ML19305E095

From kanterella
Jump to navigation Jump to search
Nuclear Containment Testing for TVA Nuclear Power Plants, Presented at ANS 791111-16 Winter Meeting
ML19305E095
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 11/16/1979
From: Clark K, White T
TENNESSEE VALLEY AUTHORITY
To:
Shared Package
ML19305E087 List:
References
NUDOCS 8004220358
Download: ML19305E095 (46)


Text

_ _

. o 4

i 1

NUCLEAR CONTAINMENT TESTING FOR TVA NUCIZAR POWER FIANTS e

Kenneth H. Clark Mechanical Engineer Tennessee Valley Authority Chattanooga, Tennessee Timothy J. White Mechanical Engineer Tennessee Valley Authority Chattanooga, Tennessee Presented to the American Nuclear Society Winter Mseting November.11-16, 1979 A004220

A TABIE OF CORISETS as.

Introduction 1

Test Objectives 3

Test Criteria 5

Techniques of Analysis 7

i Data Acquisition and Reduction Systems 10 Instrumentation Techniques 13 I

System Software 17 Discussion of Test Results I

19 l

Conclusions 22 b

i i

t I

I l

i P,

i I

l l

l'.

INTRODUCTION A significant part of the surveillance requirements tor a nuclear power plant involves the assurance of isolation of raaioactive contaminants from the environment in the event of a radiological accident. The primary containment serves as the final barrier of isolation in an accident. General Design Criteria 54 and 56 of Title 10 Code of Federal Regulations, Part 50 (10 CFR 50),

spe n.fy design provirions for the reactor building primary containment.

Appendix J to 10 CFR 50 defines the basis for a surveillance program to ensure that the primary containment will perform as designed for the life of the plant.

The most significant test prescribed by Appendix J, the reactor building containment integrated leak rate test, involves simulating as close as is practical the predicted conditions within the primary containment after the most severe postulated accident. The leakage of air from the primary containment to the environment is measured to demonstrate that offsite exposure to postulated radioactive contaminants will not exceed 10 CFR 50 guidelines, as implemented by the plant technical specifications.

Since the publication of Appendix J to 10 CFR 50, it has been customary to conduct reactor building containment leak rate tests (CILRT's) for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. This practice originated from experience gained in the ORNI,-AEC containment proof program. The current national standard for the conduct of the CILRT, ANSI 45.4-1972, recommends tests be conducted for "...not less than twenty four hours of retained pressure..." This arbitrary test duration was set as a means to ensure the primary containment leakage.would be accurately measured, with the instrumentation typically in use when the standard was prepared.

Experience gained by the Tennessee Valley Authority in the conduct of CILRT's has demonstrated that the prirary containment leak rate may be accurately mea 0ured for tests conducted for considerably less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

The purpose of this presentation is to discuss the techniques, equipment, and method of analysis TVA proposes to use to conduct future CILRT's of shorter duration than current practice. Data collected from two CILRT's conducted for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> with the techniques and equipment described by this paper are discussed.

i i

\\

l e

3-TEST OBJECTIVES A.

General The reactor building primary containment is designed to prevent the release of radioactive contaminants to the environment either in nonnal operation of a nuclear power plant or as the consequence of an accident.

Plant site meteorolo61 cal conditions determine from the guidelines presented in 10 CFR 100 a maximum amount of radioactive contaminants that may be released to the environment.

Various plant design and reactor specific features detennine a predicted maximum pressure expected to exist within the primary containment under accident conditions and a maximum rate of release of radioactive contaminants to the environment. Appendix J requires that the plant operator periodically demonstrate the ability of the primary containment to limit the release of contaminants below the calculated maximum.

The CILRT measures the rate cf release, or the leak rate, of the primary containment atmosphere to the environment at a test pressure of either one-half or equal to the calculated peak pressure expected for the most severe accident. Lines that penetrate the primary containment are aligned with the configuration assumed automatically after an accident. Lines postulated to rupti re incide the primary containment are drained to the extent practical of fluid and vented to the containment atmosphere for

~

the duration of the test. Lines postulated to.1pture outside the primary containment are drained to the extent practical of fluid and vented to the environment.

l

-4 Before a nuclear power plant may return to operation, the CILRT must demonstrate that this measured rate of leakage is less than 75 percent of the design =vimm.

The 25-percent margin provides assurance that, with unforeseen degradation of performance, the maximum leakage will not be exceeded.

B.

Specific Objectives The specific objectives of the CILRT are:

1.

Accurately measure the actual rate of primary containment atmosphere leakage under conditions close to those predicted for the most severe postulated accident.

2.

Demonstrate that the primary containment leak rate has been accurately measured by the CILRT by a subsequent verification test.

3.

Demonstrate that the measured rate of leakage is less than 75 percent of the design maximum before the nuclear plant may return to power operation.

4.

IMmonstrate that no potential means for the release of primary cortainment atmosphere has arisen since the previous CILRT.

5.

Provide a statistical statement of the validity of the measured leak rate of the primary containment by calculating the confidence interval of the results.

e

?

P e

I

9 TEST CRITERIA A.

Primary Containment Atmosphere Stabilization During the pressurization of the primary containment, the containment atmosphere temperature will significantly increase. This heating, due to the work required to pressurize the air, can introduce instabilities of the containment atmosphere that may preclude the accurate measurement of leak rate. In a similar manner, the operation of large equipment within the containment can cause the apparent leak rate to change during the CILRT.

Appendix J requires that the primary containment atmosphere be allowed to stabilize at least 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after the end of pressurization. This arbitrary requirement can prove of insufficient duration particularly when applied to high-pressure, small-volume containments. From the experience gained in the conduct of six CILRT's, the following guidelines were prepared to supplement the Appendix J requirement:

1.

The average pri2 nary containment atmosphere temperature change should be less than 10F per hour before starting the CILRT.

2.

A time versus temperature plot for the stabilization period should be approximately linear by the start of the CILRT.

3 Heat-producing equipment located within the primary containment should only be operated to maintain the safety of the reactor.

i t

4.

Any air circulation equipment operated durin; the CILRT should be operated continuously since intermittent operation could disturb the.

containment air temperature distribution.

l l

5 Water. Levels within the reactor and any other vessel within the primary containment should be held as constant as is possible. Any a

required level changes should be made slowly.

B.

Accuracy of the Measured Leak Rate Since any measurement has some degree of uncertainty associat_ vith random and systematic errors, the reported measured leak rate of the primary containment atmosphere is only an approximation to the "true" value. A statement of the goodness or degree of confidence of the CILRT results is necessary to provide assurance that the primary containment functions as designed. Following general testing practice, TVA reports a 95-percent upper confidence level for the reported leak rate.

A CILRT is ' considered satisfactory if the measured leak rate is less than 75 percent of the design maxinaam. To ensure adequate confidence in this leak rate, TVA further requires that the 95-percent upper confidence level be less than 75 percent of the design maximum leak rate.

v

7 TECHNIQUES OF ANALYSIS i

A.

Containment Modelin6 l

The accurate measurement of primary containment leak rate pivots on the precise measurement of temperature, pressure, and vapor pressure. The primary containment is not constructed as a single homogenous pressure vessel but as a series of interconnected compartments. Althou6h all ccs::partments forming the primary containment are vented to each other for the CILRT, the flow of containment atmosphere may be restricted.

Pressure suppression containment designs incorporate special compartments that may have significantly different temperature and vapor pressure conditions from the rest of the primary containment. A boiling water reactor pressure suppression chamber is characterized by humidity approaching the saturation point. The ice condenser for a pressurized vnter reactor employs two large compartments far below the freezing point-of water. Since a substantial portion of the primary containment free air volume is contained within these pressurization suppression compartments for both reactor designs, significant errors may result in the calculation of the leak rate if the containment atmosphere conditions are not. correctly considezvi by the analys.is.

