u OPERATING DATA REPORT DOCKET NO. 050-237 DATE April 1. 1985 e
j COMPLETED BY B.'A. Schroeder t.
i TELEPHONE (815) 942-2920 l
'0PERATING STATUS j-NOTES Q
,.1.
Unit Name:
Dresden II j
2..
Reporting Period:
March. 1985 3
Licensed Thermal Power (MWt):
2,527
~.'
4._~ Nameplate Rating (Gross MWe):
828 4
5.
Design Electrical Rating (Net MWe): 794 6.
Maximum Dependable Capacity (Gross MWe): 812 7
Maximum Dependable Capactty (Net MWe):
772
~
-8.
If Changes Occur in Capacity Ratings Ticems 3 Through 7) Since tast Report, Give i
Reasons:'
P' N/A Pi 1
Power Level to Which Restricted, if Any (Net MWe):
N/A
- 10. : Reasons For Restrictions, if Any: N/A This Month Yr-to-Date Curnulative.
- 11. Hours in Reporting Period 744 2160 130.464 12.: Number 'of Hours-Reactor Was Critical 0
0 99.71s.9 13 Reactor Ra' serve Shutdown-Hours 0
0 0
- 14. _ Hours Generator On-Line 0
0 97.309.8 _
15 Unit Reserve Shutdown Hours 0
0 o
~16.
Gross The'rmal Erjergy Generated (MWH) 0 0
191.338.058 L
L 17 Gross Electrical Energy G,.nerated (MWH) 0 0
61.221.341
- 18. Net Electrical Energy Generated.(MWH)
-2109
-8784 57.839.842
-19 Unit Service Factor 0.0 0.0 74.59 l'
20.: Unit Availability Factor 0.0 0.0 74.59 h;;
21.
Unit Capacity Factor (Using HDC Net) 0.0 0.0 57.43 Li 22.
Unit Capacity Factor (Using DER Net) 0.0 0.0 55.84 f(.
- 23 Unit Forced Outage Rate 0.0 0.0 11.22 i.
24.
Shutdowns. Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
{,
62-Day 1 25% after start-up for snubber inspection.
- lij,
~25.
_lf Shut' Down At End Of Report Period, Estimated Date of Startup: April 7, 1985
- i..;
N' 8504180230 850331 N
e PDR ADOCK 05000237:
/g /l
{'
?
PDR 1
I f _,
n)[
I
.=
=
=
k OPERATING DATA REPORT DOCKET NO.-
050-249 DATE April 1.
1985
[
COMPLETED BY B. A. Schroeder !
TELEPHONE (815) 942-2920 g
OPERATING STATUS
]
NOTES 1.
Unit Name:
Dresden III I
- 2. ' Reporting Period:
March. 1985
- 3.. Licensed Thermal Power (MWt):
2.527 4.~
Nameplate Rating (Gross HWe):
828 5.
Design E1'ctrical Rating (Net MWe): 794 e
6.
Maximum Dependable Capacity (Gross MWe): 812 7
Maximum Dependabie Capacity (Net MWe): 773 4
8.
If. Changes occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give 1 Reasons:
I N/A 9
Power Level to Which Restricted, if Any (Net MWe):
N/A l
- 10. - Reasons For Restrictions, if Any:
n/A This Month Yr-to-Date Cumulative.
II. Hours in Reporting Period 744 2.160 120,049 12.
Number of Hours Reactor Was Critical 744 2.059.2 91.937.2
- 13. Reactor Reserve. Shutdown Hours 0
0 0
.14.
Hours Generator On-Line 744 2.019.8 Rs.191.9 15.
Unit Reserve Shutdown Hours 0
0 0
16.
Gross Thermal Energy Generated (MWH) 1.711.446 4.704.809
'171.761.832
- 17 Gross Electrical Energy Generated (MWH) 542.128 1,508,320 55,715,297
~18.
Net Electrical Energy Generated. (MWH) 514.249 1.441.833 5?.778.063
'la.
Unit Service Factor inn.n 93.51 70.96 L
~,20.-
Unit Availability Factor 100.0 93.51 70.96 21.
Unit Capacity Factor (Using MDC Net)
R9.42 86.35 56.87 U
22.
Unit Capacity Factor (Using DER Net)
R7.05 84.07 55.37
- 23 Unit Forced Outage Rate 0.0 6.49 12.59
(
124.
Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
[i N/A i
25 If Shut Down At End Of Report Period,' Estimated Date of Startup:
N/A F
I
!~
a
-- -- Y -
n
' DOCKET NO. 050 237 i
UNITLNAME Dreaden II UNIT SHUTDOWNS AND POWER REDUCTIONS DATE Anril 1.
1985 COMPLETED ~ BY E. A.
Schroeder TELEPHONE (815) 942-2920 REPORT MONTH MARCH,'1985 METHOD OF
' LICENSEE
.CAUSE & CORRECTIVE NO.
