Power COnPORATeON November 3,1982
- 3F-1182-07 File: 3-0-26 Mr. John F. Stolz, Chief Operating Reactor Branch #te Division of Licensing US Nuclear Regulatory Commission Washington, DC 20555
Subject:
Crystal River Unit 3 Docket No. 50-302 Operating License No. DPR-72 NUREG-0737, Item II.B.3 Post Accident Sampling Capability
Dear Mr. Stolz:
In our letter to you dated December 30,1981, Florida Power Corporation submitted the specifications of the equipment to be used to fulfill the requirements of the subject item. More detailed specifications are now available for the Orion boron and chloride analyzers to further describe the equipment.
Specifically, the accuracy of the boron and chloride analyzers have been determined to be:
For boron from 100 to 6500 ppm For chloride from 0.1 to 100 ppm 5% accuracy with a 68% confidence the larger of 5% or 0.1 ppm accuracy with a 68% confidence 10% accuracy with a 95% confidence the larp,er of 10% or 0.2 ppm accuracy with a 95% confidence
~
goQb 8211090043 821103 f_PDR ADOCK 05000302
. P.
PDR i
General Office 32o1 Thirty-fourth Street South e P O. Box 14o42. St. Petersburg. Florida 33733 e 813-866-5151 l __
Mr. John F. Stolz
- 3F-ll82-07 Page 2 FPC is proceeding with the installation of the Post Accident Sampling System during Refuel IV which is consistent with our schedule submitted on September 8,1982.
Very truly yours, jr tLt &(-
il[i h
Dr. atsy Y. Baynard Assistant to Vice President Nuclear Operations ALL/myf cc:
Mr. J.P. O'Reilly Regional Administrator, Region 11 Office of Inspection & Enforcement U.S. Nuclear Regulatory Commission 101 Marietta St., N.W., Suite 3100 Atlanta, GA 30303 e