To compensate for the compartmental construction of the primary con +minnant, the leak rate is calculated from a model in which the containment is a multiple element system. Temperature, pressure, and vapor pressure are measured for each compartment. The mass of the air in each compartment is calculated from these measurements. The primary containment leak rate is calculated from the sum of the compartment air masses. Temperature, vapor l

l

8-pressure, and pressure measurements are individually assigned volumetric weighting or influence factors determined by the relative volume each sensor represents within the compartment.

p

~

A primary containment model is developed from information provided in t

i section 6.2 of the Final Safety Analysis Report. Any compartment that l

represents more than 10 percent of the containment free air volume is considered a compartment for the CILRT.

i B.

Method of Leak Rate Calculation Several techniques have been used previously to calculate the primary containment leak rate. ANS 45 2-1972 recognizes the absolute and the reference vessel methods. The proposed standard for containment testing, ANSI 56.8, reco6nizes the same techniques. We have found the absolute, or mass loss, method yields the most accurate measurement of the primary containment leak rate.

The primary containment leak rate is calculated by the application of the ideal gas law. During the CILRT, the mass of the air in the containment is calculated periodically. The leak rate is tomputed from the slope of the least squares fit line to these data. The uncertainty of the measured leak rate is estimated by calculating the dcviation of the individual mass points from the l~ sst squares fit line, with adjustments for the sample size.

C.

Instrumentation Selection Guide The accurate determination of leak rate by the absolute method requires the precise measurement of primary containment atmospheric temperature, vapor pressure, and total pressure. Since any measurement will include some error, the accuracy of.these measurements determine the accuracy of the measured primary containment leak' rate. Prior to the performance of.

the CILRT, the number of temperature, vapor pressure, and total pressure sensors required to accurately determine the leak rate m st be estimated, i

Based on the expected leak rate and the anticipated conditions encountered in the test, this instrumentation selection guide detemines the minimum instrumentation necessary to conduc+ the CILRT.

The basic criteria TVA uses for the selection of minimum CILRT instrumen-tation is that the primary containment ~ leak rate should be accurately measured within the first 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> of data collection with an assumed leak rate equal to 25 percent of the maximum allowed under technical specifica-tions. In addition, no temperature measurement may represent more than 10 percent of the containment free air volume. Appendix A presents an example of the estimation of sensors required for a typical boiling water reactor CILRT.

0 4

. IATA ACQUISITION AND REIAJCTION SYSTEMS The precise measurement of many test variables is required to accurately calculate the primary containment leak rate. CILRT test data salet, therefore, be acquired and analyzed rapidly. TVA has developed a leak rate measurement system that acquires and reduces test data automatically. The principal advantages afforded by this automatic system are highly accurate, reliable results and data collection speed. The purpose of this section is to describe the principal functions and features of the automatic data acquisition and reduction systems.

A.

Data Acquisition System The principal function of the data acquisition system is to periodically l

measure the test variables. A microprocessor controls the timing of periodic acquisition, the conversion from analog to digital values, and the transmission of data to the data reduction system. The microprocessor will periodically collect data at a set interval or, at the discretion of the test director, can be demanded to acquire data within the selected interval. A log of all collected data is printed for permanent records.

P Table 1 lists typical data collected for a boiling water reactor and a pressurized water containment. The data acquisition system is designed to allow for any combination of temperature, pressure, and vapor pressure measurements. Figure 1 depicts the components that fona the data acquisition i

system.

l The principal feature of the data acquisition system is the accurate, I

rapid measurement of test variables. In CILRT's previously conducted by

~

TVA without the automatic data acquisition system, data could not be l

l collected more frequently than once per hour. Even at this slow rate of i

l-

collection, mis' takes by test personnel in the measurement of test variables degraded the results. For a typical ice condenser pressurized water reactor, the data acquisition can collect up to 20 samples of the test variables per hour. The significant increase in the volume of collected data improves the confidence of test results.

B.

lata Reduction System The primary purpose of the data reduction system is to accurately perform the necessary calculations to compute the primary containment leak rate.

The central element of the data reduction system is a minicomputer system directly connected to the data acquisition rystem. All raw data collected by the data acquisition system is transmitted to the minicomputer and stored on flexible disks. These data are subsequently corrected accord 3.6 to each sensor's calibration data. The leak rate is automatically calculated and results are printed on a local printer. The system is designed to be tolerant of power failure. Figure 2 depicts the data reduction system.

Several features are included in the design of the data reduction system.

The most significent is that the reliability of field test results is significantly enhanced because no manual data entry or calculations'are required. The speed of data reduction is significantly increased. For a typical ice condenser, pressurized water reactor data can be collected by the acquisition system, stored, reduced, and the leak rate calculated in less than 2 minutes.

In addition to speed, the minicomputer offers several features to enhance test performance. Test variables or results may be automatically plotted by the minicomputer any time during the CIIRT. The test engineer may also choose to redefine the tima of the test start to any previously collected

c i

J2-P I

sample while the test is conducted. This " base reset" feature allows-the field evaluation of the effect of prolonging test duration.

?

I r

i i,

i F

i

- [

J e

1 i

b b

?

I a

i A

t i

I f

I t

h h

i i

d i

5 J

.r F

I i

4

'[

.l E

b e

i

(

n 4

i f

[

?

A g

f b

db :

E 1

4

' )

9

--wi-y-

g er

_.y y

-in

--Mr-y

  • ww a

r w --

y

INSTRUMENTATION TECHNIQUES A.

Temperature Measurement Four-wire resistance temperature detectors (RTD's) are used by the leak rate measurement system to monitor primary containment atmosphere temperature. Before and after the performance of each CILRT, each RTD is individually compared with a standard certified by the National Bureau of Standards over a temperature range of 0-150 F.

The uncertainty of the 0

te.Terature standard is better than 0.005 F.

A unique temperature as a 0

function of resistance calibration curve is calculated for each RTD from this comparison.

When installed in the primary containment, each RTD is connccte.d to a separate excitation bridge (wheatstone) by quick disconnect extension cables. Systematic errors due to lead length resistance, excitation bridge nonlinearity, and analog to digital conversion repeatable offset error are measured by substituting precision resistors in place of the RTD at the end of the extension cable. ~A unique resistance as a function of measured bridge output calibration curve is calculated for each measurement channel. The minicomputer automatically calcu.lates and stores each calibration curve. For each temperature measurement, measured bridge voltage is first converted to resistance. The minicomputer then uses the 4

individual RTD calibration curve to calculate.the equivalent temperature from this resistance.-

i f

Tests have been conducted to determine the accuracy of temperature.

. measurements by the integrated leak rate measurement system.~ Seven RTD's

. were ecsqmrod with a standard certified by the National Bureau of Standards at five temperatures. 'This standard is certified with a measuremsat

,, M

{.

w__,__

- n

~

i l

uncertainty of better than 0.005 F.

Figure 3 depicts the difference i',

between that temperature measured by the standard and the leak rate measurement system over the range of comparison. Analysis of the data i

indicates that the system uncertainty of temperature by the leak rate measurement system is better than 0.0202 F.

i B.