-DATE TYPE 1 DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT
' ACTION TO (HOURS).
DOWN REACTOR 3
. REPORT f CODE 4 CODES PREVENT RECURRENCE 5
84-10-05 S
744
.C 1
Refueling outage.-
~,
t
'l 2
3 4
F: Forced Reason:
Method:
Exhibit G-Instructions for S: Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data.
B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee l
C-Refueling 3--Automatic ' Scram Event Report (
) File D-Regulatory Restriction 4-Other (Explain)
(NUREG-0161) j E-Operator' Training & License Examination.
F-Administrative-l' G-Operational Error H-Other (Explain) i e
f i
0,.
.m e
DOCKET NO. 050-237'
~
UNIT NAMEDrvden Ill UNIT SHUTDOWNS AND POWER REDUCTIONS-DATE April 1.
1985-COMPLETED BY B. - A. Schroeder TELEPHONE (815) 942-2920 REPORT MONTH MARCH,' 1985:
1 4
METHOD OF LICENSEI; CAUSE & CORRECTIVE-NO..
'DATE TYPEl DURATION REASON 2 SHUTTING-EVENT ~
SYSTEM COMPONENT ACTION TO (HOURS)
DOWN REACTOR 3
~ REPORT #
CODE 4 CODE 5 PREVENT RECURRENCE i
None 4
i l
I 1
i r
j j
'l 2
3 4
F: Forced Reason:
Method:
Exhibit G-Instructions for S: Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data B-Maintenance on Te=t 2-Manual Scram Entry Sheets for Licensee i
.C-Refueling 3 -Automatic Scram ~
Event Report (
)' File i
D-Regulatory Restriction 4-Other (Explain)
(NUREG-0161) i E-Operator Training & License Examination.
F-Administrative G-Operational Error I
H-Other (Explain) 4 i
i s.
.-.. -. - - - ~ _... -.. -.
4 AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 050-237
~
,~
UNIT II
~ DATE - April ~1, 1985 COMPLETED BY B. A. Schroeder TELEPHONE 815/942-2920 MONTH March,'19'85
-DAY-AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net) 1 0
17 0
2 0
18 0
3 0
19 0
-4 0
20 0
5.
0 21 0
6 0
22 0
7 0
23 0
8 0
24 0
r 9
0 25 0
- 10 0
26 0
' 11 0
27 0
12 0
28 0
13 0
29 0
14-0 30 0
15 0
31 0
e i
]
i
-}
i-
--.:..---,..-.....~-.-..
. - ~
^
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 050-249 UtilT III-DATE ' April 1; 1985 COMPLETED BY B. A. Schroeder TELEPHONE 815/942-2920 MONTH March, 1985 DAY.
. AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net)
I 768 17 662
- 2 762 18 662 3
727 19 670
' 4 754 20 699 5':
760 21 658 6'
'770 22 668 7
782 23 666 8
776 24 669 9
755 25 668 10 724 26 658 11 734 27 662 12 74 1 28 659 13 656 29 675 14' 676 30 650 15-659 31 656 16 659
._.,s
,_fy,me---
e+^et"*t-9--4'et--'P*"**'
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - MARCH, 1985 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Shutdown Preventive W.R. #40043 N/A N/A Indication removed with a half-round Cooling Line bastard file under LMT's direction.
1001A, EPN W21d #14-5 24/48V 2B Top Corrective W.R. #38428 N/A N/A Repaired knob.
B ttery Char-gir Timer Knob Drywall Pres-Preventive W.R. #38625 N/A N/A Replaced bolt and spacer, cure Switch, EPN #2-1501-62C 2B-RPS-MG Set Preventive W.R. #36426 N/A N/A Tested breaker three times and lubri-cated with LPS #1.
SBLC 2A Squib Preventive W.R. #38916 N/A N/A Reinstalled cable in cord grip and Velva secured conduct.
U2 Torus to Preventive W.R. #32444 N/A N/A Installed new swedge block fitting.
Hotwell A02-1599-62
- 2 Dierel Preventive W.R. #36606 N/A N/A Performed quarterly inspection July, Gener tor 1984.
MO 2-2301-15 Preventive W.R. #31078 N/A N/A Replaced broken bulb.
M0 1001-4A Preventive W.R. #31080 N/A N/A Replaced indicating light bulbs.
Pirnt Local St tion RPIS Drift Preventive W.R. #36065 N/A N/A Replaced relay.
Ralty
DRFSDEN UNIT 2 SAFETY RELATED MAINTENANCE - MARCH, 1985 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT' MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Cere Spray Preventive W.R. #35476 N/A N/A
' Replaced and calibrated meter.
H;adar dP Indicetor 1467B HFA Relcy Preventive W.R. #40318 N/A N/A Rebuilt relay.
