ML20072C749
| ML20072C749 | |
| Person / Time | |
|---|---|
| Site: | Farley |
| Issue date: | 06/17/1983 |
| From: | ALABAMA POWER CO. |
| To: | |
| Shared Package | |
| ML20072C739 | List: |
| References | |
| NUDOCS 8306210201 | |
| Download: ML20072C749 (1) | |
Text
. _.
4 1
PLANT SYSTEMS 3/4.7.9 SNUBBERS LIMITING CONDITION FOR OPERATION 3.7.9 All snubbers listed in Tables 3.7-4a and 3.7-4b shall be OPERABLE.
APPLICABILITY: MODES 1, 2, 3 and 4.
(MODES 5 and 6 for snubbers located on systems required OPERA 8LE in those MODES).
l ACTION:
i
(
With one or more snubbers inoperable, within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> replace or restore the inoperable snubber (s) to OPERABLE status and perform an engineering evaluation per Specification 4.7.9.c on the supported component or declare the supported r
system inoperable and follow the appropriate ACTION statement for that system.
SURVEILLANCE REQUIREMENTS 4.7.9 Each snubber shall be demonstrated OPERABLE by performance of the following augmented inservice inspection program and the requirements of Specification 4.0.5.
l a.
Visual Inspections The first inservice visual inspection of snubbers shall be performed after four months but within 10 months of POWER OPERATION and shall include all snubbers listed in Tables 3.7-4a and 3.7-4b.
If less than two (2) snubbers are found inoperable during the first inservice visual inspection, the second inservice visual inspection shall be performed 12 months i 25% from the date of the first inspection.
Otherwise, subsequent visual inspections shall be performed in accordance with the following schedule:
Subsequent Visual l
No. Inoperable Snubbers per Inspection Period Inspection Periodj 0
18 months i 25%
1 12 months
- 25%
2 6 months
- 25% **
3,4 124 days
- 25%
5,6,7 62 days 2 25%
8 or more 31 days i 25%
The snubbers may be categorized into two groups: Those accessible and those inaccessible during reactor operation.
Each group may be inspected independently in accordance with the above schedule.
"The inspection interval shall not be lengthened more than'one step at a time.
8b8Ffidisextendedonaone-timebasisunti$plicah1fthrefuelingoutageforinac
'rovisions of Specification 4.0.2 are not a 1
the AMENDMENT NO.
F LEY-UNIT 1 8306210201 830617 PDR ADOCK 05000348 l
. P DR
_,