ML18092B526
| ML18092B526 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 04/14/1987 |
| From: | Public Service Enterprise Group |
| To: | |
| Shared Package | |
| ML18092B524 | List: |
| References | |
| NUDOCS 8704220183 | |
| Download: ML18092B526 (17) | |
Text
PI.ANT SYSTEMS 3/4.7.9 SNUBBERS LIM IT ING CONDIT ION FOR OPERATION 3.7.9 All snubbers shall be OPERABLE.
APPLICABILITY:
MODES 1, 2, 3 and 4.
(MODES 5 and 6 for snubbers located on systems required OPERABLE in those MO DES).
ACTION:
With one or more snubbers inoperable, within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, replace or restore the inoperable snubber(s) to OPERABLE status and perform an engineering evaluation per Specification 4.7.9c on the supported component or declare the supported system inoperable and follow appropriate ACTION statement for that system.
SURVEILl.ANCE REQUIREMENTS 4.7.9 Each snubber shall be demonstrated OPERABLE by performance of the following augmented inservice inspection program and the requirements of Specification 4.0.5.
- a.
Visual Inspection An inservice visual inspection of all snubbers shall be performed in accordance with the following schedule for each type.
As used in this specification, type of snubber shall mean snubber of the same design and manufacturer, irrespective of capacity.
No. Inoperable Snubbers of Each Type per Inspection Period 0
1 2
3' 4 5' 6' 7 8 or more Subsequent Inspection Period 18 months + 25%
12 months + 25%
6 months + 25%
124 days + 25%
62 days + 25%
31 days + 25%
Snubbers are categorized as accessible and inaccessible during reactor operation.
Each group (accessible and inaccessible) may be inspected independently in accordance with the above schedule.
8704220183 870414 PDR ADOCK 05000272 P
- The inspection interval shall not be lengthened more than one step at a time.
- The provisions of Specification 4.0.2 are not applicable.
SA LEM -
UN IT 1 3/4 7-28
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)
- b.
Visual Inspection Acceptance Criteria Visual inspections shall verify (1) that there are no visible indications of damage or impaired OPERABILITY, (2) attachments to the foundation or supporting structure are secure, and (3) in those locations where snubber movement can be manually induced without disconnnecting the snubber, that the snubber has freedom of movement and is not frozen up.
Snubbers which appear inoperable as a result of visual inspections may be determined OPERABLE for the purpose of establishing the next visual inspection interval, providing that (1) the cause of the rejection is clearly established and remedied for that particular snubber and for other snubbers that may be generically susceptible; and (2) the affected snubber is functionally tested in the as found condition and determined OPERABLE per Specification 4.7.9d or 4.7.9e as applicable. However, when the fluid port of a hydraulic snubber is found to be uncovered, the snubber shall be declared inoperable and cannot be determined OPERABLE via functional testing for the purpose of establishing the next visual inspection interval. All snubbers connected to an inoperable common hydraulic fluid reservoir shall be counted as inoperable snubbers.
- c. Functional Tests At least once per 18 months during shutdown, a representative sample of 10% of the total of each type of snubber in use in the plant shall be functionally tested either in place or in a bench test. For each type of snubber that does not meet the functional test acceptance criteria of Specification 4.7.9d or 4.7.9e, an additional 10% of that type of snubber shall be functionally tested.
The representative sample selected for functional testing shall include the various configurations, operating environments and the range of size and capacity of snubbers.
At least 25% of the snubbers in the representative sample shall include snubbers from the following three categories:
- 1. The first snubber away from each reactor vessel nozzle
- 2. Snubbers within five feet of heavy equipment (valve, pump, turbine, motor, etc.)
- 3. Snubbers within ten feet of the discharge from a safety relief valve SA LEM -
UN IT 1 3/4 7-29
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)
In addition to the regular sample, snubbers which failed the previous functional tests shall be retested during the next test period.
If a spare snubber has been installed in place of a failed snubber~ then both the failed snubber (if it is repaired and installed in another position) and the spare snubber shall be retested. Test results of these snubbers may not be included for the re-sampling.