Vapor Pressure Measurement Lithium chloride dewcels are used by the leak rate measurement system to t

monitor primary containment atmosphere mointure content. The principle of operatirm of a deweel is that certain hygroscopic salt solutions will l

t change the amount of water in the solution in relation to the moisture

~

content of the air. The dewcel consists of a thin coating of lithium chloridc between two gold wires. As the moisture content of the air changes, the. salt solution will either absorb or liberate water. This I

change in moisture content of the salt. solution changes the solution resistance proportionally. Passing a constant voltage through the two wires and the solution causes resistance heating'. An RTD embedded in

[

the support bobbin measures the induced heating. 'Since the temperature I

of the solution is directly related to the solution resistance, and hence i

the moisture content of the salt solution and the. air, it is necessary i

only to measure this temperature to measure atmosphere moisture content.

Three-wire IEl,'s moniter the salt solution temperature. Before and after i

- each CIIRT, each dewcel RTD is indivi<inally cospared with' a standard f

I L

certified to the National Bureau of Standards over a temperature range i

i equivalent to a dewpoint from 0 F to 100 F.- A unique temperature as a f

i function of resistance calibration curve is calculated for each dowcel i

I RTD from this comparison..

i l

i s

i e

e

i i

. Each deweel is connected to a separate excitation bridge (wheatstone) and constant voltage power supply by quick disconnect extension cables.

t As in the discussion of the air temperature measurement, a calibration i

curve of resistance as a function of measured bridge output is calculated i

i I

by the substitution of precision resistors for the dewcel. Each dewpoint is first converted to e,quivalent resistance. The minicomputer then i

calculates the salt solution temperature from the dewcel's unique element temperature as a function of resistance curve. Equivalent dowpoint is i

calculated from data tabulated by the National Bureau of Standards.

d C.

Pressure Measurement Precision quartz bourdon tube manometers were selected for contaimeent total pressure measurement. Prior to the CILRT, a pressure cell is i

selected so that the rated pressure is just above the expected test pressure. Each manometer and cell is compared with a standard certified 1

by the hational Bureau of Standards before and after each CILRT over the

{

range of the pressure cell. Proper selection of the pressure cell ensures the highest possible sensitivity to small changes of the primary con + min = ant pressure. The pressure measured by the quartz manometer is converted l

internally to digital values by a special encoder. The rated cell pressure corresponds to c digital output of four hundred thousand counts, with a resolution of one count.

I i

To convert the digital signal acquired from the quartz mancaster to i

pressure, the minicomputer linearly interpolates the true pressure from the pressure cell calibration data. This technique yields a certified system accuracy of better than 0.015 percent of reading.

l I

D.

Calibration of Test Instruments All instruments included in the leak rate measurement system are compared with standards traceable to the National Bureau of Standards prior to and after each CILRT. Any instrument found to be out of tolerance in the range of measurement for the CILRT is rejected from consideration by eliminating all data collected from the sensor. Influence or volume weight factors are aujusted for the remaining sensors to compensate for 8

the failure.

2 i

i t

b 6

0-t t

.m.

. r w

. SYSTEM SOFIWARE 8

As a minicomputer performs all calculations required to determine the primary containment leak rate, the computer software system represents a complex element of the leak rate measurement system. This section describes the purpose and features of the software required to conduct the ClLRT. Three basic tasks are performed by the software programs of the leak rate measure-l ment system. First, before the CILRT, model definition, calibration data, and channel repeatable error correction data must be stored in the minicomputer.

Secondly, sof tware programs acquire the test data and perform the leak rate calculations during the CILRT. Finally, raw and corrected data must be summarized after the test for plant records.

A.

Prior to the CILRT Several programs are used to define the model of the primary containment I

before the CILRT is conducted. Based upon the number of temperature, vapor pressure, and pressure sensors, the minicomputer allocates storage space for the test data. In addition, the calibration data for each sensor must be stored prior to the test. Several programs are available to check various parts of the data entry process. The most significant is CIIECK, which allows the computer to instantaneously compare the temperature of an installed RTD with a precision temperature standard.

Table II lists and sumnarizes all software required in the preparation for the CILRT.

B.

During the CILRT As the ClLRT is conducted, the raw data must be stored, corrected according'to the calibration factors, and the results calculated. The

primary program, JVRE, receives data from the acquisition system, corrects according to the sensor calibration factors, c,wputes,. stores, and displays the primary containment leak rate. Several other programs (BASE, TALLY, and LIST) provide the ability to change the sasyle considered the start of the test, provide statistical confidence intervals, and 3

tabula'te the test results.

Several unique features are included to prevent the loss of data and enhance the information provided to the test engineer. The moat significant i

feature ensures that any time the data acquisition is prepared to tranmait I

1 data, the minicomputer stops all activities so that the main data collection

~

program, FORE, may execute. When these data have bea:1 received and results printed, the minicomputer completes the.mak interrupted by the acquisition l

of data. All programs are designed to be tolerant of power failure. No l

i previous data is lost when power is restored. Table III lists and summarises all software pro 6 rams required during the CILRT.

C.

After the CILRT i

After the CILRT is completed, test-data can be corrected for any instrument l

failure and arranged for inclusion in the pemanent test record. Several i

1 software programs provide the ability to list all raw and corrected hts, i

final test results, and calibration constants. Table IV lists and summarizes the software programs used after the CILRT is complete.

5 I

i l.

I t

,_.-.,,..y..

_. DISCUSSION OF TEST RESULTS Two CILRT's have been conducted with the equipment and techniques described in this paper. Each type represents an extreme of conditions typically expected during the CILRT--small volume with moderately high pressure and low pressure with moderate volume. Both tests were conducted for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, with data collected at least every 15 minutes. This section presents a suonary of the CILRT results. Complete reports have been filed with the NRC's Division of Operating Reactors.

A.

Browns Ferry Nuclear Plant Unit 2, Conducted June 1978 Browns Ferry unit 2 is a boiling water reactor employing a steel pressure suppression Mark I containment. The maximum leak rate at a reduced pressure of 25 psig is limited by technical specification 4.7.a.2 to less than 0.04437 percentage per hour of containment air mass. The containment was modeled as two compartments--the pressure suppression chamber and the drywell. Twenty-nine temperature sensors, six humidity sensors, and two pressure gauges were used to measure the primary containment leak rate.

The free air primary containment volume is approximately 300,000 cubic-feet..

A 24-hour CILRT and a 12-hour verification test were conducted June 13-16, 1978. The final measured leak rate was 0.00949 percentage of containment air mass per hour. The observed 95-percent upper confidence limit for this measured leak rate was O.00994 percentage of containment air mass.

The mass leak ra'te calculated-during this test is depicted in figure 4.

Table 5.ccmpares test dura. tion with leak rate and upper confidence limit.

Clearly, the primary containment leak rate was accurately detennined within the first 4_ hours of the test. Figure 4 indicates that data collected beyond the. fourth hour of the test served. only to improve the

r t,

upper confidence limit of the leak rate. Figure 5 depicts the upper b

confidence interval as a function of the time of data collection. The rapid approach to the asymptotic limit demonstrates the value of proper l

t instrument selection. Complete summaries of the calculated test results I

are included in appendix B.

t B.

Sequoyah Nuclear Plant Unit 1, Conducted March 1979 Sequoyah unit 1 is a pressurized water reactor employing an ice condenser pressure suppression primary containment. The masinann leakage of air at

\\

a test pressure of 12 psig is limited by technical specification 4.6.1.2 to less than 0.0078 percentage per hour of containment air mass. The pri=ary containment contains four compartments--the lower ice condenser compartment which houses the energy sbsorbing ice beds, the upper ice f

condenser compartment which encloses support equipment for t:.e ice condencer system, the lower compartment which encloses the reactor and cT.in piping systems, and the upper compartment which encloses the refueling i

vork area. The free air mass was calculated separately for each compartment, f

i with the calculated leak rate derived from the sum of the compartment air j

masses. Based upon the instrument selection guide, 46 RfD's were used for containment atmosphere temperature measurement, 10 humidity sensors were i

used to monitor the containment atmosphere moisture content, and four quart: mancmeters monitored the total pressure. Total free air volume for

)

the primary containment is approximately 1.19 million cubic feet.

