ND-20-0601, Submittal of Inservice Testing Program Plan - 1st Interval

From kanterella
Jump to navigation Jump to search
Submittal of Inservice Testing Program Plan - 1st Interval
ML20142A358
Person / Time
Site: Vogtle  Southern Nuclear icon.png
Issue date: 05/21/2020
From: Chamberlain A
Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ND-20-0601
Download: ML20142A358 (134)


Text

>- Southern Nuclear May 21, 2020 Docket Nos.: 52-025 52-026 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Southern Nuclear Operating Company Vogtle Electric Generating Plant Units 3 and 4 Southern Nuclear Operating Company, Inc.

3535 Colonnade Parkway Birmingham. AL 35243 Tel 205.992.6361 ND-20-0601 10 CFR 50.55a Submittal of lnservice Testing Program Plan - 1st Interval Ladies and Gentlemen:

In accordance with the American Society of Mechanical Engineers Code for Operation and Maintenance of Nuclear Power Plants (ASME OM Code}, Subparagraph ISTA-3200, and Southern Nuclear Operating Company (SNC) procedures, SNC is submitting, for your information, a copy of the Vogtle Electric Generating Plant Units 3 and 4 lnservice Testing Program Plan - 1st Interval (Version 1.0). This is the initial issuance of the lnservice Testing Program Plan.

This letter contains no regulatory commitments. This letter has been reviewed and confirmed to contain no security-related information.

Should you have any questions, please contact Ms. Amy Chamberlain at (205) 992-6361.

Respectfully submitted, Amy C. Gflamberlain Manager, Regulatory Affairs Southern Nuclear Operating Company :

Vogtle Electric Generation Plant Units 3&4, lnservice Testing Program Plan -

P 1 Interval, Version 1.0

U.S. Nuclear Regulatory Commission ND-20-0601 Page 2 of 3 cc:

Southern Nuclear Operating Company / Georgia Power Company Mr. S. E. Kuczynski (w/o enclosures)

Mr. P. P. Sena III (w/o enclosures)

Mr. M. D. Meier (w/o enclosures)

Mr. D. H. Jones (w/o enclosures)

Mr. G. Chick Mr. M. Page Mr. P. Martino Mr. D. L. McKinney (w/o enclosures)

Mr. T. W. Yelverton (w/o enclosures)

Mr. B. H. Whitley Ms. C. A. Gayheart Ms. M. Ronnlund Mr. D. L. Fulton Mr. M. J. Yox Mr. C. T. Defnall Mr. J. Tupik Ms. S. Agee Mr. M. Humphrey Ms. A. C. Chamberlain Mr. S. Leighty Mr. N. Kellenberger Mr. E. Riffle Ms. K. Roberts Mr. J. Haswell Mr. D. T. Blythe Mr. K. Warren Mr. A. S. Parton Document Services RTYPE: VND.LI.L00 File AR.01.02.06 Nuclear Regulatory Commission Mr. W. Jones (w/o enclosures)

Mr. M. King (w/o enclosures)

Ms. M. Bailey w/o enclosures)

Mr. C. Patel Mr. C. Santos Mr. B. Kemker Mr. J. Eargle Mr. G. Khouri Ms. S. Temple Mr. C. J. Even Mr. A. Lerch Mr. S. Walker Mr. N.D. Karlovich Ms. N. C. Coovert

U.S. Nuclear Regulatory Commission ND-20-0601 Page 3 of 3 Nuclear Regulatory Commission (Continued)

Mr. C. Welch Mr. J. Gaslevic Mr. V. Hall Ms. K. P. Carrington Mr. M. Webb Mr. P.J. Heher State of Georgia Mr. R. Dunn Oglethorpe Power Corporation Mr. M. W. Price Ms. A. Whaley Municipal Electric Authority of Georgia Mr. J. E. Fuller Mr. S. M. Jackson Dalton Utilities Mr. T. Bundros Westinghouse Electric Company, LLC Mr. L. Oriani (w/o enclosures)

Mr. T. Rubenstein (w/o enclosures)

Mr. M. Corletti Mr. D. Hawkins Mr. J. Coward Other Mr. S. W. Kline, Bechtel Power Corporation Ms. L. A. Matis, Tetra Tech NUS, Inc.

Dr. W. R. Jacobs, Jr., Ph.D., GDS Associates, Inc.

Mr. S. Roetger, Georgia Public Service Commission Ms. S. W. Kernizan, Georgia Public Service Commission Mr. K. C. Greene, Troutman Sanders Mr. S. Blanton, Balch Bingham

Southern Nuclear Operating Company ND-20-0601 Vogtle Electric Generating Plant Units 3 and 4 Inservice Testing Program Plan - 1st Interval Version 1.0 (This enclosure consists of 130 pages, not including this cover page.)

Version1.0 INSERVICETESTINGPROGRAMPLAN1stINTERVAL VogtleElectricGeneratingPlantUnits3&4 DocketNos.52025&52026 LicenseNos.NPF91&92 April28,2020

CommercialOperationdates:

TBD(Unit3)

TBD(Unit4)

Owner:SouthernNuclearOperatingCompany PostOfficeBox1295 Birmingham,AL352011295

PlantLocation:7825RiverRoad Waynesboro,GA30830

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

i SouthernNuclear

Version1.0 TABLEOFCONTENTS Section Pages 1.0 ISTPROGRAMINTRODUCTION 1112 2.0 ABBREVIATIONS 2123 3.0 PROGRAMALTERNATIVES 3134 4.0 INSERVICETESTINGOFPUMPS 41 5.0 INSERVICETESTINGOFVALVES 51 6.0 VALVENOTES 61 7.0 VEGP3VALVETABLES 71737 8.0 VEGP4VALVETABLES 81837 9.0 COLDSHUTDOWNJUSTIFICATIONS 91916 10.0 REFUELINGOUTAGEJUSTIFICATIONS 101-107 11.0 INSERVICETESTINGOFDYNAMICRESTRAINTS 111 12.0 DYNAMICRESTRAINTSNOTES 121 13.0 VEGP3DYNAMICRESTRAINTSTABLES 131-136 14.0 VEGP4DYNAMICRESTRAINTSTABLES 141-146

15.0 REFERENCES

151-155

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

11 SouthernNuclear

Version1.0 1.0 ISTPROGRAMINTRODUCTION 1.1 GENERAL ThisdocumentdescribesthePump,Valve,andDynamicRestraintInserviceTesting(IST)

ProgramPlanfortheFirst10yearIntervalatVogtleElectricGeneratingPlant(VEGP),Units3&

4.ProvidedbelowareimportantdatesrelativetotheISTPlan.

CombinedOperatingLicense:February10,2012(Unit3);February10,2012(Unit4)

ScheduledFuelLoad:November23,2020(Unit3);September23,2021(Unit4)

CommercialOperation:TBD(Unit3);TBD(Unit4) 1.2 CODEEDITION ThisISTPlanisbasedontheAmericanSocietyofMechanicalEngineers(ASME)Operationand MaintenanceofNuclearPowerPlants(OM)Code2012Edition.Thisthemostrecenteditionin 10CFR50.55aon11/23/2019(12monthspriortothescheduledUnit3fuelloaddate).An Alternativeper10CFR50.55a(z)(ISTAlt01)wasauthorizedbytheNRCtoallowUnit4tousethe sameCodeEditionasUnit3,providedUnit4initialfuelloadcommencespriortoNovember23, 2022(Reference15.1.6).

1.3 EFFECTIVEDATE TheISTProgramforthe1st10yearIntervalwillbeginwiththeinitialelectricalgenerationby nuclearheatoneachunit,andendafter10years,unlessfederalregulationsarerevised otherwise.

1.4 SCOPE ThisdocumentisadescriptionoftheISTProgramPlanforUnits3and4atVEGP.This documentdescribesonlytheISTrequiredbytheOMCodeforapplicablecomponentsrequired tobetestedbytheOMCode,10CFR50.55a,andadditionalcomponentscommittedtobe includedintheISTProgramPlanintheUpdatedFinalSafetyAnalysisReport(UFSAR).

ToensurethatcomponentswhichmeettheScoperequirementsoftheOMCode,butmaynot berequiredtoconstructedtoASMEB&PVCodeClass1,2or3,areadequatelytestedfor operationalreadinessasrequiredby10CFR50.55a(f)(4),thisISTplanincludesallSafetyRelated (AP1000QualitygroupA,B,C)pumps,valvesanddynamicrestraintsthatmeettheScopeof ISTA1100,ISTC1200andISTF1100.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

12 SouthernNuclear

Version1.0 1.5 SUBSEQUENTPROGRAMPLANREVISIONS Itisanticipatedthatrevisionstothisdocumentrequiredbychangestothedesignpriortoor duringtheFirst10yearInserviceIntervalwillbemaintainedbySouthernNuclearandsubmitted totheNRCasrequiredbytheOMCodeand10CFR50.55a.AnychangeswhichrequireNRC approvalofAlternativetestingrequirementswillbesubmittedinaccordancewith 10CFR50.55(a)(z).

Additionally,thisdocumentwillbereviewedandrevisedneartheendofthe120month interval,totherequirementsof10CFR50.55aforthenext120monthinterval.

1.6 RESPONSIBILITY SouthernNuclearOperatingCompany(SNC)bearstheoverallresponsibilityforthe implementationoftheInservicetestingactivitiescontainedinthisprogrampertheASMEOM Code2012Edition,SubsectionISTA1500.

1.7 RECORDS Recordsanddocumentationofinformationandtestingresults,whichprovidedthebasisfor evaluationandwhichfacilitatecomparisonwithresultsfrompreviousandsubsequenttests,will bemaintainedandavailablefortheactivelifeofthecomponentorsysteminaccordancewith theASMEOMCode2012Edition,SubsectionISTA9000.

1.8METHODSOFTESTING Themethodoftestingapplicabletothecomponentswillbecontainedintheplantspecific procedureswhichhavenotbeenfinalizedatthistimeandarenotreferencedinthisdocument.

TheproceduresarebeingdevelopedinaccordancewithOMCoderequirementsandNRC conditions.TheOMCodedoesnotstipulateanyspecifictraining/certificationrequirementsfor personnelinvolvedinOMCodetesting.AtPlantVogtleUnits3&4,alltestingisperformedby operations,maintenance,engineeringorcontractpersonnelwhohavebeentrainedtoperform specifictestingtasks.

1.9 STANDARDSFORTESTINGEVALUATION Theacceptancecriteriaapplicableforthecomponentstobetestedwillinitiallybedeveloped basedonPreservicetestingresults,andcalculationlimitationsintheaccidentanalyses,in accordancewithOMCoderequirements.Analysislimits,whereapplicableareprovidedinthe ISTBasisdocuments.Acceptancecriteriaforspecifictestswillbecontainedintheapplicable surveillancetestingprocedureswhichwillbeavailableforreviewattheplantsite.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

21 SouthernNuclear Version1.0 2.0ABBREVIATIONS ABBREVIATION DEFINITION A

Active(valvetable)

A OMCodeCategoryAValve(seeOMCode)

AC OMCodeCategoriesAandCbothapply(seeOMCode)

ADS AutomaticDepressurizationSystem AI AsIs Alt Alternativeper10CFR50.55a(z)

AO AirOperated A/P Active/Passive(valvetable)

App Appendix App.II CheckvalvetestingtoAppendixII(ConditionMonitoring)

App.J Leakratetestingto10CFR50AppendixJrequirements(CIV)

ASME AmericanSocietyofMechanicalEngineers ASMEOMCode ASMEOperationandMaintenanceofNuclearPowerPlantsCode Aug Augmentedscope(notrequiredbyASMEOMCode)

B OMCodeCategoryBValve(seeOMCode)

BC OMCodeCategoriesBandCbothapply(seeOMCode)

BA BallValve BU ButterflyValve

C OMCodeCategoryCValve(seeOMCode)

C Close/Closed CAS CompressedAirSystem Cat Category CC CodeCase CCS ComponentCoolingWaterSystem CFR CodeofFederalRegulations CK CheckValve CIV ContainmentIsolationValve CKC CheckValveClosed CKO CheckValveOpen CKOP CheckValvePartialOpening CMT CoreMakeupTank CoOrd.

Coordinate CS ColdShutdownfrequency CSJ ColdShutdownJustification CVS ChemicalandVolumeControlSystem CV CheckValve ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

22 SouthernNuclear Version1.0

D OMCodeCategoryDValve(seeOMCode)

DTPG DefinedTestPlanGroup(snubbers)

DVI DirectVesselInjection DWS DemineralizedWaterSystem

EH ElectroHydraulicOperated ETM ExerciseTestManualValve(Fullstroke)

FHS FuelHandlingSystem FPS FireProtectionSystem FST FailSafeTest

GA GateValve GL GlobeValve

H HydraulicSnubber

IRC InsideReactorContainmentbuilding IRWST InContainmentRefuelingWaterStorageTank

LC LockedClosed LO LockedOpen LT LeakTest

MA ManualOperator MO MotorOperated MSS MainSteamSystem MTS MainTurbineSystem

N No NA NotApplicable

O Open ORC OutsideReactorContainmentbuilding

P Passive(valvebasistable)

PCS PassiveContainmentCoolingSystem PH Pneumatic/Hydraulic PI RemotePositionIndicationVerification PIV PressureIsolationValve(seeUFSARTable3.918)

PORV PowerOperatedReliefValve ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

23 SouthernNuclear Version1.0 PL PlugValve PSS PrimarySamplingSystem PWS PotableWaterSystem PXS PassiveCoreCoolingSystem

RCS ReactorCoolantSystem RD RuptureDisc RNS NormalResidualHeatRemovalSystem RO RefuelingOutagefrequency ROJ RefuelingOutageJustification RRD ReplaceRuptureDisc RV ReliefValve RVT ReliefValveTest

SA SelfActuating SC StopCheckvalve SDS SanitaryDrainageSystem SFS SpentFuelPoolCoolingSystem SGS SteamGenerationSystem SO SolenoidOperated SQ Squib(explosivelyactuated)Valve STC StrokeTimeClosedtest STO StrokeTimeOpentest

VB VacuumBreaker VBS NuclearIslandNonRadioactiveVentilationSystem VE VisualExamination VES MainControlRoomEmergencyHabitabilitySystem VFS ContainmentAirFiltrationSystem VWS CentralChilledWaterSystem

WLS LiquidRadioactiveWasteSystem

Y Yes y

Year(s)

III3300 MOVperformancetestperASMEOMCodeApp.III3300 III3600 MOVexercisetestperASMEOMCodeApp.III3600

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

31 SouthernNuclear Version1.0 3.0 PROGRAMALTERNATIVES 3.1 ALTERNATIVES ThissectionidentifiestheAlternativestotherequirementsof10CFR50.55aandtheOMCode requestedunder10CFR50.55a(z)andapprovedbytheNRC.

SeeISTAlt01forusingthesameCodeEditionforUnit4asUnit3,whichwasauthorized 3/2/2020(Reference15.1.6).

3.2 CODECASES ThissectionidentifiestheCodeCases,andassociatedlimitations,thatareincorporatedinthis ISTplan.

CodeCaseOMN20,InserviceCodeFrequencyisusedforallcomponentsintheplanin establishingtestingfrequency,asauthorizedby10CFR50.55a(b)(3)(x).Onlythebasefrequency willbeshowninthecomponenttables.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

32 SouthernNuclear Version1.0 AlternativeVEGP3&4ISTALT01 Plant Site-Unit:

VogtleElectricGeneratingPlant(VEGP)-Unit4

IntervalInterval Dates:

Appliestotheinitialinservicetest(IST)intervalforUnit4.

ASMECode Components Affected:

AllcomponentsintheISTprogram.

ApplicableCode Editionand Addenda:

ASMEOperationandMaintenanceofNuclearPowerPlants(OM)Code,2012 Editionfor1stInserviceTestInterval.

ApplicableCode Requirements:

10CFR50.55a(f)(4)(i)requirestheASMEOMCodeeditionandaddendafor the initial IST interval be the latest edition and addenda incorporated by referencein10CFR50.55a(a)(1)(iv)12monthsbeforethedatescheduledfor initialloadingoffuelunderacombinedlicenseunder10CFRpart52.

TheOMCode,ISTA3200hasthesamerequirementsforestablishingtheCode EditionfortheInitialInserviceTestInterval(inISTA3200(f)(2)).

Reasonfor Request:

WithaoneyeargapbetweenthescheduledfuelloadingsofVogtleUnit3and Unit4,thereisthepossibilitythattheCodeEditionrequiredfortheInservice Testprogramplanwillbedifferentbetweenthetwounits.Becausethetwo units are nearly identical, the Combined License application was for both units,andbothunitsshareacommonUFSAR,itwouldcreateinconsistencies betweenthetwounitsthatwouldincreasethecomplexityoftheUFSARand testing programs that would increase the probability of human error in developingandimplementingtwodifferentprograms.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

33 SouthernNuclear Version1.0

TominimizetheproblemsofdevelopingandimplementingtwoseparateIST Programs,itwouldbepreferabletohavebothISTProgramsbedevelopedto theCodeEditionandAddendarequiredfortheleadunit(Unit3).

Based on the current scheduled initial loading of fuel for Unit 3 being November23,2020,andthecurrentscheduleforadditionofASMEOMCode Editionsto10CFR50.55abeinglateFebruary2020,thecurrentlatestedition of the OM Code listed in 10CFR50.55a (2012 Edition) would be used for establishingtheinitial120monthintervalISTProgramsforVogtle3&4.

Proposed Alternativeand BasisforUse:

ProposedAlternative:

Inlieuoftherequirementsof10CFR50.55a(f)(4)(i),forestablishingtheASME OMCodeeditionandaddendafortheinitialInserviceTestinterval,andthe equivalent requirements in ISTA3200(f)(2), it is proposed that the Code EditionfortheinitialUnit4ISTIntervalbethesameeditionand/oraddenda as established for the associated initial Unit 3 Interval (which will be establishedinaccordancewith10CFR50.55a(f)(4)(i)).

BasisforUse:

HavingbothunitsonthesameCodeEditionfortheirinitialintervalsallows bothISTprogramstobedevelopedutilizingthesameeditionoftheapplicable Codes,whichwillmakeitlesscomplicatedforinvolvedpersonneltobecome familiar with the Code requirements, will ensure a greater degree of consistencyforISTbetweentheunits,andwillreducetheeffortassociated with surveillance procedure revisions for the program update and for maintenanceoftheprogramdocuments.

The Code of Record established for Unit 3 is in accordance with the 10CFR50.55arequirementsandrepresentsrequirementsestablishedbythe NRC to ensure the equipment is adequately tested to ensure safe plant operation.ApplyingacommonCodeeditiontobothUnit3andUnit4would establish common requirements which would minimize potential errors causedbyhavingtomaintaintwoseparateprogramrequirementsforthe2 units.Additionally,basedontheversionoftheCodeanticipatedforUnit3 IST program, the units will use the same Code Edition as that used for Preservicetesting,whichwillensureconsistencyofPreservicetoInservice testing.

PerNUREG1482,Rev.2,Basisfor3.3.2,ConcurrentIntervalsstatesThestaff believesthatconductingISTprogramsformultipleunitsitesusingthesame Codeeditioncouldprovideanimprovementinprogrameffectiveness.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

34 SouthernNuclear Version1.0 Basedontheabove,theproposedalternativeprovidesanequivalentlevelof qualityandsafetyinaccordancewith10CFR50.55a(z)(1).

Durationof Proposed Alternative:

ThroughtheendofthefirstVogtleUnit4ISTinterval.

References:

1. Vogtle1&2GeneralReliefRequestRRG2(LegacyAccessionNumber 9608200192).
2. NRCApprovalletterforRRG1&RRG2,dated11/27/1996(Legacy AccessionNumber9612020101)
3. NUREG1482,Rev.2,Section3.3.2,ConcurrentIntervals.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

41 SouthernNuclear Version1.0 4.0 INSERVICETESTINGOFPUMPS 4.1 GENERAL TherearenopumpsintheAP1000designthatmeetthescopingcriteriaofISTF1100.ISTF 1000whichprovidesthescopingcriteriaforpumpstobeincludedintheISTplan,includes onlypumpsthathaveanemergencypowersource.Theemergencypowersource(Class1E) fortheAP1000istheClass1EDCDistributionsystem,andtherearenopumpspowered fromthissource.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

51 SouthernNuclear Version1.0 5.0 INSERVICETESTINGOFVALVES 5.1 GENERAL ValvesinthisprogramareidentifiedbythecomponentnumberintablesforUnits3and4 respectively,andwillbetestedinaccordancewiththeOMCodeand10CFR50.55a conditions,unlessotherwisespecifiedinthisprogram.

5.2 ADDITIONALTESTINGREQUIREMENTS 10CFR50.55(a)providesconditionstotheOMCodewithregardtotestingofcertainvalves.

TheseconditionsaremetinthisISTProgramPlanasoutlinedbelow:

5.2.1 Tomeetthe10CFR50.55a(b)(3)(ii)(D)ConditiononMOVstroketime.Astroke timetesttothesafetyposition(s)isspecifiedforallactiveMOVsintheprogram.

5.2.2 Tomeetthe10CFR50.55a(b)(3)(iii)(B)CheckvalvesrequiringLicenseesmust performbidirectionaltestingofcheckvalves,isspecifiedinaccordancewith ISTC5221withinthisISTProgramPlan,wherepracticable.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

61 SouthernNuclear Version1.0 6.0 VALVENOTES

1. ForallactivePowerOperatedValvesthereisarequirementforexercisetesting,andstroke timingofthevalveinthedirectionrequiredtoperformthesafetyfunctionofthevalve.For thepurposeofthisplan,theexercisingrequirementisnotcalledoutseparately,onlythe stroketimetest,whichincludesexercisingofthevalve,isshowninthevalvetable.
2. Squibvalvecharges,aminimumof20%aretestedeveryoutage(2y),withaminimumofone fromeachsafetytrain.Circuittestingtoverifyproperelectricalparameters(voltage,current) toactuatesquibchargetobeperformedonvalvesselectedforsquibtesting.
3. Squibvalvesdisassembly/inspectionisperformedononevalveofeachsizeeachoutage(2y),

buteachvalvemustbedisassembled/inspectedevery10years.

