ML20079S107
| ML20079S107 | |
| Person / Time | |
|---|---|
| Site: | Farley |
| Issue date: | 01/27/1984 |
| From: | ALABAMA POWER CO. |
| To: | |
| Shared Package | |
| ML20079S092 | List: |
| References | |
| NUDOCS 8402030203 | |
| Download: ML20079S107 (6) | |
Text
- - _ - __-_- - -____ _
l 1
l t
n Attachnent 1 Proposed Technical' Specification Change D.C. Distribution System 0402030203 840127 PDR ADOCK 05000348 PDR p
j ELECTRICAL POWER SYSTEMS D.C. DISTRIBUTION - OPERATING SURVEILLANCE REQUIREMENTS (Continued)
TABLE 4.8-2 BATTERY SURVEILLANCE REQUIREMENTS CATEGORY A (1)
CATEGORY B Parameter Limits for each Limits for each Allowable (3) designated pilo connected cell (2) value for each cell connected cell Electrolyte
> Minimum level
> Minimum level Above top of Level indication mark, indication mark, plates, and not and < 1/4" above and < 3 /4" above overflowing maximum level maxiiiium level indication mark indication mark Float Voltage
> 2.02 volts
> 2.02 volts
> 2.02 volts Gravity (a)
-> 1.195 (b)
-> 1.190 If a cell is Specific less than 1.190, then it shall not have de-creased more than.080 from the previous 92 day test.
Average of all Average of all connected cells connected cells
> 1.195
> 1.190 (a) Corrected for electrolyte temperature of 77'F.
(b) Or battery charging current is less than 2 amps when on float charge.
(1) For any Category A parameter (s) outside the limit (s) shown, the battery may be considered DPERABLE provided that within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> all Category B measurements are taken and found to be within their allowable values, and provided all paramater(s) are restored to within Category B limits within the next 6 days.
(2) For any Category B parameter (s) outside the limit (s) shown, the battery may be considered OPERABLE provided that they are within their allowable values and provided they are restored to within limits withia 7 days.
(3) Any Category B parameter not within its allowable value indicates an inoperable battery.
Ft.RLEY - UNIT 1 3/4 8-10 AMENDMENT NO.
l l
A
[9
'ELECTAICAL-POWER' SYSTEMS-D.C. DISTR $BUTION-OPERATING SURVEILL ANCE REQUIREMENTS (Continued)
TABLE 4.8-2 BATTERY SURVEILLANCE REQUIREENTS CATEGORY A (1)
LCATEGORY B ParameterI Limits for each -
Limits for each.
Allowable (3)
' designated pilot connected cell. (2) value for each
-cell '
connected cell
. Minimum level
.Above top of Electrolyte
> Minimum level
-Level.
indication mark, indication mark, plates, and not and < 1/4" above-and < 1/4" above overflowing maxi ~ mum level mui~ mum. level indication mark indication mark Float Voltage
> 2.02 volts
> 2.02 volts -
> 2.02 volts Specific
> 1.195 (b)
> 1.190 If a cell is
~
'~
Gravity (a)-
less than 1.190, then it shall not have de-creased more than.080 from the previous 92 day test.
' Average of all Average of all Lconnected cells connected cells
> 1.195
> 1.190 (a)' Corrected, for electrolyte temperature of 77"F.
(b) ~0r battery charging current is less than 2 amps when on float charge.
(1) -For any Category A parameter (s) outside the limit (s) shown, the battery may be considered OPERABLE provided that within'24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> all Category B measurements are taken and found to be within their allowable values, and provided all paramater(s) are restored to within Category B liinits within the next 6 days.
.(2) For any Category B parameter (s) outside the limit (s) shown, the battery may be considered GPERABLE provided that they are within
.their allowable values and provided they are restored to within limits within 7. days.
(3) LAny Category B. parameter not within its allowable value indicates an inoperable. battery.
FARLEY - UNIT 2
.'3/4 8-13 AMENDMENT NO.
~
t I.
Proposed Technical Specification Change D.C. Distribution System
?
l
(P ELECTRICAL POWER SYSTEMS AUXILIARY BUILDING D.C. DISTRIBUTION - SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.2.4 As a minimum, one 125 volt D.C. bus, battery bank and its associated full capacity charger shall be OPERABLE.
APPLICABILITY: MODES 5 and 6 ACTION:
a.
With the required D.C. bus and/or battery bank inoperable, immeuiately-suspend all operations involving CORE ALTERATIONS, positive reactivity changes or movement of irradiated fuel; initiate corrective action to restore the required battery bank and/or bus to OPERABLE status as soon as possib'e.
b.
With the required full capacity charg:r inoperable, demonstrate the OPERABILITY of its associated battery bank by performing Surveillance Requirement 4.8.2.3.2 within one hour, and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.
If any Category A limit in Table 4.8-2 is not met, declare the battery inoperable.
SURVEILLANCE REQUIREMENTS 4.8.2.4.1 The above required 125-volt D.C. bus shall be determined OPERABLE and energized at least once per 7 days by verifying correct breaker alignment and indicated voltage on the bus.
4.8.2.4.2 The above required 125-volt battery bank and charger shall be demonstrated OPERABLE per Surveillance Requirement 4.8.2.3.2.
FARLEY -' UNIT 2 3/4 8-14 AMi.NDMENT N0.
ELECTRICAL POWER SYSTEMS AUXILI ARY BUILDIt'G D.C. DISTRIBUTION - SHUTDOWN
. LIMITING CONDITION FOR OPERATION 3.8.2.4 As a minimum, one 125 volt D.C. bus, battery bank and its associated full capacity charger shall be OPERABLE.
APPLICABILITY: H0 DES 5 and 6 ACTION:
- a. ' With the required D.C. bus and/or battery bank inoperable, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes or movement of irradiated fuel; initiate corrective action to restore the required battery bank and/or bus to OPERABLE status as soon as possible.
b.. With the required full capacity charger inoperable, demonstrate the OPERABILITY of its associated battery bank by performing Surveillance Requirement 4.8.2.3.2 within one hour, and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereaf ter.
If any Category A limit in Table 4.8-2 is not met, declare the battery inoperable.
SURVEILLANCE REQUIREMENTS 4.8.2.4.1 The above required 125-volt D.C. bus shall be determined OPERABLE and energized at least once per 7 days by verifying correct breaker alignment and indicated voltage on the bus.
4.8.2.4.2-The above required 125-volt battery bank and charger shall be demonstrated OPERABLE per Surveillance Requirement 4.8.2.3.2.
FARLEY UNIT 1 3/4 8-11 AMENDMENT NO.
_ _ ____ _ _____ ____-__-_ -__ - ______