1 A 24-hour CILRT and a 4-hour verification test were conducted March 13-16, 1979 The final measured leak rate was 0.00011 percentage of containment air mass. The observed 95-percent upper confidence limit was o.00024 percentage of the containment air mass. The mass leak rate calculated is l.

, depicted in figure 6.

Table 5 compares test results with the duration of data collection. Clearly, the primary containment leak rate was accurately determined within the l'irst 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> of data collection.

Figure 7 depicta the upper confidence interval as a ataction of the time of data collection. Complete summaries of the calculated test results are included in appendix C.

i i

e

[

I r

p CONCLUSIONS CILRT's conducted by TVA on a high-pressure boiling water reactor containment and a low-pressure ice condenser pressurized water reactor containment verify that the leak rate measurement system used with the techniques outlined in this paper measured the primary containment leak rate in far less than the 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> the tests were conducted. An analysis of the 95-percent upper confidence limit of the measured leak rate indicates that the primary containment leak rate was accurately detemined with a high level of confidence within the first 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> of data collection.

To consistently achieve this accuracy for future CILRT's, this paper has outlined several key techniques. The model used to calculate the primary containment leak rate must compensate for areas of varying temperature, pressure, and moisture content. The test instrumentation must be capable of extremely accurate and repeatable measurement of the containment atmosphere conditions.

Collected test data must be acquired quickly with reliable equipment. The i

test director must be provided with accurate results during the test.

TVA will conduct future CILRT's in accordance with the techniques described i

in this paper. Each CILRT will be conducted for at least 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> and extend until adequate confidence in the accuracy of the measured leak rate is achieved.

I I

l l

s s

O FIGURES t

i i

P h

g-.

)

~

ATMCSPH ERIC PRESS.

MSSE_ ME TAL TEMP.

3 RT;'S I

L i

v TVA l serial

[#

REMOTE 8

/ 'h ' *d ?

DIGITAL A'TOOJ.T2.

COMPUTER A COMMATJD y

,.gg

(

INPUT rJp T

(

irrif Iasc n itsTERFACE dO'O l

MpXR

_ _ _ _ _J a

A m, A -- p PREDATA PLOTT E4 THUM8 WHEEL AS3'Y 3

I5 5

8 8

MENSOR

.YENSOR ME'.S3P i "sotoo - 001 "iotoo - cc' "ic so _co;:

TVA J c1 A l

6 characters ecch OUTSIDE CONTAINMENT nsssssss s s / / - i s s s s s s s

////, / / / / / //

/////,,7 sin INS:DE CON TAiNMEN T TVA J. 6 8

\\

h' [

-ont roi / 616 SCANNER UP TO onc to, sc RTD'S VISIG II J. 8.

dato 100 CHANNELS eo 10 TEN-(

lg l

CHANNEL conte UNITS 616 SCANNER 7

onolog data (Nsignal )

2c J. B.

N f

soo channels

-)EWCELLS 2

H O

SYSTEM LAYOUT

~

TVA INTEGRATED LEAKAGE TEST SYSTEM DEWCELL POWER SUPPLIES

~

INTEGRATED LEAK RATE MEASUREMENT SYSTDI DATA RELUCTION SYSTEM i

I l

Dual Terminal Printer 11/D4 Minicomputer Flexible Disk Drives f

I f~r, I

l Data Acquisition System Digital Plotter k

i i

v, y

a----p p--

g ww--r--y v

-m-v r-,

w v-w--

<g,-

w,

,m w

y-w w -

e

-g-

g 9

TENNESSEE VALLEY AUTHORITY COMPARISON OF LAB AND FIELD TEMP. MEASUREMENTS

=-

SB 5

e W

is 4

n w(/)

na 00 ZZ ro I

8 u

W4 s

g,0)

- f f.

. j.

W s

8 ta. I 8

HF

-8 4

O 9

s mE Hv I

D s

J s

- O 1

es

=

m 4

.as M

~3

  • 1 I 1

s

~

STANDARD TEMP. DEG. F w -

w

,,---m--


<"ew

---,-.wp-

-,e-wm-

~ - -

-<--v

--e n_,

-en~

w--,,-

n.

f -

e O

TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT MASS LEAK RATE PLOT C25 PSIG TEST) 4..

3 2

E i

D 1

f.

==

...=- : =

=- :

=

======= = =--------

o e

LAJ E

Q

-2 M

4

-3 a

m

-4 H<

-s Lt.

m O

-e X

X 7

~S

,i, g"

2

'4 0

8 18 12 14 16 18 28 22 24

~

TIMECHRS.)

h

--m

--e---

w-t-,

---ri-e

-w n

-w,.

.w

---y

TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UCL INTERVAL (25 PSIG TEST PRESSURE) 34 M

Eg r

L,d,..

(/)

,4 (t) f it a.

y H<

b

)

"d E "ts _

g

.4 TIME CHRS) m

- - * + = - -

--wa-em

-w--, - -

-e w-e.wr--


s-e e-

-e--s

' + - -

TENNESSEE VALLEY AUTHORITY SEQUOYAH NUCLEAR PLANT MASS LEAK RATE ~ PLOT Cl2 PSIG TEST PRESSURE) 184 9.

88 e

8

-1 h

n e

M q

l=

=

m a

I aE*

e H<

=

11 o

o 24 9

x

~

g mi e

e a

in is i.

24

=

TIMECHRS.)

1 e

3,4 3-

-,w

=

-e-

.w w-- - - --

-m

---m e


r-

E o

a TENNESSEE VALLEY AUTHORITY SEQUOYAH NUCLEAR PLANT UCL INTERVAL (12 PSIG TEST PRESSURE)

=:

44 M

o x

SS

~

E y,

&)

4 e m ;

-I g

=

a= :

H 4

se (L.

O se e

N tsK 4

a

~

a 8

3 8

8 12 15 18 at 34 37 33 3

3g TIME CHRS)


..----m -m w-w


+--,-e---w

- + -

s-g-

wr-

-s-+:-e-

---w

6 TABLES

.L

- ~ -..

F

TABLE I DATA COLLECTED BY AUTOMATIC ACQUISITION SYSTEM i

i 1.

Boilin6 Water Reactor, Pressure Suppression Containment t

Quantity Function i

29 Resistance temperature detectors (RTD's) for ct.itainment f

atmospheric temperature measurement 6

Lithium chloride dewcels for containment atuospheric vapor pressure measurement 2

Precision quartz manometers for containment atmospheric total f

pressure measurement r

4 RTD's for containment vessel metal temperature and test station temperature t

1 Mass flowmeter for measurement of induced leak required for the verification test 1

Precision quartz manometer for atmospheric pressure l

1 Suppression chamber water level 1

Reactor vessel water level I

2.

Pressurized Water Reactor, Ice Condenser Suppression Containment f

Quantity Funetion I

t 46 RTD's for containment atmospheric temperature measurement t

i 10 Lithium chloride dewcels for containment atmospheric vapor pressure measurement 4

Precision quartz manometers for containment atmospheric total 1

pressure measurement 4

RTD's for containment vessel metal temperature and test station temperature measurement l

1 Mass flowmeter for measurement of induced leak required for the verification test 1

Precision quartz manometer for atmospheric pressure I

, TABLE II SYSTEM SOFTWARE REQUIRED PRIOR TO THE CILRT Program Name(s)

Description S1 Define the integrated leak rate system parameters: number of RTD's, dewcels, pressure gauges, analog inputs, and local RTD's.

Create the required system files required to store the test data.

