Final Deficiency Rept Re Separation Criteria for Power Generation Control Complex Equipment.Initially Reported on 830120.Verification of Electrical Separation Requirements in Test Instructions Now Required
ML20082B965
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 10/28/1983
From: Dise D
NIAGARA MOHAWK POWER CORP.
To: Starostecki R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
10CFR-050.55E, 10CFR-50.55E, 7611, NUDOCS 8311210385
Download: ML20082B965 (2)


Text

t

~

NUMOHAWK Y NIAGARA NIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST, SYRACUSE. N.Y.13202/ TELEPHONE (315) 474-1511

)

October 28, 1983 (7611) l Mr. R. W. Starostecki, Director U.S. Nuclear Regulatory Commission Region I Division of Project and Resident Programs 631 Park Avenue Kit.; of Prussia, PA 19406 Re: Nine Mile Point Unit 2 Docket No. 50-410

Dear Mr. Starostecki:

Enclosed is a final report in accordance with 10CFR50.55(e) for the problem concerning separation criteria for Power Generation Control Complex (PGCC) equipment. This condition was reported via telephone to Mr. J.-Wiggins of your staff on. auary 20, 1983 and was followed by interim ~ reports dated February 23, 1983 and August 9, 1983.

Very truly yours, D. P. Dise Vice President quality Assurance DPD/TL:ja

. Enclosure xc: Director of Inspection and Enforcement' U.S. Nuclear Regulatory Commission Washington, DC 20555 Mr. R. Gramm, Resident Inspector 0-l,

8311210385 831028

/v PDR ADOCK 05000

/

'g g s

e.6*

Final Report for a Problem L

Concerning Separation Criteria for the Power Generation Control

}

Complex _ (PGCC) Equipment i-t-

Description of the Deficiency i

A review by-Niagara Mohawk Quality Assurance identified that required notes concerning separation criteria, which appear on the system elementary diagrams, were-not included on.the. corresponding-connection diagrams or implemented in the connection diagrams wiring.

Therefore, these requirements.

werejnot incorporated into the PGCC hardware.

The electrical separation t

criteria notes concern the wiring of'certain power monitor and test relays.-

r

~

Analysis of Safety Implications i

l This deficiency resulted from a General Electric Quality Control and Engineering failure-to identiff all separation _ criteria deficiencies prior.to shipment to the Nine Mile Point Unit 2 site.

There.is a possibility that if this problem.were to have remained' uncorrected, it could have adversely affected the. safe-' operation of the plant.. 'A detailed analysis _of Safety Implications was not performed.

Corrective Action General-Electric has added separation. notes'to several connection diagrams asL a result of this deficiency. Subsequent to this action, Niagara Mohawk j

Quality Assurance performed a review of all' safety related connection-diagrams requiring electrical separation and found the required separation notes.

i General Electric has corrected all the monitoring and tes't relay; wiring located at the General Electric' shop except for one relay.

The remaining

  • relay will-be corrected at the Nine Mile l Point Unit 2 site by_ June 30, 1984;.

i As.a result of Niagara Mohawk's Quality. Assurance informing ' General Electric :

of' the electrical separation deficiencies in the as-shipped (PGCC modules, a.

paneliby panel : inspection lwas' performed at'the'~ site of all safety 'relatedi

.L

. panels for which electrical-separation is required. ; General-Electric Field.

Deviation-Disposition Requests-(FDDR's)-and Field.DispositionLInstructions;

.(FDI's):will be written to correct the separation deficiencies'..cThis rework.

l.

will:be completed by_. June.30 1984..

l-In order to prevent -recurrence of this: condition,4the followinglactions have ;

been taken in' General Electric's. manufacturing shop:

l 1'

.1. :The verification ~ofielectrica!~ separation-requirements in: Test.

InstructionsL(TI's)lisjow re' uired ' asia -backup to theLnorma1Einspection :

q 4

of. panels toTassure thatill' separation requirements.are met.;

~

~

L

^

2. - Round -table discussions
(mini-training classes) have:oeen: held with.

I f Quality Control personnel)(inspectors tand!. testers) for the"purposefof __ -

i,I describing;the changessin~the Test-Instructions 5as-welllas reviewing the 4

separationiinformation-wh'idh appears 7a's; notes lon theLdrawings.

^