown Width: 0.7" Counterbore US: None Counterbore OS: None Scanned across weld with 45° probe, coverage credit on far side of weld take* with higher angles. Flow 0.42" Note: 70° used to obtain remaining coverage, scan limited to area shown. Coverage Cale: a j,yr,1£ # l"cf::en-d Axial Coverage = 100% Circ Coverage= 1.3" of 1.7" exam box width= 76.5% d 1'f /?1?r/z---- Total= (100% + 76.5%)/2 = 88% E KcltM./ Lv LZI-1 c? 1f LUL Page 23 of 34 ANI I ANll REVIE\\f'{0 t>\\\\(° REVIEW DATE J_ kL-
~
- Exelon.
.1mary No.: N/A ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Supplemental Report Report No.: UT-2015-004 Page: 4 of 6 ' Sketch or Photo: !component ID: 2AF-04-21, EWH 8-19-19 I Work Package: 01782044-01 o 1" 2" 3" Weld: FW-4 I~~-~-~-~-~-~ Sketch 1: Coverage Plot Weld Crown Width: 0.7" Counterbore US: None Counterbore OS: None Profile@ LO (Extrados) Scanned across weld with 45° probe, coverage credit on far side of weld taken with higher angles. Flow 0.45" Note: 70° used to obtain remaining coverage, scan limited to area shown. Coverage Cale: Axial Coverage = 100% ~ ~. Circ Coverage = 1.3" of 1. 7" exam box width = 76.5% ,....., "} /./..un ~-e~/(.) Total= (100% + 76.5%)/2 = 88% ~c:;llm&L- -- -- - --k -~- ---*
- atu;,, <~& /O:;_;; -
ANI I ANll ReVIEW \\,_ REVIEW DATE J'_k~\\~ ~~ Page 24 of 34 /
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~Exelon. Supplemental Report Report No.: UT-2015-005 Page: 4 of 4 _ Summary No.:. NIA I ./ Sketch or Photo: ~omponent ID: 2AF-02-23, EWH 8-19-19 I Work Package: 01782044-02 o 1.. 2" 3" Weld: FW-1 I.__ _ __.___~ _ Sketch 1: Coverage Plot Weld Crown Width: 0.5" Counterbore US: None Counterbore OS: None Scanned across weld with 45° probe, coverage credit on far side of weld taken with higher angles. Flow Note: 70° used to obtain remaining coverage, scan limited to area shown. Circ Coverage Coverage Cale: Axial Coverage = 100% Circ Coverage = 1.2" of 1.5" exam box width = 80% Total = (100% + 80%)/2 = 90% chY'!s II* /llc-/:'~"/V dv. r/-/7?c,-h__ ~£u>I<./ l..<WJ /CJ - I - I ::f'" ANI I ANll REVIEW \\ d-- \\0 -i.\\,s-REVIEW DATE ~* Page 25 of 34
~Exelon ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Supplemental Report Report No.: UT-2015-006 Page: 4 of 6 .*SummaryNo.;...N/A-- - Sketch or Photo: b omponent ID: 2AF-02-24, EWH 8-19-19 I J I I / Work Package: 01782044-02 Weld: FW-2 Sketch 1: Coverage Plot Weld Crown Width: 0.5 Counterbore US: None Counterbore DS: None Profile @ LO (Extrados) 0 I 1" 2" Flow Note: 70° used to obtain remaining coverage, scan limited to area shown. Circ Coverage Coverage Cale: Axial Coverage = 100% Circ Coverage = 1.2" of 1.5" exam box width = 80% Total= (100% + 80%)/2 = 90% e,L#~ £;(~w J.I' OZ /(9 - I-I ~F ANl I ANll REVIEW 1.o \\~\\< REVIEW DATE ::b-~ ~D 0 *
- Page 26 of 34 3"
I
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports
- §? Exelon.
