ML20079G223

From kanterella
Jump to navigation Jump to search
Structural Steel Analysis for Limerick Generating Station: Spray Pond Pump Structure,El 268 Ft,Access Hatch Area,Fire Area 122D
ML20079G223
Person / Time
Site: Limerick  Constellation icon.png
Issue date: 12/20/1983
From:
PROFESSIONAL LOSS CONTROL, INC.
To:
Shared Package
ML20079G166 List:
References
NUDOCS 8401190483
Download: ML20079G223 (3)


Text

.

f[

JYcftssional Loss Control, Inc.

STRilCTURAL STEEL ANALYSIS

~

for l

LIMERICK GENERATING STATION Spray Pond Pump Structure El. 268' Access Hatch Area Fir,e Area 1220 December 20, 1983 t

?

f'401190483 840113 PDR ADOCK 05000352 F

PDR P. O. Box 446

  • Oak Ridge, Tennessec 37830 e (615) 482-3541

th LIMERICK GENERATING STATION t

1.

AREA DESCRIPTION The area under consideration is the Access Hatch Area on the 268' elevation

'of the Spray Pond Pump Structure (Fire Area 1220). The bounding walls of the area are of reinforced concrete construction with an average thickness

~

.of 2.ft.

The total surface area for heat transfer is 2014 ft2 (see Attach-ment A for sketch and calculation of surface areas).

2.

COMBUSTIBLE LOADING

, All.ca511ng' in this area is routed in conduit, there are no cable trays.

There are no combustible liquids in this area.

r 3.

VENTILATION PARAMETERS There are three openings into this area. The open stairwell from the 251' elevation, an opening into the ESW and RHRSW Pump Area, and a door leading to the outside.

4.

CASES EXAMINED With no exposed combustible cabling and no combustible liquids in the area, there is no fuel in the area to support a fire.-

5.

RESULTS

-The structural. Steel in this area will ~ not fail-due to a fire as there are no fixed combustibles -in the area to support a fire.

1

m -

w a

L_ ; j F

.a, tk.

Spray Pond Pump Structure El. 268' Access Hatch Area Surface Area Calculation Walls North wall (32' x 15')

480 ft2 South wall (32' x 15')

480 ft2 East wall (17' x 15')

255 ft2 West wall (17' x 15')

255 ft2 1470 ft4 Ceiling (32' x 17')

544 ft2 Total Surface Area for Heat Transfer 2014 ft2

+

ATTACHMENT A