4 Table 4.7-2 (continued)
SNUBBER VISUAL INSPECTION INTERVAL Hote 4:
If the number of unacceptable snubbers is equal to or less than the Column B but greater than the number in Column A, the next inspection sh611 be the same as the previous inter.i.l Note 5:
11 the number of unacceptable snubbers is equal to or greater than the number in Column C, the next inspection interval shall be two-thirds of the previous interval.
However, if the number of unaccep-table snubbers is less than the number in Column C but greater then the number in Column B, the next interval shall be reduced propor-tionally by interpolation, that is, the previous interval shall be reduced by a factor that is one third of the ratio of the difference between the number of unacceptable snubbers found during the previous interval and the nu60er in Column B to the difference in the numbers in Columns B and C.
Note 6:
The provisions of Specification 4.0.2 are applicable for all inspection intervals up to and including 48 months.
McGUIRE - UNITS 1 and 2 3/4 7-18b Amendment No.126 (Unit 1) 9112O202Ec 911125 Amendment No.108 (Unit 2)