ML19030A984
| ML19030A984 | |
| Person / Time | |
|---|---|
| Site: | Clinch River |
| Issue date: | 01/18/2019 |
| From: | James Shea Tennessee Valley Authority |
| To: | Office of New Reactors |
| Fetter A | |
| References | |
| TVACLINCHRIVERESP, TVACLINCHRIVERESP.SUBMISSION.6, CRN.P.PART08, CRN.P.PART08.2 | |
| Download: ML19030A984 (7) | |
Text
APPENDIX F.3-Soil Compaction Test Results-No Change for Rev. 4 Clinch River Data Report Rev. 4 CRP-1112.16 Page F.3-1 of 7 a me
ASTM 01557-12 Curve No.: TP-1,S-1 Project No.: 6464131072 Date: 10/20/13 Project: Clinch River SMR Project Client: Bechtel Project No: 25847-601 Source of Sam'ple: TP-1 Depth: 6-8' (Bulk)
Sample Number: S-1 Remarks: Specific Gravity is assumed Hammer Type: Automatic MATERIAL DESCRIPTION
==
Description:==
Brownish Red Fat CLAY with Sand Classifications -
Nat. Moist. = 32.2 %
Liquid Limit= 61 uses: cH Maximum dry density= 109.0 pcf Optimum moisture= 16.7%
AASHTO: A-7-6(30)
Sp.G. = 2.700 Plasticity Index= 37
% < No.200 = 77.7%
TEST RESULTS 140
\\
\\
Test specification:
\\
ASTM D 1557-12 Method C
\\
\\. \\
I'\\.
1\\
\\
I\\. '\\.
130
\\.
'\\.
1'\\.
\\.
1\\. '\\
'\\.
100% SATURATION CURVES
'\\
120 i'\\_ "
FOR SPEC. GRAV. EQUAL TO:
't3 110 0..
~
'(j) c Q)
-o
'\\
1\\. 1"-
1'\\.."\\
2.8
" "' ~ 2.7
_../. )-r-, ""
~ ~
2.6
-('
1'--"'
~
1'\\. "'
e:-
100 0
['..._
1'1'\\. I"""'
I"""'
90 I'-.
'~'--
......_ r--. 1""-
80 1-70 0
5 10 15 20 25 30 35 Water content, %
....... I'-.
1-40
. Figure TP-1,8-1
~~---------------------------------AMEC----------------------------------~
Tested By: -'C"""'S"'-----"-~-' _______ Checked By: =L=BJ"--.-~~'~'-~-'/\\-='--______ _
Clinch River Data Report Rev. 4 CRP-1112.16 0
Page F.3-2 of 7
MOISTURE DENSITY TEST DATA Client: Bechtel Project No: 25847-601 Project: Clinch River SMR Project Project Number: 6464131072 Location: TP-1 Depth: 6-8' (Bulk)
==
Description:==
Brownish Red Fat CLAY with Sand Sample Number: S-1 Natural Moisture: 32.2 1/13/2014 Liquid Limit: 61 Date: 10/20/13 Plasticity Index: 37 USCS Classification: CH AASHTO Classification: A-7-6(30)
Testing Remarks: Specific Gravity is assumed Hammer Type: Automatic "P[eparation Method: Dry Tested by: CS C/1 Percent passing 3/4 in. sieve: 95.3 Test Specification:
Type of Test: ASTM D 1557-12 Method C Checked by: LBJ ~
Mold Dia: 6.00 Hammer Wt.: 10. lbs Drop: 18" Layers: 5 Blows per Layer: 56 Point No.
1 109.5 r ~ ~'~
.70 I
\\
-'ti
\\ \\
- 0.
0
~ \\
- ~
c:
Ql 0
0
\\ \\
(
Wt.M+S 9840.6 10014.8 Wt.M 5723.9 5723.9 Wt.W+T 889.5 1002.1 Wt. D+T 815.4 904.3 Tare 286.0 292.6 Moist.
