ML13289A247

From kanterella
Jump to navigation Jump to search
6.a.iii.1 SQN Fukushima Diesel Generator Air Emissions
ML13289A247
Person / Time
Site: Sequoyah  Tennessee Valley Authority icon.png
Issue date: 01/30/2009
From:
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation
Shared Package
ML13289A109 List: ... further results
References
Download: ML13289A247 (1)


Text

Sequoyah Nuclear Plant 3 MW DG #1 3 MW DG #2 225 kva DG #1 225 kva DG #2 Total Fuel Oil Heat Content, Btu/gal 140,000 140,000 Fuel Oil Heat Content, Btu/gal 140,000 140,000 Fuel Oil Usage, gal/hr 223 223 Fuel Oil Usage, gal/hr 13.5 13.5 Annual Hours of Operation, hr 36 36 Annual Hours of Operation, hr 36 36 Fuel Oil Sulfur Content, %

0.0015 0.0015 Fuel Oil Sulfur Content, %

0.0015 0.0015 3 MW DG #1 & #2 225 kva DG #1 & #2 Emission Factor Emissions Emissions Emission Factor Emissions Emissions Emissions Pollutant lb/MMBtu ton/yr ton/yr Pollutant lb/MMBtu ton/yr ton/yr ton/yr Filterable Particulate Matter PM (1) 0.062 3.48E-02 3.48E-02 Filterable Particulate Matter PM (1) 0.31 1.05E-02 1.05E-02 9.08E-02 Filterable Particulate Matter PM 10 (1) 0.0496 2.79E-02 2.79E-02 Filterable Particulate Matter PM 10 (1) 0.31 1.05E-02 1.05E-02 7.68E-02 Filterable Particulate Matter PM 2.5 (1) 0.0479 2.69E-02 2.69E-02 Filterable Particulate Matter PM 2.5 (1) 0.31 1.05E-02 1.05E-02 7.49E-02 Condensable Particulate Matter (1) 0.0077 4.33E-03 4.33E-03 Condensable Particulate Matter (7) 0.01812 6.16E-04 6.16E-04 9.89E-03 Nitrogen Oxides (NOx) (1) 3.2 1.80 1.80 Nitrogen Oxides (NOx) (1) 4.41 1.50E-01 1.50E-01 3.90 Carbon Monoxide (CO) (1) 0.85 4.78E-01 4.78E-01 Carbon Monoxide (CO) (1) 0.95 3.23E-02 3.23E-02 1.02 Volatile Organic Compounds (VOC) (1) 0.0819 4.60E-02 4.60E-02 Volatile Organic Compounds (VOC) (1) 0.36 1.22E-02 1.22E-02 1.17E-01 Sulfur Dioxide (SO2) (1) (2) 0.0014 8.09E-04 8.09E-04 Sulfur Dioxide (SO2) (2) 0.0014 4.90E-05 4.90E-05 1.72E-03 Sulfuric Acid (1) (2) 0.00012 6.52E-05 6.52E-05 Sulfuric Acid (2) 0.00012 3.95E-06 3.95E-06 1.38E-04 Carbon Dioxide (CO2) (3) 163.1 91.6 91.6 Carbon Dioxide (CO2) (3) 163.1 5.55 5.55 194 Methane (CH4) (3) 0.007 3.72E-03 3.72E-03 Methane (CH4) (3) 0.007 2.25E-04 2.25E-04 7.88E-03 Nitrous Oxide (N2O) (3) 0.001 7.43E-04 7.43E-04 Nitrous Oxide (N2O) (3) 0.001 4.50E-05 4.50E-05 1.58E-03 GHG Emissions (CO2 equiv) (3) 163.6 91.9 91.9 GHG Emissions (CO2 equiv) (3) 163.6 5.57 5.57 195 Antimony (Sb) (4) 2.20E-05 1.24E-05 1.24E-05 Antimony (Sb) (4) 2.20E-05 7.48E-07 7.48E-07 2.62E-05 Arsenic (As) (5) 1.10E-05 6.18E-06 6.18E-06 Arsenic (As) (5) 1.10E-05 3.74E-07 3.74E-07 1.31E-05 Beryllium (Be) (5) 3.10E-07 1.74E-07 1.74E-07 Beryllium (Be) (5) 3.10E-07 1.05E-08 1.05E-08 3.70E-07 Cadmium (Cd) (5) 4.80E-06 2.70E-06 2.70E-06 Cadmium (Cd) (5) 4.80E-06 1.63E-07 1.63E-07 5.72E-06 Chromium (Cr) (5) 1.10E-05 6.18E-06 6.18E-06 Chromium (Cr) (5) 1.10E-05 3.74E-07 3.74E-07 1.31E-05 Cobalt (Co) (4) 9.10E-06 5.11E-06 5.11E-06 Cobalt (Co) (4) 9.10E-06 3.10E-07 3.10E-07 1.08E-05 Lead (Pb) (5) 1.40E-05 7.87E-06 7.87E-06 Lead (Pb) (5) 1.40E-05 4.76E-07 4.76E-07 1.67E-05 Manganese (Mn) (6) 1.01E-04 5.68E-05 5.68E-05 Manganese (Mn) (6) 1.01E-04 3.44E-06 3.44E-06 1.20E-04 Mercury (Hg) (5) 1.20E-06 6.74E-07 6.74E-07 Mercury (Hg) (5) 1.20E-06 4.08E-08 4.08E-08 1.43E-06 Nickel (Ni) (5) 4.60E-06 2.59E-06 2.59E-06 Nickel (Ni) (5) 4.60E-06 1.56E-07 1.56E-07 5.48E-06 Selenium (Se) (5) 2.50E-05 1.40E-05 1.40E-05 Selenium (Se) (5) 2.50E-05 8.51E-07 8.51E-07 2.98E-05 Hydrogen Chloride (HCl) (6) 3.11E-04 1.75E-04 1.75E-04 Hydrogen Chloride (HCl) (6) 3.11E-04 1.06E-05 1.06E-05 3.71E-04 1,3-Butadiene (7) 3.91E-05 2.20E-05 2.20E-05 1,3-Butadiene (1) 3.91E-05 1.33E-06 1.33E-06 4.66E-05 Acetaldehyde (1) 2.52E-05 1.42E-05 1.42E-05 Acetaldehyde (1) 7.67E-04 2.61E-05 2.61E-05 8.05E-05 Acrolein (1) 7.88E-06 4.43E-06 4.43E-06 Acrolein (1) 9.25E-05 3.15E-06 3.15E-06 1.52E-05 Benzene (1) 7.76E-04 4.36E-04 4.36E-04 Benzene (1) 9.33E-04 3.17E-05 3.17E-05 9.36E-04 Formaldehyde (1) 7.89E-05 4.43E-05 4.43E-05 Formaldehyde (1) 1.18E-03 4.01E-05 4.01E-05 1.69E-04 Naphthalene (1) 1.30E-04 7.31E-05 7.31E-05 Naphthalene (1) 8.48E-05 2.88E-06 2.88E-06 1.52E-04 Toluene (1) 2.81E-04 1.58E-04 1.58E-04 Toluene (1) 4.09E-04 1.39E-05 1.39E-05 3.44E-04 Xylenes (1) 1.93E-04 1.08E-04 1.08E-04 Xylenes (1) 2.85E-04 9.70E-06 9.70E-06 2.36E-04 Total POMs (1) 8.20E-05 4.61E-05 4.61E-05 Total POMs (1) 8.32E-05 2.83E-06 2.83E-06 9.78E-05 Particulate HAP Total