If any snubber selected for functional testing either fails to lockup or fails to move, i.e., frozen in place, the cause will be evaluated and if caused by manufacturer or design deficiency all snubbers of the same design subject to the same defect shall be functionally tested.
This testing requirement shall be independent of the requirements stated above for snubbers not meeting the functional test acceptance criteria.
For the snubber(s) found inoperable, an engineering evaluation shall be performed on the components which are supported by the snubber(s). The purpose of this engineering evaluation shall be to determine if the components supported by the snubber(s) were adversely affected by the inoperability of the snubber(s) in order to ensure that the supported component remains capable of meeting the designed service.
- d.
Hydraulic Snubbers Functional Test Acceptance Criteria The hydraulic snubber functional test shall verify that:
- 1. Activation (restraining action) is achieved within the specified range of velocity or acceleration in both tension and compression.
- 2. Snubber bleed, or release rate, where required, is within the specified range in compression or tension. For snubbers specifically required to not displace under continuous load, the ability of the snubber to withstand load without displacement shall be verified.
- e. Mechanical Snubbers Functional Test Acceptance Criteria The mechanical snubber functional test shall verify that:
- 1. The force that initiates free movement of the snubber rod in either tension or compression is less than the specified maximum drag force. The drag force shall not have increased more than 50% since the last functional test.
- 2. Activation (restraining action) is achieved within the specified range of velocity or acceleration in both tension and compression.
SA LEM -
UN IT 1 3/4 7-30
PLANT SYSTEMS S URVE I LI.ANGE REQUIREMENTS (Continued)
- 3. Snubber release rate, where required, is within the specified range in compression or tension. For snubbers specifically required not to displace under continuous load, the ability of the snubber to withstand load without displacement shall be verified.
- f. Snubber Service Life Monitoring A record of the service life of each snubber, the date at which the designated service life commences and the installation and maintenance records on which the designated service life is based shall be maintained as required by Specification 6.10.2.1.
Concurrent with the first inservice visual inspection and at least once per 18 months thereafter, the installation and maintenance records for each snubber shall be reviewed to verify that the indicated service life has not been exceeded or will not be exceeded prior to the next scheduled snubber service life review.
If the indicated service life will be exceeded prior to the next scheduled snubber service life review, the snubber service life shall be replaced or reconditioned so as to extend its service life beyond the date of the next scheduled service life review. This reevaluation, replacement or reconditioning shall be indicated in the records.
SA LEM -
UN IT 1 3/4 7-31
TH IS PAGE LEFT INTENTIONALLY BLANK SA LEM -
UN IT 1 3/4 7-32
TH IS PAGE LEFT INTENTIONALLY BLANK SA LEM -
UN IT 1 3/4 7-33
PLANT SYSTEMS BASES 3/4.7.9.
SNUBBERS All snubbers are required OPERABLE to ensure that the structural integrity of the reactor coolant system and all other safety related systems is maintained during and following a seismic or other svent initiating dynamic loads. Snubbers excluded from this inspection program are those installed on nonsafety related systems and then only if their failure or failure of the system on which they are installed would have no adverse effect on any safety-related system.
A list of individual snubbers required to be operable per the tech-nical specifications with detailed information of snubber location and size and of system affected shall be available at the plant in accordance with Section 50.7l(c) of 10 CFR Part 50.
The accessability of each snubber shall be determined and approved by the Station Operations Review Committee.
The determination shall be based on the existing radiation levels and the expected time to perform a visual inspection in each snubber lo~ation as well as other factors associated with accessibility during plant operations (e.g. temperature, atmosphere, location, etc.) and the recommendations of Regulatory Guide 8.8 and 8.10.
The addition or deletion of any snubber shall be made in accordance with Section 50.59 of 10 CFR Part 50.
The visual inspection frequency is based upon maintaining a constant level of snubber protection to systems.
Therefore, the required inspection interval varies inversely with the observed snubber failures and is determined by the number of inoperable snubbers found during an inspection.