Dry Den.
108 106.5 105 103.5 102 Moisture ontent1 %
11 13 15 17 19 21 23 10076.6 10010.2 5723.9 5723.9 703.1 663.5 639.9 599.7 292.2 295.7
~------------------------------------AMEC ------------------------------------~
Clinch River Data Report Rev. 4 CRP-1112.16 Page F.3-3 of 7
ASTM 01557-12 Curve No.: TP-2,S-1 Project No.: 6464131072 Date: 10/20/13 Project: Clinch River SMR Project Client: Bechtel Project No: 25847-601 Source of Sample: TP-2 Depth: 1-2.5 (Bulk)
Sample Number: S-1 Remarks: Specifc Gravity is as~umed Hammer Type : Automatic
==
Description:==
Brown Sandy Lean CLAY MATERIAL DESCRIPTION Classifications -
Nat. Moist.= 16.5%
Liquid Limit= 46 uses: cL AASHTO: A-7-6(13)
Sp.G. = 2.705 Plasticity Index= 27
% < No.200 = 59.1 %
ROCK CORRECTED TEST RESULTS UNCORRECTED Maximum dry density== 122.7 pcf 120.6 pcf Optimum moisture== 10.3%
10.9%
140 1\\
1\\
Test specification:
1\\
ASTMD 1557-12 Method C
\\
1\\ 1_:--.,
ASTM D 4718-87 Oversize Correction Applied to Final Results 1\\
1\\
1\\ \\
1\\ \\
130
\\
I'\\
1'\\.
1\\
1\\ '\\
I'\\
100% SATURATION CURVES v
--c 1'\\
<'f 1\\ \\
FOR SPEC. GRAV. EQUAL TO:
120 4-(.)
110
- 0.
~
'iii c
Q)
"0
'\\
1\\ 1\\
2.8 1\\ "'
'\\
1\\ ~ 2.7
'\\
~
~)...,
2.6
' "'- "\\
~"'-
1""'- "
100 0
t'--,
1""'-
!'..... 1""'-
1""'- "
r--..... -.....
I""'
~
90 1'-.... ~
I'--
80 70 0
5 10 15 20 25 30 35 Water content, %
f'-,_ I'--
!"- 1'..
40 Figure TP-2,SS-l
~-----------------------------------AMEC------------------------------------~
Tested By: ~c""s"'--------'&J"""'---'
1
_, _______ Checked By:,L=BJ,___~--fl--',~~r-----------
Clinch River Data Report Rev. 4 CRP-1112.16 Page F.34 of 7
Client: Bechtel Project No: 25847-601 Project: Clinch River SMR Project Project Number: 6464131072 Location: TP-2 Depth: 1-2.5 (Bulk)
==
Description:==
Brown Sandy Lean CLAY Liquid Limit: 46 MOISTURE DENSITY TEST DATA 1/13/2014 Sample Number: S-1 Natural Moisture: 16.5 Date: 10/20/13 Plasticity Index: 27 USGS Classification: CL AASHTO Classification: A-7-6(13)
Testing Remarks: Specifc Gravity is assumed Hammer Type : Automatic Preparation Method: Dry Tested by: CS aD Test Specification:
Type of Test: ASTM D 1557-12 Method C Mold Dia: 6.00 Hammer Wt.: 10. lbs Drop: 18" Layers: 5 Blows per Layer: 56 123
~VSpG 2.71 if ~ \\
'tl
- 0.
~ 1\\
.12 I
c:
Q) 0 2:'
0 I
\\
()
\\
. 121.5 120 118.5 117 115.5 Moisture ontent1 %
5 9
11 13 15 17 Rock Corrected Results:
Uncorrected Results:
Rock Correction Data:
Correction Method: ASTM D 4718-87 Wt, M+S Wt.M Wt.W+T Wt. D+T Tare 9975.6 5723.9 826.9 781.7 136.2 10199.2 5723.9 930.9 875.4 292.5 10325.0 5723.9 795.7 739.1 296.0 Percentage of Oversize Material (%> 3/4 in.): 6.1 Oversize Material Moisture Content:.7 Bulk Specific Gravity of Oversize Material: 2.700 Note: the rock correction was applied to the calculated max. density and opt. moisture values.
