OPERATING DATA REPORT 50-220 DOCKET NO.
DATL June b, 1984 COMPLETED BY Thomas W. Rom n TELEPHONE l3i6)JW-2422 OPERATING STATUS Nine Mile Point Unit #1 Notes
- 1. Unit Name:
- 2. Reporting Period:
5/1/84 thru 5/31/84
- 3. Licensed Thermal Power (MWt):
1850 640
- 4. Nameplate Rating (Gross MWe):
- 5. Design Electrical Rating (Net MWe):
630 620
- 6. Maximum Dependable Capacity (Gross MWe):
610
- 7. Maximum Dependable Capacity (Net MWe):
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
- 9. Power Level To Which Restricted,if Any (Net MWe):
- 10. Reasons For Restrictions,if Any:
This Month Yr..to.Date Cumulatise
- 11. Hours In Reporting Period 744 3288.5 127.079.2
- 12. Number Of Hours Reactor Was Critical 0
1828.5 88,130.2
- 13. Reactor Reserve Shutdown Hours 0
0 1204.2
- 14. Hours Generator On.Line 0
1828.5 85313.8
- 15. Unit Reserve Shutdown Hours 0
0 20.4
- 16. Gross Thermal Energy Generated (MWil) 0 3.062.522.0 141.156.962.0
- 17. Gross Electrical Energy Generated (MWH) 0 1,034,284.0 46,666.065.0
- 18. Net Electrical Energy Generated (MWHy 0
1,001,923.0 45,196,682.0
- 19. Unit Service Factor 0
41.6 66.2
- 20. Unit Availability Factor 0
~41.6
-66.2
- 21. Unit Capacity Factor (Using MDC Net) 0 37.4 57.5
- 22. Unit Capacity Factor (Using DER Net) 0 36.8_
56.5
- 23. Unit Forced Outage Rate 0
0.0 17.1
- 24. Shutdowns Scheduled Over Next 6 Months (Type. Date.and Duration of Each):
Unit shutdown for biennial refuel and overhaul. Shutdown 3/16/84 scheduled for startup 6/10/84.
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
- 26. Units In Test Status (Prior to Commercial Operation):
Forecast AchieSed INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION (9/771 I
8406180217 840531 PDR ADOCK 05000220 R
PDR 1
~
1 AVER AGE D AtLY UNITPOWER LEVEL DOCKET NO. 50-220 9 Mile Pt. Unit #1 UNIT 6/5/84 DATE CO\\1PLETED fly Thomas W. Roman TELEPIIONE (315) 349-2422 ay 1984-AlONTH DAY AVER AGE DAILY POWER LEVEL.
DAY AVERACE DAILY POWER LEVEL (31We-Net)
(MWe Net) 17 0
2 0
0 IS 3
-0 19 0
4 0
20 0
s 0
21 0
'O 6
22 0
0 7
0 23 8
0 24 0
0 9
25 0
10 0
26
'O II O
27 0
12 0
2S 0
13 0
29 0
14 0
30 0
15
'0 0
31 0
16 t
INSTRUCTIONS l
On this for:nat.hst the aserage daily unit piswer lesel in MWe.Nei riit #d'j' d3F I" the 'cPunF in >nili. C.iiiiputs ti the nearest whole megaws t.
er (9/77) i
s 50-220 UNITSHUTDOWNS AND POWER REDUCTIONS DOCKET NO.
UNIT NAME 9 Mlle Pt. Unit #1 DATE 6/5/84 May 1984 COMPLETED 8Y Thomas W. Roman REPORT MONT11 TELEPHONE (315) 349-2422 "i
g '1, Cause & Corrective
=
e.
3
.E _e E
gsX Licensee gg a
c
$3 Action to N"-
l'* ' c C::
35 5
_E s E Event u '?
$E E
j5g Report ar
<50
]U Prevent Recurrence 6
i 84-6 840317 S
C 1
Unit shutdown for Biennial Refuel and overhaul.
t I
2 3
4 F: Forced Reason:
Method:
Exhibit G - Instructions S: Ssheduleil A Equipment Failure (Explain) 1 Manual for Preparation of Data B Maintenance of Test 2-Manual Scram.
Entry Sheets foi Licensee C Refueling 3 Automatic Scram.