U2 Rx Bldg.
Preventive W.R. #40672 N/A N/A Inspected circuitry ac.d verified proper Intcrlock Door operation of doors.
Turbine Side CUB 2430 Bus Preventive W.R. #40917 N/A.
N/A Replaced trip coil and cleaned auxiliary 24-1 Main Feed contacts.
Brecker U2 Tip Shear Preventive W.R. #39095 N/A N/A Discharged existing shear valves and Velves installed new shear valves.
DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - MARCH, 1985 NATURE OF LER OR OUTAGE HALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION MO 3-2301-4 Preventive W.R. #29175 N/A N/A Removed and replaced valve operator.
Operctor D#3 Grepple Preventive W.R. 29679 N/A N/A Replaced the air hose on the hoist monorail for the D#3 grapple.
CRD 22-31 Preventive W.R. #36531 N/A N/A Rebuilt solenoids.
(F-8)
CRD i4-51 Preventive W.R. #36532 N/A N/A Rebuilt solenoids.
(D-13)
CRD 22-11 Preventive W.R. #36533 N/A N/A Rebuilt solenoids.
(F-3)
CRD Arco Preventive W.R. #37040 N/A N/A Tightened all fittings.
Solenoids CRD Arco Preventive W.R. #37042 N/A N/A Tightened fittings and rebuilt solenoids.
Solenoids CRD ASGS Preventive W.R. #37043 N/A N/A Tightened fittings and rebuilt solenoids.
Solenoids CRD A:co Preventive W.R. #37045 N/A N/A Tightened fittings and rebuilt solenoids.
Sslenoids CRD Arco Preventive W.R. #37046 N/A N/A Tightened all fittings.
Solenoids CRD Arco Preventive W.R. #37047 N/A N/A Tightened all fittings.
Sol noids CRD A:co Preventive W.R. #37053 N/A N/A Tightened fittings and rebuilt solenoids.
Sol:noids
J, 1DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - MARCH,'1985-
. NATURE OF LER OR OUTAGE MALFUNCTION u
EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION CRD Arco Preventive W.R. #37055 N/A N/A Tightened fittings and rebuilt Solenoids solenoids.
~
CRD Acco Preventive W.R. #37056 N/A N/A Tightened. fittings and rebuilt-Sol:noids solenoids.
1601-20B A0V Preventive W.R. #37778 N/A N/A Replaced solenoid.
~
SRM #22 Preventive W.R. #38736 N/A N/A Cleaned power supply board edge connector.
ADV Vent Valve Preventive W.R.-#38902 N/A N/A Adjusted limit switch.
302-161B CRD J7 34-27 Preventive W.R. #39561 N/A N/A Removed J-7-112 valve and reinstalled new valve bonnet with gasket.
-U3 CRD # 112 Preventive W.R. #39569 N/A N/A Pulled'#112 valves, inspected and Valvas reinstalled with new gasket.
Torua Purge Preventive W.R. #39585 N/A N/A Replaced versa. solenoid. valve.
Valva 1601-56 "A" SBLC Squib Preventive W.R. #40674 N/A N/A Replaced bulb in alarm unit and cleaned
. Valva Circuit alarm with proper indications.
- Ammetsrs, EPN # 1140-3A APRM Ch. 12 Preventive W.R. #40717 N/A N/A Replaced relay K23 and tested.
Accum. #H-13 Preventive W.R. #40756 N/A N/A Replaced accumulator.
Accum. Pres-Preventive W.R. #40791' N/A N/A Replaced pressure switch and calibrated.
cura Switch, EPN #PS-3-305-130
m, DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - MARCH, 1985 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION HPCI Oil Preventive W.R. #40926 N/A N/A Removed filter element, disassembled Fil".cr and reinstalled.
Drywell and Preventive W.R. #40041 N/A N/A Replaced Q2 regulator from U2.
Repaired Torus Cam H2 Pump and calibrated H2 sensor detector.
S;n or:
LPRM 32-09-A Preventive W.R. #40476 N/A N/A Replaced and calibrated ion power supply Ch. 6 (100 VDC).
i emi = = = =
.u, DRESDEN UNIT'2'/3' SAFETY RELATED MAINTENANCE - MARCH. 1985 NATURE OF LER OR OUTAGE MALFUNCTION
' EQUIPMENT
._ MAINTENANCE NUMBER CAUSE RESULT
~ CORRECTIVE ACTION 2/3 Diesel Preventive W.R. # 15919 N/A N/A.
' Replaced door latch.
Genarctor Interlock Door Rx.-Bldg.
Preventive W.R. #36126 N/A
'N/A
-Adjusted auxiliary hook so' limit switch' Cran 2 stops crane just above 517'.
Station Preventive W.R. #36300 N/A N/A Performed preventive maintenance on~
- Batteries station batteries.