4. Stopcheckwithmanualoperatorformaintenanceonly.Operatesasacheckvalve.
5. SFSV071&SFSV072areexercisedperISTC5221(c),onevalvedisassembled/strokeverified eachrefuelingoutage.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

71 SouthernNuclear Version1.0 7.0 VEGP3VALVETABLES

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

72 SouthernNuclear

Version1.0 VOGTLEUNIT3 CAS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3CASPLV014 2

N A

A 2

BA AO SV3CASM6005 O

C C

PI 2y

F3

STC RO ROJCAS1

FST RO ROJCAS1 InstrumentAirContainmentIsolationValve

LT App.J

SV3CASPLV015 2

N AC A

2 CK SA SV3CASM6005 O

C/O NA CKC RO ROJCAS1

F4

CKOP RO ROJCAS1 ThermalExpansion InstrumentAirContainmentIsolationCheckValve

LT App.J

SV3CASPLV204 2

N A

P 3

BA MA SV3CASM6012 LC C

AI LT App.J

ServiceAirContainmentIsolationValve

E5

SV3CASPLV205 2

N AC A

3 CK SA SV3CASM6012 C

C/O NA CKC CS CSJCAS1

E4

CKOP CS CSJCAS1 ThermalExpansion ServiceAirContainmentIsolationCheckValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

73 SouthernNuclear

Version1.0 VOGTLEUNIT3 CCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3CCSPLV200 2

N A

A 10 BU MO SV3CCSM6002 O

C AI PI 2RO/3y

H2

STC/III3600 2y

III3300 2RO/3y

CoolingWaterSupplyCtmtIsolORC

LT App.J

SV3CCSPLV201 2

N AC A

10 CK SA SV3CCSM6002 O

C/O NA CKC RO ROJCCS1

H2

CKOP RO ROJCCS1 ThermalExpanison CoolingWaterCtmtSupplyCheck

LT App.J

SV3CCSPLV207 2

N A

A 10 BU MO SV3CCSM6002 O

C AI PI 2RO/3y

B2

STC/III3600 2y

III3300 2RO/3y

CoolingWaterReturnCtmtIsolIRC

LT App.J

SV3CCSPLV208 2

N A

A 10 BU MO SV3CCSM6002 O

C AI PI 2RO/3y

B1

STC/III3600 2y

III3300 2RO/3y

CoolingWaterReturnyCtmtIsolORC

LT App.J

SV3CCSPLV220 2

N AC A

1 RV SA SV3CCSM6002 C

O/C NA RVT 10y

ThermalRelief CtmtReturnCIVThermalRelief

C2

LT App.J

SV3CCSPLV270 3

N C

A 4

RV SA SV3CCSM6002 C

O NA RVT 4y/10y

CCSSupplyLinetoCtmtSafety/Relief

H2

SV3CCSPLV271 3

N C

A 4

RV SA SV3CCSM6002 C

O NA RVT 4y/10y

CCSReturnLinetoCtmtSafety/Relief

C2

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

74 SouthernNuclear

Version1.0 VOGTLEUNIT3 CVS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3CVSPLV001 1

N B

A 3

GA MO SV3CVSM6001 O

C AI PI 2RO/3y

G8

STC/III3300 2y

CVSPurificationStopValve

III3300 2RO/3y

SV3CVSPLV002 1

N B

A 3

GA MO SV3CVSM6001 O

C AI PI 2RO/3y

G7

STC/III3300 2y

CVSPurificationStopValve

III3300 2RO/3y

SV3CVSPLV003 3

N B

A 3

GL MO SV3CVSM6001 O

C AI PI 2RO/3y

G7

STC/III3300 2y

CVSPurificationStopValve

III3300 2RO/3y

SV3CVSPLV040 2

N A

P 2

BA MA SV3CVSM6005 LC C

AI LT App.J

ResinFlushIRCIsolationValve

F4

SV3CVSPLV041 2

N A

P 2

BA MA SV3CVSM6005 LC C

AI LT App.J

ResinFlushORCIsolationValve

F4

SV3CVSPLV042 2

N AC A

1 RV SA SV3CVSM6005 C

O/C NA RVT 10y

ThermalRelief FlushLineContainmentIsolationReliefValve

G4

LT App.J

SV3CVSPLV045 2

N A

A 2

GL AO SV3CVSM6005 C

C C

PI 2y

D4

STC Q

FST Q

LetdownLineInsideContainmentIsolationValve

LT App.J

SV3CVSPLV047 2

N A

A 2

GL AO SV3CVSM6005 C

C C

PI 2y

D2

STC Q

FST Q

LetdownLineOutsideContainmentIsolationValve

LT App.J

SV3CVSPLV058 2

N AC A

1 RV SA SV3CVSM6005 C

O/C NA RVT 10y

ThermalRelief LetdownLinetoDegassifierContainmentIsolationThermalReliefValveE4

LT App.J

SV3CVSPLV064 N

N C

A 3

CK SA SV3CVSM6005 C

O NA CKOP CS CSJCVS2 ThermalExpansion MakeupDischargeHeaderCheckValve

C5

CKC CS CSJCVS2

SV3CVSPLV067 1

N C

A 1

CK SA SV3CVSM6001 O

C/O NA CKOP CS CSJCVS1 ThermalExpansion MakeupReturnLineSpringAssistedCheckValve

F7

CKC CS CSJCVS1

SV3CVSPLV080 3

N C

A 3

CK SA SV3CVSM6001 O

C/O NA CKOP CS CSJCVS1 ThermalExpansion RegenHXShellSideOutletCheckValve

G7

CKC CS CSJCVS1

SV3CVSPLV081 1

N BC A

3 SC AO SV3CVSM6001 O

C NA CKOP CS CSJCVS1

PurificationReturnLineStopCheckValve

G7

CKC CS CSJCVS1

SV3CVSPLV082 1

N C

A 3

CK SA SV3CVSM6001 O

C/O NA CKOP CS CSJCVS1 ThermalExpansion RCSPurificationReturnLineCheckValve

G8

CKC CS CSJCVS1

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

75 SouthernNuclear

Version1.0 VOGTLEUNIT3 CVS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3CVSPLV084 1

N B

A 2

GL AO SV3CVSM6001 C

C C

PI 2y

F7

STC RO ROJCVS1 AuxiliaryPressurizerSprayLineIsolationValve

FST RO ROJCVS1

SV3CVSPLV085 1

N C

A 2

CK SA SV3CVSM6001 C

C/O NA CKC RO ROJCVS1

AuxiliaryPressurizerSprayLineCheckValve

F8

CKOP RO ROJCVS1 ThermalExpansion

SV3CVSPLV090 2

N A

A 3

GA MO SV3CVSM6005 O

C AI PI 2RO/3y

C2

STC/III3600 2y

III3300 2RO/3y

MakeupLineOutsideContainmentIsolationValve

LT App.J

SV3CVSPLV091 2

N A

A 3

GA MO SV3CVSM6005 O

C AI PI 2RO/3y

C4

STC/III3600 2y

III3300 2RO/3y

MakeupLineInsideContainmentIsolationValve

LT App.J

SV3CVSPLV092 2

N A

A 1

GL AO SV3CVSM6003 O

C C

PI 2y

F6

STC Q

FST Q

ZincInjectionContainmentIsolationValveORC

LT App.J

SV3CVSPLV094 2

N A

A 1

GL AO SV3CVSM6003 O

C C

PI 2y

F7

STC Q

FST Q

ZincInjectionContainmentIsolationValveIRC

LT App.J

SV3CVSPLV098 2

N AC A

1 RV SA SV3CVSM6003 C

O/C NA RVT 10y

ThermalRelief ZincInjectionCtmtIsolThermalReliefValve

F6

LT App.J

SV3CVSPLV100 2

N AC A

1 CK SA SV3CVSM6005 C

C/O NA CKC CS CSJCVS2

B4

CKOP CS CSJCVS2 ThermalExpansion MakeupLineContainmentIsolationRelief

LT App.J

SV3CVSPLV136A 3

N B

A 3

BU AO SV3CVSM6004 C

C C

PI 2y

C4

STC Q

DemineralizedWaterSystemIsolationValve

FST Q

SV3CVSPLV136B 3

N B

A 3

BU AO SV3CVSM6004 C

C C

PI 2y

C4

STC Q

DemineralizedWaterSystemIsolationValve

FST Q

SV3CVSPLV217 2

N AC A

1/2 CK SA SV3CVSM6003 O

C/O NA CKC Q

D7

CKOP Q

ThermalExpansion HydrogenInjectionContainmentIsolationCheckValveIRC

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

76 SouthernNuclear

Version1.0 VOGTLEUNIT3 CVS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3CVSPLV219 2

N A

A 1/2 GL AO SV3CVSM6003 O

C C

PI 2y

D6

STC Q

FST Q

ZincInjectionContainmentIsolationValveIRC

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

77 SouthernNuclear

Version1.0 VOGTLEUNIT3 DWS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3DWSPLV241 3

N C

A 1

RV SA SV3DWSM6007 C

O NA RVT 10y ThermalRelief DeminWaterSupplytoContainmentRelief

E5

SV3DWSPLV244 2

N A

P 3

BU MA SV3DWSM6007 LC C

AI LT App.J

DeminWaterSupplyContainmentIsolationValveOutside

E6

SV3DWSPLV245 2

N AC A

2 CK SA SV3DWSM6007 C

C/O NA CKC CS CSJDWS1

E6

CKOP CS CSJDWS1 ThermalExpansion DeminWaterSupplyContainmentIsolationCheckValveIRC

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

78 SouthernNuclear

Version1.0 VOGTLEUNIT3 FHS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3FHSPLV001 3

N B

A 30 GA MA SV3SFSM6012 C

C AI ETM 2y

FuelTransferTubeIsolationValve

F6

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

79 SouthernNuclear

Version1.0 VOGTLEUNIT3 FPS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3FPSPLV050 2

N A

P 6

BU MA SV3FPSM6004 LC C

AI LT App.J

FireWaterContainmentSupplyIsolation

F4

SV3FPSPLV052 2

N AC A

6 CK SA SV3FPSM6004 C

C/O NA CKC CS CSJFPS1

F5

CKOP CS CSJFPS1 ThermalExpansion

FireWaterSupplyCtmtIsolCheckValveIRC

LT App.J

SV3FPSPLV702 3

N C

A 1

RV SA SV3FPSM6004 C

O NA RVT 10y

ThermalRelief FireWaterSupplyICThermalRelief

F/G5

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

710 SouthernNuclear

Version1.0 VOGTLEUNIT3 MSS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3MSSPLV001 N

Y B

A 16 GL AO SV3MSSM6001 C

C C

PI 2y

H8

STC Q

TurbineBypassControlValve

FST Q

SV3MSSPLV002 N

Y B

A 16 GL AO SV3MSSM6001 C

C C

PI 2y

H7

STC Q

TurbineBypassControlValve

FST Q

SV3MSSPLV003 N

Y B

A 16 GL AO SV3MSSM6001 C

C C

PI 2y

H6

STC Q

TurbineBypassControlValve

FST Q

SV3MSSPLV004 N

Y B

A 16 GL AO SV3MSSM6001 C

C C

PI 2y

H4

STC Q

TurbineBypassControlValve

FST Q

SV3MSSPLV005 N

Y B

A 16 GL AO SV3MSSM6001 C

C C

PI 2y

H3

STC Q

TurbineBypassControlValve

FST Q

SV3MSSPLV006 N

Y B

A 16 GL AO SV3MSSM6001 C

C C

PI 2y

H2

STC Q

TurbineBypassControlValve

FST Q

SV3MSSPLV015A N Y

B A

10 GL AO SV3MSSM6001 O

C C

PI 2y

B6

STC CS CSJMSS1 MSR2ndStageReheatSteamAOIsolationValve

FST CS CSJMSS1

SV3MSSPLV015B N

Y B

A 10 GL AO SV3MSSM6001 O

C C

PI 2y

G6

STC CS CSJMSS1 MSR2ndStageReheatSteamAOIsolationValve

FST CS CSJMSS1

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

711 SouthernNuclear

Version1.0 VOGTLEUNIT3 MTS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3MTSPLV001A N Y

B A

28 GL EH SV3MTSM6002 O

C C

PI 2y

F6

STC Q

MainStopValve#1

FST Q

SV3MTSPLV001B N

Y B

A 28 GL EH SV3MTSM6002 O

C C

PI 2y

C6

STC Q

MainStopValve#3

FST Q

SV3MTSPLV002A N Y

B A

28 GL EH SV3MTSM6002 O

C C

PI 2y

F6

STC Q

ControlValve#1

FST Q

SV3MTSPLV002B N

Y B

A 28 GL EH SV3MTSM6002 O

C C

PI 2y

C6

STC Q

ControlValve#3

FST Q

SV3MTSPLV003A N Y

B A

28 GL EH SV3MTSM6002 O

C C

PI 2y

E6

STC Q

MainStopValve#2

FST Q

SV3MTSPLV003B N

Y B

A 28 GL EH SV3MTSM6002 O

C C

PI 2y

D6

STC Q

MainStopValve#4

FST Q

SV3MTSPLV004A N Y

B A

28 GL EH SV3MTSM6002 O

C C

PI 2y

E6

STC Q

ControlValve#2

FST Q

SV3MTSPLV004B N

Y B

A 28 GL EH SV3MTSM6002 O

C C

PI 2y

D6

STC Q

ControlValve#4

FST Q

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

712 SouthernNuclear

Version1.0 VOGTLEUNIT3 PCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PCSPLV001A 3

N B

A 6

BU AO SV3PCSM6001 C

O O

PI 2y

E4

STO Q

PCSActuationValveA

FST Q

SV3PCSPLV001B 3

N B

A 6

BU AO SV3PCSM6001 C

O O

PI 2y

E6

STO Q

PCSActuationValveB

FST Q

SV3PCSPLV001C 3

N B

A 6

GA MO SV3PCSM6001 C

O AI PI 2RO/3y

E5

STO/III3600 Q

PCSActuationValveC

III3300 2RO/3y

SV3PCSPLV002A 3

N B

A 6

GA MO SV3PCSM6001 O

O AI PI 2RO/3y

E4

STO/III3600 2y

PCSIsolationValveA

III3300 2RO/3y

SV3PCSPLV002B 3

N B

A 6

GA MO SV3PCSM6001 O

O AI PI 2RO/3y

E6

STO/III3600 2y

PCSIsolationValveB

III3300 2RO/3y

SV3PCSPLV002C 3

N B

A 6

GA MO SV3PCSM6001 O

O AI PI 2RO/3y

E5

STO/III3600 2y

PCSIsolationValveC

III3300 2RO/3y

SV3PCSPLV005 3

N B

A 4

GA MA SV3PCSM6002 O

C AI ETM 2y

PCStoDWS/FPSIsoValve

G5

SV3PCSPLV009 3

N B

A 3

GA MA SV3PCSM6001 C

O/C AI ETM 2y

SpentFuelPoolEmergencyMakeupValve

E4

SV3PCSPLV015 3

N B

A 1

GL MA SV3PCSM6002 O

C AI ETM 2y

PCSLongTermSupplytoDistributionBucketDrainValve

G8

SV3PCSPLV020 3

N B

A 3

GA MA SV3PCSM6002 C

O AI ETM 2y

PCSLongTermSupplytoDistributionBucketIsoValve

E4

SV3PCSPLV023 3

N B

A 4

GA MA SV3PCSM6002 O

C AI ETM 2y

PCSRecircPumpstoPCCWSTIsoValve

F7

SV3PCSPLV039 3

N C

A 4

CK SA SV3PCSM6002 C

C/O NA CKC App.II PCS/SFSLongTermMakeupSupplyCheckValve

F4

CKO App.II

SV3PCSPLV042 3

N B

A 1

GL MA SV3PCSM6002 O

C AI ETM 2y

PCSLongTermSupplyfromTempPumpDrainValve

F3

SV3PCSPLV044 3

N B

A 4

GA MA SV3PCSM6002 C

O AI ETM 2y

PCSLongTermSupplyfromTempPumpIsoValve

F4

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

713 SouthernNuclear

Version1.0 VOGTLEUNIT3 PCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PCSPLV045 3

N B

A 2

GL MA SV3PCSM6001 C

O AI ETM 2y

PCSSupplytoSFSMakeupIsoValve

B3

SV3PCSPLV046 3

N B

A 4

GA MA SV3PCSM6002 O

C AI ETM 2y

PCCWSTRecirculationReturnIsolationValve

H7

SV3PCSPLV049 3

N B

A 1

GL MA SV3PCSM6001 O

C AI ETM 2y

PCCWSTDrainIsolationValve

C2

SV3PCSPLV050 3

N B

A 2

GL MA SV3PCSM6002 C

C/O AI ETM 2y

RecircHeaderDischargetoSFSPoolIsolationValve

F7

SV3PCSPLV051 3

N B

A 2

GL MA SV3PCSM6001 C

C/O AI ETM 2y

SpentFuelPoolEmergencyMakeupLowerIsolationValve

B2

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

714 SouthernNuclear

Version1.0 VOGTLEUNIT3 PSS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PSSPLV001A 2

N C

A 1/4 GL SO SV3PSSM6003 O

O C

RVT 10y

ThermalRelief HotLeg1SampleIsolation

E8

SV3PSSPLV001B 2

N C

A 1/4 GL SO SV3PSSM6003 C

O C

RVT 10y

ThermalRelief HotLeg2SampleIsolation

D8

SV3PSSPLV003 2

N C

A 1/4 GL SO SV3PSSM6003 C

O C

RVT 10y

ThermalRelief PzrSampleIsolation

G8

SV3PSSPLV008 2

N A

A 5/8 GL SO SV3PSSM6001 O

C C

PI 2y

D7

STC Q

FST Q

ContainmentAirSampleContainmentIsolationValveIRC

LT App.J

SV3PSSPLV010A 2

N AC A

1/4 GL SO SV3PSSM6001 O

C C

PI 2y

D7

STC Q

FST Q

LT App.J LiquidSampleLineContainmentIsolationValve AIRC

RVT 10y

ThermalRelief

SV3PSSPLV010B 2

N AC A

1/4 GL SO SV3PSSM6001 C

C C

PI 2y

G7

STC Q

FST Q

LT App.J LiquidSampleLineContainmentIsolationValve BIRC

RVT 10y

ThermalRelief

SV3PSSPLV011A 2

N A

A 1/4 GL AO SV3PSSM6001 O

C C

PI 2y

E6

STC Q

FST Q

LiquidSampleLineContainmentIsolationValve AORC

LT App.J

SV3PSSPLV011B 2

N A

A 1/4 GL AO SV3PSSM6001 C

C C

PI 2y

G6

STC Q

FST Q

LiquidSampleLineContainmentIsolationValve BORC

LT App.J

SV3PSSPLV023 2

N A

A 1

GL AO SV3PSSM6001 O

C C

PI 2y

C6

STC Q

FST Q

CtmtAirSampleReturnIsolationValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

715 SouthernNuclear

Version1.0 VOGTLEUNIT3 PSS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PSSPLV024 2

N A

A 1

GL SO SV3PSSM6001 O

C C

PI 2y

C7

STC Q

FST Q

CtmtLiquidandAirSampleReturnIRCIsolValve

LT App.J

SV3PSSPLV046 2

N A

A 5/8 GL AO SV3PSSM6001 O

C C

PI 2y

D6

STC Q

FST Q

AirSampleLineCtmtIsolORCValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

716 SouthernNuclear

Version1.0 VOGTLEUNIT3 PWS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PWSPLV418 3

N B

A 1

GL MA SV3PCSM6002 O

C AI ETM 2y

ControlRoomBoundaryOutsideIsolationValve

G4

SV3PWSPLV420 3

N B

A 1

GL MA SV3PCSM6002 O

C AI ETM 2y

ControlRoomBoundaryInsideIsolationValve

F4

SV3PWSPLV498 3

N C

A 1

VB SA SV3PWSM6002 C

O NA VB 2y

VacuumBreaker CtmtReturnCIVThermalRelief

F4

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

717 SouthernNuclear

Version1.0 VOGTLEUNIT3 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PXSPLV002A 1

N B

P 8

GA MO SV3PXSM6001 O

O AI PI 2y

RCStoCMTAIsolationValve

G/H5

SV3PXSPLV002B 1

N B

P 8

GA MO SV3PXSM6001 O

O AI PI 2y

RCStoCMTBIsolationValve

G/H4

SV3PXSPLV013A 1

N B

P 8

GA MA SV3PXSM6001 LO O

AI PI 2y

CMTADischargeManualIsolValve

D/E6

SV3PXSPLV013B 1

N B

P 8

GA MA SV3PXSM6001 LO O

AI PI 2y

CMTBDischargeManualIsolValve

D/E3

SV3PXSPLV014A 1

N B

A 8

GL AO SV3PXSM6001 C

O O

PI 2y

E7

STO Q

CMTAOutletValve

FST Q

SV3PXSPLV014B 1

N B

A 8

GL AO SV3PXSM6001 C

O O

PI 2y

E3

STO Q

CMTBOutletValve

FST Q

SV3PXSPLV015A 1

N B

A 8

GL AO SV3PXSM6001 C

O O

PI 2y

D7

STO Q

CMTAOutletValve

FST Q

SV3PXSPLV015B 1

N B

A 8

GL AO SV3PXSM6001 C

O O

PI 2y

D3

STO Q

CMTBOutletValve

FST Q

SV3PXSPLV016A 1

N C

A 8

CK SA SV3PXSM6001 O

O/C NA CKO RO ROJPXS1

CMTAOutletCheckValve

D/E6

CKC RO ROJPXS1

SV3PXSPLV016B 1

N C

A 8

CK SA SV3PXSM6001 O

O/C NA CKO RO ROJPXS1

CMTBOutletCheckValve

D/E3

CKC RO ROJPXS1

SV3PXSPLV017A 1

N C

A 8

CK SA SV3PXSM6001 O

O/C NA CKO RO ROJPXS1

CMTAOutletCheckValve

D/E6

CKC RO ROJPXS1

SV3PXSPLV017B 1

N C

A 8

CK SA SV3PXSM6001 O

O/C NA CKO RO ROJPXS1

CMTBOutletCheckValve

D/E3

CKC RO ROJPXS1

SV3PXSPLV021A 3

N B

P 1

GL SO SV3PXSM6001 C

C C

PI 2y

AccumulatorANitrogenSupplyValve

C7

SV3PXSPLV021B 3

N B

P 1

GL SO SV3PXSM6001 C

C C

PI 2y

AccumulatorBNitrogenSupplyValve

C2

SV3PXSPLV022A 3

N C

A 1

RV SA SV3PXSM6001 C

O/C NA RVT 4y/10y

AccumulatorAReliefValve

C7

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

718 SouthernNuclear

Version1.0 VOGTLEUNIT3 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PXSPLV022B 3

N C

A 1

RV SA SV3PXSM6001 C

O/C NA RVT 4y/10y

AccumulatorBReliefValve

C2

SV3PXSPLV027A 3

N B

P 8

GA MO SV3PXSM6001 O

O AI PI 2y

AccumulatorAtoRCSIsolationValve

B6

SV3PXSPLV027B 3

N B

P 8

GA MO SV3PXSM6001 O

O AI PI 2y

AccumulatorBtoRCSIsolationValve B3

SV3PXSPLV028A 1

N AC A

8 CK SA SV3PXSM6001 C

O/C NA CKC RO ROJPXS2

B6

CKO RO ROJPXS2

AccumulatorAOutlettoRCSCheck

LT 2y

PIV

SV3PXSPLV028B 1

N AC A

8 CK SA SV3PXSM6001 C

O/C NA CKC RO ROJPXS2

B3

CKO RO ROJPXS2

AccumulatorBOutlettoRCSCheck

LT 2y

PIV

SV3PXSPLV029A 1

N AC A

8 CK SA SV3PXSM6001 C

O/C NA CKC RO ROJPXS2

B6

CKO RO ROJPXS2

AccumulatorAOutlettoRCSCheck

LT 2y

PIV

SV3PXSPLV029B 1

N AC A

8 CK SA SV3PXSM6001 C

O/C NA CKC RO ROJPXS2

B4

CKO RO ROJPXS2

AccumulatorBOutlettoRCSCheck

LT 2y

PIV

SV3PXSPLV042 2

N A

A 1

GL AO SV3PXSM6001 O

C C

PI 2y

D1

STC Q

FST Q

HighPressureNitrogentoContainmentIsolationValve

LT App.J

SV3PXSPLV043 2

N AC A

1 CK SA SV3PXSM6001 C

O/C NA CKC Q

D2

CKOP Q

ThermalExpansion

HighPressureNitrogentoContainmentICCheckValve

LT App.J

SV3PXSPLV044 N

N C

A 1

RV SA SV3PXSM6001 C

O NA RVT 10y

ThermalRelief HighPressureNitrogentoContainmentPenetrationThermalReliefValveD2

SV3PXSPLV101 1

N B

P 14 GA MO SV3PXSM6002 O

O AI PI 2y

RCStoPRHRHeatExchangerIsolationValve

G1

SV3PXSPLV108A 1

N B

A 14 BA AO SV3PXSM6002 C

O O

PI 2y

G1

STO CS CSJPXS1 PRHRHeatExchangerOutletValvetoRCSA

FST CS CSJPXS1

SV3PXSPLV108B 1

N B

A 14 BA AO SV3PXSM6002 C

O O

PI 2y

F1

STO CS CSJPXS1 PRHRHeatExchangerOutletValvetoRCSB

FST CS CSJPXS1

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

719 SouthernNuclear

Version1.0 VOGTLEUNIT3 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PXSPLV109 1

N B

P 14 GA MA SV3PXSM6001 LO O

AI PI 2y

RCStoPRHRHeatExchangerIsolationValve

F1

SV3PXSPLV117A 3

N B

P 8

GA MO SV3PXSM6002 O

O AI PI 2y

ContainmentRecirculationAtoRCSIsolationValve

E7

SV3PXSPLV117B 3

N B

P 8

GA MO SV3PXSM6002 O

O AI PI 2y

ContainmentRecirculationBtoRCSIsolationValve

E5

SV3PXSPLV118A 3

N D

A 8

SQ SQ SV3PXSM6002 C

O AI RemoteInsp 2y

E7

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ContainmentRecirc.SumpAtoRCSActuationSquibValve

Disass.Insp 10y

Note3

SV3PXSPLV118B 3

N D

A 8

SQ SQ SV3PXSM6002 C

O AI RemoteInsp 2y

E5

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ContainmentRecirc.SumpBtoRCSActuationSquibValve

Disass.Insp 10y

Note3

SV3PXSPLV119A 3

N C

A 8

CK NA SV3PXSM6002 C

O/C NA PI 2y

E7

CKC RO ROJPXS3

ContainmentRecirc.SumpAOutlettoRCSCheck

CKO RO ROJPXS3

SV3PXSPLV119B 3

N C

A 8

CK NA SV3PXSM6002 C

O/C NA PI 2y

E5

CKC RO ROJPXS3

ContainmentRecirc.SumpAOutlettoRCSCheck

CKO RO ROJPXS3

SV3PXSPLV120A 3

N D

A 8

SQ SQ SV3PXSM6002 C

O AI RemoteInsp 2y

E7

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ContainmentRecirc.SumpAtoRCSActuationSquibValve