Event Report (LER) File (NIJREG-D-Regulatory Restriction 4 Other (Explain) 0161)
E-Operator Training & License Examination F-Administrative 5
G-Operational Error (Explain t Exhibit i Same Source 08/77)
Il4)ther (Explain)
NIAGARA M0 HAWK POWER CORPORATION NINE MILE POINT NUCLEAR STATION UNIT #1 NARRATIVE OF OPERATING EXPERIENCE MAY 1984 The station has been shutdown since March 17th for scheduled refueling and overhaul. During the month of May the station experienced a series of cold shutdown scrams.
On 5/9/64 a spurious trip of IRM 11 and 16.
On 5/13/84 During power board switching a loss of power to RPS MG Sets.
On 5/21/84 High Pressure Scram during vessel hydrostatic testing.
On 5/24/84 A loss of scram header air pressure during a containment spray air test resulted in a scram dump instrument volume High Level Trip.
The station is scheduled to return to service in e6rly June 1984.
m m
.-. -m-
CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 WR #26138 CRD #71635, Rebuilt CRD WR #25129 05-03 Emer. Cond. Vent Valve, repacked and adjusted WR #25335 CRD 46-31, uncoupled drive WR #25334 CRD 46-23, uncoupled drive WR #25329 CRD 22-35, uncoupled drive WR #24450 CRD 38-15, uncoupled drive WR #25321 CRD 38-19, uncoupled drive WR #23315 EC Valve #05-01, replaced packing and lap WR #25337 CRD 06-23, uncoupled drive WR #25322 CRD 38-27, uncoupled drive-WR #25332 CRD 30-31, uncoupled drive WR #25331 CRD 30-27, uncoupled drive WR #25327 CR0 30-19, uncoupled drive WR'#25333 CRD 22-31, uncoupled drive WR #25326 CRD 22-19, uncoupled drive WR #25324 CRD 14-27, uncoupled drive WR #25330 CRD.22-23, uncoupled drive WR #25325 CRD 14-19, uncoupled drive WR #25336 CRD 06-31, uncoupled drive WR #25972 CRD 34-31, uncoupled drive WR #25323 CR0 38-25, uncoupled drive WR #25328 CRD 30-35, uncoupled drive WR #24449 CRD 14-15, uncoupled drive WR #25973 CRD 42-31, uncoupled drive WR #25975 CRD 22-03, uncoupled drive WR #23445
- 14 Rx Recirc Pump-removed and replaced mechanical seal WR #26135 CRD #71634, Rebuilt Drive WR #26137 CRD #71719, Rebuilt Drive WR #26473 CRD(106)26-27 Charging Water Valve installed stem, seat ring, and packing WR #264.76 CRD(106)22-31 Charging Water Valve installed stem, seat ring, and packing WR #26427 CRD(106)26-19 Charging Water Valve installed stem, seat ring, and packing WR #26428 CRD(106)18-23 Charging Water Valve installed stem, seat ring, and packing WR #26031 CR0 #71640 Rebuilt Drive WR #26486 CRD(106)26-35 Charging Water Valve installed stem, seat ring, and packing WR #26505 CRD 10-31 replaced uncoupling pin WR #26033 CRD #71563 Rebuilt Drive WR #23460 Control Rod Drives-Leak Rate Tested listed CRD's
CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #26139 CRD #7054 Rebuilt Drive WR #26140 CRD #71682 Rebuilt Drive WR #23442
- 12 CRD Pump-Rebuilt pump WR #26136 CRD #71678 Rebuilt Drive WR #24613 N2 Purge & Fill Valve #20112-33. Disassembled, repaired, repacked, reassembled WR #26032 CRD #71627 Rebuilt Drive WR #24736