Inspections performed before that interval has elapsed may be used as a new reference point to determine the next inspection.
However the results of such early inspections performed before the original required time interval has elapsed (nominal time less 25%) may not be used to lengthen the required inspection interval.
Any inspection whose results require a shorter inspection interval will override the previous schedule:
When the cause of the rejection of a snubber is clearly established and remedied for that snubber and for any other snubbers that may be generically susceptible and verified by inservice functional testing that snubber may be exempted from being counted as inoperable.
Generically susceptitle snubbers are those which are of a specific make or model and have the same design features directly related to rejection of the snubber by visual inspection or are similarly located or exposed to the same environmental conditions such as temperature, radiation, and vibration.
When a snubber is found inoperable, an engineering evaluation is performed, in addition to the determination of the snubber mode of failure, in order to determine if any safety-related component or system has been adversely affected by the inoperability of the snubber.
The engineering evaluation shall determine whether or not the snubber mode of failure has imparted a significant effect or deg:radation on the supported component or system.
B 3/4 7-6
PLANT SYSTEMS BASES SNUBBERS (Continued)
To provide assurance of snubber functional reliability a representative sample of the installed snubbers will be functionally tested during plant shutdowns at 18-month intervals.
Observed failures of these sample snubbers shall require functional testing of additional units.
. Permanent or other exemptions from the surveillance program for individual snubbers may be granted by the Commission if a justifiable basis for exemption is presented and, if applicable, snubber life destructive testing was performed to qualify the snubbers for the applicable design conditions at either the completion of their fabrication or at a subsequent date.
Snubbers so exempted shall be listed in the list of individual snubbers indicating the extent of the exemptions.
Hydraulic snubbers and mechanical snubbers may each be treated as a different entity for the above surveillance programs.
The service life of a snubber is evaluated via manufacturer input and information through consideration of the snubber service conditions and associated installation and maintenance records (newly installed snubber, seal replaced, spring replaced, in high radiation area, in high temperature area, etc... ).
The requirement to monitor the snubber service life is included to ensure that the snubbers periodically undergo a performance evaluation in view of their age and operating conditions. These records will provide statistical bases for future consideration of snubber service life. The requirements for the maintenance of records and the snubber service life review not intended to affect plant operation.
3/4.7.10 FIRE SUPPRESSION SYSTEMS The OPERABILITY of the fire suppression systems ensures that adequate fire suppression capability is available to confine and extinguish fires occurring in any portion of the facility where safety-related equipment is located.
The fire suppression system consists of the water system, spray, and/or sprinklers, C02, and fire hose stations.
The collective capability of the fire suppression systems is adequate to minimize potential damage to safety-related equipment and is a major element in the facility fire protection program.
In the event that portions of the fir~ suppression system are inoperable, alternate backup fire-fighting equipment is required to be made available in the affected areas until the inoperable equipment is restored to service.
SALEM - UNIT T' B 3/4 7-7
BASES 3/4.7.10 FIRE SUPPRESSION SYSTEMS (Continued)
In the event the fire suppression water system becomes inoperable, immediate corrective measures must be taken since this system provides the major fire suppression capability of the plant. The requirement for a twenty-four hour report to the Commission provides for prompt evaluation of the acceptability of the corrective measures to provide adequate fire suppression capability for the continued protection of the nuclear plant.
3/4.7.11 PENETRATION FIRE BARRIERS The functional integrity of the penetration fire barriers ensures that fires will be confined or adequately retarded from spreading to adjacent portions of the facility. This design feature minimizes the possibility of a single fire rapidly involving several areas of the facility prior to detection and extinguishment. The penetration fire barriers are a passive element in the facility fire protection program and are subject to periodic inspections.
During periods of time when the barriers are not functional, a continuous fire watch is required to be maintained in the vicinity of the affected barrier until the barrier is restored to functional status.
