ML20079D627
| ML20079D627 | |
| Person / Time | |
|---|---|
| Site: | Summer |
| Issue date: | 07/11/1991 |
| From: | Office of Nuclear Reactor Regulation |
| To: | |
| Shared Package | |
| ML20079D628 | List: |
| References | |
| NUDOCS 9107190185 | |
| Download: ML20079D627 (3) | |
Text
ELECTRICAL POWER SYSTEMS Table 3.8-2 Motor Operated Valves Thermal Overloads Protection and/or Bypass Devices _
Valve #
Function Bypass Devices Y/N FCV0602A-RH RHR Pump A Miniflow Valve No FCV0602B-RH RHR Pump B Miniflow Valve No LCV01158-CS CHG Pump A Suction HDR RWST ISOL VLV Yes LCV0115C-CS Volume Control Tank Outlet ISOL Valve Yes LCV0115D-CS CHG Pump B Suction HDR RWST ISOL VLV Yes LCV0115E-CS Volume Control Tank Outlet ISOL Valve Yes XVB3106A-SW SW Booster Pump A Oischarge Valve Yes XVB31068-SW SW Booster Pump B Discharge Valve Yes XVB3110A-SW RBCU 1A & 2A 10 SYS Supply ISOL Valve Yes
-XVB3110B-SW RBCU IB & 2B IC SYS Supply ISOL Valve Yes XVB3126A-SW HVAC Chiller Condenser A SW Supply VLV No XVB3126B-SW HVAC Chiller Condenser B SW Supply VLV No XVB3128A-SW HVAC Chiller Cond C SW HDR A IN ISOL VLV No XVB3128C-SW HVAC Chiller Cond C SW HDR B IN ISOL VLV No XVB9503A-CC RHR HX A CC Inlet Valve No XVB95038-CC RHR HX B CC Inlet Valve No XVG1001A-EF MTR DR EF Pump A SW A SUCT XCONN VLV Yes XVG1001B-EF MTR DR EF Pump B SW A SUCT XCONN VLV Yes XVG1002-EF TURB DR EF Pump SW B SUCT XCONN VLV Yes XVG1008-EF TURB DR EF Pump SW A SUCT XCONN VLV Yes XVG1037A-EF EF Service Water HDR A XCONN ISOL VLV Yes XVG10378-EF EF Service Water HDR B XCONN ISOL VLV Yes XVG2802A-MS MS Heeder B EF. Pump Turbine Supply VLV Yes XVG2802B-MS MS Header C EF Pump Turbine Supply VLV Yes XVG3001A-SP RB Spray PP A RWST Suction HDR VLV Yes XVG30018-SP RB Spray PP B RWST Suction HDR VLV Yes XVG3002A-SP NA0H HDR A Supply ISOL Valve Yes SUMMER - UNIT 1 3/4 8-19 Amendment No. 63,102 9107190185 910711 DR AEOCK 0500 5
. ~. _ -. _..
IELECTRICAL-POWER SYSTEMS-3
. Table 3.8-2 (Cont.)
Motor Operated Valves Thermal-Overloads Protection and/or Bvpass Devices -
- ^
-Valve #
Function BvDass Devices
.Y.df XVG7501-ACL AC Supply Header Containinent Isol. Val /e Yes XVG7502-AC AC Supply Header Containment Isol. Va N Yes
~XVG7503-AC-AC Return Header Containment Isol. Valve Yes XVG7504-ACJ LAC Return Header Containment-Isol. Valve Yes XVG8106-CS:
Charging Pump Miniflow Header ISOL Valve
.No XVG8107-CS
- Charging Pump Discharge Header ISOL Valve-Yes XVG8108_CS Charging. Pump Discharge Header _ISOL Valve Yes XVG8130A-CS
' Charging Pump A to C SUCT XCONN VLV No XVG81308-CS Charging Pump A'to C SUCT'XCONN VLV No
-XVG8131A-CS Charging-Pump-B to C SUCT XCONN VLV No XVG81318-CS
' Charging Pump.B-to C-SUCT XCONN VLV No
~XVG8132A-CS_ rCharging. Pump'A to C DISCH XCONN VLV-No
~
XVG8132B-CS_
Charging Pump A to C DISCH XCONN VLV No
.XVG8133A-CS Charging Pump _B to C DISCH XCONN VLV No XVG81338-CS
. Charging Pump-B to C DISCH XCONN VLV
.No XVG8701A-RH.
~ RH Header A iSOL. Valve (IRC)
No XVG87018-RH
No XVG8702A-RH-RH Inlet Header, A ISOLL Valve No-y
- XVG87028-RH RH" Inlet Header B ISOL Valve No XVG8706A-RH CHG/SI Pump SUCT HDR-RH HDR A Inlet VLV No XVG87068-RH CHG/SI Pump SUCT HDR RH HDR B Inlet VLV-No
-XVG8801A-SI.
HI.HeadInjectionValve-Yes
- XVG88018-SI HI:HeadInjection' Valve Yes y
XVG8808A-SI SI Accumulator A Discharge Header Valve Yes-
.XVG8808B-SI SI Accumulator B Discharge Header Valve Yes
.XVG8808C-SI SI1Accumu'lator_C Discharge Header Valve Yes XVG8809A-SI Refuel WTR STG TK RH Pump A SUCT VLV No XVG88098-SI Refuel WTR STG TK RH-Pump B SUCT VLV No SUMMER - UNIT 1-3/4 8-21 Amendment No. 37, 63. 102
CORRECTION TO AMENDMENT N0.102 TO FACILITY OPERATING LICENSE N0. NPF
VIRGIL C. SUMMER NUCLEAR STATION, UNII N0. 1 Docket-File NRC PDR Local PDR S. Varga (14E4)
G. Lainas E. Adensam P. Anderson G. Wunder OGC D. Hagan (MNBB 3302)
G. Hill (4) (P-130A).
Wanda Jones C. Grimes (11F23)
F. Rosa (7F4)
ACRS GPA/PA OC/LFMB L. Reyes, RII Summer File cc:
Summer Service List
_ _ _ _ _ _ _ _ -