Responds to Unresolved Item Noted in Insp Repts 50-317/89-29 & 50-318/89-31.Corrective Actions:Instruction CCI-104, Surveillance Test Program Revised to Require Tighter Control Over Test Program & Associated Documentation
ML20005E336
Person / Time
Site: Calvert Cliffs  Constellation icon.png
Issue date: 12/27/1989
From: Creel G
BALTIMORE GAS & ELECTRIC CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9001050084
Download: ML20005E336 (2)


Text

'

BALTI M OR E GAS AND ELECTRIC CH ARLES CENTER. P. O. BOX 1476. BALTIMOR E, M ARYLAND 21203 GE[Ot{yEE' December 27,1989 y

p, NvCLt Am [ cmov (soo too ases U. S. Nuclear Regulatory Commission Washington, DC 20$55 ATTENTION:

Document Control Desk

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit Nos.1 & 2; Docket Nos. 50-317 & 50-318 Resnonse to Unresolved item 50-317/89-29-01: 50-318/89-31-01

REFERENCE:

(a) Letter from Mr. R.P. Bellamy (NRC) to Mr. G. C. Creel (BG&E),

dated November 29,

1989, NRC Inspection Report Nos.

50-317/89-29; 50-318/89-31 Gentlemen:

As requested in Reference (e), we are providing the following response to the subject Unresolved item which concerned missing documentation of calibration of the Waste Gas lloldup System Monitor (RI-2191) and the Liquid Discharge Monitor (RI-2201). In Reference (a), Mr. Bellamy asked us to review the item and respond with actions planned or taken in regard to this item and their results. We have been unable to locate the actual results of the calibration performed on May 27, 1988 using Surveillance Test Procedure STP-M-567-0.

Reference (a) states that the inspector verified that the calibration had been documented in the E&C Department Calibration Log and the Shift Supervisor's Log.

This provides evidence that the STP was successfully performed on May 27, 1988. The monitors were found to be within calibration when STP-M-567-0 was performed on November 18, 1989.

ACTION TAKEN We have concluded that this problem was caused by inadequate procedural control of STPs and inattention to detail on the part of the personnel completing the test. On August 29, 1989, Calvert Cliffs Instruction CCI-104 Surveillance Test Program was revised to require tighter control over STPs and their associated documentation. A Site Surveillance Test Program Manager (SSTPM) is responsible for administering the surveillance test program, lie has single point accountability for the program. A Functional Surveillance Test Coordinator (FSTC) is assigned to oversee the preparation, scheduling,

revision, review and postponement of STPs for each functional organization (e.g. operations, maintenance, etc.) at the plant. Each FSTC 1

-Qc6 9001050084 891227 n

_PDR ADOCK 05000317 O

PDC o

o -

F, Document Control Desk

., - December 27,1989 Page 2 '

l

-o' f

is also responsible for ensuring that he receives completed STPs and forwards them to the SSTPM to be filed. CCl-104. requires the SSTPM to maintain an active file of i

recently completed STPs. This level of control and accountability did not exist at the time the surveillance records were misplaced,' We believe-that the changes to

' CCI-104 are sufficient to preclude recurrence of this problem and propose no further.

corrective action, j

7 i

RESULH l

' A spot check of surveillances scheduled and completed since the procedure was revised found no instances of lost data, j

Should you have any further questions regarding this matter, we will be pleased to i

discuss them with you.

I Very truly yours, t

h

/

l O

GCC/DWM/db cc:

D. A. Brune, Esquire J. E.

Silberg, Esquire R. A.Capra, NRC S. A.McNeil,NRC W. T. Russell, NRC J. E. Beall, NRC T. Magette, DNR 5

,.