Ro:On 830822,while in Mode 1,fireproofing for Control Bldg Room CB-36-02 Declared Degraded When Section Removed from Structual Steel for Const Mod.Fire Watch Established.Fire Proofing Repaired & Detectors Declared Operable on 830831
ML20080M119
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 09/19/1983
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
NUDOCS 8310030475
Download: ML20080M119 (2)


Text

E SOUTH C' ROLINA ELECTRIC & GAS COMPANY A

POST OFFtCE 764 CO IA. SOUTH CAROLINA 29218

o. w. o m ou.;R. Q S f.E N VICE PRESIDENT September 19, 1983 nuCtE*. o,En.T.O~.

Mr. James P. O'Reilly Regional Administrator U.S.

Nuclear Regulatory Commission Region II, Suite 2900 101 Marietta Street, N.W.

Atlanta, Georgia 30303

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Special Report

Dear Mr. O'Reilly:

Please find attached a Special Report for Virgil C. Summer Nuclear Station.

This thirty day report is required by Technical Specification 6.9.2 as a result of entry into Action Statement (a) of Technical Specification 3.7.10, " Fire Rated Assemblies," on August 22, 1983.

Should there be any questions, please call us at your convenience.

Very truly yours,-

O. W.

Dixon, Jr.

LEK:OWD/dwf/fjc Attachment cc:

V. C.

Summer C.

L. Ligon (NSRC)

E.

H.

Crews, Jr.

G. J.

Braddick T.

C.

Nichols, Jr.,/O. W.

Dixon, Jr.

J.

C. Miller E.

C.

Roberts J.

L.

Skolds H. N.

Cy rus J.

B.

Knotts, Jr.

Group / General Managers I&E (Washington)

O.

S.

Bradham Document Management R.

B.

Clary Branch C.

A.

Price INPO Records Center A.

R.

Koon NPCF D. A. Lavigne File (Lic./Eng. )

J.

F. Heilman

.6FFICIAl, HOPY r310030475 830919

'd bh PDR ADOCK 05000395 S

PDR I

l

l~

Mr. James P. O'Reilly Special Report Page Two September 19, 1983 CAUSE OF OCCURRENCE AND ACTIONS TAKEN On August 22, 1983, at 1005 hours0.0116 days <br />0.279 hours <br />0.00166 weeks <br />3.824025e-4 months <br />, with the Plant in Mode 1, the fireproofing for Control Building Room CB-36-02 was declared DEGRADED when a section of fireproofing was removed from the structural steel for construction modification activities.

There were no adverse consequences as a result of this occurrence because the room fire detectors were OPERABLE, and an hourly fire watch was established.

The affected fireproofing was removed, the modification performed, and the fireproofing repaired.

Action Station (a) of Technical Specification 3.7.10 ret 11res the inoperable fire rated assembly and/or sealing device to be OPERABLE within 7 days or submit a Special Report to the Commission within the next 30 days.

PLANS AND SCHEDULE FOR RESTORING TO OPERABLE STATUS The degraded fireproofing was repaired and declared OPERABLE on August 31, 1983, at 1530 hours0.0177 days <br />0.425 hours <br />0.00253 weeks <br />5.82165e-4 months <br />.

The Licensee plans no further action in regards to this event.

~

O