Responds to IE Bulletin 80-09, Hydramotor Actuator Deficiencies. Vendors Evaluating Which Actuators Will Require Mod or Replacement & Which Will Meet Spec Requirements Re Spring & Sizing Nomograph Problem
ML19318C807
Person / Time
Site: Midland
Issue date: 06/17/1980
From: Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
References
IEB-80-09, IEB-80-9, NUDOCS 8007020306
Download: ML19318C807 (2)


Text

.

(

I O

' Censumers l

Faner I

eP s n. Atadland 14nject General of f eces: 1945 West Parnell Road, Jackson, Mechegan 49201 e (517) 788 0640 June 17,1980 US Nuclear Regulatory Commission Director of Reactor Construction Inspection, OIE Washington, DC 20555 MIDLAND PROJECT IE BULLETIU 80-09 FILE: 0505.12 UFI: 99*02*05*10 SERIAL: 906's As requested, Consumers Power Company has determined that IE Bulletin 80-09 is applicable to Midland in the following manner:

1.

Three venders with a total of 28 ITT Ceneral Controls Models AH-90 and 2H-90 series hydramotor actuators which contain defective springs have been identified and are listed in the attached table.

2.

All three vendors have been contacted and are currently evaluating which actuators will require modification or replacement and which actuators will meet the specification requirements concerning the defective spring and sizing nomograph prob 12m % scribed in IE Bulletin 80-09 The results of the vendor evaluat$on, including the need for any changes required to meet specification requirementr, are expected to be complete by August 11, 1980.

h4ff&

hG I

JW /,1m Attachmem, CC: Mr James G Keppler, Regional Director Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 6013T JUN 195eD 8.00i020 3

Attcchm2nt 9

ACTUATORS CONTAINING DEFECTIVE ITT GENERAL CONTROLS-SPRINGS Actuator Service Vendor Tag OMO-6504 A, B Control room makeup air AWV filter unit intake shutoff-dampers Control room rakeup air 0FV-6520 A, B AWV filter unit intake modula-ting dampers

~

Control room recirculating 0FV-6505 A, B AWV air filter unit supply modulating damper OMO-6529 A, B Control room recirculating AWV air filter unit supply shut-off damper OMO-6507 A, B Control room recirculating AWV air filter unit bypass two position dampers OMD-6508 A, B Control room air-handling AWV unit supply shutoff dampers OMO-6509 A, B Control room air-handling AWV unit return shutoff dampers 1HO-6559 A, B Battery room exhaust shutoff ANV 2MO-6559 A, B dampers OMD-5445 A, B Fuel handling area emergency I

AWV exhaust shutoff dampers OMO-5444 A, B

s Copes-Vulcan OTV-5755 A, B Control room ' air-handling unit bypass Fisher IPV-1975 A, B Auxiliary building chiller 2PV-1975 A, 3 control valve a
  • AWV - American Warming and Ventilating a

9 9

e e

j