Disass.Insp 10y

Note3

SV3PXSPLV120B 3

N D

A 8

SQ SQ SV3PXSM6002 C

O AI RemoteInsp 2y

E5

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ContainmentRecirc.SumpBtoRCSActuationSquibValve

Disass.Insp 10y

Note3

SV3PXSPLV121A 3

N B

P 8

GA MO SV3PXSM6002 O

O AI PI 2y

IRWST/Recirc.SumptoRCSAIsolationValve

D7

SV3PXSPLV121B 3

N B

P 8

GA MO SV3PXSM6002 O

O AI PI 2y

IRWST/Recirc.SumptoRCSBIsolationValve

D7

SV3PXSPLV122A 1

N C

A 8

CK SA SV3PXSM6002 C

O/C NA PI 2y

C7

CKC CS CSJPXS2

IRWSTInjectionLineACheckValve

CKO CS CSJPXS2

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

720 SouthernNuclear

Version1.0 VOGTLEUNIT3 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PXSPLV122B 1

N C

A 8

CK SA SV3PXSM6002 C

O/C NA PI 2y

C5

CKC CS CSJPXS2

IRWSTInjectionLineBCheckValve

CKO CS CSJPXS2

SV3PXSPLV123A 1

N D

A 8

SQ SQ SV3PXSM6002 C

O AI RemoteInsp 2y

C7

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

IRWSTInjectionAIsolationValve

Disass.Insp 10y

Note3

SV3PXSPLV123B 1

N D

A 8

SQ SQ SV3PXSM6002 C

O AI RemoteInsp 2y

C5

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

IRWSTInjectionBIsolationValve

Disass.Insp 10y

Note3

SV3PXSPLV124A 1

N C

A 8

CK NA SV3PXSM6002 C

O/C NA PI 2y

C7

CKC CS CSJPXS2

IRWSTInjectionLineACheckValve

CKO CS CSJPXS2

SV3PXSPLV124B 1

N C

A 8

CK NA SV3PXSM6002 C

O/C NA PI 2y

C5

CKC CS CSJPXS2

IRWSTInjectionLineBCheckValve

CKO CS CSJPXS2

SV3PXSPLV125A 1

N D

A 8

SQ SQ SV3PXSM6002 C

O AI RemoteInsp 2y

C7

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

IRWSTInjectionAIsolationValve

Disass.Insp 10y

Note3

SV3PXSPLV125B 1

N D

A 8

SQ SQ SV3PXSM6002 C

O AI RemoteInsp 2y

C5

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

IRWSTInjectionBIsolationValve

Disass.Insp 10y

Note3

SV3PXSPLV130A 3

N B

A 2

BA AO SV3PXSM6002 O

C C

PI 2y

H7

STC Q

IRWSTGutterIsolationAValve

FST Q

SV3PXSPLV130B 3

N B

A 2

BA AO SV3PXSM6002 O

C C

PI 2y

H7

STC Q

IRWSTGutterIsolationBValve

FST Q

SV3PXSPLV208A 2

N A

P 3/8 GL MA SV3PXSM6003 LC C

AI LT App.J

RNSSuctionLeakTestValve

D3

SV3PXSPLV230A 2

N B

P 1

GL AO SV3PXSM6003 C

C C

PI 2y

CoreMakeupTankAFillIsolation

F6

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

721 SouthernNuclear

Version1.0 VOGTLEUNIT3 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3PXSPLV230B 2

N B

P 1

GL AO SV3PXSM6003 C

C C

PI 2y

CoreMakeupTankBFillIsolation

G6

SV3PXSPLV231A 2

N C

A 1

CK SA SV3PXSM6003 C

O NA CKOP CS CSJPXS3 ThermalExpansion CMTAFillCheckValve

F7

CKC CS CSJPXS3

SV3PXSPLV231B 2

N C

A 1

CK SA SV3PXSM6003 C

O NA CKOP CS CSJPXS3 ThermalExpansion CMTBFillCheckValve

G7

CKC CS CSJPXS3

SV3PXSPLV232A 2

N B

P 1

GL AO SV3PXSM6003 C

C C

PI 2y

AccumulatorAFill/DrainIsolation

E6

SV3PXSPLV232B 2

N B

P 1

GL AO SV3PXSM6003 C

C C

PI 2y

AccumulatorBFill/DrainIsolation

G6

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

722 SouthernNuclear

Version1.0 VOGTLEUNIT3 RCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3RCSPLV001A 1

N B

A 4

GL MO SV3RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage1ControlValve

III3300 2RO/3y

SV3RCSPLV001B 1

N B

A 4

GL MO SV3RCSM6002 C

O AI PI 2RO/3y

E5

STO/III3600 CS CSJRCS1

ADSStage1ControlValve

III3300 2RO/3y

SV3RCSPLV002A 1

N B

A 8

GL MO SV3RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage2ControlValve

III3300 2RO/3y

SV3RCSPLV002B 1

N B

A 8

GL MO SV3RCSM6002 C

O AI PI 2RO/3y

E5

STO/III3600 CS CSJRCS1

ADSStage2ControlValve

III3300 2RO/3y

SV3RCSPLV003A 1

N B

A 8

GL MO SV3RCSM6002 C

O AI PI 2RO/3y

H5

STO/III3600 CS CSJRCS1

ADSStage3ControlValve

III3300 2RO/3y

SV3RCSPLV003B 1

N B

A 8

GL MO SV3RCSM6002 C

O AI PI 2RO/3y

F5

STO/III3600 CS CSJRCS1

ADSStage3ControlValve

III3300 2RO/3y

SV3RCSPLV004A 1

N D

A 14 SQ SQ SV3RCSM6001 C

O AI RemoteInsp 2y

G6

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ADSStage4Valve

Disass.Insp 10y

Note3

SV3RCSPLV004B 1

N D

A 14 SQ SQ SV3RCSM6001 C

O AI RemoteInsp 2y

F3

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ADSStage4Valve

Disass.Insp 10y

Note3

SV3RCSPLV004C 1

N D

A 14 SQ SQ SV3RCSM6001 C

O AI RemoteInsp 2y

F6

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ADSStage4Valve

Disass.Insp 10y

Note3

SV3RCSPLV004D 1

N D

A 14 SQ SQ SV3RCSM6001 C

O AI RemoteInsp 2y

F3

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ADSStage4Valve

Disass.Insp 10y

Note3

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

723 SouthernNuclear

Version1.0 VOGTLEUNIT3 RCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3RCSPLV005A 1

N C

A 6

RV SA SV3RCSM6002 C

O/C NA RVT 2y/5y IncludesPI PressurizerSafetyValve

H7

SV3RCSPLV005B 1

N C

A 6

RV SA SV3RCSM6002 C

O/C NA RVT 2y/5y IncludesPI PressurizerSafetyValve

F6

SV3RCSPLV010A 3

N C

A 1

VB SA SV3RCSM6002 C

O NA VB 2y

ADSHeaderVacuumBreaker

G4

SV3RCSPLV010B 3

N C

A 1

VB SA SV3RCSM6002 C

O NA VB 2y

ADSHeaderVacuumBreaker

E4

SV3RCSPLV011A 1

N B

A 4

GA MO SV3RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage1IsolationValve

III3300 2RO/3y

SV3RCSPLV011B 1

N B

A 4

GA MO SV3RCSM6002 C

O AI PI 2RO/3y

E5

STO/III3600 CS CSJRCS1

ADSStage1IsolationValve

III3300 2RO/3y

SV3RCSPLV012A 1

N B

A 8

GA MO SV3RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage2IsolationValve

III3300 2RO/3y

SV3RCSPLV012B 1

N B

A 8

GA MO SV3RCSM6002 C

O AI PI 2RO/3y

E5

STO/III3600 CS CSJRCS1

ADSStage2IsolationValve

III3300 2RO/3y

SV3RCSPLV013A 1

N B

A 8

GA MO SV3RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage3IsolationValve

III3300 2RO/3y

SV3RCSPLV013B 1

N B

A 8

GA MO SV3RCSM6002 C

O AI PI 2RO/3y

F5

STO/III3600 CS CSJRCS1

ADSStage3IsolationValve

III3300 2RO/3y

SV3RCSPLV014A 1

N B

P 14 GA MO SV3RCSM6001 O

O AI PI 2y

ADSStage4IsolationValve

G6

SV3RCSPLV014B 1

N B

P 14 GA MO SV3RCSM6001 O

O AI PI 2y

ADSStage4IsolationValve

F3

SV3RCSPLV014C 1

N B

P 14 GA MO SV3RCSM6001 O

O AI PI 2y

ADSStage4IsolationValve

F6

SV3RCSPLV014D 1

N B

P 14 GA MO SV3RCSM6001 O

O AI PI 2y

ADSStage4IsolationValve

F3

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

724 SouthernNuclear

Version1.0 VOGTLEUNIT3 RCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3RCSPLV150A 1

N BC A

1 GL SO SV3RCSM6001 C

O/C C

PI 2y

D4

STO CS CSJRCS2

STC CS CSJRCS2

FST CS CSJRCS2 ReactorHeadVentValve

RVT 10y

Thermalrelief SV3RCSPLV150B 1

N BC A

1 GL SO SV3RCSM6001 C

O/C C

PI 2y

D4

STO CS CSJRCS2

STC CS CSJRCS2

FST CS CSJRCS2

ReactorHeadVentValve

RVT 10y

Thermalrelief

SV3RCSPLV150C 1

N B

A 1

GL SO SV3RCSM6001 C

O/C C

PI 2y

D4

STO CS CSJRCS2

STC CS CSJRCS2 ReactorHeadVentValve

FST CS CSJRCS2

SV3RCSPLV150D 1

N B

A 1

GL SO SV3RCSM6001 C

O/C C

PI 2y

D4

STO CS CSJRCS2

STC CS CSJRCS2 ReactorHeadVentValve

FST CS CSJRCS2

SV3RCSPLV233 3

N B

P 2

GL MA SV3RCSM6002 LO O

AI PI 2y

RVHeadVenttoIRWSTIsolationValve

H3

SV3RCSPYK03 3

N D

A 10 RD SA SV3RCSM6002 C

O NA RRD 5y

SafetyValveDischargeChamberRuptureDisk

H8

SV3RCSPYK04 3

N D

A 10 RD SA SV3RCSM6002 C

O NA RRD 5y

SafetyValveDischargeChamberRuptureDisk

F7

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

725 SouthernNuclear

Version1.0 VOGTLEUNIT3 RNS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3RNSPLV001A 1

N A

A 10 GA MO SV3RNSM6001 C

C AI PI 2RO/3y

F2

STC/III3600 2y

III3300 2RO/3y

RNSSuctionfromRCSInnerIsolationValve

LT 2y

PIV

SV3RNSPLV001B 1

N A

A 10 GA MO SV3RNSM6001 C

C AI PI 2RO/3y

D2

STC/III3600 2y

III3300 2RO/3y

RNSSuctionfromRCSInnerIsolationValve

LT 2y

PIV

SV3RNSPLV002A 1

N A

A 10 GA MO SV3RNSM6001 C

C AI PI 2RO/3y

F2

STC/III3600 2y

III3300 2RO/3y

LT 2y

PIV RNSSuctionfromRCSOuterIsolation/ICContainmentIsolationValve

LT AppJ

SV3RNSPLV002B 1

N A

A 10 GA MO SV3RNSM6001 C

C AI PI 2RO/3y

D2

STC/III3600 2y

III3300 2RO/3y

LT 2y

PIV RNSSuctionfromRCSOuterIsolation/ICContainmentIsolationValve

LT AppJ

SV3RNSPLV003A 1

N C

A 1

CK SA SV3RNSM6001 C

C/O NA CKC CS CSJRNS1

RNSPIVThermalReliefValve

G2

CKOP CS CSJRNS1 ThermalExpansion

SV3RNSPLV003B 1

N C

A 1

CK SA SV3RNSM6001 C

C/O NA CKC CS CSJRNS1

RNSPIVThermalReliefValve

D2

CKOP CS CSJRNS1 ThermalExpansion

SV3RNSPLV011 2

N A

A 8

GA MO SV3RNSM6001 C

C AI PI 2RO/3y

F7

STC/III3600 2y

III3300 2RO/3y

RNSDischargeHeadertoContainmentOCContainmentIsolationValve

LT AppJ

SV3RNSPLV012 2

N A

A 1

GL MA SV3RNSM6001 LC C/O AI ETM 2y

PostAccidentLongTermRCSMakeup&ContainmentIsolationValve G7

LT AppJ

SV3RNSPLV013 2

N AC A

8 CK SA SV3RNSM6001 C

C NA CKC CS CSJRNS1

F7

CKO CS CSJRNS1 ThermalExpansion RNStoContainmentICContainmentIsolationValve

LT App.J

SV3RNSPLV015A 1

N AC A

6 CK*

SA*

SV3RNSM6001 C

C/O NA CKC CS CSJRNS1

  • Note4

F8

CKO CS CSJRNS1 ThermalExpansion RNStoDVIStopCheckValve

LT 2y

PIV

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

726 SouthernNuclear

Version1.0 VOGTLEUNIT3 RNS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3RNSPLV015B 1

N AC A

6 CK*

SA*

SV3RNSM6001 C

C/O NA CKC CS CSJRNS1

  • Note4

F8

CKO CS CSJRNS1 ThermalExpansion RNStoDVIStopCheckValve

LT 2y

PIV

SV3RNSPLV017A 1

N AC A

6 CK SA SV3RNSM6001 C

C/O NA CKC CS CSJRNS1

F8

CKO CS CSJRNS1 ThermalExpansion RNStoDVICheckValve

LT 2y

PIV

SV3RNSPLV017B 1

N AC A

6 CK SA SV3RNSM6001 C

C/O NA CKC CS CSJRNS1

F8

CKO CS CSJRNS1 ThermalExpansion RNStoDVICheckValve

LT 2y

PIV

SV3RNSPLV020 2

N AC A

1 RV SA SV3RNSM6001 C

O/C NA RVT 4y/10y

RNSSuctionReliefValve

G2

LT App.J

SV3RNSPLV021 2

N AC A

3 RV SA SV3RNSM6001 C

O/C NA RVT 4y/10y

RNSSuctionReliefValve

G2

LT App.J

SV3RNSPLV022 2

N A

A 10 GA MO SV3RNSM6001 C

C AI PI 2RO/3y

F3

STC/III3600 2y

III3300 2RO/3y

RNSSuctionfromRCSOCContainmentIsolationValve

LT AppJ

SV3RNSPLV023 2

N A

A 10 GA MO SV3RNSM6001 C

C AI PI 2RO/3y

E3

STC/III3600 2y

III3300 2RO/3y

RNSSuctionfromIRWST/ICContainmentIsolationValve

LT AppJ

SV3RNSPLV061 2

N A

A 3

GL AO SV3RNSM6001 C

C C

PI 2y

G3

STC Q

FST Q

CVSReturntoRNSSuction/ICContainmentIsolationValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

727 SouthernNuclear

Version1.0 VOGTLEUNIT3 SDS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3SDSPLV001 3

N B

A 3

BU MO SV3SDSM6001 O

C AI PI 2RO/3y

E5

STC/III3600 2y

MCRSDS(Vent)IsolationValve

III3300 2RO/3y

SV3SDSPLV002 3

N B

A 3

BU MO SV3SDSM6001 O

C AI PI 2RO/3y

E5

STC/III3600 2y

MCRSDS(Vent)IsolationValve

III3300 2RO/3y

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

728 SouthernNuclear

Version1.0 VOGTLEUNIT3 SFS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3SFSPLV031 3

N B

P 6

BU MA SV3SFSM6001 LO O

AI PI 2y

RefuelingCavityDraintoS/G2CompartmentIsolationValve

F7

SV3SFSPLV033 3

N B

P 2

PL MA SV3SFSM6001 LC C

AI PI 2y

RefuelingCavityDraintoContainmentSumpIsolationValve

E7

SV3SFSPLV034 2

N A

A 6

BU MO SV3SFSM6001 C

C AI PI 2RO/3y

D6

STC/III3600 2y

III3300 2RO/3y

RefuelingCavity/IRWSTtoSFSICContainmentIsoValve

LT App.J

SV3SFSPLV035 2

N A

A 6

BU MO SV3SFSM6001 C

C AI PI 2RO/3y

D5

STC/III3600 2y

III3300 2RO/3y

RefuelingCavity/IRWSTtoSFSOCContainmentIsoValve

LT App.J

SV3SFSPLV037 2

N AC A

4 CK SA SV3SFSM6001 C

C/O NA CKC Q

B6

CKOP Q

ThermalExpansion SFStoRefuelingCavity/IRWSTICContainmentIsoValve

LT App.J

SV3SFSPLV038 2

N A

A 4

BU MO SV3SFSM6001 C

C AI PI 2RO/3y

D5

STC/III3600 2y

III3300 2RO/3y

SFStoRefuelingCavity/IRWSTOCContainmentIsoValve

LT App.J

SV3SFSPLV041 3

N B

A 6

BU MA SV3SFSM6001 LC C

AI ETM 2y

SFSCaskLoadingPitSuctionIsolationValve

F1

SV3SFSPLV066 3

N B

A 8

BA MA SV3SFSM6001 LC O/C AI ETM 2y

SpentFuelPoolBoiloffMakeupIsolationValve

G3

SV3SFSPLV067 2

N AC A

1 RV SA SV3SFSM6001 C

O/C NA RVT 10y

ThermalRelief RefuelingCavity/IRWSTtoSFSPenetrationReliefValve

E6

LT App.J

SV3SFSPLV068 3

N B

A 6

BU MA SV3SFSM6001 LO O

AI ETM 2y

SFSCaskWashdownPitDrainIsolationValve

F2

SV3SFSPLV071 3

N C

A 6

CK SA SV3SFSM6001 C

O/C NA CKC RO*

  • Note5 RefuelingCavitySideDraintoS/G2CompartmentValve

F7

CKO RO*

SV3SFSPLV072 3

N C

A 6

CK SA SV3SFSM6001 C

O/C NA CKC RO*

  • Note5 RefuelingCavitySideDraintoS/G2CompartmentValve

F7/8

CKO RO*

SV3SFSPLV075 3

N B

P 20 BU MA SV3SFSM6001 LO O

AI PI 2y

SFSReactorCavityPostAccidentContainmentFloodupValve

G7

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

729 SouthernNuclear

Version1.0 VOGTLEUNIT3 SGS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3SGSPLV027A 2

N B

A 12 GL MO SV3SGSM6001 O

C AI PI 2RO/3y

G4/5

STC/III3600 2y

SG1PORVIsolationValve

III3300 2RO/3y

SV3SGSPLV027B 2

N B

A 12 GL MO SV3SGSM6002 O

C AI PI 2RO/3y

G5

STC/III3600 2y

SG2PORVIsolationValve

III3300 2RO/3y

SV3SGSPLV030A 2

N C

A 8

RV SA SV3SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G4

SV3SGSPLV030B 2

N C

A 8

RV SA SV3SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G4

SV3SGSPLV031A 2

N C

A 8

RV SA SV3SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G3

SV3SGSPLV031B 2

N C

A 8

RV SA SV3SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G3

SV3SGSPLV032A 2

N C

A 8

RV SA SV3SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G3

SV3SGSPLV032B 2

N C

A 8

RV SA SV3SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G3

SV3SGSPLV033A 2

N C

A 8

RV SA SV3SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G3

SV3SGSPLV033B 2

N C

A 8

RV SA SV3SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G3

SV3SGSPLV034A 2

N C

A 8

RV SA SV3SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G2

SV3SGSPLV034B 2

N C

A 8

RV SA SV3SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G2

SV3SGSPLV035A 2

N C

A 8

RV SA SV3SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G2

SV3SGSPLV035B 2

N C

A 8

RV SA SV3SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G2

SV3SGSPLV036A 2

N B

A 2

GL AO SV3SGSM6001 O

C C

PI 2y

G3

STC Q

SteamLineCondensateDrainIsolation

FST Q

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

730 SouthernNuclear

Version1.0 VOGTLEUNIT3 SGS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3SGSPLV036B 2

N B

A 2

GL AO SV3SGSM6002 O

C C

PI 2y

G3

STC Q

SteamLineCondensateDrainIsolation

FST Q

SV3SGSPLV040A 2

N B

A 38 GA PH SV3SGSM6001 O

C C

PI 2y

G1

STC CS CSJSGS1 MainSteamLineIsolation

FST CS CSJSGS1

SV3SGSPLV040B 2

N B

A 38 GA PH SV3SGSM6002 O

C C

PI 2y

G1

STC CS CSJSGS1 MainSteamLineIsolation

FST CS CSJSGS1

SV3SGSPLV057A 2

N B

A 20 GA PH SV3SGSM6001 O

C C

PI 2y

E4

STC CS CSJSGS1 MainFeedwaterLineIsolation

FST CS CSJSGS1

SV3SGSPLV057B 2

N B

A 20 GA PH SV3SGSM6002 O

C C

PI 2y

E4

STC CS CSJSGS1 MainFeedwaterLineIsolation

FST CS CSJSGS1

SV3SGSPLV058A 2

N C

A 20 CK SA SV3SGSM6001 O

C/O NA CKC CS CSJSGS2

SG1MainFeedCheckValve

E5

CKOP CS CSJSGS2 ThermalExpansion

SV3SGSPLV058B 2

N C

A 20 CK SA SV3SGSM6002 O

C/O NA CKC CS CSJSGS2

SG2MainFeedCheckValve

E5

CKOP CS CSJSGS2 ThermalExpansion

SV3SGSPLV067A 2

N B

A 6

GA MO SV3SGSM6001 O

C AI PI 2RO/3y

D5

STC/III3600 2y

StartupFeedwaterIsolation

III3300 2RO/3y

SV3SGSPLV067B 2

N B

A 6

GA MO SV3SGSM6002 O

C AI PI 2RO/3y

D5

STC/III3600 2y

StartupFeedwaterIsolation

III3300 2RO/3y

SV3SGSPLV074A 2

N B

A 4

GL AO SV3SGSM6001 O

C C

PI 2y

C5

STC Q

SG1BlowdownIsolationValve

FST Q

SV3SGSPLV074B 2

N B

A 4

GL AO SV3SGSM6002 O

C C

PI 2y

C5

STC Q

SG2BlowdownIsolationValve

FST Q

SV3SGSPLV075A 3

N B

A 4

GL AO SV3SGSM6001 O

C C

PI 2y

C5

STC Q

SG1BlowdownIsolationValve

FST Q

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

731 SouthernNuclear

Version1.0 VOGTLEUNIT3 SGS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3SGSPLV075B 3

N B

A 4

GL AO SV3SGSM6002 O

C C

PI 2y

C5

STC Q

SG2BlowdownIsolationValve

FST Q

SV3SGSPLV086A 3

N B

A 2

GL AO SV3SGSM6001 C

C C

PI 2y

F3

STC Q

SG1SteamLineDrainLevelControl

FST Q

SV3SGSPLV086B 3

N B

A 2

GL AO SV3SGSM6002 C

C C

PI 2y

F3

STC Q

SG2SteamLineDrainLevelControl

FST Q

SV3SGSPLV233A 3

N B

A 12 GL AO SV3SGSM6001 C

C C

PI 2y

H4/5

STC RO

PerISTC3510

FST RO

PerISTC3510 SG1SteamLinePowerOperatedReliefValve

LT 2y

PerI8200

SV3SGSPLV233B 3

N B

A 12 GL AO SV3SGSM6002 C

C C

PI 2y

H5

STC RO

PerISTC3510

FST RO

PerISTC3510 SG2SteamLinePowerOperatedReliefValve

LT 2y

PerI8200

SV3SGSPLV240A 2

N B

A 3

GL AO SV3SGSM6001 C

C C

PI 2y

G1

STC Q

SG1MSIVBypass

FST Q

SV3SGSPLV240B 2

N B

A 3

GL AO SV3SGSM6002 C

C C

PI 2y

G1

STC Q

SG2MSIVBypass

FST Q

SV3SGSPLV250A 3

N B

A 20 GL AO SV3SGSM6001 O

C C

PI 2y

E2/3

STC CS CSJSGS1 MainFeedwaterControlValve

FST CS CSJSGS1

SV3SGSPLV250B 3

N B

A 20 GL AO SV3SGSM6002 O

C C

PI 2y

E2/3

STC CS CSJSGS1 MainFeedwaterControlValve

FST CS CSJSGS1

SV3SGSPLV255A 3

N B

A 6

GL AO SV3SGSM6001 C

C C

PI 2y

D4

STC Q

StartupFeedwaterControlValve

FST Q

SV3SGSPLV255B 3

N B

A 6

GL AO SV3SGSM6002 C

C C

PI 2y

D4

STC Q

StartupFeedwaterControlValve

FST Q

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

732 SouthernNuclear

Version1.0 VOGTLEUNIT3 SGS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3SGSPLV256A 3