SA LEM -
UN IT 1 B 3/4 7-8
PLANT SYSTEMS 3/4.7.9 SNUBBERS LIMITING CONDITION FOR OPERATION 3.7.9 All snubbers shall be OPERABLE.
APPLICABILITY:
MODES 1, 2, 3 and 4.
(MODES 5 and 6 for snubbers located on systems required OPERABLE in those MO DES).
ACT ION:
With one or more snubbers inoperable, within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, replace or restore the inoperable snubber(s) to OPERABLE status and perform an engineering evaluation per Specification 4.7.9c on the supported component or declare the supported system inoperable and follow appropriate ACTION statement for that system.
SURVEILLANCE REQUIREMENTS 4.7.9 Each snubber shall be demonstrated OPERABLE by performance of the following augmented inservice inspection program and the requirements of Specification 4.0.5.
- a. Visual Inspection An inservice visual inspection of all snubbers shall be performed in accordance with the following schedule for each type.
As used in this specification, type of snubber shall mean snubber of the same design and manufacturer, irrespective of capacity.
No. Inoperable Snubbers of Each Type per Inspection Period 0
1 2
3, 4 5' 6, 7 8 or more Subsequent Inspection Period 18 months + 25%
12 months + 25%
6 months + 25%
124 days + 25%
- 62 days + 25%
31 days + 25%
Snubbers are categorized as accessible and inaccessible during reactor operation.
Each group (accessible and inaccessible) may be inspected independently in accordance with the above schedule.
- The inspection interval shall not be lengthened more than one step at a time.
- The provisions of Specification 4.0.2 are not applicable.
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)
- b.
Visual Inspection Acceptance Criteria Visual inspections shall verify (1) that there are no visible indications of damage or impaired OPERABILITY, (2) attachments to the foundation or supporting structure are secure, and (3) in those locations where snubber movement can be manually induced without disconnnecting the snubber, that the snubber has freedom of movement and is not frozen up.
Snubbers which appear inoperable as a result of visual inspections may be determined OPERABLE for the purpose of establishing the next visual inspection interval, providing that (1) the cause of the rejection is clearly established and remedied for that particular snubber and for other snubbers that may be generically susceptible; and (2) the affected snubber is functionally tested in the as found condition and determined OPERABLE per Specification 4.7.9d or 4.7.9e as applicable. However, when the fluid port of a hydraulic snubber is found to be uncovered, the snubber shall be declared inoperable and cannot be determined OPERABLE via functional testing for the purpose of establishing the next visual inspection interval. All snubbers connected to an inoperable common hydraulic fluid reservoir shall be counted as inoperable snubbers.
- c. Functional Tests At least once per 18 months during shutdown, a representative sample of 10% of the total of each type of snubber in use in the plant shall be functionally tested either in place or in a bench test. For each type of snubber that does not meet the functional test acceptance criteria of Specification 4.7.9d or 4.7.9e, an additional 10% of that type of snubber shall be functionally tested.
The representative sample selected for functional testing shall include the various configurations, operating environments and the range of size and capacity of snubbers.
At least 25% of the snubbers in the representative sample shall include snubbers from the following three categories:
- 1.
The first snubber away from each reactor vessel nozzle
- 2. Snubbers within five feet of heavy equipment (valve, pump, turbine, motor, etc.)
- 3. Snubbers within ten feet of the discharge from a safety relief valve SA LEM -
UN IT 2 3/4 7-24
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)
In addition to the regular sample, snubbers which failed the previous functional tests shall be retested during the next test period.
If a spare snubber has been installed in place of a failed snubber, then both the failed snubber (if it is repaired and installed in another position) and the spare snubber shall be retested. Test results of these snubbers may not be included for the re-sampling.
If any snubber selected for functional testing either fails to lockup or fails to move, i.e., frozen in place, the cause will be evaluated and if caused by manufacturer or design deficiency all snubbers of the same design subject to the same defect shall be functionally tested.
This testing requirement shall be independent of the requirements stated above for snubbers not meeting the functional test acceptance criteria.