CREAM Lefine the sensor calibration data and volume weights. Requires EllTAM ENTVW calibration reports on all dewcels and RTD's that may be used for the CILRT.

AM Measure the integrated leak rate system analog to digital repeatable offset. Requires all temporary cables to be installed and integrated leak rate system to be operational.

STARTN Define the calibration data for the quartz manometer pressure gauges and any plant process instrumentation, e.g., suppression chamber and reactor level transmitters.

CIECK Verify in-place system temperature or dewpoint measurements.

A standard for comparison is required for this program.

CIECK8 Print all stored calibration constants required to conduct the C1LRT.

r r

a TABLE III SYSTEM SOFTWARE REQUIRED DURING THE CILRT Program Name(s)

Description l

FORE Acquire containment data from the data acquisition system, store, correct raw data, and calculate leak rate.

t l

LIST Print a summary of measured leak rate. Drive an online

[

digital plotter to produce graphs of principal test results.

i TALLY Calculate confidence limits of the calculated leak rate.

I BASE Redefine the sample considered the start of the CILRT.

I l

a b

f f

r l

4 i

e l

I

TABLE IV

~

SYSTEM SOFTWARE REQUIRED APfER THE CILRT 1

Program Name(s)

Description AM Measure the integrated leak rate system analog to digital i

repeatable offset after test is completed.

DUMDEV Print all raw and corrected test data.

A1101 ASS Print a compartment summary of the measured temperature, vapor pressure, pressure, and air mass. Correct the test results for any sensor found out of calibration.

i L

i I

t

[

l L

- _, TABLE V CILRT RESULTS AS A FUNCTION OF TEST DURAT1oN Browns Ferry Nuclear Plant Unit 2 PTP Leak

  • Mass Leak UCL Nass CILRT Duration Humber of Rate Leak Rate Rete Leak Rate (Hours)

Mass Samples

% Per Hour

% Per Hour

% Per Hour

% Per Hour 8

33 0.00527 0.01693 0.00855 0.01036 12 49 0.00798 0.02318 0.00785 0.00893 24 97 0.00506 0.01921 0.00949 0.00994 Sequoyah Nuclear Plant Unit 1 PTP Leak

  • UCL PTP*

Mass Leak UCL NP.ss CILRT Duration Number of Hate Leak Rate Rate Leak Rate (flours)

Masn Samples

% Per H'our

% Per Hour

% Per Hour

% Per Hour 6

25 0.00456 0.00470 0.00193 0.00238 8

34 0.00323 0.00336 0.00159 0.00188 10 42 0.00254 0.00265 0.00190 0.00211 12 51 0.002 %

0.00307 0.00178 0.00193 24 100 0.00248 0.00258 0.00162 0.00168

  • As defined in ANS-274 (draft)

L.

INSTR? MENT SELECTION GUIDE The containment air mass is calculated by th.4 application of the ideal gas law:

g, 144 x V x (P - Pv)

(1)

RT By the mass point method the primary containment leak rate is the normalized slope of the mass loss curve:

W = At + B, LR=

x x 100 (2)

The total differential of the calculated is mass is:

V dP dPy dT (3) dW = 144 4

R T

T TI Therr' ore, LR =

NE dPy y[r (P - Pv).

x 100

'(4) dt dt dt T

The error in measurement of the independent variables, pressure, vapor pressure, and temperature determine the error in the Icak rate.

In general, an upper bound on the error in measurement of an independent variable X is:

(e ) + Ev)

E=

(5) v n*

An upper bound on the error in a dependent variable Y, as determined by the measurement of a set of independent variables X, X,

X is:

1 2

a - -

. + (Ex ) 2 ' 1/2

. N Ey1 (EX) + (EX) +.

(6) 1 2

Therefore, the upper bound of error of the measured leak rate can be expressed as:

ELR 1 (E )2 + (Epy)2 + (E )

(7)'

p T

L i

L.

The minimum change that may be reliably detected in the measurement of an independent variable is determined by the error of measurement.

In general, 2-1/2 dx <

  • ?)

+ I6 1 (8) 1 X

~.

UX i

Substituting for each independent variable differential in equat. ion (7) yields:

LR =

b

+

E_py, 4

E_7 x (P - Pv) x 100 (9) dt dt dt T

In the paper, " Describing The Uncertainties In Single Sample Experi-ments," by McClintock et. al., it was shown the contribution of the measurement of each independent variable should be equal for an optimal instrumentation system. Therefore, equation (9) may be rewritten:

I'R =

2+

- V) x 100 (10)

[

T If a bound on the error in leak rate is assumed, the error in the meanurement of an independent variable can be bounded.

l E=

(11) 100 2T + (P - Py)

TVA selects test instrumentation so that 25 percent of the maximum l

allowable leak rate can be measured within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

It is assumed that data is collected every 30 minutes. Therefore, equation (11) is rewritten:

E = (. 5 ) (. 25 x L., x. 7 5)

T (12) 100 2T + (P - Py),

Substituting into equation (8) and solving for the number of instruments yicids:

1ey)2+(gy)2'1/2 (13)

UX1 E2

~

Definition at Symbols e

Absolut e error of the ceasute of a variable 5

Absolute error of the indication of the measure of a variable E

Retnrive error of a varinble g

I.

Abnolute error of leak rate, percent of containment air mass per hour Niunber of replientions of a measurement N

Nur,her of independent measurements l'

Absolute pre.icure, i..

R Universnl gas constant S

D.:vintion from the mean of a population t

Time of nample t9 c, Student't; t dintribution for N-1 degrees T

Te:npera t ure, degrees Rankino DV T

W' V

Containment air volume, scf ci 6@

J J.

a b

t!

Absolute mass of containment air, Ibm Subscripts A

~

Estimate corrected for replication' and sample size 1.

Lower bound

'Ifpper bound-11 -

-Yoper previsus " -

  • l--

r e

l f

1

?

G f

APPENDIX B t

L P

e i

b 4

e 5s

f SHEET 110.

f I

~

Ill*E57L VALLE) Au!NORiii CONTAIMENT LEMCE MEASUREMENT 1EtT S R P Mil I!0URS A'/[9 ACE C0%ECTED TOTAL PASS SINCE 19PERAltFF PRESSWE P-i P OF AIR 101AL TIME 51ARI DEC f.

PSIA LEAKRATE LEAXRATE LEAX liATE RAS $

LBM 1 FER K

...............................0ilR.................................E HOUR 1 PER HOUR 2P

~

f.iff 83.1398 39.8807

.......e 57471.22 8.250 33.1489 39.8871 f.fNfHf f.e..tHe f.fifffff 8.5ff 83.1457 39.8794

-0.f851788

-0.8851788 l.8851528 57483.46 57475.82 f.758 83.1445 39.8893 f.0531127

-0.fl6827f

-f.f!60397 57466.83 f.8626fC' f.fifl863 f.fl44839 1.888 83.1462 39.8818 57448.21 f.f468322 f.8191448 f.f268793

!.258 83.1499 39.8858 l.5f8 83.1368 J9.8644 f.fl69681 f.fl871H f.8289792 57457.78 1.156 83.1361 39.9837

-0.1869811

-0.98!!339 f.fl51976 57473.14 57481.28 2.089 83.13f7 19.8792 f.8566827 f.flHill f.5834592 2.258 8',.1247 39.8818 f.f714629 f.fH1835 f.ff25374 57471.01 2.5ff 83.1487 39.8729

-0.84(1257

-f.9847397

-0.fff 5862 57477.35 57462.74 2.758 83.15f t 37.P743 f.lfl6789 8.9859024 f.H24834 57451.62 3.fff 83.1455 39.8708 f.f773865 8.f!Z4fH f.ff71f55 57466.25 3.259 83.1476 39.87M