- 13 Rx Recirc Pump-removed and replaced mechanical seal WR #26134 CRD #71457 Rebuilt Drive WR #26548 CRD 107 Valve) 38 replaced washer WR #26501 CRD Accum BV 111 Valve 14-23) - repaired seat and packing WR #26487 CRD 106 Valve 34-19, Replaced ball and set screw WR #26471 CRD 106 Valve 10-35 Replaced set screw WR #26426 CRD 106 Valve 18-03, Replaced ball and packing WR #26683 CRD 106 Valve 22-31, Replaced ball and packing WR #26483 CRD 106 Valve 38-35, Replaced ball and packing WR #26425 CRD 106 Valve 42-31, Adjusted nut on stem WR #26685 CRD 106 Valve 18-23, Adjusted handle WR #26508 CRD 106 Valve 42-39, Replaced ball, packing and set screw WR #26472 CRD 106 Valve 14-43, Adjusted nut on stem WR #26682 CRD 106 Valve 26-27, Adjusted nut on stem, replaced ball WR #26681 CRD 106 Valve 26-35, Adjusted nut, reassembled WR #26684 CR0 106 Valve 26-19, Replaced ball and reassembled WR #26430 CRD 106 Valve 06-35, Replaced ball, spring WR #26475 CRD 106 Valve 02-27, Replaced shaft, ball, spring WR #26433 CRD 106 Valve 02-35, Replaced shaft, ball, spring WR #26423 CRD 106 Valve 46-27 Replaced ball, spring WR #26421 CR0 106 Valve 34-51, Replaced ball, spring WR #26432 CRD 106 Valve 18-51. Replaced ball, spring WR #26431 CRD 106 Valve 06-39, Replaced ball, spring WR #26429 CRD 106 Valve 14-15, Replaced ball, spring WR #26424 CRD 106 Valve 26-51, Replaced ball, spring WR #26299 Liquid Poison Valve 42.1-03, replaced center section WR #26343 CR Door #41 repaired latch WR #26045 CR0 #71560 Rebuilt Drive WR #26595 Hanger Clamp-39-HS, Installed stud and nuts, tightened WR #26592 Hanger Clamp-39-H12, Installed stud and nuts, tightened WR #26463 Spring loaded Clamps-39-H29-Installed stud and nuts, tightened WR #26452 Spring loaded Clamps-39-H21-Installed stud and nuts, tightened WR #26046 CRD #71338 Rebuild Drive WR #26300 Liquid Poison Valve 42.1-02, replaced Chk Valve WR #23446
- 12 Rx Recirc Pump-removed and replaced mechanical seal WR #26549 CRD(107 Valve)46-35,replacedstemandrepacked
t D
CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #26422 CRD 106 Valve 46-39, Changed ball, welded new body in place WR #26438 PSV 81-11 Core Spray 12 Loop Relief Valve, removed PSV 81-11 installed in #11 Core Spray Loop WR #26444 Weld #40-SW-498, took boat samples, ground crack and welded-WR #25751
- 01-06 warm up Valve #112, removed Valve, installed plug, reinstalled valve, welded limit switch.
- 12 FW Pump FCV, replaced upper and lower stem, seat rings, gasket WR #25602 MSIV #111-01-01, installed new stem, packing, gasket, lapped r
i WR #24586 CRD #71336 Rebuild Drive WR #26417
- 112 Core Spray Topping Pump, replaced nipple on pipe l
- 11 CRD Relief Valve, removed Valve and installed blank f
WR #26048 CRD #71578 Rebuild CRD WR #26556 Valve #93-52, repaired cap WR #26457
- 39-H-34, Spring absorber, tightened upper and lower jam nut WR #26462
- 39-H-23, Shock absorber, tightened loose bolt on clamp WR #26598
- 39-H-2, Spring support, tightened loose bolt WR #26456
- 39-H-31, Shock absorber, tightened loose bolt WR #26458
- 39-H-34, Shock absorber, tightened loose bolt WR #26599
- 39-H-22, Shock absorber, tightened loose bolt WR #26455
- 39-H-37, spring support, tightened upper & lower clevis nut WR #21209 50-15 Cond. Demin., removed cover, replaced gasket, put cover in place WR #24588 Replaced 01-05 and 01-06 Drain Valves 706, 708, 709, 711, WR #25758 MSIV 01-04, disassembled, lapped and reassembled WR #26748 CRD Water Filter #12, replaced with clean filters WR #26026 DW Post LOCA Flow-Valve 201.1-09, disassembled, cleaned and reassembled WR #26245 Rx Bldg Air Lock, replaced rubber seals on both doors WR #26542 Core Spray Valve 81-11 removed, reset, replaced WR #24458 CRD 42-23, removed CRD 71453, replaced with 71592 WR #24459 CRD 42-27, removed CRD 71361, replaced with 71379 WR #26742 CRD 50-23, Foot Valve replaced worn gaskets WR #26744 CRD 38-31, Foot Valve replaced worn gaskets WR #26752 CRD 18-27, Foot Valve, replaced worn gaskets WR #26745 CRD 22-19, Foot Valve, replaced worn gaskets WR #26743 CRD 38-39, Foot Valve, replaced worn gasket 3