10339.5 5723.9 844.6 777.2 292.2
~---------------------------------- AMEC ----------------------------------~
Clinch River Data Report Rev. 4 CRP-1112.16 Page F.3-5 of 7
ASTM 01557-12 Project No.: 6464131072 Date: 10/18/13 Project: Clinch River SMRProject Client: Bechtel Project No: 25847-601 Source of Sample: TP-3 Depth: 3-6' (Bulk)
Sample Number: S-1 Remarks: Hammer Type: Automatic Preparation Method: Dry MATERIAL DESCRIPTION
==
Description:==
Brownish Red Clayey SAND Classifications
- Nat. Moist. = 20.9%
Liquid Limit= 58 uses: sc Maximum dry density= 105.4 pcf Optimum moisture = 17.4 %
AASHTO: A-7-6(7)
Sp.G. =
Plasticity Index = 31
% < No.200 = 41.0%
TEST RESULTS 140
\\
1\\
Test specification:
\\.
ASTMD 1557-12 Method C
\\
II\\ \\.
1\\.
1\\
i\\. \\.
1\\. \\
130
\\
1\\.
\\
1\\ \\
!\\.
100% SATURATION CURVES 120
\\.
\\
FOR SPEC. GRAV. EQUAL TO:
't5
- 0.
110
~
(f) c a>
""0 2:'
100 0
90 80 70 0
v
\\._
5 10 15
["-. 1"".
" 1\\ '<;
~
~ ~
!'-.. I"'-
~' !"--
20
.water content, %
2.8 2.7 2.6 I"'-
~
~"---, I"'-
1""-
I'-.
I'.
....... I'--
.....,__ I" "'-......,
'I'-................
25 30 35 I'-- "
40 Figure TP-3,S-1
~
........................................................................................... AMEc.......................................................................................... ~
Tested By: __,C=S,______t<_~------ Checked By: =LB=J'------tf+.fr-1-~-A-k _____ _
Clinch River Data Report Rev. 4 CRP-1112.16 Page F.3-6 of 7
Client: Bechtel Project No: 25847-601 Project: Clinch River SMR Project Project Number: 6464131072 Location: TP-3 Depth: 3-6' (Bulle)
==
Description:==
Brownish Red Clayey SAND MOISTURE DENSITY TEST DATA 1/13/2014 Sample Number: S-1 Natural Moisture: 20.9 Liquid Limit: 58 Date: 10/18/13 Plasticity Index: 31 USGS Classification: SC AASHTO Classification: A-7-6(7)
Testing Remarks: Hmmner Type: Automatic Preparation Method: Dry Specific Gravity is assumed= 2.700 Tested by: CS Percent passing 3/4 in. sieve: 95.8 Test Specification:
Type of Test: ASTM D 1557-12 Method C Mold Dia: 6.00 Hammer Wt.: 10. lbs Drop: 18" Layers: 5 Blows per Layer: 56 109 107 105 't;
- 0.
~
c:
Q) 0 1:-
. 103 0 101 99 13
./ r----,_
I I
j Moisture 15 17 Wt. M+S 9579.2 Wt.M 5723.9 Wt.W+T 808.4 Wt. D+T 727.6 Tare 145.0 Moist.
~
Dry Den.
\\
~
u ontent,%
19 21 23 25 Test Results:
9861.2 9954.3 9923.1 5723.9 5723.9 5723.9 699.8 791.3 757.2 643.7 707.2 672.0 295.9 285.6 292.8
~------------------------------------AMEC ------------------------------------~
Clinch River Data Report Rev. 4 CRP-1112.16 Page F.3-7 of 7