ML20070A821

From kanterella
Jump to navigation Jump to search
Advises That Provisions of IE Bulletin 81-03,Item 4.B Met, Following Extensive Insp & Cleaning of Various safety-related & nonsafety-related HXs
ML20070A821
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 10/29/1982
From: Clayton F
ALABAMA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-SSINS-6820 IEB-81-03, IEB-81-3, NUDOCS 8212090362
Download: ML20070A821 (4)


Text

'

Malfing Address Alabsma Power Company 600 North 18th Street Post Office Dox 2641 Dirmingham, Alabai,a 35291

  • g g,3 p F " 3 I Telephone 205 783-6081

.O7.G1c,.

F. L. Clayton, Jr.

$n"tidNEuUg"'

P3 0 4 ^I b"*" P * '

M) h!

tre souttum thctnc system October 29, 1982 Docket No. 50-348 Mr. J. P. O'Reilly U.S. Nuclear Regulatory Commission Region II, Suite 3100 101 Marietta Street N.W.

Atlanta, Georgia 30303 Joseph M. Farley Nuclear Plant - Unit 1 I.E.Bulletin 81-03 Item 4.B

Dear Mr. O'Reilly:

In letter dated May 26, 1981, Alabama Power Company committed to provide additional information regarding I.E.Bulletin 81-03 Item 4.b.

The following updated information is provided in regard to this subject.

On August 14, 1979, photographs of the 1A component cooling water (CCW) heat exchanger indicated no tube blockage by Corbicula (clams).

Information regarding this safety related heat exchanger is given in the attachment.

Subsequent to the May 26, 1981 response, all the charging pump room, bearing oil, and gear oil coolers on both units have been inspected.

These inspections revealed no blockage problems due to Corbicula or Corbicula shells (see attachment).

An extensive program of inspecting and cleaning various non-safety related heat exchangers was conducted on Unit 1 from September 1981 to March 1982.

No evidence of Corbicula or Corbicula shells was found during these inspections.

A summa ry of these non-safety related heat exchangers is given in the attachment.

By the above information and the letter of May 26, 1981, it is the judgement of Alabama Power Company that the provisions of I.E.

Bulletin 81-03 item 4.b have been met.

No future inspections of Unit 1 safety related heat exchangers, except during routine maintenance operations, are therefore planned.

8212090362 821029 PDR ADOCK 05000348 G

PDR SEst

Mr. J. P. O'Reilly.

U.S. Nuclear Regulatory Commission October 29, 1982 Page 2 If you have any questions, please advise.

Yours very truly, fCLu

(

F.L.Clayton,Jr<k FLCJr/RGW: Jc-D29 Attachment cc:

Mr. R. A. Thomas Mr. G. F. Trowbridge Mr. S. A. Varga Mr. E. A. Reeves Mr. W. H. Bradf ord

L h ATTACIDfENT Safety-Related Heat Exchangers Inspected 1.

Component Cooling Water Heat Exchanger, Unit 1 Location: Aux. Building EL100 Pipe Inlet I.D.: 20 inches Clams or clam shells found: None Number of blocked tubes observed: None iP ' 2.

Charging Pump Room, Bearing Oil, and Gear Oil Coolers-Units 1&2 Location: Aux. Building EL 116 (6 coolers)

Pipe Inlet I.D.: 25 inches Clams or clam sheels fstad: None Number of blocked tubes observed: None Non-Safety Related Heat Exchangers Inspected 1.

Main Turbine Generator Hydrogen Heat Exchanger-Unit 1 Location: Turbine Building EL 200 Pipe Inlet I.D.: 8 inches Clam or clam shells found: None Number of blocked tubes observed: None 2.

Main Condenser-Unit 1 Location: Turbine Building EL 145 (4 sections)

Pipe Inlet I.D.: 96 inches Clams or clam shells found: None Number of blocked tubes observed: None 4.

Hydrogen Seal Oil Coolers-Unit 1 Location: Turbine Building EL 137 (2 coolers)

Pipe Inlet I.D.: 4 inches Clam or clam shells found: None Number of blocked tubes observed: None 5.

Turbine Lube Oil coolers-Unit 1 Location: Turbine Building EL 155 (2 coolers)

Pipe Inlet I.D.: 10 inches Clams or clam shells found: None Number of blocked tubes observed: None 6.

Turbine Building HVAC Chillers-Unit 1 Location: Turbine Building EL 275 (2 chillers)

Pipe Inlet I.D.: 6 inches Clams or clae shells found: None Number of blocked tubes observed: None l

l 7.

Main Turbine Generator Exciter Coolers-Unit I Location: Turbine Building EL 195 (2 coolers) l Pipe Inlet I.D.: 2 inches i

Class or clam shells found: None Number of blocked tubes observed: None l

, ; um..

8.

Steam Generator Feed Pump 011 Coolers Location: Turbine Building EL 157 (2 coolers)

Pipe Inlet I.D.: 3 inches Clams or clam shells found: None Number of blocked tubes observed: None l

o k_