CLASS I WORK - HECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #21222
- 12 Cond. Demin 50-12, Inspected WR #26787 CRD 22-51 HCU, replaced packing and 0 rings WR #26785 CRD 38-47 HCU, replaced packing and 0 rings WR #26789 CRD 18-03 HCU, replaced packing and 0 rings WR #26784 CRD 46-27 HCU, replaced packing and 0 rings WR #26563 CRD 50-23 HCU, replaced packing, 0 rings and gasket WR #26456
- 39-SC-3 restraint, torqued bolts WR #26596
- 39-HS-1 Shock absorber, tightened clamp bolt WR #26451
- 39-HS-21 Shock absorber, tightened clamp bolt WR #25607 Torus MUIV, #58.1-01, repaired operator WR #21224 Cont. Vent Post LOCA BV, #201.2-538, installed new packing WR #26170 66-26-10" Vac. Bkr.-polished shaft, replaced 2 bushings, new gaskets WR #21223 Cont. Equip Hatch-Installed new 0 rings, closed hatch WR #26812 Cont Spray Raw Water BV #93-18, disassembled, cleaned, reassembled WR #26827
- 12 CRD Pump Bearing, inspection WR #26211 Main Stm (Sys. 66) 4" Vacuum Relief Valve, disassembled, checked internals, reassembled WR #26831 18-07 CRD Scram Outlet Valve (127), repacked, replaced seat, plug, plug guide WR #24975 CRD & Thermal Sleeve 50-19, removed and replaced CRD WR #26687 CRD #7156, leak rate tested WR #25992 Hydraulic Snubber 29-HS-16, overhauled, performed funct. test WR #26132 Hydraulic Snubber SI-HS-5, overhauled, performed funct. test WR #25991 Hydraulic Snubber 29-HS-9, overhauled, performed funct. test WR #25996 Hydraulic Snubber 38-HS-6, overhauled, performed funct. test WR #25998 Hydraulic Snubber 39-HS-2, overhauled, performed funct, test WR #25993 Hydraulic Snubber 30-HS-2, overhauled, performed funct, test WR #25999 Hydraulic Snubber 39-HS-17, overhauled, performed funct. test WR #26260 Hydraulic Snubber 39-HS-32, overhauled, performed funct, test WR #26258 Hydraulic Snubber 39-HS-25, overhauled, performed funct, test WR #26257 Hydraulic Snubber 39-HS-15, overhauled, performed funct. test WR #26253 Hydraulic Snubber 29-HS-13, overhauled, performed funct. test WR #26252 Hydraulic Snubber 29-HS-2, overhauled, performed funct. test WR #25399 CRD #7054. Removed drive, installed thermal sleeve, replaced drive WR #25712 CRD #71635, Removed drive, installed thermal sleeve, replaced drive v
CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #26248 Hydraulic Snubber 40-HS-6, reset snubber to 2 3/4" WR #26249 Hydraulic Snubber 37-HS-1, reset snubber to 3 1/2" WR #26250 Hydraulic Snubber 36-HS-2, reset snubber to 3 1/16" WR #24976 CRD Housing 50-19, rolled drive housing WR #26000 Hydraulic Snubber 39-HS-28, overhauled, performed funct. Test WR #25398 CRD 71457, removed drive, installed thermal sleeve, replaced drive WR #26764
- 13 Recirc Pump, tightened union WR #25124 31-01 FW Check Valve, replaced check valve
-WR #21226 Emerg. personnel hatch (DW) replaced DW side hatch with new gasket WR #23448
- 12 Core Spray Ck Vlv 40-03, disassembled WR #24752