For the snubber(s) found inoperable, an engineering evaluation shall be performed on the components which are supported by the snubber(s). The purpose of this engineering evaluation shall be to determine if the components supported by the snubber(s) were adversely affected by the i noperabil ity of the snubber(s) in. order to ensure that the supported component remains capable of meeting the designed service.
- d. Hydraulic Snubbers Functional Test Acceptance Criteria The hydraulic snubber functional test shall verify that:
- 1. Activation (restraining action) is achieved within the specified range of velocity or acceleration in both tension and compression.
- 2. Snubber bleed, or release rate, where required, is within the specified range in compression or tension. For snubbers specifically required to not displace under continuous load, the ability of the snubber to withstand load without displacement shall be verified.
- e. Mechanical Snubbers Functional Test Acceptance Criteria The mechanical snubber functional test shall verify that:
- 1. The force that initiates free movement of the snubber rod in either tension or compression is less than the specified maximum drag force. The drag force shall not have increased more than 50% since the last functional test.
- 2. Activation (restraining action) is achieved within the specified range of velocity or acceleration in both tension and compression.
SA LEM -
UN IT 2 3/4 7-25
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)
- 3. Snubber release rate, where required, is within the specified range in compression or tension. For snubbers specifically required not to displace under continuous load, the ability of the snubber to withstand load without displacement shall be verified.
- f. Snubber Service Life Monitoring A record of the service life of each snubber, the date at which the designated service life commences and the installation and maintenance records on which the designated service life is based shall be maintained as required by Specification 6.10.2.1.
Concurrent with the first inservice visual inspection and at least once per 18 months thereafter, the installation and maintenance records for each snubber shall be reviewed to verify that the indicated service life has not been exceeded or will not be exceeded prior to the next scheduled snubber service life review.
If the indicated service life will be exceeded prior to the next scheduled snubber service life review, the snubber service life shall be replaced or reconditioned so as to extend its service life beyond the date of the next scheduled service life review. This reevaluation, replacement or reconditioning shall be indicated in the records.
SA LEM -
UN IT 2 3/4 7-26
PAGES 3/4 7-27 thru 3/4 7-30 1 ARE OCLETED SA LEM -
UN IT 2
PLANT SYSTEMS
--~----------------------
BASES 3/4.7.9.
SNUBBERS All snubbers are required OPERABLE to ensure that the structural integrity of the reactor coolant system and all other safety related systems is maintained during and following a seismic or other event initiating dynamic loads. Snubbers excluded from this inspection program are those installed on nonsafety related systems and then only if their failure or failure of the system on which they are installed would have no adverse effect on any safety-related system.
A list of individual snubbers required to be operable per the tech-nical specifications with detailed information of snubber location and size and of system affected shall be available at the plant in accordance with Section 50.71(c) of 10 CFR Part 50.. The accessability of each snubber shall be determined and approved by the Station Operations Review Committee.
The determination shall be based on the existing radiation levels and the expected time to perform a visual inspection in each snubber location as well as other factors associated with accessibility during plant operations (e.g. temperature, atmosphere, location, etc.) and the recommendations of Regulatory Guide 8.8 and 8.10.
The addition or deletion of any snubber shall be made in accordance with Section 50.59 of 10 CFR Part 50.
The visual inspection frequency is based upon maintaining a constant level of snubber protection to systems.
Therefore, the required inspection interval varies inversely with the observed snubber failures and is determined by the number of inoperable snubbers fo~nd during an inspection.
Inspections performed before that interval has elapsed may be used as a new reference point to determine the next inspection.
However the results of such early inspections performed before the original required time interval has elapsed (nominal time less 25%) may not be used to lengthen the required inspection interval.
Any inspection whose results require a shorter inspection interval will override the previous schedule:
When the cause of the rejection of a snubber is clearly established and remedied for that snubber and for any other snubbers that may be generically susceptible and verified by inservice functional testing that snubber may be exempted from being counted as inoperable.
Generically susceptitle snubbers are those which are of a specific make or model and have the same design features directly related to rejection of the snubber by visual inspection or are similarly located or exposed to the same environmental conditions such as temperature, radiation, and vibration.
