Discusses GL 96-01, Testing of Safety Related Logic Circuits, Issued on 960110 & Licensee Responses .Informs That Submittals Provided Both Info Requested & Responses Required by GL 96-01.Closes TAC M94748
ML20216B890
Person / Time
Site: Vogtle Southern Nuclear icon.png
Issue date: 05/14/1998
From: Jaffe D
NRC (Affiliation Not Assigned)
To: Mccoy C
SOUTHERN NUCLEAR OPERATING CO.
References
GL-96-01, GL-96-1, TAC-M94748, NUDOCS 9805180502
Download: ML20216B890 (4)


Text

ro y25 e urg O

g 4

UNITED STATES g

=

j NUCLEAR REGULATORY COMMISSON p

WASHINGTON, D.C. 20066 4 001 May 14, 1998 Mr. C. K. McCoy Vice President l

Southem Nuclear Operating Company, Inc.

Post Office Box 1295 Birmingham, Alabama 35201-1295 i

SUBJECT:

COMPLETION OF LICENSING ACTION FOR GENERIC LETTER 96-01,

" TESTING OF SAFETY-RELATED LOGIC CIRCUlTS," DATED JANUARY 10,.

1996; VOGTLE ELECTRIC GENERATING PLANT, UNIT 2 (TAC NO. M94748)

Dear Mr. McCoy:

On January 10,1996, the U.S. Nuclear Regulatory Commission (NRC) issued Generic Letter (GL) 96-01, " Testing of Safety-Related Logic Circuits," to all holders of operating licenses or construction permits. The NRC issued GL 96-01 for three principal reasons:

1.

Notify addressees about problems with testing of safety-related logic circuits; 2.

Request that all addressees implement the actions described within the GL; and 3.

Require that all addressees submit to the NRC a written response regarding implementation of the requested actions.

In GL 96-01, the NRC staff specifically requested that licensees take the following actions:

1.

Compare electrical schematics and logic diagrams for the reactor protection system, emergency diesel generator load shedding and sequencing, and actuation logic for the engineered safety feature systems against plant surveillance test procedures to ensure that all portions of the logic circuitry, including the parallel logic, interlocks, bypasses, and inhibit circuits, are adequately covered in the surveillance procedures to fulfill the technical specification requirements. This review should also include rela) contacts, control switches, and other relevant electrical components within these systems, utilized in the logic circuits performing a safety function; and I

2.

Modify the surveillance procedures as necessary for complete testing to comply with the

{

technical specifications. Additionally, the licensee may request an amendment to the l

technical specificatinns if relief from certain testing requirements can be justified.

-.a i

7<o a

980518o5o2 9eo514 l

PDR ADOC% 05000425 l

P PM J

~,

.h:

\\.

' C.' K. McCoy May 14, 1998 Furthermore, the NRC staff required that addressets prepare and submit the following:

1. - A~ written response indicating whether or not the licensee would implement the actions requested above or propose an alternative action; j

.2.

. A schedule for completing the requested actians or proposed alternative; and l

3.

A response confirming completion of the requested actions.

l In response to GL 96-01, you provided letters da:ed April 12,1996, and November 20,1997, for

Vogtle Electric Generating Plant, Units 1 and 2. These submittals provided both the information requested and the responses required by GL 96-01 for Vogtle Unit 1; therefore, TAC No. M94747 was closed. Subsequently, by lette r dated May 7,1998, you, indicated that the GL 96-01 activities for Vogtle Unit 2 were completed during the Unit 2 outage. Accordingly, the GL 96-01 revie.. (TAC No. M94748) for Vogtle Unit 2 is closed, if you have any questions regarding this matter, please contact David H. Jaffe at (301) 415-1439.

I j

Sir.cerely, ORIGINAL SIGNED BY:

Dtvid H. Jaffe, Senior Project Manager Project Directorate 11-2 Disisjon of Reactor Projects - 1/11 Office of Nuclear Reactor Regulation Docket No. 50-425 cc: See next page GSTRIBUTION:

Docket File H. Garg, HICD PUBLIC ACRS PDil-2 Rdg.