2/3 Diesel Preventive W.R. #37348 N/A N/A Performed semi-annual inspection.
Generator 2/3 Diesel Preventive W.R. #37435 N/A N/A Replaced and calibrated HFA relay.
Genarctor 2/3 Rx Crane Preventive W.R. #40109 N/A N/A Key broken in restricted mode switch -
removed and set switch to normal.
FCV.7510A Preventive W.R. #40677 N/A N/A' Replaced valve positioner and stroked SBGT System valve.
2/3.."A" SBGT Preventive W.R. #40896 N/A N/A Replaced versa solenoid valve.
Flow Control Valve Solenoid 2/3 Diesel Preventive W.R. #42476 N/A N/A Installed new pressure regulator.
Generetor
- NL1 1/2 Preventive W.R. #42527 N/A N/A
. Grounded off both tads.
Primary Yoke 24/48 V Preventive W.R. #29546 N/A N/A
. Verified battery charger wiring per Battery
. print. Made necessary changes to agree Charger with wiring diagram.
1 -
i.
l
DRESDEN UNIT 2/3 SAFETY RELATED MAINTENANCE - MARCH, 1985 NATURE OF LER OR OUTAGE E M CTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION 3rd Floor Rx Preventive W.R. #37447 N/A N/A Checked the operation of interlock Bldg. to Tur-doors. Verified ok.
~bine Bldg.
Interlock Door (5) Limitorque Preventive W.R. #38211 N/A N/A Verified tightness and staking of set (Spare) screws for spring pack.
ARM Ind. Trip Preventive W.R. #38950 N/A N/A Repaired and tested spare indicator / trip Unit, EPN #
unit. Returned to Stores.
1705-8A/B Sensor /
Preventive W.R. #39178 N/A N/A Repaired and tested spare sensor / convertor.
Convertor for Returned to Stores.
ARM's Circuit Board Preventive W.R. #39505 N/A N/
Calibrated and adjusted circuit board.
Returned to Stores.
Gl Sensor /
Preventive W.R. #40855 N/A N/A Repaired and tested spare sensor / convertor.
Convertor Returned to Stores.
Gl ARM Sensor /
Preventive W.R. #40856 N/A N/A Repaired and tested spare sensor / convertor.
Convertor Returned to Stores.
SBGT "A" Train, Preventive W.R. #40965 N/A N/A Repaired and calibrated feedback signal..
EPH #2/3 7510A, Adjusted balance signal.
FIC 7541-28A 9
r.
h
SUMMARY
OF OPERATING EXPERIENCE
~
UNIT TWO h
MARCH, 1985 J03-01 to 03-31~
_ Refueling outage activities continued throughout the-entireLperiod. The; unit is presently scheduledEto start-up in early April,.1985. Major: work includes:
- Local Leak Rate Tests
. Integrated' Leak Rate Test
- Snubber Pipe: Replacement
- Clean-up Pipe Replacement s
L i.
L._.
43-
-=
[
c:: -
~
SIH1 MARY.OF OPERATING EXPERIENCE UNIT THREE
' MARCH,'1985 f03-Ol to 03-31'
- Unit 3 entered the month operating at a power level of i
768 MWe and. operated continuous 1y'throughout the entire month (with normal power reductions on weekends for surveillances), reaching a power level of ~ 832 MWe -with a capacity factor of 87.58% and an availability of J'-
100%.
E 4
i e
I r
S I
J 1
E
TT 1
UNIQUE REPORTING ~ REQUIREMENTS-s
' MAIN STEAM' RELIEF VALVE OPERATIONS Relief' valve operations during the reporting period are_ summarized in the following table. 'The table ' includes information as to which relief valve-was actuated, how~it was actuated, and the circumstances resulting in its 1
-actuation.
' Valves Description Unit ~
-Reporting Period Actuated Actuations-Conditions of Events 2:
~03-01-85 to.03-31-85 None
- 3!
103-01-85'to 03-31-85 None 5
r I
k
Commonwealth Edison Dresden Nuclear Power Station R.R. 01 Morris, Illinois 60450 Telephone 815/942-2920 April 1, 1985 DJS LTR: 85-356 Director, Office of Inspection and Enforcement United States Nuclear Regulatory Commission Washington, DC 20555 Attention: Document Control Desk
Dear Sir:
Enclosed, please find Dresden Station's operating data for last month. This information is supplied to your office per the instruc-tions set forth in Regulatory Guide 1.16.
Sincerely, D. J. Scott Station Manager Dresden Nuclear Power Station DJS:DCM:hjb cc: Region III, Regulatory Operations, U.S. NRC Chief, Division Nuclear Safety, State of IL U.S. NRC, Document Manageaent Branch Nuclear Licensing Administrator Nuclear Fuel Services Manager Nuc. Sta. Div. Vice Pres.