N C

A 6

CK SA SV3SGSM6001 C

O NA CKC Q

SG1StartupFeedCheckValve

D4

CKOP Q

ThermalExpansion

SV3SGSPLV256B 3

N C

A 6

CK SA SV3SGSM6002 C

O NA CKC Q

SG2StartupFeedCheckValve

D4

CKOP Q

ThermalExpansion

SV3SGSPLV257A 3

N C

A 1

RV SA SV3SGSM6001 C

O NA RVT 10y

ThermalRelief MainFeedwaterThermalRelief

E4

SV3SGSPLV257B 3

N C

A 1

RV SA SV3SGSM6002 C

O NA RVT 10y

ThermalRelief MainFeedwaterThermalRelief

E4

SV3SGSPLV258A 3

N C

A 1

RV SA SV3SGSM6001 C

O NA RVT 10y

ThermalRelief StartupFeedwaterThermalRelief

D4

SV3SGSPLV258B 3

N C

A 1

RV SA SV3SGSM6002 C

O NA RVT 10y

ThermalRelief StartupFeedwaterThermalRelief

D4

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

733 SouthernNuclear

Version1.0 VOGTLEUNIT3 VBS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3VBSPLV186 3

N B

A 28 BU MO SV3VBSM6007 O

C AI PI 2RO/3y

F6

STC/III3600 2y

MCRSupplyAirIsolationValve

III3300 2RO/3y

SV3VBSPLV187 3

N B

A 28 BU MO SV3VBSM6007 O

C AI PI 2RO/3y

F6

STC/III3600 2y

MCRSupplyAirIsolationValve

III3300 2RO/3y

SV3VBSPLV188 3

N B

A 28 BU MO SV3VBSM6007 O

C AI PI 2RO/3y

C7

STC/III3600 2y

MCRReturnAirIsolationValve

III3300 2RO/3y

SV3VBSPLV189 3

N B

A 28 BU MO SV3VBSM6007 O

C AI PI 2RO/3y

C6

STC/III3600 2y

MCRReturnAirIsolationValve

III3300 2RO/3y

SV3VBSPLV190 3

N B

A 6

BU MO SV3VBSM6007 O

C AI PI 2RO/3y

C3

STC/III3600 2y

MCRToiletExhaustIsolationValve

III3300 2RO/3y

SV3VBSPLV191 3

N B

A 6

BU MO SV3VBSM6007 O

C AI PI 2RO/3y

C3

STC/III3600 2y

MCRToiletExhaustIsolationValve

III3300 2RO/3y

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

734 SouthernNuclear

Version1.0 VOGTLEUNIT3 VES ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3VESPLV001 3

N B

A 1

GL MA SV3VESM6002 C

O/C AI ETM 2y

AirDeliveryIsolationValve

D5

SV3VESPLV005A 3

N B

A 1

GL SO SV3VESM6002 C

O O

PI 2y

F5

STO Q

AirDeliveryIsolationValveA

FST Q

SV3VESPLV005B 3

N B

A 1

GL SO SV3VESM6002 C

O O

PI 2y

E5

STO Q

AirDeliveryIsolationValveB

FST Q

SV3VESPLV018 3

N B

A 1

GL MA SV3VESM6002 C

O/C AI ETM 2y

TemporaryInsturmentationIsolationValve

F5

SV3VESPLV019 3

N B

A 1

GL MA SV3VESM6002 C

O/C AI ETM 2y

TemporaryInsturmentationIsolationValve

E5

SV3VESPLV022A 3

N B

A 4

BU AO SV3VESM6002 C

O O

PI 2y

C2

STO Q

PressureReliefIsolationValveA

FST Q

SV3VESPLV022B 3

N B

A 4

BU AO SV3VESM6002 C

O O

PI 2y

C2

STO Q

PressureReliefIsolationValveB

FST Q

SV3VESPLV040A 3

N C

A 1

RV SA SV3VESM6001 C

O/C NA RVT 4y10y

AirTankSafetyReliefValveA

H4

SV3VESPLV040B 3

N C

A 1

RV SA SV3VESM6001 C

O/C NA RVT 4y10y

AirTankSafetyReliefValveB

F4

SV3VESPLV040C 3

N C

A 1

RV SA SV3VESM6001 C

O/C NA RVT 4y10y

AirTankSafetyReliefValveC

D/E4

SV3VESPLV040D 3

N C

A 1

RV SA SV3VESM6001 C

O/C NA RVT 4y10y

AirTankSafetyReliefValveD

C4

SV3VESPLV044 3

N B

A 1

GL MA SV3VESM6002 LO O/C AI ETM 2y

MainAirFlowpathIsolationValve

F4

SV3VESPLV045 3

N B

A 1

GL MA SV3VESM6002 LO O/C AI ETM 2y

EductorSupplyIsolationValve

E3

SV3VESPLV046 3

N B

A 1

GL MA SV3VESM6002 C

C/O AI ETM 2y

EductorBypassIsolationValve

D3

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

735 SouthernNuclear

Version1.0 VOGTLEUNIT3 VFS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3VFSPLV003 2

N A

A 16 BU AO SV3VFSM6001 C

C C

PI 2y

B4

STC Q

FST Q

ContainmentPurgeInletContainmentIsolORC

LT App.J

SV3VFSPLV004 2

N A

A 16 BU AO SV3VFSM6001 C

C C

PI 2y

B3

STC Q

FST Q

ContainmentPurgeInletContainmentIsolIRC

LT App.J

SV3VFSPLV009 2

N A

A 16 BU AO SV3VFSM6001 C

C C

PI 2y

D8

STC Q

FST Q

ContainmentPurgeDischargeContainmentIsolIRC

LT App.J

SV3VFSPLV010 2

N A

A 16 BU AO SV3VFSM6001 C

C C

PI 2y

D7

STC Q

FST Q

ContainmentPurgeDischargeContainmentIsolORC

LT App.J

SV3VFSPLV800A 2

N A

A 6

BU MO SV3VFSM6001 C

C/O AI PI 2RO/3y

E7

STC/III3600 2y

STO/III3600 2y

III3300 2RO/3y

ContainmentVacuumReliefIsolationValveAORC

LT App.J

SV3VFSPLV800B 2

N A

A 6

BU MO SV3VFSM6001 C

C/O AI PI 2RO/3y

E7

STC/III3600 2y

STO/III3600 2y

III3300 2RO/3y

ContainmentVacuumReliefIsolationValveBORC

LT App.J

SV3VFSPLV803A 2

N AC A

6 VB SA SV3VFSM6001 C

O/C NA VB 2y

ContainmentVacuumReliefValveAIRC

E7

LT App.J

SV3VFSPLV803B 2

N AC A

6 VB SA SV3VFSM6001 C

O/C NA VB 2y

ContainmentVacuumReliefValveBIRC

E7

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

736 SouthernNuclear

Version1.0 VOGTLEUNIT3 VWS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3VWSPLV053 3

N C

A 2

RV SA SV3VWSM6003 C

O NA RVT 10y

ThermalRelief CtmtCoolingUnitSupplyHdrRelief

B6

SV3VWSPLV057 3

N C

A 2

RV SA SV3VWSM6003 C

O NA RVT 10y

ThermalRelief CtmtCoolingUnitReturnHdrRelief

H4

SV3VWSPLV058 2

N A

A 8

BU AO SV3VWSM6003 O

C C

PI 2y

B6

STC Q

FST Q

ChilledWaterInletContainmentIsolValve

LT App.J

SV3VWSPLV062 2

N AC A

8 CK SA SV3VWSM6003 O

C/O NA CKC CS CSJVWS1

B6

CKOP CS CSJVWS1 ThermalExpansion FanCoolersSupplyICIsolCheckValve

LT App.J

SV3VWSPLV080 2

N AC A

1 RV SA SV3VWSM6003 C

O/C NA RVT 10y

ThermalRelief CtmtCoolingUnitReturnCIVRelief

H4

LT App.J

SV3VWSPLV082 2

N A

A 8

BU AO SV3VWSM6003 O

C C

PI 2y

G4

STC Q

FST Q

ChilledWaterOutletContainmentIsolationValve

LT App.J

SV3VWSPLV086 2

N A

A 8

BU AO SV3VWSM6003 O

C C

PI 2y

G3

STC Q

FST Q

ChilledWaterOutletContainmentIsolationValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

737 SouthernNuclear

Version1.0 VOGTLEUNIT3 WLS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV3WLSPLV055 2

N A

A 2

PL AO SV3WLSM6001 C

C C

PI 2y

C4

STC Q

FST Q

ContainmentSumpDischargeCIVIRC

LT App.J

SV3WLSPLV057 2

N A

A 2

PL AO SV3WLSM6001 C

C C

PI 2y

C3

STC Q

FST Q

ContainmentSumpDischargeCIVORC

LT App.J

SV3WLSPLV058 2

N AC A

1 RV SA SV3WLSM6001 C

O/C NA RVT 10y

ThermalRelief ContainmentSumpDischargePenetrationThermalRelief C4

LT App.J

SV3WLSPLV067 2

N A

A 1

GL AO SV3WLSM6001 C

C C

PI 2y

E3

STC Q

FST Q

RCDTGasOutletCIVIRC

LT App.J

SV3WLSPLV068 2

N A

A 1

GL AO SV3WLSM6001 C

C C

PI 2y

E3

STC Q

FST Q

RCDTGasOutletCIVORC

LT App.J

SV3WLSPLV071A 3

N C

A 4

CK SA SV3WLSM6001 C

C/O NA CKC CS CSJWLS1

CVSComptFloorDrainCheck

C8

CKO CS CSJWLS1

SV3WLSPLV071B 3

N C

A 4

CK SA SV3WLSM6001 C

C/O NA CKC CS CSJWLS1

PXSComptAFloorDrainCheck

G8

CKO CS CSJWLS1

SV3WLSPLV071C 3

N C

A 4

CK SA SV3WLSM6001 C

C/O NA CKC CS CSJWLS1

PXSComptBFloorDrainCheck

G8

CKO CS CSJWLS1

SV3WLSPLV072A 3

N C

A 4

CK SA SV3WLSM6001 C

C/O NA CKC CS CSJWLS1

CVSComptFloorDrainCheck

C7

CKO CS CSJWLS1

SV3WLSPLV072B 3

N C

A 4

CK SA SV3WLSM6001 C

C/O NA CKC CS CSJWLS1

PXSComptAFloorDrainCheck

G8

CKO CS CSJWLS1

SV3WLSPLV072C 3

N C

A 4

CK SA SV3WLSM6001 C

C/O NA CKC CS CSJWLS1

PXSComptBFloorDrainCheck

G8

CKO CS CSJWLS1

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

81 SouthernNuclear

Version1.0 8.0 VEGP4VALVETABLES ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

82 SouthernNuclear

Version1.0

VOGTLEUNIT4 CAS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4CASPLV014 2

N A

A 2

BA AO SV4CASM6005 O

C C

PI 2y

F3

STC RO ROJCAS1

FST RO ROJCAS1 InstrumentAirContainmentIsolationValve

LT App.J

SV4CASPLV015 2

N AC A

2 CK SA SV4CASM6005 O

C/O NA CKC RO ROJCAS1

F4

CKOP RO ROJCAS1 ThermalExpansion InstrumentAirContainmentIsolationCheckValve

LT App.J

SV4CASPLV204 2

N A

P 3

BA MA SV4CASM6012 LC C

AI LT App.J

ServiceAirContainmentIsolationValve

E5

SV4CASPLV205 2

N AC A

3 CK SA SV4CASM6012 C

C/O NA CKC CS CSJCAS1

E4

CKOP CS CSJCAS1 ThermalExpansion ServiceAirContainmentIsolationCheckValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

83 SouthernNuclear

Version1.0 VOGTLEUNIT4 CCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4CCSPLV200 2

N A

A 10 BU MO SV4CCSM6002 O

C AI PI 2RO/3y

H2

STC/III3600 2y

III3300 2RO/3y

CoolingWaterSupplyCtmtIsolORC

LT App.J

SV4CCSPLV201 2

N AC A

10 CK SA SV4CCSM6002 O

C/O NA CKC RO ROJCCS1

H2

CKOP RO ROJCCS1 ThermalExpansion CoolingWaterCtmtSupplyCheck

LT App.J

SV4CCSPLV207 2

N A

A 10 BU MO SV4CCSM6002 O

C AI PI 2RO/3y

B2

STC/III3600 2y

III3300 2RO/3y

CoolingWaterReturnCtmtIsolIRC

LT App.J

SV4CCSPLV208 2

N A

A 10 BU MO SV4CCSM6002 O

C AI PI 2RO/3y

B1

STC/III3600 2y

III3300 2RO/3y

CoolingWaterReturnyCtmtIsolORC

LT App.J

SV4CCSPLV220 2

N AC A

1 RV SA SV4CCSM6002 C

O/C NA RVT 10y

ThermalRelief CtmtReturnCIVThermalRelief

C2

LT App.J

SV4CCSPLV270 3

N C

A 4

RV SA SV4CCSM6002 C

O NA RVT 4y/10y

CCSSupplyLinetoCtmtSafety/Relief

H2

SV4CCSPLV271 3

N C

A 4

RV SA SV4CCSM6002 C

O NA RVT 4y/10y

CCSReturnLinetoCtmtSafety/Relief

C2

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

84 SouthernNuclear

Version1.0 VOGTLEUNIT4 CVS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4CVSPLV001 1

N B

A 3

GA MO SV4CVSM6001 O

C AI PI 2RO/3y

G8

STC/III3300 2y

CVSPurificationStopValve

III3300 2RO/3y

SV4CVSPLV002 1

N B

A 3

GA MO SV4CVSM6001 O

C AI PI 2RO/3y

G7

STC/III3300 2y

CVSPurificationStopValve

III3300 2RO/3y

SV4CVSPLV003 3

N B

A 3

GL MO SV4CVSM6001 O

C AI PI 2RO/3y

G7

STC/III3300 2y

CVSPurificationStopValve

III3300 2RO/3y

SV4CVSPLV040 2

N A

P 2

BA MA SV4CVSM6005 LC C

AI LT App.J

ResinFlushIRCIsolationValve

F4

SV4CVSPLV041 2

N A

P 2

BA MA SV4CVSM6005 LC C

AI LT App.J

ResinFlushORCIsolationValve

F4

SV4CVSPLV042 2

N AC A

1 RV SA SV4CVSM6005 C

O/C NA RVT 10y

ThermalRelief FlushLineContainmentIsolationReliefValve

G4

LT App.J

SV4CVSPLV045 2

N A

A 2

GL AO SV4CVSM6005 C

C C

PI 2y

D4

STC Q

FST Q

LetdownLineInsideContainmentIsolationValve

LT App.J

SV4CVSPLV047 2

N A

A 2

GL AO SV4CVSM6005 C

C C

PI 2y

D2

STC Q

FST Q

LetdownLineOutsideContainmentIsolationValve

LT App.J

SV4CVSPLV058 2

N AC A

1 RV SA SV4CVSM6005 C

O/C NA RVT 10y

ThermalRelief LetdownLinetoDegassifierContainmentIsolationThermalReliefValveE4

LT App.J

SV4CVSPLV064 N

N C

A 3

CK SA SV4CVSM6005 C

O NA CKOP CS CSJCVS2 ThermalExpansion MakeupDischargeHeaderCheckValve

C5

CKC CS CSJCVS2

SV4CVSPLV067 1

N C

A 1

CK SA SV4CVSM6001 O

C/O NA CKOP CS CSJCVS1 ThermalExpansion MakeupReturnLineSpringAssistedCheckValve

F7

CKC CS CSJCVS1

SV4CVSPLV080 3

N C

A 3

CK SA SV4CVSM6001 O

C/O NA CKOP CS CSJCVS1 ThermalExpansion RegenHXShellSideOutletCheckValve

G7

CKC CS CSJCVS1

SV4CVSPLV081 1

N BC A

3 SC AO SV4CVSM6001 O

C NA CKOP CS CSJCVS1

PurificationReturnLineStopCheckValve

G7

CKC CS CSJCVS1

SV4CVSPLV082 1

N C

A 3

CK SA SV4CVSM6001 O

C/O NA CKOP CS CSJCVS1 ThermalExpansion RCSPurificationReturnLineCheckValve

G8

CKC CS CSJCVS1

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

85 SouthernNuclear

Version1.0 VOGTLEUNIT4 CVS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4CVSPLV084 1

N B

A 2

GL AO SV4CVSM6001 C

C C

PI 2y

F7

STC RO ROJCVS1 AuxiliaryPressurizerSprayLineIsolationValve

FST RO ROJCVS1

SV4CVSPLV085 1

N C

A 2

CK SA SV4CVSM6001 C

C/O NA CKC RO ROJCVS1

AuxiliaryPressurizerSprayLineCheckValve

F8

CKOP RO ROJCVS1 ThermalExpansion

SV4CVSPLV090 2

N A

A 3

GA MO SV4CVSM6005 O

C AI PI 2RO/3y

C2

STC/III3600 2y

III3300 2RO/3y

MakeupLineOutsideContainmentIsolationValve

LT App.J

SV4CVSPLV091 2

N A

A 3

GA MO SV4CVSM6005 O

C AI PI 2RO/3y

C4

STC/III3600 2y

III3300 2RO/3y

MakeupLineInsideContainmentIsolationValve

LT App.J

SV4CVSPLV092 2

N A

A 1

GL AO SV4CVSM6003 O

C C

PI 2y

F6

STC Q

FST Q

ZincInjectionContainmentIsolationValveORC

LT App.J

SV4CVSPLV094 2

N A

A 1

GL AO SV4CVSM6003 O

C C

PI 2y

F7

STC Q

FST Q

ZincInjectionContainmentIsolationValveIRC

LT App.J

SV4CVSPLV098 2

N AC A

1 RV SA SV4CVSM6003 C

O/C NA RVT 10y

ThermalRelief ZincInjectionCtmtIsolThermalReliefValve

F6

LT App.J

SV4CVSPLV100 2

N AC A

1 CK SA SV4CVSM6005 C

C/O NA CKC CS CSJCVS2

B4

CKOP CS CSJCVS2 ThermalExpansion MakeupLineContainmentIsolationRelief

LT App.J

SV4CVSPLV136A 3

N B

A 3

BU AO SV4CVSM6004 C

C C

PI 2y

C4

STC Q

DemineralizedWaterSystemIsolationValve

FST Q

SV4CVSPLV136B 3

N B

A 3

BU AO SV4CVSM6004 C

C C

PI 2y

C4

STC Q

DemineralizedWaterSystemIsolationValve

FST Q

SV4CVSPLV217 2

N AC A

1/2 CK SA SV4CVSM6003 O

C/O NA CKC Q

D7

CKOP Q

ThermalExpansion HydrogenInjectionContainmentIsolationCheckValveIRC

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

86 SouthernNuclear

Version1.0 VOGTLEUNIT4 CVS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4CVSPLV219 2

N A

A 1/2 GL AO SV4CVSM6003 O

C C

PI 2y

D6

STC Q

FST Q

ZincInjectionContainmentIsolationValveIRC

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

87 SouthernNuclear

Version1.0 VOGTLEUNIT4 DWS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4DWSPLV241 3

N C

A 1

RV SA SV4DWSM6007 C

O NA RVT 10y ThermalRelief DeminWaterSupplytoContainmentRelief

E5

SV4DWSPLV244 2

N A

P 3

BU MA SV4DWSM6007 LC C

AI LT App.J

DeminWaterSupplyContainmentIsolationValveOutside

E6

SV4DWSPLV245 2

N AC A

2 CK SA SV4DWSM6007 C

C/O NA CKC CS CSJDWS1

E6

CKOP CS CSJDWS1 ThermalExpansion DeminWaterSupplyContainmentIsolationCheckValveIRC

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

88 SouthernNuclear

Version1.0 VOGTLEUNIT4 FHS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4FHSPLV001 3

N B

A 30 GA MA SV4SFSM6012 C

C AI ETM 2y

FuelTransferTubeIsolationValve

F6

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

89 SouthernNuclear

Version1.0 VOGTLEUNIT4 FPS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4FPSPLV050 2

N A

P 6

BU MA SV4FPSM6004 LC C

AI LT App.J

FireWaterContainmentSupplyIsolation

F4

SV4FPSPLV052 2

N AC A

6 CK SA SV4FPSM6004 C

C/O NA CKC CS CSJFPS1

F5

CKOP CS CSJFPS1 ThermalExpansion

FireWaterSupplyCtmtIsolCheckValveIRC

LT App.J

SV4FPSPLV702 3

N C

A 1

RV SA SV4FPSM6004 C

O NA RVT 10y

ThermalRelief FireWaterSupplyICThermalRelief

F/G5

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

810 SouthernNuclear

Version1.0 VOGTLEUNIT4 MSS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4MSSPLV001 N

Y B

A 16 GL AO SV4MSSM6001 C

C C

PI 2y

H8

STC Q

TurbineBypassControlValve

FST Q

SV4MSSPLV002 N

Y B

A 16 GL AO SV4MSSM6001 C

C C

PI 2y

H7

STC Q

TurbineBypassControlValve

FST Q

SV4MSSPLV003 N

Y B

A 16 GL AO SV4MSSM6001 C

C C

PI 2y

H6

STC Q

TurbineBypassControlValve

FST Q

SV4MSSPLV004 N

Y B

A 16 GL AO SV4MSSM6001 C

C C

PI 2y

H4

STC Q

TurbineBypassControlValve

FST Q

SV4MSSPLV005 N

Y B

A 16 GL AO SV4MSSM6001 C

C C

PI 2y

H3

STC Q

TurbineBypassControlValve

FST Q

SV4MSSPLV006 N

Y B

A 16 GL AO SV4MSSM6001 C

C C

PI 2y

H2

STC Q

TurbineBypassControlValve

FST Q

SV4MSSPLV015A N Y

B A

10 GL AO SV4MSSM6001 O

C C

PI 2y

B6

STC CS CSJMSS1 MSR2ndStageReheatSteamAOIsolationValve

FST CS CSJMSS1

SV4MSSPLV015B N

Y B

A 10 GL AO SV4MSSM6001 O

C C

PI 2y

G6

STC CS CSJMSS1 MSR2ndStageReheatSteamAOIsolationValve

FST CS CSJMSS1

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

811 SouthernNuclear

Version1.0 VOGTLEUNIT4 MTS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4MTSPLV001A N Y

B A

28 GL EH SV4MTSM6002 O

C C

PI 2y

F6

STC Q

MainStopValve#1

FST Q

SV4MTSPLV001B N

Y B

A 28 GL EH SV4MTSM6002 O

C C

PI 2y

C6

STC Q

MainStopValve#3

FST Q

SV4MTSPLV002A N Y

B A

28 GL EH SV4MTSM6002 O

C C

PI 2y

F6

STC Q

ControlValve#1

FST Q

SV4MTSPLV002B N

Y B

A 28 GL EH SV4MTSM6002 O

C C

PI 2y

C6

STC Q

ControlValve#3

FST Q

SV4MTSPLV003A N Y

B A

28 GL EH SV4MTSM6002 O

C C

PI 2y

E6

STC Q

MainStopValve#2

FST Q

SV4MTSPLV003B N

Y B

A 28 GL EH SV4MTSM6002 O

C C

PI 2y

D6

STC Q

MainStopValve#4

FST Q

SV4MTSPLV004A N Y

B A

28 GL EH SV4MTSM6002 O

C C

PI 2y

E6

STC Q

ControlValve#2

FST Q

SV4MTSPLV004B N

Y B

A 28 GL EH SV4MTSM6002 O

C C

PI 2y

D6

STC Q

ControlValve#4

FST Q

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

812 SouthernNuclear

Version1.0 VOGTLEUNIT4 PCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PCSPLV001A 3