DJaffe

OGC LBerry JZwolinski LPlisco, Ril HBerkow PSkinner, Ril
DOCUMENT NAME: G:\\VOGTLE\\GL9601.WP To receive a copy of this document, indicate in the box: "C" = copy without enclosures "E" = Copy with cnclosures "N" = No copp

\\

ts OFFICE PM:PDilffF /

LA:PDil(2)1 HICB:NRR -

.gf.D:PDil-2 NAME DJaffe:cri d/l LBerry \\/ $ /

HGarg /M4 /" HBerkow DATE TM 9f V -

6 /P/4C \\

f /48 / 7 7 5 /M/93

.i 1

~

l OFFICIAL RECORD COPY

)

l.

.C. K. McCoy I Furthermore, the NRC staff required that addressees prepare and submit the following:

1.

A written response indicating whether or not the licensee would impfement the actions requested above or propose an attemative action; 2.

A schedule for completing the requested actions or proposed attemativo; and 3.

A response confirming cornpletion of the rt! quested actions.

1 In responst* to GL 96-01, you p ovided letters date d April 12,1996, and November 20,1997, for Vogtle Electric Generating Plant, Unita 1 and 2. These submittals provided both the information requested and the responses required by GL 96-01 for Vogtle Unit 1; therefore, TAC No. M94747 was closed. Subsequently, by letter dated May 7,1998, you indicated that the GL 96-01 activities for Vogtle Unit 2 were completed during the Unit 2 outage. Accordingly, the GL 96-01 review (TAC No. M94748) for Vogtle Unit 2 is closed. If you have any questions regarding this matter, please contact David H. Jaffe at (301) 415-1439.

{

Sincenely, T

\\

k,

~

David IUaffe, e

r Project Manager Project Directorate ll 2 Division of Reactor Projects - l/il Office of Nuclear Rea ctor Regulation Docket No. 50-425 cc: See next page

Vootle Electric Generating Plant cc:

Harold Reheis, Director Mr. J. A. Bailey Department of Natural Resources Manager, Licensing 205 Butler Street, SE. Suite 1252 Southem Nuclear Operating Atlanta, Georgia 30334 Company, Inc.

P. O. Box 1295 Attomey General Birmingham, Alabama 35201-1295 Law Department 132 Judicial Building Mr. J. B. Beasley.

Atlanta, Georgia 30334 General Manager, Vogtle Electric Generating Plant Mr. R. D. Barker Southem Nuclear Operating Program Manager Company, Inc.

Fossil & Nuclear Operations P. O. Box 1600 Oglethorpe Power Corporation Waynesboro, Georgia 30830 2100 East Exchange Place P. O. Box 1349 Regional Administrator, Region 11 Tucker, Georgia 30085-1349 U. S. Nuclear Regulatory Commission Charles A. Patrizia, Esquire Atlanta Federal Center Paul, Hastings, Janofsky & Walker 61 Forsyth Street, SW., Suite 23T85 10th Floor Atlanta, Georgia 30303 1299 Pennsylvania Avenue Washington, DC 20004-9500

, Office of Planning and Budget Room 015B Arthur H. Domby, Esquire 270 Washington Street, SW.

Troutman Sanders Atlanta, Georgia 30334 NationsBank Plaza 600 Peachtree Street, NE.

Mr. J. D. Woodard suite 5200 Executive Vice President Atlanta, Georgia 30308-2216 Southem Nuclear Operating

' Company, Inc.

Resident inspector P. O. Box 1295 Vogtle Plant Birmingham, Alabama 35201-1295 8805 River Road Waynesboro, Georgia 30830 Steven M. Jackson

. Senior Engineer-Power Supply Office of the County Commissioner Municipal Electric Authority Burke County Commission of Georgia.

Waynesboro, Georgia 30830

'1470 Riveredge Parkway, NW.

Atlanta, Georgia 30328-4684

-