ML20043H890

From kanterella
Jump to navigation Jump to search
Safety Evaluation Supporting Amend 39 to License NPF-42
ML20043H890
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 05/30/1990
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20043H886 List:
References
NUDOCS 9006270029
Download: ML20043H890 (2)


Text

- - _,

[pa tse e

e,,

UNITED STATES I

^r E '"

NUCLEAR REGULATORY COMMISSION

/

W ASHINGTON, D. C. 20566 f

\\*...*

l 6

SAFETY EVALUATION BY,._THE OFFICE OF NUCLEAR REACTOR RE_GULATION l

RELATED TD AMENDMENT N0.39 TO FACILITY OPERATING LICENSE N0. NPF-42 j

WOLF CREEK NUCLEAR OPERATING CORPORATION

{

I WOLF CREEK GENERATING STATION DOCKET NO. 50-482 4

LNTRODUCTION l

4 Technical Specification 3/4.8.4 provides the requirements for Containment i

i Penetration conductor Overcurrent Protective Devices. On March 23, 1989, the i

NRC issued Amendment 28 which revised Technical Specification 3/4.8.4 and deleted Table 3.8-1, which listed the Containment Penetration Conductor I

Overcurrent Protective Devices. During a review of Amendment 28 by Wolf Creek j

Nuclear Operating Corporation personnel, it was discovered that there were l

still references to Table 3.8-1 in the Technical Specifications, t

By letter dated March 2,1990, the licensee proposed Technical Specification changes that would delete references to Table 3.8-1 in the Wolf Creek Generating Station (WCGS)TechnicalSpecifications. These remaining references are located in the Table of Contents and in Surveillance Requirement 4.8.4.1.

l EVALUATION Table 3.8 1 provided information on the location, size and equipment protected by the Containment Penetration Conductor Overcurrent Protective Devicec. The information which was in Table 3.8-1 is currently being administrative 1y l

controlled in plant procedures. The references to this table which remain I

were inadvertently overlooked when the table was originally requested to be removed from the Technical Specifications. Removing the references to the table l

is now being pursued in order to eliminate any confusion resulting from referring to a table which no longer exists. This is an administrative change which does i

not change any of the requirements of the WCGS Technical Specifications. This change does not include any technical changes and is considered to be editorial

+

in nature.

)

~l Based on the above discussions the staff is in agreement with the licensee's findings and, therefore, finds the proposed changes acceptable.

ENVIRONMENTAL CONSIDERATION The amendment relates to changes in recordkeeping, reporting, and administrative procedures or requirements. Accordingly, the amendment meets the eli ibility criteriaforcategoricalexclusionsetforthin10CFRSection51.22(g)(10).

c Pursuant to 10 CFR 51.22(b),in connection with tae issuance of %e amendment, no environmental im>act statement or environmental assessment need be prepared j,@f$bb

,u i

.- - - l

h l'

r g

CONCLUSION The staff has concluded, based on the considerations cl1scussed above, that:

(1) there is reasonable assurance that the health and safety of the will not be endangered by operation in the prowsed manner, and (2) public such activities will be conducted in compliance witi the Comission's regulations, and the issuance of the amendment will not be inimical to the-common defense.

and security or to the health and safety of the public.

Date: May 30, 1990 Principal Contributor:

D. Pickett m

m____.____.1-__.____.__

_