-0.1818252 f.ff28841 f.ff63895 57847.68 3.586 83.1362 39.8769 f.!!92348 f.ft!6825 f.ff933f2 57475.41 3.752 83.1387 N.F7f4 0.1930818 f.ff28837 f.H62264 57454.47 4.ffs 83.1124 39.8684 f.1457422 f.H77721 8.8872359 57445.12 4.259 83.1959 39.8751 f.f688988 f.filf988 4.8989636

'~

57452.ff 2.8437366 4.5f3 83.lf78 n.%B8

$7454.09 f.ff78668 f.ff92594 4.759 83.1897 P.Elli

-0.8144959 f.ff66247 f.ff9f6N 57445.59 5.f ff 81.4Cf3 39.8683 f.891587 f.ff93883 f.H96987 5.756 63.8682 39.8694 f.fE26464 f.ft29494 f.filf531 57434.81 57454.77 5.5f3 03.8517 39.86W

-f.1445763 f.ff54538 f.fif2247 5.758 C3.836f

?.9.81,55 57453.fi f.0836518 f.ff911t?

I 57459.68 0.0341842 6.ffi 83.4535 39.%51 f.8488787 f.ff52496 f.Sf85874 57449.51 f.0298836 f.ff62958 6.251 83.f381 M.8615 57447.34 f.fl5f947 f.ff83621 6.5N 83.fl35 M.8587 57441.44 f.ff66468 f.ff8242f 6.758 82.9983 F.8578 57442.87 f.ff79722 f.H84126 f.f4tl243 7.Hf 82.9839 39.8143 8.0899559 f.lf73084 f.ff84184 57419.53 7.258 82.98Ff 39.8578 0.0232294 f.pf78766 f.H85228 57439.18 f.8824482 f.ff16894 f.NG5658 7.5N 83.f f!6 39.8626 57447.29 0.0564464 f.5855526 f.H82111 7.758 83.fil5 39.8583 57428.45 f.1311519 f.ff94825 8.5886126 8.fH 83.8852 37.8573 57437.93

-0.f66!6ff f.0072395 f.ff85458 8.258 83.0ft8 39.8538 5743f.57 f.f512798 8.8585731 f.H87tf7 8.5N 82.9951 39.8533 57432.39

-f.ft26783 f.ff79484 f.Sf37412 8.758 82.9729 39.85f4 57425.57 f.f474739 f.ff99767 9.f N 02.94!5 39.8583 57433.45

-f.f548544 f.S$89496 7.159 82.9492 39.8498 57425.H f.ff73821 f.ff88436 9.5N 82.9252 39.045.1 f.8586272 f.ff86883 f.ff89553 57425,41

-0.H26121 f.ff83909 f.H98162 9.759 82.9938 39.8515 57438.31 1.fB99ff6 f.8858725 f.8887f13 If.fH 82.8863 19.8438 57434.27 f.f281558 f.9964292 f.H84969 If.258 82.8685 39.8443 57434.49 0 Hl5587 8.fM23%

If.5H 82.8753 39.8393 57427.15 f.0511469 0.8882831 If.759 82.8576 39.P393 57438.32 f.8973031 f.ff82438 ll.ff3 82.8378 39.8384

-f.5778154 f.H53258 f.8879415 57436.94 II.258 92.8497 39.8341 f.ff96298 8.ff54227 f.H16841 57395.25 11.'.98

  1. 2.8263 37.8361 f.2983228 f.fil7498

'f.H82442 L*

11.158 82.8126 19.8?t3 5741?.78 f.Il52f82 f.H76171 1.H7965?

57416.32

-0.2862538 f.ff52797 f.H79511 S

17.fN 87.8837 31.9787 57476.47

-f.f4658 ym

.8869 3

818 H

m o w ju d

J

2

SHLET NO.

ilDESSEE.'ALLEf o'Jin3 Riff rtut:A!NMENI LEAXI.CL PE#SUREMfN1

~

11ST Ser.nr HttM t.','l P.V.i (Ori Cil'D 10iAL 11A55 P-i-P TOTAL. TIME RASS 51C fir 1PERAll#E rRISsuRE OF AIR LEAK RAll LEAX RATE LEAKRAIE Sitel lH.f.

PSIA LBM 1 PER 1409R I PER HOUR 1 PER H3UR

..............................................................................s 1;.25d 17.747 17.8331 574f4.26 f.1546803 f.ff951f6 f.8868902

~

I?.58J 82.1956 39.9291 57414.11

-0.f728391 f.ff78653 f.ff81222 12.753 82.7836 39.R290 57422.94 0.8573141 f.ff65864 f.H8Ff95 13.6fs 62.7835 39.8315 57426.73 f.1263939 f.ff59546 f.H78348

~

11.25J 82.8f26 39.0340 57413.41 f.8927534 f.ff759tf f.ff78481 13.5f1 82.1961 39.8344 57483.37 f.86997f6 f.H87448 f.Ifi9771 13.758 82.8192 39.0244 574f9.f7

-f.8391132 f.H78446 f.ff3fif9

~

14.lH 82.1988 39.83H 57417.85 f.0611832 f.ff66328 f.ff79186 14.258 82.7961 1?.P266 57416.57 f.Pf98987 f.ff6672' f.ff78235 14.5H 82.7P3 39.4i96 57417.32 f.ff52249 f.ff64673 f.ff77228 14.758 82.7357 39.8214 57484..;9 f 69stfl7 f.8878335 f.ff77692 lb.lPP 82.7551 17.8263 57418.51 0.f988889 f.ff61059 f.ff764f6 15.2';f 82.7528 39.8288 57399.67 f.1317344 f.H81434 f.ff77178 15.5fe 82.1447 39.8259 57371.89 f.f542246 f.ff89052 f.ff78558 15.758 82.7573

39. W 6 574ft.79

-f.f759592 f.ff75599 f.ff7857f 11.128 87.7697 31.0/61 57417.03 f 1948232 f.ff5Ef58 f.fS17019

~

16.258 B7.7711 37.0165 57318.92 f.2719918 f.H90933 f.ff79172 16.5ff 02.7841 39.7198 57377.47 f.fiff757 f.H98068 f.ffBil89 ll.7M 0?.1668 39.8t?f

$7304.93

-f.f52fl26 f.H09634 f.af82278 17.003 A7 790 Tr.P2H 57366.59 f.fil5175 f.ff86624 f.8f82954 17 l's U.721 37.3173 57372.55 f.f9785,5 f.ff99538 f.H847f9 17.* M R2.rfH 19.8106 57372.13

-0.1365516 f.ff78634 f.9834615 ll.h4 82.GP46 3?.4167 57399.66 0.f454654

f. full 32 f.H83895 19.HA r2.MS3 39.R10 57396.35 C.f!6f412 f.ff77312 f.ff83311 1R.258 9?.8792 3?WC5 57382.52 f.f963686 f.ffS4564 f.ff83138

~

I R. ',f f 02.9081 M.8? f'i 57388.52

-f.f417698 f.fD7786 f.HS3632 19.758 82.fiP8 M.82/9 57379.11 f.f455357 f.ff85474 f.H94457 17.f N 9.9719 31.0319 57393."8

-f.f994292 f.ffil289 f.ff83438 li.258 H3.85/l 39.8217 57330.f5 0.99286!?

f.N824f6 f.8983641 19.5f3 83.1157 39.9361 57357.46 f.15745f4 f.fifl584 f.ff952.47 17.759 83.173P 17.8413 57359.34