- 12 IAC BV 94-35, installed new valve WR #26025 DW Post LOCA Flow to Emerg. Vent, 201.1-11-Disassembled valve, cleaned WR #26958 Cont. Spray Nozzles Valve 40-09, replaced 2 new nozzles WR #26765 Retainer CRD 42-39 to IRM, installed and adjusted retainer clip WR #26768 40-12 IV, tightened body bonnet flange and took up on packing WR #25340 CRD #71634, removed drive and thermal sleeve and reinstalled CRD WR #26758 Core Spray Check VIV 81-CS-C-3, disassembled, checked internals, assembled valve WR #24460 CRD 30-33, drive uncoupled, replaced with rebuilt CRD WR #24452 CRD 14-39, drive uncoupled, replaced with rebuilt CRD WR #25922 CRD 22-39, drive uncoupled, replaced with rebuilt CRD WR #25921 CRD 42-35, drive uncoupled, replaced with rebuilt CRD WR #25923 CRD 22-47, drive uncoupled, replaced with rebuilt CRD WR #24456 CRD 18-51, drive uncoupled, replaced with rebuilt CRD WR #24453 CRD 14-35, drive uncoupled, replaced with rebuilt CRD WR #24454 CRD 34-15, drive uncoupled, replaced with rebuilt CRD WR #26528 CRD 06-39, drive uncoupled, replaced with rebuilt CRD WR #26129 CRD 22-23, drive uncoupled, replaced with rebuilt CRD WR #25971 CRD 10-31, drive uncoupled, replaced with rebuilt CRD WR #25397 CRD 34-07, drive uncoupled, replaced with rebuilt CRD WR #25339 CRD 30-07, drive uncoupled, replaced with rebuilt CRD WR #25394 CRD 14-11, drive uncoupled, replaced with rebuilt CRD WR #25400 CRD 42-39, drive uncoupled, replaced with rebuilt CDD WR #25396 CRD 46-27, drive uncoupled, replaced with rebuilt C M WR #25711 CRD 46-39, drive uncoupled, replaced with rebuilt CRD WR #23267 CRD 22-27, drive uncoupled, replaced with rebuilt CRD WR #26259 Hydraulic Snubber 39-HS-30, overhauled, performed funct, test WR #25994 Hydraulic Snubber 33-HS-1, overhauled, performed funct. test i
l
l l
CLASS I WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd t
WR #23463 Hydraulic Snubber 01-HS-2, functional tested and rebuilt, retested i
WR #26131 Hydraulic Snubber 40-HS-9, functional tested and rebuilt, retested WR #26133 Hydraulic Snubber 66-HS-9, functional tested and rebuilt, retested WR #26254 Hydraulic Snubber 30-HS-5, functional tested and rebuilt, retested WR #26251.
Hydraulic Snubber 01-HS-4, functional tested and rebuilt, retested WR #26256 Hydraulic Snubber 39-HS-8, functional tested and rebuilt, retested WR #25995 Hydraulic Snubber 36-HS-5, functional tested and rebuilt, retested i
WR #26255 Hydraulic Snubber 38-HS-8, functional tested and rebuilt, retested WR #21419 DW Cooling Fans, #11, 13, 14, Set blade angle WR #23444
- 15 Rx Recirc Pump, removed, replaced mechanical seal WR #26029
- 63-05 Post Accid. Sample Return, tightened packing glands WR #26969 replaced Cont. Spray Nozzles WR #21591 42.1-R1 Liquid Poison, reinstalled U-bolt WR #23449 Shoot out steel, installed WR #23457 Rx 340' disassembled and reassembled
+
WR #26847 CRD Scram inlet 18-07, replaced valve seat WR #26849 CRD HCU 18-07 (106 viv), replaced ball, spring, repacked valve WR #26261 Mech. Snubber #7544, replaced, attached bracket WR #23465 Mech, Snubber 51-MS-1, removed, tested, replaced snubber WR #23464 Mech. Snubber 40-MS-12, removed, tested, replaced snubber WR #23466 Mech. Snubber 32-MS-28, removed, tested, replaced snubber WR #23467 Mech. Snubber 32-MS-16, removed, tested, replaced snubber WR #23468 Mech. Snubber 32-MS-10, removed, tested, replaced snubber WR #24977 CRD & Thermal Sleeve, 50-19, Installed thermal sleeve and CRD WR #25997 Hydraulic Snubber 38-HS-12, functional tested, overhauled, retested WR #23469 Sta. Mech Snubbers, performed visual inspection per memo WR #26506
- 12 CRD Pump, rebuilt pump WR #26027 63-04, Post Accid. Sample, Return IV, reinstalled new valve WR #24615 63-05, Post Accid. Sample, Return IV, changed air lines for testing WR #23447
- 11 Rx Recirc Pump, replaced mechanical seal.
