ML18093B045

From kanterella
Jump to navigation Jump to search
Advises That NRC Planning Enforcement Conference within 30 Days to Discuss Listed Equipment Qualification Deficiencies Noted in Insps 50-272/86-23 & 50-311/86-23 on 860811-15
ML18093B045
Person / Time
Site: Salem  PSEG icon.png
Issue date: 08/19/1988
From: Johnston W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Miltenberger S
Public Service Enterprise Group
References
NUDOCS 8808300066
Download: ML18093B045 (3)


See also: IR 05000272/1986023

Text

\\

Docket Nos. 50-272

50-311

Public Service Electric and Gas Company

ATTN:

Mr. Steven E. Miltenberger

Vice President and

Chief Nuclear Officer

P. 0. Box 236

Hancocks Bridge, New Jersey 08038

Gentlemen:

19 AUG 1988

Subject:

Enforcement Conference for Equipment Qualification

During the period of August 11-15, 1986, the NRC performed an inspection at

the Salem Nuclear Generating Station to review the status of your equipment

qualification (EQ) program and to evaluate the status of your compliance with

10 CFR 50.49.

As a result of this inspection, potential violations of 10 CFR

50.49 were documented in the inspection report (50-272/86-23; 50-311/86-23)

that was sent to you on November 13, 1986.

In addition, EQ deficiencies were

identified by your staff and reported to the NRC in LER 86-007, LER 86-015 and

LER 86-018.

The most significant EQ deficiencies involve:

1.

Limitorque Valve operator without required T-drains.

2.

Solenoid operated valves without Conax seals.

3.

~lectric junction boxes not properly sealed.

4.

Limitorque valve operators with brakes electrically disconnected but

not physically removed.

5.

Terminal blocks associated with auxiliary feedwater transmitters.

All of these deficiencies were identified by your staff and documented in LER 86-007.

All deficiencies apply to both unit 1 and unit 2.

The NRC is considering these potential violations for appropriate enforcement

action.

We plan to conduct an enforcement conference with you to discuss

these violations in the NRC Region I office within .30 days of your receipt of

this letter. At the enforcement conference, you should be prepared to discuss

(1) the number of deficiencies and the number of systems and components

affected in each case; (2) the specific and underlying cause(s); and, (3) the

actions taken to correct the deficiencies as well as to ensure yourself that

-Public Service Electric and Gas Company is currently in overall compliance

with EQ requirements.

Furthermore, you should be prepared to discuss the

OFFICIAL RECORD COPY

EC L TR SALEM -

08/11/88

0001.0.0

8808300066 880819

PDR

ADOCK 05000272

~--_pl\\JJ l

,\\e

~~/~H-

l

~. Public Service Electric

and Gas Company

2

potential violations in light of the Modified Enforcement Policy for EQ

Requirements which is described in the enclosure to Generic Letter 88-07,

i.e., for the item identified by you, whether it was promptly reported to the

NRC; were your best efforts involved to comply with the rule within the

deadline; and, if appropriate, why you believe that you clearly should not

have known of these deficiencies prior to the November 30, 1985 deadline for

being in compliance with the rules.

In addition, we ask that you specifically

address the qualifiability of the deficient components above at the time that

the deficiencies were identified by you.

We request that at the enforcement

conference you provide a handout that succinctly describes your position

concerning these enforcement considerations.

Please, at your earliest convenience, contact Mr. Jacque Durr of my staff at

(215) 337-5282 to finalize arrangements for the enforcement conference.

Your

cooperation in this matter is appreciated.

Sincerely,

William V. Johnston, Director

Division of Reactor Safety

cc w/encl:

Jack Urban, General Manager, Fuels Department, Delmarva Power & Light Co.

J.M. Zupko, Jr., General Manager - Salem Operations

B. A. Preston, Manager, Licensing and Regulation

General Manager - Nuclear Safety Review

M. J. Wetterhahn, Esquire

R. Fryling, Jr., Esquire

Scott B. Lingerer, Manager, Joint Generation Projects Department,

Atlantic Electric Company

Licensing Project Manager, NRR

Public Document Room (PDR)

Local Public Document Room (LPDR)

Nuclear Safety Information Center (NSIC)

NRC Resident Inspector

State of New Jersey

OFFICIAL RECORD COPY

EC LTR SALEM - 0001.0.1

08/04/88

\\' "

Public Service Electric

and Gas Company

bee:

Region I Docket Room Cw/concurrences)

Management Assistant, DRMA (w/o encl)

Section Chief, DRP

Robert J. Bores, DRSS

D. Holody, RI

J. Lieberman, OE

F. Miraglia, NRR

L. Chandler

A. Thadani, NRR

U. Potapovs, NRR

L~C.

ct({

RI:DRS

RI:D~S

Cheung/mlb/rw Anderson

08/12/88

I: RP \\

.

Kane

)

08/ /88

08/1v/88

RI: EO

iYJ1\\

Holody

<;33

RI:DRS

Durr

08/1s788

3

wv(

RI:DRS

Johnston

08/t~ /88

08/\\l /88

OFFICIAL RECORD COPY

C) -

  • ~

er

081/f/88

EC LTR SALEM - 0001.0.1

08/11/88