When a snubber is found inoperable, an engineering evaluation is performed, in addition to the determination of the snubber mode of failure, in order to determine if any safety-related component or system has been adversely affected by the inoperability of the snubber.
The engineering evaluation shall determine whether or not the snubber mode of failure has imparted a significant effect or degradation on the supported component or system.
SALEM - UN IT 2 B 3/4 7-6
PLANT SYSTEMS BASES SNUBBERS (Conti~ued)
To provide assurance of snubber functional reliability a representative sample of the installed snubbers will be functionally tested during plant shutdowns at 18-month intervals.
Observed failures of these sample snubbers shall require functional testing of additional units.
Permanent or other exemptions from the surveillance program for individual snubbers may be granted by the Commission if a justifiable basis for exemption. is presented and, if applicable, snubber life destructive testing was performed to qualify the snubbers for the applicable design conditions at either the completion of their fabrication or at a subsequent date.
Snubbers so exempted shall be listed in the list of individual snubbers indicating the extent of the exemptions.
Hydraulic snubbers and mechanical snubbers may each be treated as a different entity for the above surveillance programs.
The service life of a snubber is evaluated via manufacturer input and information through consideration of the snubber service conditions and associated installation and maintenance records (newly installed snubber, seal replaced, spring replaced, in high radiation area, in high temperature area, etc... ).
The requirement to monitor the snubber service life is included to ensure that the snubbers periodically undergo a performance evaluation in view of their age and operating conditions.
These records will provide statistical bases for future consideration of snubber service life. The requirements for the maintenance of records and the snubber service life review not intended to affect plant operation.
3/4.7.10 FIRE SUPPRESSION SYSTEMS The OPERABILITY of the fire suppression systems ensures that adequate fire suppression capability is available to confine and extinguish fires occurring in any portion of the facility where safety-related equipment is located.
The fire suppression system consists of the water system, spray, and/or sprinklers, C02, and fire hose stations.
The collective capability of the fire suppression systems is adequate to minimize potential damage to safety-related equipment and is a major element in the facility fire protection program.
In the event that portions of the fire suppression system are inoperable, alternate backup fire-fighting equipment is required to be made available in the affected areas until the inoperable equipment is restored to service.
When the inoperable fire-fighting equipment is intended for use as a backup means of fire suppression, a longer period of time is allowed to provide an alternate means of fire fighting than if the inoperable equipment is the primary means of fire suppression.
SALEM - UN IT 2 B 3/4 7-7
.e PLANT SYSTEMS BASES FIRE SUPPRESSION SYSTEMS (Continued)
In the event the fire suppression water system becomes inoperable, immediate corrective measures must be taken since this system provides the major fire suppression capability of the plant.
The requirement for a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> report to the Commission provides for prompt evaluation of the acceptability of the corrective measures to provide adequate fire suppression capability for the continued protection of the nuclear plant.
3/4.7.11 PENETRATION FIRE BARRIERS The OPERABILITY of the penetration fire barriers ensures that fires will be confined or adequately retarded from spreading to adjacent portions of the facility.
This design feature minimizes the possibility of a single fire rapidly involving several areas of the facility prior to detection and extinguishment.
The penetration fire barriers are a passive element in the facility fire protection program and are subject to periodic inspections.
Fire barrier penetrations including cable penetration barriers, fire doors and dampers are considered OPERABLE when the visually observed condition is the same as the as-designed condition.
For those fire barrier penetrations that are not in the as-designed condition, an evaluation shall be performed to show that the modification has not degraded the fire rating of the fire barrier penetration.
During periods of time when a barrier is inoperable, either 1) a continuous fire watch is required to be maintained in the vicinity of the affected barrier, or 2) the fire detectors on at least one side of the affected barrier must be verified OPERABLE and an hourly fire watch patrol established, until the barrier is restored to OPERABLE status.
SALEM - UNIT 2 B 3/4 7-8