WR #21432 121 Core Spray Topping Pump Seal, replaced impeller wear rings, cosing rings, mechanical seal i
WR #24911 122 Core Spray Topping Pump Seal, Completely rebuilt pump WR #26691
- 122 Core Spray Pump, replaced pump WR #27003 Cond. Torus Makeup 58.1-04, installed premanent packing l
WR #23461 Torus Manway - removed and installed torus manway covers WR #27001 Cond. Torus Makeup 58.1-07, Changed spectacle flange WR #24616 Spectacle Flange 81-100 changed to blanked off position r
re CLASS 1 WORK - MECHANICAL MAINTENANCE - MAY 1984 Cont'd WR #26992 Spectacle Flange 81-99, changed to blanked off position WR #22369
- 122 Electromatic Relief Valve 66NR108D, machined parts and lapped WR #26997
_94-23 Blank Flange, removed orifice, installed blank flange WR #26994
- 111 Core Spray Topping Pump, tightened packing WR #26993
- 81-49, Core Spray Topping Pump #112, tightened packing WR #26995
- 81-52, Core Spray Topping Pump #122, tightened packing WR #26979 M.S. Warmup Valve, 01-05, replaced 0 rings in seal bushing WR #26980 M.S. Warmup Valve, 01-06, replaced 0 rings in seal bushing WR #26842 CRD HCU 38-47, 107 valve, disassembled, cleaned, checked seats, installed packing, new plug WR #26841 CR0 HCU 22-31, 107 valve, disassembled, cleaned, checked seats, installed packing, new plug WR #26975 C.U. Relief Disch to Torus 63-04 & 05, inspected and adjusted WR #27036 CR0 #46-27 #111 Foot Valve, replaced stem, packing and 0 rings WR #27035 CRD #22-11 #111 Foot Valve, replaced stem, packing and 0 rings
f CLASS I WORK - ELECTRICAL MAINTENANCE - MAY 1984 WR #25965 Torus Vent & Purge IV 201-09, removed leads and rewired WR #25966 Torus Vent & Purge IV 201-07, removed leads and rewired, checked rotation, cycled valve WR #26319 Aux. Feeder 102, repaired ARC chute with RTV 108 WR #26624 PB 102 supply 416 UV Breaker R1012, burnished contacts and checked resistance WR #26629 Cont. Spray pump 121 4160V Breaker, burnished contacts and checked resistance WR #26628 Core Spray pump 111 4160V Breaker, burnished contacts 1, 1T, 2, 2T, 4 & 4T and checked resistance WR #26622 Cont. Spray pump 111 4160V Breaker, burnished contacts 1, IT, 2, 2T, 4 & 4T and checked resistance WR #26625 PB 102 Aux. Feeder 4160V Breaker R1021, burnished contacts 1, IT, 2, 2T, 4 & 4T, and checked resistance WR #26623 Diesel Gen. 102, 4160V AA Breaker R11022, burnished contacts 1, IT, 2, 2T, 4 & 4T, and checked resistance WR #26627 Cont. Spray pump 112, 4160V Breaker, burnished contacts 1, IT, 2, 2T, 4 & 4T, and checked resistance WR #26626 Cont. Spray RW Pump 111 4168 Breaker, burnished contacts and checked resistance WR #25968 Limit switch Pos 68-01 ILSO, adjusted limit switches and operated valve switches.
'norus/0W Vac. breaker 68-04, adjusted limit switches and cycled valves WR #26634 Core Spray Topping Pump 111, overhauled breaker by GE & MPM-C2 was performed.