Supplemental Report Report No.: UT-2015-007 Page: 4 of 6 - --Summary-No.; -N/A- -- -- ) Sketch or Photo: !component ID: 2AF-01-24, EWH 8-19-19 I Work Package: 01782044-02 o 1" 2" 3" Weld: FW-3 I I I Sketch 1: Coverage Plot Weld Crown Width: 0.5 Counterbore US: None Counterbore OS: None Scanned across weld with 45° probe, coverage credit on far side of weld taken with higher angles. Flow 0.46" Note: 70° used to obtain remaining coverage, scan limited to area shown. Circ Coverage Coverage Cale: Axial Coverage = 100% C. 1,... 's If m cK-<'-tfl,J Circ Coverage= 1.2" of 1.5" exam box width = 80% Total= (100% + 80%)/2 = 90% dt1-/h~1- £.YFl.M J_,I/.JJZ J&-l-1'7 ANI I ANll REVIEW \\ REVIEW DATE J_ ~,< Page 27 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~Exelon Supplemental Report Report No.: UT-2015-008 . - - Summary-No.: NIA-Page: 4 of 6 / ) Sketch or Photo: !component ID: 2AF-01-25, EWH 8-19-19 I Work Package: 01782044-02 o 1.. 2" 3" Weld: FW-4j Sketch 1: Coverage Plot Weld Crown Width: 0.6" Counterbore US: None Counterbore OS: None Flow Profile@ LO (Extrados) Note: 70° used to obtain remaining coverage, scan limited to area shown. Coverage Cale: Axial Coverage = 100% Circ Coverage = 1.25" of 1.6" exam box width = 78% Total= (100% + 78%)/2 = 89% ANI I ANll REVIEW I \\o°\\v\\\\~ REVIEW DATE d-- \\;-.. '-~.. Page 28 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~Exelon. Supplemental Report Report No.: UT-2015-009 Page: 5 of 6 . ~um~_art tl!o.: NIA I / Sketch or Photo: !component ID: 2CV-21-58, EWH 8-19-19 I Work Package: 01692238-08 o 1.. 2" 3" Weld: FW-11 L-_ Sketch 1: Coverage Plot Weld Crown Width: 1.0" Weld Length: 14.5" Counterbore OS: None Counterbore US: None Limitations: Single sided access due to valve. Tee radii obstructed exams for 4.25" each@ 0° and 180°. Examined 3" of weld length @ 90° & 3" of weld length @ 270°. Examined 6" of 14.5" weld length. Flow / Valve //~ ~~~__L_~~- Profile@90°
- o. 10" 1 o.65" o.60" o.60" 0.76" Coverage represents 6" of 14.5" Tee Exam Coverage = 50% as per single sided access rules.
e:,_j,,,,..'_r ll * ~(.,-/<-<.1re/ d
- /Nd.-- Page 29 of 34 ANI I ANll REVIEW
\\o \\"l--\\, \\ REVIEW DATE J_ ~
I - ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~'Exelon. Supplemental Report ) Report No.: UT-2015-009 Page: 6 of 6 Sketch or Photo: !component ID: 2CV-21-58, EWH 8-19-19 I Work Package: 01692238-08 Weld: FW-1 Sketch 2: Coverage Plot 0 I 1" 2" 3" Note: 70° used to obtain remaining near side coverage, scan limited to area shown. 60° RL Tee Far side of weld examined as per single sided access rules - No coverage credit taken. Coverage Cale Exam Length Result Ax Upst O" of 14.5" 0% Ax Dnst 6" of 14.5" 41.4% Circ Upst O" of 14.5" 0% Circ Dnst 6" of 14.5" 41.4% Total: 82.8% Total I 4: 20.7% Page 30 of 34 ANI I ANll REVIEW 10 tv\\'~ REVIEW DATE_ J__ bu*