N B

A 6

BU AO SV4PCSM6001 C

O O

PI 2y

E4

STO Q

PCSActuationValveA

FST Q

SV4PCSPLV001B 3

N B

A 6

BU AO SV4PCSM6001 C

O O

PI 2y

E6

STO Q

PCSActuationValveB

FST Q

SV4PCSPLV001C 3

N B

A 6

GA MO SV4PCSM6001 C

O AI PI 2RO/3y

E5

STO/III3600 Q

PCSActuationValveC

III3300 2RO/3y

SV4PCSPLV002A 3

N B

A 6

GA MO SV4PCSM6001 O

O AI PI 2RO/3y

E4

STO/III3600 2y

PCSIsolationValveA

III3300 2RO/3y

SV4PCSPLV002B 3

N B

A 6

GA MO SV4PCSM6001 O

O AI PI 2RO/3y

E6

STO/III3600 2y

PCSIsolationValveB

III3300 2RO/3y

SV4PCSPLV002C 3

N B

A 6

GA MO SV4PCSM6001 O

O AI PI 2RO/3y

E5

STO/III3600 2y

PCSIsolationValveC

III3300 2RO/3y

SV4PCSPLV005 3

N B

A 4

GA MA SV4PCSM6002 O

C AI ETM 2y

PCStoDWS/FPSIsoValve

G5

SV4PCSPLV009 3

N B

A 3

GA MA SV4PCSM6001 C

O/C AI ETM 2y

SpentFuelPoolEmergencyMakeupValve

E4

SV4PCSPLV015 3

N B

A 1

GL MA SV4PCSM6002 O

C AI ETM 2y

PCSLongTermSupplytoDistributionBucketDrainValve

G8

SV4PCSPLV020 3

N B

A 3

GA MA SV4PCSM6002 C

O AI ETM 2y

PCSLongTermSupplytoDistributionBucketIsoValve

E4

SV4PCSPLV023 3

N B

A 4

GA MA SV4PCSM6002 O

C AI ETM 2y

PCSRecircPumpstoPCCWSTIsoValve

F7

SV4PCSPLV039 3

N C

A 4

CK SA SV4PCSM6002 C

C/O NA CKC App.II PCS/SFSLongTermMakeupSupplyCheckValve

F4

CKO App.II

SV4PCSPLV042 3

N B

A 1

GL MA SV4PCSM6002 O

C AI ETM 2y

PCSLongTermSupplyfromTempPumpDrainValve

F3

SV4PCSPLV044 3

N B

A 4

GA MA SV4PCSM6002 C

O AI ETM 2y

PCSLongTermSupplyfromTempPumpIsoValve

F4

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

813 SouthernNuclear

Version1.0 VOGTLEUNIT4 PCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PCSPLV045 3

N B

A 2

GL MA SV4PCSM6001 C

O AI ETM 2y

PCSSupplytoSFSMakeupIsoValve

B3

SV4PCSPLV046 3

N B

A 4

GA MA SV4PCSM6002 O

C AI ETM 2y

PCCWSTRecirculationReturnIsolationValve

H7

SV4PCSPLV049 3

N B

A 1

GL MA SV4PCSM6001 O

C AI ETM 2y

PCCWSTDrainIsolationValve

C2

SV4PCSPLV050 3

N B

A 2

GL MA SV4PCSM6002 C

C/O AI ETM 2y

RecircHeaderDischargetoSFSPoolIsolationValve

F7

SV4PCSPLV051 3

N B

A 2

GL MA SV4PCSM6001 C

C/O AI ETM 2y

SpentFuelPoolEmergencyMakeupLowerIsolationValve

B2

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

814 SouthernNuclear

Version1.0 VOGTLEUNIT4 PSS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PSSPLV001A 2

N C

A 1/4 GL SO SV4PSSM6003 O

O C

RVT 10y

ThermalRelief HotLeg1SampleIsolation

E8

SV4PSSPLV001B 2

N C

A 1/4 GL SO SV4PSSM6003 C

O C

RVT 10y

ThermalRelief HotLeg2SampleIsolation

D8

SV4PSSPLV003 2

N C

A 1/4 GL SO SV4PSSM6003 C

O C

RVT 10y

ThermalRelief PzrSampleIsolation

G8

SV4PSSPLV008 2

N A

A 5/8 GL SO SV4PSSM6001 O

C C

PI 2y

D7

STC Q

FST Q

ContainmentAirSampleContainmentIsolationValveIRC

LT App.J

SV4PSSPLV010A 2

N AC A

1/4 GL SO SV4PSSM6001 O

C C

PI 2y

D7

STC Q

FST Q

LT App.J LiquidSampleLineContainmentIsolationValve AIRC

RVT 10y

ThermalRelief

SV4PSSPLV010B 2

N AC A

1/4 GL SO SV4PSSM6001 C

C C

PI 2y

G7

STC Q

FST Q

LT App.J LiquidSampleLineContainmentIsolationValve BIRC

RVT 10y

ThermalRelief

SV4PSSPLV011A 2

N A

A 1/4 GL AO SV4PSSM6001 O

C C

PI 2y

E6

STC Q

FST Q

LiquidSampleLineContainmentIsolationValve AORC

LT App.J

SV4PSSPLV011B 2

N A

A 1/4 GL AO SV4PSSM6001 C

C C

PI 2y

G6

STC Q

FST Q

LiquidSampleLineContainmentIsolationValve BORC

LT App.J

SV4PSSPLV023 2

N A

A 1

GL AO SV4PSSM6001 O

C C

PI 2y

C6

STC Q

FST Q

CtmtAirSampleReturnIsolationValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

815 SouthernNuclear

Version1.0 VOGTLEUNIT4 PSS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PSSPLV024 2

N A

A 1

GL SO SV4PSSM6001 O

C C

PI 2y

C7

STC Q

FST Q

CtmtLiquidandAirSampleReturnIRCIsolValve

LT App.J

SV4PSSPLV046 2

N A

A 5/8 GL AO SV4PSSM6001 O

C C

PI 2y

D6

STC Q

FST Q

AirSampleLineCtmtIsolORCValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

816 SouthernNuclear

Version1.0 VOGTLEUNIT4 PWS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PWSPLV418 3

N B

A 1

GL MA SV4PCSM6002 O

C AI ETM 2y

ControlRoomBoundaryOutsideIsolationValve

G4

SV4PWSPLV420 3

N B

A 1

GL MA SV4PCSM6002 O

C AI ETM 2y

ControlRoomBoundaryInsideIsolationValve

F4

SV4PWSPLV498 3

N C

A 1

VB SA SV4PWSM6002 C

O NA VB 2y

VacuumBreaker CtmtReturnCIVThermalRelief

F4

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

817 SouthernNuclear

Version1.0 VOGTLEUNIT4 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PXSPLV002A 1

N B

P 8

GA MO SV4PXSM6001 O

O AI PI 2y

RCStoCMTAIsolationValve

G/H5

SV4PXSPLV002B 1

N B

P 8

GA MO SV4PXSM6001 O

O AI PI 2y

RCStoCMTBIsolationValve

G/H4

SV4PXSPLV013A 1

N B

P 8

GA MA SV4PXSM6001 LO O

AI PI 2y

CMTADischargeManualIsolValve

D/E6

SV4PXSPLV013B 1

N B

P 8

GA MA SV4PXSM6001 LO O

AI PI 2y

CMTBDischargeManualIsolValve

D/E3

SV4PXSPLV014A 1

N B

A 8

GL AO SV4PXSM6001 C

O O

PI 2y

E7

STO Q

CMTAOutletValve

FST Q

SV4PXSPLV014B 1

N B

A 8

GL AO SV4PXSM6001 C

O O

PI 2y

E3

STO Q

CMTBOutletValve

FST Q

SV4PXSPLV015A 1

N B

A 8

GL AO SV4PXSM6001 C

O O

PI 2y

D7

STO Q

CMTAOutletValve

FST Q

SV4PXSPLV015B 1

N B

A 8

GL AO SV4PXSM6001 C

O O

PI 2y

D3

STO Q

CMTBOutletValve

FST Q

SV4PXSPLV016A 1

N C

A 8

CK SA SV4PXSM6001 O

O/C NA CKO RO ROJPXS1

CMTAOutletCheckValve

D/E6

CKC RO ROJPXS1

SV4PXSPLV016B 1

N C

A 8

CK SA SV4PXSM6001 O

O/C NA CKO RO ROJPXS1

CMTBOutletCheckValve

D/E3

CKC RO ROJPXS1

SV4PXSPLV017A 1

N C

A 8

CK SA SV4PXSM6001 O

O/C NA CKO RO ROJPXS1

CMTAOutletCheckValve

D/E6

CKC RO ROJPXS1

SV4PXSPLV017B 1

N C

A 8

CK SA SV4PXSM6001 O

O/C NA CKO RO ROJPXS1

CMTBOutletCheckValve

D/E3

CKC RO ROJPXS1

SV4PXSPLV021A 3

N B

P 1

GL SO SV4PXSM6001 C

C C

PI 2y

AccumulatorANitrogenSupplyValve

C7

SV4PXSPLV021B 3

N B

P 1

GL SO SV4PXSM6001 C

C C

PI 2y

AccumulatorBNitrogenSupplyValve

C2

SV4PXSPLV022A 3

N C

A 1

RV SA SV4PXSM6001 C

O/C NA RVT 4y/10y

AccumulatorAReliefValve

C7

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

818 SouthernNuclear

Version1.0 VOGTLEUNIT4 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PXSPLV022B 3

N C

A 1

RV SA SV4PXSM6001 C

O/C NA RVT 4y/10y

AccumulatorBReliefValve

C2

SV4PXSPLV027A 3

N B

P 8

GA MO SV4PXSM6001 O

O AI PI 2y

AccumulatorAtoRCSIsolationValve

B6

SV4PXSPLV027B 3

N B

P 8

GA MO SV4PXSM6001 O

O AI PI 2y

AccumulatorBtoRCSIsolationValve B3

SV4PXSPLV028A 1

N AC A

8 CK SA SV4PXSM6001 C

O/C NA CKC RO ROJPXS2

B6

CKO RO ROJPXS2

AccumulatorAOutlettoRCSCheck

LT 2y

PIV

SV4PXSPLV028B 1

N AC A

8 CK SA SV4PXSM6001 C

O/C NA CKC RO ROJPXS2

B3

CKO RO ROJPXS2

AccumulatorBOutlettoRCSCheck

LT 2y

PIV

SV4PXSPLV029A 1

N AC A

8 CK SA SV4PXSM6001 C

O/C NA CKC RO ROJPXS2

B6

CKO RO ROJPXS2

AccumulatorAOutlettoRCSCheck

LT 2y

PIV

SV4PXSPLV029B 1

N AC A

8 CK SA SV4PXSM6001 C

O/C NA CKC RO ROJPXS2

B4

CKO RO ROJPXS2

AccumulatorBOutlettoRCSCheck

LT 2y

PIV

SV4PXSPLV042 2

N A

A 1

GL AO SV4PXSM6001 O

C C

PI 2y

D1

STC Q

FST Q

HighPressureNitrogentoContainmentIsolationValve

LT App.J

SV4PXSPLV043 2

N AC A

1 CK SA SV4PXSM6001 C

O/C NA CKC Q

D2

CKOP Q

ThermalExpansion

HighPressureNitrogentoContainmentICCheckValve

LT App.J

SV4PXSPLV044 N

N C

A 1

RV SA SV4PXSM6001 C

O NA RVT 10y

ThermalRelief HighPressureNitrogentoContainmentPenetrationThermalReliefValveD2

SV4PXSPLV101 1

N B

P 14 GA MO SV4PXSM6002 O

O AI PI 2y

RCStoPRHRHeatExchangerIsolationValve

G1

SV4PXSPLV108A 1

N B

A 14 BA AO SV4PXSM6002 C

O O

PI 2y

G1

STO CS CSJPXS1 PRHRHeatExchangerOutletValvetoRCSA

FST CS CSJPXS1

SV4PXSPLV108B 1

N B

A 14 BA AO SV4PXSM6002 C

O O

PI 2y

F1

STO CS CSJPXS1 PRHRHeatExchangerOutletValvetoRCSB

FST CS CSJPXS1

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

819 SouthernNuclear

Version1.0 VOGTLEUNIT4 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PXSPLV109 1

N B

P 14 GA MA SV4PXSM6001 LO O

AI PI 2y

RCStoPRHRHeatExchangerIsolationValve

F1

SV4PXSPLV117A 3

N B

P 8

GA MO SV4PXSM6002 O

O AI PI 2y

ContainmentRecirculationAtoRCSIsolationValve

E7

SV4PXSPLV117B 3

N B

P 8

GA MO SV4PXSM6002 O

O AI PI 2y

ContainmentRecirculationBtoRCSIsolationValve

E5

SV4PXSPLV118A 3

N D

A 8

SQ SQ SV4PXSM6002 C

O AI RemoteInsp 2y

E7

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ContainmentRecirc.SumpAtoRCSActuationSquibValve

Disass.Insp 10y

Note3

SV4PXSPLV118B 3

N D

A 8

SQ SQ SV4PXSM6002 C

O AI RemoteInsp 2y

E5

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ContainmentRecirc.SumpBtoRCSActuationSquibValve

Disass.Insp 10y

Note3

SV4PXSPLV119A 3

N C

A 8

CK NA SV4PXSM6002 C

O/C NA PI 2y

E7

CKC RO ROJPXS3

ContainmentRecirc.SumpAOutlettoRCSCheck

CKO RO ROJPXS3

SV4PXSPLV119B 3

N C

A 8

CK NA SV4PXSM6002 C

O/C NA PI 2y

E5

CKC RO ROJPXS3

ContainmentRecirc.SumpAOutlettoRCSCheck

CKO RO ROJPXS3

SV4PXSPLV120A 3

N D

A 8

SQ SQ SV4PXSM6002 C

O AI RemoteInsp 2y

E7

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ContainmentRecirc.SumpAtoRCSActuationSquibValve

Disass.Insp 10y

Note3

SV4PXSPLV120B 3

N D

A 8

SQ SQ SV4PXSM6002 C

O AI RemoteInsp 2y

E5

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ContainmentRecirc.SumpBtoRCSActuationSquibValve

Disass.Insp 10y

Note3

SV4PXSPLV121A 3

N B

P 8

GA MO SV4PXSM6002 O

O AI PI 2y

IRWST/Recirc.SumptoRCSAIsolationValve

D7

SV4PXSPLV121B 3

N B

P 8

GA MO SV4PXSM6002 O

O AI PI 2y

IRWST/Recirc.SumptoRCSBIsolationValve

D7

SV4PXSPLV122A 1

N C

A 8

CK SA SV4PXSM6002 C

O/C NA PI 2y

C7

CKC CS CSJPXS2

IRWSTInjectionLineACheckValve

CKO CS CSJPXS2

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

820 SouthernNuclear

Version1.0 VOGTLEUNIT4 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PXSPLV122B 1

N C

A 8

CK SA SV4PXSM6002 C

O/C NA PI 2y

C5

CKC CS CSJPXS2

IRWSTInjectionLineBCheckValve

CKO CS CSJPXS2

SV4PXSPLV123A 1

N D

A 8

SQ SQ SV4PXSM6002 C

O AI RemoteInsp 2y

C7

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

IRWSTInjectionAIsolationValve

Disass.Insp 10y

Note3

SV4PXSPLV123B 1

N D

A 8

SQ SQ SV4PXSM6002 C

O AI RemoteInsp 2y

C5

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

IRWSTInjectionBIsolationValve

Disass.Insp 10y

Note3

SV4PXSPLV124A 1

N C

A 8

CK NA SV4PXSM6002 C

O/C NA PI 2y

C7

CKC CS CSJPXS2

IRWSTInjectionLineACheckValve

CKO CS CSJPXS2

SV4PXSPLV124B 1

N C

A 8

CK NA SV4PXSM6002 C

O/C NA PI 2y

C5

CKC CS CSJPXS2

IRWSTInjectionLineBCheckValve

CKO CS CSJPXS2

SV4PXSPLV125A 1

N D

A 8

SQ SQ SV4PXSM6002 C

O AI RemoteInsp 2y

C7

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

IRWSTInjectionAIsolationValve

Disass.Insp 10y

Note3

SV4PXSPLV125B 1

N D

A 8

SQ SQ SV4PXSM6002 C

O AI RemoteInsp 2y

C5

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

IRWSTInjectionBIsolationValve

Disass.Insp 10y

Note3

SV4PXSPLV130A 3

N B

A 2

BA AO SV4PXSM6002 O

C C

PI 2y

H7

STC Q

IRWSTGutterIsolationAValve

FST Q

SV4PXSPLV130B 3

N B

A 2

BA AO SV4PXSM6002 O

C C

PI 2y

H7

STC Q

IRWSTGutterIsolationBValve

FST Q

SV4PXSPLV208A 2

N A

P 3/8 GL MA SV4PXSM6003 LC C

AI LT App.J

RNSSuctionLeakTestValve

D3

SV4PXSPLV230A 2

N B

P 1

GL AO SV4PXSM6003 C

C C

PI 2y

CoreMakeupTankAFillIsolation

F6

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

821 SouthernNuclear

Version1.0 VOGTLEUNIT4 PXS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4PXSPLV230B 2

N B

P 1

GL AO SV4PXSM6003 C

C C

PI 2y

CoreMakeupTankBFillIsolation

G6

SV4PXSPLV231A 2

N C

A 1

CK SA SV4PXSM6003 C

O NA CKOP CS CSJPXS3 Thermalexpansion CMTAFillCheckValve

F7

CKC CS CSJPXS3

SV4PXSPLV231B 2

N C

A 1

CK SA SV4PXSM6003 C

O NA CKOP CS CSJPXS3 Thermalexpansion CMTBFillCheckValve

G7

CKC CS CSJPXS3

SV4PXSPLV232A 2

N B

P 1

GL AO SV4PXSM6003 C

C C

PI 2y

AccumulatorAFill/DrainIsolation

E6

SV4PXSPLV232B 2

N B

P 1

GL AO SV4PXSM6003 C

C C

PI 2y

AccumulatorBFill/DrainIsolation

G6

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

822 SouthernNuclear

Version1.0 VOGTLEUNIT4 RCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4RCSPLV001A 1

N B

A 4

GL MO SV4RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage1ControlValve

III3300 2RO/3y

SV4RCSPLV001B 1

N B

A 4

GL MO SV4RCSM6002 C

O AI PI 2RO/3y

E5

STO/III3600 CS CSJRCS1

ADSStage1ControlValve

III3300 2RO/3y

SV4RCSPLV002A 1

N B

A 8

GL MO SV4RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage2ControlValve

III3300 2RO/3y

SV4RCSPLV002B 1

N B

A 8

GL MO SV4RCSM6002 C

O AI PI 2RO/3y

E5

STO/III3600 CS CSJRCS1

ADSStage2ControlValve

III3300 2RO/3y

SV4RCSPLV003A 1

N B

A 8

GL MO SV4RCSM6002 C

O AI PI 2RO/3y

H5

STO/III3600 CS CSJRCS1

ADSStage3ControlValve

III3300 2RO/3y

SV4RCSPLV003B 1

N B

A 8

GL MO SV4RCSM6002 C

O AI PI 2RO/3y

F5

STO/III3600 CS CSJRCS1

ADSStage3ControlValve

III3300 2RO/3y

SV4RCSPLV004A 1

N D

A 14 SQ SQ SV4RCSM6001 C

O AI RemoteInsp 2y

G6

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ADSStage4Valve

Disass.Insp 10y

Note3

SV4RCSPLV004B 1

N D

A 14 SQ SQ SV4RCSM6001 C

O AI RemoteInsp 2y

F3

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ADSStage4Valve

Disass.Insp 10y

Note3

SV4RCSPLV004C 1

N D

A 14 SQ SQ SV4RCSM6001 C

O AI RemoteInsp 2y

F6

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ADSStage4Valve

Disass.Insp 10y

Note3

SV4RCSPLV004D 1

N D

A 14 SQ SQ SV4RCSM6001 C

O AI RemoteInsp 2y

F3

Charge 2y/10y Note2

Circuit 2y/10y Testedwhentestingcharge

ADSStage4Valve

Disass.Insp 10y

Note3

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

823 SouthernNuclear

Version1.0 VOGTLEUNIT4 RCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4RCSPLV005A 1

N C

A 6

RV SA SV4RCSM6002 C

O/C NA RVT 2y/5y IncludesPI PressurizerSafetyValve

H7

SV4RCSPLV005B 1

N C

A 6

RV SA SV4RCSM6002 C

O/C NA RVT 2y/5y IncludesPI PressurizerSafetyValve

F6

SV4RCSPLV010A 3

N C

A 1

VB SA SV4RCSM6002 C

O NA VB 2y

ADSHeaderVacuumBreaker

G4

SV4RCSPLV010B 3

N C

A 1

VB SA SV4RCSM6002 C

O NA VB 2y

ADSHeaderVacuumBreaker

E4

SV4RCSPLV011A 1

N B

A 4

GA MO SV4RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage1IsolationValve

III3300 2RO/3y

SV4RCSPLV011B 1

N B

A 4

GA MO SV4RCSM6002 C

O AI PI 2RO/3y

E5

STO/III3600 CS CSJRCS1

ADSStage1IsolationValve

III3300 2RO/3y

SV4RCSPLV012A 1

N B

A 8

GA MO SV4RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage2IsolationValve

III3300 2RO/3y

SV4RCSPLV012B 1

N B

A 8

GA MO SV4RCSM6002 C

O AI PI 2RO/3y

E5

STO/III3600 CS CSJRCS1

ADSStage2IsolationValve

III3300 2RO/3y

SV4RCSPLV013A 1

N B

A 8

GA MO SV4RCSM6002 C

O AI PI 2RO/3y

G5

STO/III3600 CS CSJRCS1

ADSStage3IsolationValve

III3300 2RO/3y

SV4RCSPLV013B 1

N B

A 8

GA MO SV4RCSM6002 C

O AI PI 2RO/3y

F5

STO/III3600 CS CSJRCS1

ADSStage3IsolationValve

III3300 2RO/3y

SV4RCSPLV014A 1

N B

P 14 GA MO SV4RCSM6001 O

O AI PI 2y

ADSStage4IsolationValve

G6

SV4RCSPLV014B 1

N B

P 14 GA MO SV4RCSM6001 O

O AI PI 2y

ADSStage4IsolationValve

F3

SV4RCSPLV014C 1

N B

P 14 GA MO SV4RCSM6001 O

O AI PI 2y

ADSStage4IsolationValve

F6

SV4RCSPLV014D 1

N B

P 14 GA MO SV4RCSM6001 O

O AI PI 2y

ADSStage4IsolationValve

F3

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

824 SouthernNuclear

Version1.0 VOGTLEUNIT4 RCS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4RCSPLV150A 1

N BC A

1 GL SO SV4RCSM6001 C

O/C C

PI 2y

D4

STO CS CSJRCS2

STC CS CSJRCS2

FST CS CSJRCS2 ReactorHeadVentValve

RVT 10y

Thermalrelief SV4RCSPLV150B 1

N BC A

1 GL SO SV4RCSM6001 C

O/C C

PI 2y

D4

STO CS CSJRCS2

STC CS CSJRCS2

FST CS CSJRCS2

ReactorHeadVentValve

RVT 10y

Thermalrelief

SV4RCSPLV150C 1

N B

A 1

GL SO SV4RCSM6001 C

O/C C

PI 2y

D4

STO CS CSJRCS2

STC CS CSJRCS2 ReactorHeadVentValve

FST CS CSJRCS2

SV4RCSPLV150D 1

N B

A 1

GL SO SV4RCSM6001 C

O/C C

PI 2y

D4

STO CS CSJRCS2

STC CS CSJRCS2 ReactorHeadVentValve

FST CS CSJRCS2

SV4RCSPLV233 3

N B

P 2

GL MA SV4RCSM6002 LO O

AI PI 2y

RVHeadVenttoIRWSTIsolationValve

H3

SV4RCSPYK03 3

N D

A 10 RD SA SV4RCSM6002 C

O NA RRD 5y

SafetyValveDischargeChamberRuptureDisk

H8

SV4RCSPYK04 3

N D

A 10 RD SA SV4RCSM6002 C

O NA RRD 5y

SafetyValveDischargeChamberRuptureDisk

F7

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

825 SouthernNuclear

Version1.0 VOGTLEUNIT4 RNS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4RNSPLV001A 1

