ML20087F305

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re Failure of Linear Converters on multi-blade Dampers Supplied by Pacific Air Products,Co Utilized in safety-related HVAC Sys.Initially Reported on 840216.Final Rept by 840710.Also Reported Per Part 21
ML20087F305
Person / Time
Site: Perry  FirstEnergy icon.png
Issue date: 03/09/1984
From: Edelman M
CLEVELAND ELECTRIC ILLUMINATING CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
REF-PT21-84 RDC-94(84), NUDOCS 8403190051
Download: ML20087F305 (2)


Text

l 0

p

)

n tt u e

r p7ng ij ig;

-vi : s n

- LL V L L ;*, ~ U

! f. b i L i b

  • LLtg'dift,<i i W

's n b3 n i r' li li i tr< i

$3

<s

'i vr r

!s 9 b

V i i1 E P.o. BOX 5000 - CLEVELAND. oHlo 44101 - TELEPHONE (216) 622-9800 - lLLUMINATING BLOG - 55 PUBLICSoOARE Serving The Best Location in the Nation MURRAY R. EDELMAN VICE PRESIDENT NUCLEAR Mr. James G. Keppler Regional Administrator, Region III Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 RE:

Perry Nuclear Power Plant II Docket Nos. 50-440; 50-441 Linear Converters for Pacific Air Products Co. Linear Converters [RDC 94(84)]

Dear Mr. Keppler:

This letter serves as our interim report pursuant to 10CFR50.55(e) concerning a potential problem with premature failure of linear converters on multi-blade dampers utilized in safety-related heating, ventilation, and air conditioning (HVAC) systems.

Mr. P. Pelke of your of fice was first notified on February 16, 1984, by Mr. B. Walrath of The Cleveland Electric Illuminating Conpany that this natter was being evaluated for applicability to the Perry Nuclear Power Plant.

This report contains a description of the potential deficiency, method planned to complete our evaluation, and the planned date for our final report.

Description of Deficiency The Pacific Air Products Co. (PAPCO) notified the Owner, CEI, that they have filed a 10CFR21 notification with the NRC relative to a problem identified with a linear converter unit which has shown signs of excessive wear in service.

This problem was identified at a non-nuclear generating plant.

The Pacific Air Products Co. furnished identical items for the Perry Plant through our HVAC supplier, the Robert Irsay Company.

The linear converter is a mechanical device that converts the linear (push-pull) motion of an electro-hydraulic actuator into rotary motion for operating HVAC dampers. The function of the damper is to control the volume of air in a ductwork system.

l Atotaloffifty-two(52)oftheseconvertershavebeensuppliedandinkalled at the Perry Nuclear Power Plant.

I j.6 0 8403190051 840309 P,DR ADOCK 050C0440 fAAR 141984

' 0 o

PDR

Mr. James G. Keppler March 9, 1984 Method Planned to Evaluate and Complete Upon initial notification of the above deficiency, the Owner instructed the installing contractor to issue two nonconformance reports (PO49-2711, PO49-2712) in order to track resolution of this problem.

PAPCO is presently conducting an investigation into this matter and a report on their investigation is scheduled to be issued by April 30, 1984. The investigation will include an analysis of the wear and a determination of its cause. Preliminary analysis by PAPCO indicates excessive wear of the brass shaft guides on the input and output shafts.

It has also been determined through tests that a significant increase in the units life expectancy can be achieved with the addition of lubrication to the shaf t.

In the interim, PAPC0 has furnished the Project with an inspection procedure to determine if units are suspect. They have also recommended that the units be lubricated with medium oil or grease as a temporary protective measure. Once PAPC0 has completed their investigation and testing program, more information will be available to establish a basis for our evaluation.

We anticipate filing our final report on *.his subject by July 10, 1984.

Please contact us if you have any questions.

Sincerely, Murray. Edelman Vice President Nuclear Group MRE:pab cc:

Mr. M. L. Gildner NRC Site Office Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 5

U.S. Nuclear Regulatory Commission c/o Document Management Branch Washington, D.C.

20555 Records Center, SEE-IN Institute of Nuclear Power Operations 1100 circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 I

I t-

_a