~*Exelon. ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Supplemental Report Report No.: UT-2015-010 Page: 5 of 8 SunJ.m?l'.Y,No.: NIA... _ Sketch or Photo: !component ID: 2CV-21-57, EWH 8-19-19 I Work Package: 01692238-08 Weld: FW-2 Sketch 1: Coverage Plot Weld Crown Width: 1.0" Weld Length: 14.5" Counterbore OS: None Counterbore US: None Limitation: 0 I Tee radius obstructed US exams for 4.25"@ 180°. Flow 0.75" Profile @ 0° (TDC) US Coverage represents 10.25" of 14.5" weld length. OS Coverage represents 14.5" of 14.5" weld length. c:.l.~-'I H /?l<K~H/V d#mc4-- £J(EJ...t>.u £..., 07 /0-1-/~ 1" 2" I AN~ I AN~i RlEV~EW, c\\-....\\,~ RlEV~lEW DATIE J__ ~ Page 31 of 34 3"
~ ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~Exelon Supplemental Report Report No.: UT-2015-010 Page: 6 of 8 Summary No.: N/A_.. Sketch or Photo: !Component ID: 2CV-21-57, EWH 8-19-19 I Work Package: 01692238-08 o 1.. 2" 3" Weld: FW-21 ~ -~-~' -~-~~-~ Sketch 2: Coverage Plot Note: 70° used to obtain remaining coverage, scan limited to area shown. Single sided access for 4.25" 60° RL Pipe Far side of weld examined as per single sided access rules - No coverage credit taken. Coverage Cale Exam Length Result Ax Upst 10.25." of 14.5" 70.7% Ax Dnst 14.5" of 14.5" 100% Circ Upst 10.25" of 14.5" 70.7%
- Circ Dnst 14.5" of 14.5" 100%
Total: 341.4% Total/ 4: 83.3% Page 32 of 34
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports ~Exelon. Supplemental Report Summary No.: NIA ~--------~ Examiner: Salley, Michael /7J7.5 Level: II Report No.: UT-2015-012 Page: 5 of 6 Date: 1ohs/ts Examiner: NIA ~-------~ Level: NIA Site Review:...-~~~1.=~~~ill!:!!- Date: 10-1'5'-i"i" Other: _N_IA ________ Level: NIA ANll Review: Date:,!V*~S * #-tJ1~ CommerWork Order: 017827 43-01 Weld: FW-2 * !component ID: 2CV-21-56, EWH 8-19-19 I Sketch 1: Coverage Plot Weld Crown Width: 0.9" Sketch or Photo: Weld Length: 14.5" Counterbore OS: None Counterbore US: None Limitation: Tee radius obstructed OS exams for 4.25"@ 180°. Profile@ 0° (TDC) US Coverage represents 14.5" of 14.5" weld length. OS Coverage represents 10.25" of 14.5" weld length. 0 1" 2" 3" I Page 33 of 34 FW-2 j
- ~Exelon.
ATTACHMENT 3 Braidwood Station Unit 2 Third ISi Interval Limited Coverage NDE Reports Supplemental Report Report No.: UT -2015-012 Page: 6 of 6 Summary No.: N/A ~~~~~~~~~~- Examiner: Salley, Michael MT 5 Level: II Reviewer:L ~ Date: 10/ts/15 Site Review: ::r.,.'\\ \\M~\\\\ef" d==,, f\\::Q[ W Date: 10*1S*\\~ Examiner: N/A Level: N/A ~~~~~~~~~ Other: N/A Level: NIA ~~~~~~~~~ ANll Review: Afo..,m.A,,,M. ~- Date: /d*1~*~1f We~'1lr.der: 01782743-01 Weld: FW-2 Sketch 2: Coverage Plot Sketch or Photo: I Component ID: 2CV-21-56, EWH 8-19-191 0 1" 2" I I Flow Note: 70° used to obtain remaining coverage, scan limited to area shown. Single sided access for 4.25" @ 180° Pipe '\\
- ~~*
60° RL Tee 3" Far side of weld examined as per single sided access rules - No coverage credit taken. Coverage Cale Exam Length Result Ax Upst 14.5" of 14.5" 100% Ax Dnst 10.25" of 14.5" 70.7% Gire Upst 14.5" of 14.5" 100% Gire Dnst 10.25" of 14.5" 70.7% Total: 341.4% Total/ 4: 83.3% Page 34 of 34}}