N A

A 10 GA MO SV4RNSM6001 C

C AI PI 2RO/3y

F2

STC/III3600 2y

III3300 2RO/3y

RNSSuctionfromRCSInnerIsolationValve

LT 2y

PIV

SV4RNSPLV001B 1

N A

A 10 GA MO SV4RNSM6001 C

C AI PI 2RO/3y

D2

STC/III3600 2y

III3300 2RO/3y

RNSSuctionfromRCSInnerIsolationValve

LT 2y

PIV

SV4RNSPLV002A 1

N A

A 10 GA MO SV4RNSM6001 C

C AI PI 2RO/3y

F2

STC/III3600 2y

III3300 2RO/3y

LT 2y

PIV RNSSuctionfromRCSOuterIsolation/ICContainmentIsolationValve

LT AppJ

SV4RNSPLV002B 1

N A

A 10 GA MO SV4RNSM6001 C

C AI PI 2RO/3y

D2

STC/III3600 2y

III3300 2RO/3y

LT 2y

PIV RNSSuctionfromRCSOuterIsolation/ICContainmentIsolationValve

LT AppJ

SV4RNSPLV003A 1

N C

A 1

CK SA SV4RNSM6001 C

C/O NA CKC CS CSJRNS1

RNSPIVThermalReliefValve

G2

CKOP CS CSJRNS1 ThermalExpansion

SV4RNSPLV003B 1

N C

A 1

CK SA SV4RNSM6001 C

C/O NA CKC CS CSJRNS1

RNSPIVThermalReliefValve

D2

CKOP CS CSJRNS1 ThermalExpansion

SV4RNSPLV011 2

N A

A 8

GA MO SV4RNSM6001 C

C AI PI 2RO/3y

F7

STC/III3600 2y

III3300 2RO/3y

RNSDischargeHeadertoContainmentOCContainmentIsolationValve

LT AppJ

SV4RNSPLV012 2

N A

A 1

GL MA SV4RNSM6001 LC C/O AI ETM 2y

PostAccidentLongTermRCSMakeup&ContainmentIsolationValve G7

LT AppJ

SV4RNSPLV013 2

N AC A

8 CK SA SV4RNSM6001 C

C NA CKC CS CSJRNS1

F7

CKO CS CSJRNS1 ThermalExpansion RNStoContainmentICContainmentIsolationValve

LT App.J

SV4RNSPLV015A 1

N AC A

6 CK*

SA*

SV4RNSM6001 C

C/O NA CKC CS CSJRNS1

  • Note4

F8

CKO CS CSJRNS1 ThermalExpansion RNStoDVIStopCheckValve

LT 2y

PIV

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

826 SouthernNuclear

Version1.0 VOGTLEUNIT4 RNS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4RNSPLV015B 1

N AC A

6 CK*

SA*

SV4RNSM6001 C

C/O NA CKC CS CSJRNS1

  • Note4

F8

CKO CS CSJRNS1 ThermalExpansion RNStoDVIStopCheckValve

LT 2y

PIV

SV4RNSPLV017A 1

N AC A

6 CK SA SV4RNSM6001 C

C/O NA CKC CS CSJRNS1

F8

CKO CS CSJRNS1 ThermalExpansion RNStoDVICheckValve

LT 2y

PIV

SV4RNSPLV017B 1

N AC A

6 CK SA SV4RNSM6001 C

C/O NA CKC CS CSJRNS1

F8

CKO CS CSJRNS1 ThermalExpansion RNStoDVICheckValve

LT 2y

PIV

SV4RNSPLV020 2

N AC A

1 RV SA SV4RNSM6001 C

O/C NA RVT 4y/10y

RNSSuctionReliefValve

G2

LT App.J

SV4RNSPLV021 2

N AC A

3 RV SA SV4RNSM6001 C

O/C NA RVT 4y/10y

RNSSuctionReliefValve

G2

LT App.J

SV4RNSPLV022 2

N A

A 10 GA MO SV4RNSM6001 C

C AI PI 2RO/3y

F3

STC/III3600 2y

III3300 2RO/3y

RNSSuctionfromRCSOCContainmentIsolationValve

LT AppJ

SV4RNSPLV023 2

N A

A 10 GA MO SV4RNSM6001 C

C AI PI 2RO/3y

E3

STC/III3600 2y

III3300 2RO/3y

RNSSuctionfromIRWST/ICContainmentIsolationValve

LT AppJ

SV4RNSPLV061 2

N A

A 3

GL AO SV4RNSM6001 C

C C

PI 2y

G3

STC Q

FST Q

CVSReturntoRNSSuction/ICContainmentIsolationValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

827 SouthernNuclear

Version1.0 VOGTLEUNIT4 SDS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4SDSPLV001 3

N B

A 3

BU MO SV4SDSM6001 O

C AI PI 2RO/3y

E5

STC/III3600 2y

MCRSDS(Vent)IsolationValve

III3300 2RO/3y

SV4SDSPLV002 3

N B

A 3

BU MO SV4SDSM6001 O

C AI PI 2RO/3y

E5

STC/III3600 2y

MCRSDS(Vent)IsolationValve

III3300 2RO/3y

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

828 SouthernNuclear

Version1.0 VOGTLEUNIT4 SFS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4SFSPLV031 3

N B

P 6

BU MA SV4SFSM6001 LO O

AI PI 2y

RefuelingCavityDraintoS/G2CompartmentIsolationValve

F7

SV4SFSPLV033 3

N B

P 2

PL MA SV4SFSM6001 LC C

AI PI 2y

RefuelingCavityDraintoContainmentSumpIsolationValve

E7

SV4SFSPLV034 2

N A

A 6

BU MO SV4SFSM6001 C

C AI PI 2RO/3y

D6

STC/III3600 2y

III3300 2RO/3y

RefuelingCavity/IRWSTtoSFSICContainmentIsoValve

LT App.J

SV4SFSPLV035 2

N A

A 6

BU MO SV4SFSM6001 C

C AI PI 2RO/3y

D5

STC/III3600 2y

III3300 2RO/3y

RefuelingCavity/IRWSTtoSFSOCContainmentIsoValve

LT App.J

SV4SFSPLV037 2

N AC A

4 CK SA SV4SFSM6001 C

C/O NA CKC Q

B6

CKOP Q

ThermalExpansion SFStoRefuelingCavity/IRWSTICContainmentIsoValve

LT App.J

SV4SFSPLV038 2

N A

A 4

BU MO SV4SFSM6001 C

C AI PI 2RO/3y

D5

STC/III3600 2y

III3300 2RO/3y

SFStoRefuelingCavity/IRWSTOCContainmentIsoValve

LT App.J

SV4SFSPLV041 3

N B

A 6

BU MA SV4SFSM6001 LC C

AI ETM 2y

SFSCaskLoadingPitSuctionIsolationValve

F1

SV4SFSPLV066 3

N B

A 8

BA MA SV4SFSM6001 LC O/C AI ETM 2y

SpentFuelPoolBoiloffMakeupIsolationValve

G3

SV4SFSPLV067 2

N AC A

1 RV SA SV4SFSM6001 C

O/C NA RVT 10y

ThermalRelief RefuelingCavity/IRWSTtoSFSPenetrationReliefValve

E6

LT App.J

SV4SFSPLV068 3

N B

A 6

BU MA SV4SFSM6001 LO O

AI ETM 2y

SFSCaskWashdownPitDrainIsolationValve

F2

SV4SFSPLV071 3

N C

A 6

CK SA SV4SFSM6001 C

O/C NA CKC RO*

  • Note5 RefuelingCavitySideDraintoS/G2CompartmentValve

F7

CKO RO*

SV4SFSPLV072 3

N C

A 6

CK SA SV4SFSM6001 C

O/C NA CKC RO*

  • Note5 RefuelingCavitySideDraintoS/G2CompartmentValve

F7/8

CKO RO*

SV4SFSPLV075 3

N B

P 20 BU MA SV4SFSM6001 LO O

AI PI 2y

SFSReactorCavityPostAccidentContainmentFloodupValve

G7

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

829 SouthernNuclear

Version1.0 VOGTLEUNIT4 SGS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4SGSPLV027A 2

N B

A 12 GL MO SV4SGSM6001 O

C AI PI 2RO/3y

G4/5

STC/III3600 2y

SG1PORVIsolationValve

III3300 2RO/3y

SV4SGSPLV027B 2

N B

A 12 GL MO SV4SGSM6002 O

C AI PI 2RO/3y

G5

STC/III3600 2y

SG2PORVIsolationValve

III3300 2RO/3y

SV4SGSPLV030A 2

N C

A 8

RV SA SV4SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G4

SV4SGSPLV030B 2

N C

A 8

RV SA SV4SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G4

SV4SGSPLV031A 2

N C

A 8

RV SA SV4SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G3

SV4SGSPLV031B 2

N C

A 8

RV SA SV4SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G3

SV4SGSPLV032A 2

N C

A 8

RV SA SV4SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G3

SV4SGSPLV032B 2

N C

A 8

RV SA SV4SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G3

SV4SGSPLV033A 2

N C

A 8

RV SA SV4SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G3

SV4SGSPLV033B 2

N C

A 8

RV SA SV4SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G3

SV4SGSPLV034A 2

N C

A 8

RV SA SV4SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G2

SV4SGSPLV034B 2

N C

A 8

RV SA SV4SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G2

SV4SGSPLV035A 2

N C

A 8

RV SA SV4SGSM6001 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator01

G2

SV4SGSPLV035B 2

N C

A 8

RV SA SV4SGSM6002 C

O/C NA RVT 2y/5y IncludesPI MainSteamSafetyValveSteamGenerator02

G2

SV4SGSPLV036A 2

N B

A 2

GL AO SV4SGSM6001 O

C C

PI 2y

G3

STC Q

SteamLineCondensateDrainIsolation

FST Q

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

830 SouthernNuclear

Version1.0 VOGTLEUNIT4 SGS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4SGSPLV036B 2

N B

A 2

GL AO SV4SGSM6002 O

C C

PI 2y

G3

STC Q

SteamLineCondensateDrainIsolation

FST Q

SV4SGSPLV040A 2

N B

A 38 GA PH SV4SGSM6001 O

C C

PI 2y

G1

STC CS CSJSGS1 MainSteamLineIsolation

FST CS CSJSGS1

SV4SGSPLV040B 2

N B

A 38 GA PH SV4SGSM6002 O

C C

PI 2y

G1

STC CS CSJSGS1 MainSteamLineIsolation

FST CS CSJSGS1

SV4SGSPLV057A 2

N B

A 20 GA PH SV4SGSM6001 O

C C

PI 2y

E4

STC CS CSJSGS1 MainFeedwaterLineIsolation

FST CS CSJSGS1

SV4SGSPLV057B 2

N B

A 20 GA PH SV4SGSM6002 O

C C

PI 2y

E4

STC CS CSJSGS1 MainFeedwaterLineIsolation

FST CS CSJSGS1

SV4SGSPLV058A 2

N C

A 20 CK SA SV4SGSM6001 O

C/O NA CKC CS CSJSGS2

SG1MainFeedCheckValve

E5

CKOP CS CSJSGS2 ThermalExpansion

SV4SGSPLV058B 2

N C

A 20 CK SA SV4SGSM6002 O

C/O NA CKC CS CSJSGS2

SG2MainFeedCheckValve

E5

CKOP CS CSJSGS2 ThermalExpansion

SV4SGSPLV067A 2

N B

A 6

GA MO SV4SGSM6001 O

C AI PI 2RO/3y

D5

STC/III3600 2y

StartupFeedwaterIsolation

III3300 2RO/3y

SV4SGSPLV067B 2

N B

A 6

GA MO SV4SGSM6002 O

C AI PI 2RO/3y

D5

STC/III3600 2y

StartupFeedwaterIsolation

III3300 2RO/3y

SV4SGSPLV074A 2

N B

A 4

GL AO SV4SGSM6001 O

C C

PI 2y

C5

STC Q

SG1BlowdownIsolationValve

FST Q

SV4SGSPLV074B 2

N B

A 4

GL AO SV4SGSM6002 O

C C

PI 2y

C5

STC Q

SG2BlowdownIsolationValve

FST Q

SV4SGSPLV075A 3

N B

A 4

GL AO SV4SGSM6001 O

C C

PI 2y

C5

STC Q

SG1BlowdownIsolationValve

FST Q

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

831 SouthernNuclear

Version1.0 VOGTLEUNIT4 SGS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4SGSPLV075B 3

N B

A 4

GL AO SV4SGSM6002 O

C C

PI 2y

C5

STC Q

SG2BlowdownIsolationValve

FST Q

SV4SGSPLV086A 3

N B

A 2

GL AO SV4SGSM6001 C

C C

PI 2y

F3

STC Q

SG1SteamLineDrainLevelControl

FST Q

SV4SGSPLV086B 3

N B

A 2

GL AO SV4SGSM6002 C

C C

PI 2y

F3

STC Q

SG2SteamLineDrainLevelControl

FST Q

SV4SGSPLV233A 3

N B

A 12 GL AO SV4SGSM6001 C

C C

PI 2y

H4/5

STC RO

PerISTC3510

FST RO

PerISTC3510 SG1SteamLinePowerOperatedReliefValve

LT 2y

PerI8200

SV4SGSPLV233B 3

N B

A 12 GL AO SV4SGSM6002 C

C C

PI 2y

H5

STC RO

PerISTC3510

FST RO

PerISTC3510 SG2SteamLinePowerOperatedReliefValve

LT 2y

PerI8200

SV4SGSPLV240A 2

N B

A 3

GL AO SV4SGSM6001 C

C C

PI 2y

G1

STC Q

SG1MSIVBypass

FST Q

SV4SGSPLV240B 2

N B

A 3

GL AO SV4SGSM6002 C

C C

PI 2y

G1

STC Q

SG2MSIVBypass

FST Q

SV4SGSPLV250A 3

N B

A 20 GL AO SV4SGSM6001 O

C C

PI 2y

E2/3

STC CS CSJSGS1 MainFeedwaterControlValve

FST CS CSJSGS1

SV4SGSPLV250B 3

N B

A 20 GL AO SV4SGSM6002 O

C C

PI 2y

E2/3

STC CS CSJSGS1 MainFeedwaterControlValve

FST CS CSJSGS1

SV4SGSPLV255A 3

N B

A 6

GL AO SV4SGSM6001 C

C C

PI 2y

D4

STC Q

StartupFeedwaterControlValve

FST Q

SV4SGSPLV255B 3

N B

A 6

GL AO SV4SGSM6002 C

C C

PI 2y

D4

STC Q

StartupFeedwaterControlValve

FST Q

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

832 SouthernNuclear

Version1.0 VOGTLEUNIT4 SGS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4SGSPLV256A 3

N C

A 6

CK SA SV4SGSM6001 C

O NA CKC Q

SG1StartupFeedCheckValve

D4

CKOP Q

ThermalExpansion

SV4SGSPLV256B 3

N C

A 6

CK SA SV4SGSM6002 C

O NA CKC Q

SG2StartupFeedCheckValve

D4

CKOP Q

ThermalExpansion

SV4SGSPLV257A 3

N C

A 1

RV SA SV4SGSM6001 C

O NA RVT 10y

ThermalRelief MainFeedwaterThermalRelief

E4

SV4SGSPLV257B 3

N C

A 1

RV SA SV4SGSM6002 C

O NA RVT 10y

ThermalRelief MainFeedwaterThermalRelief

E4

SV4SGSPLV258A 3

N C

A 1

RV SA SV4SGSM6001 C

O NA RVT 10y

ThermalRelief StartupFeedwaterThermalRelief

D4

SV4SGSPLV258B 3

N C

A 1

RV SA SV4SGSM6002 C

O NA RVT 10y

ThermalRelief StartupFeedwaterThermalRelief

D4

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

833 SouthernNuclear

Version1.0 VOGTLEUNIT4 VBS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4VBSPLV186 3

N B

A 28 BU MO SV4VBSM6007 O

C AI PI 2RO/3y

F6

STC/III3600 2y

MCRSupplyAirIsolationValve

III3300 2RO/3y

SV4VBSPLV187 3

N B

A 28 BU MO SV4VBSM6007 O

C AI PI 2RO/3y

F6

STC/III3600 2y

MCRSupplyAirIsolationValve

III3300 2RO/3y

SV4VBSPLV188 3

N B

A 28 BU MO SV4VBSM6007 O

C AI PI 2RO/3y

C7

STC/III3600 2y

MCRReturnAirIsolationValve

III3300 2RO/3y

SV4VBSPLV189 3

N B

A 28 BU MO SV4VBSM6007 O

C AI PI 2RO/3y

C6

STC/III3600 2y

MCRReturnAirIsolationValve

III3300 2RO/3y

SV4VBSPLV190 3

N B

A 6

BU MO SV4VBSM6007 O

C AI PI 2RO/3y

C3

STC/III3600 2y

MCRToiletExhaustIsolationValve

III3300 2RO/3y

SV4VBSPLV191 3

N B

A 6

BU MO SV4VBSM6007 O

C AI PI 2RO/3y

C3

STC/III3600 2y

MCRToiletExhaustIsolationValve

III3300 2RO/3y

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

834 SouthernNuclear

Version1.0 VOGTLEUNIT4 VES ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4VESPLV001 3

N B

A 1

GL MA SV4VESM6002 C

O/C AI ETM 2y

AirDeliveryIsolationValve

D5

SV4VESPLV005A 3

N B

A 1

GL SO SV4VESM6002 C

O O

PI 2y

F5

STO Q

AirDeliveryIsolationValveA

FST Q

SV4VESPLV005B 3

N B

A 1

GL SO SV4VESM6002 C

O O

PI 2y

E5

STO Q

AirDeliveryIsolationValveB

FST Q

SV4VESPLV018 3

N B

A 1

GL MA SV4VESM6002 C

O/C AI ETM 2y

TemporaryInsturmentationIsolationValve

F5

SV3VESPLV019 3

N B

A 1

GL MA SV3VESM6002 C

O/C AI ETM 2y

TemporaryInsturmentationIsolationValve

E5

SV4VESPLV022A 3

N B

A 4

BU AO SV4VESM6002 C

O O

PI 2y

C2

STO Q

PressureReliefIsolationValveA

FST Q

SV4VESPLV022B 3

N B

A 4

BU AO SV4VESM6002 C

O O

PI 2y

C2

STO Q

PressureReliefIsolationValveB

FST Q

SV4VESPLV040A 3

N C

A 1

RV SA SV4VESM6001 C

O/C NA RVT 4y10y

AirTankSafetyReliefValveA

H4

SV4VESPLV040B 3

N C

A 1

RV SA SV4VESM6001 C

O/C NA RVT 4y10y

AirTankSafetyReliefValveB

F4

SV4VESPLV040C 3

N C

A 1

RV SA SV4VESM6001 C

O/C NA RVT 4y10y

AirTankSafetyReliefValveC

D/E4

SV4VESPLV040D 3

N C

A 1

RV SA SV4VESM6001 C

O/C NA RVT 4y10y

AirTankSafetyReliefValveD

C4

SV4VESPLV044 3

N B

A 1

GL MA SV4VESM6002 LO O/C AI ETM 2y

MainAirFlowpathIsolationValve

F4

SV4VESPLV045 3

N B

A 1

GL MA SV4VESM6002 LO O/C AI ETM 2y

EductorSupplyIsolationValve

E3

SV4VESPLV046 3

N B

A 1

GL MA SV4VESM6002 C

C/O AI ETM 2y

EductorBypassIsolationValve

D3

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

835 SouthernNuclear

Version1.0 VOGTLEUNIT4 VFS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4VFSPLV003 2

N A

A 16 BU AO SV4VFSM6001 C

C C

PI 2y

B4

STC Q

FST Q

ContainmentPurgeInletContainmentIsolORC

LT App.J

SV4VFSPLV004 2

N A

A 16 BU AO SV4VFSM6001 C

C C

PI 2y

B3

STC Q

FST Q

ContainmentPurgeInletContainmentIsolIRC

LT App.J

SV4VFSPLV009 2

N A

A 16 BU AO SV4VFSM6001 C

C C

PI 2y

D8

STC Q

FST Q

ContainmentPurgeDischargeContainmentIsolIRC

LT App.J

SV4VFSPLV010 2

N A

A 16 BU AO SV4VFSM6001 C

C C

PI 2y

D7

STC Q

FST Q

ContainmentPurgeDischargeContainmentIsolORC

LT App.J

SV4VFSPLV800A 2

N A

A 6

BU MO SV4VFSM6001 C

C/O AI PI 2RO/3y

E7

STC/III3600 2y

STO/III3600 2y

III3300 2RO/3y

ContainmentVacuumReliefIsolationValveAORC

LT App.J

SV4VFSPLV800B 2

N A

A 6

BU MO SV4VFSM6001 C

C/O AI PI 2RO/3y

E7

STC/III3600 2y

STO/III3600 2y

III3300 2RO/3y

ContainmentVacuumReliefIsolationValveBORC

LT App.J

SV4VFSPLV803A 2

N AC A

6 VB SA SV4VFSM6001 C

O/C NA VB 2y

ContainmentVacuumReliefValveAIRC

E7

LT App.J

SV4VFSPLV803B 2

N AC A

6 VB SA SV4VFSM6001 C

O/C NA VB 2y

ContainmentVacuumReliefValveBIRC

E7

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

836 SouthernNuclear

Version1.0 VOGTLEUNIT4 VWS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4VWSPLV053 3

N C

A 2

RV SA SV4VWSM6003 C

O NA RVT 10y

ThermalRelief CtmtCoolingUnitSupplyHdrRelief

B6

SV4VWSPLV057 3

N C

A 2

RV SA SV4VWSM6003 C

O NA RVT 10y

ThermalRelief CtmtCoolingUnitReturnHdrRelief

H4

SV4VWSPLV058 2

N A

A 8

BU AO SV4VWSM6003 O

C C

PI 2y

B6

STC Q

FST Q

ChilledWaterInletContainmentIsolValve

LT App.J

SV4VWSPLV062 2

N AC A

8 CK SA SV4VWSM6003 O

C/O NA CKC CS CSJVWS1

B6

CKOP CS CSJVWS1 ThermalExpansion FanCoolersSupplyICIsolCheckValve

LT App.J

SV4VWSPLV080 2

N AC A

1 RV SA SV4VWSM6003 C

O/C NA RVT 10y

ThermalRelief CtmtCoolingUnitReturnCIVRelief

H4

LT App.J

SV4VWSPLV082 2

N A

A 8

BU AO SV4VWSM6003 O

C C

PI 2y

G4

STC Q

FST Q

ChilledWaterOutletContainmentIsolationValve

LT App.J

SV4VWSPLV086 2

N A

A 8

BU AO SV4VWSM6003 O

C C

PI 2y

G3

STC Q

FST Q

ChilledWaterOutletContainmentIsolationValve

LT App.J

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

837 SouthernNuclear

Version1.0 VOGTLEUNIT4 WLS ValveID

Valve Valve Act.

Drawing PositionRequired Description Class Aug Cat. A/P Size Type Type &Coord Normal Safety FailSafe Test Freq CodeDev.

PlanNotes

SV4WLSPLV055 2

N A

A 2

PL AO SV4WLSM6001 C

C C

PI 2y

C4

STC Q

FST Q

ContainmentSumpDischargeCIVIRC

LT App.J

SV4WLSPLV057 2

N A

A 2

PL AO SV4WLSM6001 C

C C

PI 2y

C3

STC Q

FST Q

ContainmentSumpDischargeCIVORC

LT App.J

SV4WLSPLV058 2

N AC A

1 RV SA SV4WLSM6001 C

O/C NA RVT 10y

ThermalRelief ContainmentSumpDischargePenetrationThermalRelief C4

LT App.J

SV4WLSPLV067 2

N A

A 1

GL AO SV4WLSM6001 C

C C

PI 2y

E3

STC Q

FST Q

RCDTGasOutletCIVIRC

LT App.J

SV4WLSPLV068 2

N A

A 1

GL AO SV4WLSM6001 C

C C

PI 2y

E3

STC Q

FST Q

RCDTGasOutletCIVORC

LT App.J

SV4WLSPLV071A 3

N C

A 4

CK SA SV4WLSM6001 C

C/O NA CKC CS CSJWLS1

CVSComptFloorDrainCheck

C8

CKO CS CSJWLS1

SV4WLSPLV071B 3

N C

A 4

CK SA SV4WLSM6001 C

C/O NA CKC CS CSJWLS1

PXSComptAFloorDrainCheck

G8

CKO CS CSJWLS1

SV4WLSPLV071C 3

N C

A 4

CK SA SV4WLSM6001 C

C/O NA CKC CS CSJWLS1

PXSComptBFloorDrainCheck

G8

CKO CS CSJWLS1

SV4WLSPLV072A 3

N C

A 4

CK SA SV4WLSM6001 C

C/O NA CKC CS CSJWLS1

CVSComptFloorDrainCheck

C7

CKO CS CSJWLS1

SV4WLSPLV072B 3

N C

A 4

CK SA SV4WLSM6001 C

C/O NA CKC CS CSJWLS1

PXSComptAFloorDrainCheck

G8

CKO CS CSJWLS1

SV4WLSPLV072C 3

N C

A 4

CK SA SV4WLSM6001 C

C/O NA CKC CS CSJWLS1

PXSComptBFloorDrainCheck

G8

CKO CS CSJWLS1

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

91 SouthernNuclear

Version1.0 9.0 COLDSHUTDOWNTESTINGJUSTIFICATIONS

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

92 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-CAS1

SYSTEM:

CompressedAir(Service)

VALVE(S):

SV3/4CASPLV205

CATEGORY:

A/C

CLASS:

2

FUNCTION:

Thisvalveclosestoperformcontainmentisolation.

QUARTERLYTEST REQUIREMENT:

Exercisevalve,partialopencheckvalve,closecheckvalve.