  • 1.78E-04 9.99E-05 9.99E-05 Particulate HAP Total
  • 1.78E-04 6.05E-06 6.05E-06 2.12E-04 VOC HAP Total **

1.61E-03 9.06E-04 9.06E-04 VOC HAP Total **

3.87E-03 1.32E-04 1.32E-04 2.08E-03 Non-VOC Gaseous HAP Total ***

3.37E-04 1.89E-04 1.89E-04 Non-VOC Gaseous HAP Total ***

3.37E-04 1.15E-05 1.15E-05 4.02E-04 References for Emission Factors References for Emission Factors (1) US EPA, Compilation of Air Pollutant Emission Factors (AP-42), 5th Edition, Section 3.4, 10/1996.

(1) US EPA, Compilation of Air Pollutant Emission Factors (AP-42), 5th Edition, Section 3.3, 10/1996.

(2) Assumes 5% conversion to sulfuric acid.

(2) US EPA, Compilation of Air Pollutant Emission Factors (AP-42), 5th Edition, Section 3.4, 10/1996.

(3) 40 CFR Part 98 Assumes 5% conversion to sulfuric acid.

(4) US EPA, Compilation of Air Pollutant Emission Factors (AP-42), 5th Edition, Supplement B, Section 3.1, 10/1996.

(3) 40 CFR Part 98 (5) US EPA, Compilation of Air Pollutant Emission Factors (AP-42), 5th Edition, Supplement F, Section 3.1, 4/2000.

(4) US EPA, Compilation of Air Pollutant Emission Factors (AP-42), 5th Edition, Supplement B, Section 3.1, 10/1996.

(6) TVA combustion turbine fuel oil specifications.

(5) US EPA, Compilation of Air Pollutant Emission Factors (AP-42), 5th Edition, Supplement F, Section 3.1, 4/2000.

(7) US EPA, Compilation of Air Pollutant Emission Factors (AP-42), 5th Edition, Section 3.3, 10/1996.

(6) TVA combustion turbine fuel oil specifications.

(7) Estimated as 5% of VOC plus sulfuric acid.

    • Includes 1,3-butadiene, acetaldehyde, acrolein, benzene, formaldehyde, naphthalene, toluene, xylenes, and

total POMs.

    • Includes 1,3-butadiene, acetaldehyde, acrolein, benzene, formaldehyde, naphthalene, toluene, xylenes, and

total POMs.