4 REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY EVALUATION OF DEVICE i-NO.: NR-355-D-106-3 DATE: January 7, 1998 PAGE: 1 OF 3 1
[
-DEVICE TYPE:
Smoke Detector MODEL:
SI Series 4
MANUFACTURER / DISTRIBUTOR:
Hochiki America Corporation 5412 Industrial Drive
-Huntington Beach, CA-92649 l
SEALED SOURCE MODEL DESIGNATION:
NRD Model h-001
}
Amersham Model AMM1001 i
.I9OTOPE:
MAXIMUM ACTIVITY:
j_
Am-241 0.5 pCi (18.5 kBq) 1 LEAK TEST FREOUENCY:
Not-required 1
a 3
PRINCIPAL USE:
(P) Ion Generator, Smoke Detectors i
4 CUSTOM DEVICE:
- YES, X
NO I
i' 9802020171 98010e PDR RC SSD pop 4PN
/>
1 REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES
+
t'
-SAFETY EVALUATION OF DEVICE' NO.: NR-355-D-106-E_
DATE: January 7, 1998 PAGE: 2 OF 3
. DEVICE TYPEt -Smoke: Detector i
DESCRIPTION 1 The SI series. smoke-detectors [(models SIH-24F, SIH-24FAP,-and' SIJ-24) are industrial-type detectors connected to and operated j-from a central fire control unit.
They are normally mounted on the ceiling or below-the floor.. These1 detectors are-designed such that;the radioactive material isinot readily accessible to; i
installers or users.
The ion chambers'for the detectors are the same.
The only major physical differences are the design of_the
. outer cover and in the method of attachment of the outer cover; 2
the SIJ-24 detector requires a-special tool to remove the outer cover, whereas the others do'not.
There are a few' minor internal physical differences.
The sensitivity lof the detectors to detect smoke also varies-.
t The method of assembly for the ion chamber is as follows:
j (1) The foil is captured onto the_ inner electrode with_a-retaining disc which'is staked in place by a hydraulically e
contrelled welding machine; (2) The inner electrode-is placed into the insulation plate and the intermediate electrode is then snapped over the inner electrode andlinto the insulation plate.
i One leg of the intermediate electrode snaps into the insulation 4-plate-and the other leg _ protrudes through_the insulation plate and is soldered; and (3) The outer electrode is then placed over.
-this assembly.. The outer electrode has:two-tabs,-180* apart, that are placed through-openings in both the insulation; plate and--
t the printed control board.
These tabs are t. hen' soldered.
Once this is. complete, the source is inaccessible without someone i
removing the printed circuit board from'the detector and l-de-soldering the two legs of the outer electrode.
I d
4 I-U i
4
)
i-1 4
J-REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY-EVALUATION OF DEVICE' NO.: NR-355-D-106-E' DATE: January 7, 1998 EAGEA'3 OF 3 DEVICE TYPE:
Smoke Detector DESCRIPTION: (Cont'dI Hochiki distributes these devices under different trade-names, consequently, the; detectors may have different product codes listed on the point' of sale labeling (see table bei wi).
Hochiki Simplex Radionics-SIH-24F 2098-9576 or D281 2098-9550 **
SIH-24FAP NA NA SIJ-24 NA NA Model 2098-9550 is identical mechanically and in sensitivity to detect smoke to Model 2098-9576 with the exception of the epoxy encapsulated printed circuit board used in Model 2098-9550.
D REFERENCES 1 The following-supporting documents for the smoke detector models-SI Series are hereby incorporated by reference and are made a part of this registry document, Hochiki America Corporation's application dated May 2,
- 1997, o
facsimiles dated June 18, 1997, December 1,
- 1997, December 4, 1997, and January 6, 1998, and letter dated August 4,-1997,.with enclosures thereto.
ISSUING AGENCY:
U.S. Nuclear Regulatory Commission
,)
Date:
Januarv 7.
1998 Reviewer:
/?
/
Jonn'W. Lubinski Date:
January 7.
1998 Concurrence:
IN,#
Steven L. Baggett