-8.8818758 f.N90567 f.ff86553 2f.ega 83,n99 39.8475 57357.60 f.9116f44 f.ff98782 f.8887786 28.2.0 03.29H 39.8444 5733d.43 f.f5!!521 0.0183742 f 8089314 Ed.5H 83.3316 39.6507 57374.59 f.14J2ff4 f.ff85415 f.ff8942f 28,153 83.30'i7 39.8589 57375.78 0.f362226 f.HSH30 f.8039172 21.fff 83.4321 19.8582 57359.07 f.ll65f35 f.ff92923 f.H89684 11.253 91.4315 37.8601 57357.8f f.fc808f4 f.H92873 f.ff98405

~

21.5dJ 83.4112 39.8536 57346.43 8.0792715 f.fiff992 f.ff91543 21.75:1 83.4259 19.G495 57351.63

-f.8362659 f.ff95672 f.ff92202

?l.9J 63.4113 39.0583 57376.63 0.1743344 f.fM4815 f.8891488 21.250 83.4634 37.8474 57363.!3 f.f94f598 f.ff84526 f.ff91415 77.5H 83.409p 39.3477 57352.77 f.f722455 8.ff916ft 8.ff91821 12.75J J3.4s51 12.r521 57348.13 f.0278156 f.ff93645 f.H92308 n.fH 83.4;f7 I?.eWJ 57336.15 f.688dS42 f.ftf2181 f.If93315 D.254 03.4605

19. f',il 57336.25 f.fff6548 f.ftstell f.Pf94165 73.570
3.5
e3 34.ceed 9351.77

-0.1152458 f.ff87706 f.ff94183 13.15J 83.5713 31.0613 573tP.Sl 8.f269165 f.H89618 f.H94291 4. f.'il U3.C fl 39.8651 5/336.i6 f.f874867 f.ff97778 f.ff94889

~

..........................................................e

-w-D 0

.QDW]

dd

&hMin i

c

I i

e APPENDIX C I:

u t

I s

IENNESSEE VAllET AUTHORlli i

(EQUOTAH NUCllAR PIA 41 -- UNii !

CONIAINMENT LEAVACE MEASUREMENT IEST 'iut!.1RT ML CCf'PMllMENTS 12 PSIC CILRT H9URS AIR 11AS3 AIR M.%S AIR MASS AIR PASS P-i-P 10iAl ilNE MASS SINCE ICWrR COMP.

UPPER CONF.

VIFER ICE LOWER ICE LEAK RATE LEAK RATE LEAX RATE JART ILM lFM LEM LBM 1 FER HOUR 1 PER HOUR 1 FER HOUR f.fM E.t. )

it]A$,"

Jjf),)

[6949,$

p,M$$$

g,pgpfg g,ggggg 8.450

' W i.8 91149.7 7108.8 16968.8 f.92829 f.lfB20 f.ff821 f.5ff 5'l?'2.1 91144.1 7ttf.7 16966.7 0.ff21:3 f.ff266 f.ff266 f.757 M 31.2 911M.6 71H.8 169f5.0 f.f!IA6 f.ff7.1J f.ff636 1.fM 5393f.I 91l3?.4 7182.8 16963.2 f.ff277 f.ff619 f.88633

1. 2'i9 53738.9 91137.6 7183.f 16962.1

-0.99948 f.ff486 f.ff534 1.588 537N.3 91192.5 7 t et'.4 1697.3.6 f.fff37 f.ff398 f.ff439 1.758 5.1939.7 91182.5 7897.9 16959.1 f.fl334 f.ff532 f.ff473

/.fff 51929.8 91141.3 7997.6 16957.7 f.ff887 f.ff576 f.ff518 2.259 51938.6 Sil42.A 7106.5 16956.6

-f.ff9ft 0.0fil2 f.ff463 2.9H 51932.1 91143.2 71f1.4 l&?55.6

-f.ff481 f.ff323 f.ff391

?.759 53932.8 91145.6 7tfl.8 16954.6

-0.08277 f.ff268 f.ff322 3.ff4 53133.6 91144.9 7112.6 16953.8 f.01278 f.ffl39 f.ff229 3.258 53934.2 91151.2 76??.7 16952.4 f.ff318 f.88153 f.lfl13 3.500 S'932.4 91145.6 1998.9 16956.5 f.02373 f.Sf312 f.ffl91 J

3. 7'if 51731.7 91146.2 7897.8 16949.3 f.ff598 f.ff331 f.ff213 4.f.18 53931.9 91146.9 7997.4 16947.7 f.ff248 f.ff326 f.ff228 f.258

'4 93.1.1 91148.9 7997.6 16947.1 0.85728 f.ff?64 0.06223 4.5ff 539'4.1 91149.7 7191.3 16946.6 0.01138 f.ffl86 f.ffl97 4.60 53934.1 91151.4 70l8.1 16945.5 f.ff6?!

8.f8289 f.ffl84 5.08 539J4.4 91153.6 7892.6 16944.3 f.98991 f.0f248 f.ffl86 5.25f 51738.8 9115' 1 7919.7 16943.1 f.81171 f.ff292 f.ffl98

/

5.D6 0913.3 91151.'

N14.1 16141.9 f.#205 f.90266 f.ffff2 L 7'if 519';.4 91152.1 N96.2 16048.8

- 8.ff M 7 f.ff241 f.ff2fc 6.000 53?34.4 91151.4 N93.6 16'i4f.f

-8.98495 f.ff2tf 0.f3193 6.,58 5.1935.0 91156.A 7998.0 16939.5 0.01872 f.88159 f.80176 6.98 51938.9 91151.9 7f96.8 16919.5 f.f24?9 f.ffl72 f.f8164 6.430 51935.7 9115'i.9 N17.5 16937.9 f.ff376 f.00176 f.ff!56 6.79

' 1935.1 ill16.8 1895.9 16937.8 8.01957 f.fa192 f.f8152 7.8/7 51/35.7 9115'i.7 1997.1 16035.3 f.fff48 f.ffl85 f.ffl49 t.314

'iM5.1 91156.2 7693.7 169'J4.2 f.01178 8.98217 f.88153

1. %4

'i W 35.6 91156.3 N93.2 16732.9 f.ff244 f.89218 f.08155 1.'t! 1 5393.f 91155.8 7993.4 16931.8 f.ff499 f.ff227 f.ff!6f 8.ft l 5.'9J7.8 91157.9 7691.1 16931.3

-0.ff525 f.ffif3 f.ffl59 3.111

'U937.6 91157.9 7997.8 1A93f.!

8.f!!24 f.f9231 0.f8164 k

D *

  • lD
  • lD 030 Y h m

MUJuh

ilNNESSEE VAllti AUTHORIII 5.1000fAH NULLEAR N ANT -- UKli i r0H1AlNMTNT IfArACE NEASUREMENT TEST S'NRART

)_

ALL COMI M IMENTS 12 PSIC CILRT HOURS AIR MASS AIR MASS AIR MASS AIR MASS P-i P TOIAL TIME MASS j

SINCF

[0k'ER COMP.

11NTR CORP.