PARTIALQUARTERLY STROKETESTING:

None

COLDSHUTDOWN JUSTIFICATION:

Thisvalveisclosedduringoperationduetoserviceairtocontainmentbeing isolatedbythemanualvalveoutsidecontainmentbeinglockedclosedfor ContainmentIsolation,perTech.Specs.Checkvalvecannotbeexercised withoutviolatingTech.Specs.byopeningmanualvalve.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

93 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-CVS1

SYSTEM:

ChemicalVolume&Control

VALVE(S):

SV3/4CVSPLV067,V080,V081&V082

CATEGORY:

C

CLASS:

1,3(V080)

FUNCTION:

ThesevalvesprovidetheflowpathfromtheCVSdeminsbacktotheRCS,and provideRCSpressureboundaryisolationbypreventingbackflowfromtheRCS tothenonsafetyrelatedCVSpiping.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalvepartopenandclosed.

COLDSHUTDOWN JUSTIFICATION:

Testingofthesevalvesduringnormalpoweroperationwouldrequireanentry intocontainment,andinterruptionofCVSpurificationflow,andapotential thermaltransientontheCVSpurificationsystemandpipingwhenplacingthe systembackintoserviceatpower.

QUARTERLY PARTIAL STROKETESTING:

None.Noindicationofobturatorpositiontoverifypartialstrokingofvalves.

CVSpurificationflowconfirmsflowthroughthevalves,butnotobturator function.

COLDSHUTDOWN TESTING:

Exercisecheckvalvepartopenandclosed.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

94 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-CVS2

SYSTEM:

ChemicalVolume&Control

VALVE(S):

SV3/4CVSPLV064,V100

CATEGORY:

A,C

CLASS:

2

FUNCTION:

ThesevalvesareinthemakeupflowpathfromtheCVSmakeuppumpstothe RCSandprovideapathtoaccommodatethermalexpansionofwaterinthe containmentpenetration.V100alsoprovidescontainmentpressureboundary isolationbypreventingbackflow.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalvepartopenandclosed.

COLDSHUTDOWN JUSTIFICATION:

Testingofthesevalvesduringnormalpoweroperationwouldrequireanentry intocontainmenttoisolateofthemakeupline,andinstallandoperateahydro pump.

QUARTERLY PARTIAL STROKETESTING:

None.Noindicationofobturatorpositiontoverifypartialstrokingofvalve.CVS makeupflowconfirmsflowthroughthevalves,butnotobturatorfunction.

COLDSHUTDOWN TESTING:

Exercisecheckvalvepartopenandclosed.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

95 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-DWS1

SYSTEM:

DemineralizedWater

VALVE(S):

SV3/4DWSPLV245

CATEGORY:

A/C

CLASS:

2

FUNCTION:

Thisvalveclosestoperformcontainmentisolation.

QUARTERLYTEST REQUIREMENT:

Exercisevalve,partialopencheckvalve,closecheckvalve.

PARTIALQUARTERLY STROKETESTING:

None

COLDSHUTDOWN JUSTIFICATION:

Thisvalveisclosedduringoperationduetodemineralizedwatertocontainment beingisolatedbythemanualvalveoutsidecontainmentbeinglockedclosedfor ContainmentIsolation,perTech.Specs.Checkvalvecannotbeexercised withoutviolatingTech.Specs.byopeningmanualvalve.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

96 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-FPS1

SYSTEM:

FireProtection

VALVE(S):

SV3/4FPSPLV052

CATEGORY:

A/C

CLASS:

2

FUNCTION:

Thisvalveclosestoperformcontainmentisolation.

QUARTERLYTEST REQUIREMENT:

Exercisevalve,partialopencheckvalve,closecheckvalve.

PARTIALQUARTERLY STROKETESTING:

None

COLDSHUTDOWN JUSTIFICATION:

Thisvalveisclosedduringoperationduetofirewatertocontainmentbeing isolatedbythemanualvalveoutsidecontainmentbeinglockedclosedfor ContainmentIsolation,perTech.Specs.Checkvalvecannotbeexercised withoutviolatingTech.Specs.byopeningmanualvalve.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

97 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-MSS1

SYSTEM:

MainSteam

VALVE(S):

SV3/4MSSPLV015A/B

CATEGORY:

B

CLASS:

N

FUNCTION:

ThisvalveclosestoisolatemainsteamintheeventofanMSIVfailure.

QUARTERLYTEST REQUIREMENT:

Stroketimeclosed,failsafe.

PARTIALQUARTERLY STROKETESTING:

None.Valvesdonothavepartialopencontrolfeature.

COLDSHUTDOWN JUSTIFICATION:

ThesevalvessupplymainsteamtotheMSRsduringpoweroperationtoremove moisturefromthereheatsteamgoingthroughthelowpressureturbines.

Operatingthesevalvesatpowerwouldresultinasecondarythermaltransient, anderosiondamagetothelowpressureturbineblades.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

98 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-PXS1

SYSTEM:

PassiveCoreCooling

VALVE(S):

SV3/4PXSPLV108A/B

CATEGORY:

B

CLASS:

1

FUNCTION:

ThesevalvesarelocatedatthedischargeofthePRHRheatexchangertothe RCS.Theyareclosedduringnormaloperationandshutdown,andopenona PRHRHXactuationsignal,toinitiatePRHRHXheatremovalinordertomitigate designbasisaccidents.

QUARTERLYTEST REQUIREMENT:

Exercisevalveandstroketimeopen,failsafetest.

COLDSHUTDOWN JUSTIFICATION:

Thesevalvescannotbetestedatpower,asareactortripisgeneratediftheyare notclosed.

QUARTERLY PARTIAL STROKETESTING:

None.

COLDSHUTDOWN TESTING:

Exercisevalveandstroketimeopen,failsafetest.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

99 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-PXS2

SYSTEM:

PassiveCoreCooling

VALVE(S):

SV3/4PXSPLV122A/B,V124A/B

CATEGORY:

C

CLASS:

1

FUNCTION:

Thesevalvesarenormallyclosedasthereisnoflowpathduringnormal operations.Thesevalvesarerequiredtoopenduringanyeventduringwhich theIRWSTorContainmentsumpmustprovideinjectionflowtotheRCS,and willcloseifthereisreverseflow.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalve.

COLDSHUTDOWN JUSTIFICATION:

Testingofthesevalvesatpowercannotbeperformedasthereisnoflowpath sinceitisisolatedbyasquibvalve.Testingrequiresentryintocontainment, isolationofatrainofIRWST/Containmentrecirculationsumpinjection,and installationoftemporaryequipmenttoprovideaflowpathforthevalvesandto monitortheirpositionduringtesting.Duetothepersonnelhazardsinvolved thiswillbeperformedduringcoldshutdown.

PARTIALQUARTERLY EXERCISE:

None

COLDSHUTDOWN TESTING:

Verificationofcheckvalveopeningandclosingwillbeperformed.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

910 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-PXS3

SYSTEM:

PassiveCoreCooling

VALVE(S):

SV3/4PXSPLV231A/B

CATEGORY:

C

CLASS:

2

FUNCTION:

ThesevalvesopentoallowfillingoftheCMTsfromtheMakeuppumps.The safetyfunctionofthesevalvesistoallowflowfromthetrappedliquidbetween thecheckvalveandtheairoperatefillvalveintheeventofthermalexpansion duetoheatupofthearea.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalve.

COLDSHUTDOWN JUSTIFICATION:

Acontainmententryisrequiredtobeabletoclosuretestthesecheckvalves.

PARTIALQUARTERLY EXERCISE:

None.Noindicationofobturatorpositiontoverifypartialstrokingofthevalves.

Routinefilling/makeupoftheCMTsconfirmsflowthroughthevalves,butnot obturatorfunction.

COLDSHUTDOWN TESTING:

Verificationofcheckvalvepartialopeningandclosingwillbeperformed.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

911 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-RCS1

SYSTEM:

ReactorCoolant

VALVE(S):

SV3/4RCSPLV001A/B,V002A/B,V003A/B,V011A/B,V012A/B,V013A/B

CATEGORY:

B

CLASS:

1

FUNCTION:

Thesevalvesarelocatedonthepressurizerandopentoreducethepressurein theRCSduringlossofcoolantaccidentsinordertopermitsafetyinjectionby PXS.

QUARTERLYTEST REQUIREMENT:

Exercisevalveandstroketimeopen,duetobeingHighSafetySignificantMOVs.

COLDSHUTDOWN JUSTIFICATION:

Thesevalvescannotbetestedatpowerastheyarerequiredtobeclosedto meettherequirementsof10CFR50.2,andtoprovideassurancethatinadvertent RCSdepressurizationdoesnotoccurduetothemispositioningofasinglevalve.

AnADSTESTMODEsignalisgeneratedbytheoperatorstoallowthistesting viaPrimaryDSPsoftcontrols.Thesignalrequiresthatalloftheisolationvalves associatedwiththeADSvalvebeingtested(includingtestvalvesV007A/B)be closedwhilethestroketestingoftheADSvalveisdone.TheRCSHLmustalso bebelow200°F(93°C).ThisensuresthatinadvertentRCSdepressurizationdoes notoccurduringthisprocess.

QUARTERLY PARTIAL STROKETESTING:

None.

COLDSHUTDOWN TESTING:

Exercisevalveandstroketimeopen.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

912 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-RCS2

SYSTEM:

ReactorCoolant

VALVE(S):

SV3/4RCSPLV150A/B/C/D

CATEGORY:

B

CLASS:

1

FUNCTION:

Thesevalvesarethereactorheadventvalveswhichcanremovenon condensablegasesorsteamfromthereactorvesselheadtomitigateapossible conditionofinadequatecorecoolingorimpairednaturalcirculationthroughthe steamgeneratorsresultingfromtheaccumulationofnoncondensablegasesin thereactorcoolantsystem.Thereactorvesselheadventvalvescanalsobe operatedfromthemaincontrolroomtoprovideanemergencyletdownpath whichisusedtopreventpressurizeroverfillfollowinglongtermlossofheatsink events.

QUARTERLYTEST REQUIREMENT:

Exercisevalveandstroketimeopenandclosed,failsafetest.

COLDSHUTDOWN JUSTIFICATION:

Thesevalvescannotbetestedatpower,asexercisingthemwouldputtheplant atriskofalossofreactorcoolantandRCSdepressurizationduetothemis positioningofasinglevalve.

QUARTERLY PARTIAL STROKETESTING:

None.

COLDSHUTDOWN TESTING:

Exercisevalveandstroketimeopenandclosed,failsafetest.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

913 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-RNS1

SYSTEM:

NormalResidualHeatRemoval

VALVE(S):

SV3/4RNSPLV003A/B,V013,V015A/B,V017A/B

CATEGORY:

C

CLASS:

1,2

FUNCTION:

ThesevalvesareintheflowpathforRNS,andprovideclosureforRCSpressure boundary,orcontainmentisolation(V013),andopentoprovideapathto accommodatethermalexpansionofwaterisolatedbetweenvalves,intheevent ofenvironmentalheatup.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalve.

COLDSHUTDOWN JUSTIFICATION:

Thesevalvescannotbetestedatpowerastheyarelocatedincontainmentand wouldrequirecontainmententryandsetupoftemporarytestequipmentin containmenttotestatpower.Additionally,RNScannotovercomeRCSpressure duringnormaloperation,andthesuctionflowpathisrequiredtobeisolated above450psigRCSpressure.

QUARTERLY PARTIAL STROKETESTING:

None.

COLDSHUTDOWN TESTING:

Exercisecheckvalve.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

914 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-SGS1

SYSTEM:

SteamGenerator

VALVE(S):

SV3/4SGSPLV040A/B,V057A/B,V250A/B

CATEGORY:

B

CLASS:

2(V040A/B,V057A/B),3(V250A/B)

FUNCTION:

Thesevalvesisolatefeedwaterto,orsteamfrom,thesteamgeneratorsinthe eventofanaccidentinordertominimizemassreleasefromthesteam generators.

QUARTERLYTEST REQUIREMENT:

Exerciseandstroketimeclosed,Failsafetest.

COLDSHUTDOWN JUSTIFICATION:

Thesevalvescannotbetestedatpowerasclosingthemwouldresultina reactortripduetotheisolationofsteamfrom,orfeedwaterto,thesteam generator.

QUARTERLY PARTIAL STROKETESTING:

None.Themainsteamandfeedwaterisolationvalvesdonothavecontrolsfor partialstrokecapability.Feedwatercontrolvalves,duetotheircontrolfunction areconstantlystrokingverysmallamounts,andmoreduringpowerreductions.

Sincetheseareconstantlyinmotion,nospecificpartstroketestingiscalledout butwillbedocumentedquarterly.

COLDSHUTDOWN TESTING:

Stroketimeclosed,andfailsafetest.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

915 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-SGS2

SYSTEM:

SteamGenerator

VALVE(S):

SV3/4SGSPLV058A/B

CATEGORY:

B

CLASS:

2

FUNCTION:

Thesevalvesisolatefeedwaterfromthesteamgeneratorsintheeventofan accidentinordertominimizemassreleasefromthesteamgenerators.They partiallyopentoallowforthermalexpansionofwaterbetweentheseandthe feedwaterisolationvalves.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalve(partialopenandclosed).

COLDSHUTDOWN JUSTIFICATION:

Thesevalvescannotbetestedatpowerasitwouldrequireisolationof feedwatertothesteamgeneratortoperformtheclosedtest,whichwould resultinareactortrip.Notethatnormaloperationvalidatestheopenportion ofthestroke.

QUARTERLY PARTIAL STROKETESTING:

None.Noindicationofobturatorpositiontoverifypartialstrokingofthevalves.

Feedwaterflowduringpoweroperationconfirmsflowthroughthevalves,but notobturatorfunction.

COLDSHUTDOWN TESTING:

Exercisecheckvalvepartiallyopenandclosed.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

916 SouthernNuclear

Version1.0 COLDSHUTDOWNJUSTIFICATION CSJ-VWS1

SYSTEM:

ChilledWater

VALVE(S):

SV3/4VWSPLV062

CATEGORY:

A,C

CLASS:

2

FUNCTION:

Thisvalveperformsthefunctionofcontainmentisolation,andopensto accommodatethermalexpansionofwatertrappedinthecontainment penetrationfollowingisolation.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalvepartiallyopenandclosed.

COLDSHUTDOWN JUSTIFICATION:

Thisvalvecannotbetestedatpower,asitwouldrequireentryintocontainment toeitherinstallandmonitornonintrusiveequipmentortoinstallameansto providebackpressureagainstthevalvetoconfirmclosure.Thiswouldresultin personnelhazardand/orlongtermsuspensionofcoolingtocontainment,which canresultincontainmenttemperaturesexceedingallowablelimits.

QUARTERLY PARTIAL STROKETESTING:

None.Noindicationofobturatorpositiontoverifypartialstrokingofthevalve.

Flowduringnormaloperationconfirmsflowthroughthevalve,butnot obturatorfunction.

COLDSHUTDOWN TESTING:

Exercisecheckvalvepartiallyopenandclosed.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

101 SouthernNuclear

Version1.0 10.0 REFUELINGOUTAGETESTINGFREQUENCYJUSTIFICATONS

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

102 SouthernNuclear

Version1.0 REFUELINGOUTAGEJUSTIFICATION ROJ-CAS1

SYSTEM:

CompressedAir(Instrument)

VALVE(S):

3CASPLV014,V015

CATEGORY:

A,A/C

CLASS:

2

FUNCTION:

Thesevalvesclosetoperformcontainmentisolation.

QUARTERLYTEST REQUIREMENT:

Stroketimeexerciseclosed,exercisecheckvalveclosed.

BASISFOR JUSTIFICATION:

Thesevalvesareopenduringoperationtoprovideinstrumentairto containment.Closingthesevalvesduringoperationorcoldshutdownwould interruptinstrumentairtocontainment.Duringoperationthiswouldresultin PRHRheatexchangeroutletvalvesopeningresultinginaReactorTrip.During ColdShutdowninterruptingInstrumentAirtocontainmentwouldresultinloss ofcontrolofairoperatedvalvesrequiredtomaintaincontroloftheplant.

PARTIALQUARTERLY EXERCISE:

None.AOVdoesnothavepartialopencontrolfeature,checkvalvedoesnot haveabilitytomonitorobturatorpositionwhileinservicethoughnormal operationconfirmsflowthroughthevalve.

REFUELINGSHUTDOWN TESTING:

Exercisecheckvalve,partialopen,closed,whichmaybeperformedin conjunctionwithleakratetesting.

Stroketimeclosed,andFailSafeverificationofAOV.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

103 SouthernNuclear

Version1.0 REFUELINGOUTAGEJUSTIFICATION ROJ-CCS1

SYSTEM:

ComponentCoolingWater

VALVE(S):

SV3/4CCSPLV201

CATEGORY:

A/C

CLASS:

2

FUNCTION:

Thisvalveclosestoperformcontainmentisolation,andpartiallyopensto accommodatethermalexpansionofwaterinthecontainmentpenetration.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalve.

BASISFOR JUSTIFICATION:

ThisvalveisopenduringoperationduetosupplyComponentcoolingwaterto containmentforRCPandLetdownheatexchangercooling.Checkvalvecannot beexercisedwithoutinterruptingcoolingwaterflowtocontainment,which wouldinterruptcoolingflowtothereactorcoolantpumpsresultinginaReactor CoolantPumpTriponhighbearingwatertemperature,andsubsequentReactor Trip.Additionally,itwouldrequireanentryintocontainmenttosetup equipmentandtestthevalve.

ReactorcoolantpumpsareoperatedduringColdShutdownifabubbleis maintainedinthepressurizer,astheRCPisthepreferredsourceofsprayfor PressurizerPressurecontrol.Closureofthisvalvefortestingwouldlikelyresult inanRCPtriponhighbearingwateroutlettemperature.

PARTIALQUARTERLY EXERCISE:

None.Noindicationofobturatorpositiontoverifypartialstrokingofvalve.

NormalCCSflowconfirmsflowthroughthevalve,butnotobturatorfunction.

REFUELINGSHUTDOWN TESTING:

Verificationofcheckvalveclosure.ThismaybedoneinconjunctionwithLocal Leakratetesting.Partialopenverificationisdemonstratedbynormaloperation andreturntoservicefollowingtheclosuretest.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

104 SouthernNuclear

Version1.0 REFUELINGOUTAGEJUSTIFICATION ROJ-CVS1

SYSTEM:

ChemicalVolume&Control

VALVE(S):

SV3/4CVSPLV084&V085

CATEGORY:

B(V084),C(V085)

CLASS:

1

FUNCTION:

ThesevalvesareintheAuxiliarySpraysupplylinefromCVStothePressurizer spraynozzle,andisolatetheReactorCoolantPressureboundary.

QUARTERLYTEST REQUIREMENT:

V084stroketimeclosedandfailsafetest;V085Exercisecheckvalve(part open,closed).

BASISFOR JUSTIFICATION:

Testingofthesevalvesduringpoweroperation,orCOLDSHUTDOWNwiththe RCSpressurized,wouldresultinapressuretransientintheRCSduetoactuation ofAuxiliaryspray.

PARTIALQUARTERLY EXERCISE:

None

REFUELINGSHUTDOWN TESTING:

V084stroketimeclosedandfailsafetest;V085Exercisecheckvalve(part open,closed).

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

105 SouthernNuclear

Version1.0 REFUELINGOUTAGEJUSTIFICATION ROJ-PXS1

SYSTEM:

PassiveCoreCooling

VALVE(S):

SV3/4PXSPLV016A/B,V017A/B

CATEGORY:

C

CLASS:

1

FUNCTION:

ThesevalvesremainopeninaCMTactuationtoprovideflowfromtheCMTto theRCS.ItisrequiredtoclosetopreventreverseflowfromtheAccumulators throughtheCMTforlargecoldlegLOCAevents,withabreakeitherinthecold legneartheCMTpressurebalancelineorinthepressurebalancelineupstream oftheCMTisolationvalves,andsubsequentlyreopen.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalve.

BASISFOR JUSTIFICATION:

TestingofthesevalvesrequiresinitiationofsignificantreverseflowtotheDVI linewhichisnotpracticalduringoperationduetothepressureofothersystems supplyingtheDVIlineandthenormaloperatingpressureoftheCMTs.

Additionally,evenifreverseflowcouldbeachieved,flowtotheCMTpriorto thecheckvalvesseatingwoulddilutetheboronconcentrationoftheCMT.

Sincethecheckvalvesareinseriesthereisnowaytodeterminethatbothcheck valvesclosed.Testingrequiresthattestconnectionlinesoneachvalvebe utilizedandpositionindicatorsbeinsertedintothevalves,whichrequiresthe RCSdepressurized.

PARTIALQUARTERLY EXERCISE:

None

REFUELINGSHUTDOWN TESTING:

Verificationofcheckvalveclosureonbackflowconditions,andreopens followingcessationofreverseflow.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

106 SouthernNuclear

Version1.0 REFUELINGOUTAGEJUSTIFICATION ROJ-PXS2 SYSTEM:

PassiveCoreCooling

VALVE(S):

SV3/4PXSPLV028A/B,V029A/B

CATEGORY:

AC

CLASS:

1

FUNCTION:

ThesevalvesarenormallyclosedtoprovideisolationoftheRCSfromthelower designpressureaccumulators,andarerequiredtoopenduringanyeventduring whichtheAccumulatorsmustprovideinjectionflow,andwillcloseifthereis reverseflow.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalve.

BASISFOR JUSTIFICATION:

Testingofthesevalvesatpowercannotbeperformedastheaccumulatorsare atalowerpressurethantheRCS,seatingthecheckvalves.Thesevalvescannot betestedatColdShutdownduetotheneedforvolumeintheRCStoacceptthe injectionflow.Thesevalvesneedtobetestedwiththereactorheadremoved andthevesselincommunicationwiththerefuelingcavity.

PARTIALQUARTERLY EXERCISE:

None

REFUELINGSHUTDOWN TESTING:

VerificationofcheckvalveopeningandinjectiontotheRCSwiththeRCSopen totherefuelingcavity,andreclosesoncessationofflow.Thevalvesarefurther verifiedclosedduringthePIVleaktestfollowingpressurizationoftheRCS.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

107 SouthernNuclear

Version1.0 REFUELINGOUTAGEJUSTIFICATION ROJ-PXS3 SYSTEM:

PassiveCoreCooling

VALVE(S):

SV3/4PXSPLV119A/B

CATEGORY:

C

CLASS:

3

FUNCTION:

Thesevalvesarenormallyclosedasthereisnoflowpathduringnormal operations.Thesevalvesarerequiredtoopenduringanyeventduringwhich theContainmentRecirculationSumpmustprovideinjectionflowtotheRCS, andwillcloseifthereisreverseflow.

QUARTERLYTEST REQUIREMENT:

Exercisecheckvalve.

BASISFOR JUSTIFICATION:

Testingofthesevalvesatpowercannotbeperformedasthereisnowater source,andtheflowpathisisolatedbyasquibvalve.Testingrequiresopening thepipingandusingamechanicalexercisertomanipulatethevalve.Sincethe valveisincontainmentandrequiresbypassingtherecirculationsumpscreen,it willbeperformedduringrefuelingoutages.

PARTIALQUARTERLY EXERCISE:

None

REFUELINGSHUTDOWN TESTING:

Verificationofcheckvalveopeningandclosingwillbeperformedwitha mechanicalexerciserandvisualexamination.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

111 SouthernNuclear

Version1.0

11.0 INSERVICETESTINGOFDYNAMICRESTRAINTS TheVEGP3&4InserviceTestingProgramforDynamicRestraints(Snubbers)meetstherequirementsof SubsectionsISTAandISTDoftheASMEOMCode2012Edition.

SnubbervisualexaminationareperformedinaccordancewithISTD4200,onthescheduleestablished byISTD4250.

FortestingthesnubberpopulationisdividedintotwoDefinedTestPlanGroups(DTPGs)foreachUnit.

OneDTPGconsistsofalllargeboresnubbersattachedtothesteamgenerators(noneareattachedto theReactorCoolantPumps),andthesecondcontainingthebalanceofthesnubbers.BothDTPGswill betestedinaccordancewithISTD5200,atthefrequencyspecifiedbyISTD5240,usingthe10%Sample PlaninaccordancewithISTD5300.

ServiceLifemonitoringwillbeperformedforallsnubbersinaccordancewithISTD6000.