WR #26635 Core Spray Sump 112, overhauled by GE & MPM-C2 was performed WR #26636 Core Spray Topping Pump 112, overhauled by GE & MPM-C2 was performed WR #26637 Cont. Spray Raw Water Pump 121, overhauled by GE & MPM-C2 was performed WR #25367 Limit switches on valve 05-05/Pos. 05-03 ILSO 5-03 ILSC, Adjusted limit switches, cycled valves WR #25868 Pos. Valve 05/02, Pos. 05-02 ILS0, 05-02 ILSC, Adjusted limit switches cycled valves WR #26639 Main Steam IV-01-01, disconnected stem coupling and readjusted actuator slate and stem coupling WR #26640 Main Steam IV-01-02, disconnected stem coupling and readjusted actuator slate and reconnected stem ccupling WR #20731 Limitorque valve actuator 39-07, removed spring cartridge cap cover, drilled and tapped cover, installed pipe plug, replaced cover WR #26555 Emergency Condenser valve auto open relay 12K62, replaced time relay coil WR #25211 CAD 02 & H2 sample IV 201.2, 109 & 111, wires have been removed, reconnected wires, installed new flex cond.
WR #26753 Core Spray Punp Motor 121, reconnected, retaped, meggered and checked rotation WR #26755 Core Spray Pump Motor 122, reconnected, retaped, meggered and checked rotation
CLASS I WORK - ELECTRICAL MAINTENANCE - MAY 1984 Cont'd WR #26603 DW Vent & Purge limitorque, drilled spring cap cover and installed Pipe plug WR #26604 Emergency Condenser IV Limitorque, drilled and taped spring cap cover to perform movats WR #26606 DW Vent & Purge, removed spring cap cover and installed pipe plug WR #26705 Limit switches on ' valve 68-02, adjusted switches and operated valves several times WR #26704 Limit switches on valve 68-03, adjusted switches and operated valve i
several times WR #26961 SDC IV38-13, removed motor from 38-13 for rewind WR #26902 SDC IV38-01, removed motor from 38-01 for rewind WR #26864 Limitorque actuator IV33-01, removed switches and replaced gaskets with issue attached WR #26971 RPS Transmitters in West Instr. Room, replaced condelet and sealed with i
Kaowool and Bisco Locaseal WR #26972 RPS Transmitters in East Instr. Room, replaced condelet and sealed with Kaowool and Bisco Locaseal l
M.0. 3390 Mark I Containment Low Low Set Point M.0. 3410 Appendix R - ADS Logic M.0. 3938 Feedwater Low Flow Control M.0. 3405 Appendix R - Remote Shutdown Panel
[
M.0. 3384 Feedwater High Level Trip i
M.0. 3411 Appendix R - Core Spray /Rx Head Vent M.0. 1927 Equipment Qualification l
M.0. 3171 Appendix J l
M.0. 2440 containment Vent System, Post LOCA i
M.0. 3406 Appendix R-Emergency Condenser Logic M.0. 2131 Rx Protection System - MG Sets
(
5
. CLASS I WORK -INSTRUMENT & CONTROL - MAY 1984 WR #26126 SRM #13 Reading High (found moisture in connector
- cleaned,-dried, and reconnected)
. Vacuur Breaker Limit Switches 68-02 Out of Adjustment
- Recalibrated per ICP-68-TVB E,-
se>en a nemes afIACES-tNITS NO AUXILIARIES MDNTil - MaV, YEAR 1984 i[aN'a^Nr uself AWA8LA8LE hours REAScess / REPA1RS aut Eensawany pay gas T hen Las AVA IL ASLF HOURS CAP.
1 Rx 3/17/84 0130 3/84-358.5 Plant shutdown for biennial refuel and overhaul.
4/84-719 5/84-744 I
I l
total 1821.5 i
l 4
f i
i.
i I
i l
l 1
l l
N M V NIAGARA RUMOHAWK NIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST, SYRACUSE. N.Y.13202/ TELEPHONE (315) 474-1511 June 8,1984 Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 Attn:
Document and Control Desk Re: Docket No. 50-220 DPR-63
Dear Sir:
Submitted herewith is the Report of Operating Statistics and Shutdown for May 1984 for the Nine Mile Point Nuclear Station Unit $1.
Also included is a narrative report of Operating Experience for May 1984.
Very truly yours, T.
empges Vice President Nuclear Generation TEL/jkr Attachments cc: Director, Office of I&E (10 copies) 9 i i