UFPER ICE LOWER IEE LEAX RATE LEAKRATE LEAKRATE STAR 1 LBM LPM LBM

...........................................................LOM

! PER NOUR I FER HOUR I PER HOUR 8.564 51934.5 91156.0 7698.9 16928.5 f.ff839 f.ff!49 f.ffl71 8.814 53936.0 91155.5 7991.1 16927.1 f.fff26 f.If243 f.ffl77 9.864 53936.3 91155.7 7991.5 16926.2 f.fff22 f.08236 f.ffl88 9.314 53937.2 91156.1 7992.4 16925.5

-0.ff384 f.ff223 f.ff!82 9.564 53938.1 91156.9 7696.3 16924.8 f.ff311 f.00222 f.0f!84 9.814 53938.4 91159.3 7985.3 16924.1 f.ff673 f.90234 f.98186 ff.f54 53938.5 91169.4 7083.7 16922.8 f.00425 f.ff238 f.ffl98 16.314 53939.1 91151.2 1911.7 16921.8

-0.91527 f.18196 f.ff!87 16.564 53939.7 91162.3 7693.2 16921.2

f. fill 6 f.ffl65 f.ffl81 10.014 53941.2 91161.6 7986.6 16929.5 f.fif68 f.ffl85 f.ffl78 18.724 5394f.8 91161.5 7684.0 16920.2 0.98278 f.ffl81 f.ffl75 11.f64 5394?.i 91110.4 7%f.7 16928.2 f.ff389 f.ff!83 f.ffl72 11.314

'3741.2 91166.2 1870.3 16918.6 f.91737 f.ff218 f.ff!74 11.944 53939.7

?ll6?.i 7Efil.C 16916.5 f.ffl13 f 06223 f.88177

!!.814

% 939.6 91161.9 79C5.0 16915.2

-f.00396 f.ff21f f.ffl7u ll. fat 53.'.19. 6 1116.'.5 7987.1 16914,'3 F.00122 f.ff2f3 f.f8178 It.314 SP4f.3 91148.5 7005.5 16913.5 f.fJ166 f.ff2f2 f.ffl78 li. 5.',4 SND.7 ol l6.'i 7M6.f 16912.6 0.0fl33 f.ffif t f.6fl79

11. 814 4%'.4 91164..'

7600.9 16911.0 f.f8896 f.ff2f5 f.ffl??

L 13 (A4 51911.5 0l!63.2 7650.1 1A910.1 f.00155 f.ff2f 4 0.00179 13.314 5.937.2 91141.1 1998.8 11.999.1 f.*fff7 f.ff2ff f.fft?9 13.5'4 53931.6 91163.8 1989.9 16?I"1.3 0.06436 f.ff285 f.98180 13.P.14.

53937.6 9116t.?

7f90.5 16987.5

-8.ff835 f.f"!86 f.ff!79 14.i44 53133.8 91169.4 799f.6 16106.9 0.ff758 f.ffl69 f.ffl75 14.314 51939.7 91176.3 7210.1 16986.2

-f.ffl52 f.ffl63 f.ffl72 ft.564 53139.8 911%.5 7888.7 16905.3 f.ff949 f.ffl17 f.ffl10 14.814 53041.4 91172.6 if35.6 16904.4

-f.ff448 f.ffl67 f.ffl68 15.054 53941.9 91173.7 1979.9 16983.4 f.fl231 f.ffl84 f.ffl67 i

15.314 53148.1 91172.5 7679.6 16982.1 f.91161 f.ffl99 f.00168 15.564 53939.9 91171.9 1979.6 169ff.6 f.90573 f.ff205 f.ffl69 15.814 5?937.2 91172.3 7f88.0 16899.6 f.ffl74 f.88205 f.M178 16.844 53949.1 91174.6 7878.4 16899.2

-f.ff314 f.ffl97 f.ffl71 14.314 Sh41.4 91175.7 1979.8 16098.4

-0.ff665 f.ffl83 0.00178 16.544 53941.1 11178.3 7879.8 16897.3

-0.ff788 f.ffl76 f.ffl69 16.Rl4 51142.4 91176.6 7974.3 16896.3 f.fl640 f.ffl98 f.89178

" D) T Y M D * ]De w Ju e AL d d li h i

~

ifFISSEE iAllEl A01HORiff SFQUOTAll NUllE6R P'. ANT -- UNIT 1 CONTAINMENT LIAKACL MEASUREMfNT TEST SUMART 6tl COMPMilHENTS 12 PSl(, CILRI t"UR1 AIR MA 5 AIR MASS AIR MASS AIR MASS P-i-P 10iAL ilME MASS

$!hCE LOWER C0!iP.

UTFER COMP.

UFPER ICE LOWER ICE LEAK RATE LEAK RATE LEAK RATE S1AR1 LBM LBM LBM LBM I FER 110'JR I PER HOUR I PER HOUR 17.664 53941.1 11178.1 7972.9 16895.1 f.88551 f.f9283 f.ff!71 17.314 53948.8 91174.6 7974.6 16893.8 f.ff987 f.ff215 f.ff!73 17.564 53948.4 91175.7 707i.8 16892.7

-0.01868 f.ffl96 f.fflT3 17.814 53948.6 91177.3 7773.2 16891.8 f.01182 f.ff209 f.88175 19.f64 53948.6 91177.6 7873.3 16898.7 f.98174 f.ff289 f.89176 18.314 51986.4 91176.5 7079.8 16889.4

-0.ff916 f.ffl93 f.ffl76

!?.564 53948.2 91174.1 7f81.2 16889.2 f.ff399 f.ffl96 f.ffl16 19.014 53!4f.3 91!76.9 7902.2 16887.4

-0.88549 f.98186 f.89176 10.9.'6 53941.3 71178.2 7P81.4 16087.4

-0.ffi62 f.ff!78 f.f9175 19.186 5MO.5 91t'9.1 790f.3 16886.7

-f.ff255 f.ffl73 f.00173 19.06 53947.9 11188.1 1979.1 16885.5 f.ff718 f.ffl88 f.96173 17.!86 53948.9 91177.3 7879.1 16884.2 f.fil35 f.00192 f.fsl73 19.9 4 53942.4 91178.4 7976.0 16 % 3.3

-9.fff41 f.ff189 f.ffl73 27.186 53947.4 91177.6 7078.5 16867.4 f.ff311 f.ffl98 f.ffl13 20.U6 SH4I 5 11179.2 1978.6 16881.7

-f.ff279 f.ffl85 f.ffl73 Tf.686 51942.1 71179.1 7918 6 1688f.7 9.98383 f.90186 f.ff!73 If.935 53143.5 91179.6 7378.7 16068.2

-0.ffl99 f.ffl88 f.ffl72 21.11;.-

53943.5 91189.5 7917.7 16879.3 f.ff251 f.ff!81 f.ffl72 Z!.436 539 0.6 91191.2 7977.9 16370.4

-f.fff33 f.05179 f.ffl71 21.686 53943.4 91100.3 7678.7 16877.3 8.99299 f.ff!88 8.ffl7f 2!.936 53944.7 91181.9 7879.8 16876.7

-0.f8708 f.ffl69 f.ffl69 22.145 53945.4 91184.1 7G78.8 16876.5

-f.cf399 f.ff!63 f.8f168 22.436 53947.3 91187.3 7978.6 16876.0 0.81829 f.ffl58 f.ffl66 22.6 %

53948.8 91183.9 7678.5 16875.6

-f.ff603 f.ff141 f.ffl63 22.916 53949.8 91191.7 7968.8 16875.1 f.fl5ff f.ffl56 f.ff!62 23.196 53949.6 91191.5 7962.2 16873.5 f.92826 f.ffl76 f.ffl62 23.436 53947.3 91189.3 7f67.1 16871.9 f.88281 f.ff!77 f.ffl62 23.696 53945.6 91107.3 707f.8 1687f.3 f.ff356 f.H179 f.00162 23.936 53946.8 11183.1 7874.8 16869.3 f.00181 f.ffl79 f.ffl&2 24.196 53946.8 91185.4 7f74.0 16868.3

-0.00981 f.f0177 f.ffl62 24.436 53946.6 91187.3 7973.8 16867.5 f.88392 f.ffl71 0.00162 24.686 53946.0 911P1.9 7874.8 10866.6 f.ff822 f.ffl69 f.ffl61 i

,