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

121 SouthernNuclear

Version1.0 12.0 DYNAMICRESTRAINTSNOTES

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

131 SouthernNuclear

Version1.0

13.0 VEGP3DYNAMICRESTRAINTSTABLES

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

132 SouthernNuclear

Version1.0

VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit3

DTPG1

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

SV3RCSSSE03A1 1

H SV3PH01V1001/G7&F4 N

SV3RCSSSE03A2 1

H SV3PH01V1001/G7&F4 N

SV3RCSSSE03B1 1

H SV3PH01V1001/G7&F4 N

SV3RCSSSE03B2 1

H SV3PH01V1001/G7&F4 N

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

133 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit3

DTPG2

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

CVS SV3CVSPH11Y02621 3

H SV3CVSPLW171/D4 N

SV3CVSPH11Y02622 3

H SV3CVSPLW171/D4 N

SV3CVSPH11Y0268 1

H SV3CVSPLW188/C4 N

SV3CVSPH11Y2040 1

H SV3CVSPLW171/C5 N

SV3CVSPH11Y2223 1

H SV3CVSPLW171/C5 N

SV3CVSPH11Y2224 1

H SV3CVSPLW171/C4 N

SV3CVSPH11Y2227 3

H SV3CVSPLW171/C3 N

SV3CVSPH11Y2229 1

H SV3CVSPLW182/C6 N

SV3CVSPH11Y2263 N

H SV3CVSPLW091/C4 N

SV3CVSPH11Y2265 N

H SV3CVSPLW091/B6 N

SV3CVSPH11Y2266 N

H SV3CVSPLW091/B6 N

SV3CVSPH11Y7074 3

H SV3CVSPLW187/B5 N

PXS SV3PXSPH11Y0020 1

H SV3PXSPLW01Q/C5 N

SV3PXSPH11Y0578 3

H SV3PXSPLW01Z/C5 N

SV3PXSPH11Y2052 3

H SV3PXSPLW02E/C5/6 N

SV3PXSPH11Y2057 3

H SV3PXSPLW015/C5 N

SV3PXSPH11Y2059 3

H SV3PXSPLW01H/B6 N

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

134 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit3

DTPG2(cont)

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

RCS SV3RCSPH11Y0039 1

H SV3RCSPLW023/B5 N

SV3RCSPH11Y0060NE 1

H SV3RCSPLW023/C6 N

SV3RCSPH11Y0060NW 1 H

SV3RCSPLW023/C6 N

SV3RCSPH11Y0067 1

H SV3RCSPLW01L/D4 N

SV3RCSPH11Y00811 1

H SV3CVSPLW188/D6 N

SV3RCSPH11Y00812 1

H SV3CVSPLW188/D6 N

SV3RCSPH11Y0082 1

H SV3RCSPLW028/C5 N

SV3RCSPH11Y0090 1

H SV3PXSPLW050/C3 N

SV3RCSPH11Y0103 1

H SV3RCSPLW043/C4 N

SV3RCSPH11Y0112 1

H SV3RCSPLW016/B5 N

SV3RCSPH11Y0388 1

H SV3RCSPLW030/D3 N

SV3RCSPH11Y0391 1

H SV3RCSPLW03D/D3 N

SV3RCSPH11Y0528 1

H SV3RCSPLW01K/D6 N

SV3RCSPH11Y0810 1

H SV3RCSPLW080/B5 N

SV3RCSPH11Y0811 1

H SV3RCSPLW080/B4 N

SV3RCSPH11Y0813 1

H SV3RCSPLW070/B4 N

SV3RCSPH11Y1127 1

H SV3RCSPLW021/C5 N

SV3RCSPH11Y1130 1

H SV3RCSPLW024/C4 N

SV3RCSPH11Y1132 1

H SV3RCSPLW023/B5 N

SV3RCSPH11Y1134 1

H SV3RCSPLW023/B6 N

SV3RCSPH11Y1140 1

H SV3RCSPLW029/B6 N

SV3RCSPH11Y1141 1

H SV3RCSPLW023/C6 N

SV3RCSPH11Y1144 1

H SV3CVSPLW182/B4 N

SV3RCSPH11Y2005 1

H SV3RCSPLW015/C5 N

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

135 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit3

DTPG2(cont)

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

RCS(cont.)

SV3RCSPH11Y2101 1

H SV3RCSPLW01F/B5 N

SV3RCSPH11Y2106 1

H SV3RCSPLW03B/D3 N

SV3RCSPH11Y2107 1

H SV3RCSPLW03A/D3 N

SV3RCSPH11Y2264 1

H SV3RCSPLW028/B6 N

RNS SV3RNSPH12Y2060 3

H SV3RNSPLW091/C6 Y

SGS SV3SGSPH11Y0001 2

H SV3SGSPLW020/C7 N

SV3SGSPH11Y0002 2

H SV3SGSPLW020/C7 N

SV3SGSPH11Y0004 2

H SV3SGSPLW020/C5 N

SV3SGSPH11Y0057 2

H SV3SGSPLW010/C4 N

SV3SGSPH11Y0058 2

H SV3SGSPLW010/B7 N

SV3SGSPH11Y0063 2

H SV3SGSPLW010/B7 N

SV3SGSPH11Y0463LO 2 H

SV3SGSPLW030/B6 N

SV3SGSPH11Y0463UP 2 H

SV3SGSPLW030/B6 N

SV3SGSPH11Y0464 2

H SV3SGSPLW030/A5 N

SV3SGSPH11Y0470 2

H SV3SGSPLW040/B6 N

SV3SGSPH11Y2002NW 2 H

SV3SGSPLW030/B/C6 N

SV3SGSPH11Y2002NE 2 H

SV3SGSPLW030/B/C6 N

SV3SGSPH11Y2021NW 2 H

SV3SGSPLW030/B6 N

SV3SGSPH11Y2021SW 2 H

SV3SGSPLW030/B6 N

SV3SGSPH11Y3101 2

H SV3SGSPLW040/B5/6 N

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

136 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit3

DTPG2(cont)

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

SGS(cont)

SV3SGSPH11Y3102 2

H SV3SGSPLW040/C6 N

SV3SGSPH11Y3121NW 2 H

SV3SGSPLW040/B6 N

SV3SGSPH11Y3121NE 2 H

SV3SGSPLW040/B6 N

SV3SGSPH11Y7057 2

H SV3SGSPLW040/C6 N

SV3SGSPH12Y0108UP 3 H

SV3SGSPLW140/D4 Y

SV3SGSPH12Y0108DN 3 H

SV3SGSPLW140/D4 Y

SV3SGSPH12Y0136UP 3 H

SV3SGSPLW130/D4 Y

SV3SGSPH12Y0136DN 3 H

SV3SGSPLW130/D4 Y

SV3SGSPH12Y0507UP 2 H

SV3SGSPLW140/C5 Y

SV3SGSPH12Y0507DN 2 H

SV3SGSPLW140/C5 Y

SV3SGSPH12Y0510UP 2 H

SV3SGSPLW130/C5 Y

SV3SGSPH12Y0510DN 2 H

SV3SGSPLW130/C5 Y

SV3SGSPH12Y7056 2

H SV3SGSPLW130/B6 Y

SV3SGSPH12Y7058 2

H SV3SGSPLW140/B6 Y

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

141 SouthernNuclear

Version1.0 14.0 VEGP4DYNAMICRESTRAINTSTABLES

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

142 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit4

DTPG1

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

SV4RCSSSE03A1 1

H SV4PH01V1001/G7&F4 N

SV4RCSSSE03A2 1

H SV4PH01V1001/G7&F4 N

SV4RCSSSE03B1 1

H SV4PH01V1001/G7&F4 N

SV4RCSSSE03B2 1

H SV4PH01V1001/G7&F4 N

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

143 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit4

DTPG2

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

CVS SV4CVSPH11Y02621 3

H SV4CVSPLW171/D4 N

SV4CVSPH11Y02622 3

H SV4CVSPLW171/D4 N

SV4CVSPH11Y0268 1

H SV4CVSPLW188/C4 N

SV4CVSPH11Y2040 1

H SV4CVSPLW171/C5 N

SV4CVSPH11Y2223 1

H SV4CVSPLW171/C5 N

SV4CVSPH11Y2224 1

H SV4CVSPLW171/C4 N

SV4CVSPH11Y2227 3

H SV4CVSPLW171/C3 N

SV4CVSPH11Y2229 1

H SV4CVSPLW182/C6 N

SV4CVSPH11Y2263 N

H SV4CVSPLW091/C4 N

SV4CVSPH11Y2265 N

H SV4CVSPLW091/B6 N

SV4CVSPH11Y2266 N

H SV4CVSPLW091/B6 N

SV4CVSPH11Y7074 3

H SV4CVSPLW187/B5 N

PXS SV4PXSPH11Y0020 1

H SV4PXSPLW01Q/C5 N

SV4PXSPH11Y0578 3

H SV4PXSPLW01Z/C5 N

SV4PXSPH11Y2052 3

H SV4PXSPLW02E/C5/6 N

SV4PXSPH11Y2057 3

H SV4PXSPLW015/C5 N

SV4PXSPH11Y2059 3

H SV4PXSPLW01H/B6 N

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

144 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit4

DTPG2(cont)

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

RCS SV4RCSPH11Y0039 1

H SV4RCSPLW023/B5 N

SV4RCSPH11Y0060NE 1

H SV4RCSPLW023/C6 N

SV4RCSPH11Y0060NW 1 H

SV4RCSPLW023/C6 N

SV4RCSPH11Y0067 1

H SV4RCSPLW01L/D4 N

SV4RCSPH11Y00811 1

H SV4CVSPLW188/D6 N

SV4RCSPH11Y00812 1

H SV4CVSPLW188/D6 N

SV4RCSPH11Y0082 1

H SV4RCSPLW028/C5 N

SV4RCSPH11Y0090 1

H SV4PXSPLW050/C3 N

SV4RCSPH11Y0103 1

H SV4RCSPLW043/C4 N

SV4RCSPH11Y0112 1

H SV4RCSPLW016/B5 N

SV4RCSPH11Y0388 1

H SV4RCSPLW030/D3 N

SV4RCSPH11Y0391 1

H SV4RCSPLW03D/D3 N

SV4RCSPH11Y0528 1

H SV4RCSPLW01K/D6 N

SV4RCSPH11Y0810 1

H SV4RCSPLW080/B5 N

SV4RCSPH11Y0811 1

H SV4RCSPLW080/B4 N

SV4RCSPH11Y0813 1

H SV4RCSPLW070/B4 N

SV4RCSPH11Y1127 1

H SV4RCSPLW021/C5 N

SV4RCSPH11Y1130 1

H SV4RCSPLW024/C4 N

SV4RCSPH11Y1132 1

H SV4RCSPLW023/B5 N

SV4RCSPH11Y1134 1

H SV4RCSPLW023/B6 N

SV4RCSPH11Y1140 1

H SV4RCSPLW029/B6 N

SV4RCSPH11Y1141 1

H SV4RCSPLW023/C6 N

SV4RCSPH11Y1144 1

H SV4CVSPLW182/B4 N

SV4RCSPH11Y2005 1

H SV4RCSPLW015/C5 N

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

145 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit4

DTPG2(cont)

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

RCS(cont.)

SV4RCSPH11Y2101 1

H SV4RCSPLW01F/B5 N

SV4RCSPH11Y2106 1

H SV4RCSPLW03B/D3 N

SV4RCSPH11Y2107 1

H SV4RCSPLW03A/D3 N

SV4RCSPH11Y2264 1

H SV4RCSPLW028/B6 N

RNS SV4RNSPH12Y2060 3

H SV4RNSPLW091/C6 Y

SGS SV4SGSPH11Y0001 2

H SV4SGSPLW020/C7 N

SV4SGSPH11Y0002 2

H SV4SGSPLW020/C7 N

SV4SGSPH11Y0004 2

H SV4SGSPLW020/C5 N

SV4SGSPH11Y0057 2

H SV4SGSPLW010/C4 N

SV4SGSPH11Y0058 2

H SV4SGSPLW010/B7 N

SV4SGSPH11Y0063 2

H SV4SGSPLW010/B7 N

SV4SGSPH11Y0463LO 2 H

SV4SGSPLW030/B6 N

SV4SGSPH11Y0463UP 2 H

SV4SGSPLW030/B6 N

SV4SGSPH11Y0464 2

H SV4SGSPLW030/A5 N

SV4SGSPH11Y0470 2

H SV4SGSPLW040/B6 N

SV4SGSPH11Y2002NW 2 H

SV4SGSPLW030/B/C6 N

SV4SGSPH11Y2002NE 2 H

SV4SGSPLW030/B/C6 N

SV4SGSPH11Y2021NW 2 H

SV4SGSPLW030/B6 N

SV4SGSPH11Y2021SW 2 H

SV4SGSPLW030/B6 N

SV4SGSPH11Y3101 2

H SV4SGSPLW040/B5/6 N

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

146 SouthernNuclear

Version1.0 VogtleElectricGeneratingPlant-Units3&4 DynamicRestraintTableUnit4

DTPG2(cont)

Pipe SnubberID Class Type Iso.Drawing/Coord Accessible Alt/CC Comments/Notes

SGS(cont)

SV4SGSPH11Y3102 2

H SV4SGSPLW040/C6 N

SV4SGSPH11Y3121NW 2 H

SV4SGSPLW040/B6 N

SV4SGSPH11Y3121NE 2 H

SV4SGSPLW040/B6 N

SV4SGSPH11Y7057 2

H SV4SGSPLW040/C6 N

SV4SGSPH12Y0108UP 3 H

SV4SGSPLW140/D4 Y

SV4SGSPH12Y0108DN 3 H

SV4SGSPLW140/D4 Y

SV4SGSPH12Y0136UP 3 H

SV4SGSPLW130/D4 Y

SV4SGSPH12Y0136DN 3 H

SV4SGSPLW130/D4 Y

SV4SGSPH12Y0507UP 2 H

SV4SGSPLW140/C5 Y

SV4SGSPH12Y0507DN 2 H

SV4SGSPLW140/C5 Y

SV4SGSPH12Y0510UP 2 H

SV4SGSPLW130/C5 Y

SV4SGSPH12Y0510DN 2 H

SV4SGSPLW130/C5 Y

SV4SGSPH12Y7056 2

H SV4SGSPLW130/B6 Y

SV4SGSPH12Y7058 2

H SV4SGSPLW140/B6 Y

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

151 SouthernNuclear

Version1.0

15.0 REFERENCES

15.1 GeneralReferences

15.1.1 ASMEOperationandMaintenanceofNuclearPowerPlantsCode,2012Edition (ASMEOM2012) 15.1.2 Vogtle3&4UpdatedFinalSafetyAnalysisReport,Revision8.2 15.1.3 AppendixA,VogtleElectricGeneratingPlant,Units3and4Technical Specifications,Amendment172(Unit3),Amendment170(Unit4).

15.1.4 LDCR2017070,MainControlRoomEmergencyHabitabilitySystem(VES)

ChangestoSatisfyPostActuationPerformanceRequirements(LAR17001)

[DesignChangePackage,APPGWGEE4733,Revision0]

15.1.5 CorrectiveActionRequest50001849 15.1.6 LetterfromVictorE.Hall(NRC)toBrianWhitley(SNC)datedMarch2, 2020,VOGTLEELECTRICGENERATINGPLANT,UNIT4-REQUESTFOR ALTERNATIVEUNDERTITLE10OFTHECODEOFFEDERALREGULATIONS, SECTION50.55a(z)(1):ALTERNATIVEREQUIREMENTSFORINSERVICETEST INTERVALCODEEDITION,UNIT4(ISTALT01),ADAMSAscensionNo.

ML20045D517.

15.2 SystemSpecificationDocuments

15.2.1 SV3CASM3001,AP1000CompressedandInstrumentAirSystem(CAS)

SystemSpecificationDocument,Revision0[APPCASM3001,Rev.2]

15.2.2 SV4CASM3001,AP1000CompressedandInstrumentAirSystem(CAS)

SystemSpecificationDocument,Revision0[APPCASM3001,Rev.2]

15.2.3 APPCCSM3001,AP1000ComponentCoolingWaterSystemDescription Document,Revision5 15.2.4 APPCNSM3001,ContainmentSystem:SystemSpecificationDocument, Revision6 15.2.5 APPCVSM3001,AP1000ChemicalandVolumeControlSystem(CVS)System SpecificationDocument,Revision9 15.2.6 SV3DWSM3001,DemineralizedWaterTransferandStorageSystem(DWS),

SystemSpecificationDocument,Revision1[APPDWSM3001,Rev.2]

15.2.7 SV4DWSM3001,DemineralizedWaterTransferandStorageSystem(DWS),

SystemSpecificationDocument,Revision1[APPDWSM3001,Rev.2]

15.2.8 APPFHSM3001,AP1000FuelHandlingSystemSystemSpecification Document,Revision4 15.2.9 SV3FPSM3001,AP1000FireProtectionSystemSystemSpecification Document,Revision0[APPFPSM3001,Rev.0]

15.2.10 SV4FPSM3001,AP1000FireProtectionSystemSystemSpecification Document,Revision0[APPFPSM3001,Rev.0]

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

152 SouthernNuclear

Version1.0 15.2.11 APPMSSM3001,AP1000MainSteamSystemSpecificationDocument, Revision4 15.2.12 APPMTSM3001,AP1000MainTurbineSystemSystemSpecification Document,Revision4 15.2.13 APPPCSM3001,PassiveContainmentCoolingSystemSystemSpecification Document,Revision11 15.2.14 APPPSSM3001,AP1000PrimarySamplingSystemSystemSpecification Document,Revision5 15.2.15 SV3PWSM3001,AP1000PotableWaterSystem(PWS)SystemSpecification Document,Revision0[APPPWSM3001,Rev.2]

15.2.16 SV4PWSM3001,AP1000PotableWaterSystem(PWS)SystemSpecification Document,Revision0[APPPWSM3001,Rev.2]

15.2.17 APPPXSM3001,PassiveCoreCoolingSystem,SystemSpecificationDocument, Revision10 15.2.18 APPRCSM3001,ReactorCoolantSystem,SystemSpecificationDocument, Revision12 15.2.19 APPRNSM3001,NormalResidualHeatRemovalSystemSystemSpecification Document,Revision7 15.2.20 APPSDSM3001,SanitaryDrainageSystem(SDS)SystemSpecification Document,Revision1 15.2.21 APPSFSM3001,AP1000SpentFuelPoolCoolingSystemSystemSpecification Document,Revision12 15.2.22 APPSGSM3001,SteamGeneratorSystem(SGS)SystemSpecification Document,Revision8 15.2.23 SV3VBSM3001,NuclearIslandNonradioactiveVentilationSystem,System SpecificationDocument,Revision2[APPVBSM3001,Rev.2]

15.2.24 SV4VBSM3001,NuclearIslandNonradioactiveVentilationSystem,System SpecificationDocument,Revision2[APPVBSM3001,Rev.2]

15.2.25 SV3VESM3001,AP1000MainControlRoomEmergencyHabitabilitySystem (VES)SystemSpecificationDocument,Revision4[APPVESM3001,Rev.8]

15.2.26 SV4VESM3001,AP1000MainControlRoomEmergencyHabitabilitySystem (VES)SystemSpecificationDocument,Revision4[APPVESM3001,Rev.8]

15.2.27 SV3VFSM3001,ContainmentAirFiltrationSystemSystemSpecification Document,Revision0[APPVFSM3001,Rev.1]

15.2.28 SV4VFSM3001,ContainmentAirFiltrationSystemSystemSpecification Document,Revision0[APPVFSM3001,Rev.1]

15.2.29 APPVUSM3001,AP1000ContainmentLeakRateTestSystemSystem SpecificationDocument,Revision6 15.2.30 SV3VWSM3001,CentralChilledWaterSystemSystemSpecification Document,Revision1[APPVWSM3001,Rev.0]

15.2.31 SV4VWSM3001,CentralChilledWaterSystemSystemSpecification Document,Revision1[APPVWSM3001,Rev.0]

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

153 SouthernNuclear

Version1.0 15.2.32 SV3WLSM3001,AP1000PlantLiquidRadwasteSystemSystemSpecification Document,Revision0[APPWLSM3001,Rev.9]

15.2.33 SV4WLSM3001,AP1000PlantLiquidRadwasteSystemSystemSpecification Document,Revision0[APPWLSM3001,Rev.9]

15.2.34 SV3WWSM3001,WasteWaterSystem(WWS)-SystemSpecification Document,Revision1[APPWWSM3001,Rev.4]

15.2.35 SV4WWSM3001,WasteWaterSystem(WWS)-SystemSpecification Document,Revision1[APPWWSM3001,Rev.4]

15.3 PipingandInstrumentationDiagrams-Unit3 15.3.1 SV3CASM6005,Revision5 15.3.2 SV3CASM6012,Revision4 15.3.3 SV3CCSM6002,Revision6 15.3.4 SV3CNSM6001,Revision0 15.3.5 SV3CNSM6002,Revision0 15.3.6 SV3CVSM6001,Revision6 15.3.7 SV3CVSM6003,Revision7 15.3.8 SV3CVSM6004,Revision5 15.3.9 SV3CVSM6005,Revision3 15.3.10 SV3DWSM6007,Revision2 15.3.11 SV3FPSM6004,Revision6 15.3.12 SV3MSSM6001,Revision2 15.3.13 SV3MTSM6002,Revision4 15.3.14 SV3PCSM6001,Revision5 15.3.15 SV3PCSM6002,Revision4 15.3.16 SV3PCSM6003,Revision2 15.3.17 SV3PSSM6001,Revision6 15.3.18 SV3PWSM6002,Revision5 15.3.19 SV3PXSM6001,Revision6 15.3.20 SV3PXSM6002,Revision9 15.3.21 SV3PXSM6003,Revision5 15.3.22 SV3PXSM6004,Revision3 15.3.23 SV3PXSM6005,Revision0 15.3.24 SV3RCSM6001,Revision7 15.3.25 SV3RCSM6002,Revision9 15.3.26 SV3RCSM6003,Revision4 15.3.27 SV3RCSM6004,Revision4 15.3.28 SV3RCSM6005,Revision1 15.3.29 SV3RNSM6001,Revision4 15.3.30 SV3SDSM6001,Revision2 15.3.31 SV3SFSM6001,Revision6 15.3.32 SV3SGSM6001,Revision7 ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

154 SouthernNuclear

Version1.0 15.3.33 SV3SGSM6002,Revision7 15.3.34 SV3VBSM6002,Revision7 15.3.35 SV3VBSM6007,Revision9 15.3.36 SV3VESM6001,Revision1 15.3.37 SV3VESM6002,Revision4 15.3.38 SV3VFSM6001,Revision8 15.3.39 SV3VUSM6001,Revision2 15.3.40 SV3VWSM6003,Revision3 15.3.41 SV3WLSM6001,Revision4 15.3.42 SV3WLSM6007,Revision5 15.3.43 SV3WWSM6005,Revision6

15.4 PipingandInstrumentationDiagrams-Unit4 15.4.1 SV4CASM6005,Revision6 15.4.2 SV4CASM6012,Revision5 15.4.3 SV4CCSM6002,Revision6 15.4.4 SV4CNSM6001,Revision0 15.4.5 SV4CNSM6002,Revision0 15.4.6 SV4CVSM6001,Revision5 15.4.7 SV4CVSM6003,Revision6 15.4.8 SV4CVSM6004,Revision4 15.4.9 SV4CVSM6005,Revision3 15.4.10 SV4DWSM6007,Revision2 15.4.11 SV4FPSM6004,Revision6 15.4.12 SV4MSSM6001,Revision2 15.4.13 SV4MTSM6002,Revision4 15.4.14 SV4PCSM6001,Revision5 15.4.15 SV4PCSM6002,Revision4 15.4.16 SV4PCSM6003,Revision3 15.4.17 SV4PSSM6001,Revision6 15.4.18 SV4PWSM6002,Revision6 15.4.19 SV4PXSM6001,Revision6 15.4.20 SV4PXSM6002,Revision9 15.4.21 SV4PXSM6003,Revision5 15.4.22 SV4PXSM6004,Revision3 15.4.23 SV4PXSM6005,Revision0 15.4.24 SV4RCSM6001,Revision7 15.4.25 SV4RCSM6002,Revision9 15.4.26 SV4RCSM6003,Revision4 15.4.27 SV4RCSM6004,Revision4 15.4.28 SV4RNSM6001,Revision4 15.4.29 SV4SDSM6001,Revision2 ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval

155 SouthernNuclear

Version1.0 15.4.30 SV4SFSM6001,Revision6 15.4.31 SV4SGSM6001,Revision7 15.4.32 SV4SGSM6002,Revision7 15.4.33 SV4VBSM6002,Revision7 15.4.34 SV4VBSM6007,Revision9 15.4.35 SV4VESM6001,Revision1 15.4.36 SV4VESM6002,Revision4 15.4.37 SV4VFSM6001,Revision8 15.4.38 SV4VUSM6001,Revision2 15.4.39 SV4VWSM6003,Revision3 15.4.40 SV4WLSM6001,Revision3 15.4.41 SV4WLSM6007,Revision4 15.4.42 SV4WWSM6005,Revision4

ND-20-0601 Enclosure 1: Vogtle Electric Generation Plant Units 3&4, Inservice Testing Program Plan - 1st Interval